seadxx2412 air conditioner- electric heat dimensional

4
DATE: DESCRIPTION: SEADXX2412 AIR CONDITIONER- ELECTRIC HEAT DIMENSIONAL & PERFORMANCE DATA PROJECT: TAG: SEAD752412 SEAD102412 SEAD152412 6.30 / 7.71 8.41 / 10.28 12.61 / 15.42 2 2 3 700 (LO) 800 (MED) 800 (MED) 21.5 / 26.3 28.7 / 35.1 43.0 / 52.6 39.80 52.48 77.78 40 60 80 43.78 57.74 85.68 45 60 90 * T.C. = NET COOLING CAPACITY (HEAT DISSIPATION FROM FAN MOTOR INCLUDED) ** FACTORY SUPPLIED MAX FUSE/CCT. BKR. 230V MAX FUSE/CCT. BKR. 208V APPROX. SHIP. WEIGHT 14.1 58.3 24 in. x 34 in. / 1 inch Thick REPLACEABLE MEDIA 325 FILTER SIZE / TYPE** CFM (MOTOR SPEED) HEATING OUTPUT MBTU / HR COOLING SECTION (R-410A) BTU/HR SENSIBLE NO. OF ELEMENTS ELECTRIC HEAT SECTION MODEL NUMBER 208-230/1/60 KW Total - 208/230 PERFORMANCE TESTED IN ACCORDANCE WITH ARI STANDARD 210/240-94. RATING CONDITIONS OF 95 o F OUTDOOR AMBIENT, AND 80 o F db / 67 o F wb INDOOR AIR TEMPERATURE CAUTION: COOLING SECTION OF THIS UNIT SHOULD NOT BE OPERATED WHEN OUTSIDE TEMPERATURE IS BELOW 60 o F BTU/HR T.C.* COMPRESSOR R.L.A. MIN. CIRCUIT AMPACITY 208V CFM AT .30" E.S.P EFFICIENCY (S.E.E.R.) COMPRESSOR L.R.A. MIN. CIRCUIT AMPACITY 230V 11.0 208-230/1/60 (197 MIN. OPER. VOLTS) 24,400 19,400 800 March 2008 Form 145.25-PA11 (308) 1 of 4 Johnson Controls maintains a continuous product improvement policy, therefore specifications are subject to change without notice.

Upload: others

Post on 14-May-2022

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: SEADXX2412 Air Conditioner- Electric Heat Dimensional

DATE:

DESCRIPTION:

SEADXX2412AIR CONDITIONER- ELECTRIC HEAT

DIMENSIONAL & PERFORMANCE DATA

PROJECT: TAG:

SEAD752412 SEAD102412 SEAD152412

6.30 / 7.71 8.41 / 10.28 12.61 / 15.422 2 3

700 (LO) 800 (MED) 800 (MED)21.5 / 26.3 28.7 / 35.1 43.0 / 52.6

39.80 52.48 77.7840 60 80

43.78 57.74 85.6845 60 90

* T.C. = NET COOLING CAPACITY (HEAT DISSIPATION FROM FAN MOTOR INCLUDED)

** FACTORY SUPPLIED

MAX FUSE/CCT. BKR. 230V

MAX FUSE/CCT. BKR. 208V

APPROX. SHIP. WEIGHT

14.158.3

24 in. x 34 in. / 1 inch Thick REPLACEABLE MEDIA

325

FILTER SIZE / TYPE**

CFM (MOTOR SPEED)HEATING OUTPUT MBTU / HRCOOLING SECTION (R-410A)

BTU/HR SENSIBLE

NO. OF ELEMENTS

ELECTRIC HEAT SECTIONMODEL NUMBER

208-230/1/60KW Total - 208/230

PERFORMANCE TESTED IN ACCORDANCE WITH ARI STANDARD 210/240-94. RATING CONDITIONS OF

95oF OUTDOOR AMBIENT, AND 80oF db / 67oF wb INDOOR AIR TEMPERATURE

CAUTION: COOLING SECTION OF THIS UNIT SHOULD NOT BE OPERATED WHEN OUTSIDE TEMPERATURE IS BELOW 60oF

BTU/HR T.C.*

COMPRESSOR R.L.A.

MIN. CIRCUIT AMPACITY 208V

CFM AT .30" E.S.PEFFICIENCY (S.E.E.R.)

COMPRESSOR L.R.A.

MIN. CIRCUIT AMPACITY 230V

11.0

208-230/1/60 (197 MIN. OPER. VOLTS)

24,40019,400

800

March 2008

Form 145.25-PA11 (308)

1 of 4

Johnson Controls maintains a continuous product improvement policy, therefore specifications are subject to change without notice.

Page 2: SEADXX2412 Air Conditioner- Electric Heat Dimensional

DATE:

DESCRIPTION:

MECHANICAL SPECIFICATIONSSKYPAK ELECTRIC HEAT UNIT

GENERALAll SKYPAK models feature a complete heating, cooling, and air handling system in one self-containedassembly. Units are shipped completely factory assembled, tested, and ready for field connection. The unitcasing is made entirely of heavy gauge galvanized steel. The cabinet interior is fully insulated with foil facedfiberglass insulation, firmly attached with nonflammable adhesive, to prevent heat loss or gain to the interiorspace. All operating components of the mechanical systems are completely enclosed in the insulated cabinetto minimize sound transmission.

Units are designed for freestanding floor mounting, in conjunction with the companion wall sleeve. Airfloworientation is up-flow, top discharge. Units may be ordered in either left hand, or right hand, return airconfiguration. The return air opening is field selectable for side intake or bottom intake; a pre-scored intake-opening panel requires removal from either the evaporator side panel, or the unit bottom panel.

An optional bottom return air plenum is available to allow alternate return air duct layouts. The outdoor wallgrille is available in five standard colors, or may be custom color matched.

COOLING SECTIONAll models utilize a high efficiency rotary or Scroll type compressor. Each refrigeration circuit is thoroughlyevacuated, and fully charged with R-410A refrigerant before shipment. Internal compressor-motor overloadprotection is standard. Compressors are mounted on rubber isolators to minimize vibration transmission. Acompressor start assist device is included to ensure reliable compressor operation in the event of low supplyvoltage.

The refrigeration circuit includes an externally equalized thermal expansion valve, liquid line filter drier, a highrefrigerant pressure switch (manual-reset), and service gauge ports. The evaporator and condenser coils areconstructed of internally enhanced copper tubes mechanically bonded to enhanced aluminum plate fins. Theevaporator coil is employed in a blow-through configuration. Large evaporator coil face areas maximizesefficiency and cooling performance.

INDOOR AND OUTDOOR FANSForward curved, double inlet and double width, direct-drive centrifugal blowers are used for evaporator andcondenser air movement. Large diameter wheels are employed to provide required airflow performance atminimum sound levels. Blower wheels are fabricated of galvanized steel. Fan motors are PSC types, withminimum three speeds on the evaporator motor. The PSC motors feature permanently lubricated bearings andinternal thermal overload protection.

ELECTRIC FURNACE SECTIONElectric heating elements consist of resistance-type nickel-chrome wire supported in ceramic holders. Thebare wire elements are exposed directly in the air stream resulting in instant heat transfer, lower elementtemperatures, and long service life. Each heavy-gauge element frame is equipped with an auto reset limitcontrol, and elements are individually removable for service. Relays bring the heating elements on and off, insequence and equal increments, with a time delay between each element. In addition, relays initiate or stopblower operation, or change blower speed. The unit controls are factory wired to a low-voltage terminal strip,for connection to single stage heat/cool thermostat.

FILTERSAll models are shipped complete with an internal, suspended wire-frame style filter rack, for use withreplaceable filter media. A one-inch thick fiberglass media filter is factory provided (Media Size = 24” Wide X 34” Long).An optional flat-panel filter rack is available for field installation on units employing the side return air intake. Aone-inch thick throwaway filter must be field provided (Flat Filter Size = 16 X 25 X 1).

March 2008

Form 145.25-PA11 (308)

2 of 4

Johnson Controls maintains a continuous product improvement policy, therefore specifications are subject to change without notice.

Page 3: SEADXX2412 Air Conditioner- Electric Heat Dimensional

March 2008

Form 145.25-PA11 (308)

3 of 4

Page 4: SEADXX2412 Air Conditioner- Electric Heat Dimensional

March 2008

Form 145.25-PA11 (308)

4 of 4