series c from 10 to 60 kva - masterguard chloride en/c series.pdf · mka4cat0ukc/rev. 4-07/2008/uk...

23
Secure Power Always UPS Catalogue Series C from 10 to 60 kVA

Upload: ngothien

Post on 17-Feb-2018

581 views

Category:

Documents


40 download

TRANSCRIPT

Page 1: Series C from 10 to 60 kVA - Masterguard Chloride EN/C Series.pdf · MKA4CAT0UKC/Rev. 4-07/2008/UK Series C from 10 to 60 kVA UPS Catalogue • 2008 Uninterruptible Power Supply Systems

Secure Power Always

UPS Catalogue

Series C from 10 to 60 kVA

Page 2: Series C from 10 to 60 kVA - Masterguard Chloride EN/C Series.pdf · MKA4CAT0UKC/Rev. 4-07/2008/UK Series C from 10 to 60 kVA UPS Catalogue • 2008 Uninterruptible Power Supply Systems

Important note!

The technical data enclosed is for general information.Please note the operating instructions and the referencesindicated on the products are for installation, operation andmaintenance.

Product designations

All product designations used are trademarks or productnames of Chloride S.p.A.

This publication is issued to provide outline information andis not deemed to form any part of any offer and contract. Thecompany has a policy, of continuous product developmentand improvement and we therefore reserve the right to varyany information quoted without prior notice.

Person to contact

Page 3: Series C from 10 to 60 kVA - Masterguard Chloride EN/C Series.pdf · MKA4CAT0UKC/Rev. 4-07/2008/UK Series C from 10 to 60 kVA UPS Catalogue • 2008 Uninterruptible Power Supply Systems

MKA4CAT0UKC/Rev. 4-07/2008/UK

Series Cfrom 10 to 60 kVA

UPS Catalogue • 2008

Uninterruptible Power Supply Systems

Scope 2

System Description 2

General Requirements 3

Device Description 3

Monitoring and Control Interfaces 5

Battery Management 7

Mechanical Data 8

Technical Data (10 - 40 kVA range) 9

Technical Data (50 - 60 kVA range) 12

Options 15

Parallel Configuration 17

Special Versions 18

01

Page 4: Series C from 10 to 60 kVA - Masterguard Chloride EN/C Series.pdf · MKA4CAT0UKC/Rev. 4-07/2008/UK Series C from 10 to 60 kVA UPS Catalogue • 2008 Uninterruptible Power Supply Systems

1. Scope

MASTERGUARD Series CUPS Systems from 10 to 60 kVA

MKA4CAT0UKC/Rev. 4-07/2008/UK

within defined limits and withoutinterruption, upon failure ordegradation of the commercial ACsource. The continuity of conditionedelectric power shall be defined by the

battery system for the autonomy timeperiod; the battery system will beautomatically recharged by the UPSupon restoration of the commercial ACsource.

The following specification describes acontinuous duty three phase, static,IGBT Uninterruptible Power System(UPS). The UPS shall automaticallyprovide continuity of electrical power,

Series C is an intelligent doubleconversion UPS, as shown in Figure 1.The systems shall operate on a DSP-based IGBT inverter. Through VectorControl technology, the performanceof the inverter shall be enhanced andshall be capable of providing reliable,high quality AC power. In order toincrease system redundancy, anindependent electronic static bypassshall be integrated into the UPS. By adding system components, suchas parallel kits, safety anddisconnecting devices, system bypassswitches, as well as software andcommunications solutions, it shall bepossible to set up elaborate systemsensuring the complete protection ofthe supplied loads.

2.1 The system

The UPS shall provide high quality ACpower for electronic equipment loadsand shall offer the following benefits:

• Increased power quality, for optimaland safe operation of loads.

• Full noise rejection, for completeload protection against upstream network disturbances

• Full compatibility with all types ofloads, including heavily non-linear ones

• Power blackout protection in caseof power outages

• Full battery care, to preserve theuseful life of the battery system

• Transformer-less design, allowingreduced footprint and weight(galvanic isolation transformers areavailable as standard options)

The UPS shall automatically providecontinuity of electrical power, withinthe defined limits and withoutinterruption, upon failure ordegradation of the commercial ACsource. The length of the backup time,i.e. autonomy time in the event ofnetwork failure, shall be determined bythe battery capacity.

Figure 1. Series C single-line block diagram

Maintenance Bypass

Battery Fuse

Battery Fuse

Battery System

RemoteSignalling(optional)

FuseRectifier InverterBooster

ElectronicBypass switch

Battery switch

Battery Charger

Reserveswitch

Output switch

LoadSwitch

Reserve Mains

Regular Mains

2. System Description

02

Page 5: Series C from 10 to 60 kVA - Masterguard Chloride EN/C Series.pdf · MKA4CAT0UKC/Rev. 4-07/2008/UK Series C from 10 to 60 kVA UPS Catalogue • 2008 Uninterruptible Power Supply Systems

2. System Description

MASTERGUARD Series CUPS Systems from 10 to 60 kVA

3. General Requirements

MKA4CAT0UKC/Rev. 4-07/2008/UK

MODEL Rating (kVA) MODEL Rating (kVA)

Series C/10 10 Series C/40 40

Series C/15 15 Series C/50 50

Series C/20 20 Series C/60 60

Series C/30 30

3.1 Applied Standards

MASTERGUARD is certified by theBritish Standard Institution (BSl), as acompany with a quality andenvironmental system in accordancewith the ISO 9001 and ISO 14001. SeriesC shall carry the CE mark in accordancewith the Safety and EMC Directives2006/95 (superseding the 72/23 andsuccessive amendments), 89/336, 92/31and 93/68. Series C is designed andmanufactured in accordance with thefollowing international standards:

2.2 Models Available

The Series C range shall include threephase input/output models asspecified in the following table:

• IEC/EN 62040-1-1 General and safety requirements

• EN 50091-2 EMC requirements• IEC/EN 62040-3 Performance and

Operating requirements

3.2 Components and materials

All materials and parts containedwithin the UPS shall be new and incurrent production and, to ensuremaximum reliability, they shall be used well within the parametersrecommended by the supplier.

3.3 Neutral/Earth

Series C neutral output shall beelectrically isolated from the UPSchassis. Series C shall not modify theneutral state. Therefore, the downstreamdistribution shall be of the same type asthe input distribution whilst the upstreamneutral is connected to the UPS.

Series C must be used in installationswith grounded neutral; for furtherdetails please contactMASTERGUARD Technical Support(special versions may be used - see

4. Device Description

In this section the main functionalblocks of Series C and operatingmodes of this UPS are described.

4.1 Functional blocks

The UPS shall consist of the followingmajor functional blocks (refer also toFigure 1):

• AC/DC converter. The rectifier shallbe capable of delivering thenecessary power to the DC bus todrive the inverter, absorbingvirtually only active power from theupstream network (Power FactorCorrection)

• Battery Charger. This device shallbe able to completely recharge thebattery bank, by delivering DCpower to the batteries with a verylow voltage and residual currentripple

• Booster. This DC/DC converter willboost the rectifier/battery DCvoltage, creating a split DC bus,which will allow the inverter torecreate the AC nominal voltagewithout the need for an outputtransformer

• DC/AC converter. The IGBTtransformer-less inverter shall becontrolled by a Digital SignalProcessor (DSP), see section 4.3for details

• Static bypass with separate inputfeeder. The electronic static switchon the reserve supply shall becapable of switching the load fromthe inverter line to the direct line,and vice-versa, with a Make BeforeBreak (MBB) transition, either uponmanual or automatic command (see section 4.4 for details)

• Manual maintenance bypass switch.This manual switch shall allowcomplete internal maintenance of the unit without interruptions to theload power supply

• Integrated batteries into the UPScabinet (10 - 40 kVA range) for basicautonomies

• Matching battery cubicles forextended battery autonomies

4.2 Microprocessor diagnostics andcontrol

Operation and control of the UPS shall be provided through the use of microprocessor controlled logic.Indications, measurements and alarmstogether with battery autonomy shall beshown on a back-illuminated graphicalLCD display. The procedures for start up,shut down and manual transfer of theload to bypass and return from bypassshall be described by clear step-by-stepactions, reported on the user manual andassisted through the LCD display.

Control of the power electronics moduleswill be optimised in order to provide:

• An optimum three-phase supply ofthe load

• Controlled charging of the battery • Minimum phase effects upon the

upstream supply network

4.2.1 Redundancy, preventativemonitoring

In order to maximise the reliability ofthe system, the control unit shall monitora wide number of operating parametersof the rectifier, inverter and battery. Allthe important operating parameters,such as temperature, frequency andvoltage stability at the system output,as well as all the load parameters andinternal system values shall becontinuously monitored and controlledfor irregularities. The system shall reactautomatically prior to a criticalsituation for the UPS or the load, inorder to ensure the supply of the loadeven in the most critical situations.

4.2.2 Remote diagnosis and control

Using an advanced remote diagnosis andcontrol system, it shall be possible toremotely monitor and control the UPSfrom a location such as a service centrein order to maintain the reliability ofthe system at optimal levels.

03

Page 6: Series C from 10 to 60 kVA - Masterguard Chloride EN/C Series.pdf · MKA4CAT0UKC/Rev. 4-07/2008/UK Series C from 10 to 60 kVA UPS Catalogue • 2008 Uninterruptible Power Supply Systems

4.4.1.2 Overload

If the inverter stops, via operatorintervention or due to an overload, the UPS automatically transfers to the direct line (if available) withoutinterruption. When the overload ceases,return to the inverter is automatic. This enables Series C to handle theinrush current of the load without theneed to over-size the UPS. The transfer todirect line is only allowed when voltageand frequency of the mains powersupply are within limits. In the event ofan overload with an unsuitable mainssupply, Series C prevents the transferand the inverter continues to supplythe load for a period, depending on thedegree of overload. Appropriate visualand audible alarms inform the user of theparticular abnormal operating condition.

4.4.1.3 Emergency

If the mains supply has failed or isoutside tolerance limits, the batteriesare used to power the load. The user isalerted to the battery discharge throughvisual and audible alarms and the batterycapacity is displayed on the graphicaldisplay. It is possible to extend theautonomy remaining by turning OFFnon-essential loads. The warning indicatoron Series C will display battery operation.

4.4.1.4 Return to normal conditions

When the mains power supply returnswithin tolerance limits, Series C resumesnormal operation. The battery chargerautomatically recharges the battery toensure maximum autonomy in theshortest possible timeframe.

4.4.1.5 Recharge

Even if batteries are completelydischarged, the rectifier/charger shallautomatically restart upon restoration ofthe commercial AC source and shall takeover the inverter after a programmabledelay. This shall be a fully automaticfunction and shall cause no interruptionto the critical load.

4.4.2 Digital interactive mode

If priority has been set to digital interactivemode, intelligent double conversiontechnology shall allow Series C tocontinuously monitor the condition ofthe input supply to ensure maximumreliability for critical users.

On the basis of the analysis performed, itshall decide whether to supply theload through direct line or conditionedline. This operational mode, which allowssignificant energy savings by increasingoverall UPS AC/AC efficiency, is primarilyintended for general purpose ICTapplications. However, it does not providethe same output power quality aswhen the UPS is operated in DoubleConversion mode. Therefore, it shall benecessary to verify whether this modeis appropriate for special applications.Digital Interactive mode shall not beavailable for parallel systems.

4.4.2.1 Normal

The operating mode will depend onthe quality of the mains during therecent past. If the line quality hasremained within permitted tolerancelevels, the direct line continuouslysupplies the critical AC load throughthe static switch. Control of the IGBTinverter constantly operates and issynchronised with the direct line. Inthe event of any deviation from theselected input power tolerance levels,this ensures that the load can betransferred to the conditioned linewithout any break in supply. If thedirect line failure rate has reachedoutside permitted parameters, Series Cshall supply the load from theconditioned line. The battery chargersupplies the energy necessary tomaintain the optimal charging level tothe battery.

4.4.2.2 Inverter stop or overload

If the Inverter is stopped either by theoperator or due to an overload, there is notransfer to the conditioned line and theload continues to be supplied by the directline. Mains voltage and frequency valuesmust remain within the specifiedtolerance limits. In the event of anoverload lasting more than the maximumspecified capacity, the load is transferredto the conditioned line, which will supply itfor a specific time depending on the levelof overload. In the event of an overloadand an unsuitable mains supply, Series Ctransfers the load from the direct line tothe conditioned line (assuming Series Cwas operating from direct line) and theinverter continues to supply the criticalload for a time that depends on thedegree of the overload and the UPSfeatures. Visual and audible alarms alertthe user to the problem.

4. Device Description

MASTERGUARD Series CUPS Systems from 10 to 60 kVA

MKA4CAT0UKC/Rev. 4-07/2008/UK

4.3 Digital Vector Control System

By using digital signal processors(DSP), Series C shall implement themost advanced Digital Vector Controlsystem. Special arithmetic algorithmsshall be implemented to ensure quickand flexible processing of measuringdata. As a result, controlled variablesshall be rapidly generated andtransferred to the IGBT drivers inPWM mode (Pulse Width Modulation).Thus, real time control of inverterelectronics shall be possible. This results in advantages concerningthe performance of power components.Advantages involved shall include:

• Improved short circuit behaviour,since the individual phases can bequickly and individually controlled

• Synchronism or phase angle precision between UPS output and reservesupply even in the event of adistorted mains voltage

• High flexibility and reliability inparallel operations. Furthermore,parallel blocks can be placed indifferent rooms

4.4 Intelligent Double Conversionoperating modes

Series C adopts Intelligent DoubleConversion technology which allowsUPS to operate in double conversionor digital interactive mode according tothe selected priority. The UPS willoperate as follows:

4.4.1 Double Conversion Mode

4.4.1.1 Normal

The IGBT inverter continuously suppliesthe load. The rectifier derives powerfrom the mains supply and converts itinto DC power for the inverter. TheAC/DC rectifier corrects the loadpower factor to a value of >0.95 and,for the 10 - 40 kVA range, also reducesthe input current total harmonicdistortion (THDI) to a value of less than8% (at POUT = PNOM). The battery chargerautomatically maintains the battery ina fully charged and optimum operationalcondition. The IGBT inverter is constantlysynchronised to the direct input line,thus allowing load transfer from theinverter to the direct bypass linewithout any interruption in power tothe load in the event of overload orinverter stop.

04

Page 7: Series C from 10 to 60 kVA - Masterguard Chloride EN/C Series.pdf · MKA4CAT0UKC/Rev. 4-07/2008/UK Series C from 10 to 60 kVA UPS Catalogue • 2008 Uninterruptible Power Supply Systems

5.1 General

The UPS shall incorporate the necessarycontrols, instruments and indicators toallow the operator to monitor the systemstatus and performance, as well astake any appropriate action. Furthermore,interfaces shall be available which allowextended monitoring and control, as wellas service functions.

5.2 LCD display and control panel

The control panel of Series C includes aback-lit Liquid Crystal Display (LCD with 8lines x 12 characters, which can displaygraphic diagrams and symbols) forcomplete UPS monitoring and control.Complete access to all LCD menus ispossible through navigation push buttonslocated below the screen. This navigationgroup includes two buttons - “up” and“down” - for menu scrolling and twosoftware-assigned push buttons: thefunction linked to these two buttons isdisplayed on the lower right and lower leftcorners of the LCD during navigation.

Default display pageThe default page continuously displays asingle-line diagram of the UPS (forreference see Figure 1). The mainfunctional blocks and power paths of theUPS are displayed using simple universaltechnical symbols, making it possible

4. Device Description

MASTERGUARD Series CUPS Systems from 10 to 60 kVA

5. Monitoring and Control Interfaces

MKA4CAT0UKC/Rev. 4-07/2008/UK

a period of time dependant upon thedirect line failure rate (the conditioned linedraws power from the mains not thebattery). When the direct line hasstabilised, Series C returns to normaloperation. The battery chargerautomatically begins to recharge thebattery. Consequently, maximum autonomyis guaranteed in the shortest possible time.

4.4.3 Maintenance bypass

If for any reason the UPS has to be takenout of service for maintenance or repair,the UPS shall be provided with an internalmaintenance bypass switch whichenables a load transfer to reserve supplywith no interruption in power to the criticalload. Bypass isolation shall be complete,all serviceable components such as fuses,power modules etc. shall be isolated.

4.4.4 Operation Without Battery

If the battery is taken out of service formaintenance, it shall be disconnected

from the rectifier by means of batteryswitches provided in the UPS or in theexternal battery cabinet. During themaintenance, the UPS will continue tooperate and meet the performancecriteria specified, with the exception ofback-up capability.

4.5 Backfeed protection (fromNovember 2005)

This feature shall prevent any potentialrisk from electric shock on the UPSbypass input AC terminals in the event offailure of the bypass static switch SCR.The control circuit shall include a contact(available for the user) which activates anexternal isolating device, such as anelectromechanical relay or a tripping coil,upon backfeed detection. The externalisolating device is not included in theUPS, in compliance with IEC/EN 62040-1.The external isolating device shall be anair gap isolator, and shall be definedaccording to clause 5.1.4 of thepreviously cited standard.

4.4.2.3 Emergency (the mains supplyhas failed or is outside tolerance limits)

If Series C supplies the load via directline and the mains supply reachesoutside the tolerance levels (adjustable bysoftware), the load will be transferredfrom the direct line to the conditioned line.The load is powered from the mainsvia the rectifier and inverter, providedthe input mains remains within itsnominal tolerance. If the input mains isoutside these limits, batteries are usedto power the load via the inverter. Theuser is alerted to the battery discharge byvisual and audible alarms and theautonomy remaining is displayed on thegraphical display. At this time, it is possibleto extend the autonomy remaining byturning off non-essential loads.

4.4.2.4 Return to normal conditions

When the mains supply returns to withintolerance limits, Series C continues tosupply the load via the conditioned line for

LCDDisplay

Navigation buttons: left soft-key, up and down button, right soft-key

“Off” button(load transferred tobypass and inverter off)

“On” button(load on inverter)

UPS summary status:Green LED (system normal)Yellow LED (environmentalwarning)Red LED (system alarm)

“Reset” push button(e.g. audible signalsilence for warning and alarm conditions)

to instantly understand the overall statusof the UPS. On the same screen, theoutput load percentage measurement ispermanently displayed, using threehistograms (one for each output phase).In case the UPS is not in normalfunctioning mode, it is possible to accessthe “Warning and Alarm” summary page

directly from the default page; warningsand alarms shall be identified by textstrings and codes. In battery operation,the display shall switch between warningcode and estimated backup time inminutes. After 30 seconds of inactivity(e.g. no buttons pressed) the displayreverts to the default page.

Figure 2. Control panel and LCD.

05

Page 8: Series C from 10 to 60 kVA - Masterguard Chloride EN/C Series.pdf · MKA4CAT0UKC/Rev. 4-07/2008/UK Series C from 10 to 60 kVA UPS Catalogue • 2008 Uninterruptible Power Supply Systems

Output (for each phase)Voltage Current FrequencyActive ApparentPower PowerInput (for each phase)Voltage FrequencyBypass (for each phase)Voltage Current FrequencyBatteryVoltage Current

(recharge and discharge)

Battery TestFrom this menu it is possible to set thebattery test parameters or to initiate amanually requested test. Results ofthe test will be shown at the end ofthe procedure. See also 6.2.

Pin Description Function1 BYPASS ACTIVE (normally closed) Volt-free contact ‘bypass operation’2 LOW BATTERY (normally closed) Volt-free contact ‘battery discharged’3 SUMMARY ALARM (normally closed) Volt-free contact ‘summary alarm’4 MAINS FAILURE (normally closed) Volt-free contact ‘power failure’5 COMMON6 BYPASS ACTIVE (normally open) Volt-free contact ‘bypass operation’7 LOW BATTERY (normally open) Volt-free contact ‘battery discharged’8 SUMMARY ALARM (normally open) Volt-free contact ‘summary alarm’9 MAINS FAILURE (normally open) Volt-free contact ‘power failure’

5. Monitoring and Control Interfaces

MASTERGUARD Series CUPS Systems from 10 to 60 kVA

MKA4CAT0UKC/Rev. 4-07/2008/UK

Main Menus descriptionUsing the navigation push buttons it ispossible to access the followingmenus:

MeasurementsFrom this menu it is possible to accessthe sub-menus, which display themeasured values from each UPSfunctional block. Below is shown asubset of the available measurementsrelated to the input/output power portsof the UPS:

UPS Parameters settingsFrom this menu it is possible to modifysome settings related to input/outputsignals and functions of the UPS.

LCD Display settingsFrom this menu it is possible to selectlanguages for the messages (languagesavailable are English, Italian, German,French, Spanish and Portuguese) andthe contrast of the LCD to allowregulation for optimal user visibility.

General InformationFrom this menu it is possible to accessgeneral information about the UPS(e.g. firmware revision, release date etc.).

5.3 Communication interfaces

5.3.1 Volt-free contact ports

Volt-free contacts shall be provided bySeries C in accordance with therequirements of IBM AS/400 and othercomputer types. This interface shall bevia a 9 pin D socket wired as follows:

The voltage-free contacts shall be rated at 24 V, 1 A.

Pin Description Function1 Shield Cable shield2 TXD Transmit RS2323 RXD Receive RS2324 Not used5 Not used6 Not used7 Ground RS232 Signal ground for receiving

and transmitting8 Not used9 Not used

5.3.2 Serial interface

Series C will be equipped with twoserial ports. The interface shall be a Dtype connector with 9 pins for serialcommunication. The function of eachpin shall be as follows:

Serial #1 (e.g. LIFE.net port); connector D type, 9 pins, male.

Pin Description Function1 Ground Shielding2 TXD Transmit RS2323 RXD Receive RS2324 Not used5 Ground RS232 Signal ground for receiving and trans

mitting6 Not used7 RTS Transmit enable RS2328 Not used9 Not used

Serial #2 (e.g. PPVis port); connector D type, 9 pins, female.

See section 10.13 for the details about connectivity applications that can be used with these ports.

06

Page 9: Series C from 10 to 60 kVA - Masterguard Chloride EN/C Series.pdf · MKA4CAT0UKC/Rev. 4-07/2008/UK Series C from 10 to 60 kVA UPS Catalogue • 2008 Uninterruptible Power Supply Systems

5. Monitoring and Control Interfaces

MASTERGUARD Series CUPS Systems from 10 to 60 kVA

MKA4CAT0UKC/Rev. 4-07/2008/UK

The UPS shall automatically telephonethe service centre at defined intervalsto provide detailed information that shallbe analysed in order to predict nearterm problems. In addition, it shall bepossible to control the UPS remotely.The transmission of UPS data to theMASTERGUARD Command Centreshall take place via the integratedmodem at the following intervals:

• ROUTINE: settable between 5 minutesand 2 days (typically once a day)

• EMERGENCY: when a problemoccurs or the parameters areoutside the tolerance limits

• MANUAL: following the request ofthe command centre

During the call the command centreshall:

• Identify the UPS connected• Request the data stored in the UPS

memory during the time intervalsince the last connection

• Request real time information fromthe UPS (selectable)

5.4 E.P.O.

An Emergency Power Off (E.P.O.)contact shall be available on the unit.When this connection is open, with theinverter or static bypass supporting theload, the logic circuit will immediatelypower down the UPS output.

5.5 LIFE.net

In order to increase the overallreliability of the system, Series C will be compatible with LIFE.netcommunication kits, allowingconnection to MASTERGUARD’sLIFE.net diagnostic service. LIFE.netshall allow the remote diagnosis of theUPS through telephone lines or GSMlink in order to ensure the maximumreliability of the UPS throughout itsoperational life. The monitoring shall be a true 24 hour, 365 day service thanks to aunique feature that allows trainedService Engineers to remain inconstant electronic contact with theservice centre and therefore the UPS.

The service centre shall analysehistorical data and issue a regulardetailed customer report informinghim of the UPS operational conditionand any critical conditions.The LIFE.net centre allows thepossibility to activate the option LIFE-SMS delivery system, where thecustomer can receive SMS notificationshould one of the following events beactivated:

• Mains power failure• Mains power recovered• Reserve line failure• Load supplied by reserve

6. Battery Management

Using Advanced Battery Care (ABC)Series C series shall preserve thedesign battery life. By followingenvironmental recommendationsgiven by battery manufacturers, ABCmeans batteries meet or exceed thedeclared design life. The main batterycare features are described below.

6.1 Operating Parameters

When operating with maintenancefree, valve regulated lead acid batteries(VRLA), the default parameters per cellshall be as follows:

• End of discharge voltage (V) 1.65• Shutdown imminent alarm:

Controlled by dedicated algorithm• Nominal voltage (V) 2.0• Battery discharging

alarm (V) 2.20 @ 20°C• Float voltage (V) 2.27 @ 20°C• High voltage alarm (V) 2.4

6.2 Automatic Battery Test

The operating condition of thebatteries shall be automatically testedby the control unit at selectableintervals, e.g. weekly, fortnightly ormonthly. A short-time discharge of thebattery will be made to confirm that allbattery blocks and connecting elementsare in good working order. In order topreclude a faulty diagnosis, the testwill be launched, at the earliest, 24hours after the last battery discharge.The battery test will be performedwithout any risk to the user, even if thebattery is completely defective. Adetected battery fault shall be alertedto the user. The battery test shall notcause any degradation in terms ofexpected life of the battery system.The automatic battery test parameters(e.g. activation, time interval etc.) shallbe settable through the graphical LCDdisplay (see section 5.2); also, it shallbe possible to initiate a manual batterytest using the same interface.

6.3 Ambient Temperature CompensatedBattery Charger

The float voltage shall be automaticallyadjusted as a function of thetemperature in the battery compartment(see technical tables for details) tomaximise battery operating life.

6.4 Time Compensated End OfDischarge Voltage

When the discharge time becomeslonger than 1 hour, the shutdown voltageshall be automatically increased, toavoid deep discharge to the batterydue to a light load. The adjustment ofthe EOD voltage shall be controlled bya dedicated algorithm; it shall be alsopossible to modify the algorithmparameters using PPVis connectivitytool (see section 10.12).

07

Page 10: Series C from 10 to 60 kVA - Masterguard Chloride EN/C Series.pdf · MKA4CAT0UKC/Rev. 4-07/2008/UK Series C from 10 to 60 kVA UPS Catalogue • 2008 Uninterruptible Power Supply Systems

7. Mechanical Data

MASTERGUARD Series CUPS Systems from 10 to 60 kVA

MKA4CAT0UKC/Rev. 4-07/2008/UK

For 10 – 40 kVA range the cooling airentry shall be in the front panel and theair exit in the rear panel; clearancerequired in the rear of the unit shall beat least 100mm for ventilation reasons.

7.3 Cable entry

Cable entry shall be from the bottom or bottom-side of the cabinet. Top cable entry shall be available as standard for 50 - 60 kVA range (not valid for special versions).

7.4 Enclosure design

All the surfaces of the enclosure shallbe finished with an electrostaticallyapplied epoxy coat. The coating shallhave a thickness of at least 60 microns.Standard colour of the enclosure shallbe RAL 7035 (light grey).

7.5 Access to integrated subassemblies

For 50 - 60 kVA range, all internalsubassemblies shall be accessible, for typical and most frequentmaintenance, from the front of the unitvia hinged doors. Rear access shall notbe required for installation or servicing.The UPS shall be fork-liftable from thefront after the removal of the bottomtrim panel.For 10 - 40 kVA range, the UPS will bemovable on casters.

7.1 Enclosure

The UPS shall be housed in a space-saving modular enclosure with frontdoors and removable panels (protectionas standard to IP 21 for 10 - 40 kVArange, IP 20 for 50 - 60 kVA). Theenclosure shall be made of zinteccoated sheet steel. The doors shall belockable.

7.2 Ventilation

Forced air cooling will ensure that all thecomponents are operated within theirspecification. For 50 –60 kVA range, thecooling air entry shall be in the baseand the air exit at the top of the device.The enclosure shall be installed with atleast 400 mm of free space betweendevice and ceiling at the top in order toallow an unhindered cooling air exit.

08

Page 11: Series C from 10 to 60 kVA - Masterguard Chloride EN/C Series.pdf · MKA4CAT0UKC/Rev. 4-07/2008/UK Series C from 10 to 60 kVA UPS Catalogue • 2008 Uninterruptible Power Supply Systems

8.Technical Data (10 - 40 kVA range)

MASTERGUARD Series CUPS Systems from 10 to 60 kVA

MKA4CAT0UKC/Rev. 4-07/2008/UK

UPS Unit Rating 10 15 20 30 40

8.1 Rectifier

Nominal input voltage (V) 400

Input phases 3 Ph + N

Input voltage tolerance Full output load (%) -30/+15 -30/+15 -25/+15 -25/+15 -25/+1575% output load (%) -30/+15 -30/+15 -30/+15

Nominal frequency (Hz) 50/60 [selectable]

Frequency tolerance (%) ±10%

Maximum input power Float (kVA) 9.3 13.9 18.5 27.8 37.0Recharge (kVA) 11.2 15.8 20.4 30.3 42.1

Power factor @ nominal input voltage >0.97

Input current distortion at full load (%) <8

Inrush current (A) <Iinput max

8.2 Battery charger

Battery nominal voltage (V) 288 288 288 384 384

Output voltage Operating at 20°C (V) 327 327 327 436 436

Battery float voltage temperature compensation (V/°C %) -3mV cell / °C

Battery ripple current (%)(1) <5

Output current (A) 5 5 5 5 10

8.3 Inverter

Nominal power rating @ 40°C (kVA) 10 15 20 30 40

Nominal power rating @ 25°C (kVA) 11 16.5 22 33 44

Nominal active power rating (kW) 8 12 16 24 32

Power factor 0.8

Overload For 5 minutes (%) 125For 30 seconds (%) 150

Short-circuit current 300 % @ 50 Hz (ms) 10150% @ 50 Hz (s) 5

Output voltage rating (V) 400 [380/415 selectable]

Output frequency (Hz) 50/60

Static output voltage stability for input AC voltage variations within limits and 100% load variations (%) ±1

Dynamic output voltage stability for 100% load variations (%) Complies with IEC/EN 62040-3, Class 1 (VFI, SS, 111)

Phase angle precision with balanced loads (degrees) ±1

Phase angle precision with 100% unbalanced loads (degrees) ±2

Output frequency stabilityWith mains synchronism (%) ±2 [1, 3, 4 selectable]With internal quartz oscillator (%) 0.1

Frequency variation rate (Hz/s) <1 [0.1 to 2 selectable]

Output voltage distortion Linear full load <2%Non-linear full load Complies with IEC/EN 62040-3

Load peak factor without derating (Ipk/IRMS) 3

Neutral conductor sized up to 1.6 Iout nominal

Automatic output power upgrading with temperature @ 25°C (%) 110

@ 30°C (%) 105@ 40°C (%) 100

09

Page 12: Series C from 10 to 60 kVA - Masterguard Chloride EN/C Series.pdf · MKA4CAT0UKC/Rev. 4-07/2008/UK Series C from 10 to 60 kVA UPS Catalogue • 2008 Uninterruptible Power Supply Systems

UPS Unit Rating 10 15 20 30 40

8.4 Static switch

Voltage rating (V) 400 [380/415 selectable]

Nominal frequency (Hz) 50/60 [auto selection]

Frequency tolerance (%) ±2 [0.2 to 6 selectable]

Voltage tolerance (%) ±10 [5 to 15 selectable]

Maximum overload capacityFor 5 minutes (%) 125For 30 seconds (%) 150

Bypass SCR characteristicsI2t @ Tvj =125°C (A2s) 18000ITSM @ Tvj =125°C, 10ms (A) 1900

In-phase switching modebypass/inverter (ms) Make Before Break (0ms)inverter/bypass (ms)

8.5 UPS data

No load dissipated power (W) 300 300 300 500 600

Maximum dissipated power Float (W) 800 1200 1500 2350 3150Recharge (W) 1000 1400 1800 2550 3650

AC/AC efficiency digital interactive mode(2) 100% of load (%) 98

AC/AC efficiency double conversion mode(2) 100% of load (%) 91

Maximum noise level @ 1 metre (± 2 dBA) (dBA) <50 <50 <50 <52 <52

EMC class EN 50091-2 Class A

Degree of protection IP 21

Mechanical dimensions:Height (mm) 1400 1400 1400 1600 1600Width (mm) 500 500 500 550 550Depth (mm) 800 800 800 800 800

Weight without integrated batteries (kg) 145 145 145 190 210

Frame colour (RAL scale) 7035

Cooling Forced

Cable entry Bottom/Side

Equipment mobility On casters

8.6 Environmental

Temperature:Operating (°C) 0 - 40Max average daily (24 hrs) (°C) 35Maximum (8 hrs) (°C) 40

Maximum relative humidity @ 20°C (not condensing) (%) 90

Elevation without derating (-1.2% Pn every 100m above 1000m up to 3000m) (m) 1000

MASTERGUARD Series CUPS Systems from 10 to 60 kVA

MKA4CAT0UKC/Rev. 4-07/2008/UK

8.Technical Data (10 - 40 kVA range)

10

Page 13: Series C from 10 to 60 kVA - Masterguard Chloride EN/C Series.pdf · MKA4CAT0UKC/Rev. 4-07/2008/UK Series C from 10 to 60 kVA UPS Catalogue • 2008 Uninterruptible Power Supply Systems

8.Technical Data (10 - 40 kVA range)

MASTERGUARD Series CUPS Systems from 10 to 60 kVA

MKA4CAT0UKC/Rev. 4-07/2008/UK

UPS Unit Rating 10 15 20 30 40

8.7 Battery

Optimum battery temperature (°C)(3) 20

Power Output (kW) 8.9 13.3 17.8 26.7 35.6

Recommended no. cellsVRLA 144 144 144 192 192

Wet 144 144 144 192 192NiCd 225 225 225 300 300

End of discharge voltage (V) 238 238 238 316 316

End of discharge current (A) 37 56 75 84 113

Charging current (A) 5 5 5 5 10

(1) <0.01 C10 for standard battery configuration.

(2) For tolerances see IEC/EN 60146-1-1 or DIN VDE 0558.

(3) The expected battery life is defined at 20°C. For every increment of 10° above 20°C the expected life is halved.

Note: The data shown are typical and are not specifically defined; furthermore the data refer to 25° C ambient temperature and PF = 1 where not specified. Not all data shown apply simultaneously and are subject to change without notice. If options described in chapter 10 are added, data shown in chapter 8 “Technical data (10 - 40 kVA range)” may be affected.

11

Page 14: Series C from 10 to 60 kVA - Masterguard Chloride EN/C Series.pdf · MKA4CAT0UKC/Rev. 4-07/2008/UK Series C from 10 to 60 kVA UPS Catalogue • 2008 Uninterruptible Power Supply Systems

9.Technical Data (50 - 60 kVA range)

MASTERGUARD Series CUPS Systems from 10 to 60 kVA

MKA4CAT0UKC/Rev. 4-07/2008/UK

UPS Unit Rating 50 60

9.1 Rectifier

Nominal input voltage (V) 400

Input phases 3 Ph + N

Input voltage tolerance Full output load (%) -25/+1575% output load (%) -30/+15

Nominal frequency (Hz) 50/60 [selectable]

Frequency tolerance (%) ±10%

Maximum input power Float (kVA) 45.8 54.9Recharge (kVA) 51.1 60.2

Power factor @ nominal input voltage >0.97

Input current distortion at full load (%) <25

Inrush current (A) <Iinput max

9.2 Battery charger

Battery nominal voltage (V) 396

Output voltage Operating at 20°C (V) 449

Battery float voltage temperature compensation (V/°C %) -3mV cell / °C

Battery ripple current (%)(1) <5

Output current (A) 10

9.3 Inverter

Nominal power rating @ 40°C (kVA) 50 60

Nominal power rating @ 25°C (kVA) 55 66

Nominal active power rating (kW) 40 48

Power factor 0.8

Overload For 5 minutes (%) 125For 30 seconds (%) 150

Short-circuit current 300 % @ 50 Hz (ms) 10150% @ 50 Hz (s) 5

Output voltage rating (V) 400 [380/415 selectable]

Output frequency (Hz) 50/60

Static output voltage stability for input AC voltage variations within limits and 100% load variations (%) ±1

Dynamic output voltage stability for 100% load variations (%) Complies with IEC/EN 62040-3, Class 1 (VFI, SS, 111)

Phase angle precision with balanced loads (degrees) ±1

Phase angle precision with 100% unbalanced loads (degrees) ±2

Output frequency stabilityWith mains synchronism (%) ±2 [1, 3, 4 selectable]With internal quartz oscillator (%) 0.1

Frequency variation rate (Hz/s) <1 [0.1 to 2 selectable]

Output voltage distortion Linear full load <2%Non-linear full load Complies with IEC/EN 62040-3

Load peak factor without derating (Ipk/IRMS) 3

Neutral conductor sized up to 1.6 Iout nominal

Automatic output power upgrading with temperature @ 25°C (%) 110

@ 30°C (%) 105@ 40°C (%) 100

12

Page 15: Series C from 10 to 60 kVA - Masterguard Chloride EN/C Series.pdf · MKA4CAT0UKC/Rev. 4-07/2008/UK Series C from 10 to 60 kVA UPS Catalogue • 2008 Uninterruptible Power Supply Systems

MKA4CAT0UKC/Rev. 4-07/2008/UK

UPS Unit Rating 50 60

9.4 Static switch

Voltage rating (V) 400 [380/415 selectable]

Nominal frequency (Hz) 50/60 [auto selection]

Frequency tolerance (%) ±2 [0.2 to 6 selectable]

Voltage tolerance (%) ±10 [5 to 15 selectable]

Maximum overload capacityFor 5 minutes (%) 125For 30 seconds (%) 150

Bypass SCR characteristicsI2t @ Tvj =125°C (A2s) 80000ITSM @ Tvj =125°C, 10ms (A) 4000

In-phase switching modebypass/inverter (ms) Make Before Break (0ms)inverter/bypass (ms)

9.5 UPS data

No load dissipated power (W) 800

Maximum dissipated power Float (W) 3500 4150Recharge (W) 4000 4650

AC/AC efficiency digital interactive mode(2) 100% of load (%) 98

AC/AC efficiency double conversion mode(2) 100% of load (%) 92

Maximum noise level @ 1 metre (± 2 dBA) (dBA) <55

EMC class EN 50091-2 Class RS

Degree of protection IP 20

Mechanical dimensions:Height (mm) 1780Width (mm) 620Depth (mm) 835

Weight without integrated batteries (kg) 260

Frame colour (RAL scale) 7035

Cooling Forced

Cable entry Bottom/Side/Top

Required service access Front/Top

9.6 Environmental

Temperature:Operating (°C) 0 - 40Max average daily (24 hrs) (°C) 35Maximum (8 hrs) (°C) 40

Maximum relative humidity @ 20°C (not condensing) (%) 90

Elevation without derating (-1.2% Pn every 100m above 1000m up to 3000m) (m) 1000

MASTERGUARD Series CUPS Systems from 10 to 60 kVA

9.Technical Data (50 - 60 kVA range)

13

Page 16: Series C from 10 to 60 kVA - Masterguard Chloride EN/C Series.pdf · MKA4CAT0UKC/Rev. 4-07/2008/UK Series C from 10 to 60 kVA UPS Catalogue • 2008 Uninterruptible Power Supply Systems

MKA4CAT0UKC/Rev. 4-07/2008/UK

9.Technical Data (50 - 60 kVA range)

MASTERGUARD Series CUPS Systems from 10 to 60 kVA

UPS Unit Rating 50 60

9.7 Battery

Optimum battery temperature (°C)(3) 20

Power Output (kW) 44.0 52.7

Recommended no. cellsVRLA 198

Wet 198NiCd 300

End of discharge voltage (V) 327

End of discharge current (A) 134 161

Charging current (A) 10

(1) <0.01 C10 for standard battery configuration.

(2) For tolerances see IEC/EN 60146-1-1 or DIN VDE 0558.

(3) The expected battery life is defined at 20°C. For every increment of 10° above 20°C the expected life is halved.

Note: The data shown are typical and are not specifically defined; furthermore the data refer to 25° C ambient temperature and PF = 1 where not specified. Not all data shown apply simultaneously and are subject to change without notice. If options described in chapter 10 are added, data shown in chapter 9 “Technical data (50 - 60 kVA range)” may be affected.

14

Page 17: Series C from 10 to 60 kVA - Masterguard Chloride EN/C Series.pdf · MKA4CAT0UKC/Rev. 4-07/2008/UK Series C from 10 to 60 kVA UPS Catalogue • 2008 Uninterruptible Power Supply Systems

10.10 MopUPS Shutdown andmonitoring software

The main function of the MopUPSsoftware shall be the safe shutdownof the operating system in the event ofa power failure. Other functions include:

1. Automatic actions for events-email,messages, etc.

2. Recording of event log and status information on files

3. Viewing and monitoring of UPS in real time

4. Programmed system shutdown5. Remote monitoring of UPS

connected to network server usingNamed Pipes or TCP/IP

10.11 ManageUPS adapter

This option shall include a completepackage (including hardware adapter,slot-in for 10 – 40 kVA range) to ensuremonitoring and control of thenetworked UPS through TCP/IPprotocol. The adapter permits:

• UPS monitoring from an NMS viaSNMP

• UPS monitoring from PC via WebBrowser

• Sending of e-mail messages onoccurrence of events

ManageUPS, in conjunction withMopUPS, shall also permit safeshutdown of the operating systems.

10.1 Remote alarm unit

A remote alarm panel shall be availableto display individual importantmessages from UPS. Upon request, it shall be possible to connect up to 4 UPS systems to one alarm unit. The length of the connecting cablemust not exceed 300 m.

10.2 Extended battery charger

It shall be possible to increase the UPS battery recharging capacity by adding one additional batterycharger to the standard one. This additional board shall be housedinside the UPS cabinet.

10.3 Battery Management Modules(only upon request)

With measuring modules connectedto the battery blocks, enhancedbattery management shall be possibleoffering the following features:

• Measuring of the condition of each individual battery block bymeans of separate batterymeasuring modules (BMM)

• Analysis of each battery blockthrough measuring of the minimumand maximum voltage values

10.4 External isolation transformer(only upon request)

This option shall be a double woundtransformer housed in a specialcubicle. Upon specific requirement,the transformer shall be provided withan electrostatic screen and/or with lowinrush current. The option shall beused to isolate the UPS output fromthe load or the rectifier/reserve inputfrom the mains AC input.

10.5 Dust filters

The option shall improve theprotection degree of the air entrancefrom IP21 (IP20) to lP31 (IP30) forspecific applications such as dustyenvironments. The filter shall behoused in the UPS cubicle (IP20/IP21).

10. Options

MASTERGUARD Series CUPS Systems from 10 to 60 kVA

MKA4CAT0UKC/Rev. 4-07/2008/UK

10.6 Input low THDi option (50 - 60kVA only)

Series C features active inputharmonic reduction as standard in the10 - 40 kVA range. For 50- 60 kVA UPS,a low input current distortion optionshall be available, which shall reducethe THDi to less than 10%, withoutsignificantly affecting AC/AC efficiency.The option will be housed inside theUPS cubicle.

10.7 Empty battery cubicle

Matching empty battery cubicles shallbe available and shall include thefollowing:

• Cubicle• Disconnecting device• Fuses• Safety screen• Power terminal block

Three cubicle sizes shall be available:

Width Depth Height Weight(mm) (mm) (mm) (kg)

Type A 820 830 1780 220

Type A1 550 800 1600 100

Type A2 500 800 1400 90

10.8 Empty options cubicle (onlyupon request)

A special cubicle shall be available forcustomised applications such as:

• Input/Output voltage matchingtransformers

• Customised distribution boards• Customised applications

10.9 Telephone switch for LIFE.net

The installation of this telephone switchfor LIFE.net shall allow the customerto use a telephone line normally usedfor other purposes (fax or telephone).

15

Page 18: Series C from 10 to 60 kVA - Masterguard Chloride EN/C Series.pdf · MKA4CAT0UKC/Rev. 4-07/2008/UK Series C from 10 to 60 kVA UPS Catalogue • 2008 Uninterruptible Power Supply Systems

10. Options

MASTERGUARD Series CUPS Systems from 10 to 60 kVA

MKA4CAT0UKC/Rev. 4-07/2008/UK

10.12 PPVIS surveys MonitoringSoftware

The survey images displayed belowsupply the user with essentialinformation on the connected UPS:

State indication - power flux survey

• Current state of components (UPS)• Display of output voltage, UPS

performance and load currents• Number of power failures• Battery cell voltage• Available backup time

10.13 Connectivity tables

The following table displaysconnectivity solutions which can beused in association with Series C. For further details, please refer to the MASTERGUARD ConnectivitySolutions specifications.

The oscilloscope - measuring ofnetwork or load conditions

• Dual-carrier measuring of thecurves of input or output voltages or currents

• Flexible definable trigger conditionscapable of being coupled onto themost different events, e.g. when amains failure occurs

Battery display - Recognizing ofparasitic effects in the early stages (forsingle block monitoring, BMM optionis needed, see 10.3)

• Measuring of the condition of eachindividual battery block by means of separate battery measuringmodules (BMM)

• Through mouse click: Analysis ofeach battery block with measuringof the minimum and maximum voltage values

Single Connectivity Solutions Table for Series C

ManageUPSNET Internal slot-in card(*) or external (box) network adapter (uses one serial port)

MopUPSPROFESSIONAL

Standard serial port (both can be used)

PPVis Serial Port #1 and #2 can be used

LIFE.net Only Serial Port #1 can be used

Simultaneous (up to 2) Connectivity Solutions Table for Series C

Use the two different serial ports and/or the internal slot cards(*)

MangeUPSNET MopUPSPROFESSIONAL

LIFE.net

ManageUPSNET Yes Yes Yes

MopUPSPROFESSIONAL

Yes Yes Yes

LIFE.net Yes Yes No

PPVis Yes Yes Yes

(*) Only for 10 - 40 kVA range

16

Page 19: Series C from 10 to 60 kVA - Masterguard Chloride EN/C Series.pdf · MKA4CAT0UKC/Rev. 4-07/2008/UK Series C from 10 to 60 kVA UPS Catalogue • 2008 Uninterruptible Power Supply Systems

11. Parallel Configuration

MASTERGUARD Series CUPS Systems from 10 to 60 kVA

MKA4CAT0UKC/Rev. 4-07/2008/UK

The Series C series of uninterruptiblepower systems shall have the capabilityto be connected in parallel for multimodule configurations between units ofthe same rating. The maximum numberof UPS in modular parallel configurationshall be 8. The load sharing shall be equalbetween the individual UPS systems, atany output load percentage.

The parallel connection of UPS shallincrease redundancy (for reliability)and power.

RedundancyIf the installation requires more thanone unit in redundant configuration,the power of each UPS should not belower than Ptot/(N-1) where:Ptot = Total load powerN = Number of UPS units in parallel 1 = Minimum coefficient of

redundancy

Under normal operating conditions, thepower delivered to the load shall beshared between the number of UPSunits connected to the parallel bus. Incase of an overload the configuration isable to deliver Pov x N without transferringthe load onto the reserve, where:Pov = Max overload power of a

single UPSN = Number of UPS units in

parallel

In the event of a failure of one of theUPS units, the faulty unit shall bedisconnected from the parallel bus andthe load shall be supplied from theremaining units without any break insupply continuity.

PowerIt shall be possible to increase thepower of the system using a non-redundant parallel configuration(redundancy coefficient = 0). In thiscase, all connected UPS units shalldeliver the rated power, and in theevent of a unit failure or overload thesystem shall transfer the load toreserve.

11.1 Modular parallel operations

The UPS systems of the Series Cseries shall be capable of operating inparallel modular configuration. For thispurpose, UPS systems of the samerating shall be connected in parallel toform multi-module configurations.

The parallel connection of UPS shallimprove reliability or the total outputpower or both. When Series C issupplied with the parallel kit option, upto 8 equal UPS units can be operatedin parallel for power upgrade orincrease of redundancy. This optioncan also be added on at a later date inthe field. It shall consist of onesubassembly POB (Parallel OperationBoard) and 25 pole, screened datalines to the neighbouring UPSmodules. A multi-module system shallbe controlled and monitoredautomatically by controlling theindividual UPS systems (distributedcontrol system). The communicationbus which connects the paralleledunits shall be arranged as a loop,allowing proper parallel operationseven in the case of a singleinterruption occurring to this bus (first-failure proof bus). The reserve linesand inverters included in each UPSshare the load, at any load percentage.See Figure 3 for details about thepower connections.

Figure 3.

Critical Load

SBSOption

UPS 1 UPS 2 UPS n

MainsSupply

SystemBypass

Common Neutral

11.1.1 System bypass switches

A system bypass switch shall beavailable as an option for the modularparallel configuration. This shall includetwo power disconnect switches. The ratings available shall be:

Height Width Depth Weight(mm) (mm) (mm) (kg)

160A 1400 440 840 190

400A 1780 620 858 300

Special SBS are needed forgalvanically isolated special versions T and LAM (see Chapter 12).

17

Page 20: Series C from 10 to 60 kVA - Masterguard Chloride EN/C Series.pdf · MKA4CAT0UKC/Rev. 4-07/2008/UK Series C from 10 to 60 kVA UPS Catalogue • 2008 Uninterruptible Power Supply Systems

12. Special Versions

MASTERGUARD Series CUPS Systems from 10 to 60 kVA

MKA4CAT0UKC/Rev. 4-07/2008/UK

Series C can be customised to achievefull galvanic isolation and voltageadaptation for specific loadrequirements. The following versionsare available upon order:

A further variation of T version, intended for electrically harsh environments, is also available. This version, called Series C-R,features TVSS (Transient Voltage Surge Suppressors) connected in parallel to the input transformer primary winding; thesedevices are housed within the UPS cubicle. For further information about the improved immunity grade of Series C–R tovoltage surges, please contact MASTERGUARD Technical Support.

12.1 T-version

Series C–T includes an internal isolationtransformer on the input. Thistransformer is installed in the place of

batteries (for 10 to 40 kVA) and allowsfull galvanic isolation between the loadand the input mains utility. Technicaldata will change accordingly asindicated in the following table.

DESCRIPTION Unit UPS power rating

kVA 10 15 20 30 40 50 60

Electrical data

INPUT Voltage Vrms 400V, 3Ø (+N), + 15%, (-30% with derating)

Current (single phase) Arms 15 22 29 42 68 85 100

Frequency Hz 50/60 Hz auto selection

OUTPUT Power rating kVA 10 15 20 30 40 50 60

kW 8 12 16 24 32 40 48

Voltage Vrms 380, 400, 415V , 3Ø+N

Current @ 400 Vrms Arms 14 22 29 43 58 72 87

Frequency Hz 50/60 Hz auto selection

Wave form - sinusoidal

Max dissipation (@ nominal load

and battery in recharge) W 1200 1700 2200 3050 4850 6000 6750

Mechanical data

Depth mm 800 835

Width mm 500 550 620

Height mm 1400 1600 1780

Weight kg 280 380 460 560

Max. noise level (@ 1m) dBA <55 <58 <58

18

Page 21: Series C from 10 to 60 kVA - Masterguard Chloride EN/C Series.pdf · MKA4CAT0UKC/Rev. 4-07/2008/UK Series C from 10 to 60 kVA UPS Catalogue • 2008 Uninterruptible Power Supply Systems

12. Special Versions

MASTERGUARD Series CUPS Systems from 10 to 60 kVA

MKA4CAT0UKC/Rev. 4-07/2008/UK

12.2 LAM-version

Series C – LAM includes two internaltransformers for isolation and voltageadaptation from 400V to 208/220Vphase to phase.

These transformers are installed inplace of batteries (10-40 kVA): the oneon the input (isolation transformer)allows full galvanic isolation andvoltage adaptation (208/220 primaryside, 400V secondary side), the one

on the output (auto-transformer)allows voltage adaptation (400Vprimary side, 208/220V secondaryside). Technical data will changeaccordingly to the following table.

DESCRIPTION Unit UPS power rating

kVA 10 15 20 30 40 50 60

Electrical data

INPUT Voltage Vrms 208/220V, 3Ø (+N), + 15%, (-30% with derating)

Current (single phase) Arms 33 50 66 99 132 165 198

Frequency Hz 60 Hz

OUTPUT Power rating kVA 10 15 20 30 40 50 60

kW 8 12 16 24 32 40 48

Voltage Vrms 208, 220V, 415V , 3Ø+N

Current @ 208 Vrms Arms 28 42 56 84 111 139 167

Frequency Hz 60 Hz

Wave form - sinusoidal

Max dissipation (@ nominal load

and battery in recharge) W 1450 2060 2650 3660 5820 7200 8100

Mechanical data

Depth mm 800 835

Width mm 500 550 620

Height mm 1400 1600 1780

Weight kg 350 470 583 720

Max. noise level (@ 1m) dBA <55 <58 <58

19

Page 22: Series C from 10 to 60 kVA - Masterguard Chloride EN/C Series.pdf · MKA4CAT0UKC/Rev. 4-07/2008/UK Series C from 10 to 60 kVA UPS Catalogue • 2008 Uninterruptible Power Supply Systems

Notes

MKA4CAT0UKC/Rev. 4-07/2008/UK

MASTERGUARD Series CUPS Systems from 10 to 60 kVA

20

Page 23: Series C from 10 to 60 kVA - Masterguard Chloride EN/C Series.pdf · MKA4CAT0UKC/Rev. 4-07/2008/UK Series C from 10 to 60 kVA UPS Catalogue • 2008 Uninterruptible Power Supply Systems

Chloride Systems WORLD HEADQUARTERSVia Fornace 3040023 Castel Guelfo (BO)Italy

T +39 0542 632 111F +39 0542 632 120E [email protected]

www.chloridepower.com

For a full list of contacts please visit our website at www.chloridepower.com MK

A4C

AT

0UK

C