SUBSTATIONSUBSTATIONFITTINGSFITTINGS
40
SECTIONSECTION -- 22
CatalogueNo.
Split BoltClamp Size
MaximumConductor
mm² K W T L
CL2 B22 16 M10 19 3 59
CL4 B24 35 M12 25 3 74
CL6 B26 95 M12 32 3 83
CL8 B28 185 M12 51 3 100
Dimensions
Type CT cable terminals provide a compact connection between cable andswitchgear stem. Cable connection is soldered and pressure ring providesmechanical connection to switchgear stem. Terminal body is made of silverplated copper. Pressure ring is cadmium plated high carbon steel.
Cable Size Catalogue No.
Metric Imperial SwitchgearStem
Dia.12mm.
Switchgearstem
Dia.14mm.mm² Strand Inch² Strand
150 Compacted to dia.14.3 CT12-150 CT14-150
185 CT12-185 CT14-185
240 61/2.25 0.4 61/093 CT12-240 CT14-240
300 61/2.52 0.5 61/103 CT12-300 CT14-300
Compacted to dia 15.9
CABLE TERMINAL - TYPE CT
CLAMP LUG TYPE - CL
www.powerline-equipment.com.au41
Made from tin plated copper and fitted with tin plated split bolt clamp.
COPPER SUBSTATION FITTINGS
Designed for tube to flat connections. Castings are of high Copper content alloy. TypeCBT Terminal Lugs are machined on the underside and fitted with stainless steel boltsand nuts.
Cat. NoTube OD
Fig.No.
Dimensions in Millimetres
Met.(mm) Imp.(inch) A B C D E L K T
CBT25 25.4 1 2 41 38 16 53 67 137 M12 10
CBT25A 25.4 1 1 38 - 19 51 59 108 M12 6
CBT25/S 25.4 1 2 43 50 25 64 70 170 M12 12
CBT25-T4 25.4 1 2 50 50 25 64 70 170 M12 12
CBT30/S 30.2 1 2 43 50 25 64 70 170 M12 12
CBT30-T4 30.2 1 2 50 50 25 64 70 170 M12 12
CBT32 31.75 1 2 48 38 16 51 59 127 M12 10
CBT32/S 31.75 1 2 43 50 25 64 70 170 M12 12
CBT32-T4 31.75 1 2 50 50 25 64 70 170 M12 12
CBT33 33.4 1 5/16 3 70 38 16 51 76 130 M12 10
CBT38-T4 38.1 1 2 50 50 25 64 76 170 M12 12
CBT46 46.0 1 13/16 3 70 38 16 64 89 146 M12 11
CBT51 50.8 2 3 100 50 16 70 95 152 M12 11
CBT51-T4 50.8 2 2 50 50 25 64 90 170 M12 12
CBT51-5X 50.8 2 3 100 50 25 64 90 180 M12 11
TERMINAL LUG -COPPER TUBE TO SWITCHGEARTYPE CBT
www.powerline-equipment.com.au42
COPPER SUBSTATION FITTINGS
Fig.No
Tube ODmm (inch) Cat. No. A
mmB
mmC
mmD
mmE
mmStandardBolt Size
1 13 (1/2”) CTF13-1 32 25 54 - 29 M10 X 50
1 16 (5/8) CTF16-1 32 25 54 - 29 M10X50
2 16 (5/8) CTF16 32 48 54 22 29 M10 X 55
2 19 (3/4”) CTF19 35 48 57 22 32 M10 X 60
1 25 (1”) CTF25-1 44 29 60 - 38 M10 X 65
2 25 (1”) CTF25-51 41 76 76 51 51 -
2 25 (1”) CTF25 41 54 64 29 38 M10 X 65
2 29 (11/8”) CTF29 44 54 64 29 38 M10 X 75
2 30 (1 3/16”) CTF30 46 54 70 29 44 M10 X 75
2 32 (11/4”) CTF32 46 54 70 29 44 M10 X 75
2 38 (11/2”) CTF38 54 54 76 29 51 M10 X 80
2 40 (37/64”) CTF40 56 55 76 29 51 M10 X 80
2 48 ( 1 29/32”) CTF48 64 57 83 29 57 M10 X 90
2 51 (2”) CTF51 67 54 89 29 64 M10 X 100
2 76 (3”) CTF76 95 54 114 29 89 M10 X 120
2 89 (31/2”) CTF89 116 60 130 29 102 M10 x 140
COPPER TUBULAR BUSBAR TO FLAT CONNECTORTYPE CTF
Type CTF tube connectors provide an economical means of terminating tubular busbar.They also combine with flexible braid connections to make expansion joints between tubesin line or at right angles. Unless ordered otherwise CTF tube connectors will be suppliedwith standard length stainless steel bolts and nuts as shown in table.
www.powerline-equipment.com.au43
COPPER SUBSTATION FITTINGS
Type CTP connectors are designed to connect copper tubular busbar direct to equipmentpalms drilled in accordance with AS2395 type 5, namely four holes 14 mm diameter at50mm centres. Connector components are high-copper alloy. Hardware is stainless steel.
Two connectors are required per four bolt connection.
COPPER TUBE TO TERMINAL PALM CONNECTORTYPE CTP
www.powerline-equipment.com.au44
Cat. No. O.D. Tube A Bolt Detail
CTP25 25 (1”) 53 M12 X 85
CTP30 30 (1 3/16”) 58 M12 X 90
CTP38 38 (1 1/2”) 66 M12 X 100
COPPER SUBSTATION FITTINGS
Cat.No.
TubeOD
(mm)
Dimensions in Millimetres
A B C D L M T K
CCS19 19.1 16 51 51 83 130 83 10 M12
CCS22 22 16 51 51 83 141 83 10 M12
CCS25 25.4 16 51 51 83 171 83 13 M12
CCS25B 25.4 19 35 38 83 141 83 13 M10
CCS28 28.6 25 50 50 102 171 108 13 M12
CCS30 30 25 51 51 102 171 108 13 M12
CCS30/130 30 35 60 60 130 215 133 13 M12CCS30/140 30 35 60 60 130 215 133 13 M12
CCS32 31.8 25 51 51 102 171 108 13 M12
CCS35 35 25 51 51 102 171 105 13 M12
CCS38 38.1 25 51 51 102 171 105 13 M12
CCS40 40 25 51 51 102 171 105 13 M12
CCS40/130 40 35 60 60 130 215 133 13 M12
CCS40/140 40 35 60 60 140 225 146 19 M16
CCS40/150 40 35 60 60 150 215 133 13 M12
CCS44 44 25 50 50 100 171 105 13 M12
CCS44/140 44 35 60 60 140 225 146 19 M16
CCS48 48 25 51 51 102 178 105 13 M12
CCS51 51 25 51 51 102 178 105 13 M12
CCS44/115 44 30 60 60 115 225 146 19 M16
Type CCS terminal lugs are designed to connect cylindrical terminals or tubular busbarto palm terminals of switchgear. Hardware is stainless steel.Castings are copper alloy.
Note. When required Electro-Tin Plated add “P” to Cat. No. For example CCS30-P.
TERMINAL LUG BUSBAR TO PALM - TYPE CCS
CCS30 - P (Electro tin plated) shown
www.powerline-equipment.com.au45
COPPER SUBSTATION FITTINGS
Cat.No.
TubeOD
(mm)
Dimension in Millimetres
C E H L TK boltsize
D
CLS19 19.1 79 35 44 133 10 M12 50
CLS22 22.2 79 35 44 133 10 M12 50
CLS25 25.4 76 41 64 143 10 M12 50
CLS25C 25.4 102 57 64 171 13 M12 50
CLS30 30 102 67 76 184 19 M12 50
CLS30C 30 102 57 64 171 13 M12 50
CLS32 31.8 83 43 64 146 13 M12 50
CLS38 38.1 102 57 60 184 13 M12 50
CLS44 44.2 140 80 80 243 20 M16 50
CLS51C 51 102 60 75 200 13 M12 50
CLS51C/140
CLS25C/140
CLS30/140
CLS30/150
CLS32/140
CLS40
CLS40/140
CLS48
RIGHT ANGLE TERMINAL LUG -TYPE CLS
Designed for connecting cylindrical terminals or tubular busbar at right angles toswitchgear. Standard palm drilling conforms to AS 2395 Palm Terminal No 5.Castings are high copper content alloy. Hardware is stainless steel.
Type CLS Right Angle Terminal Lugs can also be supplied Electro- Tin plated.For this variation add suffix “P” to Cat.No. For example CLS25- P.Other sizes available upon request.
www.powerline-equipment.com.au 46
COPPER SUBSTATION FITTINGS
The type CTT tee connector provides a heavyduty connection for copper tubular busbar.The three piece design allows easy assembly.Castings are in high copper content alloy.Hardware is stainless steel.
Cat. No.M T B L
CTT2519 25.4 19 55 120
CTT2525 25.4 25.4 60 130
CTT3030 30 30 70 135
CTT3230 31.7 30 70 135
CTT3232 31.7 31.7 70 135
CTT3825 38.1 25.4 70 140
CTT3838 38.1 38.1 80 150
CTT8989 89 89 135 268
CTT100100 100 100 150 295
Dimensions
COPPER TUBULAR BUSBAR TEE CONNECTOR - TYPE CTT
COPPER SUBSTATION FITTINGS
www.powerline-equipment.com.au47
A-frame assemblies allow self-supporting busbar structures to be made from theconductors themselves resulting in a saving of supporting steelwork and insulators.Castings are in high copper content alloy .All components are supplied with stainlesssteel bolts, nuts and spring washers. Catalogue Number includes one complete setof A - Frame connectors but does not include the vertical connecting tubes .
A - FRAME CONNECTORSTYPE - CAF
‘D’ Vertical connecting tubes
Cat. No. of completeA - Frame set
Dimensions in millimeters
A B C-dia. D-dia. E-dia.
CAF 2525 610 273 25 25 25
CAF 3825 610 273 38 25 25
CAF 8944 1800 580 89 44 44
48www.powerline-equipment.com.au
COPPER SUBSTATION FITTINGS
Type CST connectors are designed forjoining tubular copper busbars end to end.Connector sections are cast in high coppercontent alloy. Hardware is stainless steel.
Cat. No. Tube ODD
L
CST19 19.1 80
CST25 25.4 112
CST30 30.0 125
CST32 31.8 125
CST38 38.1 140
CST51 50.8 179
STRAIGHT CONNECTOR COPPER TUBE - TYPE CST
REDUCER - COPPER BUSBAR OR STUD - TYPE CRS
Type CRS reducers are cast in high copper content alloy and machined to suit thebusbar diameter. Supplied complete with stainless steel bolts and nuts.
CATNo
O.D. TUBE
RUN TAP A B L
CRS3829 38 29 60 54 114
CRS383O 38 30 60 54 114
CRS3832 38 32 60 54 114
CRS4O25 40 25.4 60 57 120
CRS4030 40 30 60 57 120
Dimensions in mm
Bolt Size
M10
M10
M10
M12
M12
CRS3825 38 25.4 60 57 120 M12
www.powerline-equipment.com.au
Bolt size
49
COPPER SUBSTATION FITTINGS
BUSBAR SUPPORT CLAMP - TYPE CBS
Type CBS busbar support clamps are used to secure copper tubular busbar topost insulators with either 51, 76 or 127 mm PCD. They are cast in high strengthcopper alloy and supplied with stainless steel bolts and washers.Clamps are converted from clamping to sliding type simply by reversing the cap.
CatalogueNo.
TubeOD
Dimensions
B C K R S
CBS1951 19.05 50.8 33 M10 x 65 48 52 .74
CBS1976 19.05 76.2 38 M12 x 70 47 52 1.34
CBS2551 25.4 50.8 33 M10 x 65 46 48 .64
CBS2576 25.4 76.2 38 M12 x 70 48 52 1.28
CBS3251 31.7 50.8 33 M10 x 80 58 60 .74
CBS3276 31.7 76.2 38 M12 x 70 46 48 1.14
CBS3851 38.1 50.8 33 M10 x 80 60 62 .78
CBS3876 38.1 76.2 38 M12 x 80 50 52 1.56
CBS5176 50.8 76.2 38 M12 x 90 71 73 1.67
CBS6076 60.0 76.2 38 M12 x 100 80 82 1.80
Mass (kg)
ADAPTOR BRACKETTYPE BCA-1
Type BCA-1 Adaptor Brackets are cast in high strength copperalloy They convert the type CBS busbar support clamps 51 and76 mm PCD to 127 mm PCD.
The slots assist with accurate busbar to insulator alignment.
www.powerline-equipment.com.au
For aluminium equivalent refer to section-Aluminium Substation Fittings.
50
COPPER SUBSTATION FITTINGS
The type CX connector makes an effective 90 degree connection between coppertubular busbar and copper cables. Castings are copper alloy, machined to matchthe tube diameter. Hardware is stainless steel.
Cat. No. Tube OD Cable Range Dimensions
mm² OD mm L W
CX1919 19.0
25 to 215
130 54
CX2519 25.4 138 54
CX3019 30.0 138 54
CX3219 32.0 138 54
CX3819 38.0 150 54
CX7619 76.0 155 60
6.75 to 19.25
CX3826 38.0 170 64
CX2526 25.4 145 54
CX5119 51 165 64
K
M10
M10
M10
M10
M10
M1O
M10
M10
M10
TEE CONNECTOR - TYPE CXCOPPER TUBE TO CABLE
K bolt size
www.powerline-equipment.com.au
For Aluminium equivalent refer to section “Aluminium Substation Fittings”
51
COPPER SUBSTATION FITTINGS
The type CE end connector makes an effective end connection between copperstems or tubular busbar and copper cable. Castings are copper alloy, machinedto match the busbar. Hardware is stainless steel.
Cat. No. Tube OD Cable Range Dimensions (mm) Mass(kg)
mm2 OD mm L W K
CE1919 19.0
25 to 215 6.75 to 19.25
122 58 M10 1.29
CE2519 25.4 130 65 M10 1.34
CE2919 28.5 125 70 M10 1.50
CE3019 30.0 125 70 M10 1.50
CE3219 31.7 125 70 M10 1.51
CE3519 35.0 130 78 M10 1.82
CE3819 38.1 130 78 M10 1.81
CE4019 40.0 130 78 M10 1.76
CE3826 38.1150 to 400
150 67 M10 2.42
CE7626 76.2 140 56 M10 3.2915.75 to 25.6
CE5119 50.8 135 80 M10 2.24
For Aluminium equivalent refer to section “Aluminium Substation Fittings”
END CONNECTOR - TYPE CECOPPER TUBE TO CABLE
www.powerline-equipment.com.au
K bolt size
52
COPPER SUBSTATION FITTINGS
TERMINAL LUG -TYPE CTL, CONDUCTOR TO PALMTWIN U- BOLT CLAMP BAR STYLE
Cat.No.
Conductor Range No ofpalmHoles
Dimensions in mm
mm² OD mm A B C K T L
CTL19-1A 25to
215
6.75to
19.25
2 40 15 29 10 8 150
CTL19-2C 1 40 15 - 12 8 150
CTL19-3A 2 40 15 38 12 8 150
CTL19-3C 2 40 15 50 12 8 150
CTL19-T4 2 50 25 50 12 12 183
CTL19-4A 4 80 15 38 12 8 150
CTL19-5X 4 100 25 50 12 14 170
CTL34-T4 25.65to
32.76
2 50 25 50 12 13 208
CTL34 -T4-38 2 50 19 38 12 13 208
400to
630
CTL19-5C CTL19-3C -T [Tin Plated]
Type CTL terminal lugs are cast in copper alloy and palms machined on lower surface.The interlocking clamping design accommodates a wide range of cables. Lugs are fittedwith stainless steel “U” bolts, nuts and spring washers.When required with blank palms, add “B” to Cat.No. For example CTL19-T4-B.When required Electro-Tin Plated, add “T” to Cat. No. For example CTL19-3C-T.
www.powerline-equipment.com.au
RIGHT ANGLE TERMINAL LUG CONDUCTOR TO PALMTYPE CTL-L TWIN U-BOLT CLAMP BAR STYLE
Type CTL-L right angle terminal lugs are designed to accept vertical substation droppers.Otherwise they have the same characteristics as the straight terminals shown above.Supplied with palm blank or drilled to specification.
Cat.No. ConductorRange
Palm Dimensions mm.
mm² ODmm Length Width Thickness
CTL19-L2 25 to215
6.75 to19.25
85 40 11
53
COPPER SUBSTATION FITTINGS
CTL Terminal lugs are cast in Copper alloy. Palms are machined on lower face. Theclamping element utilises a four bolt cap to suit the larger cable sizes. Supplied withstainless steel hardware. Lugs can be supplied with either drilled or blank palm.For blank palm add ‘B’ to Cat. No. For example CTL 26-T4-B.For Electro Tin Plating add ‘T’ to Cat. No. For example CTL 26-T4-P
Cat.No.
Cable Range No.ofPalmholes
Dimensions in mm
mm² OD mm A B C K T L
CTL26-T4B 150to
400
15.75to
25.65
- 50 - - - 12 183
CTL26-T4 2 50 25 50 12 12 183
CTL26-B - 81 - - - 10 165
CTL26-5C 4 81 15 50 12 10 165
D
10
10
10
10
CTL 93-5X 4 102 25 50 12 12 13 190
CTL 113-5X 4 102 25 50 12 12 13 195
CTL 134-5X 4 102 25 50 12 12 13 200
150 to300
300 to500
500 to630
15.75 to22.68
22.68 to28.80
28.80 to33.80
TERMINAL LUG - COPPER CABLE TO SWITCHGEARTYPE CTL SERIES - 4 BOLT CLAMP STYLE
www.powerline-equipment.com.au
K bolt size
RIGHT ANGLE TERMINAL LUG TYPE CTL- RFOUR BOLT CLAMP STYLE
Type CTL-R right angle terminal lugs are designed to accept vertical substation droppers.Otherwise they have the same characteristics as the straight terminals shown above .
Cat.No.
Conductor Range No. ofPalm Holes
mm² OD mm
CTL93R-5X 150to
300
15.75to
22.68
4
54
COPPER SUBSTATION FITTINGS
Type CPC Palmless Connectors provide an economical method of clamping Copper Cablesdirect to switchgear palms. Castings are in high conductivity copper alloy.U-Bolts, nuts and spring washers are stainless steel.* Denotes M10 U-Bolts. All others are fitted with M12 U-Bolts.
Fig.No. Cat. No.
Cable Range Dimensions in mm Switch PalmDrilling
Areamm2
OverallDia.
C L T W X
1 CPC-S2*
50To300
8.9To
22.68
33 38 7 44 SingleU-BoltType
2 Holes 12mmdiameterAt 30 mmcentres
2 CPC302*
25to
215
6.75to
19.2530 65 7 55 30
4 holes 12mmdiameterAt 30 mmcentres
2 CPC3 70To150
10.70To
15.75
50 102 13 76 50 4 Holes 12 mmDiameterAt 50 mmcentres
=
=
2 Holes 14 mmDiameterAt 50 mmcentres
2 CPC4 150To240
15.75To
20.2550 102 13 76 50
2 CPC7 500To630
28.80To
33.8050 102 13 76 50
1 CPC7-S2 500to
630
28.80To
33.80
50 50 13 76 SingleU-boltType
PALMLESS CONNECTORS TYPE CPCFOR COPPER CABLES
Fig.1 Fig. 2
www.powerline-equipment.com.au55
COPPER SUBSTATION FITTINGS
A reliable U-bolt connector designed for substation applications requiring vibration proofconnections. Type CTC Connectors accommodate a wide range of conductor sizes.Made of high copper content alloy and fitted with stainless steel hardware.
Cat. No.
Conductor Range OverallDiameter Dimensions
Main
Min. Max. Min. Max. C B
CTC1919 6.7 17.6 6.7 17.6 65 128
CTC2619 15.7 25.6 6.7 17.6 76 135
CTC2626 15.7 25.6 15.7 25.6 76 150
CTC3434 25.6 33.8 25.6 33.8 100 175
Tap
A
103
105
120
133
CTC1926 6.7 17.6 15.7 25.6 65 130 100
TEE CONNECTOR - TYPE CTCCOPPER CONDUCTOR TO CONDUCTOR
www.powerline-equipment.com.au
Cat.No.
Conductor RangeRun and Tap
Lmm
Area mm² O.D.
CSJ 1919 25 to 215 6.75 to 19.75 138
STRAIGHT CONNECTOR- CONDUCTOR TO CONDUCTORTYPE CSJ
Type CSJ straight connectors allow in-linejointing of copper conductors.They are castIn high copper content alloy and suppliedwith stainless steel hardware.
56
COPPER SUBSTATION FITTINGS
THREADED STUD CONNECTOR - TYPE TSC
A variable conductor stud connector which takes a wide range of conductor sizes eitherin line or at right angles to the stud. Connector body is made of high copper content alloy.
Bolts and nuts are stainless steel.
CatalogueNo.
StudS
ConductorRange OD
mm. B C L
TSC12 1/2” BSW 5.1 - 8.9 See Note 45 75
TSC58 5/8” BSW 6.7-15.75 45 55 102
TSC34 3/4” BSW 6.7-15.75 45 55 102
TSC78 7/8” BSW 6.7-15.75 58 55 123
Dimensions in mm.
NOTE: Catalogue number TSC12 is supplied with lock nut in place of pinch screws.Type TSC connectors can also be supplied with electro tin-plated finish if required.For this variation add ’P’ to Cat. No. For example TSC58-P.
THREADED STUD CLAMPCat. No. TSC1635
A two-piece clamp in tinned copper alloy. Lower section is tapped M16 x 2.0 thread.Upper section is drilled 18mm diameter. Both cable grooves accommodate cablesfrom 16mm² to 35mm². Clamp connection is completed by equipment threaded studlocking nut. Other thread and cable sizes can be supplied.
www.powerline-equipment.com.au57
COPPER SUBSTATION FITTINGS
CatalogueNo.
No. ofBraids
CurrentRating
ShortTime
CurrentRating
Dimensions
C F L T W D
CFA100 1 100 2600 30 - 300 6 25 11.5 1
CFA300 4 300 10700 30 - 300 8 25 11.5 1
CFA450 6 450 16100 30 - 300 10 25 11.5 1
CFX100 1 100 2600 30 - 300 6 25 13.5 1
CFX300 4 300 10700 30 - 300 8 25 13.5 1
CFX450 6 450 16100 30 - 300 10 25 13.5 1
CFB100 1 100 2600 60 22 300 6 25 11.5 2
CFB300 4 300 10700 60 22 300 8 25 11.5 2
CFB450 6 450 16100 60 22 300 10 25 11.5 2
CFC100 1 100 2600 60 29 300 6 25 11.5 2
CFC300 4 300 10700 60 29 300 8 25 11.5 2
CFC450 6 450 16100 60 29 300 10 25 11.5 2
CFD300 4 300 84 50 300 8 25 11.5 2
CFY300 4 300 84 50 300 8 25 14.0 2
Fig.No.
COPPER FLEXIBLE BRAID CONNECTIONS– TYPE CF
Flat flexible tinned copper braid is swaged into seamless tinned copper ferrules to formthese flexible connections.Applications include the earthing of switch handles and substation fences. Standard drill-ings of type CFB and CFC match those of the type CTF tube connectors, which can becombined to provide expansion joints for tubular busbar.
www.powerline-equipment.com.au 58
COPPER SUBSTATION FITTINGS
COPPER FLEXIBLE BRAID CONNECTIONS—TYPE CR
Round flexible tinned copper braid is swaged into seamless tinned copper ferrules toform these flexible connections. Applications include the earthing of switch handlesand substation fences. Standard drillings of type CRB and CRC match those of thetype CTF tube connectors, which can be combined to provide expansion joints fortubular busbar.
No. ofBraids
CurrentRating
ShortTime
CurrentRating
Dimensions
Fig.No.C F L T W D
CRA200 1 200 6200 30 - 300 7 25 11.5 1
CRA400 2 400 12500 30 - 300 9 25 11.5 1
CRB200 1 200 6200 60 22 300 7 25 11.5 2
CRB400 2 400 12500 60 22 300 9 25 11.5 2
CRC200 1 200 6200 60 29 300 7 25 11.5 2
CRC400 2 400 12500 60 29 300 9 25 11.5 2
CRC500 2 500 200000 60 29 300 12 30 11.5 2
CRC500X 2 500 200000 100 - - 10 30 - 2
CatalogueNo.
CRC670 2 670 2
CRC1000 3 1000 50 2
NOTE: The above flexible connector configurations are an indication only.Other lengths, hole drillings and ferrule lengths can be manufactured to order.
www.powerline-equipment.com.au
Fig.2Fig.1
59
COPPER SUBSTATION FITTINGS
COPPER FLEXIBLE LAMINATED CONNECTORS– TYPE LXC
Suitable for flexible end-to-end connections between busbar and equipment terminalpalms. Connectors are made from a series of copper strips which are pre– formedin order to to allow movement during expansion of the busbar system. Drilled endsare soldered to provide a solid bolted connection. Standard finish is electro tin plate.Other sizes and shapes can be supplied to customer requirements.
Fig.No.
Dimensions in Millimetres Approx. D/C
RatingAmp.
A C DBolt
Size E W L
ApproxThick-ness
LXC600-51 2 - 19 40 M10 51 300 9 600
LXC800-51 2 - 19 40 M10 51 300 10 800
LXC1200-51 2 - 19 40 M10 51 300 12 1200
LCX 800-76 1 40 19 40 M10 76 300 9 800
LCX1200-76 1 40 19 40 M10 76 300 13 1200
Catalogue No.
LCX 1800-76 1 40 19 40 M10 76 300 19 1800
LCX 800-100 1 50 25 50 M12 100 400 6 800
www.powerline-equipment.com.au
NOTE. Type LXC Flexible Connectors can also be suppliedas illustrated for on-site drilling when required.
OTHER SIZES AVAILABLE UPON REQUEST
60
COPPER SUBSTATION FITTINGS