Service Facts © 2004 American Standard Inc. All Rights Reserved NOTICE: Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to change design and specifications without notice. B - FURNACES PRODUCT SPECIFICATIONS 1 MODEL TYPE RATINGS 2 1st Stage Input BTUH 1st Stage Capacity BTUH (ICS) 3 2nd Stage Input BTUH 2nd Stage Capacity BTUH (ICS) 3 Temp. rise (Min.-Max.) °F. BLOWER DRIVE Diameter - Width (In.) No. Used Speeds (No.) CFM vs. in. w.g. Motor HP R.P.M. Volts / Ph / Hz COMBUSTION FAN - Type Drive - No. Speeds Motor HP - RPM Volts / Ph / Hz FLA FILTER — Furnished? Type Recommended Hi Vel. (No.-Size-Thk.) VENT — Size (in.) HEAT EXCHANGER Type -Fired -Unfired Gauge (Fired) ORIFICES — Main Nat. Gas. Qty. — Drill Size L.P. Gas Qty. — Drill Size GAS VALVE PILOT SAFETY DEVICE Type BURNERS — Type Number POWER CONN. — V / Ph / Hz 4 Ampacity (In Amps) Max. Overcurrent Protection (Amps) PIPE CONN. SIZE (IN.) DIMENSIONS Crated (In.) WEIGHT Shipping (Lbs.) / Net (Lbs) *UY080R9V3W Upflow / Horizontal 52,000 48,000 80,000 73,000 35 - 65 DIRECT 10 x 8 1 Variable See Fan Performance Table 1/2 Variable 115/1/60 Centrifugal Direct - Variable 1/50 - 5000 33 - 110/3/60 - 180 1.0 Yes High Velocity 1 - 17x25 - 1 in. 2 Round Aluminized Steel - Type I 20 4 — 45 4 — 56 Redundant - Two Stage Hot Surface Igniter Multiport Inshot 4 115/1/60 11.1 15 1/2 H x W x D 41-3/4 x 19-1/2 x 30-1/2 168 / 156 Gas Furnace – Var. Speed Blower – Var. Speed Inducer – Two Stage Heat – Direct Vent Models: * - First letter may be “A” or “T” *UY060R9V3W *DY060R9V3W *UY080R9V3W *DY080R9V3W *UY100R9V4W *DY100R9V4W *UY120R9V5W *DY120R9V5W Page B-648-435 W.M. 7/04 IMPORT ANT — This document contains a wiring diagram and service information. This is customer property and is to remain with this unit. Please return to service information pack upon completion of work. DISCONNECT POWER BEFORE SERVICING WARNING *UY060R9V3W Upflow / Horizontal 39,000 37,000 60,000 56,000 35 - 65 DIRECT 10 x 8 1 Variable See Fan Performance Table 1/2 Variable 115/1/60 Centrifugal Direct - Variable 1/50 - 5000 33 - 110/3/60 - 180 1.0 Yes High Velocity 1 - 17x25 - 1 in. 2 Round Aluminized Steel - Type I 20 3 — 45 3 — 56 Redundant - Two Stage Hot Surface Igniter Multiport Inshot 3 115/1/60 11.1 15 1/2 H x W x D 41-3/4 x 19-1/2 x 30-1/2 158 / 146 *UY100R9V4W Upflow / Horizontal 65,000 60,000 100,000 93,000 35 - 65 DIRECT 10 x 10 1 Variable See Fan Performance Table 1 Variable 115/1/60 Centrifugal Direct - Variable 1/50 - 5000 33 - 110/3/60 - 180 1.0 Yes High Velocity 1 - 20x25 - 1 in. 3 Round Aluminized Steel - Type I 20 5 — 45 5 — 56 Redundant - Two Stage Hot Surface Igniter Multiport Inshot 5 115/1/60 13.5 20 1/2 H x W x D 41-3/4 x 23 x 30-1/2 197 / 185 *UY120R9V5W Upflow / Horizontal 78,000 72,000 120,000 112,000 40 - 70 DIRECT 10 x 10 1 Variable See Fan Performance Table 1 Variable 115/1/60 Centrifugal Direct - Variable 1/50 - 5000 33 - 110/3/60 - 180 1.0 Yes High Velocity 1 - 24x25 - 1 in. 3 Round Aluminized Steel - Type I 20 6 — 45 6 — 56 Redundant - Two Stage Hot Surface Igniter Multiport Inshot 6 115/1/60 17.5 30 1/2 H x W x D 41-3/4 x 26-1/2 x 30-1/2 206 / 193 1 Central Furnace heating designs are certified by AGA and CSA. 2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level. 3 Based on U.S. government standard tests. 4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes. X341119P10

Upload: others

Post on 29-Mar-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Service Facts X341119P10 Gas Furnace – Var. Speed Blower – … Info/Furnace Service Facts/TUYsf.pdf · within the 4 second ignition trial period. As the flame sensor confirms

Service Facts

© 2004 American Standard Inc. All Rights Reserved

NOTICE: Since the manufacturer has a policy of continuous product and product data improvement,it reserves the right to change design and specifications without notice.

B - F

UR

NA

CE

S

PRODUCT SPECIFICATIONS 1MODELTYPERATINGS 21st Stage Input BTUH

1st Stage Capacity BTUH (ICS) 32nd Stage Input BTUH

2nd Stage Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)HEAT EXCHANGERType-Fired

-UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs)

*UY080R9V3WUpflow / Horizontal

52,00048,00080,00073,00035 - 65

DIRECT10 x 8

1Variable

See Fan Performance Table1/2

Variable115/1/60

CentrifugalDirect - Variable

1/50 - 500033 - 110/3/60 - 180

1.0Yes

High Velocity1 - 17x25 - 1 in.

2 Round

Aluminized Steel - Type I

20

4 — 454 — 56

Redundant - Two Stage

Hot Surface IgniterMultiport Inshot

4115/1/60

11.1151/2

H x W x D41-3/4 x 19-1/2 x 30-1/2

168 / 156

Gas Furnace – Var. Speed Blower –Var. Speed Inducer – Two Stage Heat –Direct VentModels: * - First letter may be “A” or “T”

*UY060R9V3W *DY060R9V3W*UY080R9V3W *DY080R9V3W*UY100R9V4W *DY100R9V4W*UY120R9V5W *DY120R9V5W

Page B-648-435W.M. 7/04

IMPORTANT — This document contains a wiring diagram and service information. This is customer property and is toremain with this unit. Please return to service information pack upon completion of work.

DISCONNECT POWER BEFORE SERVICINGWARNING

*UY060R9V3WUpflow / Horizontal

39,00037,00060,00056,00035 - 65

DIRECT10 x 8

1Variable

See Fan Performance Table1/2

Variable115/1/60

CentrifugalDirect - Variable

1/50 - 500033 - 110/3/60 - 180

1.0Yes

High Velocity1 - 17x25 - 1 in.

2 Round

Aluminized Steel - Type I

20

3 — 453 — 56

Redundant - Two Stage

Hot Surface IgniterMultiport Inshot

3115/1/60

11.1151/2

H x W x D41-3/4 x 19-1/2 x 30-1/2

158 / 146

*UY100R9V4WUpflow / Horizontal

65,00060,000

100,00093,00035 - 65

DIRECT10 x 10

1Variable

See Fan Performance Table1

Variable115/1/60

CentrifugalDirect - Variable

1/50 - 500033 - 110/3/60 - 180

1.0Yes

High Velocity1 - 20x25 - 1 in.

3 Round

Aluminized Steel - Type I

20

5 — 455 — 56

Redundant - Two Stage

Hot Surface IgniterMultiport Inshot

5115/1/60

13.5201/2

H x W x D41-3/4 x 23 x 30-1/2

197 / 185

*UY120R9V5WUpflow / Horizontal

78,00072,000120,000112,00040 - 70

DIRECT10 x 10

1Variable

See Fan Performance Table1

Variable115/1/60

CentrifugalDirect - Variable

1/50 - 500033 - 110/3/60 - 180

1.0Yes

High Velocity1 - 24x25 - 1 in.

3 Round

Aluminized Steel - Type I

20

6 — 456 — 56

Redundant - Two Stage

Hot Surface IgniterMultiport Inshot

6115/1/60

17.5301/2

H x W x D41-3/4 x 26-1/2 x 30-1/2

206 / 193

1 Central Furnace heating designs are certified by AGA and CSA.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level.

For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.

X341119P10

Page 2: Service Facts X341119P10 Gas Furnace – Var. Speed Blower – … Info/Furnace Service Facts/TUYsf.pdf · within the 4 second ignition trial period. As the flame sensor confirms

2 Page B-648-435

Service FactsPRODUCT SPECIFICATIONS 1

MODELTYPERATINGS 21st Stage Input BTUH

1st Stage Capacity BTUH (ICS) 32nd Stage Input BTUH

2nd Stage Capacity BTUH (ICS) 3Temp. rise (Min.-Max.) °F.BLOWER DRIVEDiameter - Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts / Ph / HzCOMBUSTION FAN - TypeDrive - No. SpeedsMotor HP - RPMVolts / Ph / HzFLAFILTER — Furnished?Type RecommendedHi Vel. (No.-Size-Thk.)VENT — Size (in.)HEAT EXCHANGERType -Fired

-UnfiredGauge (Fired)ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill SizeGAS VALVEPILOT SAFETY DEVICETypeBURNERS — TypeNumberPOWER CONN. — V / Ph / Hz 4Ampacity (In Amps)Max. Overcurrent Protection (Amps)PIPE CONN. SIZE (IN.)DIMENSIONSCrated (In.)WEIGHTShipping (Lbs.) / Net (Lbs)

*DY080R9V3WDownflow / Horizontal

52,00048,00080,00074,00035 - 65

DIRECT10 x 8

1Variable

See Fan Performance Table1/2

Variable115/1/60

CentrifugalDirect - Variable

1/50 - 500033 - 110/3/60 - 180

1.0Yes

High Velocity2 - 14x20 - 1 in.

2 Round

Aluminized Steel - Type I

20

4 — 454 — 56

Redundant - Two Stage

Hot Surface IgniterMultiport Inshot

4115/1/60

11.1151/2

H x W x D41-3/4 x 19-1/2 x 30-1/2

168 / 158

*DY120R9V5WDownflow / Horizontal

78,00072,000

120,000112,00040 - 70

DIRECT10 x 10

1Variable

See Fan Performance Table1

Variable115/1/60

CentrifugalDirect - Variable

1/50 - 500033 - 110/3/60 - 180

1.0Yes

High Velocity2 - 16x20 - 1 in.

3 Round

Aluminized Steel - Type I

20

6 — 456 — 56

Redundant - Two Stage

Hot Surface IgniterMultiport Inshot

6115/1/60

17.5301/2

H x W x D41-3/4 x 26-1/2 x 30-1/2

206 / 196

*DY100R9V4WDownflow / Horizontal

65,00060,000

100,00094,00035 - 65

DIRECT10 x 10

1Variable

See Fan Performance Table3/4

Variable115/1/60

CentrifugalDirect - Variable

1/50 - 500033 - 110/3/60 - 180

1.0Yes

High Velocity2 - 16x20 - 1 in.

3 Round

Aluminized Steel - Type I

20

5 — 455 — 56

Redundant - Two Stage

Hot Surface IgniterMultiport Inshot

5115/1/60

13.5201/2

H x W x D41-3/4 x 23 x 30-1/2

185 / 175

*DY060R9V3WDownflow / Horizontal

39,00036,00060,00056,00035 - 65

DIRECT10 x 8

1Variable

See Fan Performance Table1/2

Variable115/1/60

CentrifugalDirect - Variable

1/50 - 500033 - 110/3/60 - 180

1.0Yes

High Velocity2 - 14x20 - 1 in.

2 Round

Aluminized Steel - Type I

20

3 — 453 — 56

Redundant - Two Stage

Hot Surface IgniterMultiport Inshot

3115/1/60

11.1151/2

H x W x D41-3/4 x 19-1/2 x 30-1/2

160/ 146

1 Central Furnace heating designs are certified by AGA and CSA.2 For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level.

For Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.3 Based on U.S. government standard tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.

Page 3: Service Facts X341119P10 Gas Furnace – Var. Speed Blower – … Info/Furnace Service Facts/TUYsf.pdf · within the 4 second ignition trial period. As the flame sensor confirms

Page B-648-435 3

Service FactsSAFETY SECTION

WARNING!CARBON MONOXIDE POISONING HAZARD

Failure to follow the installation instructions for the ventingsystem being placed into operation could result in carbonmonoxide poisoning or death.

WARNING!FIRE OR EXPLOSION HAZARD

Failure to follow the safety warnings exactly could result inserious injury, death or property damage.

Never test for gas leaks with an open flame. Use a com-mercially available soap solution made specifically for thedetection of leaks to check all connections. A fire orexplosion may result causing property damage, personalinjury, or loss of life.

WARNING!FIRE OR EXPLOSION HAZARD

Failure to follow the safety warnings exactly could result inserious injury, death or property damage.

Improper servicing could result in dangerous operation,serious injury, death, or property damage.

WARNING!BODILY INJURY CAN RESULT FROM HIGH VOLTAGEELECTRICAL COMPONENTS, FAST MOVING FANS, ANDCOMBUSTIBLE GAS. FOR PROTECTION FROM THESEINHERENT HAZARDS DURING INSTALLATION ANDSERVICING, THE ELECTRICAL SUPPLY MUST BEDISCONNECTED AND THE MAIN GAS VALVE MUST BETURNED OFF. IF OPERATING CHECKS MUST BEPERFORMED WITH THE UNIT OPERATING, IT IS THETECHNICIAN’S RESPONSIBILITY TO RECOGNIZE THESEHAZARDS AND PROCEED SAFELY.

CAUTION!The integrated furnace control is polarity sensitive. The hotleg of the 115 VAC power must be connected to the BLACKfield lead.

WARNING!The cabinet must have an uninterrupted or unbrokenground according to National Electrical Code, ANSI/NFPA 70 - “latest edition” and Canadian Electrical Code,CSA C22.1 or local codes to minimize personal injury if anelectrical fault should occur. A failure to follow this warn-ing could result in an electrical shock, fire, injury, or death.

CARBON MONOXIDE POISONING HAZARD

Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death.

The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:

1. Seal any unused openings in the venting system.

2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or the CAN/CGA B149 Installation Codes and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.

3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other deficiencies which could cause an unsafe condition.

4. Close fireplace dampers.

5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan.

6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so appliance is operating continuously.

7. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z221.1/NFPA 54 and/or CAN/CGA B149 Installation Codes.

8. After it has been determined that each appliance connected to the venting system properly vents where tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas -fired burning appliance to their previous conditions of use.

WARNING!

Page 4: Service Facts X341119P10 Gas Furnace – Var. Speed Blower – … Info/Furnace Service Facts/TUYsf.pdf · within the 4 second ignition trial period. As the flame sensor confirms

4 Page B-648-435

Service FactsSEQUENCE OF OPERATION

Thermostat call for heat (2-stage thermostat)Call for 1st stage only:W1 thermostat contacts close signaling the control module torun its self-check routine. After the control module hasverified that the 1st stage pressure switch contacts are openand the limit switch(es) contacts are closed, the draft blowerwill be energized.

As the induced draft blower comes up to speed, the pressureswitch contacts will close and the ignitor warm-up period willbegin. The ignitor will heat for approx. 20 seconds, then thegas valve is energized in 1st stage to permit gas flow to theburners.

The flame sensor confirms that ignition has been achievedwithin the 4 second ignition trial period.

As the flame sensor confirms that ignition has been achieved,the delay to fan ON period begins timing and after approx.45 seconds the indoor blower motor will be energized at lowspeed and will continue to run during the heating cycle.

Call for 2nd stage after 1st stage:W2 thermostat contacts close signaling a call for 2nd stageheat. After a 30 second delay, the induced draft blower willbe energized on high speed and the 2nd stage pressure switchcontacts will close. The gas valve is energized in 2nd stageand the indoor blower motor in high speed.

2nd stage satisfied, 1st stage still called:W2 thermostat contacts open signaling that 2nd stageheating requirements are satisfied.

The induced draft blower is reduced to low speed allowing the2nd stage pressure switch contacts to open and the gas valveis reduced to 1st stage. The indoor blower motor is reduced tolow speed.

1st stage satisfied:W1 thermostat contacts open signaling that 1st stage heatingrequirements are satisfied. The gas valve will close and theinduced draft blower will be de-energized. The indoor blowermotor will continue to run for the fan off period (Fieldselectable at 60, 100, 140 or 180 seconds), then will be de-energized by the control module.

Thermostat call for heat (1-stage thermostat)W1/W2 (jumpered) thermostat contacts close signaling a callfor heat. 1st stage sequence of operation remains the same asabove. 2nd stage heat will energize after the stage delaytimer (field selectable at .5, 5, 10 or 15 minutes) has expired.

Thermostat satisfied:W1/W2 (jumpered) contacts open signaling the controlmodule to close the gas valve. The induced draft blower isswitched to low speed and de-energized after the post purgetimer has expired. The indoor blower motor will continue tooperate after the flames are extinguished and then isswitched to low heat speed for the FAN-OFF period.

WARNING!Should overheating occur, or the gas supply fail to shut off,shut off the gas valve to the unit before shutting off theelectrical supply. Failure to follow this warning could resultin property damage, personal injury, or death.

Indoor blower operation with thermostat fan switch “ON”:Fan is R-G.R-W energized, fan continues to run without interruption.Heat Low speed if it is a two stage furnace.Heat speed if it is a single stage furnace.

INDOOR BLOWER TIMINGHeating: The integrated furnace control module controlsthe indoor blower. The blower start is fixed at 45 secondsafter ignition. The FAN-OFF period is field selectable bydip switches SW-2, #1 and #2 at 60, 100, 140, or 180seconds. The factory setting is 100 seconds.

W1-W2 stage delay (jumpered together) is field selectable bydip switch SW-1, #1 and #2 at .5, 5, 10 or 15 minutes. Thefactory setting is 10 minutes. (See wiring diagram).

Cooling: The fan delay-off period is set by dip switches onthe Integrated Furnace Control. The options for coolingdelay off is field selectable by dip switches #5 and #6.

The following table and graph explain the delay-off settings:

COOLING OFF - DELAY OPTIONS

SWITCH SETTINGS SELECTION NOMINALAIRFLOW

5 - OFF 6 - OFF NONE SAME

5 - ON 6 - OFF 1.5 MINUTES 100% *

5 - OFF 6 - ON 3 MINUTES 50%

5 - ON 6 - ON ** 50 - 100%

* - This setting is equivalent to BAY24X045 relay benefit

** - This selection provides ENHANCED MODE, which is aramping up and ramping down of the blower speed to provideimproved comfort, quietness, and potential energy savings.See Wiring Diagram notes on the unit or in the Service Factsfor complete wiring setup for ENHANCED MODE. The graphwhich follows, shows the ramping process.

OFF

50%50%

80%

Dehumidify

EfficiencyFast Coil Cooling

1

minute

3

minutes

7.5

minutes

100% if necessary

OFF

WARNING!BODILY INJURY CAN RESULT FROM HIGH VOLTAGEELECTRICAL COMPONENTS, FAST MOVING FANS, ANDCOMBUSTIBLE GAS. FOR PROTECTION FROM THESEINHERENT HAZARDS DURING INSTALLATION ANDSERVICING, THE ELECTRICAL SUPPLY MUST BEDISCONNECTED AND THE MAIN GAS VALVE MUST BETURNED OFF. IF OPERATING CHECKS MUST BE PER-FORMED WITH THE UNIT OPERATING, IT IS THETECHNICIAN’S RESPONSIBILITY TO RECOGNIZE THESEHAZARDS AND PROCEED SAFELY.

CAUTION!The integrated furnace control is polarity sensitive. The hotleg of the 115 VAC power must be connected to the BLACKfield lead.

Page 5: Service Facts X341119P10 Gas Furnace – Var. Speed Blower – … Info/Furnace Service Facts/TUYsf.pdf · within the 4 second ignition trial period. As the flame sensor confirms

Page B-648-435 5

Service FactsPERIODIC SERVICING REQUIREMENTS

WARNING!Disconnect power to the unit before removing the blowerdoor. Allow a minimum of 10 seconds for IFC power supplyto drain to 0 volts. Failure to follow this warning couldresult in property damage, personal injury or death.

WARNING!CARBON MONOXIDE POISONING HAZARD

Failure to follow the service and/or periodic maintenanceinstructions for the furnace and venting system, couldresult in carbon monoxide poisoning or death.

1. GENERAL INSPECTION – Examine the furnaceinstallation annually for the following items:a. All flue product carrying areas external to the furnace

(i.e. chimney, vent connector) are clear and free ofobstruction. A vent screen in the end of the vent (flue)pipe must be inspected for blockage annually.

b. The vent connector is in place, slopes upward and isphysically sound without holes or excessive corrosion.

c. The return air duct connection(s) is physically sound,is sealed to the furnace and terminates outside thespace containing the furnace.

d. The physical support of the furnace should be soundwithout sagging, cracks, gaps, etc., around the base soas to provide a seal between the support and the base.

e. There are no obvious signs of deterioration of the furnace.

2. FILTERS – Filters should be cleaned or replaced (withhigh velocity filters only), monthly and more frequentlyduring high use times of the year such as midsummeror midwinter.

3. BLOWERS – The blower size and speed determine theair volume delivered by the furnace. The blower motorbearings are factory lubricated and under normaloperating conditions do not require servicing. If motorlubrication is required it should only be done by aqualified servicer. Annual cleaning of the blower wheeland housing is recommended for maximum air output,and this must be performed only by a qualified serviceror service agency.

4. IGNITER – This unit has a special hot surface directignition device that automatically lights the burners.Please note that it is very fragile and should be handledwith care.

CAUTION!Do not touch igniter. It is extremely hot.

5. BURNER – Gas burners do not normally requirescheduled servicing, however, accumulation of foreignmaterial may cause a yellowing flame or delayed igni-tion. Either condition indicates that a service call isrequired. For best operation, burners must be cleanedannually using brushes and vacuum cleaner.

Turn off gas and electric power supply. To clean burners,remove burner box cover (6 to 8 screws) and top burnerbracket. Lift burners from orifices.

NOTE:Be careful not to break igniter when removing burners.

Clean burners with brush and/or vacuum cleaner. Re-assemble parts by reversal of the above procedure. Theburner box must be resealed when replacing box cover.

NOTE:On LP (propane) units, some light yellow tipping of theouter mantle is normal. Inner mantle should be bright blue.

Natural gas units should not have any yellow tipped flames.This condition indicates that a service call is required. Forbest operation, burners must be cleaned annually usingbrushes and vacuum cleaner.

NOTE:On LP (propane) units, due to variations in BTU contentand altitude, servicing may be required at shorter intervals.

WARNING!CARBON MONOXIDE POISONING HAZARDFailure to follow the service and/or periodic maintenanceinstructions for the furnace and venting system, couldresult in carbon monoxide poisoning or death.

6. HEAT EXCHANGER/FLUE PIPE – These items must beinspected for signs of corrosion, and/or deterioration at thebeginning of each heating season by a qualified servicetechnician and cleaned annually for best operation. Toclean flue gas passages, follow recommendations below:

a. Turn off gas and electric power supply.

b. Inspect flue pipe exterior for cracks, leaks, holes orleaky joints. Some discoloration of PVC pipe is normal.

c. Remove burner compartment door from furnace.

d. Inspect around insulation covering flue collector box.Inspect induced draft blower connections fromrecuperative cell and to the flue pipe connection.

e. Remove burners. (See 4.)

f. Use a mirror and flashlight to inspect interior of heatexchanger, be careful not to damage the igniter, flamesensor or other components.

g. If any corrosion is present, contact a service agency.Heat exchanger should be cleaned by a qualifiedservice technician.

h. After inspection is complete replace burner box cover,burners, and furnace door.

i. Restore gas supply. Check for leaks using a soapsolution. Restore electrical supply. Check unit fornormal operation.

7. COOLING COIL CONDENSATE DRAIN - If a coolingcoil is installed with the furnace, condensate drainsshould be checked and cleaned periodically to assurethat condensate can drain freely from coil to drain. Ifcondensate cannot drain freely water damage couldoccur. (See Condensate Drain in Installer’s Guide.)

CAUTION!Label all wires prior to disconnection when servicingcontrols. Wiring errors can cause improper anddangerous operation.

Verify proper operation after servicing.

WARNING!NEVER USE AN OPEN FLAME TO TEST FOR GAS LEAKS:AN EXPLOSION COULD OCCUR, CAUSING INJURY ORDEATH.

Page 6: Service Facts X341119P10 Gas Furnace – Var. Speed Blower – … Info/Furnace Service Facts/TUYsf.pdf · within the 4 second ignition trial period. As the flame sensor confirms

6 Page B-648-435

Service Facts

From Drawing No. D342118P01 Rev 1

*UY WIRING DIAGRAM

Page 7: Service Facts X341119P10 Gas Furnace – Var. Speed Blower – … Info/Furnace Service Facts/TUYsf.pdf · within the 4 second ignition trial period. As the flame sensor confirms

Page B-648-435 7

Service Facts

From Drawing No. D342118P01 Rev 1

*UY SCHEMATIC DIAGRAM

Page 8: Service Facts X341119P10 Gas Furnace – Var. Speed Blower – … Info/Furnace Service Facts/TUYsf.pdf · within the 4 second ignition trial period. As the flame sensor confirms

8 Page B-648-435

Service Facts

From Drawing No. D342119P01 Rev 2

*DY WIRING DIAGRAM

Page 9: Service Facts X341119P10 Gas Furnace – Var. Speed Blower – … Info/Furnace Service Facts/TUYsf.pdf · within the 4 second ignition trial period. As the flame sensor confirms

Page B-648-435 9

Service Facts

From Drawing No. D342119P01 Rev 2

*DY SCHEMATIC DIAGRAM

Page 10: Service Facts X341119P10 Gas Furnace – Var. Speed Blower – … Info/Furnace Service Facts/TUYsf.pdf · within the 4 second ignition trial period. As the flame sensor confirms

10 Page B-648-435

Service Facts

*UY060R9V3W FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

OUTDOORUNIT SIZE

(TONS)

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

SW 1 SW 2 SW 3 SW 4 0.1 0.3 0.5 0.7 0.9

1.5

LOW(350 CFM/TON) ON ON OFF ON CFM

WATTS57565

57590

575125

550155 -

NORMAL(400 CFM/TON) ON ON OFF OFF CFM

WATTS64070

640110

640140

630175 -

HIGH(450 CFM/TON) ON ON ON OFF CFM

WATTS70085

700125

700160

700200 -

2.0

LOW(350 CFM/TON) OFF ON OFF ON CFM

WATTS700100

700130

700170

700210 -

NORMAL(400 CFM/TON) OFF ON OFF OFF CFM

WATTS800115

800155

800200

800250 -

HIGH(450 CFM/TON) OFF ON ON OFF CFM

WATTS900140

900195

900240

900290 -

2.5

LOW(350 CFM/TON) ON OFF OFF ON CFM

WATTS875130

875180

875230

875270 -

NORMAL(400 CFM/TON) ON OFF OFF OFF CFM

WATTS1000175

1000235

1000285

1000335

900310

HIGH(450 CFM/TON) ON OFF ON OFF CFM

WATTS1125235

1125295

1125345

1100370

925318

3

LOW(350 CFM/TON) OFF OFF OFF ON CFM

WATTS1050195

1050260

1050305

1050350

920315

NORMAL(400 CFM/TON) OFF OFF OFF OFF CFM

WATTS1200275

1200330

1200385

1100385

940330

HIGH(450 CFM/TON) OFF OFF ON OFF CFM

WATTS1325360

1325425

1300460

1175425

1000365

NOTES: * First letter may be "A" or "T" 1. At continuous fan setting: Heating or Cooling airflows are approximately 50% of selected cooling value. 2. LOW airflow (350 cfm/ton) is COMFORT & HUMID CLIMATE setting; NORMAL airflow (400 cfm/ton) is typical setting; HIGH airflow (450 cfm/ton) is DRY CLIMATE setting.

*UY060R9V3W FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

1st Stage Capacity =2nd Stage Capacity =

37,00056,000

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

SW 7 SW 8 0.1 0.3 0.5 0.7 0.9

HEATING1ST

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

6005785

60057110

60057155

60057190

-

MEDIUM LOW OFF ONCFM

TEMP. RISEWATTS

7004990

70049130

70049175

70049

210-

NORMAL ** ON OFFCFM

TEMP. RISEWATTS

77544105

77544155

77544195

77544240

-

HIGH OFF OFFCFM

TEMP. RISEWATTS

87039135

87039185

87039

235

87039

290-

HEATING2ND

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

86061

140

92057

200

92057245

92057

300

67079

245

MEDIUM LOW OFF ONCFM

TEMP. RISEWATTS

100053190

100053255

100053305

100053

340

70075

255

NORMAL ** ON OFFCFM

TEMP. RISEWATTS

112547

250

112547315

112547370

102551

355

77568

285

HIGH OFF OFFCFM

TEMP. RISEWATTS

125042340

125042

405

125042

445

110048390

100053

355

NOTES: * First letter may be "A" or "T" ** Factory setting

Page 11: Service Facts X341119P10 Gas Furnace – Var. Speed Blower – … Info/Furnace Service Facts/TUYsf.pdf · within the 4 second ignition trial period. As the flame sensor confirms

Page B-648-435 11

Service Facts*UY080R9V3W FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

1st Stage Capacity =2nd Stage Capacity =

49,00073,000

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

SW 7 SW 8 0.1 0.3 0.5 0.7 0.9

HEATING1ST

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

80056105

80056140

80056180

80056

220

80056

265

MEDIUM LOW OFF ONCFM

TEMP. RISEWATTS

86052115

88051

165

89050

215

92048265

91049

320

NORMAL ** ON OFFCFM

TEMP. RISEWATTS

96046150

99045

200

100044230

102044310

101044350

HIGH OFF OFFCFM

TEMP. RISEWATTS

108041

195

111040255

112040315

112040365

108041

390

HEATING2ND

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

110062

205

110062

260

112061

320

112061

370

109063

400

MEDIUM LOW OFF ONCFM

TEMP. RISEWATTS

121057265

124055

340

126054410

126054

470

113061

430

NORMAL ** ON OFFCFM

TEMP. RISEWATTS

136050365

139049445

140049500

136050

535

121057

475

HIGH OFF OFFCFM

TEMP. RISEWATTS

136050355

139049

450

140049520

135051

535

118058

465

NOTES: * First letter may be "A" or "T" ** Factory setting

*UY080R9V3W FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

OUTDOORUNIT SIZE

(TONS)

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

SW 1 SW 2 SW 3 SW 4 0.1 0.3 0.5 0.7 0.9

2.0

LOW(350 CFM/TON) ON ON OFF ON CFM

WATTS75084

750122

750154

720185

710221

NORMAL(400 CFM/TON) ON ON OFF OFF CFM

WATTS840109

840146

840181

840226

820264

HIGH(450 CFM/TON) ON ON ON OFF CFM

WATTS940136

940177

940215

940274

940318

2.5

LOW(350 CFM/TON) OFF ON OFF ON CFM

WATTS850113

850150

870200

890250

890295

NORMAL(400 CFM/TON) OFF ON OFF OFF CFM

WATTS960150

990200

1000230

1020305

1010350

HIGH(450 CFM/TON) OFF ON ON OFF CFM

WATTS1080195

1110255

1120315

1120365

1080390

3.0

LOW(350 CFM/TON) ON OFF OFF ON CFM

WATTS1020175

1020225

1040280

1050330

1050375

NORMAL(400 CFM/TON) ON OFF OFF OFF CFM

WATTS1170240

1180300

1200365

1200415

1130420

HIGH(450 CFM/TON) ON OFF ON OFF CFM

WATTS1290310

1320410

1350470

1340520

1150440

3.5

LOW(350 CFM/TON) OFF OFF OFF ON CFM

WATTS1170250

1190315

1210370

1210435

1100405

NORMAL(400 CFM/TON) OFF OFF OFF OFF CFM

WATTS1360365

1390445

1400500

1360535

1210475

HIGH(450 CFM/TON) OFF OFF ON OFF CFM

WATTS1360355

1390450

1400520

1350535

1180460

NOTES: * First letter may be "A" or "T" 1. At continuous fan setting: Heating or Cooling airflows are approximately 50% of selected cooling value. 2. LOW airflow (350 cfm/ton) is COMFORT & HUMID CLIMATE setting; NORMAL airflow (400 cfm/ton) is typical setting; HIGH airflow (450 cfm/ton) is DRY CLIMATE setting.

Page 12: Service Facts X341119P10 Gas Furnace – Var. Speed Blower – … Info/Furnace Service Facts/TUYsf.pdf · within the 4 second ignition trial period. As the flame sensor confirms

12 Page B-648-435

Service Facts

*UY100R9V4W FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

OUTDOORUNIT SIZE

(TONS)

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

SW 1 SW 2 SW 3 SW 4 0.1 0.3 0.5 0.7 0.9

2.5

LOW(350 CFM/TON) ON ON OFF ON CFM

WATTS80875

824125

840170

835210

830250

NORMAL(400 CFM/TON) ON ON OFF OFF CFM

WATTS938100

963160

959205

964255

975310

HIGH(450 CFM/TON) ON ON ON OFF CFM

WATTS1058150

1100200

1121265

1136330

1142395

3.0

LOW(350 CFM/TON) OFF ON OFF ON CFM

WATTS1004120

1010175

1027230

1044285

1050345

NORMAL(400 CFM/TON) OFF ON OFF OFF CFM

WATTS1141170

1190245

1214310

1229380

1234450

HIGH(450 CFM/TON) OFF ON ON OFF CFM

WATTS1336250

1375330

1387410

1388480

1384545

3.5

LOW(350 CFM/TON) ON OFF OFF ON CFM

WATTS1153180

1206250

1230320

1239395

1244460

NORMAL(400 CFM/TON) ON OFF OFF OFF CFM

WATTS1390285

1418465

1439445

1441515

1373540

HIGH(450 CFM/TON) ON OFF ON OFF CFM

WATTS1575400

1606495

1632590

1596645

1445590

4.0

LOW(350 CFM/TON) OFF OFF OFF ON CFM

WATTS1388290

1423360

1444440

1444515

1390540

NORMAL(400 CFM/TON) OFF OFF OFF OFF CFM

WATTS1610415

1641515

1666635

1607650

1449595

HIGH(450 CFM/TON) OFF OFF ON OFF CFM

WATTS1847630

1863735

1816780

1687720

1532665

NOTES: *First letter may be "A" or "T" 1. At Continuous fan setting: Heating or Cooling airflows are approximately 50% of selected cooling value. 2. LOW airflow (350 cfm/ton) is COMFORT & HUMID CLIMATE setting; NORMAL airflow (400 cfm/ton) is typical setting; HIGH airflow (450 cfm/ton) is DRY CLIMATE setting.

*UY100R9V4W FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

1st Stage Capacity =2nd Stage Capacity =

62,00093,000

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

SW 7 SW 8 0.1 0.3 0.5 0.7 0.9

HEATING1ST

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

87364100

89363145

90062195

89962

240

90262

290

MEDIUM LOW OFF ONCFM

TEMP. RISEWATTS

97158115

99756170

100656

220

102255

280

102954

335

MEDIUM ** ON OFFCFM

TEMP. RISEWATTS

113649160

114649

230

116548295

118047365

118447425

HIGH OFF OFFCFM

TEMP. RISEWATTS

125844225

129843300

131942

390

132842

450

128644490

HEATING2ND

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

126068

213

130466

305

132965

380

133465

460

131765

510

MEDIUM LOW OFF ONCFM

TEMP. RISEWATTS

146459

315

147159

405

147858

485

147858

560

135064

540

MEDIUM ** ON OFFCFM

TEMP. RISEWATTS

163153

450

167851

570

169051

670

157955

645

141961

585

HIGH OFF OFFCFM

TEMP. RISEWATTS

184647640

186746760

179448770

164452

700

149857

650

NOTES: * First letter may be "A" or "T" ** Factory setting

Page 13: Service Facts X341119P10 Gas Furnace – Var. Speed Blower – … Info/Furnace Service Facts/TUYsf.pdf · within the 4 second ignition trial period. As the flame sensor confirms

Page B-648-435 13

Service Facts

*UY120R9V5W FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

OUTDOORUNIT SIZE

(TONS)

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

SW 1 SW 2 SW 3 SW 4 0.1 0.3 0.5 0.7 0.9

3.5

LOW(350 CFM/TON) OFF ON OFF ON CFM

WATTS1210220

1210270

1220325

1230400

1230445

NORMAL(400 CFM/TON) OFF ON OFF OFF CFM

WATTS1400305

1440390

1450465

1450510

1410560

HIGH(450 CFM/TON) OFF ON ON OFF CFM

WATTS1590425

1600520

1610600

1600645

1380575

4.0

LOW(350 CFM/TON) ON OFF OFF ON CFM

WATTS1390305

1400375

1430445

1440515

1420565

NORMAL(400 CFM/TON) ON OFF OFF OFF CFM

WATTS1620420

1650530

1670595

1640660

1480600

HIGH(450 CFM/TON) ON OFF ON OFF CFM

WATTS1840600

1830690

1820765

1670700

1490620

5

LOW(350 CFM/TON) OFF OFF OFF ON CFM

WATTS1800570

1780630

1780705

1700695

1530615

NORMAL(400 CFM/TON) OFF OFF OFF OFF CFM

WATTS2050845

2010875

1860805

1710735

1530655

HIGH(450 CFM/TON) OFF OFF ON OFF CFM

WATTS2160995

2040935

1920875

1780805

1620730

NOTES: * First letter may be "A" or "T" 1. At continuous fan setting: Heating or Cooling airflows are approximately 50% of selected cooling value. 2. LOW airflow (350 cfm/ton) is COMFORT & HUMID CLIMATE setting; NORMAL airflow (400 cfm/ton) is typical setting; HIGH airflow (450 cfm/ton) is DRY CLIMATE setting.

*UY120R9V5W FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

1st Stage Capacity =2nd Stage Capacity =

74,000112,000

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

SW 7 SW 8 0.1 0.3 0.5 0.7 0.9

HEATING1ST

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

109062165

112060

225

108063

270

107063

310

101067

380

MEDIUM LOW OFF ONCFM

TEMP. RISEWATTS

121056

220

120056

280

120056

330

118057

395

116058

455

NORMAL ** ON OFFCFM

TEMP. RISEWATTS

134050295

136050350

137049425

138049

495

133051

535

HIGH OFF OFFCFM

TEMP. RISEWATTS

143047390

157043

490

158043565

157043625

139049

565

HEATING2ND

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

166063

485

169062

590

168062

640

164064

675

146072

600

MEDIUM LOW OFF ONCFM

TEMP. RISEWATTS

187056675

187056745

181058

770

168062

715

149070

625

NORMAL ** ON OFFCFM

TEMP. RISEWATTS

206051

880

199053890

185057810

171061

750

153068

665

HIGH OFF OFFCFM

TEMP. RISEWATTS

220048

1030

209050965

194054895

179058

830

164064

750

NOTES: * First letter may be "A" or "T" ** Factory setting

Page 14: Service Facts X341119P10 Gas Furnace – Var. Speed Blower – … Info/Furnace Service Facts/TUYsf.pdf · within the 4 second ignition trial period. As the flame sensor confirms

14 Page B-648-435

Service Facts*DY060R9V3W FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

1st STAGE CAPACITY =2nd STAGE CAPACITY =

37,00056,000

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

SW 7 SW 8 0.1 0.3 0.5 0.7 0.9

HEATING1ST

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

6005655

6005685

60056120

60056150

60056185

MEDIUM LOW OFF ONCFM

TEMP. RISEWATTS

6755065

67550105

67550140

67550175

67550

205

NORMAL ** ON OFFCFM

TEMP. RISEWATTS

7504585

75045125

75045160

75045

210

75045

260

HIGH OFF OFFCFM

TEMP. RISEWATTS

85040115

85040155

85040205

85040260

85040

320

HEATING2ND

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

90058125

90058165

90058

220

90058

270

90058

315

MEDIUM LOW OFF ONCFM

TEMP. RISEWATTS

100052170

105050

230

105050

295

105050

335

105050

370

NORMAL ** ON OFFCFM

TEMP. RISEWATTS

206051

880

199053890

185057810

171061

750

153068

665

HIGH OFF OFFCFM

TEMP. RISEWATTS

220048

1030

209050965

194054895

179058

830

164064

750

NOTES: * First letter may be "A" or "T" ** Factory setting

*DY060R9V3W FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

OUTDOORUNIT SIZE

(TONS)

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

SW 1 SW 2 SW 3 SW 4 0.1 0.3 0.5 0.7 0.9

1.5

LOW(350 CFM/TON) OFF OFF OFF ON CFM

WATTS52545

52570

525100

525135

525160

NORMAL(400 CFM/TON) OFF OFF OFF OFF CFM

WATTS60055

60085

600120

600150

600185

HIGH(450 CFM/TON) OFF OFF ON OFF CFM

WATTS67565

675105

625140

675175

675205

2.0

LOW(350 CFM/TON) ON ON OFF ON CFM

WATTS70070

700115

700145

700185

700220

NORMAL(400 CFM/TON) ON ON OFF OFF CFM

WATTS800100

800135

800175

800225

800280

HIGH(450 CFM/TON) ON ON ON OFF CFM

WATTS900125

900165

900220

900270

900330

2.5

LOW(350 CFM/TON) OFF ON OFF ON CFM

WATTS875115

875160

875210

875260

875310

NORMAL(400 CFM/TON) OFF ON OFF OFF CFM

WATTS1000150

1000207

1000265

1000320

1000380

HIGH(450 CFM/TON) OFF ON ON OFF CFM

WATTS1125215

1125285

1125340

1125395

1125440

3

LOW(350 CFM/TON) ON OFF OFF ON CFM

WATTS1050175

1050240

1050305

1050345

1050380

NORMAL(400 CFM/TON) ON OFF OFF OFF CFM

WATTS1200240

1200315

1200385

1200440

1100410

HIGH(450 CFM/TON) ON OFF ON OFF CFM

WATTS1350330

1350410

1350500

1275485

1170450

NOTES: * First letter may be "A" or "T" 1. At continuous fan setting: Heating or Cooling airflows are approximately 50% of selected cooling value. 2. LOW airflow (350 cfm/ton) is COMFORT & HUMID CLIMATE setting; NORMAL airflow (400 cfm/ton) is typical setting; HIGH airflow (450 cfm/ton) is DRY CLIMATE setting.

Page 15: Service Facts X341119P10 Gas Furnace – Var. Speed Blower – … Info/Furnace Service Facts/TUYsf.pdf · within the 4 second ignition trial period. As the flame sensor confirms

Page B-648-435 15

Service Facts

*DY080R9V3W - FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

OUTDOORUNIT SIZE

(TONS)

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

SW 1 SW 2 SW 3 SW 4 0.1 0.3 0.5 0.7 0.9

2.0

LOW(350 CFM/TON) ON ON OFF ON CFM

WATTS70095

700105

700115

680200

670235

NORMAL(400 CFM/TON) ON ON OFF OFF CFM

WATTS800130

800160

800205

790245

740265

HIGH(450 CFM/TON) ON ON ON OFF CFM

WATTS900160

900215

900255

900300

750270

2.5

LOW(350 CFM/TON) OFF ON OFF ON CFM

WATTS875145

875185

875240

875280

760270

NORMAL(400 CFM/TON) OFF ON OFF OFF CFM

WATTS1000205

1000265

1000310

1000340

800295

HIGH(450 CFM/TON) OFF ON ON OFF CFM

WATTS1150295

1150340

1150385

1020350

800300

3.0

LOW(350 CFM/TON) ON OFF OFF ON CFM

WATTS1050235

1050295

1050340

1010350

800290

NORMAL(400 CFM/TON) ON OFF OFF OFF CFM

WATTS1200335

1200385

1200410

1040365

840310

HIGH(450 CFM/TON) ON OFF ON OFF CFM

WATTS1350455

1350480

1210435

1070390

900345

NOTES: * First letter may be "A" or "T" 1. At continuous fan setting: Heating or Cooling airflows are approximately 50% of selected cooling value. 2. LOW airflow (350 cfm/ton) is COMFORT & HUMID CLIMATE setting; NORMAL airflow (400 cfm/ton) is typical setting; HIGH airflow (450 cfm/ton) is DRY CLIMATE setting.

*DY080R9V3W FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

1st STAGE CAPACITY =2nd STAGE CAPACITY =

49,00073,000

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

SW 7 SW 8 0.1 0.3 0.5 0.7 0.9

HEATING1ST

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

80056130

80056170

80056

210

79056

245-

MEDIUM LOW OFF ONCFM

TEMP. RISEWATTS

90049162

90049

210

90049260

90049

295-

NORMAL ** ON OFFCFM

TEMP. RISEWATTS

100044205

100044265

100044310

100044345

80056

295

HIGH OFF OFFCFM

TEMP. RISEWATTS

117038305

117038

350

117038

400

102044360

83054

310

HEATING2ND

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

115060

285

115060

345

115060

385

102067***360

83083***305

MEDIUM LOW OFF ONCFM

TEMP. RISEWATTS

127554380

127554445

120057425

104066***380

90076***350

NORMAL ** ON OFFCFM

TEMP. RISEWATTS

143048515

134051

490

122056

455

109063

410

93074***380

HIGH OFF OFFCFM

TEMP. RISEWATTS

143048515

134051

490

122056

455

109063

410

93074***380

NOTES: * - First letter may be "A" or "T" ** Factory setting *** Above MAX Temperature change value

Page 16: Service Facts X341119P10 Gas Furnace – Var. Speed Blower – … Info/Furnace Service Facts/TUYsf.pdf · within the 4 second ignition trial period. As the flame sensor confirms

16 Page B-648-435

Service Facts*DY100R9V4W - FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

1st STAGE CAPACITY =2nd STAGE CAPACITY =

62,00093,000

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

SW 7 SW 8 0.1 0.3 0.5 0.7 0.9

HEATING1ST

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

92361

110

95559165

96058

210

95858

265

94759

310

MEDIUM LOW OFF ONCFM

TEMP. RISEWATTS

102055145

104753190

105353

250

104254295

102954350

MEDIUM ** ON OFFCFM

TEMP. RISEWATTS

115648185

116648

240

117248300

117748350

117848420

HIGH OFF OFFCFM

TEMP. RISEWATTS

127544225

130543

290

132842

365

132842

445

132842

510

HEATING2ND

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

129866

235

132065305

133565

380

134364

445

134364

520

MEDIUM LOW OFF ONCFM

TEMP. RISEWATTS

143960

310

145959390

148258

470

148358

550

147059

610

MEDIUM ** ON OFFCFM

TEMP. RISEWATTS

163953430

165052525

165052

600

164452

680

149658

640

HIGH OFF OFFCFM

TEMP. RISEWATTS

179018

570

181847670

181347770

170850750

153556

675

NOTES: * - First letter may be "A" or "T" ** Factory setting *** Above MAX temperature change

*DY100R9V4W - FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

OUTDOORUNIT SIZE

(TONS)

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

SW 1 SW 2 SW 3 SW 4 0.1 0.3 0.5 0.7 0.9

2.5

LOW(350 CFM/TON)

ON ON OFF ONCFM

WATTS870100

885140

887185

881230

876270

NORMAL(400 CFM/TON)

ON ON OFF OFFCFM

WATTS989120

1018180

1016230

1012285

999325

HIGH(450 CFM/TON)

ON ON ON OFFCFM

WATTS1124175

1139225

1130275

1135335

1135390

3.0

LOW(350 CFM/TON)

OFF ON OFF ONCFM

WATTS1053145

1075200

1070245

1070295

1049350

NORMAL(400 CFM/TON)

OFF ON OFF OFFCFM

WATTS1186195

1205255

1220310

1220370

1216440

HIGH(450 CFM/TON)

OFF ON ON OFFCFM

WATTS1336255

1366340

1383405

1385470

1381545

3.5

LOW(350 CFM/TON)

ON OFF OFF ONCFM

WATTS1216190

1225255

1235320

1240385

1243445

NORMAL(400 CFM/TON)

ON OFF OFF OFFCFM

WATTS1394270

1422360

1436430

1437505

1430580

HIGH(450 CFM/TON)

ON OFF ON OFFCFM

WATTS1579395

1604475

1610555

1599645

1517640

4.0

LOW(350 CFM/TON)

OFF OFF OFF ONCFM

WATTS1377270

1412355

1426430

1433510

1428575

NORMAL(400 CFM/TON)

OFF OFF OFF OFFCFM

WATTS1599425

1624510

1636585

1618670

1512635

HIGH(450 CFM/TON)

OFF OFF ON OFFCFM

WATTS1801580

1818690

1815775

1694735

1525660

NOTES: * - First letter may be "A" or "T" 1. At continuous fan setting: Heating or Cooling airflows are approximately 50% of selected cooling value. 2. LOW airflow (350 cfm/ton) is COMFORT & HUMID CLIMATE setting; NORMAL airflow (400 cfm/ton) is typical setting; HIGH airflow (450 cfm/ton) is DRY CLIMATE setting.

Page 17: Service Facts X341119P10 Gas Furnace – Var. Speed Blower – … Info/Furnace Service Facts/TUYsf.pdf · within the 4 second ignition trial period. As the flame sensor confirms

Page B-648-435 17

Service Facts*DY120R9V5W - FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

1st STAGE CAPACITY =2nd STAGE CAPACITY =

74,000112,000

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

SW 8 SW 7 0.1 0.3 0.5 0.7 0.9

HEATING1ST

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

102565150

102565

200

100067

240

100067

290

100067

340

MEDIUM LOW OFF ONCFM

TEMP. RISEWATTS

120056

230

120056

270

120056

330

120056

390

120056

450

NORMAL ** ON OFFCFM

TEMP. RISEWATTS

135049

280

135049340

135049490

135049

470

135049

530

HIGH OFF OFFCFM

TEMP. RISEWATTS

155043

400

155043

490

155043560

155043620

145046

600

HEATING2ND

STAGE

LOW ON ONCFM

TEMP. RISEWATTS

155066

380

155066

470

155066

540

155066

610

145071***690

MEDIUM LOW OFF ONCFM

TEMP. RISEWATTS

185056660

185056750

185056

780

170060

720

150069

640

NORMAL ** ON OFFCFM

TEMP. RISEWATTS

205050860

200051

880

185056

810

170060

750

155066

670

HIGH OFF OFFCFM

TEMP. RISEWATTS

210549

1000

205050940

190054880

177558

820

162563

750

NOTES: * First letter may be "A" or "T" ** Factory setting

*DY120R9V5W - FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

OUTDOORUNIT SIZE

(TONS)

AIRFLOWSETTING

DIP SWITCH SETTING EXTERNAL STATIC PRESSURE

SW 1 SW 2 SW 3 SW 4 0.1 0.3 0.5 0.7 0.9

3.5

LOW(350 CFM/TON) OFF ON OFF ON CFM

WATTS1225240

1225280

1225340

1225400

1225450

NORMAL(400 CFM/TON) OFF ON OFF OFF CFM

WATTS1400310

1400390

1400470

1400520

1400570

HIGH(450 CFM/TON) OFF ON ON OFF CFM

WATTS1600450

1600520

1600590

1600640

1450600

4.0

LOW(350 CFM/TON) ON OFF OFF ON CFM

WATTS1400300

1400380

1400450

1400520

1400570

NORMAL(400 CFM/TON) ON OFF OFF OFF CFM

WATTS1600460

1600530

1600610

1600670

1450600

HIGH(450 CFM/TON) ON OFF ON OFF CFM

WATTS1800610

1800700

1800760

1650690

1500630

5

LOW(350 CFM/TON) OFF OFF OFF ON CFM

WATTS1750580

1750640

1750720

1650680

1450610

NORMAL(400 CFM/TON) OFF OFF OFF OFF CFM

WATTS2000830

2000860

1850800

1700740

1550660

HIGH(450 CFM/TON) OFF OFF ON OFF CFM

WATTS2100970

2000910

1900850

1650780

1600710

NOTES: * - First letter may be "A" or "T" 1. At continuous fan setting: Heating or Cooling airflows are approximately 50% of selected cooling value. 2. LOW airflow (350 cfm/ton) is COMFORT & HUMID CLIMATE setting; NORMAL airflow (400 cfm/ton) is typical setting; HIGH airflow (450 cfm/ton) is DRY CLIMATE setting.

Page 18: Service Facts X341119P10 Gas Furnace – Var. Speed Blower – … Info/Furnace Service Facts/TUYsf.pdf · within the 4 second ignition trial period. As the flame sensor confirms

18 Page B-648-435

Service FactsINTEGRATED FURNACE CONTROL RED LED "ERROR" FLASH CODES

2 Flashes --- System Lockout (Retries or Recycles exceeded)

3 Flashes ---

Draft Pressure Error - Possible problems: a) Venting problem b) Pressure switch problem c) Inducer problem

4 Flashes --- Open Temperature Limit Switch5 Flashes --- Flame sensed when no flame should be present

6 Flashes --- 115 volt AC power reversed, ignitor (Triac) fault, poor grounding orsystem voltage too low

7 Flashes --- Gas valve circuit error8 Flashes --- Low flame sense9 Flashes --- Open Inducer Limit switch10 Flashes --- Inducer communication errorSolid --- Internal GV error or Low TH voltageSolid Red w/SolidGreen "STATUS" LED Continuous Reset caused by a blown fuse or internal error.

INTEGRATED FURNACE CONTROLGREEN "STATUS" LED FLASH CODES

Flashing Slow --- Normal - No call for Heat

Flashing Fast --- Normal - Call for Heat

Fault Code ResetThe last 4 fault codes can be erased from memory by power-ing up the control with “G” energized and then applying “R”to the “W1” terminal 3 times within 6 seconds. The controlwill acknowledge the reset by turning on the red LED for2 seconds.

FAULT CODE RECOVERYOn power up, last 4 faults, if any, will be flashed on the redLED. The newest fault detected will flash first and the oldestlast. There will be a 2 second delay between fault codeflashes. Solid red LED error codes will not be displayed.

The Green LED will be on solid during last fault recovery.At any other time the control is powered, the Green LEDindicator light will operate as shown in Table 14 and the redLED will flash LitePort data (one flash) every 20 seconds.

*UY / DY Integrated Furnace Control

Red LitePort™ LEDGreen Status LED

IFC Error Flash Codes

Page 19: Service Facts X341119P10 Gas Furnace – Var. Speed Blower – … Info/Furnace Service Facts/TUYsf.pdf · within the 4 second ignition trial period. As the flame sensor confirms

Page B-648-435 19

Service FactsNOTES