shahnawaz report
DESCRIPTION
Kahramaa QatarTRANSCRIPT
Mission Statement
Mission
Our Mission is to provide our customers with high quality electricity and water services, whilst creating value for our shareholders.
Objectives
Our objectives are to:Efficiently meet our obligation to supply Qatars need for electricity and water. Operate on a commercial basis. Comply with local and international health, safety, and environmental standards. Maximize the employment of capable Qatari nationals and develop them to the competence level of employees in leading international companies.
History
IntroductionQatar General Electricity & Water Corporation,was established in July, 2000 further to the Emiri Law number 10, to regulate and maintain supply of Electricity & Water to customers.Since inception, Kahramaa has operated as an independent corporation on a commercial basis with a total capital of four billion Qatari Riyals. Kahramaa was mandated with several responsibilities and commitments, some of which are:
The right to own, construct, operate and maintain electricity generation stations, water desalination plants, electricity transmission and water distribution networks.
Set up of infrastructure & network development plans and programs. Lay out regulations, standards and codes of practices which pertain to
provision of electricity and water supplies to various buildings and establishments as well as review of their implementations.
Provide consultancies & services related to its operations.
1
Board Of DirectorsKahramaa board of directors comprises of Chairman, vice-chairman and several members. The board is appointed for a four-year office term subject to renewal by an Emiri decree, based on Kahramaa's law- article 7.
a. JurisdictionsThe Board of directors at Kahramaa is granted extensive authorities to achieve the corporation's goals mainly, the setting, and implementation and follows up of general policies, plans, programs and projects.The board main responsibilities are the approval of corporation’s organizational structure, endorsement of the financial, administrative and technical internal rules and regulations, employees policies and regulations, as well as approving the corporation investment plans, its annual budgets and closing fiscal year and approves loans with the Government and other parties, in addition to review of the operational and strategic performance.
b. The Financial ResourcesThe main financial resources of Kahramaa is the annual allocated funds from the state (government), services fees and revenues, the return of its capital investments on its assets as well as the value of its shares and loans extendedtoothers.
The Electricity SectorThe Electricity transmission networks consist of approximately 100 primary High Voltage sub-stations with total 660 km of overhead lines supported by 600 km of underground cables across the country. The network is coupled with 6500 low and medium voltage sub-stations (11kv) and more than 4500km of cable lines.The National Control Center (NCC), which contains state-of-art technologies, manages all network demand and data acquisition from generation plants and primarysub-stations.
Electricity DemandDemand on the electrical energy in Qatar has increased over the past fifty years; the maximum load over the network during the period from 1988 to 2003 has risen from 941 Megawatt to 2312 Megawatts (MW). It has reached 2520MWin2004.
The Water SectorThe water network in Qatar has been expanded extensively in recent
years, the growth of urban areas; industry and agriculture has lead to the increase in the length of the water network to 3622 km and expansion in the number of storage reservoirs to 23 with a total capacity of 259 million gallons of water a day.
DISTRIBUTION SYSTEM ,KAHRAMAA,QATAR
2
Primary distribution voltage – 11 KV, Frequency – 50 Hz.
System Voltege variation allowed – 10.7 KV to 11.3 KV
HT network – 3 phase 3 wire System
LT network - 3 phase 4 wire System
GENERAL OVER VIEW
Kahramaa distribution Network consists of about 10000 Nos substation. They
are either Indoor type or Out door type.
Max demand - 3025 (27.06.2006) till date
The domestic consumption is more predominant in the system and domestic
load contributes major portion of the total demand. Remaining are industrial
and they contribute very less, near about 15% of the load (approx. 450
mw).Seasonal variations are predominant because of the extreme climatic
conditions. In summer, hot season begins from May – September, the
demand reaches its maximum value But in winter season, (Nov- Feb), the
demand reaches its minimum value.
In summer season demand is about 3000 MW
In winter season demand is about 1000 MW
But the Repaid economical & industrial development brings, Qatar power
sector a demand growth of about10% every year.
KAHRAMAA'S distribution Network consists of about 10000 Nos substation.
They are either Indoor type or Out door type. Distribution network is fed from
Primary substations ( 92 Nos ) and mostly they are 66 /11 KV substation's
with two incoming transformers (Rating 25/36/40MVA ). Some 33 / 11 KV
sabstation's are also provided for feeding the 11 KV distributions network.
Under ground cables are widely used to meet the urban load and rural
network is constructed by using OH/L. There are indoor and outdoor
substations are provided depending upon the load requirement and
operational flexibility. These substations are also helps to achieve
continious,stable and reliable supply thruogh out the state of Qatar. The
indoor & outdoor substations are provided with different sources to feed the
LT transformers. Closed Ring, Ring off ( Normaly opened point's – NOP ) and
3
Radial feedings are used in the distribution network depending upon the
nature of the Consunar load.
MAIN NETWORK ELEMENTS1) Primary Substation
2) Indoor Substation
3) Outdoor Substation
4) Under ground cables
5) Over head lines - OH/L.
1) Primary Substation
Main incoming supply to the Primary Substation is fed from 66
KV system. Two main incoming transformers are generally provided to feed
the 11 KV Distribution system. 11 KV Bus is provided with a Bus
Coupler(A120) for oparational flexibility and is normally in closed condition..
All Switchgear panels for incoming feeders,transformers and outgoing feeders
are equiped with Circuit Breakers,Isolators and Earth switches. Current
transformer and Voltage transformers are also provided in each circuit for
protection & metering. Earthing transformers are provided for stable neutral
and for station supply. Circuit breakers are of either VCB/SF6 / OCB types are
used.DC System is 110 V DC with Battery and Charger. The primary
substatoin are well equipped with Control panel,protection panel,Switch gear
panel and Axilliary facilities. Local and remote control is possible for all
panels by selecting the selection switch on panels.RTCC with AVR is also
provided for meeting on load automatic tap changing.
Operation and Maintanance
Maintenance of Primary Substation is always under the control
of transmission wing. All switching operations on 11 KV outgoing feeders are
done by distribution engineer. But switching operation on HV , LV side of
Primary transformers (Incomers) and Bus section Breakers are done by the
transmission wing.
Safety Measures
4
All primary Substation are well protected from fire hazards.Co2
fire extinguisher system (auotamatic) is provided in Primary substation where
Cicuit Breaker is OCB.But in new phase v Primary’s are commissioned with
SF6 as insulation medium.
Operation Control
A selector switch is provided in each panel to control the
operation of breakers from either locally or remotely (Grid). Normally the
Selector switches are in Grid position where Out going feeders are in DCC
control and Incomers and Bus Coupler are in NCC control.A Senior
Authorised person can change the Selector switch position for work only with
the consent of Contrl Engineers of NCC/DCC.
2) Indoor SubstationAll Indoor Substations are well equipped with Switchgear panels
with Circuit Breakers,isolating & eathing facility,control and protection circuitry
and metering facility for the smooth operation and control of feeder and Local
distribution transformers. All Feeders and L/Tx are connected to the common
bus of the Indoor substation through the respective circuit breaker. DC
system available is 30V DC with Battery and Charger.Station LT supply for
station lighting and Battery Charger is taken from L/Tx. All of the switchgeer
panels, L/Tx and Communication systems are protected inside a room.
Circuit Breakers used
1) OCB- Oil Circuit Breaker –Oil (Medium)- Vertical isolation
Types available are
Ray RlleSouth WalesBrush GEC2) VCB- Vaccum circuit Breaker- Vaccum(medium) – Horizontal isolation
Types available are
TAMCOAL-AHILIYAEPE, Ray Rolle and Ranhil
Distribution Transformers
5
Local & Remote transformer are provided to cater the
distribution load. Available ratings are 500 KVA, 800 KVA,1000 KVA ,1250
KVA & 1600 KVA. The HT cable length more than 15 metre is considered as
R/TX
Control and Protection
Control and protection circuitry is provided with the Switchgear panel
for the control and protection of Feeders and L/Tx’s.Local control facility is
only available for CB.
Metering
Ammeters are provided in each circuit to measure the load current
Status indicators are provided for circuit Breakers
DC voltmeter is provided to measure the DC voltage.
Operation and Maintanance
Presently no remote control is possible. Local operation &
Maintenance is always done by the Field engineers(Senior Authorised
Person) of Distribution Department with proper consent from System Control
Engineer on duty.
3) Out Door Substations
In Outdoor substations, Main Switches and Transformer
switches along with Earthing facility is provided for oparational, maintanance
and construction activities. The main switches are intended to break/make the
load current manually.Protection and control circuits are not assosiated with
the main switches inorder to protect the curcuit under overload / fault
condition.But the transformer circuit is provided with Oil Fuse Switches(OFS)/
TX Switch with Time lag Fuse(TLF) to protect the transformer from overload
and fault condition. The automatic tripping of the TX Switch is depend upon
the rating of fuse provided in the circuit.The fuse rating is selected as per the
transformer capacity.If the load current is more than the rated value of fuse.
Then the transformer switch automaticaly trips the circuit and protect the
transformer. Other than OFS / TLF,there is no protection available in Out door
S/S.Metering circuits are also absent in the outdoor substation except the
Ammeter with load current and Maximam Demand indicator provided in the
6
Feeder Pillar.Status Indicators are provided for Main switches,earth switches
and transformer switches.Earth fault indicators and Gas pressure indicators
are also provided in outdoor substation.
Main Components of Out door S/S
Main Switches for Feeders
Earth Switches for Feeders and Transformers
Transformer Switches (OFS & TXS)
Current Transformers provided for EFI
Local Transformers - 11KV/433 V
Bolt on Feeder Pillar (BOFP) /Free Standing Feeder Pillar (FSFP)
HT and MV cables.
Earth fault Indicators
Gas Pressure Indicators (only in SF6 Outdoor s/s)
Classification according to Insulation Medium
In outdoor s/s, all feeder switches and TX switches are provided with either oil
or SF6 Gas as insulation medium for breaking/making load current.
Oil Switches:- Oil is used as insulation medium for breaking /making the load
current. All switches are rated for breaking/ making load current and not
intended to break /make the fault current.But for transformer circuit Oil Fuse
Switches (OFS) are parovided with Oil Fuses.In OFS a mechanical inter
locked over load protection is provided for tripping the transformer circuit
under over load condition..If any of the fuses blows out, a mechanical
interlocking arrangement by means of a Plunger and latch opens the contacts
of the OFS. Different types of Oil Fuse Switches are:-
Long Crawford – Old version, operation is risky, if any abnormalities found,
avoid the switching. Then other remote switches can be
used for operational purposes.
W LucyYorkshireTiger
7
SF6 Switches:- SF6 gas is used as insulation medium in new outdoor s/s's
where the breaking / making of load current is through the SF6 gas insulation
medium. In SF6 O/D substations, for transformer Switches are normally
provided with the Time Lag Fuses (TLF) for tripping the circuit Breaker (TXS)
on abnormal condition. These fuses are provided in the secondary circuit of
the CT across a shunt coil. Normal condition the current will flow through the
TLF( low impedence path) Any abnormality comes the fuse will blown out and
it will results the flow of current through the shunt coil (high impedence trip
coil) which in turn trips the circuit breaker.Different types used are :-
TamcoMerlin GerinABB W Lucy
Fuse rating for different rating transformer
Oil Fuse rating available - 40A,63A,70A& 90A
Standard TLF Rating available – 5A,7.5A,10A,12.5A &15A
Voltage Transformer
Voltage Transformers (VT) are provided for metering, protection and
synchrocheck. VT is always part of Cable and is provided in all Primary
substation and in some Indoor Substation.In Primary all Feeders ,Incomers
and Bus sections are equipped with VT. VT's are consider as part of the
cable and hence VT isolation is compulsory while doing any type of injection
test like HV Pressure test.Before VT isolation, confirm the cable is dead and
isolated at both ends.
Current Transformer
Different Class CTs are used in Primary as well as in Indoor
Substation for protection & metering. CT's are also provided in O/D
substations in the Earth Fault Indicator circuit for indicating passage of the
Earth fault. In SF6 -O/D Substation , CT is required in the TLF protection
circuitry.
Types of Out Door substation
Ring Main Unit (RMU)
Semi Extensible RMU
8
Extensible RMU
Out Door Substation with feeder switches &TX Switch
Out Door Switching station
Package Substation
Ring Main Unit(RMU)
A single unit with two feeder switches and one T-off
transformer switch. Oil and SF6 switches are available. Only one Transformer
circuit is available .Normally Transformer is connected to the T-off circuit and
two feeder switches provided on both sides.
Semi Extensible RMU
The outdoor substation with one RMU unit and which has a
provision to extend its Bus bar towards one side to add more circuits (Feeder
Switches/Tx switches) depending upon the Bus Bar current carrying
capacity.The extensible side of the RMU is provided with an Endcap.
Extensible RMU
The outdoor substation with one RMU unit and which has a provision to
extend its Bus bar towards both sides to add more circuits (Feeder
Switches/Tx switches) depending upon the Bus bar current carrying
capacity.Endcaps provided on both sides.
Extensible Out door Substation
In this out Door substations, individual switches are provided for
transformer and feeder circuit in a common Bus Bar and has a provision to
extend its Bus Bar towards both sides. Endcaps provided on both sides. No
RMU unit is available.
Out door Switching Station
Transformer switches and RMU units are absent in this type.
Feeder switches provided for switching and operational flexibility and
connected in a common busbar with extensible feature.
9
Package Substation
In package substation where the RMU unit and FeederPillar
units are attached (Bolted) to the transformer and formed a single package
unit. HV and MV cables are not required for transformer.
Main Switch,Transformer Switch & Earth Switch
Main Switches are intended to making /breaking load current only and
there is no associated protection circuitry. These switches are not
designed to break / make fault current.
Status indication windows are available for Main swtches,Earth
switches and TXS to indicate the current status of operation.
Main Switch Closed condition - "ON" with red background
TX Switch Closed condition - "ON" with red background
Earth Switch Closed condition - "ON" with yellow background
Earth Switch /Main Switch /TX Switch - Opened condition -
"OFF" with green background
TX Switches are provided with Oil Fuse/ TLF for tripping the circuit
under overload / abnormal condition.
Inter locking
1) Inter locking facility is provided between Earth Switch ON and Main
Switch ON condition.
2) Inter locking facility is provided between Earth Switch ON and TX
Switch ON condition.
3) No inter locking facility is provided between Earth Switch OFF and Main
Switch /Transformer Switch OFF condition.
4) Opening/Closing of test plug is allowed only when the earth switch of
respective circuit is in ON condition. In SF6 RMU , the TLF compartment
also having the inter locking facility of this type.
5) Safety and normal operational locks are also provided to all switches.
Earth Fault Indicators (EFI)
10
Earth Fault Indicators (EFI) are provided in Out Door substations for
indicating the passage of fault current. EFI is normaly provided in left hand
side of RMU. EFI is actuated by a CT secondary current during earth fault.
The CT is wrapped around the feeder circuit cable. Manual reset and Auoto
reset types EFI’s are available.
Manual type –Manual reset is required after the Flag ON condition due to fault
Auto type - LT supply is provided to EFI and it automatically reset the Flag
due to the fault after a delayed time period when supply resumed.
Gas Pressure Indicator for SF6 RMU
The Gas Pressure Indicator reading should be in the green zone for the safe
oparation of SF6 RMU.
Filling Pressure at 20 degree cent.- 0.4 BARG
Minimum oparating Pressure - 0.05 BARG
Red zone - operation of RMU is not allowed.
Green zone - Operation is allowed
If it is in red zone, refilling is required for further operation and is allowed only
with PTW.
HV and MV cable of Distribution Transformer
11KV HT Single run 3 core cable connect the TX Switch to the Transformer
Primary winding. MV cable Seven run single core (Double run for phases and
Single run for neutral) connect the Transformer Secondary to the MV feeder
piller.
Feeder Pillar
Bolt on Feeder Pillar(BOFP) – 4 LT Out going Cables
Free Standing Feeder Pillar (FSFP)- 6 LT Cable Out going
MV panel could be mounted in two ways:-
1. As an attachement (Bolted) to the Transformer Secondary without MV
cables is called Bolt on Feeder Pillar(BOFP)
2. As a separate unit anchored to the ground and secondary of Transformer is
connected with MV cable called Free Standing Feeder Pillar(FSFP)
11
Special free standing feeder pillar – Consumer FSFP and Special consumer
panel is available. 4 or 5 LT Out going Cables + Cable for one separate
consumer panel.
MV Panel - Components
MV link (R,Y,B &N)
Ammeter with Maximum Demand Indicating feature
Bus Bar (R,Y,B and Neutral)
MV side cut out fuses ( 100A,200A,315 A)
MV outgoing Cable (4 or 6 circuits)
Eatrhing Bus
Current Transformer
In Feeder Pillar MV links are provided for LT Outgoing Cables (3 Phase 4 wire
with separate Earth wire ) HRC fuses are provided in LT cable for overload
protection rating depends on the load current. In some consumer MV panel is
available with ACB and REF protection.
Maximum Demand Indicator
Ammeter is provided in MV panel with two needles. One is for the real
time load current measurement and the other one is for all time Meximum
Demand.This indication is more usefull tripping/fault analysis.
LT Transformer – ( 11 / 0.433 KV ) Dyn 11 Off load tap changing feature – 1 to 5 tap possisions- nominal tap is 3
Local TX - upto 15 mtr
Remote TX - above 15 mtr
Available Transformer ratings - 100, 200,300,500,800,1000,1250,1600 KVA
Under Ground Cables XLPE - recent standard( ax,bx,cx,dx,ex &gx)
PILC - Old (a,b,c,d)
HT – 3 phase 3core cable , MV – 3 phases and Neutral
12
Overhead Lines (OH/L)Rural areas are electrified by means of OH/L .ACSR and Copper conductors
areavailable
HT - 3 phase 3 wire system and seperate Earth wire is provided
- for 10 poles one Earth pit is provided
- Separate earth pits are provided for LA,Pole Box and PMT
LT - 3 phase 4 wire System
- Cut out fuses are provided depending upon the load.
Safety during shut down
The working section should be dead , isolate & Earth at both ends
before doing any work
Test OH/L line before starting work by using an HV Tester for
confirmation
If the OH/L found Dead,apply Portable Earth at the point of work
Always instruct the workforce to wear
Safety Belt
Safety Shoe
Helmet
Gloves
Field Engineer should collect the original copy of safety document
(PTW) signed by the competent person
OHL work should be stopped immediately when the atmosphere
becomes cloudy and chances of lightning and thunder showers are
likely to occure.
Main components
AB Switch (S)
Lightning arrester (LA)
Ploe Mounted Transformer (PMT)
Auto Recloser (R)
Pole Box
Flashing Fault Indicator (FFI)
Conductors & Earth wire
13
Air Break Switch - Designed to operate on load condition, AB Switches are
numbered in s- series. Oparating hand lever is provided on the botton of pole
with ON/OFF locking facility and can be lock off as a point of isolation.
For safety, open ABS and apply S/L and C/N & simillarly close ABS & L/OFF
Handle upward dirction - ON
Handle downward direction- OFF
- A visual check is reccomended after each operation whether the
contacts are properly inserted/seperated.
- Arcing Shields are provided to minimise the arcing of blades.
- If ABS is deffective , jumper connections are used to bypass it.
Test OH/L, If Dead, Apply Portable Earth
An HV OH/L Tester used to test the isolated line to make sure that the line is
electrically Dead and is always applicable before applying Portable Earth to
commence a work. After isolating & earthing( if facility is available) both ends,
then test the OH/L , If found dead apply Portable Earth at the point of work by
a copetent person with the precense of a senior authourised person.
If the OHL is dead - tester making normal low beep
If OHL is live - tester making high beep
( Before and after the tester itself should be check )
Portable Earth(PE):-Before doing any kind of work on OH/L, the Portable
Earth must be applied at point of work and is very essential to give a Permit to
Work(PTW) . So before issuing PTW, the System Control Engineer should
confirm that the PE is applied at the point of work and simillarly he should
confirm that PE is removed after the work for cancellation of a PTW.
At point of work
PE is applied by the competent person on the OH/L by means of an
insulated oparating rod. The PE circuit consits of four wires and one lead of
each wire is connected together. Then first connect one wire to the Earth wire
and then the other three wires to R,Y,B, phases. After the work , the PE must
be removed fom the OH/L. While removing PE, first disconnect R,Y,B phases
wires and finally disconnect the wire from the earth conductor.
14
Pole Mounted Transformer (PMT)Pole Mouted transformer (PMT) are transformer,which is mounted on an OH/L
pole PMT ratings are normally 100 KVA, 200 KVA and 500 KVA. Vector group
is Dynll.
Lightning Arresters are provided nearer to the transformer to protect it
from lightning surges.Possitioning is always in between the transformer
and OH/L line. LA provided at PMT, Pole Box and Auto Recloser
Drop Out fuses are provided for the transformer
protection.Replacement of D.O fuses is permitted under live condition..
Out going cable with Fuse Cut – outs are used to feed the LT 3phase 4
wire system. Ratings available are 100 A, 200 A , 315 A .
Earthing arrangement for PMT – Normally two Earth pits are provided,
one for ground /Body Earthing and the other one is for system neutral
earthing.
Pole BoxTermination in a pole which provides connection between OH/L
circuit and UG Cable circuit is called a Pole Box. The HT cable may be either
from any I/D Substation / Out Door Substation or from another OH/L portion
due to crossing of road / EHT line.
CT and Earth Fault Indicators are provided in some Pole Box to
indicate earth fault passage
LA's are provided to protect the cable termination from lightning surges.
Separate Earthing is needed for pole Box.
Auto reclosersAuto recloser is provided to restore the service continuity after a
transient fault on OH/L. Faults which are not permanent called transient fault.
90% of the faults in OH/L are of transient nature, after a short time called the
dead time, the CB can be reclosed.
Auto recloser will trip the circuit for a fault beyond it (O/C or E/F) and it
save the healthy section.
Auto Recloser normally provided nearer to the AB Switch and that will
helps to isolate the faulty portion and there by restore the healthy
portion after opening the AB switch
15
CT's are also inserted with the Auto Recloser, to measure the load
current for protection.
Different type used in Kahramaa OHL System
In Kahramaa distribution system, Auto Reclosers used as sectionalizers since
the Auto reclosing feature is disabled. Auto Recloser should not consider as a
point of isolation. According to the operation and control, two types of
Recloser are used in OH/L System.
Auto reclosers with manual control
During fault, the auto recloser trips the circuit. But after the first opening, the
recloser attains Lock-Off. Manual operation is needed for closing the Auto
recloser and this is done by using an insulated operating rod. First the
operator should manually reset the switch and then close.
Auto reclosers with auto control
A microprocessor control is provided along with the Auto recloser and is
mounted on the pole (bottom). The operator can operate it from the ground
itself. This type of Auto recloser trips the OH/L faulty section and attains to
lock off. Closing after patrolling and clearing the fault is possible from the
automatic control installation. This type of auto recloser should protect the
OH/L section from O/C, short circuit, E/F and sensitive E/F.
Main Components
Battery – 240/ 120 V AC is required to charge the battery.
VT - VT's are the voltage source for charging the battery
It always provided in the source side of the Auto recloser.
LA - Lighting Arresters are provided to protect A/R.
Flashing Fault indicator
16
It is a device that is used to identify the earth fault passage. FFI
flashes only when the fault current passing through it. Its location is always
nearer to the AB switch and is clip on to the OH/L.
17
National Control Centre
Qatar Power System Over viewPower Station – Installed Capacity
RAS ABU FONTAS A - 497 MW
RAS ABU FONTAS – B/B1 - 996 MW
RAS LAFFAN - 756 MW
RAS ABU ABOUD - 107 MW
SATALLITE STATIONS
i. AL WAJBAH
ii. SALIYAH
iii. DSS - 473 MW
Q- POWER - 699 MW
TOTAL 3528 MW
Transmission networkKahramaa transmission grid consists of the following voltage levels.
Transmission Network
220 KV
132 KV
66 KV
Distribution Network
11KV
0.433 KV
There are 100 Nos. of transmission substation out of which 90 Nos. are
Primary Substations. They are facilitating to feed 11 KV distribution systems.
The primary substations can be either any of the following type.
1. 220 / 132 / 66 / 11KV
2. 132 / 66 / 11KV
3. 220 / 66 / 11KV
4. 66 / 11KV
18
Demand ProfileThe domestic consumption is more predominant in the system and domestic
load contributes major portion of the total demand. Remaining are industrial
and they contribute very less, near about 15% of the load (approx. 450
mw).Seasonal variations are predominant because of the extreme climatic
conditions. In summer, hot season begins from May – September, the
demand reaches its maximum value But in winter season, (Nov- Feb), the
demand reaches its minimum value.
Power System – Control The National Control Centre (NCC) controls the QGEWC'S power
system in an efficient way. The smooth, stable and efficient grid control is
achieved by the automated control system (SCADA / EMS). Two control
desks are available, they are (I) Generation Desk and the other is (ii)
Switching Desk.
(i) Generation Desk.
Controlling the Active and Reactive power flow to maintain the
system voltage & frequency to a predetermined value.
Act according to the surplus & deficit condition.
Act according to the abnormal condition.
Merit Order Dispatch is observed
Automatic Generation Control is in operation.
(ii) Switching Desk.
Coordinating & controlling to all Switching operations.
Give Sanctions ( PTW & SFT ) to all switching operation
Executing load rearrangement programmes during shut down /
abnormal conditions.
Arranging Periodic / Break down maintenance activities for the
network elements.
Frequency ControlFrequency is controlled by maintaining the balance between Active
power and Demand of the system. This is achieved by Automatic Generation
Control(AGC). AGC will ensure stable frequency by automatic adjustments of
19
generation in accordance with the system demand. AGC controls the active
power flow depending upon the current frequency.
Target Frequency
The system should run at a target frequency – 50HZ with minimum deviation
(not exceeding 0.2 %) as far as possible to keep agreeable level of power
supply quality. The frequency band is 49.90 to 50.1 HZ .Beyond the set
frequency band, AGC change over to local. Participation factor percentage is
also selected to determine the degree of involvement of each generator unit in
the AGC mode of operation.
Minimum Spinning Reserve
A spinning reserve equal to the capacity of the largest unit in service is
to be maintained as far as possible.
Operation with less than above or zero spinning reserve is allowed
when there is a short fall of generation capacity during summer peak,
or due to agreed plant maintenance programme, or units purposefully
kept off to avoid plants running winter nights or when generation unit
are agreed to be kept stand by ,to save running hours for anticipated
usage in next summer peak.
Voltage Control (I) Generator MVAR Control
System Voltage is maintained by controlling the reactive power flow.
Due to the highly inductive nature of load, a larger capacity of MVAR is
required. The main MVAR generation source is the generator and all
generators are normally supplying about 50% of the active power as MVAR.
Then the major source and control point of MVAR is generator source.
Voltage is maintained by controlling the MVAR output of generators. The VAR
control can be achieved either through SCADA control or by local control.
(2) Capacitor Bank
Capacitor Banks are provided at remote areas (MVAR Generation) to
control voltage in 11 KV network. Automatic switching facility is available.
When the transformer (Incomer) MVAR is crossed a pre set value,
automatically the capacitor bank will switch on to the system one by one. That
means supplying VAR to the system.
20
During summer – Low voltage problem.
During winter : High voltage problem due to capacitive charging of
cables. Reactor compensates the purpose.
Capacitor Bank at
AL GIFARA - 1.5 MVAR x 3 = 4.5 MVAR
AL SULAIMI - 1.5 MVAR x 3 = 4.5 MVAR
(3) Voltage Regulators
Provided in the 11 KV systems across the 11 KV Bus Coupler to regulate the
voltage as required.
(4) Transformer taps changing.
Immediate improvement in voltage to a limited extent is possible by changing
the tap of transformers in the system.
The Remote tap changing cubicle (RTCC) is having different ways of control.
They are:-
(i) Automatic control (with AVR)
(ii) Supervisory control (NCC)
(iii) Manual control (local)
For Grid Transformer - control is done from the NCC (supervisory mode only)
- ON Load Tap changing is possible.
For Primary Transformer (66 / 11KV) – Automatic control mode operation is
enabled with AVR(ON Load Tap Changing)
For Distribution Transformer – OFF load, manual control only permitted.
Operation at Abnormal ConditionsThere are generally two conditions where the system runs on bellow target
frequently.
Condition 1 - When all the plants on bar (POB) are fully loaded and the
frequency starts to drop as the load increases further. This is an anticipated
frequency drop situation.
Action required: - Manual load shedding is required to maintain the system
frequency by NCC.
Action sequence:-
21
1) Request private generation assistance ( QAPCO ,QVC and
QAFCO )
2) If frequency drops to 49.9, instruct QASCO to shed one of
there three arc furnaces.
3) Further drop to 49.9, restrict QASCO to single furnace
operation.
4) If frequency drops again and if the tendency of load is to
increase further, manual domestic load shedding is done.
For manual load shedding, 38 list are now functional, each list given a load
relief of about 40 MW. The manual domestic load shedding list in waiting (out
of the existing prepared list) is shed when the frequently drop to 49.8 HZ. And
if necessary this is continued with next list and so on. Next load shedding list
for cyclic shedding is # 23.
Note: DCC should be informed before domestic shedding, and they inform the
stand by offices concerned. Maximum load shedding time is limited to 2 hrs.
First domestic load and then furnaces are restored and later import of energy
is stopped as frequency improves.
Condition 2 - A Sudden drop in frequency due to an unexpected major
generation loss. This is an unanticipated frequency drop situation.
Action required – In this case automatic under frequency load shedding takes
place at various stages.
1. Automatic under frequency Bulk load shedding.
2. 11KV feeders at Primary s/s (domestic load) are kept selected at
predetermined frequency levels as below for automatic shedding.
Stage 1 A - Setting 49.2 HZ
Stage 1 - Setting 48.8 HZ
Stage 2 - Setting 48.4 HZ
Stage 3 - Setting 48.0 HZ
Stage 4 - Setting 47.8 HZ
Load shedding selector switch at the Primary's can be put in the desired stage
of under frequency tripping.
3. To improve MVAR levels during the under frequency tripping, reactors
are selected to be automatically closed during stage 2, 3, and 4.
22
4. First domestic and later the furnaces to be restored manually when
frequency improves.
Load Re arrangement
In order to meet the outage of network elements like Transformer, EHT line,
Bus section etc, the NCC may instruct the DCC to transformer load from one
Transformer to other or one primary to another primary.
Automatic Voltage Regulator
The voltage Band is 10.8 KV to11.20 KV, with a 100 second delay provides to
allow grid level restoration measures.
23
Distribution Control Centre (DCC)
ObjectiveMonitors and ensures continuous electricity supply for the distribution
network, within the prescribed values of limit violations, giving priority to
security and safety.
Major functions Controls Active & Reactive power flow in the network and there by
regulate the voltage.
Confirms to all the operation are done in strict compliance with the
department safety rules and regulations and there by ensuring system
safety and security.
Control , coordinate and direct to all switching operations by giving
instruction to field engineers for switching in the 11 KV network for
maintenance / repair of network components and for after fault
restoration.
Co-ordinate with NCC, in case of generation shortage or other system
contingency to shed the load in accordance to the prearranged
methods.
Issue permit to work (PTW), sanction for test (SFT) and isolation
certificate for work in distribution network and also ensure for proper
isolation and earthing by giving priority to safety and security.
Immediate restoration of supply after disturbance and there by limiting
interruption to the minimum.
Inform management about any abnormality & important events.
Co-ordinate with other department for the smooth and efficient
functioning of distribution Network.
Network control by using telemetryA telemetry system is provided for the smooth operation and monitoring of
distribution network on real time basis.
24
The circuit breakers of the out going feeders of Primary s/s can be controlled
from the DCC console. This is achieved by RTU and telemetry provided at
PRY & DCC. All data's like, Bus voltage, current (out going feeders) and
Breaker status are transferred to DCC for monitoring and controlling. It also
provided alarm and limits violation condition to remind the Control Engineer to
act accordingly. The available data's in the DCC computer console can be
utilized to originate different report for the smooth functioning of DCC.
Available Data's & facilities
Loading Values of different Primary transformers.
Loading values of different outgoing feeders of PRY
Bus voltages of PRY
Breaker and VT status of PRY
Limit violation, alarm and important events.
All the data's available in the DCC console can be utilized for past and
present system analysis and also helpful for the contingency analysis. The
data's available in the database also helps to originate various technical report
& statistics.
Role of System Control Engineer
1) Switching Programmes- Verification & ExecutionThe switching programme is very essential to perform a
switching operation in the network in order to avoid danger and risk. For all
scheduled works the switching programmes should be sent in prescribed from
in advance (Before 48 hrs, if possible) exceptions can be allowed during
emergency and contingency operation like after fault restoration, emergency
load shifting & back feeding etc. For load balancing among primary's and
among feeders, the DCC should prepare switching programmes and send it to
the O&M section for execution. After receiving a switching programme,
Control Engineer on duty should study the programme in accordance with the
following criteria.
25
Effects of the operation on system- check whether the shut down is
affecting any consumers, and confirm that the field engineer issued
the S/D notice.
Check whether all the safety aspects are taken care of before
execution.
Study the load rearrangement during the shut down, possible way of
back feeding, loading values of feeders and Transformers involved.
Check the load of feeders involved in paralleling at the time of
isolation and live phasing.
Analyze the paralleling involved in the programme and check
whether it is a bad paralleling or not.
Scrutinize the point of isolation, back feeding arrangement in terms
of system security and safety.
Study the loading condition due to the shut down and check whether
the shut down causes any overloading to any feeders and primary
transformers involved in the programme.
Check the substation planning Number and Name, Sequence of
operation and safety aspects related to the programme, date of
execution and duration of shut down etc.
Study the Live phasing route ,loading during Live phasing and
consumer effected (If any VIP Consumer is in the route of 11KV Live
phasing, then alternative path should he selected for doing the
same.
2. Activities on the day of executionThe verified switching programmes can be execute after considering the
following
Present loading of the feeders and transformers of the system
Present loading of feeders and transformers involved during isolation
(shifting load from one feeder to another) and during 11 KV Live
phasing.
Mostly the loading data's of Transformers and feeders are available in DCC
console except some PRY's. S.S.A can be utilized to collect the data's from
the PRY's where telemetry is not available.
26
Special care at the time of paralleling Paralleling should be essential for NOP shifting and 11 KV Live phasing, while
paralleling, the following points to be noted.
Check the load of feeders involved before paralleling.
Check whether it is a bad paralleling.
Check the bus voltage of the Primaries involved.
If possible, request NCC to minimize the voltage difference
between Primaries involved.
Block the tap changing in order to avoid furthers changes in
voltage and thus the unwanted circulating current. This will
minimize bad paralleling effect.
If there is a bad paralleling history then arrange two field engineers
for make & break operation (if possible) or break and make
depending upon the consumer affected.
Check the load on feeder involved after paralleling in order to
confirm the paralleling is successful and is not interrupted the
consumer.
Supply confirmation from the field engineer is very essential after
paralleling.
Before energizing a transformer, study the present loading of feeder
involved and if it will over load after energisation, then study other
possible alternatives.
After the work, DCC can advise the field engineer to establish new
NOP in view of load balance among feeders and Primaries.
3. Fault RestorationInformation about the fault is either any one of the following way
1. NCC will transmit the message if the standby Earth fault alarm initiated
at NCC or if the Primary Transformer CB tripped.
2. Alarm initiated at DCC telemetry console.
3. Information's from the call centre / stand by offices.
Action required:-
27
If the CB of feeder at PRY has not tripped, then retrieve the past data
from data base and compare with the present load and calculate the
load loss. This load loss data will help to find out in which indoor the
tripping has occurred.
For collecting additional information about the tripping, the Control
Engineer can utilize the help of SSA and Stand by Technicians.
Convey all information collected to the Distribution Stand by Engineer
and also give the Tel. No. of SSA who attending the fault. Control
Engineer should instruct the field engineer to proceed to the Indoor /
Outdoor / PRY where the fault is suspected.
If OH/L is involved, then inform ABU HAMUR OH/L section to arrange
the patrolling.
Report the matter to the top officials with details.
Study the possible back feeding arrangement.
Collect all information from the SSA at site and from the Stand by
Engineer like relay indication, EFI status, station supply (Battery) and
abnormalities etc.
With the above information locate the fault as early as possible.
While test charging, keep the relay time setting to the minimum.
Isolate the faulty section, apply C/N, L/ off and apply CME at point of
isolation.
Back feed the healthy portion as possible.
Inform the fault to the O&M section for repair and rectification.
If supply is effected and to be continue for a long time, then arrange
Movable Generator.
Before test charging, if OH/L involved make sure that all of the OH/L
patrolling gang are away from the live system. This is confirmed by
direct contact with Field Engineer.
Prepare Abnormality report, along with detailed logging in Station Log.
Report the final status to the top officials.
IMPORTANT SAFETY PRECAUTIONS
28
While executing the switching programme, before first operation check
the switching programme No, Name of work and Name of Engineer.
Execute the programme in a sequential manner.
Give instructions as per the programme to the Field Engineer and ask
him to repeat the given instructions.
Always tell the name and planning No. of location and circuit to the
Engineer.
Note down the time of instruction and time of confirmation of operation.
Before issuing PTW and SFT confirm that the working section is
isolated, Earthed at both ends. And also confirm that the S/L and C/N
applied at the point of isolation.
Always confirm switching positions after cancellation of SFT.
Confirming switching positions after SFT is mandatory because of the
Field Engineer has the approval for the operations of earth switches
under SFT. He has the temporary control over Earth switches during
SFT for the purpose like HV injection, signal injection, colour phasing
etc.
If OH/L involved in the isolated section, apply CME at point of isolation
(if possible) and test OH/L line, if found dead apply Portable Earth at
the point of work. After confirming the above, issue PTW. Before
cancellation of PTW confirm that all CME and portable earth are
removed from the line.
Rack out VT from the line only after isolating both ends. And VT should
be rack in before energizing the cable. VT status should always confirm
before energizing the circuit.
Before HV pressure test, confirm that the transformers are in CME
condition and VT is in rack out condition.
After isolating a circuit breaker (Rack out) always instruct the Field
Engineer to do Trip –Test for the CB.
Before Earthing the transformer, confirm that the MV side is isolated.
Before earthing a section, confirm that the section is dead and isolated.
Apply CME at both ends to a faulty section after isolating both ends.
Also apply S/L and C/N.
29
Always maintain PRY Substation Battery voltage to a value of 110 V
DC.
Always maintain the Indoor Substation Battery voltage to a value of 30
V DC.
Gas pressure should be in green zone for SF6 Outdoor Substation.
When multi permits issued to the same Field Engineer or to different
Field Engineers within the same point of isolation, then the energisation
shall be done only after the cancellation of all holding PTW's within the
isolated section. When multi permits issued to different field engineer,
cross reference numbering is recommended (# CR).
A field engineer can't hold more than one SFT at a time. SFT is issued
by the field engineer to himself and his direct supervision involvement
is required to perform the test.
Proper informational tags must be placed on single line diagram to
avoid any wrong operation.
The field engineer can't suspend the SFT. He has to cancel SFT before
he leaves the site. Any inconvenience occurred to complete the test,
then he should cancel the SFT and also confirm the switching positions
before the leaving the site.
The field engineer can't hold PTW and SFT together.
OTHER IMPORTANT ACTIVITIES
Load shifting / rearrangement as per NCC advise.Some occasions , NCC instruct DCC to shift some load from one Primary to
other as a part of shut down programmes ( Transmission ) or to avoid over
loading of Transformers / feeders. For this arrangement, DCC Control
Engineer on duty should study the present loading of Primary Transformers
and do the possible arrangements.
Voltage Complaints - Voltage complaints received from the consumer can be
solved by the following measures.
Study the present voltage profile.
If possible, request NCC to raise the voltage at 11 KV Bus of PRY.
30
Instruct the Distribution Field Engineer on Stand by duty to attend
the case and to take present voltage of transformer secondary (MV
Voltage) line to line and L-N and also instruct him to verify the
present tap position.
If further increase of tap position is possible, then Switch-off
Transformer and raise the tap. Confirm the voltage and ensure
system back to normal.
In case of PMT, remove the HT fuse and then adjust the tap
position as required.
NOP Shifting:Paralleling between same or different sources is required
Different Situations:-
Load balancing among same or different Primary transformers.
Load balancing among Feeders.
During shut down works – to back feed the load to avoid interruption.
During fault restoration.
To avoid over loading of Feeders and Transformers.
Important Considerations required
Before paralleling, study the voltage profile of sources and block the
tap if required.
Before and after paralleling study the real time loading values of
Feeders and Transformers involved.
Always confirm the supply status and this is necessary to find out
any load loss due to tripping in between.
If the paralleling is having a bad paralleling history, then arrange
make and break with two Field Engineers.
Preparation of Reports1. Commissioning Report.
Collect the relevant details from the Field Engineer and fill up the data in a
prescribed from. The main information's required are as follows
Circuit Labeling Check.
Protection status
Cable / Transformer size
Cable length
31
Battery & Battery Charger Voltage
Earth Fault Indicator positioning
2. Abnormality Report
Any abnormality / tripping happened in the system should be recorded in the
Station Log and also prepare an abnormality report of the incident with details
in a prescribed form.
3. PTW and SFT Cards.
Prepared in prescribed form separate for PTW and SFT and which is serially
numbered with brief details particularly about CME, Name of Engineer,
Section isolated, work, Date and Time etc.
4. Station Log
All events recorded by the Control Assistant in a chronological order during
the shift. This includes all the switching operation instructions given by the
Control Engineer.
5. Control Engineer Log Book
Brief reports about the Operations during the shift.
6. Daily Report – system statistics
7. Weekly Maximum Demand Log
8. Daily peak print out.
Communication facility available
Q-Telephone, KM's Pax phone, Hot line telephone and Fax
Construction & Reinforcement section -Distribution,
Introduction
32
All the construction & Reinforcement activities connected with Distribution
Network is executed by the construction section. The work includes
strengthening of the distribution system by adding /upgrading the network
elements with the existing network. Adding network elements like Indoor /
outdoor substation, transformer and associated network for meeting
consumer demand are always done under the construction activity. But
upgrading the network is always comes under the reinforcement section. For
any new proposal, the Planning and Design department should conduct the
detailed study and after that the proposal passes over to the construction
section for final execution. So Construction section has a vital role in the
development of Qatar’s distribution Network.
New project execution The Electricity planning Network department submitted all the
proposals to the construction section (Head) for final execution. The
construction section upon receipt of the scheme of works from the planning
department, allocates the schemes to the engineers of the construction
section after obtaining the proper consent from governmental authorities.
ROA wing should arrange the approval from the governmental agencies (Qtel,
Sewerage, Civil engineering Department, Road Division and Water
Department of Kahramaa).
Role of Construction Engineer Estimates the material requirement and coordinate the same with the
suppliers & ABUHAMUR work shop
Coordinate with consumer for execution of scheme
Allocate the work to different contractors and coordinate with them for
final execution.
Prepare an action plan for the proposed work.
Prepare shut down notices before execution, if any supply interruption
anticipated.
Prepare switching programme for shut down and Commissioning. The
switching programme along with the alteration proposed to the existing
system is required to get proper consent from the system control (DCC)
33
in advance (before 48 hrs). For preparing SW / programme, collect
additional information like NOP, Existing Network details etc from DCC
The single line diagram with all details (substation type ,cable length &
type , transformer capacity & Nos ) of the existing network and the
proposed alterations should be send along with the switching
programme to the DCC for concurrent and comments in advance
(before 48 hrs ). Keep a copy of the same ( switching programme &
drawing ) for reference & execution
Execute the work with the consent of DCC on a particular day as
indicated in the switching programme or a day mutually agreed
between the construction engineer & DCC.
Commissioning On the day of execution, the construction engineer should contact
system control engineer, DCC for executing the work as per the
switching program.
The system control engineer should arrange for possible back feeding
and load transfer in order to avoid interruption during the execution of
work.
The switching programme and other activities involved during the
execution shall comply the Safety Rules and Operation memorandum
of QGEWC high voltage system. The system operation memorandum
D15 is followed in this aspect.
Before Commissioning a New Substation / Transformer
- Check the new label and fix it properly and confirm the same to
control (DCC)
- Protection and fault level of CB. Verify and inform to DCC.
- Check the operation of CB.
- Check the station lighting
- Check the trip circuit healthiness
- Check station Battery and Charger.
- Check the transformer before energizing (oil check, tap setting,
name plate, abnormalities etc.)
- Fix operating lock and label for new s/s
34
After checking all the safety aspects, the Construction Engineer can
commission the new s/s with proper consent from the System Control
Engineer.
- Do HV Pressure Test for the new circuit.
- Check 11 KV live phasing for the new joints and Terminations
before paralleling.
- Check Phase Rotation & MV voltage for the new transformer.
If all the above checks are satisfying, then Commission the new system.
Techniques used for system safety
A number of different techniques and procedures are adopted for satisfying
the system safety during construction and maintenance / repair activities in
distribution network. The newly constructed or repaired network element has
to full fill all the standards, before it connecting to the existing system. In
Kahramaa, the techniques and procedures used before connecting a new
network element to the existing system are as follows.
1. Cable Identification.
2. Spiking
3. Colour phasing ( core phasing )
4. 11 KV Jointing work & Termination work on HT cable )
5. HV pressure test for 11 KV cable and Bus Bar
6. Dead phasing check – 11 KV system
7. Live phasing check - 11 KV system
8. Phase rotation check for MV side.
9. MV voltage check.
10.Trip / test check for CB.
11.Relay inter trip check
12.Transformer, Switchgear panel, Switches and Substation observation.
13.Relay setting & fault level.
Cable IdentificationDuring construction and maintenance, the existing cable has to be cut
for fault rectification and for commissioning new substations in between the
35
existing cable. Then the Field Engineer should confirm the cable which is
going to be cut is the same cable that he isolated and earthed for doing the
work. This is required only where more cables are present with the isolated
and earthed cable. Any mistake will leads to danger to human life and to
system safety. So before doing any work on cable (joints), the field engineer
should always identify the cable by using proper methods.
Safety measures
The cable has to be dead, isolated and earthed at both ends as
per the switching programme and with proper consent from
System Control Engineer.
SFT is required and is issued by the Field Engineer to himself
with consent of system control engineer.
Senior Authorized Person in charge of the work has the full
responsibility of the operation and test
Method
The Identifier kit consists of an Audio Transmitter and Receiver set, by which
the signal generation and reception is possible. For cable identification test,
connect the Audio transmitter between any two phases of the isolated cable
after removing the earth. Keep remote end of cable as earthed for return
path .Then by using the Audio receiver and head phone, we can identify the
cable in which signal is generated. When the receiver is put nearer along the
cable gives a clear beep but varying sound from the cable trough which
transmitted the signal. Sound variation is obtained only from the injected cable
due to the twisting of cable pairs. But for other cables, humming sound is
obtained from live cables and clear beep but not varying is obtained from
dead cable if any. The Cable Identification test is done by the field engineer
himself in charge of work. See the figure.
SpikingAfter identifying the cable, before cutting, spiking has to
require for 100% confirmation that the cable is absolutely dead and safe for
cutting. Spike gun is a special arrangement, where the iron bullet is used for
firing. The spiking gun with bullet is placed over the cable and firing is done
remotely with the help of a rope. If the cable is the correct one, there is no
heavy sound. But for live cables heavy flash over and tripping may occur.
36
Thus spiking will helps to avoid dangerous situation and it provide more safety
to the working personnel's.
Safety measures
The cable should be Dead, isolated and earthed at both ends
with the consent of System Control Engineer.
SFT is required before doing the spiking
After spiking, the cable has to be cut and prepare ends for phasing PTW is
required for any work on cables. But this is a lengthy procedure which can be
reduced subject to pre conditions detailed on Kahramaa S.O.M. No.7.
Colour phasing / Core phasing –Phase identification checkDuring construction / maintenance, cable jointing, break and make termination
works are required. Due to straight jointing perfection and easiness, human
errors and termination difficulties, there may be a chance of colour crossing
while doing cable works with respect to the system colour. So colour phasing
is required during termination & jointing work and is the process of identifying
the 3 phases of system with the 3 core of the cable. Incorrect phasing cannot
be parallel with other systems. So colour phasing is more essential for all type
of jointing / termination works to transfer the same system phase(R, Y, and B)
from one point to other point. Colour crossing of the cable is serious and to
avoid this colour phasing is required during jointing and termination work.
Different methods for colour phasing
1. Banana Resistance and Megger
Connect the three different resistances (known value) to the RYB phases of
one cable end (Star connection with star point earthed) then by using a
Megger, which connected to the other end of cable and measures the
resistance. The corresponding values of resistance obtained on phases will
give the correct phase.
Uni directional LED with Battery set.
Connect the battery between any two phases of cable at the known end. Then
the lamp glow will indicate the phases where the battery connected and it also
37
indicate the direction of current flow. Then from the lamp glow and direction
we can easily confirm the three phases.
Safety
Before doing test, the cable should be isolated, earthed at
both ends with the consent of System Control Engineer.
SFT is required.
General safety measure for Identification, Spike & Colour phasing of cables
Under SFT, the Field Engineer (Senior Authorized Person) has the
approval to operate the earth switch for testing purposes.
The Field Engineer should confirm the switching position after the
cancellation of SFT to the System Control Engineer.
The Field Engineer will be responsible for all such operation or test on
the isolated cable and equipment and also responsible for ensuring
safety , during test.
HT Termination & Jointing works for Cables
All termination & jointing works on cable required PTW. PTW is issued
by the Senior Authorized Person to a competent person (Cable jointer / Fitter)
for doing the work with proper consent from System Control Engineer.
Before issuing PTW for a working section, the System Control Engineer
should confirm that there is no SFT is pending. Issuing PTW and SFT
together for same point of isolation is not permitted. If PTW is issuing after the
SFT, then the Control Engineer should always confirm the switching position
and also confirm that both ends of the cable is isolated and earthed.
Competent person - Kahramaa certified HV Cable jointer / Fitter with
Identity card of Kahramaa
Straight joint kit - XLPE cable to similar XLPE or PILC to similar PILC
Transit joint kit - XLPE cable to PILC or PILC cable to XLPE
Dead joint - Jointing work on Dead cable
Breaking a Termination – Removing an existing cable at a termination point
Making a Termination - Connecting a new cable at a termination point
Break & Make Termination - Breaking and making termination of cable at a
Point during construction / maintenance work
38
Safety
Before doing any work on cables, the cable section must be
isolated & earthed at both ends.
Any work on cables like Break & make terminations, Cable
jointing works required PTW safety document.
PTW is issued by the Senior Authorized Person to the
Competent Person (Cable jointer/Fitter) with the consent of
system control engineer.
The Senior Authorized Person should keep the original copy
of PTW and give a copy of the same to the Competent
Person. After the completion of work, the Competent Person
should give clearance to the Senior Authorized Person for
cancellation of PTW.
High Voltage Pressure Test The High Voltage Pressure Test is compulsory for cables after the
completion of termination and jointing works during construction and
maintenance. The HV Pressure test for new Bus Bar is also required during
construction. The HV Pressure test or injection test is required for cables to
test dielectric strength of insulation. A special HV Pressure Testing Kit is used
for this purpose. During test, -11 KV DC is applied between Phase and
ground(R-E, Y-E, and B-E) and 22 KV DC (-11KV – 0 - +11KV) is applied
between Phases(R-Y, Y-B, and R-B). The duration of HV injection is about 15
minutes for each test. Pressure test is also required to test the perfection of
terminating & jointing work.
Pressure Test Kit
In the testing instrument, meters are provided to indicate the applied KV and
leakage mA of the circuit. If the leakage current value during injection is in
between 0.1 and 1.5 mA, then the cable is declared as healthy. The leakage
current higher than 3mA indicates the breakdown of the circuit. That means
excessive leakage current or tripping indicates that the dielectric strength of
insulation, jointing work / termination work is not up to the standard. If there is
a new bas bar is involved in the circuit, then HV Pressure test for Bus Bar is
also compulsory. For safety, discharge rode is provided with the test kit to
discharge the capacitive charge of cable after the test.
39
Phase to Earth Test
Voltage applied = 11 KV DC (Negative)
(R-E, Y-E and B-E)
Duration - 15 Minutes
Apply – 11KV DC between each phase and earth for 15 minute.
Phase to Phase Test
Voltage applied = 22 KV DC (11 KV 0 +11 KV)
Duration - 15 Minutes
Apply 22 KV DC between R&Y phases for 15 minutes. And repeat the same
test for the other two combinations (R-B & Y-B)
Safety during pressure test
SFT is required for doing Pressure Test.
Before doing Pressure Test, remove all type of earth applied for the
section.
Inform to all the personnel working at site about the test and keep
them away.
The field engineer responsible for the test should confirm that all newly
constructed / repaired elements including Bus Bar, cable joints,
termination are subject to the test.
After the Pressure Test, the SFT taken should return and cancelled
with the consent of system control engineer. Confirm switching
position is mandatory.
11 KV DEAD PHASING
This is a method of checking R, Y, B, phasing of the newly constructed
elements from known end to the other end before live phasing. Dead phasing
will not disturb the existing system. This is a pre - confirmation test before live
phasing.
11 KV LIVE PHASING After all type of constructional / maintenance activities on cables,
terminations, the 11 KV live phasing is required. This is essential for meeting
40
same RYB sequence condition before paralleling between two systems. It
always conducted at I/D substation and it prove that the added network
elements in same phase sequence with respect to the existing. The I/D
Substation nearer to the newly commissioned Substation should be taken in
order to minimize interruption to the consumers.
Live phasing proving the there statements below:-
R phase is connected to Existing System R phase
Y phase is connected to Existing System Y phase
B phase is connected to Existing System B phase
At the time of live phasing, we have two different sources from two stations
and is available at the Bus Bar spout and Cable spout in an Indoor S/S. One
is the existing supply source of I/D substation where the live phasing test to
be carried out and is available at the Bus Bar spout. The other one is the
existing supply taken through the new circuits (includes all terminations, cable
joints, and Bas Bar except the transformer circuit) and is available at the
Cable spout of the Indoor S/S.
Live phasing sticks
Live phasing is proved by measuring the voltage between the phases
available at the Bus Bar spout and the Cable spout. Live phasing sticks
consists of two sticks connected in a special manner with a Voltmeter and one
is inserted in Bus bar spout and the other is inserted in the Cable spout during
the test. The Voltmeter measures the potential difference between the Bus
Bar spout phases and the Cable spout phases. While observing the live
phasing between the two system available at Bus bar spout &
Cable spout, for correct live phasing the voltage should be as follows:-
R of (Bus bar spout) to R (Cable Spout) – 11 KV
Y of (Bus bar spout) to Y (Cable Spout) – 11 KV
B of (Bus bar spout) to B (Cable Spout) – 11 KV
R of (Bus bar spout) to Y (Cable Spout) – 5.5 KV
Y of (Bus bar spout) to B (Cable Spout) – 5.5KV
B of (Bus bar spout) to R (Cable Spout) – 5.5KV
If any mistakes happened during work, then the voltmeter will indicate
incorrect reading. Then the Field Engineer should rectify the mistake.
41
At Indoor substation, the CB towards the new circuit should be kept opened.
Then Bus Bar spout is having the existing supply and cable spout is having
the existing system through the new circuit. By inserting live phasing sticks
between bas bar spout & cable spouts, we can confirm whether the live
phasing is correct or not.
Safety during live phasing
Keep Circuit Breakers of L/TX's at new substation as opened, isolated
and earthed condition ( MV link should be opened before closing Earth
switch)
Include all the terminations, cable joints for checking the live phasing.
Some times including all joints and termination together is not possible
at that time check separately for different routs.
Make sure that all the newly constructed /repaired circuit is included in
the test and have the same phasing with respect to the existing system
phasing.
After successful live phasing check, the Field Engineer should
coordinate with the System Control Engineer for closing the CB
between existing system and new system. Bad paralleling and loading
capacity of feeder should be considered for safety and stability.
Check live phasing at an I/D substation which is mutually agreed
between the Field Engineer and System Control Engineer.
Considerations are minimum interruption, distance traveling, loading,
bad paralleling etc. We can conduct live phasing at any I/D substations
( existing or new one )
If the supply is taken through the new circuit includes an existing O/D
substation, then the existing and new phase rotation has to be check
for consumer safety.
Phase Rotation & MV voltage check for MV side11 KV live phasing only proving that the new HT network elements are
in correct phase with respect to the existing system. But for transformers MV
phase rotation & voltage check is required to ensure that the consumer supply
is not affected due to the alterations and modifications done during the work.
This is required to ensure proper MV voltage and phase rotation to the
consumer.
42
Methods
1. Phase Rotation meter
2. LED Flickering meter
Phase rotation can be checked either by using a phase sequence check
meter (rotating dial with arrow indication) or by using an LED flickering
meter. The rotation in arrow direction indicates the correct Phase
sequence.
Phase rotation check is done at the MV link of transformer.
MV Voltage
Check the voltage at MV panel between three phases and also check the
voltage between phases and neutral.
Correct Value R-N
Y-N - 240 V
B-N
R-Y
B-Y - 433 V
R-B
Safety
Keep the MV side link / ACB as open during the phase rotation and MV
voltage check.
LT side fuse replaced only after the successful commissioning of
transformer.
Close, Trip-Test and recloseTrip-Test
If any CB is Rack out for any operational purpose, then it must be checked
for trip test. This is for a confirmation that all the auxiliary contacts are healthy
as before. Trip test is done by rotating the disc manually and it ensure the
following
Circuit Breaker auxiliary contacts are healthy and okay as before.
Trip circuit is healthy.
Close
If the live phasing is correct, for proving the same the Field Engineer
should close the CB between two systems.
43
Reclose
After proving the live phasing, the system NOP should be as per the
direction of System Control Engineer. That means the close or reclose is
according to the system condition.
Relay inter trip test
Air Circuit Breakers are provided in some consumer panel with
Restricted Earth fault relay ( REF ). REF protects the MV side winding of
transformer and the MV cable up to the point of CT from Earth Fault. Inter trip
feature is provided to trip the HT side CB of transformer during MV fault/ACB
tripping condition. So this inter tripping feature has to be tested before
commissioning the transformer
Physical checks before Commissioning The Field Engineer should observe all the Transformer, Circuit Breakers,
panels, Switch gear room and Switches etc before commissioning the station.
Check the following.
Transformer - Oil check
- Tap position (nominal ‘3’).
- Termination (MV & HV)
- Name plate details (Rating and % Z)
Circuit Breaker - fault level
- Operation check.
- Trip circuit healthiness.
Panel - Circuit labeling.
- Meters to be check for its functioning.
- provide operational locks.
- relay setting & trip circuit status.
Substation and Switchgear room - Planning Number.
- Door Lock.
- DC Battery Voltage check.
- Battery charger healthiness.
- Station lighting.
Operation & Maintance section, Distribution, Kahramaa
44
Introduction
The smooth functioning of distribution system is always in
accordance with the performance of its operation & maintenance team. So
continuous and reliable supply is ensured only through the better and efficient
performane of the operational and maintanance section of the department. In
Kahramaa, this is achieved through the engineering wing and workforce.
Engineering wing is headed by one senior engineer and execution of
oparational & maintenance activities are done by the group of Field
Engineers. Work force is available at the ABU HAMUR work shop and from
there the work is arranged and cordinated. The material and manpower for a
work should be arranged from the ABU HAMUR workshop. LT maintance and
operational activities are done by the different distribution stand by offices.
Cordination of stand by offices are done by the DOHA call centre. The Field
Engineers can use the help of stand by offices and that is depend on their
availability.The O &M works includes the repairs of Switchgear and the
network elements.The ultimate aim of all activity is to deliver good quality
power supply to the consumers without interruption.
O & M Section activitiesAll switching operation for the operational & maint works is done by the
field engineers. Operational and maintenance activities can be subdivided into
the following categories.
i. Preventive Maintenance : - Preventing a future breakdown and
ensure continuous supply. All periodic scheduled maintenance
on the 11 KV Distribution system is comes under this category.
Regular systematic maintenance, all preventive action taken for
the smooth & efficient operation of the system. Servicing,
Overhauling and routine oil and gas check are examples.
ii. Corrective maintenance or Breakdown Maintenance :- This is the
corrective actions taken for the smooth and efficient operation of
the system. The Break down or corrective maintenance
activities are conducted after the failure of an equipment. Such
maintenance results in outage of circuit and supply. In general,
it consists of locating the trouble, repair and recommissioning.
45
General duties of O&M Field engineersAll switching operations for O&M work are done by field engineers on duty
1) Periodic repair & maintenance – Preventive works-oil /gas
changing, servicing etc.
2) Break down Maintenance -TX replacement, Faulty Cable
rectification etc.
3) Emergency break down duty - stand by engineer generally attend
this duty on rotation basis. Loss of supply due to tripping and
emergency load shifting are coming under this category.
4) System operation duty - The spare field engineer should attend
the load rearrangement works as per switching programme (NOP
shifting) for the smooth running of system as per the request of
system operation (DCC).
5) Cable fault: - The field engineer (Cable fault) on duty should
locate the cable fault. After finding the fault, the field engineer has to
arrange the excavation team and the cable jointer. After repairing he
has to restore the supply.
All these above discussed activities should be coordinated by the
senior Engineer of O&M and shall comply the safety practice and Operation
Memorandum of Kahramaa. The interference to the live system is permitted
only with the proper consent from the System Control Engineer on duty
(DCC). So for all the work (operational, repair and maintenance ) the field
engineer should obtain proper consent from System Control Engineer (DCC).
Immediate supply Restoration:- Immediate supply restoration always gives better service to
consumers and is important in distribution system. The kahramaa distribution
system has adopted an efficient and effective way for overcoming the
emergency breakdown condition. The field engineer are posted on a round
the clock rotation basis for the stand by duty in order to attend the emergency
tripping conditions and restoration thereon. During the tripping and emergency
condition, the system control engineer should co-ordinate and directs the field
engineers for immediate restoration. The system control engineer should
46
direct and co-ordinate by giving instructions to the field engineer as per the
relay indication and other field information. First, he should find out the faulty
portion and then isolate it from the healthy system and then restore the
remaining healthy system as early as possible. After that, DCC Control
engineer has to direct and coordinate the field engineer to rectify the faulty
section as early as possible. All the above switching operation must be done
according to the safety rules & as per the Operation Memorandum of
kahramaa.
The stand by offices staff provides assistance to locate the fault during the
restoration process. Along with the stand by office staff, kahramaa has
substation attendants who comes under NCC and posted to some Primary
Substations. The SSA also provides necessary assistance during a fault or
system disturbance. Apart from the above, kahramaa providing stand by
diesel generators, this is capable of delivering power to the interrupted
consumers. DG Set allocation is mainly depends on the duration of
interruption and the nature of consumer.
Load re- arrangement (NOP Shifting)As discussed in the introduction, in kahramaa distribution system, the open
ended Ring main system (Ring –off with NOP) is mostly used. NOP is the
normally opened points in the 11 KV Distribution systems and is shifted to
transfer load from one primary to another or shifted load from one feeder to
another feeder of same primary. NOP is provided for the smooth operation of
system grid and for operational flexibility. Closed Ring operation is also
provided for some important distribution consumers. But mostly all I/D and
O/D substations are feeding from one source at a time and there is always
one or more alternative sources (either from same or different PRY) are
available as NOP. Some Radial feeding s/s and multiple source feeding s/s
are also available (same primary). The location of NOP decides the loading of
the 11 KV feeders which in turn reflects the loading of the transformers of the
Primary Substation.
NOP shifting will always helps to balance the loading among 11 KV feeder/
primary transformers and also helps to back feed the system at the time of
supply failure. There NOP shifting can be execute either by a pre-planned
manner (prior switching programmers) or for an emergency situation like over
47
loading / tripping of feeder / transformer (PRY). If it is in urgent nature, then
the field engineer on stand by duty has to attend the NOP shifting. The pre-
planned NOP shifting programme is normally executed by the field engineer
on system operation duty.
For system operation load shifting (NOP- Shifting), the DCC
should prepare the switching programme and the switching is
done by the field engineer.
Work fore for Distribution Kahramaa is having a strong work fore to do its operational,
maintenance, repair and construction activities of the distribution system.
Abu Hamur workshopAll repair / maintenance activities for switch gears, panels,
transformers, switches etc are done at this work shop. There are different
section are working under the Head of workshop. The man power for the O&M
activities and constructional activities are also supplied from this work
shop .Round the clock duty is also available for some important areas.
Fitting Section
OHL Section
Cable section
Diesel Generator section
Stand by OfficesStand by offices are under the system operation department (DCC).Their
primary duty is providing service to the consumers (MV / side service). Supply
interruption of the consumer is attended by the stand by office Staff.
Depending on their availability, the O&M, Construction and DCC can
utilize them for finding Substation location and for collecting information’s from
site etc.
1. DOHA STAND BY / EMERGENCY CALL CENTRE2. KHALIFA TOWN STAND BY
3. RAYYAN STAND BY
4. WAKRAH STAND BY
48
5. M. SALAL STAND BY
6. KHORE STAND BY
7. AL- GHOWAIRIYA STAND BY
8. SHAHANIYA STAND BY
9. RUWAIS STAND BY
Substation Assistant –SSAControlling from NCC / DCC
Duty - Primary substation
-Collecting information’s from the different sites as per the requirement
of NCC/DCC.
Switching ProgrammeA group of sequential operation and activities required to avail shutdown for a
live system to perform some operational, repair / Maintenance work and to
energize back the system to normal after completion of work.
Switching Programme Form
Operation No Location Circuit Operation Time Initial
Work Execution
For arranged work like preventive maintenance,Corrective
maintenance, the field engineer should prepare the switching
programme after obtaining proper data from DCC and send to the DCC
prior to the execution(48 hrs before).
For emergency break down / tripping work the field engineer should
operate according to the proper instruction from control engineer on
duty ( DCC).
Distribution System Protection
Introduction
49
The function of a protection scheme is to ensure the maximum continuity of
supply. This is done by detecting the faults and isolating the minimum
possible part of power system during fault and abnormal condition. Protective
relays are the devices that detect abnormal conditions in the Electrical power
system by constantly monitoring and measuring Electrical quantities as well
as various other parameters to discriminate between Normal and abnormal
conditions. The basic Electrical quantities which are monitored for detecting
abnormal conditions are
Voltage
Current
Phase Angle
Frequency
Discrimination
Discrimination is the ability of the protective relaying scheme to determine the
point at which the fault occurs and isolate (by mean of Tripping actions) only
the faulty element or section. Basically there are there methods of
Discrimination.
Time Discrimination
Comparison Discrimination
Magnitude Discrimination
When more than one protective device is used in series, it is necessary to
have discrimination between these protective devices.
Types of faults The most common fault that can occur on a power system are as follows
1) There phase fault (L-L-L)
2) There phase to ground (L-L-L-G)
3) Phase to phase (L-L)
4) Phase to ground (L-G)
5) Phase to Phase with ground (L-L-G)
Faults in system
Cable faults – Joint faults, termination faults and third party damage
Transformer faults – Incipient faults, over loads, terminal faults, winding
faults and through faults
50
Switch gear faults – Flash over due to insulation failure
Bus bar faults
Natural events
Physical accidents
Mal operation
Kahramaa Distribution system protectionThe protection scheme used in Distribution Network including the Primary
substation, Indoor substation and outdoor substation are detailed below.
Primary Substation protectionThe protection schemes at a typical primary substation 66/11KV with 2 X 40
MVA Transformers is as follows.
1. Transformer Differential – Instantaneous relay
Unit Protection scheme protects the LV & HV windings of the Transformer
from internal faults (short circuit & heavy Earth fault) protected zone is in
between the LV & HV side CT’s
2. HV side REF Protection – Instantaneous relay –4B3 type
A type of Unit protection and it protects the HV side winding of transformer.
REF is highly sensitive to all Earth faults. Protected zone is within the line
CT’s and neutral CT’s. A small Protection of winding nearer to the neutral
remains as unprotected.
3. LV REF Protection – Instantaneous relay
It Protects the LV side winding of transformer from internal Earth faults.
4. HV side IDMT Relay - (2 O/C+1 E/F)-Type –TJ M10.
A type of Back up protection and it protects the transformer from HV Side
Over currents and Earth faults.
5. LV Side – Directional Over current and E/F Protection (DOC)
It always directed towards transformer LV winding. Protects the transformer
from heavy circulating current occurred at the time of tap changing and it also
protect the other source in the same Bus from the internal LV fault of the
transformer.
51
6) Temperature, Gas and oil surge protection for transformer
Main TX Bucholz /PRV trip
Tap changer Bucholz surge/gas trip
Earthing TX Bucholz surge trip
Main Transformer winding temp trip
Eathing TZ Bucholz Alarm
Earthing TX low oil level
Main TX Bucholz Alarm
Main TX winding temp alarm
Main TX low oil level
Other Relays
Master trip Relay-All relays are wired to the master trip to initiate the tripping
signal for Circuit breaker. Type –F8H trip relay.
Pilot wire inter trip –Type TEC Relay
Pilot wire protection sustained inter trip -Type TC-5
Earthing transformer and system protections Since the Primary transformer is star delta, an Earthing transformers OF 500
KVA with Zig Zag winding is used on the 11 KV side with tertiary delta
winding.
Tertiary – 166.6KVA
11/0.415KV
Percentage impedance – 4.23 %
Impedance per phase is 27.5 ohm
Maximum fault current for 3 seconds is 750 A
Earthing transformer is required for the following purposes
The earthing transformer is mainly used for the earthing purpose. It
creates an artificial neutral point on the delta 11 KV side winding.
Used to limit the fault current to a maximum of 750 Amps
52
Used for the purpose of SBEF protection and also for the REF
protection
Used to provide Auxiliary supply to primary substations (415 volts)
Stand by Earth fault ProtectionStand by earth fault relay is provided in the secondary circuit of earthing
transformer neutral CT. If an earth fault is not cleared by appropriate Circuit
breaker of 11KV feeder in the Primary substation, the earth fault current will
continue to flow through of the 66/11KV transformers in the Primary
substation.
If the fault persists without clearing by the feeder earth fault protection the
fault will be cleared by the SBEF stage 1 and 2 timer relays. Stage 1 will trip
the bus section and stage 2 will trip the transformer. Main features are as
follows.
o Protects the 11 KV distribution systems including the Primary
transformer LV winding from Earth fault and the maximum earth fault
clearing time is limited 3 seconds.
o The SBEF relay will initiate “Flag ON” condition for all earth faults
(magnitude higher than the set value). Current setting depends on the
independence of the Earthing transformer.
o If the fault is not cleared by the appropriate feeder earth fault
protection, then it will be cleared by the SBEF stage 1 & stage 2 timer
relays. SBEF stage 1 will trip the bus section CB after a definite time
delay of 2.4 seconds and stage 2 will trips the CB,s of faulty section
transformer HV and LV side after 3 seconds definite time delay.
o Relay operation will initiates alarm in NCC and PRY
In Kahramaa Earthing transformers are designed to allow a maximum fault
current of approximately 750 Amps for 3 seconds and Normal current setting
is 20%. C/T Ratio for SBEF protection is 750/1
(27.5/ phase – impedance of ETX)
Effective impedance (27.5/3) =9.16 OHM
I fault (Max) = 11000 / 3x9.16 =694 =750A for 3 Sec
53
SBEF - Flag ON initiated at NCC and PRY sub station
(If the If is set value)
Stage-1 –Trips the Bus coupler CB after 2.4sec
Stage-2 – Trips both the HV & LV side CB of PRY TX after 3 sec
11 KV Bus bar Protection 1. Partial Bus bar Protection
2. SBEF where there is no partial bus bar protection and in the substations
with partial bus bar, SBEF act as a back up protection.
Partial Bus bar protection Partial bus bar deferential protection employed in the 11 KV feeders of
primary substation equipped with bus section breaker. This relay works on
deferential principle and the relay is connected across the secondary CT's of
bus coupler and incomer with an overlapping arrangement. The feeder CT’s
are not involved in this scheme of protection causes relay operation during
through fault condition. To avoid this, discrimination between Bus Bar fault
and 11 KV feeder faults is provided. Main features are as follows.
It protects a portion of Bus Bar from bus Bar faults and provides a back up
protection for the 11 KV feeders. For 11 KV system faults feeder protection
act first and when it fails partial bus bar protection will act as back up.
The phase fault element of the partial Bus Bar protection is graded with
the feeder phase fault protection and Earth fault element is graded with
feeder Earth fault element and stand by Earth fault protection.
In Partial Bus Bar, its 50 element (Hi set) 100m sec delayed operation is
enabled to avoid the tripping in through fault condition. After 100 m second
delay, the partial Bus Bar relay will trips the Three CB's (Bus coupler CB,
HV& LV CB of faulty section transformer).
51 element of partial Bus Bar act as a back up protection to outgoing
feeders. A time grading of 300 millisecond is provided between the IDMT
O/C elements of Out going feeders & PB relay and Transformer HV O/C
For Internal Fault
54
PBDP- 50 element (High set) - will operate after 100 milli sec delay.
For External Fault (Through fault)
PBDP –50 high elements will receive a blocking signal from the out going
feeder 1DMT (50 element hi set) within the 100 milli sec time, Then its
operation is blocked by the feeder IDMT (Hi set). If the feeder fails to
send blocking signal, PBDP (50 high set)will trips the LV ,HV side breakers of
transformer along with the Bus coupler breaker.51 elements act as a back up
protection for the feeder
Grading
50element -100 milli sec time delayed operation.
51element (O/C) – graded with the feeder IDMT O/C and TX HV side O/C
(Time grading only possible - 300 milli sec)
51 element (E/F) - graded with feeder E/F (IDMT) and SBEF
(Magnitude grading only possible)
CT is -2000/1; current setting is normally 7% (300 m sec time grading)
Primary substation feeder protectionNormal protection scheme consist of the following relays.
1. Pilot wire protection
2. Standard IDMT Relays (2 O/C +1E/F)
Pilot wire protection A type of unit protection
Solkor R instantaneous protection (60 milli sec)
Relay operates on either current or voltage comparison
Used as main protection in feeders
Pilot wires interconnect the CTs at each end of the line. Employing the well-
known differential principle this would compare the current entering the line
with the current leaving the line. In practice two relays are connected at each
end of the line connected by two pilot wires. Summation CT is used for
converting multiple input quantities from a 3 phase system quantity to a single
phase quantity.
55
For Internal fault - fault within the two CT’s
Difference in current (entering & leaving) causes relay operation and trips the
CB at both ends.
For External fault
Entering and Leaving current is same. No current flow through the relay coil
and
relay remains stable.
Important points
The padding Resistance to set to a value such that, the total loop
resistance of the pilot wire cable is 1000 Ω. Let RL be the Pilot wire
lead resistance. There the padding resistor to be provided at each end
is , RP =1000-RL Ω (RL is normally about 10 Ω).
Current Check Relay (B 69 Relay) is used in series with the SOLKOR
Relay and it will prevent the tripping of the 11 KV cable feeder on
account of any pilot wire open condition or pilot wire shorted condition.
For the current check Relay the O/C setting is provided with more than
the O/C setting of the IDMT O/C relay on the feeder.
Pilot wire supervision relay is also used to detect any fault in the pilot
wire circuit and for any type of fault in the pilot wire
If pilot wire supervisor Relay or current check relay is not provided
along with SOLOKOR R Relay, the following situations can occur
SOLOKOR R unit protection acted and the Feeder trips only at receiving end,
it can be assumed that it is pilot wire problem and in this Situation, the feeder
not to be put in service until the Pilot wire unit protection is decommissioned.
The sending end of the feeder Tripped on SOLKOR R unit protection but no
tripping at the receiving end. Then in this situation the feeder not to be put in
service until the 11kv cable is meggered. On meggering, if no fault is found
on the Cable, then the feeder to be charged from the sending end.
Standard IDMT Over current and Earth fault relays Simplest type of protection
56
Protect the feeder and network elements from O/C and E/F
Time and Current grading or combination is possible
Standard IDMT relay is provided (2O/C(R and B phases) +1E/F(Y phase))
Induction type – TJM10 and Static relay-MCGG52
Normal current setting is 125% for O/C element and 40% is for E/F element
with a time setting of 0.4 TSM
Some IDMT relays are provided with stage 1 & stage 2 operation features
Stage 1 –50(High set element) & 51(IDMT element)
Where 50 high set is used for SOTF (Switch on to fault) feature.
100 milli sec –300 milli sec delayed operation is provided for this type relay in
order to avoid tripping during heavy inrush currents (100 m sec –300 m sec) is
the decaying time required for inrush. In some cases, SOTF protection is also
provided with Harmonic Restraint feature (100 millisecond delay ) or with out
Harmonic Restraint feature (300 millisecond delay ). The 2nd Harmonics from
magnetizing inrush currents or switching surges will decay with in 300 milli
second.
51- Normal IDMT element with grading.
Stage-2
50 element - Initiate blocking signal to the Partial Bus bar high set element
and the signal will reach within 60 milli sec. during a fault in the out going
feeder. The High set element of IDMT relay is not used for tripping but it
sending blocking signal to the partial Bus bar relay.
Relay OperationFor Three phase balanced fault – R&B O/C relay will operate.
For Three phase earth fault - R&B O/C relay will operate
Phase to phase fault - R or B phase O/C relay will operate
Phase to phase to earth fault R or B phase O/C+E/F will operate
IDMT act as primary protection in feeders where pilot wire protection not
commissioned. If an Out going feeder is commissioned with pilot wire
protection, then the IDMT relay act as a back up protection.
57
Protection used in Indoor SubstationFeeders-1) Standard IDMT relay (2O/C(R and B phases) +1E/F(Y phase))
Induction type – TJM10 and Static relay-MCGG52
2) Pilot wire protection - SOLKER R instantaneous tripping
Pilot wire protection (SOLOKOR R) is provided in cables between two
indoors and also provided between the Indoor and Primary s/s.
Bleed off feature is available for 20% of the cable full load. That means
for a 300 ampere cable, 20% bleed off is allowed (60A).
Transformer protection – 11/.433KV HV side is protected by EIDMT O/C & E/F protection with separate
High set instantaneous element for O/C and E/F.
LV side winding and cable up to the CT point is protected by Restricted
Earth fault protection. (In case of consumer MV panel with ACB and
REF relay available)
From MV panel REF relay to HV panel, intertrip cable used for the
connection for 11 KV inter tripping.
IDMT relay with EI Characteristic is used. This Provides better grading
with the MV fuses. Type TJM 31 &2TJm31.
Separate High set instantaneous element is provided to protect
transformer from heavy fault
Current setting and CT ratio required is as per the transformer capacity
High set relay setting is as per the short circuit fault current of the
transformer. (To avoid the unwanted tripping due to magnetizing inrush
current, 130% of the expected fault current is taken for relay current
setting)
MV side protection - Fuse protection is available.
- ACB with REF is provided in some consumer panel
Time and Current grading
58
In Radial feeders, Standard IDMT relays are graded with time and current
discrimination.
PRY substations relay setting (O/C element) -125% plug setting with 0.4 TSM
PRY substation relay setting (E/F element) - 40% plug setting with 0.4 TSM
First Indoor S/S setting (O/C element) - 100% plug setting with 0.275 TSM
First Indoor S/S setting (E/F element) - 30% plug setting with 0.275 TSM
From first indoor the current setting is fixed as 100% for O/C and 30% for E/F.
Then the protection is graded by time and always keeps a grading margin of
0.125 TSM to avoid false tripping. The maximum grading stages allowed is 3.
Protection used in Out door Substation Feeder - no protection is available
- EFI is provided to identify the path of earth fault current.
Transformer -Oil Fuse Switch
HRC fuses are used to protect HV side
Transformer rating and Fuse required
500 KVA - 40A
800 KVA - 60A
1000 KVA - 60A
1600 KVA - 90A
Transformer with SF6 TX switch
Time lag fuses are provided in the CT secondary circuit to protect HV side.
TLF required for Transformers with different CT is shown below.
Voltage
KV
TX Rating
KVA
CT Ratio
A
TLF rating
A
Max.distributo
r fuse link
rating
A
59
11 200 50/5 3 160
11 300 50/5 5 250
11 500 50/5 7.5 315
11 800 50/5 12.5 400
11 1000 100/5 7.5 500
11 1250 100/5 10 630
11 1500 100/5 12.5 630
11 1600 100/5 12.5 630
Parallel Feeder ProtectionSource end -IDMT relay (51)
Load end - Directional relay(67)
Closed Ring
Protection schemes required for a closed ring system are as follows
Pilot wire protection (SOLKOR R-type) should be commissioned before
closing a Ring system. Ring splitter should be provided in order to separate
the ring at the time of tripping of Bus coupler CB by the operation of
PBDP/SBEF protection during the fault. Ring splitter is an IDMT relay with
current setting 100% for O/C and 20% for E/F element. The time setting
should be minimum (0.1 TSM)
OR
Combination of IDMT relays (Directional &Non –Directional) with Ring splitter.
Over head line protection IDMT (2 O/C+E/F)
Sensitive Earth fault protection
Sensitive Earth fault protection
IN OH/L, the earth path resistivity is very high and then the normal E/F relay
will not detect the earth fault of the system. To overcome, this condition OH/L
60
are provided with sensitive earth fault relay (current setting is 3% with a long
definite time lag of 3 seconds).
CT Ratio - standardsPrimary substation
LV side of TX and Bus bar - 2000/1 for PBDP
-2000/1 for D O/C and D E/F
Out going Feeders - 400/1 or 300/1 for IDMT, SOLOKER R & Metering
Earthing Transformer - 750/1 (Neutral CT)
Indoor substation
Feeders - 300/5 or 400/5 for SOLKER R, IDMT and
metering.
Transformers - 150/100/50/5, 80/40/5, 60/30/5, 100/50/5
for IDMT & Metering
Out door substation
Transformer with SF6 TX Switch – 100/5 or 50/5
CT classIDMT Relays - 5P10, 15VA
SOLKER R (for differential type) - Class x
Metering - Class 1
Battery supply availablePrimary substation - 110V DC
Indoor Substation - 30V DC
General Informations Operation & safety locks.
61
Co2 System features.
Location map
NO P Shifting
Bad paralleling and Tap Blocking
Confirm supply in I/D and O/D Substations.
Substation & Circuit Identification.
System Safety.
Circuit Breakers – Method of isolation.
Pot End & Cap End Cables.
Operational & Safety Locks with Keys.
For better operational and system safety, kahramaa provided Operational and
Safety locks with keys to their Field engineers. Apart from operational & safety
lock, Substation keys are also available and is provided to all field engineers
and to some contractors.
Operational lock with key
Indoor and Outdoor Substations
All Switches, Circuit Breakers, Panels, Isolating and Earthing devices are
provided with Operational lock with key. Normally two types available and
given to all Field Engineers.
1) 246 Type
2) Den ( Department of electricity network )- small size
Strictly follow kahramaa's Safety Rules, while using the operational locks
during the work.
Primary Substation
Separate operational lock sets are provided for each circuit of Primary
Substation. A main key box is fixed in all Primaries. Any circuit is taken for
PTW / SFT, then after proper locking the corresponding key set for the circuit
should be kept under safe custody in separate Danger Envelop as per Safety
Rules. The Operation and handling of PRY keys is limited to the Field
Engineers.
Substation Gate locks with key
62
1. Primary Substation gate key
2. I/D & O/D Substation gate key – 2 types
Substation gate keys are giving to all Field Engineers and to some
Contractors.
Safety locks with key
This is separate lock, unique in nature with key and is an additional
Safety measure during Switching. Safety locks preferably differing from
standard locks of the system shall be used to lock off all switches at points
where the circuit on which work is to be carried out could be energized. The
keys for such locks shall be kept in a key safe, if provided, or in some other
safe place preferably in the possession of the Senior Authorized Person in
charge of the work. See Kahramaa Safety Rules12.3
Locking facility available for Indoor VCB Bus Bar spout shutter
Feeder spout shutter
Earth Switches
Push Button ( Trip / Close )
Panel Door
Interlocking features available Without opening the OCB, the inter locking lever will not be
disengaged.
The Isolating lever entry is possible only when the OCB/VCB in opened
condition.
Closing of Earth Switch is allowed only when the VCB is in Racked
Out/Test position.
Closed condition of Earth Switch will not permit to Rack in UCB into
Service position.
When VCB is in Service position, the Earth Switch closure not allowed.
CO2- Automatic spraying system for 11 KV Switchgear room at PRY
All Primary Substation with 11 KV OCB switchgears are equipped with an
automatic CO2 spraying system in its Switchgear room for the safety of
63
switchgears. Castle – key interlocking system facility is also provided for
personal safety. During the switching operation / any other purposes the field
engineer (SAP) is required to enter this room, then the automatic spraying
mechanism should be blocked temporarily to prevent accidental operation. So
there is an inter locking facility is provided and is designed that, a person will
get the key of switchgear room only after blocking the automatic spraying
feature of CO2. A separate control system is provided for controlling the
operation from a nearby room. After the operation, the Field Engineer should
normalize the system as before.
A data transfer is provided to transfer the operation status of CO2 spraying
system (Automatic / blocked / manual) to NCC and it will gives alarm for the
changes in operation. So the field engineer should inform NCC before doing
any operation.
Confirm SupplyOut Door Substation
Check the humming sound of Local Transformer.
Check the vibration of transformer.
Ammeter Indication from MV panel / Feeder pillar.
Indoor Substation
Check Transformer humming sound & vibration.
Check Meters indication in the switchgear panel
Check Station Battery charger voltage.
Station lighting.
Location MapAn up to date location route map is provided to all Field Engineers for helping
them to find out the Location of Substation.
Substation Labeling
64
Name with voltage level (capital letters) displayed for Primary Substation.
Indoor and Out door Substation:-
Name plate with Planning Number and Name displayed.
If there is no name plate label, then substation can be confirmed by checking
the circuit label.
Circuit IdentificationOnce the substation is identified, then the circuit can be confirmed by the
circuit label and name plate provided on each circuit (Feeders and L/TX)
If circuit label is absent or not legible then the method of confirming the
circuits are:-
1. In Out door substation, Earth Fault Indicator positioning is normally in
left hand side circuit of RMU.
2. Cable size & type as per mimic diagram available at DCC.
3. If all the identification procedures fails, then the Field Engineer can
identify the circuit by switching operation from the remote / adjacent
(Feeding) substation. (First switch off the substation where
identification failed and then close the main switch one by one. Then
identify the circuit from the feeding source by checking the station
supply.)
Pot End & Cap End CablesPot End ( P.E ) - Idly charged cable without connected load.
One ends of the cable is connected to the 11KV Bus and the other end is kept
free ( not terminated but the terminals are made and covered with a pot
termination kit ). Pot End cable is idly charged from one end.
Cap end ( C.E ) - Earthed Cable
One end of the cable is connected to the 11 KV Bus and the other end is kept
free, not terminated but only covered with a cap. The cap End cable is always
in earthed condition from its 11 KV Bus side.
Parallel Operation
Condition for parallel operation of two systems
65
1. frequency,
2. Voltage and
3. Phase sequence should be same
In Kahramaa, QGEWC system, the frequency is same. There is no
interconnecting system. The phase sequence can be correct is there any
mistake. Then the only one depending variable is voltage. So, the voltage
variation between the two sources for paralleling should keep as minimum
within the prescribed limit. So before paralleling, the voltage of the two
sources should be same as possible by adjusting the tap position of tap
changer.
Parallel operation of transformers
The five essential condition to be satisfied are that they should all have the
same.
Polarity
Voltage ratio
Percentage impedance
Phase rotation.
Identical vector diagram and phase displacement.
Active and reactive power transfer
The power transfer from a source to load is always depends on
the total impedance (transformer + line + generator) and the voltage angle /
load angle of the system. Here Reactive power transfer is always depends on
the magnitude of the voltage, that is always higher voltage to low voltage. The
active power transfer is always depending on the load angle / voltage angle
''δ'' irrespective of the magnitude of the voltage. So magnitude of the voltage
is depends on the voltage regulation and in turn depends on the impedance of
the system. Therefore the percentage impedance and voltage phase angle /
load angle are the determining factors of load flow from a source to a load at
remote end. The following factors determine the power transfer and thus the
current through a line.
1. Percentage impedance of transformers
2. Impedance of the line up to the load.
3. Load angle at different load centre or the phasor
displacement of voltage between source end and load end.
66
Bad paralleling
Causes of bad paralleling.
1. Voltage difference at the two systems involved. This will determine
the Reactive power flow and the circulating current.
2. Network impedance up to the point of NOP closure.
3. Power system load angle.
During shut down or for load rearrangement, we have to shift Normal
Opened Point between PRY's. To avoid interruption paralleling is required. In
some paralleling cases, the circulating current increases rapidly and trips the
weaker portion. This is bad paralleling. The main causes of bad paralleling
are, (i) the loads feeding from different sources (load angle)(ii) Percentage
impedance of the transformers are different (iii ) line impedance up to the load
from the sources are different due to the difference in length .
Tap Blocking
At the time of paralleling, the tap position should be normal to all
transformers to avoid the voltage difference. The voltage difference is not
advisable for healthy paralleling. So blocking of tap is required at the tune of
paralleling. Otherwise, the voltage difference cause to produce high
circulating current and this trips the weaker portion.
One another reason for tap blocking is the tap changer is designed to
operate on load condition and not for operating on fault condition. One reason
for blocking the tap during paralleling is to avoid flow of fault current through
the tap changer while tap changing takes place.
Isolation and Earthing for Different Switchgears
Oil Circuit Breaker - Vertical isolation.
67
1. Service position - OCB, connect the Bus bar to the feeder /
transformer circuit when OCB is in closed condition , the live Bus bar is
connected with the feeder / Transformer.
2. Circuit Earth Position ( CK/E )
OCB provides connection facility between feeder / transformer circuit and
earthing system (station earth) .When OCB is in closed condition , the feeder /
transformer circuit is in earthed condition.
3. Bus bar Earth Position
OCB provides connection facility between Bus bar and earthing system. When
it is in closed condition ,the Bus bar is earthed.
Vaccum Circuit Breaker - Horizontal isolation
1. Service position
VCB provided connection facility between Bus bar and Feeder / Transformer
circuit.
2. Isolated / Tested Position
This is Rack / out condition, that means disconnected from the live system.
Earth Switch- Earth switches are provided to earth the feeder /
transformer/Bus bar circuits during shut down.
Progress report on Construction section04-06-2006
Eng: Dharam
Commissioning of new I/D
substation in between 4345 I/D
Qatar Islamic Bank s/s and 9899
After proper back feeding, the
cable between the two s/s is
isolated and earthed as per
68
Qatar international Islamic Bank I/D
11 325 NAJOA CAR PARK – 1- I/D
TAMCO VCB
1 L/TX – 1000 KVA
4345 – I/D –OCB
9899 I/D – VCB.
switching programme. PTW issued
to make and break (2 No)
termination for the new s/s. After
the work cancelled t he PTW. SFT
issued to HV / pressure test for the
cable between the I/D including
new s/s. P/ Test done at new I/D.
and cancelled SFT& confirmed
SW/ position. Live phasing done at
new s/s (11325- I/D).
Commissioned new s/s and local
TX.
05-06-2006
Eng. Dharam
Commissioning of new O/D
substation, Semi extensible 12603
with 1250 KVA transformer,
LABOUR CAMP –O/D in between
9935 I/D and 3828 O/D substation.
RMU is TAMCO ( SF 6 )
Rated voltage -12 KV ,
rated current – 630A, Rated short
time breaking current = 20 KA for 3
Sec
After proper back feeding, the
working portion isolated and
earthed as per switching
programme. Issued SFT to
identify, spike and color phasing
the cable. Cancel SFT & confirm
SW/P. Issued PTW to break and
make (1 No) termination and for
(1 No) straight joint for the new
substation, cancelled PTW. Issued
SFT to HV – PR / Test and
cancelled SFT & confirm SW / P.
P/T done at 9935- I/D. Live
phasing done at 9935 I/D.
Commissioned the new s/s and
after MV Voltage & phase rotation
check commissioned the local TX.
06-06-2006
Eng. Prakash
Choudary
Commissioning of (A 400) feeder at
ABU HAMUR NORTH PRY.
PRY – New SEIMEN'S VCB –
After proper isolation & back
feeding, the cable between the two
I/D is earthed. Issued SFT for
69
German make.
(A400) cable – bx size.
A400 is Connecting to the 10811
SALWA RD SHML I/D ( VCB – EPE
make )
identification, spike and color
phasing the cable, cancel SFT &
confirm SW/P. Issued PTW to
make one No. ST. joint for the
cable A400 between the two I/D's
after the work cancelled PTW.
Issued SFT for P/T and cancelled
SFT confirm SW/ P. After checking
11 KV live phasing, cable A400
commissioned.
07-06-2006
Eng Nizamudeen
Commissioning of 10132 KSW- I/D
in between 4180 (O/ D) and 4160
(O/D) substation.
Commissioned the new I/D and one
local TX (1000 KVA) commissioned
after checking the existing MV
voltage & phase rotation.
Normalized the system by re
establishing NOP.
Shifted the load as per switching
programme. Isolated & Earthed the
working section at both end.
Issued SFT for identification, spike
and colour phasing. Cancelled
SFT & confirmed SW/ position.
Issued PTW for 2 Nos. straight
joint. Cancelled PTW after the
work. Issued SFT for HV P/Test.
Cancelled SFT and confirmed SW/
position. Live phasing done at new
I/D
08-06-2006 Attended Construction office work.
12-06-2006
Eng: Dharam
Replacement of RMU & ADD on
feeder switch at substation 4953
O/D
Old RMU – Merlin Gerin (SF6 )
After load shifting, CME applied at
both ends of point of isolation.
Issued PTW to break and make
the HV termination & to replace the
70
Extensible type.
New RMU - LUCY (SF6 )
Extendible type
Commissioned new RMU with an
additional feeder switch.
old RMU with additional feeder
switch. After the work, cancelled
PTW. Issued SFT , cancelled SFT
& confirm SW/P.11 KV Live
phasing done at 5167 DN- 13 I/D.
13-06-2006
Eng. Nizamudeen
Replacement of Defective RMU at
10313 KR – 6 O/D and to close the
ring with spare cables of 10313 KR-
6 O/D between 9787 KHORE EAST
-5 and 10319 KHORE SOUTH O/D
After MV check and phase rotation
commissioned the s/s and TX's.
After isolation, applied CME at
both ends. SFT issued for colour
phasing. cancelled SFT , PTW
issued to make 3 Nos ( Break and
make ) termination at 10313 O/D
and for I No. Termination at 9787
O/D and also for one ST joint
between 10319 KR-9 O/D and
120313 O/D. Cancelled the PTW.
Issued SFT for HV P/Test,
Cancelled SFT& confirmed the
SW/ P. Live phasing done at
10320 I/D
14-06-2006
Eng: Mr. Imad
11 KV cable diversion between
Naeeja North PRY ( A 200 ) and
( 0534 ) OAP – 8 I/D.
VCB at Naeeja North PRY is
SEIMENS.
Live phasing done at (0534) – I/D
After load shifting and isolation,
applied CME at both ends. SFT
issued for identifying, spike and
colour phasing the cable. SFT
cancelled and PTW issued to
make 2 Nos st.joints for the cable
between Naeeja(A200) and (0534)
OAP-8 I/D Cancelled the PTW.
Issued SFT for HV P/Test,
Cancelled SFT& confirmed the
SW/ P.
71
Progress report on Distribution Protection 18.06.2006
Eng. Shahul
Location- 11456 Villagio -11 I/D
ABB Make numerical relay
Replacement of SPAJ135C by
new high set SPAJ140C for L/TX's
19.06.2006 Pre commissioning test for I/D Attended magnetization test,
72
With technicians
Primary injection, Trip circuit
healthy test for breakers
20.06.2006
Eng. Shahul
1.Abu Hamur North PRY
SIEMENS-SIPROTEC-7SJ61
2.Indoor substations
After fault maintenance- Setting
change for feeders
Relay setting change- as per DCC
advice
21.06.2006
With technician
1671- O/D- Industrial area
Old L/TX is 500 KVA
Setting change for L/TX (1000
KVA)
CT Ratio changing
22.06.2006
With technician
Saliya PRY A200 Tripped, Solkor
operated
Solkor decommissioning attended
25-05.2006 to
28.06.2006
NCC Attended routine activities
01.07.2006
Eng. Murali
Transmission protection
Hamad Medical City PRY
Commissioning
02.07.2006
Eng. Salim
AL SADD PRY Relay maintenance
03.07.2006
Eng. Sherrif
Learning session conducted
04.07.2006 to
06.07.2006
Transmission O&M
73
74
Progress report (O &M)
Date Engineer Work Remark Safety22-05-06 Mr. HAKKIM
Mr. Raju
Replacement of faulty TX4 (Due to oil leak )at (9649) City Centre -1-1/D VCB – TAMCO
1.Replacement of faully TX (Due to oil leak)at an O/D substation.
2.Replacement of transformer(BOFP) by a New TX ( FSFP) at an O/D substation.
VCB – TAMCOE/S – available for each circuit consumer MV panel with ACB available and REF realy provided for MV side protection.Inter trip for HT is provided.Before restoring MV side,Checked MV voltage & Phase rotation
O/D extensible RMU ( oil ) Yorkshire type.
Semi Extensible RMU ( Oil ).Before restoring MV side checked MV voltage & phase rotation.
Operational safety as per switching programme instruction from system control engineer.After proper isolation & Earth, issued PTW for Break and make 11 KV termination.
Operational safety as per SW/ProgrammePTW issued for break and make HT termination to New TX.Operational safety as per SW/ProgrammePTW issued for break and make HT termination to New TX.
Date Engineer Work Remark Safety
75
23.05.06
24.05.06
25.05.06
Mr.Rajivkumar
Mr. Hakim
Mr. Raju (Stand by Duty)
NOP shifting programme to Load DUHAIL PRYsystem operation duty.
1) Rectification of faulty cable by making straight joint& charging the cable.(Cable bitween 1036 city BANK s/s I/D and 5716 O/D )
2)Rectification of faulty cable between ( 2462 ) SH EID BIN MAD No: 3 s/s and an O/D S/S
Fault restorationSFT & PTW issued for an HT Cable between NDC,PRY & an I/D S/S
3nos1/D&5nosO/D Substation visited as a part of NOP shifting. VCB - EPE, TAMCO OCB - south wales RMU -
Tiger oil switchVCB – AGEStraight jiont fault
Third party damage
NDC, PRY visited OCB Panel,Co2 Blasters provided for safety
Operation as per system control ( DCC ) switchihng programme.Confirm supply is important in each operation.
Issue SFT for Identification, Spike& Colour phasing .Issue PTW for one termination & one No: ST joint nearer to 5716 O/D Issue SFT for spike,colour phasing the cable.Issue PTW for straight joint the cable
SFT issued for Identification,Spike&Colour phasing. Issued PTW for 2 Nos stright joint.
76
27.05.06
28.05.06
29.05.06
30.05.06
Mr. Raju
Mr. Mahmood
Mr. Inose
Mr.Rajivkumar
Transformer replacement ( BOFP ) -1000 KVA By new one at 725 I/D
11 KV OHL – Maintenance-Redial circuit from ( 9757 ) new Al Qayan O/D ( Al Khore lnd.Area) Replacing ABS (S-144 ) , (S- 145) & 8 Nos. LA installation at Pole box and PMT
Cable fault Rectification
1.Replacemant of faulty O/D substation (package type) at 4362 O/D – HV P/Test pending
2. SF6 gas pressure Low -Refilling at 5484 O/D Substation ( Lucy SF6 )
Ray Rolle OCB MV Voltage & Phase rotation checked before MV restoration
RMU at O/D s/s is SF6 ( TAMCO )
Ray Roll OCB
HV Pressure Test done for new O/D substation.Live phasing done at 2569 1/D. Before the Live phsing Existing and new phase rotation checked at 2420 O/D.
Checked 11 KV line phasing at 1/D
PTW issued for Break & make 1 No.HT termination to loop the transformer.
After isolation &Earth issued PTW to the competent person ( Before issueing PTW, test OHL,if Dead,Apply Portable Earth )
Issued SFT for colour phasing the HT cableIssued PTW for making 2 No Stright joint for the faulty cable.
Issued SFT for HV P/Test for the new O/D subatation.Issued PTW for refilling SF6 Gas at 5484 O/D substation.Issued PTW for MV termination.
77
31.05.06
01.06.06
Mr. Hakkim 1.Fault rectification of an HT cable between SH . ABDULLA FARM-1 1/D and pole Box Pole Box termination faulty.
2.Fault restorationKHORE A300- tripped at an 1/D substation, the OHL lodial line ( with two TEE off -circuit ) Total supply failure.Indication - stand by E/F flag ON at PRY and alarm initiated at NCC for both TX
ABU HAMUR WORK SHOP VISIT
2) Fault restoration Industrial area 1671- MI 1/D Substation, one TX ( 500KVA ) tripped on over loadTX -replaced by ( 1000 KV )
Over head line involved
1/D – E/F relay operated EFI flagged at one pole Box(Radial TEE-off circuit )
Hands on training on different types of switches ( Oil & SF6 ), VCB & OCB'S
Indication R&B O/C
Issued SFT for colour phasing the cable.Tested the OHL, found Dead then applied the protable Earth.Issued PTW for one No. Jumper connection and for raise the Pole box. Noticed all indication and after proper petrolling found that the earth wire(1 span) snapped in the radial TEE-off circuit.Isolated & earthed the faulty portion. Then charged the healthy circuit from the 1/ D (All Relays and indications resetted.Kept the relay setting TSM minimum for test charging.).PTW issued for fault rectification.Issued PTWfor transformer replacement.Informed protection department to change the relay settings.
78
79
80
81
82