scsu light pole led retrofit analysis

31
SCSU Light Pole LED Retrofit Analysis Don Granlund III Krystal Sweeter Joseph A. Sanders

Upload: mayes

Post on 23-Feb-2016

38 views

Category:

Documents


0 download

DESCRIPTION

SCSU Light Pole LED Retrofit Analysis. Don Granlund III Krystal Sweeter Joseph A. Sanders. Project Description. - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: SCSU Light Pole LED Retrofit Analysis

SCSU Light Pole LED Retrofit

Analysis

Don Granlund IIIKrystal Sweeter

Joseph A. Sanders

Page 2: SCSU Light Pole LED Retrofit Analysis

Project Description

• The purpose of this project was to find and map and collect data on all of the light poles on the SCSU campus for the maintenance department using ArcGIS 10.1 software, and to conduct a cost/benefit analysis of retrofitting those light poles to LED

• Joe Teff• Alyssa Heinen

Page 3: SCSU Light Pole LED Retrofit Analysis

Objectives

• Map, inspect, and photograph every light pole on the SCSU campus and create a detailed ArcGIS “layer” for the existing campus map

• Determine the total number of light poles on campus

• Determine the difference between high-pressure sodium lights and LEDs in initial cost, maintenance, energy usage, and average lifespan

• Create a cost/benefit analysis

Page 4: SCSU Light Pole LED Retrofit Analysis

Phase 1 of ArcGIS

• Primary objective: Gather data for “electronic” map

• Created 6 “mini-maps” which were used to accurately map all 530 light poles on campus

• 1,060 photo’s were taken for inspection and maintenance records

• Each light pole was given an identification number and “Image_id”

Page 5: SCSU Light Pole LED Retrofit Analysis
Page 6: SCSU Light Pole LED Retrofit Analysis
Page 7: SCSU Light Pole LED Retrofit Analysis
Page 8: SCSU Light Pole LED Retrofit Analysis
Page 9: SCSU Light Pole LED Retrofit Analysis

Phase 2 of ArcGIS

• Primary objective: Develop a layer within the ArcGIS campus map

• Plotted every light pole in our layer on the “electronic” version of the campus map

• Developed an attribute table for data and maintenance records

• Inputted data manually into our ArcGIS layer

Page 10: SCSU Light Pole LED Retrofit Analysis

Attribute Table – (9 Fields)• OBJECTID*, Lightpole_ID, Image_ID, Bulb_type, Pole_Material, Wattage, Voltage, Last_Insp_Date, Comments

Page 11: SCSU Light Pole LED Retrofit Analysis

Phase 3 of ArcGIS

• Primary objective: Develop an ArcGIS Instructional booklet

• Booklet consists of 4-steps

• These 4-steps are identical to the steps used to create the layer with the ArcGIS campus map

• Designed the Instructional booklet to ArcGIS “noob-friendly”

Page 12: SCSU Light Pole LED Retrofit Analysis
Page 13: SCSU Light Pole LED Retrofit Analysis
Page 14: SCSU Light Pole LED Retrofit Analysis
Page 15: SCSU Light Pole LED Retrofit Analysis

LED vs. HPS

• Lumens - derived unit of luminous flux, a measure of the total "amount" of visible light emitted by a source.

• LED engines have a mean of 3,425 lumens compared to 2,250 lumens of HPS bulbs.

• LED engines operate at 55 watts and have a lower operating temperature. Current bulbs on campus operate at 150 Watts.

• LED engines have a life span of 100,000 hours or 22.83 years! HPS last only 16,000 years or 3.65 years.

Page 16: SCSU Light Pole LED Retrofit Analysis

D-Series Size 1

Jordan Ruddy – Grainger Industrial Supply

Page 17: SCSU Light Pole LED Retrofit Analysis

D-Series Size 1

• Mast Arm Mount• Features:

– Consists of 1 or 2 LED engines: each engine has 30 LEDs

– Majority of lamps can be replaced easily with just four bolts

– Long lasting– Energy Efficient– Ideal for replacing 100W to 400W area

lighting

Page 18: SCSU Light Pole LED Retrofit Analysis

Cost and Benefits

• High Pressure Sodium:– Cost of Lamps:

$40.75– Cost of ballast:

$178.25– Lifespan: 16,000

hours

• LED– Cost of LED

Replacement: $740.00

– Lifespan: 100,000 hours

• HPS and LED:– Average hours lit: 12 hours– Amount Xcel charges per Kilowatt: $.072– Total Number of light poles: 530

Page 19: SCSU Light Pole LED Retrofit Analysis

Cost and Benefits Cont.

HPS Wattages• 70%- 100 Watts• 20%- 150 Watts• 10%- 200 Watts

LED Wattages • 55 Watts

Page 20: SCSU Light Pole LED Retrofit Analysis

Costs and Benefits Cont.

Page 21: SCSU Light Pole LED Retrofit Analysis

Cost and Benefits Cont.

• Results

• HPS• 100 Watts: $11,645• 150 Watts: $5,014• 200 Watts: $3,346

– Total: $20,005 per year

• LED• 55 Watts: $9,285.69 per year• Savings: $10,719.31

Page 22: SCSU Light Pole LED Retrofit Analysis

Cost and Benefits Cont.

• Initial investment– $405,980 • $405,980 / $10,971 (difference in operating

costs)= 37.62 years to break even!?

• For Real?

Page 23: SCSU Light Pole LED Retrofit Analysis

Cost and Benefits Cont.

• HPS operating Cost per year = $20,005.00…16,000 hours of life or 3.6 years

• LED operating cost per year = $9,285.00…100,000 hours of life or 22.83 years

• Initial Investment for LED = $405,980.00

• Operating cost (electricity used) difference between LED and HPS = $10,791.31

• $405,980 / $10,791 = 37.62 years to break even on initial investment not counting labor or HPS bulb cost.

Page 24: SCSU Light Pole LED Retrofit Analysis

Cost and Benefits Cont.

• Currently, SCSU has roughly 530 HPS bulbs / 3.6 year life expectancy = 147.2 bulbs replaced per year on average which costs $5,998.40 in replacement HPS bulbs. Lets assume 10 bulbs per day are replaced over 14 days. Estimated labor cost is $100 per hour. So to buy and replace HPS bulbs costs a total of $14,720 per year in labor plus $5,998.40 in replacement bulbs. Which accumulates a of $20,718.40 per year.

Page 25: SCSU Light Pole LED Retrofit Analysis

Cost and Benefits Cont.

• So if you take $405,980 (initial investment) / $20,718.40 (Labor and HPS replacement cost) in labor that equals only 19.59 years to break even. Which is before any LEDs will burn out. This leaves SCSU a period of 3.24 years before the first LED fails. During this time SCSU will realize a savings of $20,718.40 per year in labor and energy, with a total of $67,127.62 over 3.24 years by not buying HPS bulbs and saving in labor costs. This $67,127.62 is deducted from the initial investment of $405,980.00 equaling $341,853 which means that SCSU will realistically “break even” in a little over 20 years.

Page 26: SCSU Light Pole LED Retrofit Analysis

Excel Graph

*This Excel graph was designed to be updated with potential change with costs, total bulbs, labor costs, and other variables if need be

Page 27: SCSU Light Pole LED Retrofit Analysis

Conclusions and Recommendations

• SCSU should switch to all LED– Conserve Energy– Excellent Long-term

investment– Status Symbol– Forward Thinking • An average of 147 HPS bulbs cease to

operate on campus per year. Instead of replacing those 147 bulbs, invest in LED.

• Map ALL the exterior lights on campus • LIGHT POLE SPACING ANALYSIS?• Professional Audit. Again?

Page 28: SCSU Light Pole LED Retrofit Analysis

Reflection and Discussion

• We feel the Project was a big success

• Purpose of Project– Save SCSU time and money– Laid groundwork for future mapping of exterior lights– Provided hard data on switching to LED lights

• Valuable Experience– Project had a late start– Meeting with experts– Time management – Work delegation

Page 29: SCSU Light Pole LED Retrofit Analysis

Work Log

• ArcGIS mapping, photographs, procedures, and development – 22 hours

• Cost/benefit Analysis – 12 hours

• Research, written report, meetings, and communication – 16 hours

• TOTAL – 50 hours

Page 30: SCSU Light Pole LED Retrofit Analysis

Reflection and Discussion

• Skills Acquired/Refined– Long and short term planning– Time management (setting goals)– GIS

• Useful Courses– Principles of Geographic Information Systems– Resource Management– Communication Technology– Environmental and Technological Assessment– Environmental Systems Modeling– Environmental Economics

Page 31: SCSU Light Pole LED Retrofit Analysis

Questions???“I get to graduate