SCHEDULE OF RATES
FOR
ELECTRICAL INSTALLATION
WORKS IN SARAWAK 2020
Notes to tenderers:
1. This is only a cover page for this document. Please obtain the full set from the JKR Sarawak webpage.
2. The “Location Factor From Base at Kuching City” for this tender is ____ %
and is the percentage over all the items and rates as listed in this Schedule of Rates to be used for the purposes as stated in the tender documents.
3. Any attempt to amend / change / correct etc. this percentage by the
tenderer shall cause the tender to be disqualified.
JKR Sarawak
December 2020
LOCATION FACTOR FROM BASE AT KUCHING CITY
(To be read together with the Rules of Determining the Location Factor)
Kuching
City
Padawan
Santubong
Bau
Lundu
Sematan
0%
2%
3%
5%
8%
9%
Serian
District
Tebedu
Siburan
Tebakang
Balai Ringin
5%
8%
3%
8%
8%
Samarahan
District
Simunjan
Sebuyau
Asajaya
Sadong Jaya
2%
12%
15%
10%
12%
Sri Aman
District
Lubok Antu
Lingga
Pantu
Engkilili
Skrang
15%
20%
20%
20%
18%
20%
Betong
District
Spaoh
Debak
Pusa
Beladin
Maludam
Saratok
Roban
Kabong
20%
20%
20%
21%
20%
22%
20%
20%
20%
Sarikei
District
Bintangor
Pakan
Selalang
Julau
Meluan
Ulu Entabai
Engkamop
Nanga Wak
Nanga Entabai
18%
18%
20%
20%
20%
22%
40%
25%
15%
14%
Sibu
District
Kem Bt. 10 & 14
Durin
Bawang Assan
Sungai Assan
Kanowit
Machan
Nibong Tada
Nanga Tada
Nanga Dap
Nanga Ngemah
Nanga Ngungun
Nanga Poi
Nanga Jagau
Selangau
Ulu Balingian
Arip
Stapang
Rassau
12%
13%
15%
13%
13%
16%
16%
15%
17%
20%
20%
20%
22%
40%
18%
20%
22%
16%
22%
LOCATION FACTOR FROM BASE AT KUCHING CITY
(To be read together with the Rules of Determining the Location Factor)
Bintulu
District
Tatau
Sebauh
15%
20%
23%
Miri
City
Subis
Bekenu
Marudi
Long Lama
Beluru
15%
20%
15%
25%
40%
22%
Limbang District
Lawas
30%
28%
Mukah
District
Dalat
Oya
Igan
Balingian
Kuala Balingian
Semop
Matu
Betanak
Daro
Bruit
Tanjung Manis
20%
20%
20%
18%
23%
23%
30%
25%
30%
25%
30%
18%
Kapit
District
Song
Belaga
Sungai Asap
Bukit Mabong
30%
25%
70%
25%
40%
RULES OF DETERMINING THE LOCAT ION FACTOR
1. The percentage (%) factors as stated are for those projects accessible by motorized vehicles
within fifteen kilometres (15 km) radius from the location shown.
2. Where the project site is beyond fifteen kilometres (15 km) radius of the above stated
locations, these additional percentage (%) factors shall be added on to those percentages
stated above:
Item Radius Percentage (%) Addition
(i) > 15 km to < 45 km 5%
(ii) > 45 km to < 90 km 10%
(iii) > 90 km to < 135 km 15%
(iv) > 135 km to < 180 km 20%
(v) > 180 km to < 220 km 25%
3. Where the project sites are accessible only by waterway:
Item Radius Percentage (%) Addition
(i) areas within 15 km radius 0%
(ii) areas within 30 km radius 5%
(iii) areas within 60 km radius 10%
(iv) areas within 90 km radius 15%
(v) areas within 120 km radius 20%
(vi) areas within 150 km radius 25%
4. Where the project sites can only be accessible by air, the location factor shall be doubled
over the value obtained from that by motorized vehicles.
5. Where the project sites can only be accessible by foot, the location factor shall be fifty
percent (50%) over the value obtained from that by motorized vehicles.
6. Where in determining the locations factor and two or more factors and radial distances are
equally applicable, the lower in each case shall be used.
7. Where in determining the location factor and two or more factors and radial distances by the
rules above whereby there can be a combination due to accessibility, say partly land and
partly waterway or partly waterway and partly by foot, there shall be a combination of the
rules according to the radial distance from the nearest locations stated above.
8. Where in determining the location factor and the site for the project lies within two radial
distances, the additional percentage (%) for the radial distance within which more than fifty
percent (50%) of the Site lies shall be used.
SOR for Electrical Installation Works 2020 1
PREAMBLES
1. All rates given shall include supply, delivery, installation, testing and commissioning and shall include associated accessories and fitting.
2. Rate per point applies for the stated route length. For longer route length, the rate per metre, derived from the rate per point shall be used.
3. All rates shall be used and read together with the “Location Factor From Base at Kuching City”.
4. All rates herein have reasonably taken into account anticipated and calculated inflation and risk factors for the next two (2) years from the date of publication.
5. All descriptions are to be read with reference to the Standard Electrical Installation Specification (Latest Version) and the following:
(A) All rates herein shall be held to include for supply and delivery to site, wastage on materials, carriage and cartage, carrying in and return of empties, hoisting, setting, fitting and fixing in position, making good and all other labours and everything else necessary (including any custom duties, etc.) for the proper completion of each item and for establishment charges and profit.
(B) Rates for each item of paving shall be held to include for all rounded angles, arises and making good and any other sundry items of alike nature.
(C) Rates for mild steel tubing are to include for short running lengths, sockets, backnuts, elbows and bends.
A GENERAL WIRING
SOR ELECTRICAL INSTALLATION WORKS 2020/Page 1 of 15
Item No.
Description Unit Rate (RM)
(A1)
1
(a)
(b)
(c)
2
(a)
3
(a)
(b)
4
(a)
(b)
(c)
5
(a)
(b)
(c)
(d)
(e)
6
(a)
GS Concealed conduit wiring c/w metal clad switch and socket plates and accessories : Wiring shall be run concealed, in Class ‘B’ galvanised
steel conduits and complete with GS conduit boxes let into cement or timber wall, or partition, together with all necessary metal clad lighting switch plates, switched socket plates, isolators and accessories. Wiring shall be 1.5 mm
2 PVC for fan and lighting points, 2.5 mm
2 PVC for 13A and 15A
switched sockets. 13A 3-pin switched socket points shall be wired in ring circuit(s). Lighting & Fan Points shall be terminated to ceiling rose. Accepted brands – Clipsal, PDL, MEM & JMAL approved brands. Lighting Point : wired from nearest switch c/w 1.5 mm
2 PVC cable (up to
20 metres route length). 6A 1-way lighting point c/w switch. 6A 2-way lighting point c/w switch. 6A immediate lighting point c/w switch. Lighting Point : wired from nearest lighting point (sharing same switch) (up
to 4 metres route length). 6A 1-way lighting point. Fan Point : wired from nearest switch c/w 1.5 mm
2 PVC cable (up to 10
metres route length). Ceiling fan point c/w 6A switch. Extractor fan point c/w 6A switch. Cost excludes hard-wood frame and opening for fan. 13A 3-pin : Switched Socket Outlets :
13A 3-pin switched socket point in ring circuit : 1 – gang (up to 10 metres route length). 13A 3-pin switched socket point in ring circuit : 2 – gang (up to 10 metres route length). 15A 3-pin switched socket point (up to 15 metres route length). Isolator and Water Heater Points : (up to 15 metres route length).
Water heater point c/w 20A double pole switch with neon light indicator (4mm
2 PVC cable).
20A single phase isolator point c/w 4 mm
2 PVC cable.
30A single phase isolator point c/w 6 mm
2 PVC cable.
20A TPN isolator point c/w 4 mm
2 PVC cable.
30A TPN isolator point c/w 6 mm
2 PVC cable.
TV / Telephone Point : (up to 15 metres route length).
1-pair c/w socket and 2 x 0.63 mm
2 cable.
per point
per point
per point
per point
per fan point
per fan point
per 1-gang socket outlet pt.
per 2-gang
socket outlet pt.
per point
per point
per isolator point
per isolator point
per isolator point
per isolator point
per point
110.00
150.00
175.00
58.00
110.00
110.00
150.00
200.00
250.00
285.00
330.00
450.00
475.00
640.00
105.00
A GENERAL WIRING
SOR ELECTRICAL INSTALLATION WORKS 2020/Page 2 of 15
Item No.
Description Unit Rate (RM)
6
(b)
(c)
7
(a)
(b)
(A2)
8
(a)
(b)
(c)
9
(a)
10
(a)
(b)
11
(a)
(b)
(c)
TV / Telephone Point : (up to 15 metres route length). (Cont’d)
2-pairs c/w socket and 4 x 0.63 mm
2 cable.
TV antennae point c/w 5c / 2v cable and TV socket. Miscellaneous Wiring Point : (up to 15 metres route length).
Single phase power supply to fire alarm control panel c/w 16A mcb and 2.5 mm
2 PVC cable.
Lighting point for “Emergency Lighting” or “Keluar Light” c/w 1.5 mm
2 PVC
cable. GS Surface conduit wiring c/w metal clad switch and socket plates and accessories : Wiring shall be run concealed, in Class ‘B’ galvanised steel
conduits and complete with GS conduit boxes, together with all necessary metal clad lighting switch plates, switched socket plates, isolators and accessories. Wiring shall be 1.5 mm
2 PVC for fan and lighting points, 2.5
mm2
PVC for 13A and 15A switched sockets. 13A 3-pin switched socket points shall be wired in ring circuit(s). Lighting & Fan Points shall be terminated to ceiling rose. Accepted brands – Clipsal, PDL, MEM & JMAL approved brands. Lighting Point : wired from nearest switch c/w 1.5 mm
2 PVC cable (up to
20 metres route length). 6A 1-way lighting point c/w switch. 6A 2-way lighting point c/w switch. 6A immediate lighting point c/w switch. Lighting Point : wired from nearest lighting point (sharing same switch) (up
to 4 metres route length). 6A 1-way lighting point. Fan Point : wired from nearest switch c/w 1.5 mm
2 PVC cable (up to 10
metres route length). Ceiling fan point c/w 6A switch. Extractor fan point c/w 6A switch. Cost excludes hard-wood frame and opening for fan. 13A 3-pin : Switched Socket Outlets :
13A 3-pin switched socket point in ring circuit : 1 – gang (up to 10 metres route length). 13A 3-pin switched socket point in ring circuit : 2 – gang (up to 10 metres route length). 15A 3-pin switched socket point (up to 15 metres route length).
per point
per point
per point
per point
per point
per point
per point
per point
per fan point
per fan point
per 1-gang socket outlet point
per 2-gang socket
outlet point
per point
130.00
105.00
250.00
105.00
100.00
135.00
155.00
53.00
100.00
100.00
135.00
180.00
225.00
A GENERAL WIRING
SOR ELECTRICAL INSTALLATION WORKS 2020/Page 3 of 15
Item No.
Description Unit Rate (RM)
12
(a)
(b)
(c)
(d)
(e)
13
(a)
(b)
(c)
14
(a)
(b)
(A3)
15
(a)
(b)
(c)
16
(a)
17
(a)
Isolator and Water Heater Points : (up to 15 metres route length).
Water heater point c/w 20A double pole switch with neon light indicator (4mm
2 PVC cable).
20A single phase isolator point c/w 4 mm
2 PVC cable.
30A single phase isolator point c/w 6 mm
2 PVC cable.
20A TPN isolator point c/w 4 mm2 PVC cable.
30A TPN isolator point c/w 6 mm2 PVC cable.
TV / Telephone Point : (up to 15 metres route length).
1 – pair c/w socket and 2 x 0.63 mm
2 cable.
2 – pairs c/w socket and 4 x 0.63 mm
2 cable.
TV antennae point c/w 5c / 2v cable and TV socket. Miscellaneous Wiring Point : (up to 15 metres route length).
Single phase power supply to fire alarm control panel c/w 16A mcb and 2.5 mm
2 PVC cable.
Lighting point for “Emergency Lighting” or “Keluar Light” c/w 1.5 mm
2 PVC
cable. GS Concealed conduit wiring c/w plastic moulded switch and socket plates and accessories : Wiring shall be run concealed, in Class ‘B’ galvanized steel conduits and complete with GS conduit boxes let into cement or timber wall, or partition, together with all necessary PVC moulded lighting switch plates, switched socket plates and accessories. Wiring shall be 1.5 mm
2 PVC for fan and lighting points, 2.5 mm
2 PVC for 13A and 15A
switched sockets. 13A 3-pin switched socket points shall be wired in ring circuit/s. Lighting & Fan Points shall be terminated to ceiling rose. Accepted brands – Clipsal, PDL, MEM & JMAL approved brands. Lighting Point : wired from nearest switch c/w 1.5 mm
2 PVC cable (up to
20 metres route length). 6A 1-way lighting point c/w switch. 6A 2-way lighting point c/w switch. 6A immediate lighting point c/w switch. Lighting Point : wired from nearest lighting point (sharing same switch) (up
to 4 metres route length). 6A 1-way lighting point. Fan Point : wired from nearest switch c/w 1.5 mm
2 PVC cable (up to 10
metres route length). Ceiling fan point c/w 6A switch.
per point
per isolator point
per isolator point
per isolator point per isolator point
per point
per point
per point
per point
per point
per point
per point
per point
per point
per fan point
255.00
295.00
405.00
430.00
580.00
95.00
115.00
95.00
225.00
95.00
105.00
145.00
165.00
55.00
105.00
A GENERAL WIRING
SOR ELECTRICAL INSTALLATION WORKS 2020/Page 4 of 15
Item
No. Description Unit Rate (RM)
17
(b)
18
(a)
(b)
(c)
19
(a)
(b)
(c)
(d)
(e)
20
(a)
(b)
(c)
21
(a)
(b)
(A4)
22
(a)
Fan Point : wired from nearest switch c/w 1.5 mm2 PVC cable (up to 10
metres route length). (Cont’d)
Extractor fan point c/w 6A switch. Cost excludes hard-wood frame and
opening for fan.
13A 3-pin : Switched Socket Outlets :
13A 3-pin switched socket point in ring circuit :
1-gang (up to 10 metres route length).
13A 3-pin switched socket point in ring circuit :
2-gang (up to 10 metres route length).
15A 3-pin switched socket point (up to 15 metres route length).
Isolator and Water Heater Points : (up to 15 metres route length).
Water heater point c/w 20A double pole switch with neon light indicator
(4 mm2
PVC cable).
20A single phase isolator point c/w 4 mm2 PVC cable.
30A single phase isolator point c/w 6 mm2 PVC cable.
20A TPN isolator point c/w 4 mm2 PVC cable.
30A TPN isolator point c/w 6 mm2 PVC cable.
TV / Telephone Point : (up to 15 metres route length).
1 – pair c/w socket and 2 x 0.63 mm2 cable.
2 – pairs c/w socket and 4 x 0.63 mm2 cable.
TV antennae point c/w 5c / 2v cable and TV socket.
Miscellaneous Wiring Point :(up to 15 metres route length).
Single phase power supply to fire alarm control panel c/w 16A mcb and 2.5
mm2 PVC cable.
Lighting point for “Emergency Lighting” or “Keluar Light” c/w 1.5 mm2 PVC
cable.
uPVC Concealed conduit wiring c/w plastic moulded switch and socket plates and accessories : Wiring shall be run surface in High
Impact / uPVC conduit and complete with PVC conduit boxes together with all necessary PVC lighting switch plates, switched socket plates, isolator and accessories. Wiring shall be 1.5 mm
2 PC for fan and lighting points,
2.5 mm2 PVC for 13A and 15A switched sockets. Lighting & Fan Points
shall be terminated to ceiling rose. Accepted brands – Clipsal, PDL, MEM & JMAL approved brands. Lighting Point : wired from nearest switch c/w 1.5 mm
2 PVC cable (up to
20 metres route length). 6A 1-way lighting point c/w switch
per fan point
per 1-gang
socket outlet pt.
per 2-gang
socket outlet pt.
per point
per point
per isolator point
per isolator point
per isolator point
per isolator point
per point
per point
per point
per point
per point
per point
105.00
140.00
190.00
240.00
270.00
310.00
430.00
450.00
608.00
100.00
120.00
100.00
240.00
100.00
95.00
A GENERAL WIRING
SOR ELECTRICAL INSTALLATION WORKS 2020/Page 5 of 15
Item No.
Description Unit Rate (RM)
22
(b)
(c)
23
(a)
24
(a)
(b)
25
(a)
(b)
(c)
26
(a)
(b)
(c)
(d)
(e)
27
(a)
(b)
(c)
28
(a)
(b)
Lighting Point : wired from nearest switch c/w 1.5 mm
2 PVC cable (up to
20 metres route length). (Cont’d) 6A 2-way lighting point c/w switch 6A immediate lighting point c/w switch Lighting Point : wired from nearest lighting point (sharing same switch)
(up to 4 metres route length). 6A 1-way lighting point. Fan Point : wired from nearest switch c/w 1.5 mm
2 PVC cable (up to 10
metres route length). Ceiling fan point c/w 6A switch. Extractor fan point c/w 6A switch. Cost excludes hard-wood frame and opening for fan. 13A 3-pin : Switched Socket Outlets :
13A 3 – pin switched socket point in ring circuit : 1 – gang (up to 10 metres route length). 13A 3 – pin switched socket point in ring circuit : 2 – gang (up to 10 metres route length). 15A 3 – pin switched socket point (up to 15 metres route length). . Isolator and Water Heater Points : (up to 15 metres route length).
Water heater point c/w 20A double pole switch with neon light indicator (4 mm
2 PVC cable).
20A single phase isolator point c/w 4 mm
2 PVC cable.
30A single phase isolator point c/w 6 mm
2 PVC cable.
20A TPN isolator point c/w 4 mm
2 PVC cable.
30A TPN isolator point c/w 6 mm
2 PVC cable.
TV / Telephone Point : (up to 15 metres route length).
1 – pair c/w socket and 2 x 0.63 mm
2 cable.
2 – pairs c/w socket and 4 x 0.63 mm
2 cable.
TV antennae point c/w 5c / 2v cable and TV socket. Miscellaneous Wiring Point : (up to 15 metres route length).
Single phase power supply to fire alarm control panel c/w 16A mcb and 2.5 mm
2 PVC cable
Lighting point for “Emergency Lighting” or “Keluar Light” c/w 1.5 mm
2 PVC
cable
per point
per point
per point
per fan point
per fan point
per 1-gang socket
outlet point
per 2-gang socket outlet point
per point
per point
per isolator point
per isolator point
per isolator point
per isolator point
per point
per point
per point
per point
per point
130.00
150.00
50.00
95.00
95.00
130.00
175.00
219.00
249.00
289.00
399.00
419.00
569.00
90.00
110.00
90.00
215.00
90.00
A GENERAL WIRING
SOR ELECTRICAL INSTALLATION WORKS 2020/Page 6 of 15
Item No.
Description Unit Rate (RM)
(A5)
29
(a)
(b)
(c)
30
(a)
31
(a)
(b)
32
(a)
(b)
(c)
33
(a)
(b)
(c)
(d)
(e)
34
(a)
(b)
uPVC Surface conduit wiring c/w plastic moulded switch and socket plates and accessories : Wiring shall be run surface in High Impact /
uPVC conduits and complete with PVC conduit boxes together with all necessary PVC lighting switch plates, switched socket plates, isolator and accessories. Wiring shall be 1.5 mm
2 PVC for fan and lighting points, 2.5
mm2 PVC for 13A and 15A switched sockets. Lighting & Fan Points shall
be terminated to ceiling rose. Accepted brands – Clipsal, PDL, MEM & JMAL approved brands. Lighting Point : wired from nearest switch c/w 1.5 mm
2 PVC cable
(up to 20 metres route length). 6A 1-way lighting point c/w switch. 6A 2-way lighting point c/w switch. 6A immediate lighting point c/w switch. Lighting Point : wired from nearest lighting point (sharing same switch)
(up to 4 metres route length). 6A 1-way lighting point. Fan Point: wired from nearest switch c/w 1.5 mm
2 PVC cable (up to 10
metres route length). Ceiling fan point c/w 6A switch. Extractor fan point c/w 6A switch. Cost excludes hard-wood frame and opening for fan. 13A 3-pin : Switched Socket Outlets :
13A 3-pin switched socket point in ring circuit : 1 – gang (up to 10 metres route length). 13A 3-pin switched socket point in ring circuit : 2 – gang (up to 10 metres route length). 15A 3-pin switched socket point (up to 15 metres route length). Isolator and Water Heater Points : (up to 15 metres route length).
Water heater point c/w 20A double pole switch with neon light indicator (4 mm
2 PVC cable).
20A single phase isolator point c/w 4 mm
2 PVC cable.
30A single phase isolator point c/w 6 mm
2 PVC cable.
20A TPN isolator point c/w 4 mm
2 PVC cable.
30A TPN isolator point c/w 6 mm
2 PVC cable.
TV/Telephone Point :(up to 15 metres route length).
1 – pair c/w socket and 2 x 0.63mm2
cable. 2 – pairs c/w socket and 4 x 0.63mm
2 cable.
per point
per point
per point
per point
per fan point
per fan point
per 1-gang socket
outlet point
per 2-gang socket outlet point
per point
per point
per isolator point
per isolator point
per isolator point
per isolator point
per point
per point
85.00
117.00
135.00
45.00
85.00
85.00
117.00
157.00
198.00
224.00
260.00
359.00
377.00
512.00
81.00
99.00
A GENERAL WIRING
SOR ELECTRICAL INSTALLATION WORKS 2020/Page 7 of 15
Item No.
Description Unit Rate (RM)
34
(c)
35
(a)
(b)
(A6)
36
(a)
(b)
(c)
37
(a)
38
(a)
(b)
39
(a)
(b)
(c)
40
(a)
(b)
TV/Telephone Point : (up to 15 metres route length). (Cont’d)
TV antennae point c/w 5c / 2v cable and TV socket. Miscellaneous Wiring Point : (up to 15 metres route length).
Single phase power supply to fire alarm control panel c/w 16A mcb and 2.5 mm
2 PVC cable.
Lighting point for “Emergency Lighting” or “Keluar Light” c/w 1.5 mm
2 PVC
cable. Surface Wiring : Wiring shall be run surface on batten wood complete with
all necessary PVC moulded conduit boxes, lighting switch plates, 13A or 15A switched socket plates and accessories. Wiring shall be 1.5 mm
2
PVC/PVC for fan and lighting points, 2.5 mm2 PVC/PVC for 13A and 15A
switched sockets. 13A 3-pin switched socket points shall be wired in ring circuit/s. Lighting & Fan Points shall be terminated to ceiling rose. Accepted brands – Clipsal, PDL, MEM & JMAL approved brands. Lighting Point : wired from nearest switch c/w 1.5 mm
2 PVC/PVC cable
(up to 20 metres route length). 6A 1-way lighting point c/w switch. 6A 2-way lighting point c/w switch. 6A immediate lighting point c/w switch. Lighting Point : wired from nearest lighting point (sharing same switch)
(up to 4 metres route length). 6A 1-way lighting point. Fan Point: wired from nearest switch c/w 1.5 mm
2 PVC/PVC cable
(up to 10 metres route length). Ceiling fan point c/w 6A switch. Extractor fan point c/w 6A switch. Cost excludes hard-wood frame and opening for fan. 13A 3-pin : Switched Socket Outlets :
13A 3-pin switched socket point in ring circuit : 1 – gang (up to 10 metres route length). 13A 3-pin switched socket point in ring circuit : 2 – gang (up to 10 metres route length). 15A 3-pin switched socket point (up to 15 metres route length). Isolator and Water Heater Points : (up to 15 metres route length).
Water heater point c/w 20A double pole switch with neon light indicator (4 mm
2 PVC/PVC cable).
20A single phase isolator point c/w 4 mm
2 PVC/PVC cable.
per point
per point
per point
per point
per point
per point
per point
per fan point
per fan point
per 1-gang socket
outlet point
per 2-gang socket outlet point
per point
per point
per isolator point
81.00
193.00
81.00
81.00
111.00
128.00
43.00
81.00
81.00
111.00
149.00
188.00
213.00
247.00
A GENERAL WIRING
SOR ELECTRICAL INSTALLATION WORKS 2020/Page 8 of 15
Item No.
Description Unit Rate (RM)
40
(c)
(d)
(e)
41
(a)
(b)
(c)
42
(a)
(b)
(A7)
43
(a)
(b)
(c)
(d)
44
(a)
(b)
Isolator and Water Heater Points : (up to 15 metres route length).
(Cont’d) 30A single phase isolator point c/w 6 mm
2 PVC/PVC cable.
20A TPN isolator point c/w 4 mm
2 PVC/PVC cable.
30A TPN isolator point c/w 6 mm
2 PVC/PVC cable.
TV / Telephone Point : (up to 15 metres route length).
1 – pair c/w socket and 2 x 0.63 mm
2 cable.
2 – pairs c/w socket and 4 x 0.63 mm
2 cable.
TV antennae point c/w 5c / 2v cable and TV socket. Miscellaneous Wiring Point : (up to 15 metres route length).
Single phase power supply to fire alarm control panel c/w 16A mcb and 2.5 mm
2 PVC/PVC cable.
Lighting point for “Emergency Lighting” or “Keluar Light” c/w 1.5 mm
2
PVC/PVC cable. Others Wiring. Main and Sub-mains Wiring : from SESCO supply intake to distribution
boards / consumer units, through meter and cut-outs, using surface wiring. 1-phase 2 x 16 mm
2 1-core PVC insulated and sheathed cables.
1-phase 2 x 25 mm
2 1-core PVC insulated and sheathed cables.
3-phase 4 x 16 mm
2 1-core PVC insulated and sheathed cables.
3-phase 4 x 25 mm
2 1-core PVC insulated and sheathed cables.
Earthing Leads: from distribution board to earth electrode-green PVC
insulated copper cable protected by Class ‘B’ galvanised steel conduits to be installed below surface of hard-standing, cement floor, corridor, apron, etc. (up to 10 metres route length). 16 mm
2 PVC insulated.
25 mm
2 PVC insulated.
per isolator point
per isolator point
per isolator point
per point
per point
per point
per point
per point
per meter
per meter
per meter
per meter
per lot
per lot
341.00
358.00
486.00
77.00
94.00
77.00
183.00
77.00
34.00
45.00
56.00
79.00
281.00
359.00
B LIGHTING FITTINGS, FANS AND ACCESSORIES
SOR ELECTRICAL INSTALLATION WORKS 2020/Page 9 of 15
Item No.
Description Unit Rate (RM)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Accessories : Cost for extractor fan hole openings in brick or wooden
walls shall include cost of making the hole together with 2” x 4” hardwood frame. Size of opening shall be appropriate for the diameter of fans indicated. Installation of fan hook from cement floor slab. Installation of fan hook from timber floor joist. Extractor fan hole opening in brick wall for extractor fan of diameter from 400mm to 500mm (16” to 20”). Extractor fan hole opening in brick wall for extractor fan of diameter from 200mm to 350mm (8” to 14”). Extractor fan hole opening in wooden wall for extractor fan of diameter from 400mm to 500mm (16” to 20”). Extractor fan hole opening in wooden wall for extractor fan of diameter from 200mm to 350mm (8” to 14”). Extractor fan hole opening in glass panel for extractor fan of diameter from 200mm to 350mm (8” to 14”). Fans : Cost includes supply and installation of fittings. Ceiling fans and
oscillating fans shall have individual 3-speed (low/medium/high) regulators. Wall fans shall feature pull cord oscillation control and 3-speed (low/medium/high) regulators. Ceiling fans shall have safety steel suspension wire and safe power disconnection feature. Cost of making fan hole opening is priced separately. Accepted brands – Khind, National, KDK, Sanyo & JMAL approved brands.
Ceiling fan 1,520 mm (60”) diameter sweep. Ceiling mount oscillating fan – 500 mm (20”) dia. Ceiling mount oscillating fan – 400 mm (16”) dia. Wall mount fan – 500 mm (20”) diameter. Wall mount fan – 400 mm (16”) diameter. Extractor fan – 500 mm (20”) diameter. Extractor fan – 400 mm (16”) diameter. Extractor fan – 350 mm (14”) diameter. Extractor fan – 300 mm (12”) diameter. Extractor fan – 200 mm (8”) diameter.
per unit
per unit
per no.
per no.
per no.
per no.
per no.
per unit
per unit
per unit
per unit
per unit
per unit
per unit
per unit
per unit
per unit
36.00
29.00
219.00
180.00
148.00
129.00
165.00
183.00
365.00
292.00
292.00
258.00
292.00
247.00
213.00
191.00
165.00
B LIGHTING FITTINGS, FANS AND ACCESSORIES
SOR ELECTRICAL INSTALLATION WORKS 2020/Page 10 of 15
Item No.
Description Unit Rate (RM)
18
(a)
(b)
(c)
(d)
(e)
(f)
(g)
19
(a)
(b)
(c)
(d)
(e)
(f)
20
(a)
(b)
(c)
21
(a)
(b)
(c)
Fluorescent Fittings : All fluorescent fittings shall be complete with low
loss polyester resin impregnated ballast of loss not exceeding 6.5 watts, power factor correction capacitor to correct to power factor of not less than 0.85, starter, fluorescent tubes and holders. Cost includes supply and installation. Acceptable brands – LHL, Britelite, Davis, Jetlite, National, GEC, Philip, Thorn & JMAL approved brands. (T8 Fluorescent) Channel Fluorescent Fitting – 1 x 18W / 36 W Surface Mount.
1 x 18 watt bare channel fluorescent fitting. 1 x 18 watt channel fluorescent fitting c/w wire guard. 1 x 36 watt bare channel fluorescent fitting. 1 x 36 watt bare channel fluorescent fitting c/w metal angle reflector. 1 x 36 watt bare channel fluorescent fitting c/w suspension rod. 1 x 36 watt channel fluorescent fitting c/w wire guard. 1 x 36 watt channel fluorescent fitting c/w wire guard and suspension rod. Channel Fluorescent Fitting – 2 x 36 W Surface Mount.
2 x 36 watt bare channel fluorescent fitting. 2 x 36 watt channel fluorescent fitting c/w suspension rod. 2 x 36 watt bare channel fluorescent fitting c/w diakon diffuser. 2 x 36 watt bare channel fluorescent fitting c/w diakon diffuser and suspension rod. 2 x 36 watt bare channel fluorescent fitting c/w metal trough reflectors. 2 x 36 watt channel fluorescent fitting c/w metal trough reflectors and suspension rod. Modular Type Fluorescent Fittings – Recessed Fittings.
2 x 18 watt modular recessed (2’ x 2’) fluorescent fitting c/w aluminium parabolic reflector and baffles. 2 x 36 watt modular recessed (2’ x 4’) fluorescent fitting c/w aluminium parabolic reflector and baffles. 3 x 36 watt modular recessed (2’ x 4’) fluorescent fitting c/w aluminium parabolic reflector and louvers. Modular Type Fluorescent Fittings – Surface Fittings.
2 x 18 watt modular recessed (2’ x 2’) fluorescent fitting c/w aluminium parabolic reflector and baffles. 2 x 36 watt modular recessed (2’ x 4’) fluorescent fitting c/w aluminium parabolic reflector and baffles. 3 x 36 watt modular recessed (2’ x 4’) fluorescent fitting c/w aluminium parabolic reflector and louvers.
per unit
per unit
per unit
per unit
per unit
per unit
per unit
per unit
per unit
per unit
per unit
per unit
per unit
per unit
per unit
per unit
per unit
per unit
per unit
35.00
64.00
41.00
76.00
82.00
71.00
101.00
71.00
94.00
106.00
129.00
100.00
135.00
165.00
200.00
242.00
165.00
200.00
229.00
B LIGHTING FITTINGS, FANS AND ACCESSORIES
SOR ELECTRICAL INSTALLATION WORKS 2020/Page 11 of 15
Item No.
Description Unit Rate (RM)
22
(a)
(b)
(c)
(d)
23
(a)
(b)
(c)
(d)
24
(a)
(b)
(c)
(d)
25
(a)
(b)
(c)
(d)
(e)
Self-contained Modular Type Fluorescent Fittings c/w Battery & Charger.
2 x 18 watt modular recessed (2’ x 2’) fluorescent fitting c/w aluminium parabolic reflector and baffles, 3-hr maintenance free sealed lead-acid battery, charger and control unit. 2 x 36 watt modular recessed (2’ x 4’) fluorescent fitting c/w aluminium parabolic reflector and baffles, 3-hr maintenance free sealed lead-acid battery, charger and control unit. 2 x 18 watt modular surface (2’ x 2’) fluorescent fitting c/w aluminium parabolic reflector and baffles, 3-hr maintenance free sealed lead-acid battery, charger and control unit. 2 x 18 watt modular recessed (2’ x 4’) fluorescent fitting c/w aluminium parabolic reflector and baffles, 3-hr maintenance free sealed lead-acid battery, charger and control unit. Fluorescent Fittings : All fluorescent fittings shall be complete with low
loss polyester resin impregnated ballast of loss not exceeding 6.5 watts, power factor correction capacitor to correct to power factor of not less than 0.85, starter, fluorescent tubes and holders. Cost includes supply and installation. Acceptable brands – LHL, Philip & JMAL approved brands. (T5 Fluorescent) Channel Fluorescent Fitting – 14W / 28W Surface Mount.
1 x 14 watt.
2 x 14 watt. 1 x 28 watt. 2 x 28 watt. Channel Fluorescent Fitting – 14W / 28W Surface Mount c/w Metal Trough Reflector.
1 x 14 watt.
2 x 14 watt. 1 x 28 watt. 2 x 28 watt. Modular Type Fluorescent Fitting c/w Aluminium Parabolic Reflector and Baffles.
2 x 14 watt (modular : 600mm x 600mm). 3 x 14 watt (modular : 600mm x 600mm). 4 x 14 watt (modular : 600mm x 600mm). 2 x 28 watt (modular : 300mm x 1200mm). 2 x 28 watt (modular : 600mm x 1200mm).
per unit
per unit
per unit
per unit
per unit
per unit
per unit
per unit
per unit
per unit
per unit
per unit
per unit
per unit
per unit
per unit
per unit
343.00
425.00
342.00
425.00
65.00
85.00
82.00
108.00
85.00
120.00
95.00
135.00
200.00
266.00
294.00
228.00
244.00
B LIGHTING FITTINGS, FANS AND ACCESSORIES
SOR ELECTRICAL INSTALLATION WORKS 2020/Page 12 of 15
Item No.
Description Unit Rate (RM)
25
(f)
(g)
26
(a)
(b)
(c)
(d)
(e)
(f)
(g)
(h)
(i)
27
(a)
28
(a)
(b)
(c)
(d)
(e)
Modular Type Fluorescent Fitting c/w Aluminium Parabolic Reflector and Baffles. (Cont’d)
3 x 28 watt (modular : 600mm x 1200mm) 4 x 28 watt (modular : 600mm x 1200mm) Miscellaneous Lighting Fittings : Cost includes supply and installation of
fittings. Installation for floodlight fittings is in reference to standard installation on walls accessible by ladder. Accepted brands – for flood lights (Nikkon, Thorn, Philips & JMAL approved brands) & for others (JMAL approved brands). Emergency Light / KELUAR Sign Fittings : self contained c/w sealed 3-
hr maintenance free sealed lead-acid battery, charger and control unit c/w trickle charging & over-charge protection. Self contained 2 x 8 watts emergency lighting fitting. ‘KELUAR’ sign – fluorescent type, single sided.
‘KELUAR’ sign – fluorescent type, double sided. ‘KELUAR’ c/w direction signage – single sided fluorescent type. ‘KELUAR’ c/w direction signage – double sided fluorescent type. ‘KELUAR’ sign – LED type, single sided. ‘KELUAR’ sign – LED type, double sided.
‘KELUAR’ c/w direction signage – single sided LED type.
‘KELUAR’ c/w direction signage – double sided LED type. Lamp-Shade c/w Incandescent Lamp.
Coolicon lamp shade, lamp holder c/w 40W, 60W or 100W incandescent lamp. Flood-Light / Spot-Light Fittings.
Outdoor type spot lighting c/w metal lamp holder and PAR 38 150W lamp of various colours. Outdoor type metal halide floodlight fittings c/w 400W lamp, control gear and power factor correction capacitor. Outdoor type metal halide floodlight fittings c/w 250W lamp, control gear and power factor correction capacitor Outdoor type high pressure sodium floodlight fittings c/w 400W lamp, control gear and power factor correction capacitor. Outdoor type high pressure sodium floodlight fittings c/w 250W lamp, control gear and power factor correction capacitor.
per unit
per unit
per unit
per unit
per unit
per unit
per unit
per unit
per unit
per unit
per unit
per unit
per unit
per unit
per unit
per unit
per unit
324.00
358.00
129.00
189.00
234.00
194.00
247.00
194.00
206.00
212.00
225.00
18.00
71.00
543.00
472.00
566.00
483.00
B LIGHTING FITTINGS, FANS AND ACCESSORIES
SOR ELECTRICAL INSTALLATION WORKS 2020/Page 13 of 15
Item
No. Description Unit Rate (RM)
29
(a)
(b)
30
(a)
(b)
(c)
(d)
31
(a)
(b)
(c)
(d)
(e)
(f)
(g)
(h)
(i)
32
(a)
(b)
(c)
(d)
(e)
(f)
Bulkhead Fittings.
Bulkhead fitting – pressure die-cast aluminium alloy type c/w 40W, 60W or
100W incandescent lamp, glass cover and wire guard.
Bulkhead fitting – plastic die-cast type c/w 40W, 60W or 100W
incandescent lamp, plastic cover and wire guard.
LED Lighting Fittings : Cost includes supply and installation of fittings.
Installation for LED light fittings is in reference to standard installation on
walls/ceilings complete with strong bracket/metal wire/support and
accessible by ladder. Accepted brands – for LED lights (Nikkon, Thorn,
Philips, Osram, SAG, Davis, Panasonic).
LED Bulb.
LED Bulb 7W, min. (8000 hours, 3000 K)
LED Bulb 11W, min. (8000 hours, 3000 K)
LED Bulb 13W, min. (8000 hours, 3000 K)
LED Bulb 15W, min. (8000 hours, 3000 K)
LED Downlight.
LED Downlight : 6W, min. (3000 K, 600 lm)
LED Downlight : 9W, min. (3000 K, 800 lm)
LED Downlight : 10W, min. (3000 K, 800 lm)
LED Downlight : 13W, min. (3000 K, 1000 lm)
LED Downlight : 15W, min. (3000 K, 1000 lm)
LED Downlight : 18W, min. (3000 K, 1500 lm)
LED Downlight : 25W, min. (3000 K, 2500 lm)
LED Downlight : 30W, min. (3000 K, 3000 lm)
LED Downlight : 35W, min. (3000 K, 3200 lm)
LED Floodlight.
LED Floodlight : 30W, min. (3000 K, 2000 lm), IP65
LED Floodlight : 50W, min. (3000 K, 4000 lm), IP65
LED Floodlight : 70W, min. (3000 K, 5000 lm), IP65
LED Floodlight : 100W, min. (3000 K, 7000 lm), IP65
LED Floodlight : 150W, min. (3000 K, 11000 lm), IP65
LED Floodlight : 200W, min. (3000 K, 15000 lm), IP65
per unit
per unit
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
94.00
47.00
10.00
14.00
16.00
19.00
131.00
142.00
145.00
158.00
166.00
173.00
191.00
250.00
285.00
63.00
95.00
136.00
311.00
388.00
569.00
C DISTRIBUTION BOARDS & CONSUMER UNITS
SOR ELECTRICAL INSTALLATION WORKS 2020/Page 14 of 15
Item No.
Description Unit Rate (RM)
1
(a)
(b)
(c)
(d)
(e)
(f)
2
(a)
(b)
(c)
(d)
(e)
(f)
3
(a)
(b)
(c)
(d)
(e)
(f)
4
(a)
(b)
Distribution Boards & Consumer Units : Distribution boards and
consumer units shall be metal clad type c/w isolator, Type-A - residual current circuit breaker (RCCB) and assortment of miniature circuit breakers (MCB). Isolators and RCCB shall be double pole and four pole respectively for single phase and three phase units. Isolators shall be rated at 60A min. Miniature circuit breakers shall be single pole 6A, 15A or 32A as required, of minimum breaking capacity 5 kA, and tripping curve Type B. Comb-type busbars are not accepted. Units shall feature DIN rail mounting for plug-in, wired-out MCB. Accepted brands – MEM, Hager, L&T, LKH & JMAL approved brands. Single Phase Consumer Units / Distribution Boards.
4 – way (Type A - RCCB : 40A, 30 mA sensitivity). 4 – way (Type A - RCCB : 60A, 30 mA sensitivity). 6 – way (Type A - RCCB : 40A, 30 mA sensitivity). 6 – way (Type A - RCCB : 60A, 30 mA sensitivity). 8 – way (Type A - RCCB : 40A, 30 mA sensitivity). 8 – way (Type A - RCCB : 60A, 30 mA sensitivity). Single Phase Consumer Units / Distribution Boards.
4 – way (Type A - RCCB : 40A, 100 mA sensitivity). 4 – way (Type A - RCCB : 60A, 100 mA sensitivity). 6 – way (Type A - RCCB : 40A, 100 mA sensitivity). 6 – way (Type A - RCCB : 60A, 100 mA sensitivity). 8 – way (Type A - RCCB : 40A, 100 mA sensitivity). 8 – way (Type A - RCCB : 60A, 100 mA sensitivity). Three Phase Distribution Boards.
4 – way (Type A - RCCB : 40A, 30 mA sensitivity). 4 – way (Type A - RCCB : 60A, 30 mA sensitivity). 6 – way (Type A - RCCB : 40A, 30 mA sensitivity). 6 – way (Type A - RCCB : 60A, 30 mA sensitivity). 8 – way (Type A - RCCB : 40A, 30 mA sensitivity). 8 – way (Type A - RCCB : 60A, 30 mA sensitivity). Three Phase Distribution Boards.
4 – way (Type A - RCCB : 40A, 100 mA sensitivity). 4 – way (Type A - RCCB : 60A, 100 mA sensitivity).
per set
per set
per set
per set
per set
per set
per set
per set
per set
per set
per set
per set
per set
per set
per set
per set
per set
per set
per set
per set
370.00
425.00
460.00
515.00
535.00
595.00
315.00
370.00
405.00
461.00
480.00
540.00
1,125.00
1,185.00
1,230.00
1,265.00
1,425.00
1,560.00
1,070.00
1,130.00
C DISTRIBUTION BOARDS & CONSUMER UNITS
SOR ELECTRICAL INSTALLATION WORKS 2020/Page 15 of 15
Item No.
Description Unit Rate (RM)
4
(c)
(d)
(e)
(f)
Three Phase Distribution Boards. (Cont’d)
6 – way (Type A - RCCB : 40A, 100 mA sensitivity). 6 – way (Type A - RCCB : 60A, 100 mA sensitivity). 8 – way (Type A - RCCB : 40A, 100 mA sensitivity). 8 – way (Type A - RCCB : 60A, 100 mA sensitivity).
per set
per set
per set
per set
1,175.00
1,210.00
1,370.00
1,505.00