Section 4.1Ground Floors
Below slab
Product: Polyfoam ECO Floorboard Gf01
Suspended concrete floor
Product: Polyfoam ECO Floorboard
Above slab
Product: Polyfoam ECO Floorboard
Gf03
Gf04
Above slab
Product: Earthwool Thermal Floor Slab Plus
Gf02
Suspended concrete floor
Product: Earthwool Thermal Floor Slab Plus
Gf05
Suspended timber floor
Product: Earthwool Loft Roll 44 / 40
Gf06
Underfloor heating - Standard system
Product: Polyfoam ECO Floorboard Gf07
Suspended timber floor
Product: Earthwool Flexible Slab
Gf08
4.1 Ground Floors
Technical Advice and Support Centre 01744 766666 www.knaufinsulation.co.uk204
Ground floorsGround floor design
GeneralWhen designing a ground floor the following should be considered in addition to the achievement of the desired U-value.
• Appliedfloorloading
• Positionoftheinsulationwithinthe floor structure
• Minimisingthermalbridging,airleakageandpreventingcondensationforming
IntroductionGround bearing floors can include insulationeitherbeloworabovetheconcreteslab,dependingonthechoiceofthedesigner.Iftheinsulationisinstalledbelowtheslab,thisincreasesthethermalcapacityofthebuilding,helpingtomaintainsteadyinternaltemperatures.Ifinsulationisinstalledabovetheslab,thebuildingwillrespondmuchmorequicklytotheheatingsystem.Suspendedfloorsareusuallyinsulatedinsuchawaythattheyofferreducedthermalmassandrespondquicklytotheheatingsystem.Inthecaseofsuspendedconcrete,theinsulationisinstalledabovethedeck,eitherunderascreedortimberboarding.Suspendedtimberfloorsarenormallyinsulatedbetweenthejoists.Floorinsulationisofparticularimportanceif installing underfloor heating. The use ofchannelled rigid insulation boards cancombine the function of floor insulation andhousingfortheheatingpipes.
AppliedfloorloadingAllmaterialsarecompressedunderload.Insulationmaterialsusedunderslabs,screedsandchipboardshouldbecapableofaccommodatingtheappliedloadswiththeminimumofcompression.
Standardised values are available to the designerforthedeadloadsappliedbybuildingcomponentsandtheestimatedactiveloadsforvarioustypesofbuildinguse.Theseformthestructuraldesignrequirementsofthefloor,butare of less value when considering the compressionresistancerequirementsofthefloorastheactiveloadsarelikelytobelocalisedorpointloads,notuniformlydistributedloads.
Position of InsulationAswaspreviouslystated,thepositionoftheinsulation in the floor has an influence over the thermal characteristics that the floor brings to thebuilding,howeveritalsohasrelevancewhenconsideringtheactiveloadsthatapplyduetotheuseofthefloor.Obviously,intimberjoistfloorswheretheinsulationmaterialisplacedbetweenthejoiststheentireloadiscarriedbythejoistsandthereisnoloadontheinsulation.However,wheretheinsulationisbelowaslab,screedortimberboardstheentireload is acting on the insulation.
Pointloadsarespreadbythelayersabovetheinsulation so that the load acting on the insulationislowerthantheloadappliedtothefloorsurface.Thespreadofaloadisafunctionofthedepthofthelayerabovetheinsulation.Thismeansthatapointloadappliedtoafloorwheretheinsulationispositionedbelowathinscreedwillresultinahigherappliedloadonthe insulation than where the insulation was positionedbelowathickerfloorslabbecausethe load is bearing on a smaller area of insulation under the screed. Of course the differingdeadloadappliedbythescreedandthe floor slab should also be allowed for when calculatingthetotalloadappliedtotheinsulation.
Active and dead loadsTheactualappliedfloorloadactingontheinsulationmaterialhastwocomponents:
• Thedeadload,whichisduetotheweightofthematerialslaidontheinsulant,and
• Thedesignloadassociatedwiththeuseofthe floor
Forspecificapplicationstheguidanceandrecommendations contained in BS EN 1991-1-1:2002andBSEN1990:2002+A1:2005shouldbefollowed,andthiswillhelpthedesigner ensure that the strength of the floor will besufficienttosupportanyappliedloadsoverthe loaded area.
Thedesignermustalsoconsiderthedynamicloadsandhowtheyareapplied.
Inrealitytheloadsassociatedwiththeuseofthefloorwillnotbeapplieduniformly.Infactmanyloadsareappliedinalocalisedwayorevenaspointloadssothatwhilsttheoverallload on a floor is in line with the relevant standardsthelocalisedloadingmaybemanytimeshigher.Forexample,acupboardraisedonfeethasasignificantlyincreasedpointloadingcomparedtoonesatonthewholebase. This results in increased localised loading acting on the insulation.
4.1Ground Floors
Technical Advice and Support Centre 01744 766666 www.knaufinsulation.co.uk 205
4.1
Compression resistanceTheinsulationmaterialwillbecompressedbythetotalloadappliedtoit.Itisvitallyimportantthat the insulation material has sufficient compressionresistancetorestricttheeffectsofthecompressiveload.Compressionresistanceismeasuredintwoways,mostcommonlytheimmediateeffectofcompressiveloadismeasuredandthisisquotedasacompressionresistanceinkPa.Theapplicationssectionshowsthecompressionresistanceofindividualinsulationmaterials,thisisusefulinidentifyingthegeneralsuitabilityofamaterialfortheapplicationintended.Thesecondmeasurementofcompressionresistancemeasuresthelongterm effects of loading on a material and is describedascompressivecreep.Wherehigherloadsareappliedthisfigurehashighrelevanceas long term loading will result in greater progressivecompressionofthicknessinsomeinsulation materials than others.
Compressive creepCompressivecreepisthemeasuredvalueofthelong term behaviour of a material under load. Highresistancetocompressivecreepiscriticalforlong-termstructuralperformance.Theidealinsulation material used in flooring needs to be strong without being brittle over the long term asthiswillminimiseanybuildingmovement.Amaterialwithsuperiorresistancetocompressivecreepenablesdesignerstotrulyoptimisetheirdesigntomaximisethepotentialusesofthestructurewithouttheriskoffailureinthemediumto long term.
Compressivecreeptestsarenecessarilylongtermprojectsastheypredicttheeffectofloadingover50years.PolyfoamECOextrudedpolystyrene(XPS)insulationhasbeentestedforcompressivecreepandachievedtheresultsshown in Table 1.
Thermal Bridging and Air LeakageThermal bridges are a significant source of heat lossandtheymayalsocauselocalisedcondensation and mould growth. The details on thefollowingpagesillustratebestpractice.
CalculationofU-valuesUnlikewallsandroofs,theheatlossthrough agroundfloorvarieswithitssizeandshape.TheBuildingRegulationsrequirethatwhenground floor U-values are calculated the methodologyinBSENISO13370:1998shouldbeemployed.
Thisstandardusestheratiooftheexposedfloorperimetertothefloorareatotakeaccountofthe variation in heat loss due to floor size and shape.
Themeasurementoftheperimeterandareashould be to the finished inside surfaces of the perimeterwallsthatenclosetheheatedspace.Projectingbaysshouldbeincluded,butunheatedspacessuchasporchesorgaragesshould be excluded.
When considering extensions to existing buildingsthefloordimensionsmaybetakenasthoseofthecompletebuildingincludingtheextension.
Table 1 - Compressive creep results for Polyfoam ECO Floorboards
Product Load applied kPa
Initial compression % Further compression after 50 years %
PolyfoamECOFloorboard Standard
60 2 1.5
PolyfoamECOFloorboard Extra
120 2 1.5
PolyfoamECOFloorboardSuper
175 2 1.5
WorkedexampleThefollowingworkedexampleillustrateshow toestablishtheP/Aratio.
ExampleAsemi-detachedhouseasshownbelow
Perimeter (P) = 8+4+3+6+5 = 26m
Area (A) = (10x8)-(6x3) = 62m2
Ratio (P/A) = 26/62 = 0.42
AgroundfloorwithaP/Aratioof0.42wouldachieveaU-valueof0.25W/m2K if insulated with75mmPolyfoamECOFloorboardStandardin a ground bearing concrete slab.
Determining the U-valueThe tables for each ground floor solution show typicalU-valuesforarangeoffloorconstructions,assumingaconductivityof1.50W/mKforthegroundbelowthefloor.
The high number of variables that have to be takenintoaccountcansignificantlyaffectthe U-valueforaparticularsetofconditions. ProjectspecificU-valuecalculationscanbesuppliedbyourTechnicalAdviceandSupportCentre.
CondensationAvapourcontrollayerisnotnormallyrequiredformostgroundfloorconstructions.However, avapourcontrollayerisrecommendedbetweentheinsulationandachipboardfloor,especiallyifthereisariskofexcessivemoisturefromthefloorslabdryingout.
4.1 Ground Floors
Technical Advice and Support Centre 01744 766666 www.knaufinsulation.co.uk206
Ground floors
Above slabProduct:EarthwoolThermalFloorSlabPlus
Seepage:210
Below slabProduct:PolyfoamECOFloorboard Seepage:208
Knauf Insulation solution
Solutionoptimiserandpathfinder
U-values 0.25 0.20 0.15 0.09
Gf01
Gf02
Above slabProduct:PolyfoamECOFloorboard
Seepage:212
Gf03
Suspended concrete floor Product:PolyfoamECOFloorboard
Seepage:214
Gf04
Suspended concrete floorProduct:EarthwoolThermalFloorSlabPlus
Seepage:216
Gf05
0.300.33
4.1Ground Floors
Technical Advice and Support Centre 01744 766666 www.knaufinsulation.co.uk 207
4.1
Suspended timber floorProduct: Earthwool LoftRoll44/40
Seepage:218
Gf06
Suspended timber floor Product: Earthwool Flexible Slab
Seepage:218
Gf08
Underfloor heating - Standard system Product:PolyfoamECOFloorboard
Seepage:220
Gf07
Knauf Insulation solution U-values
Key
Thermalinsulationachievablebyconstructionswithinthisdocument.
Findonline.Visitknaufinsulation.co.ukandkeyinconstructioncodetofindthe
mostuptodateinformationonyourchosensolution.Pb01
0.25 0.20 0.15 0.090.300.33
4.1 Ground Floors
Technical Advice and Support Centre 01744 766666 www.knaufinsulation.co.uk208
Ground floorsBelow slab
Polyfoam ECO Floorboard
PerformanceThermal performanceThethermalconductivitiesofPolyfoamECOFloorboardproductsare:-
StandardandExtra–0.033W/mK
Super–0.034-0.036W/mK
Unlikemostotherinsulants,moisturehasanegligibleeffectonthermalperformance.
Fire performanceWhenPolyfoamECOFloorboardisinstalledinaconcretefloorconstruction,itwillnotcontributetothedevelopmentstagesofafire.
Moisture resistanceMoistureresistanceofPolyfoamECOFloorboardenablesittobelaidexposedtogroundwater,withnegligibleimpactonperformance.Theboardsthemselvesdonotperformthefunctionofadampproofmembrane,butcanbelaidindampconditionsorupagainstwetconcretewithoutcompromisingthermalperformance.
Compression resistancePolyfoamECOFloorboardishighlyresistanttocompressionandwithstandsbothoccasionaland long term static loads. Load bearing construction elements should be designed to adequatelysupportthecombinationofimposedand dead loads without creating excessive deflection.
InstallationLevel the sand blinding over the hardcore to receive the insulation.
LaythePolyfoamECOFloorboarddirectlyonthesandblindingandthenlaythedpmovertheinsulationandlapwiththewalldampproofcourse.Alternatively,layPolyfoamECOFloorboardoverthedpminastretcherbrickbondpatterntocoverthewholefloorarea.Thejointsshouldbetightlybuttedtogether.Wheninstallingtheinsulationboardsinlayers,staggerthelayoutoftheboardstoavoidcoincidentverticaljointsrunningthroughthetotalinsulationthickness.Usespreaderboards,asnecessary,topreventpointloadspuncturingthedpm.Asliplayerisrequiredbetweentheinsulation and the concrete slab.
Placeastripofinsulation,minimum25mmthick,verticallyattheslabperimetertominimisethermalbridging.Theheightoftheperimeterinsulationtoequaltheslabthickness.Ensuretheperimeterinsulationboardsaresecurelyheldinplacetopreventdislodgementbyfollowingwork,e.g.bytapingthemtothemainfloorinsulation.
Laytheconcreteslab.Theconcreteslabmaybescreededoralternativelyhaveapowerfloatfinish.
ProductsPolyfoam ECO Floorboard is a range of rigid extrudedpolystyreneinsulationboards.
Theyarelightweight,haveexcellentstructuralstrength and long term effectiveness and are availableinthreegrades:
Polyfoam ECO Floorboard Standard – domestic and light commercial loading
Polyfoam ECO Floorboard Extra–commercial,industrial flooring and cold storage
Polyfoam ECO Floorboard Super–veryhighloadcommercial,industrialandcoldstoragefloors.
Typical constructionAsolidconcretegroundfloorslabcastoninsulationonadampproofmembrane(dpm)laidoverblindedhardcore.Alternativelyconcretefloorslabcastonadampproofmembrane laid over the insulation. The wall insulationshouldstartaminimumof150mmbelowthetopofthefloorinsulation.Thereshould be a flexible sealant between the wall finishandthefloorslabtominimiseairleakageatthisjunction.
• Moistureresistant-longterm exposure to water has negligible impact on thermal performance
• Highcompressivestrength-protects damp proof membrane from damage
• Robust and can tolerate traffic from following trades without damage prior to floor finish being laid
Polyfoam ECO Floorboard
• BBAcertified
• ZeroOzoneDepletionPotential(ODP)
• GlobalWarmingPotential(GWP)<5
04/4186
PolyfoamECOFloorboard
PolyfoamECOFloorboard
Dampproofmembrane
25mmPolyfoamECOFloorboardatperimeterofslab
Concretefloorslab
Wall insulation takendownatleast150mm belowtopoffloorinsulation
Sliplayer,oralternativepositionfordampproofmembrane
Sand blinding
Flexible sealantGf01
NEW BUILD REFURB
4.1Ground Floors
Technical Advice and Support Centre 01744 766666 www.knaufinsulation.co.uk 209
4.1
Cavitywallinsulation
Minimum150mmoverlapbetween wall and floor insulation
to minimise thermal bridging
Flexible seal between wall finish and floor
Continuousribbonofplasterboardadhesive
PolyfoamECOFloorboard Dampproofmembrane
25mm(min)PolyfoamECOFloorboardatslabperimeter
TypicalspecificationThe whole of the ground floor area between brick,blockorconcretewallstobeinsulatedwithPolyfoamECOFloorboardStandard*/Extra/*Super*…...mmthickandlaiddirectlyoverblindedhardcore.PolyfoamECOFloorboardStandard*/Extra/*Super*atleast25mmthick,tobecutandplacedverticallyagainstthewallstothedepthoftheconcreteslab.
Theinsulationtobelaidabove*/below*dampproofmembrane,whichshouldlaptheperimeterwalldampproofcourse.Concreteslabandfloorfinishasspecifiedbythedesigner. (*deleteasappropriate)
Alternatively,consulttheNationalBuildingSpecifications,Standardversionclause/clauses…E20/30or
E20/200……………
KnaufInsulationspecificationclausescanbedownloadedfromknaufinsulation.co.uk/nbs
Typicalwall/floorjunction
Table 2 - U-values for concrete ground floors insulated below slab
U-values(W/m2K)
Thickness(mm) Ratioofperimeter(m)toarea(m2)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
Polyfoam ECO Floorboard Standard and Extra
165 (100+65)* 0.09 0.12 0.14 0.15 0.15 0.16 0.16 0.17
150 (75+75) 0.10 0.13 0.15 0.16 0.17 0.18 0.18 0.18
140 (75+65) 0.10 0.14 0.16 0.17 0.18 0.18 0.19 0.19
125 (75+50) 0.11 0.15 0.17 0.18 0.19 0.20 0.20 0.21
110 (75+35) 0.11 0.16 0.18 0.19 0.21 0.22 0.22 0.23
100 (1x100)** 0.11 0.16 0.19 0.20 0.21 0.22 0.23 0.24
90 (65+25) 0.12 0.17 0.20 0.22 0.24 0.25 0.26 0.26
75 (1x75) 0.13 0.19 0.23 0.25 0.27 0.28 0.29 0.30
65 (1x65) 0.13 0.20 0.24 0.27 0.29 0.30 0.32 0.33
U Value Competency SchemeCERTIFICATE CS/1001-2
Note: The U-values have been calculated assuming a clay subsoil with a thermal conductivity of 1.50 W/mK.
U-values for Polyfoam ECO Floorboard Super available on request - contact Technical Advice and Support Centre
* Polyfoam ECO Floorboard Extra - 2x50+65
** Polyfoam Floorboard ECO Extra - 2x50
Table 3 - Compressive creep results for Polyfoam ECO Floorboards
Product Load applied(kPa)
Initial compression
(%)
Further compressionafter50years(%)
PolyfoamECOFloorboard Standard
60 2 1.5
PolyfoamECOFloorboard Extra
120 2 1.5
PolyfoamECOFloorboard Super
175 2 1.5
4.1 Ground Floors
Technical Advice and Support Centre 01744 766666 www.knaufinsulation.co.uk210
Ground floorsAboveslab
Earthwool Thermal Floor Slab Plus
Screed finishPlaceaminimum30mmthickverticalpieceofEarthwoolThermalFloorSlabPlus,tothefulldepthofthescreedaroundtheperimetertominimisethermalbridging.Tapetheperimeterinsulationsecurelyinplacetopreventdislodgementbyfollowingwork.
LaytheEarthwoolThermalFloorSlabPlusandcoverwithavapourcontrol/sliplayerandturnupatthejunctionwiththewalls.Ifthisisarefurbishmentprojectandsecondarydampproofingisrequired,useasuitabledampproofmembranethatwillalsoactasasliplayer.
Laythescreed,eitherreinforcedsand/cementscreed,minimum65mmthick,oraproprietaryscreed,minimum35mmthick.Thesand/cementscreedshouldbereinforcedtoBS8204-1:2003+A1:2009.Itisimportanttocompactthescreedwelltoproduceadurablefloorsurface.
InstallationLayEarthwoolThermalFloorSlabPlusdirectlyoverthewholeoftheconcretefloor,thesurfaceofwhichtobesmoothandflattowithin5mmwhen measured with a two metre straight-edge. ThenatureofEarthwoolThermalFloorSlabPlusenables small irregularities in the concrete slab surface to be accommodated. When installing theinsulationslabsinlayers,staggerthelayoutoftheslabstoavoidcoincidentverticaljointsrunningthroughthetotalinsulationthickness.
Chipboard finishLayavapourcontrollayer(suchas1000gaugepolythene)betweentheinsulationandthechipboarddeckandturnitupatthejunctionwith the walls.
LaythechipboardinastaggeredpatternandgluealljointsusingawaterproofPVAadhesive.Leaveanexpansiongapofatleast10mmor2mmpermetrerunoffloorattheroomperimeter.Atdoorways,roomperimetersandaccesstrapstopipeworkruns,supportthecutedgesofchipboardonpreservativetreatedbattens.Ifindoubtrefertothechipboardmanufacturer’sinstructions.Sealthegapbetweenthefloorfinishandthesliplayerwithaflexiblesealanttominimiseairleakage.
ProductsEarthwool Thermal Floor Slab Plusisarigid,compressionresistantslabofnon-combustiblerockmineralwooldesignedforuseindomesticordomestictypeapplications.
Typical constructionAsolidconcretegroundfloorslabonadampproofmembraneonblindedhardcore.EarthwoolThermalFloorSlabPlusislaidoverthe whole of the concrete floor slab and finished with either a screed or flooring grade chipboard.
• Tolerancefriendly,accommodates slight imperfections in the sub-floor
• Productknitstogetherandcloses joints to ensure thermal performance is achieved avoiding localised cold spots
Earthwool Thermal Floor Slab Plus
• Non-combustible with a Euroclass A1 reaction to fire rating
• BBAcertified
• ZeroOzoneDepletionPotential(ODP)
• ZeroGlobalWarmingPotential(GWP)
Flooringgradechipboard
Vapourcontrollayer
Dampproofmembrane
EarthwoolThermalFloorSlabPlus
Concretefloorslab
Wall insulation takendownatleast150mm belowtopoffloorinsulation
Flexible sealant to maintain air barrier
Gf02 NEW BUILD REFURB
4.1Ground Floors
Technical Advice and Support Centre 01744 766666 www.knaufinsulation.co.uk 211
4.1
Cavitywallinsulation
Minimum150mmoverlapbetween wall and floor insulation to minimise thermal bridging
Flexiblesealbetweenskirtingboard and floor
EarthwoolThermalFloorSlabPlus
Vapourcontrollayerbelowchipboard
TypicalspecificationInsulation below screedEarthwoolThermalFloorSlabPlus......mmthick,tobeclosebuttedandplacedoverthewhole area of the floor. Earthwool Thermal FloorSlabPlus,30mmthick,tobecutandplacedtofulldepthofscreedandfloorinsulationatthefloorperimeter.
Theinsulationtobeoverlaidwith1000gaugepolythene,takenupandovertheperimeterinsulation.A65mmthicksand/cement screed reinforced in accordance with BS8204-1:2003+A1:2009.Alternatively,installaproprietaryliquidscreed(minimumthickness35mm)laidinaccordancewithmanufacturers instructions. Floor finish as specifiedbythedesigner.
(*deleteasappropriate)
Alternatively,consulttheNationalBuildingSpecifications,Standardversionclause/clauses…M10/40orM10/290……………
KnaufInsulationspecificationclausescanbedownloadedfromknaufinsulation.co.uk/nbs
Insulation below chipboardThe whole area of the concrete floor to be covered with Earthwool Thermal Floor Slab Plus,…...mmthick.Allslabstobeclosebutted.
The insulation to be overlaid with avapourcontrollayerof1000gaugepolytheneandcoveredwith18mmtandgflooringgradechipboard.
Alternatively,consulttheNationalBuildingSpecifications,Standardversionclause/clauses…K11/25orK11/225……………
KnaufInsulationspecificationclausescanbedownloadedfromknaufinsulation.co.uk/nbs
PerformanceThermal performanceEarthwoolThermalFloorSlabPlushasathermalconductivityof0.038W/mK.
Fire performanceEarthwoolThermalFloorSlabPlusisclassifiedasEuroclassA1toBSEN13501-1.
Flexible sealant to maintain air barrier
Typicalwall/floorjunction
Table 4 - Earthwool Thermal Floor Slab Plus compressive strength
Thickness(mm) Compressivestrength(kPa)
60,70 60
80,90,100 70
Table 5 - U-valuesforconcretegroundfloors,insulationbelowchipboard
U-values(W/m2K)
Thickness(mm) Ratioofperimeter(m)toarea(m2)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
Earthwool Thermal Floor Slab Plus
160(2x80) 0.10 0.13 0.15 0.16 0.17 0.17 0.18 0.18
150(80+70) 0.10 0.14 0.15 0.17 0.17 0.18 0.19 0.19
140(2x70) 0.10 0.14 0.16 0.17 0.18 0.19 0.20 0.20
130(70+60) 0.11 0.15 0.17 0.18 0.19 0.20 0.21 0.21
120(2x60) 0.11 0.15 0.18 0.19 0.20 0.21 0.22 0.22
100 0.12 0.17 0.20 0.21 0.23 0.24 0.25 0.25
90 0.12 0.18 0.21 0.23 0.24 0.25 0.26 0.27
U Value Competency SchemeCERTIFICATE CS/1001-2
Note: The U-values have been calculated assuming a clay subsoil with a thermal conductivity of 1.50 W/mK.
4.1 Ground Floors
Technical Advice and Support Centre 01744 766666 www.knaufinsulation.co.uk212
• Moistureresistant-longterm exposure to water has negligible impact on thermal performance
• Robust and can tolerate traffic from following trades without damage prior to floor finish being laid
• Highcompressivestrength-protects damp proof membrane from damage
Polyfoam ECO Floorboard
• BBAcertified
• ZeroOzoneDepletionPotential(ODP)
• GlobalWarmingPotential(GWP)<5
Ground floorsAboveslab
Polyfoam ECO Floorboard04/4186
PolyfoamECOFloorboard
PVAadhesive.Leaveanexpansiongapofatleast10mmor2mmpermetrerunoffloorattheroomperimeter.Atdoorwaysoraccesstrapstopipeworkruns,supportthecutedgesofchipboardonpreservativetreatedbattens.Ifindoubtrefertothechipboardmanufacturer’sinstructions. Seal between the wall and floor air barrierwithaflexiblesealant,orsealthespacebetweentheskirtingboardandthefloorusingaflexiblesealanttominimiseairleakage.
PerformanceThermal performanceThethermalconductivitiesofPolyfoamECOFloorboardproductsare:-
StandardandExtra-0.033W/mK
Super-0.034-0.036W/mK
Fire performance
WhenPolyfoamECOFloorboardisinstalledina floor construction it will not contribute to the developmentstagesofafire.
Compression resistancePolyfoamECOFloorboardishighlyresistanttocompressionandwithstandsbothoccasionaland long term static loads. Load bearing construction elements should be designed to adequatelysupportthecombinationofimposedand dead loads without creating excessive deflection.
boardstoavoidcoincidentverticaljointsrunningthroughthetotalinsulationthickness.
Screed finishPlaceaminimum25mmthickverticalpieceofPolyfoamECOFloorboardtothefulldepthofthescreedaroundtheperimetertominimisethermalbridging.Tapetheperimeterinsulationboardssecurelyinplacetopreventdislodgementbyfollowingwork.
CoverthePolyfoamECOFloorboardwithaseparating/sliplayerandturnupatthejunctionwiththewalls.Ifthisisarefurbishmentprojectandsecondarydampproofingisrequired,useasuitabledampproofmembranethatwillalsoactasasliplayer.
Laythescreed,eitherreinforcedsand/cementscreed,minimum65mmthickindwellingsand75mminothertypesofbuildings,oraproprietaryscreed,minimum35mmthick.Thesand/cementscreedshouldbereinforcedinaccordancewithBS8204-1:2003+A1:2009.Itisimportanttocompactthescreedwelltoproduceadurablefloorsurface.
Chipboard finishLayavapourcontrollayer(suchas1000gaugepolythene)betweentheinsulationandthechipboarddeckandturnitupatthejunctionwiththewalls.Laythechipboardinastaggeredpatternandgluealljointsusingawaterproof
ProductsPolyfoam ECO Floorboard is a range of rigid extrudedpolystyreneinsulationboards.
Theyarelightweight,haveexcellentstructuralstrength and long term effectiveness and are availableinthreegrades:
Polyfoam ECO Floorboard Standard – domestic and light commercial loading
Polyfoam ECO Floorboard Extra–commercial,industrial flooring and cold storage
Polyfoam ECO Floorboard Super–veryhighloadcommercial,industrialandcoldstoragefloors.
Typical constructionAsolidconcretegroundfloorslabonadampproofmembraneonblindedhardcore.PolyfoamECOFloorboardslaidoverthewholeof the concrete floor slab and finished with eitherflooringgradechipboardorafloatingscreed,eithersand/cementbased,oraproprietaryflowingscreed.
InstallationLaythePolyfoamECOFloorboarddirectlyoverthe whole of the concrete floor. The surface of the floor should be smooth and flat to within 5mmwhenmeasuredwitha2metrestraight-edge. Irregularities greater than this mustbelevelledout.Thejointsshouldbetightlybutted together. When installing the insulation boardsinlayers,staggerthelayoutofthe
25mmPolyfoamECOFloorboard at screed perimeter
Gf03
Floating screed
Separating/sliplayer
Dampproofmembrane
PolyfoamECOFloorboard
Concretefloorslab
Wall insulation takendownatleast150mm belowtopoffloorinsulation
Flexible sealant to maintain air barrier
NEW BUILD REFURB
4.1Ground Floors
Technical Advice and Support Centre 01744 766666 www.knaufinsulation.co.uk 213
4.1
Cavitywallinsulation
Minimum150mmoverlapbetween wall and floor insulation to minimise thermal bridging
Flexiblesealbetweenskirtingboard and floor
PolyfoamECOFloorboard
Separating/sliplayerbelow floating screed
TypicalspecificationInsulation below screedPolyfoamECOFloorboardStandard*/Extra......mmthick,tobeclosebuttedandplacedoverthewholeareaofthefloor.PolyfoamECOFloorboardStandard*/Extra,25mmthick,tobecutandplacedtofulldepthofscreedatthefloorperimeter.
The insulation to be overlaid with a separatinglayer*/1000gaugepolythene*takenupandovertheperimeterinsulation.A65*/75*mmthicksand/cementscreedreinforcedinaccordancewithBS8204-1:2003+A1:2009.Alternativelyinstallaproprietaryliquidscreed(minimumthickness35mm)laidinaccordancewithmanufacturers instructions. (*deleteasappropriate)
Alternatively,consulttheNationalBuildingSpecifications,Standardversionclause/clauses…M10/40orM10/290……………
KnaufInsulationspecificationclausescanbedownloadedfromknaufinsulation.co.uk/nbs
Insulation below chipboard
The whole area of the concrete floor to be linedwithPolyfoamECOFloorboardStandard*/Extra…...mmthick.Allboardstobe close butted.
Theinsulationtobe(overlaidwithavapourcontrollayerof1000gaugepolytheneand)*coveredwith18mmtandgflooringgradechipboard.(*deleteasappropriate)
Alternatively,consulttheNationalBuildingSpecifications,Standardversionclause/clauses…K11/25orK11/225……………
KnaufInsulationspecificationclausescanbedownloadedfromknaufinsulation.co.uk/nbs
Typicalwall/floorjunctionFlexible sealant to maintain air barrier
Table 6 - U-values for concrete ground floors insulated below slabU-values(W/m2K)
Thickness(mm) Ratioofperimeter(m)toarea(m2)0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
Polyfoam ECO Floorboard Standard and Extra165 (100+65)* 0.09 0.12 0.14 0.15 0.15 0.16 0.16 0.17150 (75+75) 0.10 0.13 0.15 0.16 0.17 0.18 0.18 0.18140 (75+65) 0.10 0.14 0.16 0.17 0.18 0.18 0.19 0.19125 (75+50) 0.11 0.15 0.17 0.18 0.19 0.20 0.20 0.21110 (75+35) 0.11 0.16 0.18 0.19 0.21 0.22 0.22 0.23100 (1x100)** 0.11 0.16 0.19 0.20 0.21 0.22 0.23 0.2490 (65+25) 0.12 0.17 0.20 0.22 0.24 0.25 0.26 0.2675 (1x75) 0.13 0.19 0.23 0.25 0.27 0.28 0.29 0.3065 (1x65) 0.13 0.20 0.24 0.27 0.29 0.30 0.32 0.33
U Value Competency SchemeCERTIFICATE CS/1001-2
Note: The U-values have been calculated assuming a clay subsoil with a thermal conductivity of 1.50 W/mK.
U-values for Polyfoam ECO Floorboard Super available on request - contact Technical Advice and Support Centre
* Polyfoam ECO Floorboard Extra - 2x50+65
** Polyfoam Floorboard ECO Extra - 2x50
Table 7 - Compressive creep results for Polyfoam ECO Floorboards
Product Loadapplied(kPa)
Initialcompression(%)
Furthercompressionafter50years(%)
PolyfoamECOFloorboardStandard 60 2 1.5
PolyfoamECOFloorboardExtra 120 2 1.5
PolyfoamECOFloorboardSuper 175 2 1.5
4.1 Ground Floors
Technical Advice and Support Centre 01744 766666 www.knaufinsulation.co.uk214
Ground floorsSuspendedconcretefloor
Polyfoam ECO Floorboard04/4186
PolyfoamECOFloorboard
preventdislodgementbyfollowingwork.
Laythesliplayer/vclovertheinsulationandturnupatthejunctionwiththewalls.
Laythescreed,eitherreinforcedsand/cementscreed,minimum65mmthickindwellingsand75mminothertypesofbuildings,oraproprietaryscreed,minimum35mmthick.Thesand/cementscreedshouldbereinforcedinaccordancewithBS8204-1:2003+A1:2009.Itisimportanttocompactthescreedwelltoproduceadurablefloorsurface.
Chipboard finish
The insulation should be laid over the whole ofthebeamandblockfloor.
LaythechipboardinastaggeredpatternwithalljointsgluedusingawaterproofPVA adhesive.Leaveanexpansiongapofatleast10mmor2mmpermetrerunoffloorattheroomperimeter.Atdoorwaysoraccesstrapstopipeworkruns,supportthecutedgesofchipboardonpreservativetreatedbattens.Ifindoubt,refertothechipboardmanufacturer’sinstructions. Seal between the wall and floor air barrierwithaflexiblesealant,orsealthespacebetweentheskirtingboardandthefloorusingaflexiblesealanttominimiseairleakage.
InstallationPolyfoamECOFloorboardscanbeusedonabeamandblocksuspendedconcretefloorthatisthesubjectofacurrentBritishBoardofAgrementCertificateandinstalledinaccordancewith,andwithinthelimitationsof,thatcertificate.Thesurfaceofanyfloorshouldbesmoothandflattowithin5mmwhenmeasuredwitha2metrestraight-edge.Providedthesurfaceissmoothandflat,theinsulationmaybelaiddirectlyontotheflooringsystem.Otherwiselayathinlevellingscreed(thismaybethegroutwithbeamandblocksystems)priortolayingtheinsulation.Irregularities greater than those detailed above mustberemoved.Thejointsshouldbetightlybutted together. When installing the insulation inlayers,staggerthelayoutoftheboardstoavoidcoincidentverticaljointsrunningthroughthetotalinsulationthickness.
Whereabeamandblockfloorhasacamberorunevenuppersurface,alevellingscreedisrecommended.
Screeded finishPlaceaminimum25mmthickverticalpieceofPolyfoamECOFloorboardtothefulldepthofthescreed,aroundtheperimetertominimisethermalbridging.Ensuretheseperimeterinsulationboardsaresecurelyheldinplaceto
ProductsPolyfoam ECO Floorboard is a range of rigid extrudedpolystyreneinsulationboards.
Theyarelightweight,haveexcellentstructuralstrength and long term effectiveness and are availableinthreegrades:
Standard – domestic and light commercial loading
Extra–commercial,industrialflooringand cold storage
Super–veryhighloadcommercial,industrialand cold storage floors.
Typical constructionAsuspendedconcretefloorofeitherbeamandblockconstructionorprecastconcreteplanks,overlaidwithPolyfoamECOFloorboardandfinishedwitheitherflooringgradechipboardorafloatingscreed,eithersand/cementbased, oraproprietaryflowingscreed.
Whereascreedisused,astripofPolyfoamECOFloorboardinsulation,minimum25mmthick,shouldbeplacedverticallyattheperimeterofthescreedtominimisethermalbridging.Asliplayer/vclof1000gaugepolythenesheetshouldbeplacedbetweentheinsulation and the screed.
The wall insulation should start a minimum of 150mmbelowthetopofthefloorinsulation.
• Moistureresistant-longterm exposure to water has negligible impact on thermal performance
• Robust and can tolerate traffic from following trades without damage prior to floor finish being laid
• Lightweight,robustproduct,quick and easy to install
Polyfoam ECO Floorboard
• BBAcertified
• ZeroOzoneDepletionPotential(ODP)
• GlobalWarmingPotential(GWP)<5
Screedorchipboard
Sliplayer/vcl
PolyfoamECOFloorboard
Wall insulation takendownatleast150mmbelowtopoffloor insulation
Gf04NEW BUILD REFURB
4.1Ground Floors
Technical Advice and Support Centre 01744 766666 www.knaufinsulation.co.uk 215
4.1
Cavitywallinsulation
Minimum150mmoverlapbetween wall and floor insulation to minimise thermal bridging
Flexiblesealbetweenskirtingboard and floor
PolyfoamECOFloorboard
Vapourcontrollayerbelowchipboard
Levellingscreed(whererequired)
TypicalspecificationInsulation below screedPolyfoamECOFloorboardStandard*/Extra*Super*......mmthick,tobeclosebuttedandplacedoverthewholeareaofthefloor.PolyfoamECOFloorboardStandard*/Extra*Super*......mmthick,tobecutandplacedtofulldepthofscreedatthefloorperimeter.
Theinsulationtobeoverlaidwith1000gaugepolythene,takenupandovertheperimeterinsulation. A65*/75*mmthicksand/cementscreedreinforcedinaccordancewithBS8204-1:2003+A1:2009.Alternativelyinstallaproprietaryliquidscreed(minimumthickness35mm)laidinaccordancewithmanufacturersinstructions.Floorfinishasspecifiedbythedesigner. (*deleteasappropriate)
Alternatively,consulttheNationalBuildingSpecifications,Standardversionclause/clauses…M10/40orM10/290……………
KnaufInsulationspecificationclausescanbedownloadedfromknaufinsulation.co.uk/nbs
Insulation below chipboardThe whole area of the concrete floor to be overlaidwithPolyfoamECOFloorboardStandard*/Extra,*/Super*…...mmthick.Allboards to be close butted.
Theinsulationtobe(overlaidwithavapourcontrollayerof1000gaugepolytheneand)*coveredwith18mmtandgflooringgradechipboard.(*deleteasappropriate)
Alternatively,consulttheNationalBuildingSpecifications,Standardversionclause/clauses…K11/25orK11/225……………
KnaufInsulationspecificationclauses can be downloaded from knaufinsulation.co.uk/nbs
PerformanceThermal performance
ThethermalconductivitiesofPolyfoamECOFloorboardproductsare:-
StandardandExtra-0.033W/mK
Super-0.034-0.036W/mK
Fire performanceWhenPolyfoamECOFloorboardisinstalledina floor construction it will not contribute to the developmentstagesofafire.
Typicalwall/floorjunction
Compression resistance
PolyfoamECOFloorboardsishighlyresistanttocompressionandwithstandsbothoccasionaland long term static loads. Load bearing construction elements should be designed to adequatelysupportthecombinationofimposedand dead loads without creating excessive deflection.
Table 8 - U-values for beam and block ground floors insulated below chipboard deck
U-values(W/m2K)
Thickness(mm) Ratioofperimeter(m)toarea(m2)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
Polyfoam ECO Floorboard Standard and Extra
165(100+65) 0.11 0.13 0.14 0.15 0.15 0.16 0.16 0.16
150(75+75) 0.12 0.15 0.16 0.17 0.17 0.17 0.18 0.18
140(75+65) 0.12 0.15 0.17 0.17 0.18 0.18 0.19 0.19
125(75+50) 0.13 0.16 0.18 0.18 0.19 0.20 0.20 0.20
110(75+35) 0.14 0.17 0.19 0.20 0.21 0.22 0.22 0.22
100 0.14 0.18 0.20 0.21 0.22 0.22 0.23 0.23
90(65+25) 0.15 0.19 0.21 0.23 0.24 0.25 0.25 0.26
75 0.16 0.21 0.24 0.26 0.27 0.28 0.29 0.29
65 0.17 0.22 0.26 0.28 0.29 0.30 0.31 0.32
U Value Competency SchemeCERTIFICATE CS/1001-2
Notes: The U-values have been calculated assuming a clay subsoil with a thermal conductivity of 1.50 W/mK. The thermal conductivity of concrete blocks – 1.13 W/mK. For project specific calculations contact our Technical Advice and Support Centre on 01744 766666.
Table 9 - Compressive creep results for Polyfoam ECO Floorboards
Product Load applied(kPa)
Initial compression
(%)
Further compressionafter50years(%)
PolyfoamECOFloorboard Standard
60 2 1.5
PolyfoamECOFloorboard Extra
120 2 1.5
PolyfoamECOFloorboard Super
175 2 1.5
4.1 Ground Floors
Technical Advice and Support Centre 01744 766666 www.knaufinsulation.co.uk216
Screedorchipboard
Vapourcontrollayer
EarthwoolThermalFloorSlabPlus
Ventilated sub floor
Wall insulation takendownatleast 150mmbelowtopoffloorinsulation
Ground floorsSuspendedconcretefloor
Earthwool Thermal Floor Slab Plus
Chipboard finishThe insulation should be laid over the whole of the concrete floor.
LaythechipboardinastaggeredpatternwithalljointsgluedusingawaterproofPVAadhesive.Leaveanexpansiongapofatleast10mmor2mmpermetrerunoffloorattheroomperimeter.Atdoorways,roomperimetersandaccesstrapstopipework,runssupportthecutedgesofchipboardonpreservativetreatedbattens.Ifindoubt,refertothechipboardmanufacturer’sinstructions.Sealbetween the wall and floor air barrier with a flexiblesealant,andsealthespacebetweentheskirtingboardandthefloorusingaflexiblesealanttominimiseairleakage.
Performance
Thermal performanceEarthwoolThermalFloorSlabPlushasathermalconductivityof0.038W/mK.
Fire performanceEarthwoolThermalFloorSlabPlusisclassifiedasEuroclassA1toBSEN13501-1.
Wheninstallingtheinsulationinlayers,staggerthelayoutoftheslabstoavoidcoincidentverticaljointsrunningthroughthetotalinsulationthickness.
Screed finishPlaceaminimum30mmthickverticalpieceofEarthwoolThermalFloorSlabPlustothefulldepthofthescreed,aroundtheperimetertominimisethermalbridging.Ensuretheperimeterinsulationissecurelyheldinplacetopreventdislodgementbyfollowingwork.
Laythevapourcontrollayer/sliplayerovertheinsulationandturnupatthejunctionwiththewalls.
Laythescreed,eitherreinforcedsand/cementscreed,minimum65mmthickindwellingsand75mminothertypesofbuildings,oraproprietaryscreed,minimum35mmthick.Thesand/cementscreedshouldbereinforcedinaccordancewithBS8204-1:2003+A1:2009.Itisimportanttocompactthescreedwelltoproduceadurablefloorsurface.
ProductsEarthwool Thermal Floor Slab Plusisarigid,compressionresistantslabofnon-combustiblerockmineralwooldesignedforuseindomesticordomestictypeapplications.
Typical constructionAsuspendedconcretefloorofeitherbeamandblockconstructionorprecastconcreteplanks,overlaidwithEarthwoolThermalFloorSlabPlusand finished with either flooring grade chipboardorafloatingscreed,eithersand/cementbased,oraproprietaryflowingscreed.
Avapourcontrollayer/sliplayerof1000gaugepolythenesheetshouldbeplacedbetween the insulation and the screed.
The wall insulation should start a minimum of 150mmbelowthetopofthefloorinsulation.
InstallationEarthwoolThermalFloorSlabPlusmaybelaiddirectlyontotheflooringsystem.Thesurfaceofanyfloorshouldbesmoothandflattowithin5mmwhenmeasuredwitha2metrestraight-edge. Irregularities greater than those detailed above must be removed.
Thejointsshouldbetightlybuttedtogether.
• Tolerancefriendly,accommodates slight imperfections in sub-floor
• Productknitstogetherandcloses joints to ensure thermal performance is achieved and avoid localised cold spots
Earthwool Thermal Floor Slab Plus
• Non-combustiblewithaEuroclassA1 reaction to fire rating
• BBAcertified
• ZeroOzoneDepletionPotential(ODP)
• ZeroGlobalWarmingPotential(GWP)
Gf05NEW BUILD REFURB
4.1Ground Floors
Technical Advice and Support Centre 01744 766666 www.knaufinsulation.co.uk 217
4.1
Cavitywallinsulation
Minimum150mmoverlapbetween wall and floor insulation to minimise thermal bridging
Flexiblesealbetweenskirtingboard and floor
Earthwool Thermal Floor SlabPlus
Vapourcontrol/sliplayerbelowscreedorchipboard
Levellingscreedwhererequired
TypicalspecificationInsulation below screedEarthwoolThermalFloorSlabPlus......mmthick,tobeclosebuttedandplacedoverthewhole area of the floor. Earthwool Thermal FloorSlabPlus,30mmthick,tobecutandplacedtofulldepthofscreedatthefloorperimeter.
Theinsulationtobeoverlaidwith1000gaugepolythene,takenupandovertheperimeterinsulation.A65*/75*mmthicksand/cementscreedreinforcedinaccordancewithBS8204-1:2003+A1:2009.Alternativelyinstallaproprietaryliquidscreed(minimumthickness35mm)laidin accordance with manufacturers instructions.Floorfinishasspecifiedbythedesigner.
(*deleteasappropriate)
Alternatively,consulttheNationalBuildingSpecifications,Standardversionclause/clauses…M10/40orM10/290……………
KnaufInsulationspecificationclausescanbedownloadedfromknaufinsulation.co.uk/nbs
Insulation below chipboardThe whole area of the concrete floor to be overlaid with Earthwool Thermal Floor Slab Plus,…...mmthick.Allslabstobeclosebutted.
Theinsulationtobeoverlaidwithavapourcontrollayerof1000gaugepolytheneandcoveredwith18mmtandgflooringgradechipboard.
Alternatively,consulttheNationalBuildingSpecifications,Standardversionclause/clauses…K11/25orK11/225……………
KnaufInsulationspecificationclausescanbedownloadedfromknaufinsulation.co.uk/nbs
Typicalwall/floorjunction
Table 10 - Earthwool Thermal Floor Slab Plus compressive strength
Thickness(mm) Compressivestrength(kPa)
60,70 60
80,90,100 70
Table 11 - U-values for beam and block ground floors insulated below chipboard deck
U-values(W/m2K)
Thickness(mm) Ratioofperimeter(m)toarea(m2)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
Earthwool Thermal Floor Slab Plus
160(2x80) 0.12 0.14 0.15 0.16 0.16 0.17 0.17 0.17
150(80+70) 0.12 0.15 0.16 0.17 0.17 0.17 0.18 0.18
140(2x70) 0.12 0.15 0.16 0.17 0.18 0.18 0.19 0.19
130(70+60) 0.13 0.16 0.17 0.18 0.19 0.19 0.20 0.20
120(2x60) 0.13 0.16 0.18 0.19 0.20 0.20 0.21 0.21
100 0.14 0.18 0.20 0.21 0.22 0.23 0.23 0.24
90 0.15 0.19 0.21 0.22 0.23 0.24 0.25 0.25
80 0.15 0.20 0.22 0.24 0.25 0.26 0.26 0.27
U Value Competency SchemeCERTIFICATE CS/1001-2
Note: The U-values have been calculated assuming a 0.16 W/mK aircrete block between concrete beams.
4.1 Ground Floors
Technical Advice and Support Centre 01744 766666 www.knaufinsulation.co.uk218
Flexible seal
EarthwoolLoftRoll44/40orEarthwoolFlexibleSlab
Supportnetting
Ventilated floor void
Wall insulation takendownatleast 200mmbelowtopoffloorinsulation
Chipboarddeck
Ground floorsSuspendedtimberfloor
Earthwool Loft Roll or Earthwool Flexible Slab
Whenfixingtheskirtingboard,applyaself-adhesivefoamstriptotheundersideoftheskirtingandtwobeadsofsealanttothebacksurface.Applypressuretoensurethefoamstripiscompressedimmediatelybeforefixingtheskirtinginplace.
PerformanceThermal performanceEarthwoolLoftRoll40hasathermal conductivityof0.040W/mK.
EarthwoolLoftRoll44hasathermal conductivityof0.044W/mK.
Earthwool Flexible Slab has a thermal conductivityof0.037W/mK,except140mmthicknesswhichhasathermalconductivityof0.035W/mK.
Fire performanceEarthwoolLoftRoll44/40andEarthwoolFlexibleSlabareclassifiedasEuroclassA1toBSEN13501-1.
InstallationIftheinsulationisthefulldepthofthefloorjoists,staplethesupportnettingtotheundersideofthefirstjoistandunrollthenetting,staplingtotheunderside(orside)ofeachjoistasthenetting is unrolled.
Wherethejoistisdeeperthanthefloorinsulation,markthedepthoftheinsulationonthesideofthejoists.Staplethesupportnettingalongthislineandpulltauttotheadjacentjoistandstapleagain.Pullthenettingoverthetopofthejoistandstapletothedepthofthefloorinsulation.Repeattheprocessuntilthereisnettingsupporttothewholefloor.
InstallEarthwoolLoftRoll44/40ensuringtherearenoairgapsbetweentheinsulationandtheundersideofthefloordeck.
Fixthechipboardfloordeckintheusualway,usingwaterproofPVAglueatthejoints,andallowaminimum10mmgapattheroom perimeter.Ifindoubtrefertothechipboardmanufacturers instructions.
ProductsEarthwool Loft Rolls 44 / 40 are made from glass mineral wool and formed into rolls which arelightweight,flexible,resilientand non-combustible.
Earthwool Flexible Slabisamulti-use,flexible,rockmineralwoolslabdesignedforfriction-fittinginarangeofacoustic,thermalandfireresistantapplications.
Typical constructionAsuspendedandventilatedtimbergroundfloor.Theinsulationisplacedbetweenthejoistsandsupportedonpolypropylenenetting.
Thenettingshouldbepositionedtosupporttheinsulationsothatthereisnogapbetweentheinsulationandtheundersideofthefloordeck.
Thefloorjoistsrunningparallelwithmasonrywallsshouldbespacedatleast35mmawayfromthewalltoallowinsulationtobeplacednext to the wall.
The wall insulation should start a minimum of 200mmbelowthetopofthefloorinsulationtominimise thermal bridging.
• Frictionfittingbetweentimber joistsclosesjoints,preventingair movement and infiltration
• Flexibleproductswhich accommodates movements in floor ensuring all joints remain closed
Earthwool Loft Roll and Earthwool Flexible Slab
• Non-combustiblewithaEuroclass A1 reaction to fire rating
• A+GenericBREGreenGuideRating
• ZeroOzoneDepletionPotential(ODP)
• ZeroGlobalWarmingPotential(GWP)
Gf06 Gf08NEW BUILD REFURB
4.1Ground Floors
Technical Advice and Support Centre 01744 766666 www.knaufinsulation.co.uk 219
4.1
Table 12 - U-values of suspended timber ground floors insulated between joists
Thickness (mm)
Productcombination
Product U-values(W/m2K)
Ratioofperimeter(m)toarea(m2)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
300- EarthwoolLoftRoll40 - - - - - - - -
150+150 EarthwoolLoftRoll44 0.10 0.12 0.13 0.13 0.14 0.14 0.14 0.14
250 150+100EarthwoolLoftRoll40 0.10 0.13 0.14 0.14 0.15 0.15 0.15 0.15
EarthwoolLoftRoll44 0.11 0.13 0.14 0.15 0.16 0.16 0.16 0.16
200 1x200EarthwoolLoftRoll40 0.12 0.15 0.16 0.17 0.17 0.18 0.18 0.18
EarthwoolLoftRoll44 0.12 0.15 0.16 0.17 0.17 0.18 0.18 0.18
150 1x150EarthwoolLoftRoll40 0.13 0.17 0.19 0.20 0.21 0.22 0.22 0.23
EarthwoolLoftRoll44 0.13 0.17 0.19 0.20 0.21 0.22 0.22 0.23
100 1x100EarthwoolLoftRoll40 0.16 0.21 0.24 0.26 0.27 0.28 0.29 0.30
EarthwoolLoftRoll44 0.16 0.21 0.24 0.26 0.27 0.28 0.29 0.30
250 100+90+60 Earthwool Flexible Slab 0.10 0.12 0.13 0.14 0.14 0.14 0.14 0.15
200 100+100 Earthwool Flexible Slab 0.11 0.14 0.15 0.16 0.17 0.17 0.17 0.18
140 Earthwool Flexible Slab 0.13 0.17 0.19 0.20 0.21 0.21 0.22 0.22
100 Earthwool Flexible Slab 0.15 0.20 0.23 0.25 0.26 0.27 0.28 0.29
U Value Competency SchemeCERTIFICATE CS/1001-2
Note: The U-values have been calculated assuming that the timber joists are 48mm wide at 600mm centres.
Cavitywallinsulation
Flexiblesealbetweenskirtingboard and floor
EarthwoolLoftRoll44/40orEarthwoolFlexibleSlabfullyfillingthespacebetweenthefloorjoists
Nettingsupportforinsulation
35mmgapfilledwithEarthwoolLoftRoll44/40orEarthwool Flexible Slab
TypicalspecificationPolypropylenenettingtobe(drapedoverandbetweenthejoistsandstapledtothesidesofeachjoist*/stapledtotheundersideofthejoists*).(*deleteasappropriate)
EarthwoolLoftRoll44*/40*/EarthwoolFlexibleSlab*of......mmthicknessandofwidthtosuitjoistspacings,supportedonthenetting and to be in contact with the undersideofthefloordeck.EarthwoolLoftRoll44*/40*/EarthwoolFlexibleSlab*tobecutandplacedtofullyfillinthegapbetweenthelastjoistandtheperimeterwall.Flooringgradetandgchipboardtobefixedtothefloorjoists,allasspecifiedbythedesigner.
Alternatively,consulttheNationalBuildingSpecifications,Standardversionclause/clauses…P10/250……………
KnaufInsulationspecificationclausescanbedownloadedfromknaufinsulation.co.uk/nbs
Minimum200mmoverlapbetween wall and floor insulation to minimise thermal bridging
Typicalwall/floorjunction
Gf06
Gf08
4.1 Ground Floors
Technical Advice and Support Centre 01744 766666 www.knaufinsulation.co.uk220
Ground floorsUnderfloor heating
Polyfoam ECO Floorboard Standard04/4186
PolyfoamECOFloorboard
PerformanceThermal performanceThethermalconductivityofPolyfoamECOFloorboardStandardis0.033W/mK.
Fire performanceWhenPolyfoamECOFloorboardStandardisinstalled below a screed it will not contribute to thedevelopmentstagesofafire.
Compression resistancePolyfoamECOFloorboardStandardishighlyresistanttocompressionandwithstandsbothoccasional and long term static loads. Load bearing construction elements should be designedtoadequatelysupportthecombinationofimposedanddeadloadswithout creating excessive deflection.
InstallationTheconcreteslabiscastinthenormalmanner,withthedampproofmembranebelowthe slab. Starting from the corner furthest from the manifoldoutletconnectionlaythePolyfoamECOFloorboardStandard,ensuringtheentirefloor area is covered.
Startingfromthemanifold,laythesinglerun ofpipe,fixingitfirmlyintotheinsulationboards.Ensurethepipesandpipereturnsareinstalledattherequiredcentresandarereturnedtothemanifoldsystem.Testthesystembefore finishing the floor.
Laytheliquidortraditionalcement/sandscreedtothespecifieddepth.Alternatively,theunderfloorheatingsystemisinstalledwithintheconcretefloorslabwhichislaidontopofPolyfoamECOStandardFloorboard.Thejointsshouldbetightlybuttedtogether.Wheninstallingtheinsulationinlayers,staggerthelayoutoftheboardstoavoidcoincidentverticaljointsrunningthroughthetotalinsulationthickness.
ProductsPolyfoam ECO Floorboard Standard is a rigid extrudedpolystyreneinsulationboard.
Itislightweight,andhasexcellentstructuralstrength and long term effectiveness.
Polyfoam ECO Floorboard Standard is ideal for usewithanunderfloorheatingsystem,usingeitherclips,staplesorarailsystem,makingitanidealsolutionforuseinawidevarietyoffloors.
Typical constructionAsolidconcretegroundfloorslabonadampproofmembraneonblindedhardcore.PolyfoamECOFloorboardStandardislaidoverthewholeoftheconcretefloorslab,theheatingpipes,usingclips,staplesorrailsareinstalledandcoveredwitheitheraliquidortraditional screed finish.
• Moisture resistant - long term exposure to water has negligible impact on thermal performance
• Robust and can tolerate traffic from following trades without damage prior to floor finish being laid
Polyfoam ECO Floorboard
• BBA certified
• ZeroOzoneDepletionPotential(ODP)
• GlobalWarmingPotential(GWP)<5
Gf07
Concretefloorslab
Dampproofmembrane
Sand blinding
Wall insulation takendownatleast150mm belowtopoffloorinsulation
PolyfoamECOFloorboardStandard
Table 13 - Compressive creep results for Polyfoam ECO Floorboard Standard
Loadapplied(kPa)
Initial compression
(%)
Further compressionafter50years(%)
PolyfoamECOFloorboard Standard
2 1.5
NEW BUILD REFURB
4.1Ground Floors
Technical Advice and Support Centre 01744 766666 www.knaufinsulation.co.uk 221
4.1
Cavitywallinsulation
Minimum150mmoverlapbetween wall and floor insulation to minimise thermal bridging
Flexible seal between skirtingboardandfloor
PolyfoamECOFloorboardStandard
Floatingscreed,withembeddedheatingpipes
Concretefloorslab
25mmPolyfoamECOFloorboardStandard Floorboard Standard
TypicalspecificationPolyfoamECOFloorboardStandard......mmthick,tobecloselybuttedandplacedoverthewholeareaofthefloor.PolyfoamECOFloorboardStandard,atleast25mmthick,tobecutandplacedtofulldepthofscreedatthefloorperimeter.
Asinglerunofpipetobefixedfirmlyintotheinsulation boards and returned to the manifoldsystem.Thepipestobetestedbefore the screed is laid.
A65*/75*mmthicksand/cementscreedreinforcedinaccordancewithBS8204-1:2003+A1:2009.Alternativelyinstallaproprietaryliquidscreed(minimumthickness35mm)laidinaccordancewithmanufacturers instructions. Floor finish as specifiedbythedesigner.
(*deleteasappropriate)
Alternatively,consulttheNationalBuildingSpecifications,Standardversionclause/clauses…M10/40orM10/290……………
KnaufInsulationspecificationclausescanbedownloadedfromknaufinsulation.co.uk/nbs
Typicalwall/floorjunction
Continuousribbonofplasterboardadhesive
Table 14 - U-values for concrete ground floors insulated below slabU-values(W/m2K)
Thickness(mm) Ratioofperimeter(m)toarea(m2)0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
Polyfoam ECO Floorboard Standard and Extra165(100+65)* 0.09 0.12 0.14 0.15 0.15 0.16 0.16 0.17
150(75+75) 0.10 0.13 0.15 0.16 0.17 0.18 0.18 0.18
140(75+65) 0.10 0.14 0.16 0.17 0.18 0.18 0.19 0.19
125(75+50) 0.11 0.15 0.17 0.18 0.19 0.20 0.20 0.21
110(75+35) 0.11 0.16 0.18 0.19 0.21 0.22 0.22 0.23
100(1x100)** 0.11 0.16 0.19 0.20 0.21 0.22 0.23 0.24
90(65+25) 0.12 0.17 0.20 0.22 0.24 0.25 0.26 0.26
75(1x75) 0.13 0.19 0.23 0.25 0.27 0.28 0.29 0.30
65(1x65) 0.13 0.20 0.24 0.27 0.29 0.30 0.32 0.33
U Value Competency SchemeCERTIFICATE CS/1001-2
Note: The U-values have been calculated assuming a clay subsoil with a thermal conductivity of 1.50 W/mK. U-values for Polyfoam ECO Floorboard Super available on request - contact Technical Advice and Support Centre on 01744 766666 * Polyfoam ECO Floorboard Extra - 2x50+65 ** Polyfoam Floorboard ECO Extra - 2x50
Table 15 - U-values for beam and block ground floors insulated below chipboard deck
U-values(W/m2K)
Thickness(mm) Ratioofperimeter(m)toarea(m2)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
Polyfoam ECO Floorboard Standard and Extra
165(100+65) 0.11 0.13 0.14 0.15 0.15 0.16 0.16 0.16150(75+75) 0.12 0.15 0.16 0.17 0.17 0.17 0.18 0.18
140(75+65) 0.12 0.15 0.17 0.17 0.18 0.18 0.19 0.19125(75+50) 0.13 0.16 0.18 0.18 0.19 0.20 0.20 0.20
110(75+35) 0.14 0.17 0.19 0.20 0.21 0.22 0.22 0.22100 0.14 0.18 0.20 0.21 0.22 0.22 0.23 0.23
90(65+25) 0.15 0.19 0.21 0.23 0.24 0.25 0.25 0.2675 0.16 0.21 0.24 0.26 0.27 0.28 0.29 0.2965 0.17 0.22 0.26 0.28 0.29 0.30 0.31 0.32
U Value Competency SchemeCERTIFICATE CS/1001-2
Notes: The U-values have been calculated assuming a clay subsoil with a thermal conductivity of 1.50 W/mK. The thermal conductivity of concrete blocks – 1.13 W/mK. For project specific calculations contact our Technical Advice and Support Centre on 01744 766666.
Knauf Insulation Ltd Customer Service (Sales) Technical Advice and Support Centre LiteraturePO Box 10 Tel: 0844 800 0135 Tel: 01744 766 666 Tel: 08700 668 660Stafford Road Fax: 01744 612007 Fax: 01744 766 667 Fax: 0870 400 5797St Helens Email: [email protected] Email: [email protected] Email: [email protected] www.knaufinsulation.co.ukWA10 3NS