Sectionalizing
Rick SeelingIntroductionPhilosophy
Pete MalamenThree Phase ReclosersHigh-Side ProtectionSpecific Applications
![Page 2: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/2.jpg)
History –Early 1970’sSmall Substation Transformers <5,000 kVASingle Phase Reclosers – Mostly H typeLimited Three Phase Reclosers – McGraw Type 3
Phase/Ground Trip PlugsNo Sequential CoordinationNo Automation
Current Limit Fuses for UG ProtectionHigh-Side FusesElectromechanical Relays40 Ohm Minimum Fault Resistance
Smaller Reclosers and FusesUse Smallest Recloser which will Carry Load
![Page 3: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/3.jpg)
History - PresentLarger Substation Transformers >5,000 kVASingle Phase Reclosers – 4H & LThree Phase Reclosers w/ Single Phase Trip
Select Settings on PanelSequential Coordination StandardAutomation
Multiple OptionsSwitchgear w/ E fuses for UG ProtectionThree Phase Circuit Switcher/Transducer High-Side ProtectionSolid-State Relays w/ many Options30 Ohm Minimum Fault resistance
Larger Single Phase ReclosersUse Largest Recloser Possible
![Page 4: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/4.jpg)
Sectionalizing Publications
REA/RUS Bulletin 61-2 – Guide for Making Sectionalizing Study on Rural Electric Systems – 1978 (Rescinded)Cooper/McGraw – Distribution System Protection ManualWestinghouse – Applied Protective RelayingCRN Bulletin 96-5 Ground Fault Impedance Values for System ProtectionManufacturer’s Literature
![Page 5: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/5.jpg)
Recloser Interruption & Control
Hydraulic Interruption & ControlLeast Expensive ($1,200-2,300)Maintain @ 5 Year or Less IntervalsSubject to Miscoordination in Winter
![Page 6: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/6.jpg)
Recloser Interruption & Control
Hydraulic Control & Vacuum Interruption
$100 More Expensive per UnitMaintain @ 10+ Year IntervalsSame Miscoordination as AboveHigher Interruption Ratings
![Page 7: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/7.jpg)
Recloser Interruption & Control
Vacuum Interruption & Solid-State Control
Limited MaintenanceMost Expensive (1-ph: $5,700 & 3-ph: $17,000)Coordination Not Affected by TemperatureMost OptionsHigh Interruption RatingsSolid – Type Insulations (e. g. Epoxy)
![Page 8: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/8.jpg)
Recloser Selection
Interrupting RatingLoadMinimum Fault CoordinationSimultaneous Trip
![Page 9: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/9.jpg)
Recloser Ratings
4000----10K4000--------4002004000----84004000--------28014040002500600040002000----20010040002500----40002000----1407030002500----30002000125010050-----2100----210014008757035----1500----150010006255025----900--------60037530154EEWEL4HH
Min.Trip
CoilSize
![Page 10: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/10.jpg)
Recloser TCC
10 100
1,00
0
10,0
00
Tim
e In
Sec
onds
.1
1
10
100
1,000
70,L(A)
70,L(B)
70,L(C)
70,L(D)
![Page 11: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/11.jpg)
Recloser-Recloser Coordination
C t i A
10 100
1,00
0
10,0
00
Tim
e In
Sec
onds
.1
1
10
70,L(B)
50,L(B)
70,L(A)
50,L(A)
50,4H(B)
50,H(B)
![Page 12: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/12.jpg)
Simultaneous Trip
10 100
1,00
0
10,0
00
Tim
e In
Sec
onds
.1
1
10
100
1,000
70,L(B)
50,L(B)
70,L(A)
50,L(A)
600 400
10 100
1,00
0
10,0
00
Tim
e In
Sec
onds
.1
1
10
100
1,000
70,L(B)
50,L(B)
70,L(A)
50,L(A)
600 400
![Page 13: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/13.jpg)
Simultaneous Trip
i
10 100
1,00
0
10,0
00
Tim
e In
Sec
onds
.1
1
10
100
70,L(B)
70,L(A)
35,L(B)
35,L(A)
800
650
![Page 14: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/14.jpg)
Recloser-Recloser Coordination Summary
One Size Smaller Recloser will CoordinateSkipping one Size will Reduce Simultaneous Trip
May Run Out of Sizes
![Page 15: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/15.jpg)
Recloser–Fuse CoordinationType T
Current in Amperes
10 100
1,00
0
10,000
Time In
Sec
onds
.1
1
10
100
1,000
70,L(B)
70,L(A)
25,T(TC)
15,T (MM)
12,T (MM)
![Page 16: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/16.jpg)
Recloser-Fuse CoordinationType 200
Current in Amperes
10 100
1,00
0
10,0
00
Tim
e In
Sec
onds
.1
1
10
100
1,000
70,L(B)
70,L(A)
30,N(TC)
15,N (MM)
20,N (MM)
Current in Amperes
10 100
1,00
0
10,0
00
Tim
e In
Sec
onds
.1
1
10
100
1,000
70,L(B)
70,L(A)
30,N(TC)
15,N (MM)
20,N (MM)
![Page 17: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/17.jpg)
Recloser-Fuse CoordinationType E
Current in Amperes
10 100
1,00
0
10,0
00
Tim
e In
Sec
onds
.1
1
10
100
1,000
70,L(B)
70,L(A)
15<E (MM)
20,E (MM)
30,E(TC) 40,E
(TC)
![Page 18: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/18.jpg)
Recloser-Fuse Summary
Fuse Total Clearing Faster than RecloserDelayFuse Minimum Melt Slower than Recloser FastPick a Standard – Usually Largest Fuse Possible
![Page 19: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/19.jpg)
Fuse-Fuse Coordination
C i A
10 100
1,00
0
10,0
00
Tim
e In
Sec
onds
.1
1
10
100
1,000
25,T (MM)20,T
(TC)
![Page 20: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/20.jpg)
Fuse-Fuse Coordination (T Type)
Current in Amperes
10 100
1,00
0
10,0
00
Tim
e In
Sec
onds
.1
1
10
100
1,000
10,T 15,T 25,T 40,T
![Page 21: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/21.jpg)
Fuse-Fuse Coordination (T Type)
Current in Amperes
10 100
1,00
0
10,0
00
Tim
e In
Sec
onds
.1
1
10
100
1,000
30,T20,T12,T8,T
![Page 22: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/22.jpg)
Fuse-Fuse Coordination (T-Bayonet)
Current in Amperes
10 100
1,00
0
10,0
00
Tim
e In
Sec
onds
.1
1
10
100
1,000
25,T (MM)
C10 (25A.) Bayonet
![Page 23: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/23.jpg)
Fuse-Fuse Coordination (T-E)
Current in Amperes
10 100
1,00
0
10,0
00
Tim
e In
Sec
onds
.1
1
10
100
1,000
10,000
25,T (MM)
25,E MM)(Std & Slow)
C i A
10 100
1,00
0
10,0
00
Tim
e In
Sec
onds
.1
1
10
100
1,000
25,T (MM)
25,E MM)(Std & Slow)
![Page 24: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/24.jpg)
Fuse-Fuse Coordination (T-K)
i
10 100
1,00
0
10,0
00
Tim
e In
Sec
onds
.1
1
10
100
1,000
10,000
25,T (MM)
25,K (MM)
![Page 25: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/25.jpg)
Fuse-Fuse Coordination (T-CL)
C i A
10 100
1,00
0
10,0
00
Tim
e In
Sec
onds
.1
1
10
100
1,000
10,000
25,T (MM)
25, NX C (MM)
25 NXII (MM)
Current in Amperes
10 100
1,00
0
10,0
00
Tim
e In
Sec
onds
.1
1
10
100
1,000
25,T (MM)
25, NX C (MM)
25 NXII (MM)
![Page 26: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/26.jpg)
Fuse-Fuse CoordinationSummary
Total Clearing Faster than Minimum MeltStick within a Series or Skip a SizeAvoid Mixing Different Types
![Page 27: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/27.jpg)
Sectionalizing Philosophy
CompromiseCompromiseCompromise
![Page 28: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/28.jpg)
Minimum Fault Resistance
40 OhmOld REA/RUS StandardBased on 1920’s Bell Lab StudiesLargest Single Phase Recloser - 70 Amp Smaller Reclosers and Fuses Overall
![Page 29: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/29.jpg)
Minimum Fault Resistance
30 OhmSupported by CRN 96-5Less ConservativeLargest Single Phase Recloser – 100 AmpLarger Reclosers & FusesFewer Three Phase Reclosers
![Page 30: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/30.jpg)
Minimum Fault Resistance
Values Used by IOU’sNSP/Excel – 20 OhmsMP – 0 Ohms or Twice Load Current
![Page 31: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/31.jpg)
Sectionalizing PhilosophyRecloser Sizing
Smallest vs. Largest vs. HybridSmallest
Smallest Recloser which can carry loadFaster Fault ClearingSmaller Load-Side Fuses
![Page 32: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/32.jpg)
Recloser Sizing
LargestLargest Recloser that CoordinatesLarger Load-Side FusesFewer Changes in Future
HybridSame as Largest, but Size Reclosers to Twice Load LevelLess Simultaneous Tripping
![Page 33: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/33.jpg)
Fast vs. Delay Operations
Substation (1) Fast & (3) Delay
85% Faults TemporaryBetter Coordination with Down-Stream ReclosersFewer Consumers Affected by Interruption
(0) Fast & (3 or 4) DelayPossibly More Outages for Temporary FaultsExcellent Coordination with Down-Stream ReclosersNo Interruption to Affect Electronic or Commercial Loads
![Page 34: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/34.jpg)
Fast vs. Delay Operations
Feeder Reclosers(2) Fast & (2) Delay
Almost UniversalAllows for Temporary Faults to Clear – Fewer OutagesAffects Electronic Equipment – Reset Clocks
![Page 35: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/35.jpg)
Fast vs. Delay OperationsUnderground
(1) DelayNo Temporary Faults on UGShouldn’t Use If Overhead BeyondLeast Amount of Cable Damage
(2) DelayGood Coordination if Fuse Used for Overhead Beyond or Fuses on UGLimited Cable Damage
(2) Fast & (2) DelayNecessary if Overhead Feeder BeyondMost Cable Damage
![Page 36: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/36.jpg)
Recloser Spacing
Mileage Between Reclosers on Three Phase 5 Miles
Sectionalize Circuit MoreShorter OutagesRun Out of Sizes on Long Feeders
10 MilesMore Line to Patrol for Outage – Longer OutagesNot as Likely to Run Out of Sizes Except at 24.9kV
Longer DistanceDifficulty Finding FaultMostly Easily to Backfeed
![Page 37: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/37.jpg)
Tap Protection w/ Recloser vs. Fuse
RecloserSmaller Reclosers or Lightly Loaded ReclosersMore Expensive if have to Purchases ReclosersOne More Operation for Temporary Fault –Fewer OutagesSmaller Fuses on Taps Beyond Recloser
FuseLarger Fuses and on TapReplace Fuse for OutagePossibly More Outages
![Page 38: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/38.jpg)
Feeder Protection
ReclosersSubstationTaps with Load Larger than 20 amps or Longer than 5 MilesEvery 10 Miles Along Three PhaseEvery 10 Miles Along Taps Where Load Larger than 20 AmpsBeyond Special Loads
![Page 39: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/39.jpg)
Feeder Protection
FusesAll Taps or All Taps Longer than Three SpansDivide Taps Longer than 10 Miles
SectionalizersAll Taps that Could be Fuses, But Would Overload Fuse
![Page 40: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/40.jpg)
Minimum Line Recloser & Fuse Size
What Size Transformer Fuse Do You Want to Coordinate?
![Page 41: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/41.jpg)
Minimum Recloser & Fuse Size
What Size Transformer Fuse Do You Want to Coordinate?
25 kVA – 6,T
![Page 42: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/42.jpg)
Minimum Recloser & Fuse Size
Current in Amperes
10 100
1,00
0
10,0
00
Tim
e In
Sec
onds
.1
1
10
100
1,000
6,T (TC)
10,T
Current in Amperes
10 100
1,00
0
10,0
00
Tim
e In
Sec
onds
.1
1
10
100
1,000
6,T (TC)
10,T
![Page 43: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/43.jpg)
Minimum Recloser & Fuse Size
What Size Transformer Fuse Do You Want to Coordinate?
25 kVA – 6,TLine Fuse – 10,T
![Page 44: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/44.jpg)
Minimum Recloser & Fuse Size
C i A
10 100
1,00
0
10,0
00
Tim
e In
Sec
onds
.1
1
10
100
1,000
6,T (TC)
10,T
25,4H(B)
Current in Amperes
10 100
1,00
0
10,0
00
Tim
e In
Sec
onds
.1
1
10
100
1,000
6,T (TC)
10,T
25,4H(B)
![Page 45: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/45.jpg)
Minimum Recloser & Fuse Size
What Size Transformer Fuse Do You Want to Coordinate?
25 kVA – 6,TLine Fuse – 10,TRecloser – 25 amp
![Page 46: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/46.jpg)
Fuses in Series
ConsiderationsDamage to Upstream FusesMinimum Fuse SizeCoordination LimitationsAvoid as Much as Possible
![Page 47: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/47.jpg)
Sectionalizing
Rick SeelingIntroductionPhilosophy
Pete MalamenThree Phase ReclosersHigh-Side ProtectionSpecific Applications
![Page 48: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/48.jpg)
![Page 49: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/49.jpg)
Three Phase Reclosers
![Page 50: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/50.jpg)
Hydraulic Reclosers
![Page 51: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/51.jpg)
Recloser with CT’s & Solenoids
![Page 52: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/52.jpg)
Electronic Control
![Page 53: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/53.jpg)
Triple-Single Option
1Ø Trip, 1Ø L.O.1Ø Trip, 3Ø L.O.3Ø Trip, 3Ø L.O.
![Page 54: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/54.jpg)
Current in Amperes
100
1,00
0
10,0
00
100,
000
Tim
e In
Sec
onds
.01
.1
1
10
100
1,000
100 A PU, TD=2 U4-US Ext Inv
300 A PU, TD=2 U4-US Ext Inv
200 A PU, TD=2 U4-US Ext Inv
Time Dial Settings
![Page 55: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/55.jpg)
Current in Amperes
100
1,00
0
10,0
00
100,
000
Tim
e In
Sec
onds
.01
.1
1
10
100
1,000
200 A PU, TD=4 U4-US Ext Inv
200 A PU, TD=1 U4-US Ext Inv
200 A PU, TD=2 U4-US Ext Inv
Pickup Settings
![Page 56: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/56.jpg)
Current in Amperes
100
1,00
0
10,0
00
100,
000
Tim
e In
Sec
onds
.01
.1
1
10
100
1,000
100 A PU, TD = 4 U2-US Inverse
300 A PU, TD = 2 U4-US Ext Inv
Phase – Ground Coordination
![Page 57: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/57.jpg)
ANSI Standard Device Designation Numbers
25) Synchronizing or Synchronism-Check Device Is a device that operates when two a-c circuits are within the desired limits of frequency, phase angle, or voltage, to permit or to cause the paralleling of these two circuits.
27) Undervoltage Relay Is a relay that functions on a given value of under-voltage.
32) Directional Power Relay Is a device that functions on a desired value of power flow in a given direction or upon reverse power resulting from arcback in the anode or cathode circuits of a power rectifier.
50) Instantaneous Overcurrent or Rate-of-Rise Relay Is a relay that functions instantaneously on an excessive value of current or on an excessive rate of current rise, thus indicating a fault in the apparatus or circuit being protected.
51) A-C Time Overcurrent Relay Is a relay with either a definite or inverse time characteristic that functions when the current in an a-c circuit exceed a predetermined value.
![Page 58: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/58.jpg)
ANSI Standard Device Designation Numbers
52) A-C Circuit BreakerIs a device that is used to close and interrupt an a-c power circuit under normal conditions or to interrupt this circuit under fault of emergency conditions.
59) Overvoltage Relay Is a relay that functions on a given value of over-voltage.
67) A-C Directional Overcurrent Relay Is a relay that functions on a desired value of a-c overcurrent flowing in a predetermined direction.
79) A-C Reclosing Relay Is a relay that controls the automatic reclosing and locking out of an a-c circuit interrupter.
81) Frequency Relay Is a relay that functions on a predetermined value of frequency (either under or over or on normal system frequency) or rate of change of frequency.
89) Line Switch Is a switch used as a disconnecting, load-interrupter, or isolating switch in an a-c or d-c power circuit, when this device is electrically operated or has electrical accessories, such as an auxiliary switch, magnetic lock, etc.
![Page 59: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/59.jpg)
One-line Diagram
![Page 60: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/60.jpg)
Conductor Arcing through Asphalt
![Page 61: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/61.jpg)
Conductor Breakage / Glassification
![Page 62: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/62.jpg)
Steady State Harmonic Energy
![Page 63: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/63.jpg)
Arcing Fault Harmonic Energy
![Page 64: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/64.jpg)
Substation Protection
![Page 65: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/65.jpg)
Current in Amperes
100
1,00
0
10,0
00
100,
000
Tim
e In
Sec
onds
.01
.1
1
10
100
1,000
10,00065E SMD-Standard -Total Clear A0.87 Low-Side Line to Line Fault
Mechanical Damage
Inrush
Thermal Damage
5,000 kVA, 69-12.47 kV Transformer
65E SMD-Standard -Total Clear A1.73 Low-Side Single Line to Ground Fault
65E SMD-Standard -Total Clear Low-Side Three Phase Fault
Substation Transformer
![Page 66: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/66.jpg)
Current in Amperes
100
1,00
0
10,0
00
100,
000
Tim
e In
Sec
onds
.01
.1
1
10
100
1,000
10,000
Mechanical Damage
Thermal Damage
Inrush
12/16/20 MVA, 69-12.47 kV Transformer
150E SMD-Standard -Total Clear
150E SMD-Standard -Total Clear A1.73 Low-Side Single Line to Ground Fault
Low-Side Three Phase Fault
Large Substation Transformers
![Page 67: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/67.jpg)
Zones of Protection
![Page 68: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/68.jpg)
Differential Relays
![Page 69: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/69.jpg)
C.T. Curves
![Page 70: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/70.jpg)
Transformer Protection
![Page 71: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/71.jpg)
One-line Diagram
![Page 72: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/72.jpg)
Specific Applications
![Page 73: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/73.jpg)
Current in Amperes
10 100
1,00
0
10,0
00
Tim
e In
Sec
onds
.001
.01
.1
1
10
100
1,000
GE 10% Probability Case Rupture 100 kVAr Units
15 T -Total Clear
15 T -Minimum Melt
Capacitor Protection
![Page 74: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/74.jpg)
Current in Amperes
10 100
1,00
0
10,0
00
Tim
e In
Sec
onds
.001
.01
.1
1
10
100
1,000
GE 10% Probability Case Rupture 100 kVAr Units
15 T -Total Clear
15 T -Minimum Melt
25 T -T otal Clear
25 T -Minimum Melt
Parallel Capacitors
![Page 75: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/75.jpg)
Current in Amperes
10 100
1,00
0
10,0
00
Tim
e In
Sec
onds
.001
.01
.1
1
10
100
1,000
100 kVAr Units
GE 10% Probability Case Rupture
25 T -Total Clear
25 T -Minimum Melt
25K NX Companion Fuses -Minimum Melt
25K NX Companion Fuses -Total Clear
Capacitor with C.L. Fuse
![Page 76: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/76.jpg)
Current Limiting Fuses
Partial range C.L. fusesPad/Pole TransformerOverhead capacitors
Underground applicationsPower qualityHard to coordinate areas
![Page 77: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/77.jpg)
Step Down Transformer Protection
![Page 78: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/78.jpg)
![Page 79: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/79.jpg)
Automatic Loop Restoration - 5 Reclosers
Substation 1 3.3 miles
R
3.3 miles
Substation 2
R
N.O.RecloserR
N.C.Recloser
N.C.Recloser
N.C. - Normally-ClosedN.O. - Normally-Open
R
R
N.C.Recloser
N.C.Recloser
3.3 miles
![Page 80: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/80.jpg)
Loop Coordination
Loss of VBy # of recloses & loss of VNormal O.C. & comm.Current diff & comm.
![Page 81: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/81.jpg)
Control Logic
![Page 82: Sectionalizing - usgweb.com Presentation.pdf · Necessary if Overhead Feeder Beyond ... Feeder Protection ... Is a relay with either a definite or inverse time characteristic that](https://reader030.vdocuments.us/reader030/viewer/2022021510/5aa8bf8b7f8b9a90188bef2c/html5/thumbnails/82.jpg)
Questions & comments