Seismic performance of New Zealand two-storey brick veneer houses S J Thurston and G J Beattie NZSEE conference - April 2009

Upload: others

Post on 23-Feb-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Seismic performance of New Zealand two-storey brick veneer …db.nzsee.org.nz/2009/Pres21.pdf · 2012. 1. 20. · Ties are robustly screwed. Ties are proven (via AS/NZS 2699) to carry:

Seismic performance of New Zealand two-storey brick veneer houses

S J Thurston and G J Beattie

NZSEE conference - April 2009

Page 2: Seismic performance of New Zealand two-storey brick veneer …db.nzsee.org.nz/2009/Pres21.pdf · 2012. 1. 20. · Ties are robustly screwed. Ties are proven (via AS/NZS 2699) to carry:

►To see if modern brick veneer

construction performs well in

earthquakes

►To see if the veneer can provide a

bracing function

►To see if use of two-storey veneer

can be incorporated into NZS 3604

Why do the Research?

Page 3: Seismic performance of New Zealand two-storey brick veneer …db.nzsee.org.nz/2009/Pres21.pdf · 2012. 1. 20. · Ties are robustly screwed. Ties are proven (via AS/NZS 2699) to carry:

►Ties are robustly screwed.

►Ties are proven (via AS/NZS 2699) to carry:

10 mm stud shrinkage and plate compression

±20 mm in-plane differential displacement

Out of plane loads (>Tributary weight x 1.7)

►Mainly 70 mm wide brick with holes

Construction Improvements

Page 4: Seismic performance of New Zealand two-storey brick veneer …db.nzsee.org.nz/2009/Pres21.pdf · 2012. 1. 20. · Ties are robustly screwed. Ties are proven (via AS/NZS 2699) to carry:

BRANZ Investigations

Ring beam restraints

Steel ring beam on rollers

Load beam

a) Racking test on a single storey 6.7m x 3.9 m building

Page 5: Seismic performance of New Zealand two-storey brick veneer …db.nzsee.org.nz/2009/Pres21.pdf · 2012. 1. 20. · Ties are robustly screwed. Ties are proven (via AS/NZS 2699) to carry:

BRANZ Investigations

b) Racking test on isolated brick veneer walls in a single storey building

Page 6: Seismic performance of New Zealand two-storey brick veneer …db.nzsee.org.nz/2009/Pres21.pdf · 2012. 1. 20. · Ties are robustly screwed. Ties are proven (via AS/NZS 2699) to carry:

BRANZ Investigations

c) Shake test on a 4 m x 2.5 m clay brick veneer building

Page 7: Seismic performance of New Zealand two-storey brick veneer …db.nzsee.org.nz/2009/Pres21.pdf · 2012. 1. 20. · Ties are robustly screwed. Ties are proven (via AS/NZS 2699) to carry:
Page 8: Seismic performance of New Zealand two-storey brick veneer …db.nzsee.org.nz/2009/Pres21.pdf · 2012. 1. 20. · Ties are robustly screwed. Ties are proven (via AS/NZS 2699) to carry:

BRANZ Investigations

d) Shake test on a 4 m x 2.5 m concrete brick veneer building

Page 9: Seismic performance of New Zealand two-storey brick veneer …db.nzsee.org.nz/2009/Pres21.pdf · 2012. 1. 20. · Ties are robustly screwed. Ties are proven (via AS/NZS 2699) to carry:
Page 10: Seismic performance of New Zealand two-storey brick veneer …db.nzsee.org.nz/2009/Pres21.pdf · 2012. 1. 20. · Ties are robustly screwed. Ties are proven (via AS/NZS 2699) to carry:

► For bricks with internal holes as tested:

Veneer carried large seismic shear loads

From knowing tie characteristics, could

calculate shear loads in veneer

Stable reliable in-plane behaviour

Fully interlocking bricks at corners

enhanced performance

► Did not fully test out-of-plane dynamic

behavior

Conclusions from single storey testing

Page 11: Seismic performance of New Zealand two-storey brick veneer …db.nzsee.org.nz/2009/Pres21.pdf · 2012. 1. 20. · Ties are robustly screwed. Ties are proven (via AS/NZS 2699) to carry:

Why not allowed by NZS 3604? Can only surmise:

► If veneer does not move, then twice inter-storey

slip between veneer and LTF

► Higher inter-storey shear forces

► Higher axial loads on bottom storey veneer

► If large openings in lower storey and upper storey

openings offset, can vertical loads from seismic

rocking be carried?

► Possible injury from falling bricks

Two Storey Brick Veneer

Page 12: Seismic performance of New Zealand two-storey brick veneer …db.nzsee.org.nz/2009/Pres21.pdf · 2012. 1. 20. · Ties are robustly screwed. Ties are proven (via AS/NZS 2699) to carry:

BRANZ Two-Storey Investigations

Side 1 before testing

Note that single storey construction did not have lintels

Steel ring beam on rollers

Page 13: Seismic performance of New Zealand two-storey brick veneer …db.nzsee.org.nz/2009/Pres21.pdf · 2012. 1. 20. · Ties are robustly screwed. Ties are proven (via AS/NZS 2699) to carry:

BRANZ Two-Storey Investigations

Side 2 before testing

Page 14: Seismic performance of New Zealand two-storey brick veneer …db.nzsee.org.nz/2009/Pres21.pdf · 2012. 1. 20. · Ties are robustly screwed. Ties are proven (via AS/NZS 2699) to carry:

Behaviour PredictionTop Spandrel

Middle Spandrel

Bottom Spandrel

► Predictions suggested top storey veneer would behave similar to

single storey

► But bottom storey needed far greater shear forces to make panels rock

► Therefore spandrel cracking likely

Page 15: Seismic performance of New Zealand two-storey brick veneer …db.nzsee.org.nz/2009/Pres21.pdf · 2012. 1. 20. · Ties are robustly screwed. Ties are proven (via AS/NZS 2699) to carry:

Actual Behaviour

Initially force control (NZS 4203 load distribution)

At ±64 mm roof displacement:

► Top storey strength exceeded

► Little displacement or damage in bottom storey

► Behaviour in upper storey was mainly just a rocking mechanism

► Cracks almost fully closed on unload

Switched to deflection control

Page 16: Seismic performance of New Zealand two-storey brick veneer …db.nzsee.org.nz/2009/Pres21.pdf · 2012. 1. 20. · Ties are robustly screwed. Ties are proven (via AS/NZS 2699) to carry:

Brick veneer damage

±143 mm top and ±69 mm first floor displacement

► Veneer cracked near the corners but no separation

► Some cracks passed through bricks

► Horizontal, vertical and diagonal cracks in spandrels

► Cracks mainly originated from window corners

► Some brick crushing at window bottom corners

► Reduced but still large shear forces carried by veneer

Model OK for top storey but unconservative for bottom

storey

Page 17: Seismic performance of New Zealand two-storey brick veneer …db.nzsee.org.nz/2009/Pres21.pdf · 2012. 1. 20. · Ties are robustly screwed. Ties are proven (via AS/NZS 2699) to carry:

Veneer cracking on Side 1 at peak imposed displacement

Page 18: Seismic performance of New Zealand two-storey brick veneer …db.nzsee.org.nz/2009/Pres21.pdf · 2012. 1. 20. · Ties are robustly screwed. Ties are proven (via AS/NZS 2699) to carry:

Veneer cracking on Side 2 at peak imposed displacement

Page 19: Seismic performance of New Zealand two-storey brick veneer …db.nzsee.org.nz/2009/Pres21.pdf · 2012. 1. 20. · Ties are robustly screwed. Ties are proven (via AS/NZS 2699) to carry:

82mm Side 1

Page 20: Seismic performance of New Zealand two-storey brick veneer …db.nzsee.org.nz/2009/Pres21.pdf · 2012. 1. 20. · Ties are robustly screwed. Ties are proven (via AS/NZS 2699) to carry:

143mm Side 1

Page 21: Seismic performance of New Zealand two-storey brick veneer …db.nzsee.org.nz/2009/Pres21.pdf · 2012. 1. 20. · Ties are robustly screwed. Ties are proven (via AS/NZS 2699) to carry:

110mm Side 2

Page 22: Seismic performance of New Zealand two-storey brick veneer …db.nzsee.org.nz/2009/Pres21.pdf · 2012. 1. 20. · Ties are robustly screwed. Ties are proven (via AS/NZS 2699) to carry:

NZS 3604 Recommendations

► Assume veneer can carry its self-

weight induced inertia force (VERY

conservative)

► A simple method is given to calculate

this force

► Simply subtract this from the demand

force stipulated in NZS3604

► Applies to single and two storey

construction

Page 23: Seismic performance of New Zealand two-storey brick veneer …db.nzsee.org.nz/2009/Pres21.pdf · 2012. 1. 20. · Ties are robustly screwed. Ties are proven (via AS/NZS 2699) to carry:

Conclusions

Two storey brick veneer with

reasonable openings performs

well under seismic in-plane loads

and can be conservatively

assumed to carry its self-weight

induced inertia loads

Page 24: Seismic performance of New Zealand two-storey brick veneer …db.nzsee.org.nz/2009/Pres21.pdf · 2012. 1. 20. · Ties are robustly screwed. Ties are proven (via AS/NZS 2699) to carry:

Further Work

► BRANZ two storey tests have not yet

fully examined the veneer

performance under face loading

► Others have performed face load

tests but bricks and ties were older

style

► Face load shaking tests underway

Page 25: Seismic performance of New Zealand two-storey brick veneer …db.nzsee.org.nz/2009/Pres21.pdf · 2012. 1. 20. · Ties are robustly screwed. Ties are proven (via AS/NZS 2699) to carry:

Face load Tests

Page 26: Seismic performance of New Zealand two-storey brick veneer …db.nzsee.org.nz/2009/Pres21.pdf · 2012. 1. 20. · Ties are robustly screwed. Ties are proven (via AS/NZS 2699) to carry:

Acknowledgements

►Building Research funding of the

project

►CSR Monier and Firth Industries for

the supply of bricks

►Eagle Wire Co. for the supply of

ties

►Elephant plasterboard for the

supply of wall linings