sesimic papers

Upload: awais-jalali

Post on 03-Apr-2018

223 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/28/2019 Sesimic Papers

    1/7

    Pakistan Journal of Science (Vol. 63 No. 2 June, 2011)

    84

    NEW SEISMIC PARAMETERS FOR BUILDING CODE OF PAKISTAN AND THEIR

    EFFECT ON EXISTING REINFORCED CONCRETE BUILDINGS: A CASE STUDY

    M. B. Sharif, A. U. Qazi, M.Ilyas*, N. Mohsin*

    Department of Civil Engineering, University of Engineering and Technology, Lahore.*

    Strucrual Division Nespak House, LahoreCorresponding author e-mail:[email protected]

    ABSTRACT:The large scale devastation caused by the earthquake of October 08, 2005 in NorthernPakistan and Azad Jammu and Kashmir has raised several questions on the adequacy of the present

    design and construction practice in the country. Realizing the gravity of the situation, the Government

    of Pakistan appointed a Committee of technical experts and Government Officials to supervise and

    provide guidance for revision/updating of Building Code of Pakistan, to suggest modifications to the

    present codes of practice and to particularly incorporate the recommendations for earthquake resistant

    design of buildings. Therefore, It is important to check the adequacy of existing structures especially in

    high seismic risk zones according to revised seismic parameters. The National Insurance Complex

    Limited (NICL) Building, Jinnah Avenue, Blue Area Islamabad is selected for study. It was

    constructed in 1994. In this research seismic analysis has been performed for National Insurance

    Complex Limited (NICL) building. These analyses include linear static analysis, response spectrumanalysis, non-linear static analysis and linear time history analysis which are performed using ETABS.

    Different analysis approaches have been used to carry out the lateral analysis on the basis of BCOP-

    2007 and the time histroy of October 8, 2005 earthquake. The study revealed that base shear is

    increased by 7% due to the change in the seismic zoning for the current location of the building. It is

    concluded that the change in seismic zoning has not seriously threatened the stability of existing

    buildings. The buildings which are then designed according to some recogonized building codes when

    analyzed according to BCP-2007 should fall safe. However failure may be expected incase of the

    building is not preperly designed or poorly constructed.

    Key words: Seismic zone, base shear, drift.

    INTRODUCTION

    The large scale devastation caused by October

    08, 2005 earthquake in Northern Pakistan and Azad

    Jammu and Kashmir has raised several questions on the

    adequacy of the present design and construction practice

    in the country(Ilyas, M & Rizwan,M. 2006). Realizing

    the gravity of the situation, the Government of Pakistan

    appointed a Committee of technical experts and

    Government Officials to supervise and provide guidance

    for revision/updating of Building Code of Pakistan, to

    suggest modifications to the present codes of practice and

    to incorporate the recommendations for earthquake

    resistant design of buildings.This committee resulted in

    the development of new building code of Pakistan which

    is abbreviated as BCOP-2007.It is expected that thestructures constructed under any established earlier

    building codes may become nonconforming in relation to

    the revised seismic parameters present Building Code of

    Pakistan 2007. Proper design and detailing considering

    realistic seismic parameters with good construction

    practices will reduce the devastation to a much lesser

    extent by reducing causalities.

    It is essentially important to check the adequacy

    of existing structures specially in high seismic risk zones

    according to revised seismic parameters. The mainpurpose of the proposed research work is to review the

    design of existing reinforced concrete building

    considering revised seismic parameters and to ascertain

    the adequacy for resistance against adverse effects of

    earthquake induced forces. Moreover, to suggest remedy

    for different structural components in order to ensure

    their safety and stability. An urgent action is needed to

    avoid failure of vulnerable structures.

    There is a lack of awareness for seismic

    protection in many parts of the country. In high seismic

    risk zones, time history analysis for high rise structures

    must be carried out to depict actual behavior. The

    compliance of the specified earthquake resistant designand construction practice must be ensured through

    appropriate legal, administrative and technical control.

    New buildings must be earthquake resistant in order to

    prevent constant addition to existing vulnerable structures

    that are already seriously threatened.

    Gulten and Calim (2003) studied the torsionally

    unbanlanced multistorey RC structures. They found that

    by introducing 5% eccentricity an increase of about 10%

    mailto:[email protected]:[email protected]
  • 7/28/2019 Sesimic Papers

    2/7

    Pakistan Journal of Science (Vol. 63 No. 2 June, 2011)

    85

    bending moments in the columns and beams located at

    critical locations, occurred.

    Erduran and Yakut (2004) studied the seismic

    performance for an RC frame system. According to them

    detailed assessment procedures generally require a full

    blown seismic analysis of the building to determine the

    forces and deformations experienced by its components

    under a presumed level of earthquake intensity. A

    number of widely used such procedures (FEMA 356,

    ATC-40 and EUROCODE 8) compare these demands

    with the recommended values of member capacities

    varying with the level of the performance objectives

    employed.

    Yun et. al. (2006) presented a procedure for

    analyzing the building which was based on non linear and

    reliablilty theory. This procedure gives simplified method

    for the analysis of steel moment frames with fair

    accuracy specially during the non linear analysis. Hugo

    (2003) has devised various principles for engineers and

    architects for the seismic design of the buildings. It can

    be concluded from this report that any building which isdesigned using the principles mentioned in the report of

    the author will perform well during an earthquake.

    Young et al. (1985) developed the damaged

    model for reinforced concrete. They investigated the full

    capacity of member which may be used during an

    earthquake. Ahsan and Saif (2008) investigated the

    failure due to the kashmir hazara earthquake (2005) and

    concluded that although knowledgeable and competent

    structural engineers are avaialble in Pakistan but the

    execution of construction with respect to the design is

    very important. They also empahsized that the

    recommendations suggested by them are very significant

    for new construction. This will help in the reduction ofproperty loss and human lives.

    Building description: The National Insurance Complex

    Limited (NICL) Building, Jinnah Avenue, Blue Area

    Islamabad is selected for study. It was constructed in

    1994. The building mainly comprises of two blocks,

    Tower block and low-rise block which are separated from

    each other by an expansion joint. The Tower block is

    mainly used for offices and the low-rise block is used for

    parking of vehicles. Tower block has sixteen floors with

    two basements and low-rise block has two basements and

    two floors. After the earthquake of October 08, 2005

    some cracking was observed in the masonry walls which

    are non-structural in nature and does not impair strengthof the structural system. Some cracks were also observed

    in the construction joints of parapet wall and retaining

    wall which do not cause structural instability. The

    material properties considered in the design were verified

    using non destructive methods.

    Structural system: The structural system for the NICL

    building is an essentially space frame providing support

    for gravity loads and resistance to lateral load is mostly

    provided by concrete shear walls and lift-well walls. Slab

    system consists of two-way slab with shallow wide Ribs

    acting as column strips along the column centre lines.

    Flexural effective width of the slab also acts as a wide

    shallow beam to transfer gravity and other unbalanced

    forces to the columns and shear walls. Reinforcement has

    been laid out as for two-way slab system with

    concentration of reinforcement in the column strips.

    Concrete shear walls and lift-well walls provide lateral

    resistance in two orthogonal directions. Structural

    members (columns shear walls and lift-well walls) resist

    the total seismic lateral loads in proportion to their

    relative rigidities with shear walls resisting almost 76

    percent of total seismic base shear loads due to their

    greater stiffness in the two principal directions. Shear

    walls at the periphery of the building are located at each

    corner of the building whereas lift-well walls are located

    eccentrically with respect to the building center.

    Foundation system of the Tower Block building employs

    cast-in-place piles with thick pile caps providing load

    transfer mechanism from columns and shear walls to thedeep foundations. Low-rise block uses raft foundation.

    Seismic parameters: All structures and their components

    are analyzed to determine their adequacy to withstand

    lateral forces caused by seismic loads. The original

    design of the building was based on BCP-1986 with

    following seismic parameters:

    Z. = Seismic Zone factor = 0.30

    I. = Importance factor = = 1.00

    Ct. = Numerical coefficient = 0.03

    S. = Soil factor = 1.50

    Rw. = Numerical Coefficient = 12.0

    Above parameters have been revised in the Building

    Code of Pakistan 2007. New seismic provisions, which

    are based on revised seismic zoning map of Pakistan

    which is shown in Figure-1.

    Figure-1 Seismic zoning of Pakistan (BCOP-2007)

    Few parameters which have been revised by the

    BCOP-2007 are shown below.

  • 7/28/2019 Sesimic Papers

    3/7

    Pakistan Journal of Science (Vol. 63 No. 2 June, 2011)

    86

    Z. = Seismic Zone factor = 0.20

    I. = Importance factor = = 1.00

    Cv.= Seismic coefficient = 0.32

    Ca. = Seismic coefficient = 0.28

    R. = Numerical Coefficient = 5.50

    S. = Soil profile type = = SD

    Material properties: Reinforcement yield strengthconsidered as per original design criteria of National

    Insurance Complex Limited building is 60,000 psi.

    Following concrete strengths taken from original design

    criteria:

    Columns 5000 psi

    Shear walls 5000 psi

    Slab 2500 psi

    Beam 2500 psi

    Foundation 2500 psi

    Dead loads: Dead loads are the vertical loads due to the

    weight of all permanent structural and non-structural

    components of a building, such as walls, built-in and

    moveable partitions, floors, roofs and finishes includingall other permanent construction. Following loads are

    used in analysis as taken from original design criteria:

    Finishes 30 psf

    Partitions 20 psf

    Roofing 10 psf

    Plaster 10 psf

    Live loads: Live loads include loads due to intended use

    and occupancy of an area, personnel, moveable

    equipments, lateral earth pressures, vehicle and impact

    loadings. For National Insurance Complex limited

    building, floor live loads are taken as per occupancy and

    intended use requirements, from original design criteria

    as given below.

    Parking Floor 100 psf

    Ground Floor 100 psf

    Mezzanine Floor 60 psf

    First Floor 60 psf

    Typical Floor 60 psf

    Roof Floor 30 psf

    Wind loads: Lateral loads due to wind were imposed on

    the building using wind velocity of 80 mph and Exposure

    Category-C as per BCP-2007. Wind loads were combined

    with other applicable loads as per BCP-2007 load

    combinations.

    Analytical modeling: The analysis for the study is

    carried out using Extended Three Dimensional Analysis

    of Building System ETABS Nonlinear Version. The

    building is modeled in 3-D with spatial distribution of

    masses and stiffness of the structural system. Tower

    Block of the building is modeled separately as there is 1inch wide expansion joint separating the two blocks.

    Superstructure is modeled by using discrete frame

    elements for columns, beams, shell elements, slabs, shear

    walls and other concrete lift-well walls. Concrete

    dimensions of frame elements were based on sizes of the

    structural members provided in the structural drawings.

    Materials properties used in the review are as provided in

    the original design criteria of the building. In order to

    carry out the study different types of computer models

    are prepared in software ETABS which are given in

    Table-1.

    Table-1 Types of analysis and their nomenclature

    Model Description

    LS-A 86 Building is modeled with 3D space frame, with un-cracked sections considering provisions of BCP 1986.

    LS-B 86 3D interior frame of building is modeled with cracked sections considering provisions of BCP 1986.

    LS-A 07 Building is modeled with 3D space frame, with un-cracked sections considering provisions of BCP 2007.

    LS-B 07 3D interior frame of building is modeled with cracked sections considering provisions of BCP 2007.

    RS 86 Building is modeled with 3D space frame, shear walls, lift wells and slab system considering provisions of BCP 1986.

    RS 07 Building is modeled with 3D space frame, shear walls, lift wells and slab system considering provisions of BCP 2007.

    NLS 86 3D interior frame of building is modeled with beam and column elements considering provisions of BCP 1986.

    NLS 07 3D interior frame of building is modeled with beam and column elements considering provisions of BCP 2007.

    NLS 01 3D interior frame of building is modeled with beam and column elements.

    NLS 02 3D exterior frame of building is modeled with beams, columns and shear wall elements.

    TH 01 Building is modeled with 3D space frame considering actual time history record.

    TH 02 Building is modeled with 3D space frame considering scaled time history record.

    Discussion on results: The different analysis options

    which are shown in Table-1 were analyzed on separate

    computer model based on the parameters which have also

    been mentioned in the previous sections. The main

    considerations were given on the story drifts and drift

    ratios because the divergence of these values during

    different analysis options can comment on the status of

    the structure.

    The linear static analysis and Response spectra

    analysis based on BCOP-86 and BCOP-07 is shown in

    figure -2

  • 7/28/2019 Sesimic Papers

    4/7

    Pakistan Journal of Science (Vol. 63 No. 2 June, 2011)

    87

    Figure-2 Lateral Displacements and Storey Drift Ratios for LS & RS Analysis

    The linear static analysis of building due to

    revised seismic zoning of Pakistan increases the base

    shear by 7%. Due to the increase in base shear maximum

    lateral displacement at top of building increases by 32%.It was also observed that the maximum storey drift for

    eigth storey increases to 0.42 The structural system of

    building shows unsymmetrical distribution of stiffness

    which result in additional torsion, due to this reason the

    lateral displacements for elastic response spectrum

    analysis are on higher side to that of linear static analysis.

    It was observed that the maximum storey drift for storey

    number seven is having a storey drift ratio of 0.6. Shear

    wall and lift wells attract 76% of total base shear and

    24% of total base shear is taken by reinforced concreteframe.

    The next set of analysis was carried out for non

    linear behavior of building. The behaviour of the building

    for lateral displacements and storey drift ratios is shown

    in Figure-3.

    Figure-3 Lateral Displacements and Storey Drift Ratios for NL and LS analysis

    Non-linear static analysis of building has shown

    that maximum storey drift is experienced by storey

    number three with storey drift ratio of 1.1 which is due to

    the presence of mezzanine floor in the building. Plastic

    hinges are formed at beams only showing strong column

    weak beam structure. For revised seismic parameters the

    building remains in state of immediate occupancy. Push

    over analysis reveal that the beam at third floor will yield

    to collapse at base shear of 0.547 times the weight of

    structure.

    The results of NLS-01 and NLS-02 is shown in

    figure -4 and 5. The two analysis differ in a sense that

    NLS-01 was without considering shear wall and NLS-02

    was with shear wall.

    The later displacement for both the cases remains

    the same, however the collapse load occur for beams at

    story-3 at 0.345W (W= Total weight of structure)

    where as in case of NLS-02 the collapse load occurs at

    fourth storey at 0.547W as eminent from figure 4 and 5 as

    well.

  • 7/28/2019 Sesimic Papers

    5/7

    Pakistan Journal of Science (Vol. 63 No. 2 June, 2011)

    88

    Figure-4 Lateral Displacements and Storey Drift Ratios for NLS-01

    Figure-5 Lateral Displacements and Storey Drift Ratios for NLS-02

    Time history record of October 08, 2005 at

    Islamabad is collected and TH-01 is prepared in ETABS.

    Time history record is shown in Figure -6. Time historyanalysis of NICL building is carried out using ETABS

    and buildings response is studied.

    TH-01 analysis of NICL building reveals that the

    structure suffered maximum displacement at roof with

    magnitude of 3.40 inches at time of 71 second and global

    drift of 0.13%. At this displacement magnitude and

    global drift ratio the structure should not suffer any crack

    in non structural walls whereas NICL building actually

    suffered cracks in its non structural walls.

    Further more the floor acceleration at roof after

    TH-01 analysis comes to be 0.033g. At this magnitude of

    floor displacement the occupants should not experience

    any sever shaking whereas the occupants at top floorexperienced violent shaking. It means that the time

    history record is probably scaled down. The displacement

    response of NICL building at roof is shown in figure-7

    and acceleration response is shown in figure-8.

    As the time history record at Nilor for October

    08, 2005 earthquake in Kashmir and Hazara seems to be

    scaled down so TH-02 is prepared in ETABS. In order to

    perform time history analysis of NICL building for scaled

    up time history, Original E-W component is scaled up to

    achieve the value of global drift of 1.0% and to the reach

    peak acceleration of 0.2g to make it compatible with

    seismic zone factor of seismic zone 2b. The Scaled up E-W Component of October 08, 2005 earthquake at Nilor is

    shown in figure-9.

    Figure -6 E-W Component of Kashmir Hazara

    Earthquake at Nilore(WAPDA, LAHORE)

  • 7/28/2019 Sesimic Papers

    6/7

    Pakistan Journal of Science (Vol. 63 No. 2 June, 2011)

    89

    Figure-7 Displacement Response of NICL building at

    Roof for E-W Component

    Figure -8 Acceleration Response of NICL building at

    Roof for E-W Component

    Figure -9 Scaled up E-W Component of Kashmir

    Hazara Earthquake at Nilore (WAPDA,

    LAHORE)

    TH-02 analysis of NICL building reveals that the

    structure suffered maximum displacement of 30.76

    inches at time of 71 second and global drift of 1.13%.

    The displacement response at roof of NICL building is

    shown in figure 4.21. Further more the peak acceleration

    observed is 0.296g at roof. Acceleration response of

    NICL building is shown in figure -10.

    Figure -10: Displacement Response of NICL Building

    at Roof for E-W Component.

    Conclusions: It is concluded that the change in seismic

    zoning has not threatened the stability of NICL building

    which is because of its proper design, detailing and

    construction. According to the previous building code of

    Pakistan, it is concluded that the buildings which are

    designed according to previous building codes when

    analyzed according to present building code of Pakistan

    with revised parameters should satisfy seismicrequirements. However, if it is not the case then they

    were not either properly designed or were poorly

    constructed.

    REFERENCES

    Applied Technology Council (ATC), Seismic

    Evaluation and Retrofit of Concrete Buildings,

    Vol.1. Report No. SSC 96-01 (ATC-40): (1996)

    Building code of Pakistan,section-2, seismic hazard

    studies, (1986).

    Building Code of Pakistan. Section 5. Seismic design

    parameters:(2007).Erduran, E. and A. Yakut. Drift based damage functions

    for Reinforced Concrete Columns. Computers

    and Structures. Vol. No. 82/2-3: 121-130 (2004)

    Federal Emergecny Management Agency. NEHRP

    Guidelines for Seismic Rehabilitation of

    Buildings, FEMA 273. (1997)

    Gulten G. F. and G. Calim. A Comparative Study of

    Torsionally Unbalanced Multi-Story Structures

  • 7/28/2019 Sesimic Papers

    7/7

    Pakistan Journal of Science (Vol. 63 No. 2 June, 2011)

    90

    Under Seismic Loading, Istanbul Technical

    University, Civil Engineering Department: 11

    19 (2003).

    Hugo, B. Seismic Conceptual Design of Buildings, Basic

    principles for engineers, architects, building

    owners and authorities, Urgent Action Needed.

    (2003) http://www. preventionweb. net/english/

    professional/ publications/ v.php?id=687

    accessed on 15-02-11.

    Park Y. and F. Alfredo H.S. Ang. Mechanistic seismic

    damage model for reinforced concrete. Journal

    of Structural Engineering. Vol. 111(4):722-39

    (1985).

    Sheikh Ahsan M. and M. Hussain Saif. Pakistan

    Earhquake reconstruction and recovery program:

    Structural Engineering consideration. (2008)

    www.structuremag.org/article.aspx?articleID=7

    93 accessed in January 2011.

    Yun, S.; R. Hamburger; C.C. Allin and F. D.A. Seismic

    Performance evaluation for steel moment

    Frames. Postdoctoral Research Associate of

    Civil and Environmental Engineering.

    University of Illinois, 205N. Mathews Ave., IL

    61801, (2006).

    Ilyas, M. and M. Rizwan. Devastating effects of

    Kashmir-Hazara Earthquake. Proceeding of The

    International Conference and Expo on Safe and

    Quality Building in Asia Review of Practices .

    March 28-29, Lahore, Pakistan. (2006)

    http://www.preventionweb.net/english/professional/publications/v.php?id=687http://www.preventionweb.net/english/professional/publications/v.php?id=687http://www.structuremag.org/article.aspx?articleID=793http://www.structuremag.org/article.aspx?articleID=793http://www.structuremag.org/article.aspx?articleID=793http://www.structuremag.org/article.aspx?articleID=793http://www.preventionweb.net/english/professional/publications/v.php?id=687http://www.preventionweb.net/english/professional/publications/v.php?id=687