schedule of quantities for hvac works for state bank …€¦ · insulation 80 rmt 3.0 drain piping...
TRANSCRIPT
a
b
c
d
SR.
NO.DESCRIPTION OF WORKS QTY UNIT
A
VRF / VRV SYSTEM (Makes : Mitsubishi Elect.
Daikin,Samsung,Toshiba,Mitsubishi Heavy, Hitachi,Blue star,
Voltas,Carrier )
1.0 Supply of Out Door Units suitable for VRF / VRV System
Supply, Installation, Testing and Commissioning of Variable
refrigerant volume modular type airconditioning system,suitable for
cooling by using inverter Driven compressors complete with indoor
and outdoor units with individual controller and with fittings etc., as
per quantity given below i/c full charging of R410A refrigerant gas
Price of outdoor unit shall be inclusive of refrigerant charge for entire
system
Outdoor units suitable for following capacities:
1.1 46 HP VRF ODU(At Second floor Level) 1 Nos.
2.1Ceiling mounted Type Indoor Units , unit shall be complete with
wireless remote controller
2.1.1 8.0 TR (Open Area) 4 Nos.
2.2Ceiling concealed Type Indoor Units , unit shall be complete with
wireless remote controller
2.2.1 1.0 TR (Credenza) 1 Nos.
2.34 way Standard - (3X 3) Cassette Type Indoor Units , unit shall be
complete with wireless remote controller
2.3.1 1.5 TR (AGM Room) 1 Nos.
2.3.2 2.5 TR (AGM Room) 1 Nos.
2.3.3 2.5 TR (Pantry & Canteen Room) 1 Nos.
2.3.4 3TR (Conference Room) 2 Nos.
SCHEDULE OF QUANTITIES FOR HVAC WORKS FOR STATE BANK OF
Prices offered for VRF equipments shall be based on CIF-Site basis. The break up pricing
Designing, engineering, fabricating and supplying, unloading, shifting, lifting of the following
Indoor units comprising of combination of Cassette, Hi-Wall, Ductable Units, (Hi-wall units
Electrical power supply – Single / 3-phase near each of the IDUs (Indoor Units) and 3-phase
Controls – remote, indoors, inside the occupied area, System should be BMS compatible
2.3.5 2.5 TR (Lounge Room) 2 Nos.
3.0 VRV Ref net Joints
3.1 Multi Kits / Ref Joints 11 Nos.
3.2 Remote controllers(Wired) 4 Nos.
Remote controllers(Wireless) 8 Nos.
4.0 DX AC units for server room
4.1 1 TR hi wall split 3 Star 2 Nos.
5.0Inline centrifugal fans with necessary supports, canvas
connections and other accessory.
Inline cabinate Ex fan
5.1 2200 cfm 40 mm static for toilet CDIF 20 FFA, single phase 1 No.
TOTAL FOR 'A' - VRF / VRV SYSTEM (Including Taxes)
GST Taxes @ 28%
TOTAL FOR 'A' - VRF / VRV SYSTEM (Including Taxes)
Installation and Commissioning of VRF/ VRV system
B VRV / VRF SYSTEM (LOCAL ITEMS)
1.0 Installation of AC units
1.1
Transportation, lifting,shifting, rigging, vibration isolators, supports,
Gas charging , etc complete arrangment for commissioning of Outdoor
units (48 HP) with all required accessories.
1 no
1.3Ceiling mounted Type Indoor Units , unit shall be complete with
wireless remote controller
1.3.1 8.0 TR (Open Area) 4 Nos.
1.44 way Standard - (3X 3) Cassette Type Indoor Units , unit shall be
complete with wireless remote controller
1.4.1 1.0 TR (AGM Room) 1 Nos.
1.4.2 1.6 TR (AGM Room) 1 Nos.
1.4.3 2.5 TR (Pantry & Canteen Room) 1 Nos.
1.4.4 3 TR (Conference Room) 2 Nos.
1.4.5 2.5 TR (Lounge Room) 2 Nos.
1.5 VRV Ref net Joints
1.5.1 Multi Kits / Ref Joints 11 Nos.
1.6 DX AC units for server room
16.1 1 TR hi wall split 2 Nos.
1.7 Timer for operating Split units
1.7.1. Timer for operating Split units 2 Nos.
1.8Inline Ceiling fans with necessary supports, canvas connections
and other accessory.
Inline ceiling suspended Ex fans
1.8.1 2200 cfm 40mm static for toilet CDIF 20 FFA single phase 1 No.
1.9
Condensing unit stands , Supply and installation of floor standing
condensing units stand on roof level to install the condensing units 300
mm above roof finish floor. Condensing units stand should be
manufactured out of heavy gauge MS channnel frame work and
painted with one coat of red oxide and two coat of black paint
3 NO
Table type Condensing unit stands for hiwall splits 2 NO
2.0 Refrigerant piping
All refrigerant piping between indoor & outdoor units duly insulated
and covered with Al. foil as per specifications. All expose piping
outside the room shall on GI Perforated cable tray / MS Ladder type &
exposed piping shall be properly supported in GI Perforated cable tray.
Pipe line must be tested for requisite pressure & must be supported.
All refrigerant piping to be insulated with 19 mm thick class "O"
armaflex nitrile rubber with UV protection as per manufacturer
Length of refrigerent line mentioned in the BOQ is inclusive of
liquid and gas line together. ie 1 m of ref pipe inclusive of 1 m of
liquid line + 1 m of gas line including insulation on each line.
2.1 Hard /Soft Pipe with insulation – 19 mm thick 180 RMT
2.1.2Hiwall unit refrigerant piping with 9mmm thick class O tube
insulation80 RMT
3.0 Drain piping
Drain piping in hard PVC with all fittings, supports and clamps upto
50 mm dia. including drilling hole in wall chipping wall etc to conceal
and to route the drain pipe. The piping shall be suitably insulated with
13 mm thk Closed Cell insulation / 60 kg/m3 density stuck with
approved adhesive compound.
3.1 PVC piping 32 mm to 50 mm Dia 110 RMT
4.0 Power & Control cabling:
Supply and installation of AHU starter panel complete with incomer,
star delta starter suitable for 20 HP AHU, Starter shall be complete
with Ammitor, voltmeter, Incoming , outgoing and start/stop and trip
indicating lamps. For on/off/remote and local operation, 3 pole single
throw switch shall be provided in each AHU panel to facilitate
override of the automatic operation.All starters shall be provided with
suitable potential free contract for connections to the Building
Automation System.3 Nos of Single Pole MCB's Shall be provided at
the incoming section of the starter panel for DDC Panel , fire damper
actuator & as a spare.220 / 24 V Transformer
For on/off/remote and local operation, 3 pole single throw switch shall
be provided in each AHU panel to facilitate override of the automatic
operation.
4.1 Power cabling as per manufacturers requirement 30 RMT
Electrical contractor shall terminate power in individual switch
socket for each IDU as per requirement. For VRF ODU incoming
power shall be provided at the PDB, from there to each VRF ODU
the cabling shall be carried out by HVAC contractor.
4.2
Power and Control cabling with copper conductor cable with end
termination for Indoor units with Plug Top, Earthing connection, etc.
with FRST PVC conduit ( minimum cable size 2C X 1.5 mm2), OEM
to certify and if cable size certified by OME is higher than the
specified one, same to be considered by the vendor
300 RMT
5 AIR DISTRIBUTION:
5.1 SHEET METAL DUCTING - FACTORY FABRICATED
Rectangular / Circular Ducting in Galvanised Steel
Supply,Fabrication, Installation, Testing & Commissioning of
following gauges of Galvanised Iron ( GI ) Sheet complete with
splitters, supports, dampers, and turning vanes. (Approved Makes:
Jindal, SAIL, TATA, Equivalent) 180 GSM sheet. GI duct fabrication
shall follow SMACNA Standards
a 0.63 mm (24 SWG) GSS ducting 340 Sq.M.
b 0.80 mm (22 SWG) GSS ducting 15 Sq.M.
6.0 ACCESSORIES
6.1 Volume Control Dampers
Supply, installation and adjusting of GSS Volume Control Damper
complete with Manual quadrant control with position indicator to be
provided to enable adjust volume of air as required.in 18 G complete
as per specifications.
4.8 Sq.M.
Al powder coated black opposed blade dampers 10 Sq.M.
6.2 GRILLES
Supply, fabrication, assembling and installation of linear aluminium
powder coated grilles as indicated in the drawings and as per
specifications.
(color to match as per architects requirements)
6.2.1 100/150 mm wide 20 Sq.M.
6.3 DIFFUSERS
Supply, fabrication, assembling and installation of Square Diffusers as
indicated in the drawings and as per specifications.
(color to match as per architects requirements)
6.3.1 SA Diffuser with collar damper - 225 x 225 18 Nos
6.3.2 SA Diffuser with collar damper - 300 x 300 3 Nos
6.3.3 RA Diffuser - 250 x 250 21 Nos
6.3.4 RA Diffuser - 300 x 300 RO Nos
6.3.5 RA Diffuser - 225 x 225 RO Nos
6.4 Fresh Air / exhaust louvers
Fresh /exhaust air louvers shall be AL powder coated complete with
bird screen3 Sq.M.
6.5 Double Canvass Connection
Supply, fabrication & installation of double canvass (fire retardant)
flexible connection as per drawings & specifications.4 SETS
6.6 INSULATION
6.6.1 Thermal Insulation of Ducts
Supply, fabrication & Installation of thermal insulation on GI ducts
complete with Closed Cell Foam(Nitral Rubber) with minimum
density of 40 Kg/m3 with minimum R Value 4.1/inch & thermal
conductivity -0.035 w/mok confirming to Class 'O' & the inner side
stuck to the outer facia of the GI ducts with recommended /
Proprietory Synthetic adhesive bonding (SR998 or equivalent) &
installed as per manufacturers recommendation. The insulation joints
shall be sealed with 3" wide Black Tape.
9 mm thick Insulation 441 Sq.M.
6.7 Acoustic Lining of Ducts
Supply, fabrication and installation of acoustic lining of supply and
return air ducts as specified and shown on the drawing complete with
50 mm thick 48Kg/m3 density Fiberglass insulation covered with RP
tissue and AL perforated sheets
76 Sq.M.
TOTAL FOR B' Installation Work (Without Taxes)
GST 18%
TOTAL INSTALLATION "B 'With taxes
CANNUAL MAINTANANCE CONTRACT FOR 5YEARS AFTER DEFECT LAIBILITY PERIOD OF ONE YEAR
1 ANNUAL MAINTANANCE CONTRACT FIRST YEAR
1.2 ANNUAL MAINTANANCE CONTRACT SECOND YEAR
1.3 ANNUAL MAINTANANCE CONTRACT THIRD YEAR
1.4 ANNUAL MAINTANANCE CONTRACT FOURTH YEAR
1.5 ANNUAL MAINTANANCE CONTRACT FIFTH YEAR
TOTAL FOR C'AMC WORK(Without Taxes)
GST 18%
TOTAL INSTALLATION "C 'With taxes
TOTAL AMOUNT (Rs.)
RATE
(Rs.)
TOTAL
AMOU
NT
(Rs.)
SCHEDULE OF QUANTITIES FOR HVAC WORKS FOR STATE BANK OF
TOTAL INSTALLATION "B 'With taxes
ANNUAL MAINTANANCE CONTRACT FOR 5YEARS AFTER DEFECT LAIBILITY PERIOD OF ONE YEAR