service manual no. obh489 utilized · service manual contents 1. ... indoor unit service manual...
TRANSCRIPT
SERVICE MANUAL
CONTENTS
1. TECHNICAL CHANGES ····································32. PART NAMES AND FUNCTIONS······················33. SPECIFICATION·················································44. NOISE CRITERIA CURVES·······························65. OUTLINES AND DIMENSIONS ·························76. WIRING DIAGRAM ············································87. REFRIGERANT SYSTEM DIAGRAM··············108. PERFORMANCE CURVES ······························119. ACTUATOR CONTROL····································22
10. SERVICE FUNCTIONS·····································2311. TROUBLESHOOTING······································2312. DISASSEMBLY INSTRUCTIONS·····················39
Wireless typeModels
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
MUZ-FD25VA -MUZ-FD25VAH -MUZ-FD35VA -MUZ-FD35VAH - E1
E1
E1
E1
NOTE:RoHS compliant products have <G> mark on the spec name plate.
HFCutilized
R410A
No. OBH489OUTDOOR UNIT
Indoor unit service manualMSZ-FD•VA Series (OBH488)
PARTS CATALOG (OBB489)
OBH489--1.qxp 07.8.9 11:53 AM Page 1
2
OBH489--1.qxp 07.8.9 11:53 AM Page 2
3
TECHNICAL CHANGES1
PART NAMES AND FUNCTIONS2
ACCESSORIES
Air outlet
Drain outlet
Piping
Drain hose
Air inlet
MUZ-FD25/35VA
1 Drain socket 1
MUZ-FD25VAMUZ-FD25VAHMUZ-FD35VAMUZ-FD35VAH
MUZ-FD25VA -MUZ-FD25VAH -MUZ-FD35VA -MUZ-FD35VAH - E1
E1
E1
E1
1.New model
OBH489--1.qxp 07.8.21 9:54 AM Page 3
4
3 SPECIFICATION
3.2 (1.5-5.5)
MUZ-FD25VA
3.5 (1.1-4.0)4.0 (1.5-6.3)
8508653.94.095944.0
4.124.62
3.313.33
4.0 (1.3-7.7)
8358503.83.996953.9
4.194.71
3.213.23
Power outlet
Power input ✽1 (Total)
Running current ✽1 (Total)
Power factor ✽1 (Total)
Starting current ✽1 (Total)
kW
A
W
A
%
A
W
A
A
mmkgr/h
K /h
dB(A)
rpm
kg
Compressor
Spe
cial
rem
arks
Coefficient of performance(C.O.P) ✽1(Total)
Ele
ctric
al d
ata
MUZ-FD35VAMUZ-FD25VAH MUZ-FD35VAH
Single phase230 V, 50 Hz
15
SNB130FGBH900
RC0J50-EA
800o550o28536
2,016/1,776/1,386
870/770/6103
1.15NEO22
Power supply
Outdoor model
Capacity Rated frequency(Min.-Max.)CoolingHeating
CoolingHeatingCoolingHeatingCoolingHeating
CoolingHeating
CoolingHeating
CoolingHeating
CoolingCoolingHeatingCoolingHeatingCoolingHeating
DehumidificationAir flow ✽1 (High/Low) (High/Med./Low)
Sound level ✽1
Fan speed (High/Low) (High/Med./Low)Fan speed regulatorRefrigerant filling capacity(R410A)Refrigeration oil (Model)
Dimensions WOHODWeight
Fan motor
Model
Current ✽1
ModelOutput
Current ✽1
2.5 (1.1-3.5)
4856102.42.988912.9
5.155.25
1.882.30
0.270.30
1.41,872/1,086
46
810/490
3.2 (1.5-6.3)
0.320.35
2.01,872/1,086
4750
810/490
3.5(0.8-4.0)
NOTE : Test conditions are based on ISO 5151Cooling : Indoor Dry-bulb temperature 27 : Wet-bulb temperature 19 :
Outdoor Dry-bulb temperature 35 :Heating : Indoor Dry-bulb temperature 20 :
Outdoor Dry-bulb temperature 7 : Wet-bulb temperature 6 :Refrigerant piping length (one way): 5 m✽1 Measured under rated operating frequency
OBH489--1.qxp 07.8.9 11:53 AM Page 4
5
ModelItem
Current
transformer
Smoothing capacitor
Diode module
Fuse
Defrost heater
Intelligent power module
Expansion valve coil
Reactor
Current-detecting
resistor
Current-limiting PTC thermistor
Terminal block
Relay
R.V.coil
Heater protector
IGBT
MUZ-FD25VA
(CT)
(CT761, CT781)
(C61, C62, C63)
(DB61)
(DB65)
(F61)
(F701,F801,F901)
(H)
(IPM)
(LEV)
(L61)
(R61,R62)
(R825)
(R937,R938,R939)
(PTC64,PTC65)
(TB1,TB2)
(X63)
(X64)
(X66)
(21S4)
(26H)
(TR821)
MUZ-FD25VAH MUZ-FD35VA MUZ-FD35VAH
—
—
—
230 V 130 W
3 A 250 V
Open 45 :
—
—
—
230 V 130 W
3 A 250 V
Open 45 :
20 A
15 A
620 + 420 V
15 A 600 V
25 A 600 V
T20AL250V
T3.15AL250V
20 A 600 V
DC 12 V
23.0 mH
180 m" 5 W (2 elements)
25 m" 5 W
430 m" 2 W
33 "
3P
3 A 250 V
20 A 250 V
AC 220 - 240 V
30 A 600 V
Specifications and rating conditions of main electric parts
OBH489--1.qxp 07.8.9 1:31 PM Page 5
6
4 NOISE CRITERIA CURVES
90
80
70
60
50
40
30
20
1063 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LE
VE
L, d
B r
e 0.
0002
MIC
RO
BA
R
BAND CENTER FREQUENCIES, Hz
COOLING
FUNCTION SPL(dB(A)) LINE
HEATING46
NC-10
MUZ-FD25VAMUZ-FD25VAH
90
80
70
60
50
40
30
20
1063 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LE
VE
L, d
B r
e 0.
0002
MIC
RO
BA
R
BAND CENTER FREQUENCIES, Hz
COOLING
FUNCTION SPL(dB(A)) LINE
HEATING
47
50
Test conditions Cooling : Dry-bulb temperature 35 : Heating : Dry-bulb temperature 7 : Wet-bulb temperature 6 :
OUTDOOR UNIT
MICROPHONE
1 m
NC-10
MUZ-FD35VAMUZ-FD35VAH
OBH489--1.qxp 07.8.9 11:53 AM Page 6
7
OUTLINES AND DIMENSIONS5
Unit: mmMUZ-FD25VAMUZ-FD25VAHMUZ-FD35VAMUZ-FD35VAH
10
69
800
302.5
500 Bolt pitch for installation
150
22.3
Handle
550
280
164.
5
99.5 170.5
23Service panel
Service port
285
344.
5 44
400Air in
Air out
Air in
17.5
Bol
t pitc
h fo
rin
stal
latio
n30
4~32
5
40
Liquid refrigerant pipe jointRefrigerant pipe (flared) [6.35
Gas refrigerant pipe jointRefrigerant pipe (flared) [9.52
43-
35-
2 holes 10 X 21
Drain hole [33 (FD25/35VAH)
REQUIRED SPACEBasically open 100 mm or more without any obstruction in front and on both sides of the unit.
350 mm or more200 mm or more
100 mm or more
100 mm or more
Open two sides of left, right, or rear side.
Drain hole [42 (FD25/35VA)
OBH489--1.qxp 07.8.9 11:53 AM Page 7
8
6 WIRING DIAGRAM
MUZ-FD25VAMUZ-FD35VA
OBH489--1.qxp 07.8.9 11:53 AM Page 8
9
MUZ-FD25VAHMUZ-FD35VAH
OBH489--1.qxp 07.8.9 11:53 AM Page 9
10
7 REFRIGERANT SYSTEM DIAGRAM
Unit:mmMUZ-FD25VAMUZ-FD25VAHMUZ-FD35VAMUZ-FD35VAH
Outdoorheatexchanger
Flared connection
DefrostthermistorRT61
DischargetemperaturethermistorRT62
Flared connection
Stop valve(with strainar)
Stop valve(with service port)
Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe [9.52(with heat insulator)
Refrigerant pipe [6.35(with heat insulator)
R.V. coilheating ONcooling OFF
Strainer#100
Capillary tube[3.0✕[1.8✕600(✕2)
LEV
Ambient temperature thermistorRT65
Muffler
Capillary tube[3.0✕[2.0✕240
Outdoor heatexchangertemperature thermistorRT68Muffler
ADDITIONAL REFRIGERANT CHARGE (R410A:g)
Outdoor unit
precharged 14m7m6m5m 11mModel
Refrigerant piping length (one way)
8m 9m 10m 12m 13m 15m 20m
270000 18090 120 150 210 240 300 4501,150
MUZ-FD25VA
MUZ-FD25VAH
MUZ-FD35VA
MUZ-FD35VAH
Max. length A
Max. Heightdifference
B
Indoorunit
Outdoor unit
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
Max. length
A
20
Max. Height difference
B
12
Model
Gas
9.52
Liquid
6.35
Piping size O.D : mmRefrigerant piping : m
MUZ-FD25VAMUZ-FD25VAHMUZ-FD35VAMUZ-FD35VAH
Calculation : Xg=30 g/m ✕ (Refrigerant piping length (m)–7)
NOTE: Refrigerant piping exceeding 7 m requires additional refrigerant charge according to the calculation.
OBH489--1.qxp 07.8.9 11:53 AM Page 10
11
8 PERFORMANCE CURVES
The standard specifications apply only to the operation of the air conditioner under normal conditions. Since operating condi-tions vary according to the areas where these units are installed, the following information has been provided to clarify theoperating characteristics of the air conditioner under the conditions indicated by the performance curve.(1) GUARANTEED VOLTAGE
198 ~ 264 V, 50 Hz(2) AIR FLOW
Air flow should be set at MAX.(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature : °C WB(2) Indoor outlet air wet-bulb temperature : °C WB(3) Outdoor intake air dry-bulb temperature : °C DB(4) Total input: W(5) Indoor intake air dry-bulb temperature : °C DB(6) Outdoor intake air wet-bulb temperature : °C WB(7) Total input : WIndoor air wet/dry-bulb temperature difference on the left side of the following chart shows the difference between theindoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your reference at service.
}}
Cooling
Heating
How to measure the indoor air wet-bulb / dry-bulb temperature difference1. Attach at least 2 sets of wet and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets
of wet and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where airspeed is high.
2. Attach at least 2 sets of wet and dry-bulb thermometers to the outdoor air intake.Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.4. Open windows and doors of room.5. Press the EMERGENCY OPERATION switch once (twice) to start the EMERGENCY COOL (HEAT) MODE.6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.7. 10 minutes later, measure temperature again and check that the temperature does not change.
MUZ-FD25VA MUZ-FD35VAMUZ-FD25VAH MUZ-FD35VAH
INDOOR UNIT OUTDOOR UNIT
Wet and dry-bulbthermometers
Wet and dry-bulbthermometers
Cooling capacity
0.9
1.0
1.1
1.2
1.3
1.4
1.5
-10 -5 0 5 10 15 20 25 30 35 40 45
Outdoor intake air Dry-bulb temperature(:)
Cap
acit
y co
rrec
tio
n f
acto
rs
26
24
2018
22
Indoor intake air Wet-bulbtemperature(:)
MU
Z-F
D35
VA
MU
Z-F
D35
VA
Hat
Rat
ed fr
eque
ncy
at R
ated
freq
uenc
y
Ind
oo
r ai
r W
et-b
ulb
tem
per
atu
red
iffe
ren
ce (:
)M
UZ
-FD
25V
AM
UZ
-FD
25V
AH
6.5
6.0
5.5
5.1
4.6
4.1
3.7
9.1
8.4
7.7
7.0
6.3
5.7
5.1
8-1. Capacity and input curves
OBH489--1.qxp 07.8.9 3:33 PM Page 11
NOTE:The above broken lines are for the heating operation without any frost and defrost operation.
12
0.8
0.9
1.0
1.1
1.2
1.3
-10 -5 0 5 10 15 20 25 30 35 40 45
Outdoor intake air Dry-bulb temperature (:)
Inp
ut
corr
ecti
on
fac
tors
26 24 222018
Indoor intake air Wet-bulbtemperature(:)
at R
ated
freq
uenc
y
MU
Z-F
D35
VA
MU
Z-F
D35
VA
H
at R
ated
freq
uenc
y
Ind
oo
r ai
r W
et-b
ulb
tem
per
atu
red
iffe
ren
ce (:
)
MU
Z-F
D25
VA
MU
Z-F
D25
VA
H
5.5
5.1
4.6
4.1
3.7
3.3
7.7
7.0
6.3
5.7
5.1
4.5
at R
ated
freq
uenc
y
MU
Z-F
D35
VA
MU
Z-F
D35
VA
H
at R
ated
freq
uenc
y
Ind
oo
r ai
r D
ry-b
ulb
tem
per
atu
red
iffe
ren
ce (:
)
MU
Z-F
D25
VA
MU
Z-F
D25
VA
H
17.3
16.0
14.6
13.3
12.0
10.6
9.3
8.0
6.7
5.3
20.9
19.3
17.7
16.1
14.5
12.9
11.3
9.7
8.0
6.4
Outdoor intake air Wet-bulb temperature (:) -20 -15 -10 -5 0 5 10 15
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3Heating capacity
Cap
acit
y co
rrec
tio
n f
acto
r
152026
Indoor intake air D
ry-bulb temperature (:)
at R
ated
freq
uenc
y
MU
Z-F
D35
VA
MU
Z-F
D35
VA
H
at R
ated
freq
uenc
y
Ind
oo
r ai
r D
ry-b
ulb
tem
per
atu
red
iffe
ren
ce (:
)
MU
Z-F
D25
VA
MU
Z-F
D25
VA
H
17.3
16.0
14.6
13.3
12.0
10.6
9.3
8.0
6.7
5.3
20.9
19.3
17.7
16.1
14.5
12.9
11.3
9.7
8.0
6.4
Outdoor intake air Wet-bulb temperature (:) -20 -15 -10 -5 0 5 10 15
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3Total input(heating)
Inp
ut
corr
ecti
on
fac
tor
152026
Indoor intake air Dry-bulb temperature (:)
Total input (cooling)
OBH489--1.qxp 07.8.9 11:53 AM Page 12
13
Correction of Cooling input
Inpu
t cor
rect
ion
fact
ors
The operational frequency of compressor
Correction of Cooling capacity
Cap
acity
cor
rect
ion
fact
ors
The operational frequency of compressor
Correction of Cooling capacity
Cap
acity
cor
rect
ion
fact
ors
The operational frequency of compressor
Correction of Cooling input
Inpu
t cor
rect
ion
fact
ors
The operational frequency of compressor
Correction of Heating input
The operational frequency of compressor
Correction of Heating capacity
Cap
acity
cor
rect
ion
fact
ors
The operational frequency of compressor
Correction of Heating capacityC
apac
ity c
orre
ctio
n fa
ctor
s
The operational frequency of compressorIn
put c
orre
ctio
n fa
ctor
s
MUZ-FD25VAHMUZ-FD25VA
MUZ-FD35VA
0 50 100 150(Hz)0.0
0.5
1.0
1.5
0 50 100 150(Hz)0.0
1.0
2.0
3.0
0 50 100 150(Hz)0.0
0.5
1.0
1.5
2.0
0 50 100 150(Hz)0.0
1.0
2.0
3.0
4.0
0 50 100 150(Hz)0.0
0.5
1.0
1.5
0 50 100 150(Hz)0.0
0.5
1.0
1.5
0 50 100 150(Hz)0.0
0.5
1.0
1.5
2.0
Correction of Cooling capacity
Cap
acity
cor
rect
ion
fact
ors
The operational frequency of compressor
Correction of Cooling input
Inpu
t cor
rect
ion
fact
ors
The operational frequency of compressor
Correction of Heating input
Inpu
t cor
rect
ion
fact
ors
The operational frequency of compressor
Correction of Heating capacity
Cap
acity
cor
rect
ion
fact
ors
The operational frequency of compressor
MUZ-FD35VAH
Correction of Heating input
Cap
acity
cor
rect
ion
fact
ors
The operational frequency of compressor
0 50 100 150(Hz)0.0
1.0
2.0
3.0
0 50 100 150(Hz)0.0
0.5
1.0
1.5
0 50 100 150(Hz)0.0
0.5
1.0
1.5
0 50 100 150(Hz)0.0
1.0
2.0
3.0
0 50 100 150(Hz)0.0
0.5
1.0
1.5
2.0
8-2. Capacity and input correction by operational frequency of compressor
8-3. Test run operation (How to operate fixed-frequency operation)
1. Press EMERGENCY OPERATION switch to COOL or HEAT mode (COOL : Press once, HEAT : Press twice).2. Test run operation starts and continues to operate for 30 minutes.3. Compressor operates at rated frequency in COOL mode or 58Hz in HEAT mode.4. Indoor fan operates at High speed.5. After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts (Operation frequency of compressor
varies).6. To cancel test run operation (EMERGENCY OPERATION), press EMERGENCY OPERATION switch or any button on
remote controller.
OBH489--1.qxp 07.8.9 11:53 AM Page 13
14
kgf/F
[Gau
ge]
MP
a [G
auge
]
15 2050
2560
3070 (%)
35(˚C)
323070 (%)
35(˚C)
0.2
0.4
0.6
0.8
1.0
1.2
2
4
6
8
10
12
14 1.4
Ambient temperature(˚C) Ambient humidity(%)
Outdoor low pressure
Ambient temperature(˚C) Ambient humidity(%)
15 2050
2560
2.5
3.0
3.5
4.0
18
MUZ-FD25VA MUZ-FD25VAH
MUZ-FD25VA MUZ-FD25VAH
MUZ-FD35VA
MUZ-FD35VA
kgf/F
[Gau
ge]
MP
a [G
auge
]
0.2
0.4
0.6
0.8
1.0
1.2
2
4
6
8
10
12
14 1.4
15 2050
2560
1.8
2.0
2.2
2.4
18
(A) (A)
Outdoor unit current
Ambient temperature(˚C) Ambient humidity(%)
Ambient temperature(˚C) Ambient humidity(%)
15 2050
2560
3070 (%)
35(˚C)
323070 (%)
35(˚C)
Ambient temperature(˚C) Ambient humidity(%)
15 2050
2560
2.5
3.0
3.5
4.0
18
MUZ-FD35VAH(A)
323070 (%)
35(˚C)
MUZ-FD35VAH
kgf/F
[Gau
ge]
MP
a [G
auge
]
0.2
0.4
0.6
0.8
1.0
1.2
2
4
6
8
10
12
14 1.4
Ambient temperature(˚C) Ambient humidity(%)
15 2050
2560
3070 (%)
35(˚C)
(A) (A)
Ambient temperature(˚C) Ambient temperature(˚C)
MUZ-FD25VA MUZ-FD25VAH MUZ-FD35VAOutdoor unit current
(A)
Ambient temperature(˚C)
MUZ-FD35VAH6.0
5.5
5.0
4.5
4.05 10 15 20 25(:)
6.0
5.5
5.0
4.5
4.02 5 10 15 20 25(:)
6.0
5.5
5.0
4.5
4.02 5 10 15 20 25(:)
COOL operation1 Both indoor and outdoor unit are under the
same temperature/humidity condition.2 Operation : TEST RUN OPERATION (refer to 8-3.)
Dry-bulb temperature(:) Relative humidity(%)
20 50
25 60
30 70
8-4. Outdoor low pressure and outdoor unit current
1 Condition :
2 Operation : Test run operation (refer to 8-3.)
HEAT operation
Dry bulb temperature (°C)
Indoor
20.0
14.5
2
1
Outdoor
7
6
15
12
20.0
14.5Wet bulb temperature (°C)
NOTE : The unit of pressure has been changed to MPa on the international system of units (SI unit system)The conversion factor is: 1(MPa [Gauge]) =10.2(kgf/ff [Gauge])
OBH489--1.qxp 07.8.9 11:53 AM Page 14
15
MUZ-FD25VA MUZ-FD25VAH
21 1821 2022 1822 2022 2223 1823 2023 2224 1824 2024 2224 2425 1825 2025 2225 2426 1826 2026 2226 2426 2627 1827 2027 2227 2427 2628 1828 2028 2228 2428 2629 1829 2029 2229 2429 2630 1830 2030 2230 2430 2631 1831 2031 2231 2431 2632 1832 2032 2232 2432 26
INDOOR INDOOR
CAPACITY:2.5(kW) INPUT:485(W)SHF:0.85
21OUTDOOR DB(:)
25 27 30WB(:) Q SHC SHF Q SHC SHF Q SHC SHF Q SHC SHFINPUT INPUT INPUT INPUTDB(:)
1.971.682.091.811.502.201.931.632.322.051.751.442.442.171.881.572.562.302.011.711.352.672.422.141.841.482.792.542.261.981.622.912.662.392.111.762.942.792.522.241.902.942.912.652.382.042.943.032.772.512.17
2.943.062.943.063.192.943.063.192.943.063.193.352.943.063.193.352.943.063.193.353.452.943.063.193.353.452.943.063.193.353.452.943.063.193.353.452.943.063.193.353.452.943.063.193.353.452.943.063.193.353.45
0.670.550.710.590.470.750.630.510.790.670.550.430.830.710.590.470.870.750.630.510.390.910.790.670.550.430.950.830.710.590.470.990.870.750.630.511.000.910.790.670.551.000.950.830.710.591.000.990.870.750.63
388407388407422388407422388407422441388407422441388407422441466388407422441466388407422441466388407422441466388407422441466388407422441466388407422441466
2.812.942.812.943.082.812.943.082.812.943.083.232.812.943.083.232.812.943.083.233.352.812.943.083.233.352.812.943.083.233.352.812.943.083.233.352.812.943.083.233.352.812.943.083.233.352.812.943.083.233.35
1.881.622.001.731.452.111.851.572.221.971.691.392.332.091.811.522.452.201.941.641.312.562.322.061.771.442.672.442.181.901.572.782.562.312.031.712.812.672.432.161.842.812.792.552.291.982.812.912.682.422.11
0.670.550.710.590.470.750.630.510.790.670.550.430.830.710.590.470.870.750.630.510.390.910.790.670.550.430.950.830.710.590.470.990.870.750.630.511.000.910.790.670.551.000.950.830.710.591.000.990.870.750.63
407432407432449407432449407432449466407432449466407432449466490407432449466490407432449466490407432449466490407432449466490407432449466490407432449466490
2.702.852.702.853.002.702.853.002.702.853.003.152.702.853.003.152.702.853.003.153.302.702.853.003.153.302.702.853.003.153.302.702.853.003.153.302.702.853.003.153.302.702.853.003.153.302.702.853.003.153.30
1.811.571.921.681.412.031.801.532.131.911.651.352.242.021.771.482.352.141.891.611.292.462.252.011.731.422.572.372.131.861.552.672.482.251.981.682.702.592.372.111.822.702.712.492.241.952.702.822.612.362.08
0.670.550.710.590.470.750.630.510.790.670.550.430.830.710.590.470.870.750.630.510.390.910.790.670.550.430.950.830.710.590.470.990.870.750.630.511.000.910.790.670.551.000.950.830.710.591.000.990.870.750.63
427441427441461427441461427441461480427441461480427441461480504427441461480504427441461480504427441461480504427441461480504427441461480504427441461480504
2.602.752.602.752.882.602.752.882.602.752.883.052.602.752.883.052.602.752.883.053.202.602.752.883.053.202.602.752.883.053.202.602.752.883.053.202.602.752.883.053.202.602.752.883.053.202.602.752.883.053.20
1.741.511.851.621.351.951.731.472.051.841.581.312.161.951.701.432.262.061.811.561.252.372.171.931.681.382.472.282.041.801.502.572.392.161.921.632.602.502.272.041.762.602.612.392.171.892.602.722.502.292.02
0.670.550.710.590.470.750.630.510.790.670.550.430.830.710.590.470.870.750.630.510.390.910.790.670.550.430.950.830.710.590.470.990.870.750.630.511.000.910.790.670.551.000.950.830.710.591.000.990.870.750.63
446461446461480446461480446461480504446461480504446461480504519446461480504519446461480504519446461480504519446461480504519446461480504519446461480504519
PERFORMANCE DATA COOL operation at Rated frequency
NOTE: Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperatureSHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OBH489--1.qxp 07.8.9 11:53 AM Page 15
16
21 1821 2022 1822 2022 2223 1823 2023 2224 1824 2024 2224 2425 1825 2025 2225 2426 1826 2026 2226 2426 2627 1827 2027 2227 2427 2628 1828 2028 2228 2428 2629 1829 2029 2229 2429 2630 1830 2030 2230 2430 2631 1831 2031 2231 2431 2632 1832 2032 2232 2432 26
35 40 46
CAPACITY:2.5(kW) INPUT:485(W)SHF:0.85
OUTDOOR DB(:)INDOOR INDOORDB (:) WB (:) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
2.452.582.452.582.732.452.582.732.452.582.732.882.452.582.732.882.452.582.732.883.032.452.582.732.883.032.452.582.732.883.032.452.582.732.883.032.452.582.732.883.032.452.582.732.883.032.452.582.732.883.03
1.641.421.741.521.281.841.621.391.941.731.501.242.031.831.611.352.131.931.721.471.182.232.031.831.581.302.332.141.931.701.422.432.242.041.811.542.452.342.151.931.662.452.452.262.041.782.452.552.372.161.91
0.670.550.710.590.470.750.630.510.790.670.550.430.830.710.590.470.870.750.630.510.390.910.790.670.550.430.950.830.710.590.470.990.870.750.630.511.000.910.790.670.551.000.950.830.710.591.000.990.870.750.63
475495475495514475495514475495514534475495514534475495514534553475495514534553475495514534553475495514534553475495514534553475495514534553475495514534553
2.252.402.252.402.552.252.402.552.252.402.552.702.252.402.552.702.252.402.552.702.852.252.402.552.702.852.252.402.552.702.852.252.402.552.702.852.252.402.552.702.852.252.402.552.702.852.252.402.552.702.85
1.511.321.601.421.201.691.511.301.781.611.401.161.871.701.501.271.961.801.611.381.112.051.901.711.491.232.141.991.811.591.342.232.091.911.701.452.252.182.011.811.572.252.282.121.921.682.252.382.222.031.80
0.670.550.710.590.470.750.630.510.790.670.550.430.830.710.590.470.870.750.630.510.390.910.790.670.550.430.950.830.710.590.470.990.870.750.630.511.000.910.790.670.551.000.950.830.710.591.000.990.870.750.63
504519504519543504519543504519543558504519543558504519543558577504519543558577504519543558577504519543558577504519543558577504519543558577504519543558577
2.082.232.082.232.382.082.232.382.082.232.382.552.082.232.382.552.082.232.382.552.682.082.232.382.552.682.082.232.382.552.682.082.232.382.552.682.082.232.382.552.682.082.232.382.552.682.082.232.382.552.68
1.391.221.471.311.121.561.401.211.641.491.311.101.721.581.401.201.811.671.501.301.041.891.761.591.401.151.971.851.691.501.262.051.941.781.611.362.082.021.881.711.472.082.111.971.811.582.082.202.071.911.69
0.670.550.710.590.470.750.630.510.790.670.550.430.830.710.590.470.870.750.630.510.390.910.790.670.550.430.950.830.710.590.470.990.870.750.630.511.000.910.790.670.551.000.950.830.710.591.000.990.870.750.63
524548524548563524548563524548563582524548563582524548563582601524548563582601524548563582601524548563582601524548563582601524548563582601524548563582601
PERFORMANCE DATA COOL operation at Rated frequency
NOTE: Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperatureSHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
MUZ-FD25VA MUZ-FD25VAH
OBH489--1.qxp 07.8.9 11:53 AM Page 16
17
21 1821 2022 1822 2022 2223 1823 2023 2224 1824 2024 2224 2425 1825 2025 2225 2426 1826 2026 2226 2426 2627 1827 2027 2227 2427 2628 1828 2028 2228 2428 2629 1829 2029 2229 2429 2630 1830 2030 2230 2430 2631 1831 2031 2231 2431 2632 1832 2032 2232 2432 26
INDOOR INDOOR
CAPACITY:3.5(kW) INPUT:850(W)SHF:0.85
21OUTDOOR DB(:)
25 27 30WB(:) Q SHC SHF Q SHC SHF Q SHC SHF Q SHC SHFINPUT INPUT INPUT INPUTDB(:)
4.114.294.114.294.464.114.294.464.114.294.464.694.114.294.464.694.114.294.464.694.834.114.294.464.694.834.114.294.464.694.834.114.294.464.694.834.114.294.464.694.834.114.294.464.694.834.114.294.464.694.83
2.762.362.922.532.103.082.702.283.252.872.452.023.413.042.632.203.583.222.812.391.883.743.392.992.582.083.913.563.172.772.274.073.733.352.952.464.113.903.533.142.664.114.073.703.332.854.114.243.883.523.04
0.670.550.710.590.470.750.630.510.790.670.550.430.830.710.590.470.870.750.630.510.390.910.790.670.550.430.950.830.710.590.470.990.870.750.630.511.000.910.790.670.551.000.950.830.710.591.000.990.870.750.63
680714680714740680714740680714740774680714740774680714740774816680714740774816680714740774816680714740774816680714740774816680714740774816680714740774816
3.944.113.944.114.313.944.114.313.944.114.314.523.944.114.314.523.944.114.314.524.693.944.114.314.524.693.944.114.314.524.693.944.114.314.524.693.944.114.314.524.693.944.114.314.524.693.944.114.314.524.69
2.642.262.802.432.022.952.592.203.112.762.371.943.272.922.542.123.433.082.712.301.833.583.252.882.482.023.743.413.062.662.203.903.583.232.842.393.943.743.403.032.583.943.913.573.212.773.944.073.753.392.95
0.670.550.710.590.470.750.630.510.790.670.550.430.830.710.590.470.870.750.630.510.390.910.790.670.550.430.950.830.710.590.470.990.870.750.630.511.000.910.790.670.551.000.950.830.710.591.000.990.870.750.63
714757714757786714757786714757786816714757786816714757786816859714757786816859714757786816859714757786816859714757786816859714757786816859714757786816859
3.783.993.783.994.203.783.994.203.783.994.204.413.783.994.204.413.783.994.204.414.623.783.994.204.414.623.783.994.204.414.623.783.994.204.414.623.783.994.204.414.623.783.994.204.414.623.783.994.204.414.62
2.532.192.682.351.972.842.512.142.992.672.311.903.142.832.482.073.292.992.652.251.803.443.152.812.431.993.593.312.982.602.173.743.473.152.782.363.783.633.322.952.543.783.793.493.132.733.783.953.653.312.91
0.670.550.710.590.470.750.630.510.790.670.550.430.830.710.590.470.870.750.630.510.390.910.790.670.550.430.950.830.710.590.470.990.870.750.630.511.000.910.790.670.551.000.950.830.710.591.000.990.870.750.63
748774748774808748774808748774808842748774808842748774808842884748774808842884748774808842884748774808842884748774808842884748774808842884748774808842884
3.643.853.643.854.033.643.854.033.643.854.034.273.643.854.034.273.643.854.034.274.483.643.854.034.274.483.643.854.034.274.483.643.854.034.274.483.643.854.034.274.483.643.854.034.274.483.643.854.034.274.48
2.442.122.582.271.892.732.432.052.882.582.211.843.022.732.372.013.172.892.542.181.753.313.042.702.351.933.463.202.862.522.113.603.353.022.692.283.643.503.182.862.463.643.663.343.032.643.643.813.503.202.82
0.670.550.710.590.470.750.630.510.790.670.550.430.830.710.590.470.870.750.630.510.390.910.790.670.550.430.950.830.710.590.470.990.870.750.630.511.000.910.790.670.551.000.950.830.710.591.000.990.870.750.63
782808782808842782808842782808842884782808842884782808842884910782808842884910782808842884910782808842884910782808842884910782808842884910782808842884910
PERFORMANCE DATA COOL operation at Rated frequency
NOTE: Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperatureSHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
MUZ-FD35VA
OBH489--1.qxp 07.8.9 11:53 AM Page 17
18
21 1821 2022 1822 2022 2223 1823 2023 2224 1824 2024 2224 2425 1825 2025 2225 2426 1826 2026 2226 2426 2627 1827 2027 2227 2427 2628 1828 2028 2228 2428 2629 1829 2029 2229 2429 2630 1830 2030 2230 2430 2631 1831 2031 2231 2431 2632 1832 2032 2232 2432 26
35 40 46
CAPACITY:3.5(kW) INPUT:850(W)SHF:0.85
OUTDOOR DB(:)INDOOR INDOORDB (:) WB (:) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
3.433.613.433.613.823.433.613.823.433.613.824.033.433.613.824.033.433.613.824.034.243.433.613.824.034.243.433.613.824.034.243.433.613.824.034.243.433.613.824.034.243.433.613.824.034.243.433.613.824.034.24
2.301.982.442.131.792.572.271.952.712.422.101.732.852.562.251.892.982.702.402.051.653.122.852.562.211.823.262.992.712.371.993.403.142.862.542.163.433.283.012.702.333.433.423.172.862.503.433.573.323.022.67
0.670.550.710.590.470.750.630.510.790.670.550.430.830.710.590.470.870.750.630.510.390.910.790.670.550.430.950.830.710.590.470.990.870.750.630.511.000.910.790.670.551.000.950.830.710.591.000.990.870.750.63
833867833867901833867901833867901935833867901935833867901935969833867901935969833867901935969833867901935969833867901935969833867901935969833867901935969
3.153.363.153.363.573.153.363.573.153.363.573.783.153.363.573.783.153.363.573.783.993.153.363.573.783.993.153.363.573.783.993.153.363.573.783.993.153.363.573.783.993.153.363.573.783.993.153.363.573.783.99
2.111.852.241.981.682.362.121.822.492.251.961.632.612.392.111.782.742.522.251.931.562.872.652.392.081.722.992.792.532.231.883.122.922.682.382.033.153.062.822.532.193.153.192.962.682.353.153.333.112.842.51
0.670.550.710.590.470.750.630.510.790.670.550.430.830.710.590.470.870.750.630.510.390.910.790.670.550.430.950.830.710.590.470.990.870.750.630.511.000.910.790.670.551.000.950.830.710.591.000.990.870.750.63
8849108849109528849109528849109529788849109529788849109529781012884910952978101288491095297810128849109529781012884910952978101288491095297810128849109529781012
2.913.122.913.123.332.913.123.332.913.123.333.572.913.123.333.572.913.123.333.573.752.913.123.333.573.752.913.123.333.573.752.913.123.333.573.752.913.123.333.573.752.913.123.333.573.752.913.123.333.573.75
1.951.712.061.841.562.181.961.702.292.091.831.542.412.211.961.682.532.342.091.821.462.642.462.231.961.612.762.592.362.111.762.882.712.492.251.912.912.832.632.392.062.912.962.762.532.212.913.082.892.682.36
0.670.550.710.590.470.750.630.510.790.670.550.430.830.710.590.470.870.750.630.510.390.910.790.670.550.430.950.830.710.590.470.990.870.750.630.511.000.910.790.670.551.000.950.830.710.591.000.990.870.750.63
9189619189619869189619869189619861020918961986102091896198610201054918961986102010549189619861020105491896198610201054918961986102010549189619861020105491896198610201054
PERFORMANCE DATA COOL operation at Rated frequency
NOTE: Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperatureSHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
MUZ-FD35VA
OBH489--1.qxp 07.8.9 11:53 AM Page 18
19
21 1821 2022 1822 2022 2223 1823 2023 2224 1824 2024 2224 2425 1825 2025 2225 2426 1826 2026 2226 2426 2627 1827 2027 2227 2427 2628 1828 2028 2228 2428 2629 1829 2029 2229 2429 2630 1830 2030 2230 2430 2631 1831 2031 2231 2431 2632 1832 2032 2232 2432 26
INDOOR INDOOR
CAPACITY:3.5(kW) INPUT:835(W)SHF:0.85
21OUTDOOR DB(:)
25 27 30WB(:) Q SHC SHF Q SHC SHF Q SHC SHF Q SHC SHFINPUT INPUT INPUT INPUTDB(:)
4.114.294.114.294.464.114.294.464.114.294.464.694.114.294.464.694.114.294.464.694.834.114.294.464.694.834.114.294.464.694.834.114.294.464.694.834.114.294.464.694.834.114.294.464.694.834.114.294.464.694.83
2.762.362.922.532.103.082.702.283.252.872.452.023.413.042.632.203.583.222.812.391.883.743.392.992.582.083.913.563.172.772.274.073.733.352.952.464.113.903.533.142.664.114.073.703.332.854.114.243.883.523.04
0.670.550.710.590.470.750.630.510.790.670.550.430.830.710.590.470.870.750.630.510.390.910.790.670.550.430.950.830.710.590.470.990.870.750.630.511.000.910.790.670.551.000.950.830.710.591.000.990.870.750.63
668701668701726668701726668701726760668701726760668701726760802668701726760802668701726760802668701726760802668701726760802668701726760802668701726760802
3.944.113.944.114.313.944.114.313.944.114.314.523.944.114.314.523.944.114.314.524.693.944.114.314.524.693.944.114.314.524.693.944.114.314.524.693.944.114.314.524.693.944.114.314.524.693.944.114.314.524.69
2.642.262.802.432.022.952.592.203.112.762.371.943.272.922.542.123.433.082.712.301.833.583.252.882.482.023.743.413.062.662.203.903.583.232.842.393.943.743.403.032.583.943.913.573.212.773.944.073.753.392.95
0.670.550.710.590.470.750.630.510.790.670.550.430.830.710.590.470.870.750.630.510.390.910.790.670.550.430.950.830.710.590.470.990.870.750.630.511.000.910.790.670.551.000.950.830.710.591.000.990.870.750.63
701743701743772701743772701743772802701743772802701743772802843701743772802843701743772802843701743772802843701743772802843701743772802843701743772802843
3.783.993.783.994.203.783.994.203.783.994.204.413.783.994.204.413.783.994.204.414.623.783.994.204.414.623.783.994.204.414.623.783.994.204.414.623.783.994.204.414.623.783.994.204.414.623.783.994.204.414.62
2.532.192.682.351.972.842.512.142.992.672.311.903.142.832.482.073.292.992.652.251.803.443.152.812.431.993.593.312.982.602.173.743.473.152.782.363.783.633.322.952.543.783.793.493.132.733.783.953.653.312.91
0.670.550.710.590.470.750.630.510.790.670.550.430.830.710.590.470.870.750.630.510.390.910.790.670.550.430.950.830.710.590.470.990.870.750.630.511.000.910.790.670.551.000.950.830.710.591.000.990.870.750.63
735760735760793735760793735760793827735760793827735760793827868735760793827868735760793827868735760793827868735760793827868735760793827868735760793827868
3.643.853.643.854.033.643.854.033.643.854.034.273.643.854.034.273.643.854.034.274.483.643.854.034.274.483.643.854.034.274.483.643.854.034.274.483.643.854.034.274.483.643.854.034.274.483.643.854.034.274.48
2.442.122.582.271.892.732.432.052.882.582.211.843.022.732.372.013.172.892.542.181.753.313.042.702.351.933.463.202.862.522.113.603.353.022.692.283.643.503.182.862.463.643.663.343.032.643.643.813.503.202.82
0.670.550.710.590.470.750.630.510.790.670.550.430.830.710.590.470.870.750.630.510.390.910.790.670.550.430.950.830.710.590.470.990.870.750.630.511.000.910.790.670.551.000.950.830.710.591.000.990.870.750.63
768793768793827768793827768793827868768793827868768793827868893768793827868893768793827868893768793827868893768793827868893768793827868893768793827868893
PERFORMANCE DATA COOL operation at Rated frequency
NOTE: Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperatureSHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
MUZ-FD35VAH
OBH489--1.qxp 07.8.9 11:53 AM Page 19
20
21 1821 2022 1822 2022 2223 1823 2023 2224 1824 2024 2224 2425 1825 2025 2225 2426 1826 2026 2226 2426 2627 1827 2027 2227 2427 2628 1828 2028 2228 2428 2629 1829 2029 2229 2429 2630 1830 2030 2230 2430 2631 1831 2031 2231 2431 2632 1832 2032 2232 2432 26
35 40 46
CAPACITY:3.5(kW) INPUT:835(W)SHF:0.85
OUTDOOR DB(:)INDOOR INDOORDB (:) WB (:) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
3.433.613.433.613.823.433.613.823.433.613.824.033.433.613.824.033.433.613.824.034.243.433.613.824.034.243.433.613.824.034.243.433.613.824.034.243.433.613.824.034.243.433.613.824.034.243.433.613.824.034.24
2.301.982.442.131.792.572.271.952.712.422.101.732.852.562.251.892.982.702.402.051.653.122.852.562.211.823.262.992.712.371.993.403.142.862.542.163.433.283.012.702.333.433.423.172.862.503.433.573.323.022.67
0.670.550.710.590.470.750.630.510.790.670.550.430.830.710.590.470.870.750.630.510.390.910.790.670.550.430.950.830.710.590.470.990.870.750.630.511.000.910.790.670.551.000.950.830.710.591.000.990.870.750.63
818852818852885818852885818852885919818852885919818852885919952818852885919952818852885919952818852885919952818852885919952818852885919952818852885919952
3.153.363.153.363.573.153.363.573.153.363.573.783.153.363.573.783.153.363.573.783.993.153.363.573.783.993.153.363.573.783.993.153.363.573.783.993.153.363.573.783.993.153.363.573.783.993.153.363.573.783.99
2.111.852.241.981.682.362.121.822.492.251.961.632.612.392.111.782.742.522.251.931.562.872.652.392.081.722.992.792.532.231.883.122.922.682.382.033.153.062.822.532.193.153.192.962.682.353.153.333.112.842.51
0.670.550.710.590.470.750.630.510.790.670.550.430.830.710.590.470.870.750.630.510.390.910.790.670.550.430.950.830.710.590.470.990.870.750.630.511.000.910.790.670.551.000.950.830.710.591.000.990.870.750.63
868893868893935868893935868893935960868893935960868893935960994868893935960994868893935960994868893935960994868893935960994868893935960994868893935960994
2.913.122.913.123.332.913.123.332.913.123.333.572.913.123.333.572.913.123.333.573.752.913.123.333.573.752.913.123.333.573.752.913.123.333.573.752.913.123.333.573.752.913.123.333.573.752.913.123.333.573.75
1.951.712.061.841.562.181.961.702.292.091.831.542.412.211.961.682.532.342.091.821.462.642.462.231.961.612.762.592.362.111.762.882.712.492.251.912.912.832.632.392.062.912.962.762.532.212.913.082.892.682.36
0.670.550.710.590.470.750.630.510.790.670.550.430.830.710.590.470.870.750.630.510.390.910.790.670.550.430.950.830.710.590.470.990.870.750.630.511.000.910.790.670.551.000.950.830.710.591.000.990.870.750.63
9029449029449699029449699029449691002902944969100290294496910021035902944969100210359029449691002103590294496910021035902944969100210359029449691002103590294496910021035
PERFORMANCE DATA COOL operation at Rated frequency
NOTE: Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperatureSHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
MUZ-FD35VAH
OBH489--1.qxp 07.8.9 11:53 AM Page 20
21
PERFORMANCE DATA HEAT operation at Rated frequency
CAPACITY:3.2(kW) INPUT:610(W)
OUTDOOR WB(:)INDOOR -10 -5 0 5 10 15 20DB(:) Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
152126
2.021.921.73
397427458
2.432.302.14
476506537
2.852.722.53
537561592
3.263.102.94
580604634
3.683.523.36
616634665
4.063.903.74
634653683
4.484.304.16
647677702
CAPACITY:4.0(kW) INPUT:865(W)
OUTDOOR WB(:)INDOOR -10 -5 0 5 10 15 20DB(:) Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
152126
2.522.402.16
562606649
3.042.882.68
675718761
3.563.403.16
761796839
4.083.883.68
822856900
4.604.404.20
874900943
5.084.884.68
900926969
5.605.385.20
917960995
MUZ-FD25VA MUZ-FD25VAH
MUZ-FD35VA
CAPACITY:4.0(kW) INPUT:850(W)
OUTDOOR WB(:)INDOOR -10 -5 0 5 10 15 20DB(:) Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
152126
2.522.402.16
553595638
3.042.882.68
663706748
3.563.403.16
748782825
4.083.883.68
808842884
4.604.404.20
859884927
5.084.884.68
884910952
5.605.385.20
901944978
MUZ-FD35VAH
NOTE: Q:Total capacity (kW) INPUT:Total power input (W) DB : Dry-bulb temperature WB : Wet-bulb temperature
OBH489--1.qxp 07.8.9 11:53 AM Page 21
22
9 ACTUATOR CONTROL
MUZ-FD25VA MUZ-FD35VAMUZ-FD25VAH MUZ-FD35VAH
9-3. Relation between main sensor and actuator
9-2. R.V. coil controlHeating . . . . . . . . . . . . . . . . ONCooling . . . . . . . . . . . . . . . . OFFDry. . . . . . . . . . . . . . . . . . . . OFFNOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
ON
OFF
ON
OFF
Outdoor fanmotor
Compressor
5 seconds 15 seconds
ON
OFFCompressor
Outdoor fan
motor
R.V.coilON
OFF
ON
OFF
<COOL>
5 seconds
<HEAT>
5 seconds
9-1. Outdoor fan motor controlThe fan motor turns ON/OFF, interlocking with the compressor.[ON] The fan motor turns ON 5 seconds before the compressor starts up.[OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.
Discharge temperature thermistor
Indoor coil temperature thermistor
Defrost thermistor
Fin temperature thermistor
Ambient temperature thermistor
Outdoor heat exchanger temperature thermistor
Compressor LEV Outdoor fan motor
Indoor fan motor
DefrostheaterR.V. coil
Sensor PurposeActuator
Protection
Cooling : Coil frost prevention
Heating : High pressure protection
Cooling : High pressure protection
Heating : Defrosting
Protection
Cooling : Low outside temperature operation
Heating : Defrosting (Heater)
Low outside temperature operation
OBH489--1.qxp 07.8.9 11:53 AM Page 22
23
SERVICE FUNCTIONS10
10-1. CHANGE IN DEFROST SETTINGChanging defrost finish temperature<JS> To change the defrost finish temperature, cut/solder the JS wire of the outdoor inverter P.C. board.(Refer to 11-6-1.)
MUZ-FD25VA MUZ-FD35VAMUZ-FD25VAH MUZ-FD35VAH
11 TROUBLESHOOTING
3. Troubleshooting procedure1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality.
To make sure, check how many times the abnormality indication is flashing on and off before starting service work.2) Before servicing, check that the connector and terminal are connected properly.3) When the electronic control P.C. board seems to be defective, check the copper foil pattern for disconnection and the
components for bursting and discoloration.4) Refer to 11-2. and 11-3.
11-1. Cautions on troubleshooting1. Before troubleshooting, check the following
1) Check the power supply voltage.2) Check the indoor/outdoor connecting wire for miswiring.
2. Take care of the following during servicing1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, and then after
confirming the horizontal vane is closed, turn OFF the breaker and / or disconnect the power plug.2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic
control P.C. board.3) When removing the electrical parts, be careful to the residual voltage of smoothing capacitor. 4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the
components.5) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
Housing pointLead wiring
Jumper wire Defrost finish temperature (:)
JSnone(cut)
soldered(Initial setting)
10
5
MUZ-FD25VA MUZ-FD35VAMUZ-FD25VAH MUZ-FD35VAH
10-2. PRE-HEAT CONTROL SETTINGPRE-HEAT CONTROLWhen moisture gets into the refrigerant cycle, it may interfere the start-up of the compressor at low outside tempera-ture. The pre-heat control prevents this interference. The pre-heat control turns ON when outside temperature is 20°Cor below. When pre-heat control is turned ON, compressor is energized. (about 50 W)
<JK> To activate the pre-heat control, cut the JK wire of the inverter P.C. board. (Refer to 11-6.1)
NOTE: When the inverter P.C. board is replaced, check the Jumper wires, and cut/solder them if necessary.
OBH489--1.qxp 07.8.9 4:27 PM Page 23
24
Operational procedure
Yes(Blinks)
No(OFF)
Yes
No
Releasing the failure mode recall function
NOTE: 1. Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly. 2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
W2. Blinking pattern when the indoor unit is abnormal:
W3.Blinking pattern when the outdoor unit is abnormal:
ONOFF
BeepsRepeated cycle Repeated cycle
ONOFF
No beep BeepsRepeated cycle
2.5-second OFFBlinking at 0.5-second interval
2.5-second OFF 3-second ONBlinking at 0.5-second interval
BeepsRepeated cycle
2.5-second OFFBlinking at 0.5-second interval
No beep BeepsRepeated cycle
2.5-second OFF 3-second ONBlinking at 0.5-second interval
Repeated cycle
Beeps
Does POWER lamp on the indoor unit blink at the interval of 0.5 seconds?Blinks: Either indoor or outdoor unit is abnormal. Beep is emitted at the same timing as the blinking of POWER lamp. W2
The cause of abnormality cannot be found because the abnormality doesn't recur.
Setting up the failure mode recall function
Before blinking, does POWER lamp stay ON for 3 seconds?Stays ON for 3 seconds (without beep): The outdoor unit is abnormal.
The indoor unit is abnormal.Check the blinking pattern, and confirm the abnormal point with the indoor unitfailure mode table (Refer to indoor unit service manual.)Make sure to check at least two consecutive blinking cycles. W2
Turn ON the power supply.<Preparation of the remote controller>1 While pressing both OPERATION SELECT button and TOO COOL button on the remote controller at the same time, press RESET button.2 First, release RESET button. And release the other two buttons after all LCD in operation display section of the remote controller is displayed after 3 seconds.
Deleting the memorized abnormal condition
1After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall function" mentioned above.2Press OPERATE/STOP(ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit.3Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.4Release the failure mode recall function according to "Releasing the failure mode recall function" mentioned above.
Repair the defective parts.
Release the failure mode recall function by the following procedures.Turn OFF the power supply and turn it ON again.Press RESET button of the remote controller.
Judgment of indoor/outdoor abnormality
Press OPERATE/STOP(ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. W1
Indoor unit is normal.But the outdoor unit might be abnormal because there are some abnormalities that can't be recalled with this way.Confirm if outdoor unit is abnormal according to the detailed outdoor unit failure mode recall function.(Refer to 11-2.2)
The outdoor unit is abnormal.Check the blinking pattern, and confirm the abnormal point with theoutdoor unit failure mode table (Refer to 11-2.3).Make sure to check at least two consecutive blinking cycles. W3
W1. Regardless of normal or abnormal condition, a short beep is emitted once the signal is received.
Outline of the functionThis air conditioner can memorize the abnormal condition which has occurred once.Even though LED indication listed on the troubleshooting check table (11-3.) disappears, the memorized failure detailscan be recalled.This mode is very useful when the unit needs to be repaired for the abnormality which doesn't recur.
11-2. Failure mode recall function
1. Flow chart of failure mode recall function for the indoor/outdoor unit
OBH489--1.qxp 07.8.9 4:27 PM Page 24
25
2. Flow chart of the detailed outdoor unit failure mode recall function
Operational procedure
NOTE: 1. Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly. 2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
W2.Blinking pattern when outdoor unit is abnormal:
Yes(Blinks)
No(OFF)
ONOFF
No beep BeepsRepeated cycle
2.5-second OFF 3-second ONBlinking at 0.5-second interval
No beep BeepsRepeated cycle
2.5-second OFF 3-second ONBlinking at 0.5-second interval
Repeated cycle
W1. Regardless of normal or abnormal condition, 2 short beeps are emitted as the signal is received.
Does POWER lamp on the indoor unit blink at the interval of 0.5 seconds?Blinks: The outdoor unit is abnormal. Beep is emitted at the same timing as the blinking of POWER lamp. W2
Deleting the memorized abnormal condition
1After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall function" mentioned above.2Press OPERATE/STOP(ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit.3Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.4Release the failure mode recall function according to "Releasing the failure mode recall function" mentioned above.
Repair the defective parts.
With the remote controller headed towards the indoor unit, press TOO COOL or TOOWARM button to adjust the set temperature to 25 :. W1
The outdoor unit is normal.
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures. Turn OFF the power supply and turn it ON again.Press RESET button of the remote controller.
The outdoor unit is abnormal.Check the blinking pattern, and confirm the abnormal point with theoutdoor unit failure mode table (Refer to 11-2.3.).Make sure to check at least two consecutive blinking cycles. W2
Release the failure mode recall function according to the left mentioned procedure.
Confirm that the remote controller is in the failure mode recallfunction.
The outdoor unit might be abnormal.Confirm if outdoor unit is abnormal according to the following procedures.
OBH489--1.qxp 07.8.9 4:27 PM Page 25
26
3. Outdoor unit failure mode table
2-time flash2.5 seconds OFF
3-time flash2.5 seconds OFF
4-time flash2.5 seconds OFF
5-time flash2.5 seconds OFF
6-time flash2.5 seconds OFF
7-time flash2.5 seconds OFF
8-time flash2.5 seconds OFF
9-time flash2.5 seconds OFF10-time flash2.5 seconds OFF
11-time flash2.5 seconds OFF
12-time flash2.5 seconds OFF
14-time flash2.5 seconds OFF
None (Normal)Outdoor power system
Discharge temperature thermistor Defrost thermistor Fin temperature thermistor
P.C. board temperature thermistor
Ambient temperature thermistor
Overcurrent
Compressor synchronous abnormality (Compressor start-up failure protection)
Discharge temperature
High pressure
Fin temperature/ P.C. boardtemperature
Outdoor fan motor
Nonvolatile memory data
Discharge temperature
DC voltage
Each phase current of compressor
OvercurrentCompressor open-phase
Stop valve(Closed valve)
Abnormal point(Failure mode / protection)
Overcurrent protection stop is continuously performed 3 times within 1 minute after the compressor gets started.
Thermistor shorts or opens during compressor running.
Large current flows into intelligent power module.
Waveform of compressor current is distorted.
Temperature of discharge temperature thermistor exceeds 116 :, compressor stops. Compressor can restart if dischargetemperature thermistor reads 100 : or less 3 minutes later.Temperature indoor coil thermistorexceeds 70 : in HEAT mode.Temperature defrost thermistor exceeds 70 : in COOL mode.Temperature of fin temperature thermistor on the inverter P.C. board exceeds 75 : ~80 :, or temperature of P.C. board temperature thermistor on the inverter P.C. board exceeds 70 :~75 :.
Outdoor fan has stopped 3 times in a row within 30 seconds after outdoor fan start-up.
Nonvolatile memory data cannot be read properly.Temperature of discharge temperature thermistor has been 50 : or less for 20 minutes.
DC voltage of inverter cannot be detected normally.Each phase current of compressor cannot be detected normally.Large current flows into intelligent power module (IPM). The open-phase operation of compressor is detected. The interphase short out occurs in the output of the intelligent power module (IPM).The compressor winding shorts out.
Closed valve is detected by compressorcurrent.
Condition
•Reconnect connectors.•Refer to 11-5. A"How to check inverter/ compressor".•Check stop valve.•Refer to 11-5.G"Check of outdoor thermistors".❈ Defective outdoor thermistors can be identified by checking the blinking pattern of LED.
•Reconnect compressor connector.•Refer to 11-5.A"How to check inverter/ compressor".•Check stop valve.•Reconnect compressor connector.•Refer to 11-5.A"How to check inverter/ compressor".•Check refrigerant circuit and refrigerant amount.•Refer to 11-5.K"Check of LEV".
•Check refrigerant circuit and refrigerant amount.•Check stop valve.
•Check around outdoor unit.•Check outdoor unit air passage.•Refer to 11-5.I"Check of outdoor fan motor".
•Refer to 11-5.I"Check of outdoor fan motor". Refer to 11-5.L"Check of inverter P.C. board".
•Replace the inverter P.C. board.•Refer to 11-5.K"Check of LEV".•Check refrigerant circuit and refrigerant amount.•Refer to 11-5.A"How to check inverter/ compressor".
•Reconnect compressor connector.•Refer to 11-5. A"How to check inverter/ compressor".
•Check stop valve
CorrespondenceIndoor/outdoor
unit failure moderecall function
Outdoor unitfailure mode
recall function
1-time flash every2.5 seconds3-time flash2.5 seconds OFF4-time flash2.5 seconds OFF2-time flash2.5 seconds OFF11-time flash2.5 seconds OFF
12-time flash2.5 seconds OFF
7-time flash 2.5 seconds OFF
5-time flash2.5 seconds OFF
8-time flash2.5 seconds OFF9-time flash2.5 seconds OFF10-time flash2.5 seconds OFF
LED indication(Outdoor P.C. board)
OFF
POWER lamp(Indoor unit)
14-time flash2.5 seconds OFF
NOTE: Blinking patterns of this mode differ from the ones of Troubleshooting check table (11-3.).
OBH489--1.qxp 07.8.9 4:27 PM Page 26
27
ON
OFF2.5-second OFF 2.5-second OFF
The flashing frequency shows the number of times the LED blinks after every 2.5-second OFF.(Example) When the flashing frequency is “2”.
Abnormal point/ ConditionOvercurrent protection stop is continuously performed 3 times within 1 minute after the compressor gets started, or failure of restart of compressor has repeated 24 times.
Discharge temperature thermistor, fin temperature thermistor, defrost thermistor, P.C. board temperature thermistor or ambient temperature thermistor shorts or opens during compressor running.Nonvolatile memory data cannot be read properly.
(POWER lamp of the indoor unit lights up or flashes 7-time.)
Large current flows into intelligent power module, or compressor repeats after 15 seconds when overcurrent protection occures within 10 seconds after compressor starts. (Repeated 24 times at Maximum)
Temperature of discharge temperature thermistor exceeds 116:, compressor stops. Compressor can restart if discharge temperature thermistor reads 100: or less 3 minutes later.
Temperature of fin temperature thermistor on the heat sink exceeds 75 :~ 80 : or temperature of P.C. board temperature thermistor on the inverter P.C.board exceeds 70 :~ 75 :.
Indoor coil thermistor exceeds 70 : in HEAT mode. Defrost thermistor exceeds 70 : in COOL mode.
Current from power outlet reaches the protection current, and compressor frequency lowers.
Temperature of indoor coil thermistor exceeds 55 : in HEAT mode, compressor frequency lowers.
Indoor coil thermistor reads 8 : or less in COOL mode, compressor frequency lowers.
Temperature of discharge temperature thermistor exceeds 111 :, compressor frequency lowers.
Temperature of discharge temperature thermistor has been 50 : or less for 20 minutes.
No.
1
2
3
7
8
9
10
15
16
17
18
19
Symptom LED indication Condition Correspondence
Outdoor unit does not operate.
'Outdoor unit stops and restarts 3 minutes later' is repeated.
Outdoor unit operates.
Outdoor unit operates.
1-time flash every 2.5 seconds
2-time flash 2.5 seconds OFF
3-time flash2.5 seconds OFF
4-time flash2.5 seconds OFF
5-time flash2.5 seconds OFF
1-time flash2.5 seconds OFF
3-time flash 2.5 seconds OFF
4-time flash2.5 seconds OFF
7-time flash2.5 seconds OFF
Outdoor power system
Outdoor thermistors
Outdoor control system
Overcurrent protection
Discharge temperature overheatprotection
Fin temperature /P.C. board temperature thermistor overheat protection
High pressure protection
Frequency drop by current protection
Frequency drop by high pressure protection Frequency drop by defrosting in COOL mode
Frequency drop by discharge temperature protection
Low discharge temperature protection
· Reconnect connector of compressor.· Refer to 11-5.A "How to check
inverter/ compressor".· Check stop valve.
· Refer to 11-5.G "Check of outdoor thermistors".
· Reconnect connector of compressor.· Refer to 11-5.A "How to check inverter/compressor".· Check stop valve.
Replace inverter P.C. board.
· Check refrigerant circuit and refrigerant amount.
· Refer to 11-5.K "Check of LEV".
· Check around outdoor unit.· Check outdoor unit air passage.· Refer to 11-5.I "Check of outdoor
fan motor".
· Check refrigerant circuit and refrigerant amount.
· Check stop valve.
The unit is normal, but check the following.· Check if indoor filters are clogged. · Check if refrigerant is short.· Check if indoor/outdoor unit air
circulation is short cycled.
· Refer to 11-5.K "Check of LEV".· Check refrigerant circuit and
refrigerant amount.
Inverter P.C. board (Parts side)
LEDFlashing
Refer to 11-5.M "How to check miswiring and serial signal error.
The communication fails between the indoor and outdoor unit for 3 minutes.
Serial signal
8-time flash2.5 seconds OFF
Compressor synchronous abnormality
The waveform of compressor current is distorted. · Reconnect connector of compressor.· Refer to 11-5.A "How to check inverter/compressor".
8-time flash2.5 seconds OFF
PAM protection
PAM:Pulse Amplitude Modulation
The overcurrent flows into IGBT(Insulated Gate Bipolar transistor : TR821) or when the bus-bar voltage reaches 320 V or more, PAM stops and restarts.
This is not malfunction.PAM protection will be activated inthe following cases;1Instantaneous power voltage drop (Short time power failure)2When the power supply voltage is high.
9-time flash2.5 seconds OFF
Inverter check mode
The connector of compressor is disconnected, inverter check mode starts.
Check if the connector of the compressor is correctly connected.Refer to 11-5.A "How to check inverter/ compressor".
4
11
20
10-time flash2.5 seconds OFF
Outdoor fan motor
6-time flash2.5 seconds OFF
· Check stop valve.Closed valve is detected by compressor current.Stop valve/Closed valve5
11-time flash2.5 seconds OFF
Outdoor fan has stopped 3 times in a row within 30 seconds after outdoor fan start-up.
· Refer to 11-5.I "Check of outdoor fan motor.
· Refer to 11-5.L "Check of inverter P.C. board.
12
13
14
12-time flash2.5 seconds OFF
Each phasecurrent ofcompressor
Each phase current of compressor cannot be detected normally
· Refer to 11-5.A "How to check inverter/compressor".
13-time flash2.5 seconds OFF
DC voltage DC voltage of inverter cannot be detected normally. · Refer to 11-5.A "How to check inverter/compressor".
· Check refrigerant circuit and refrigerant amount.
· Refer to 11-5.K "Check of LEV".· Refer to 11-5.G "Check of
outdoor thermistors".
Refer to 11-2.2. "Flow chart of the detailed outdoor unit failure mode recall function".
Outdoor unit is defective. Outdoor unit (Other abnormality)6
14-time flash2.5 seconds OFF
0.5-second ON 0.5-second ON
11-3. Troubleshooting check table
NOTE: 1. The location of LED is illustrated at the right figure. Refer to 11-6.1.2. LED is lighted during normal operation.
OBH489--1.qxp 07.8.9 4:27 PM Page 27
28
11-4. Trouble criterion of main partsMUZ-FD25VA MUZ-FD35VAMUZ-FD25VAH MUZ-FD35VAH
Part name FigureCheck method and criterion
Outdoor fan motor (MF)
R.V. coil (21S4)
Expansion valve coil (LEV)
Measure the resistance between the terminals with a tester.(Part temperature –20 ~ 40 ˚C)
WHT – BLKBLK – REDRED – WHT
Normal
Measure the resistance between the terminals with a tester.(Part temperature –10 ~ 40 ˚C)
Normal
1.32 k" ~ 1.62 k"
WHT – REDRED – ORNYLW – BRNBRN – BLU
Normal
40 " ~ 50 "
Measure the resistance with a tester.(Part temperature –10 ~ 40 ˚C)
Measure the resistance with a tester.
Refer to 11-7. "Test point diagram and voltage", 1. "Inverter P.C. board", the chart of thermistor.
Refer to 11-7. "Test point diagram and voltage", 1. "Inverter P.C. board", the chart of thermistor.
Color of the lead wire
Color of the lead wire
Discharge temperaturethermistor (RT62)
Measure the resistance with a tester. Before measurement, hold the thermistor with your hands to warm it up.
Defrost thermistor(RT61)
Fin temperaturethermistor (RT64)
Ambient temperaturethermistor (RT65)
11 " ~ 16 "
Measure the resistance between the terminals with a tester. (Part temperature –20 ~ 40 ˚C)
Compressor (MC) U-VU-WV-W
Normal
0.82 " ~ 1.06 "
Measure the resistance with a tester.(Part temperature –10 ~ 40 ˚C)
2 3
W
UV
1
WHT RED BLK
2 3
W
UV
1
WHT RED BLK
Defrost heater (H)
Normal
349 " ~ 428 "
MUZ-FD25/35VAH
Outdoor heat exchangertemperature thermistor (RT68)
LEV
WHT6
RED1
ORN4
YLW5
BR
N2
BLU
3
OBH489--1.qxp 07.8.9 11:53 AM Page 28
29
Check of open phaseB
How to check inverter/ compressorA
POWER lamp flashes 5-times.Outdoor unit does not operate.
Check the voltagebetween terminals.
Check thecompressor.
Disconnect the connector (CN61)between compressor and the intelligent power module (IPM).
See 11-5.C “Check of compressor” .
No
See 11-5.B “Check of open phase” .
Replace the inverter P.C. board.
Yes
Are the voltagesbalanced?
11-5. Troubleshooting flow
Check of compressor
OK
Replace the compressor.Refer to 11-5.D "Check of compressor winding".Is the compressor normal?
No
No
Yes
Yes
Refer to 11-5.E "Check of compressor operation time". Does the compressor operate continuously?
Refer to 11-5.F "Check of compressor start failure".
C
●With the connector between the compressor and the intelligent power module disconnected, activate the inverter and check if the inverter is normal by measuring the balance of voltage between the terminals.
<< Operation method>> Start cooling or heating operation by pressing EMERGENCY OPERATION switch on
the indoor unit. (Test run operation : refer to 8-3.)<<Measurement point>>
at 3 pointsBLK (U)-WHT (V)BLK (U)-RED (W) WHT(V)-RED (W)
NOTE: 1. Output voltage varies according to power supply voltage. 2. Measure the voltage by analog type tester. 3. During this check, LED of inverter P.C. board flashes 9 times. (Refer to 11-6.1.)
Output voltage 115 V
w Measure AC voltage between the lead wires at 3 points.
9-time flash
2.5-second OFF
OBH489--1.qxp 07.8.9 11:53 AM Page 29
30
Check of compressor winding
Check of compressor operation time
● Disconnect the connector (CN61) between the compressor and intelligent power module, and measure the resistance between the compressor terminals.
<<Measurement point>>at 3 points BLK-WHTBLK-REDWHT-RED
<<Judgement>>Refer to 11-4.0["] ···············Abnormal [short]Infinite["] ·······Abnormal [open]NOTE: 1. Be sure to zero the ohmmeter before measurement.
w Measure the resistance between the lead wires at 3 points.
●Connect the compressor and activate the inverter. Then measure thetime until the inverter stops due to over current.
<<Operation method>> Start heating or cooling operation by pressing EMERGENCY OPERATION switch on the indoor unit.
(Test run operation : Refer to 8-3.)<<Measurement>> Measure the time from the start of compressor to the stop of compressor
due to over current.
0 second
10 seconds
10 minutes
1 second
2 seconds
Normal
Abnormal(Refrigerant circuit defect)(closed valve)
Abnormal (Poor contact,)(Outdoor P.C.board defect)(disconnected connector)
Abnormal (Compressor lock out)(Starting defect)
Abnormal(IPM failure)(Compressor winding short)
Compressor starts
<<Judgement>> For reference
D
E
Check of compressor start failureF
Yes
No
Yes
Confirm that 1~4 is normal.•Electrical circuit check1Contact of the compressor connector (including CN61)2Output voltage of inverter P.C.board and balance of them (See 11-5.B)3Direct current voltage between DB61(+) and (-) on inverter P.C.board 4Voltage between outdoor terminal block S1-S2
Check the refrigerant circuit.Check the stop valve.
w1Heat the compressor with a drier for about 20 minutes.Do not recover refrigerantgas while heating.
Compressor start failure. Activate pre-heat control.(Refer to 10-2. "PRE-HEAT CONTROL SETTING")
After the compressor is heated with a drier, does the compressor start? w1
Does the compressor run for 10 secondsor more after it starts?
No Replace the compressor
Heating part
OBH489--1.qxp 07.8.9 11:53 AM Page 30
31
Check of outdoor thermistorsG
POWER lamp flashes 6-time.The thermistors in the outdoor unit are abnormal.
Check of R.V. coilH
Disconnect connector (CN61) between the compressor and intelligent power module.Turn ON the power supply and press EMERGENCY OPERATION switch twice (HEAT mode).
Is there 230 VAC between CN7211 and 2 on the inverter P.C.board 3 minutes after the power supply is turned ON?
Yes
No Replace the inverterP.C.board.
Replace the 4-way valve.
Replace the 4-way valve.
Disconnect connector (CN61) between the compressor and the intelligent power module.Turn ON the power supply and press EMERGENCY OPERATION switch once (COOL mode).
Is there 230 VAC between CN7211 and 2 on the inverter P.C.board 3 minutes after the power supply is turned ON?
No
Yes
w First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 11-4.w In case CN721 is not connected or R.V. coil is open, voltage is generated between the terminal pins of the connector although any signal is not being transmitted to R.V. coil. Check if CN721 is connected.
CN721
Inverter P.C.board(Soldered side)
Replace the inverterP.C.board.
Unit operates COOL mode even if it is set to HEAT mode.
Unit operates HEAT mode even if it is set to COOL mode.
Yes
Yes
No
No
Reconnect the connector of thermistor. Turn ON the power supply and press EMERGENCY OPERATION switch.
Defrost Discharge temperature Fin temperatureAmbient temperatureOutdoor heat exchanger termperature
Thermistor Board
Inverter P.C. board
RT61RT62RT64RT65RT68
Between CN641 pin1 and pin2Between CN641 pin3 and pin4Between CN642 pin1 and pin2Between CN643 pin1 and pin2Between CN644 pin1 and pin3
Is the thermistor normal? (Refer to 11-6.1.)
Does the unit operate for 10 minutes or more withoutshowing thermistor abnormality?
Replace the thermistor except RT64.When RT64 is abnormal, replace the inverter P.C. board.
OK.(Cause is poor contact.)
Replace the inverter P.C.board.
Disconnect the connector of thermistor in the outdoor P.C.board (see below table), and measure the resistance of thermistor.
OBH489--2.qxp 07.8.9 11:54 AM Page 31
32
Check of outdoor fan motorI
Outdoor fan motor does not operate.
No
Yes
Is the outdoor fan motor normal?(Refer to 11-4.)
Replace the inverter P.C. board.
Disconnect CN932 from the inverter P.C. board,and measure the resistance of the outdoor fan motor.
Replace the outdoor fanmotor.
Check of power supplyJ
Inverter does not operate.
Disconnect the connector(CN61) between compressor and intelligent power module.Turn ON power supply and press EMERGENCY OPERATION switch.
Check the electric parts in main circuit.
If light up, ok.If flash, refer to 11-3.
Is there voltage 280 ~ 370 VDC between DB61 (+) and DB61 (–) on the inverter P.C. board?(Refer to 11-6.1.)
Dose LED on the inverter P.C. board light up or flash? (Refer to 11-6.1.)
Yes
Yes
Yes
No
No
Replace the indoor electronic control P.C. board.
No
Yes
No Replace the inverter P.C. board.
DB61
280~370 VDC
Inverter P.C. board(Solder side)
Is there voltage 230 VAC between the indoor terminal block S1 and S2?
Rectify indoor/ outdoor connecting wire.
Does POWER lamp on the indoor unit light up?
OBH489--2.qxp 07.8.9 11:54 AM Page 32
33
Check of LEV (Expansion valve)K
Heating/Cooling does not work sufficiently.
Replace the LEV.
Expansion valve operates in full-opening direction.
Is LEV properly fixed to the expansion valve?
OK
Do you hear the expansion valve "click, click·······"?Do you feel the expansion valve vibrate on touching it ?
Does the resistance of LEV have the characteristics?(Refer to 11-4.)
Measure each voltage between connector pins of CN724 on the inverter P.C. board.1.Pin3(-) Pin1(+)2.Pin4(-) Pin1(+)3.Pin5(-) Pin1(+)4.Pin6(-) Pin1(+)Is there about 3~5 VAC between each?NOTE: Measure the voltage by an analog tester.
No
Yes
Yes
Yes
No
Yes
No
NoProperly fix the LEV to the expansion valve.
Replace the inverter P.C. board.
NOTE : After check of LEV, do the undermentioned operations.1. Turn OFF the power supply and turn ON it again.2. Press RESET button on the remote controller.
Replace the LEV.
W1. Regardless of normal or abnormal condition, a short beep is emitted once the signal is received.
Turn ON the power supply.<Preparation of the remote controller>1 While pressing both OPERATION SELECT button and TOO COOL button on the remote
controller at the same time, press RESET button.2 First, release RESET button. And release the other two buttons after all LCD
except the set temperature in operation display section of the remote controller is displayed after 3 seconds.
Press OPERATE/STOP(ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. W1
OBH489--2.qxp 07.8.9 11:54 AM Page 33
34
Check of inverter P.C. boardL
Yes(10-time flash)
Yes
Check the LED indication onthe inverter P.C. board.Does the LED flash 10-time?
No
No
Is the fuse (F901) blown on the inverter P.C. board?
Replace the inverter P.C. board.
CN932
Inverter P.C.board(Solder side)
Check the corresponding parts following LED indication.(Refer to 11-3.)
Operate the outdoor unit by starting EMERGENCY OPERATION.
Check the connection of the connector (CN932) of outdoor fan motor. If the connection is poor, make it correct.
Check the outdoor fan motor. (Refer to11-5.I.)
Outdoor fan motor does not operate , or stops immediately after starting up.
OBH489--2.qxp 07.8.9 11:54 AM Page 34
35
How to check miswiring and serial signal error (when outdoor unit does not work)M
• Unit cannot operate neither by the remote controller nor by EMERGENCY OPERATION switch.Indoor unit does not operate.
• POWER lamp flashes ON and OFF every 0.5-second.Outdoor unit doesn’t operate.
Is there rated voltage in the power supply?
Is there any miswiring, poor contact, or wire disconnection of the indoor/outdoor connecting wire?
W1. Miswiring may damage indoor electronic control P.C. board during the operation. Be sure to confirm the wiring is correct before the operation starts.W3.Be sure to check this within 3 minutes after turning ON. After 3 minutes, LED blinks 6 times. Even when the inverter P.C.board is normal, LED blinks 6 times after 3 minutes.
(Lighted or not lighted)
No
Yes
No
Yes
Yes
No
Yes
No Yes
W2 Be careful to the residual voltage of smoothing capacitor.
Be sure to release the failure-moderecall function after checking.
No
No
Yes
No
Yes
Yes
Yes
No Yes
Turn OFF the power supply.
Turn ON the power supply.
Is there rated voltage betweenoutdoor terminal block S1 andS2?
Does AREA-L lamp light up? <Confirmation of the power to the indoor unit>
Press EMERGENCY OPERATION switch once.
Check the powersupply.
A
Turn OFF the power supply.Check once more if the indoor/outdoorconnecting wire is not miswiring.Short-circuit outdoor terminal block S2 andS3.W1
B
Turn ON the power supply.
Check the wiring.
Correct them.
Turn OFF the power supply.Remove the short-circuit betweenoutdoor terminal block S2 and S3.Turn ON the power supply.Is there amplitude of 10 to 20 VDCbetween outdoor terminal block S2and S3? <Confirmation of serialsignal>
Is there rated voltage between indoorterminal block S1 and S2?<Confirmation of power voltage>
Replace the indoor electronic control P.C. board.
Replace the inverterP.C. board.W2
Is there any error of theindoor/outdoor connecting wire,such as the damage of the wire,intermediate connection, poorcontact to the terminal block?
Is there any error of theindoor/outdoor connecting wire,such as the damage of the wire,intermediate connection, poorcontact to the terminal block?
No
Replace theindoor/outdoorconnecting wire.
Replace theindoor/outdoorconnecting wire.
Is serial signalerror indicated 6 minutes later?
Yes
No
· Turn OFF inverter-controlled lighting equipment.
· Turn OFF the power supply and then turn ON again.
· Press EMERGENCY OPERATION switch.
B
· Reinstall either the unit or the light each other away.
· Attach a filter on remote control receiving section of the indoor unit.
A
Is serial signal error indicated 6 minutes later?
No
Does the LED on the inverter P.C. boardrepeat "3.6-second-OFF and 0.8-second-quick blinking"?W3
OBH489--2.qxp 07.8.9 4:30 PM Page 35
36
Electromagnetic noise enters into TV sets or radiosN
Replace or repair the antenna.Replace or repair the coaxial cable.
No
No
No
Yes
Yes
No
No
Yes
Yes
Yes
Is the distance between theantennas and the indoorunit within 3 m, or is thedistance between theantennas and the outdoorunit within 3 m?
Is the distance between theTV sets or radios and theindoor unit within 1 m, or isthe distance between the TVsets or radios and theoutdoor unit within 3 m?
Are the antennas damaged?Is the coaxial cable damaged?Is there any poor contact inthe antenna wiring?
Is the indoor/outdoorconnecting wire of the airconditioner and the wiring ofthe antennas close?
Even if all of the above conditions are fulfilled, the electromagnetic noise may enter, depending on the electric field strength or the installation condition (combination of specific conditions such as antennas or wiring).Check the followings before asking for service.1.Devices affected by the electromagnetic noise TV sets, radios (FM/AM broadcast, shortwave)2.Channel, frequency, broadcast station affected by the electromagnetic noise3.Channel, frequency, broadcast station unaffected by the electromagnetic noise4.Layout of ; indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, erath wire, antennas, wiring from antennas, receiver5.Electric field intensity of the broadcast station affected by the electromagnetic noise6.Presence or absence of amplifier such as booster7.Operation condition of air conditioner when the electromagnetic noise enters in 1)Turn OFF the power supply once, and then turn ON the power supply. In this situation, check for the electromagnetic noise. 2)Within 3 minutes after turning ON the power supply, press OPERATE/STOP (ON/OFF) button on the remote controller for power ON, and check for the electromagnetic noise. 3)After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the electromagnetic noise. 4)Press OPERATE/STOP (ON/OFF) button on the remote controller for power OFF, when the outdoor unit stops but the indoor/outdoor communication still runs on. In this situation, check for the electromagnetic noise.
Is the unit earthed? Earth the unit.
Extend the distance betweenthe antennas and the indoorunit, and/or the antennas andthe outdoor unit.
Extend the distance betweenthe TV sets and/or radios andthe indoor unit, or the TV setsor radios and the outdoor unit.
Extend the distance betweenthe indoor/outdoor connectingwire of the air conditioner andthe wiring of the antennas.
OBH489--2.qxp 07.8.9 11:54 AM Page 36
37
Check of defrost heaterO
Replace the inverter P.C. board.
Is there 230 VAC between CN722 1 and 3 on the inverter P.C. board? Refer to 11-6.
Yes
No
No problem of the inverter P.C. board.
NOTE: In case both thermistors are more than the above temperature, cool them with cold water etc...
In HEAT mode, for more than 5 minutes, let the ambient temperature thermistor continue to read 5 : or below, and let the defrost thermistor continue to read -1 : or below.
Check the following points before checking electric continuity.1) Does the resistance of ambient temperature thermistor have the characteristics? Refer to 11-6.1.2) Is the resistance of defrost heater normal? Refer to 11-4.3) Does the heater protector remain conducted (not open)?4) Are both ambient temperature thermistor and circuit of defrost heater securely connected to connectors?
Outdoor base gets frozen.
MUZ-FD25VAH MUZ-FD35VAH
OBH489--2.qxp 07.8.9 11:54 AM Page 37
38
-20 -10 0 10 20 30 400
10
20
30
40
50
60
70
80
90
100
Temperature(:)
Defrost thermistor(RT61)Ambient temperature thermistor(RT65)Outdoor heat exchanger temperature thermistor(RT68)
Temperature(:)
Discharge temperature thermistor(RT62)
0 10 20 30 40 50 60 70 80 90 100 110 1200
100
200
300
400
500
600
700
0 10 20 30 40 50 60 70 800
20
40
60
80
100
120
140
160
180
200
Temperature(:)
Fin temperature thermistor(RT64)
Res
ista
nce
(k"
)
Res
ista
nce
(k"
)
Res
ista
nce
(k"
)
1. Inverter P.C. board
MUZ-FD25VAMUZ-FD25VAH
11-6. Test point diagram and voltage
Back side of unit
Fin
tem
pera
ture
ther
mis
tor
/RT
64(C
N64
2)
Am
bien
t te
mpe
ratu
re
ther
mis
tor
/RT
65(C
N64
3)
Dis
char
ge t
empe
ratu
reth
erm
isto
r /R
T62
(CN
641)
Def
rost
the
rmis
tor
/RT
61(C
N64
1)
LEVconnector(CN724)
DB61DC260 ~300 V
Front side of unit
AC230V
Smoothingcapacitor(C62)
Output to drivecompressor(LDU,LDV,LDW)
(+)(-)
Fuse(F701)250 V 3.15 A
MUZ-FD35VAMUZ-FD35VAH Smoothing
capacitor(C61)
Smoothingcapacitor(C63)
Fuse(F801)250 V 3.15 A
Fuse(F901)250 V 3.15 A
Heaterconnector(CN722)MUZ-FD•VAH
R.V.coil(CN721)230 VAC
Jumper wire for changing defrost setting (JS)
Out
put
to d
rive
outd
oor
fan
mot
or (
CN
932)
AC230 V
Out
door
hea
t ex
chan
ger
tem
pera
ture
the
rmis
tor
/RT
68(C
N64
4)
Jumper wire for pre-heat control setting(JK)
OBH489--2.qxp 07.8.9 11:54 AM Page 38
39
1. Removing the cabinet(1) Remove the screw fixing the service panel. (See Photo 2.)(2) Pull down the service panel and remove it. (See Photo 2.)(3) Disconnect the power supply and indoor/outdoor connecting wire.(4) Remove the screws fixing the top panel. (See Photo 1.)(5) Remove the top panel. (See Photo 1.)(6) Remove the screws fixing the cabinet.(7) Remove the cabinet.(8) Remove the screws fixing the back panel.(9) Remove the back panel.
12 DISASSEMBLY INSTRUCTIONS
OPERATING PROCEDURE PHOTOS
(1) Slide the sleeve and check if there is a locking lever or not. (2) The terminal with this connector has the locking mechanism.
1Slide the sleeve.2Pull the terminal while pushing the locking lever.
1Hold the sleeve, and pull out the terminal slowly.
The terminal which has the locking mechanism can be detached as shown below.There are two types ( Refer to (1) and (2)) of the terminal with locking mechanism.The terminal without locking mechanism can be detached by pulling it out.Check the shape of the terminal before detaching.
<"Terminal with locking mechanism" Detaching points>
Connector
Sleeve
Locking lever
12-1. MUZ-FD25VA MUZ-FD25VAHMUZ-FD35VA MUZ-FD35VAH NOTE : Turn OFF power supply before disassembling.
Photo 1
Photo 2
Screw of theservice panel
Direction to remove
Back panel
Servicepanel
Screw of the cabinet
Screws ofthe top panel
Screws of the cabinet
Screws of the cabinet
Screws ofthe top panel
Hooks
OBH489--2.qxp 07.8.21 8:33 AM Page 39
40
4. Removing the discharge temperature thermistor,defrost thermistor and outdoor heat exchanger tem-perature thermistor.(1) Remove the cabinet and panels. (Refer to 1.)(2) Pull out the discharge temperature thermistor from its
holder. (See Photo 5.)(3) Pull out the defrost thermistor from its holder. (See Photo
6.)(4) Pull out the outdoor heat exchanger temperature thermistor
from its holder. (See Photo 6.)
Photo 5
Discharge temperature thermistor
OPERATING PROCEDURE PHOTOS
2. Removing the inverter assembly, inverter P.C. board(1) Remove the cabinet and panels. (Refer to 1.)(2) Disconnect the lead wire to the reactor and the following
connectors;<Inverter P.C. board>CN721 (R.V.coil)CN722 (Defrost heater)CN932 (Fan motor)CN641 (Defrost thermistor and discharge temperature
thermistor)CN643 (Ambient temperature thermistor) CN644 (Outdoor heat exchanger temperature thermistor)CN724 (LEV)
(3) Remove the compressor connector (CN61).(4) Remove the screws fixing the relay panel. (See Photo 3.)(5) Remove the inverter assembly. (See Photo 4.)(6) Remove the screw of the earth wire and screw of the
T.B.support. (See Photo 4.)(7) Remove the inverter P.C. board from the inverter assembly.
Photo 3
Photo 4 (inverter assembly)
Heat sink
3. Removing R.V. coil (1) Remove the cabinet and panels. (Refer to 1.)(2) Remove the R.V. coil. (See Photo 5.)
InverterP.C. board
Screws of therelay panel
Screw of theearth wire
T.Bsupport
Screw of theT.Bsupport
R.V. coil
OBH489--2.qxp 07.8.9 11:54 AM Page 40
41
OPERATING PROCEDURE PHOTOS
Photo 6
Defrostthermistor
5. Removing outdoor fan motor(1) Remove the cabinet and panels. (Refer to 1.)(2) Disconnect the connectors for outdoor fan motor.(3) Remove the propeller nut. (See Photo 7.)(4) Remove the propeller. (See Photo 7.)(5) Remove the screws fixing the fan motor. (See Photo 7.)(6) Remove the fan motor.
Photo 8
6. Removing the compressor and 4-way valve(1) Remove the cabinet and panels. (Refer to 1.)(2) Remove the inverter assembly. (Refer to 2.)(3) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure gauge shows 0 kg/cm2 (0 MPa).
(4) Detach the welded part of the suction and the dischargepipe connected with compressor.
(5) Remove the nuts of compressor legs.(6) Remove the compressor.(7) Detach the welded part of pipes connected with 4-way
valve. (See Photo 8.)
Photo 7
Propeller
Screws of the outdoor fan motor
Welded parts of 4-way valve
Outdoor heatexchanger tempera-ture thermistor
Propeller nut
OBH489--2.qxp 07.8.9 11:55 AM Page 41
42
OBH489--2.qxp 07.8.9 11:55 AM Page 42
43
OBH489--2.qxp 07.8.9 11:55 AM Page 43
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
CC Copyright 2007 MITSUBISHI ELECTRIC ENGINEERING CO.,LTDDistributed in Aug. 2007. No. OBH489 6Made in Japan
New publication, effective Aug. 2007Specifications subject to change without notice.
OBH489--2.qxp 07.8.9 11:55 AM Page 44