s.c.b.a. maintenance by: lt. eric miller parksville fire department
TRANSCRIPT
ObjectivesObjectives
Review of SCBA system Review the maintenance of the system and
it’s components Hands on experience checking over and
maintaining an SCBA system Review of the fill station and how it works
Maintenance of the SCBA Maintenance of the SCBA SystemSystem
The five components of the system combine to allow a firefighter to safely operate in a dangerous environment.
Proper maintenance of all parts is required to ensure the system does not fail.
Air CylinderAir Cylinder
Visual inspection of the cylinder, gauge, and valve to check for damage, dents, cracks or other anomalies.
Check the cylinder to ensure it has at least 4000 psi. If below, have the cylinder filled.
Prior to filling, check the hydrostatic test date to ensure within limits. All cylinders we have must be hydrostatically tested every three years.
RegulatorRegulator
Takes the high pressure air of the cylinder, and steps it down to a usable pressure.
1st stage or pressure reducer connected to backpack frame, and is not serviceable by field level technician.
2nd stage mounts to the face piece.
RegulatorRegulator
High pressure and low pressure hoses can be checked for nicks, cuts, or abrasions that could cause failure. Check “O” ring at cylinder connection.
Hose connections can be checked for air leaks.
RegulatorRegulator
Leaking or damaged hoses or “O” rings can be serviced by field level technician
Minor repairs can be done to regulator, ie: replace gaskets, springs, diaphragm
Backpack FrameBackpack Frame
Provides the mounting platform to hold the air cylinder in place, and attachment for pressure reducing and regulator assembly, and remote pressure gauge.
Shoulder and waist straps allow the system to be carried comfortably on the body
Two styles – wire frame model, and solid aluminum frame contoured to wearers back
Backpack FrameBackpack Frame
All straps should be checked for cuts or abrasions that could result in failure
Heavily worn or damaged straps should be replaced
Frame should be inspected for broken welds, and worn or broken mounting hardware
FacepieceFacepiece
Protects the wearer from exposure to heat, toxic gases, and unburned products of combustion
Allows the wearer to see in a smoke filled environment
In conjunction with the regulator, provides a source of fresh air
FacepieceFacepiece
Examine face piece for cracks or scratches that could cause failure, especially around the regulator mount
Check temple and neck straps for excessive wear, or loss of elasticity. If worn, or no stretch in them, have them replaced
FacepieceFacepiece
Check skirt of mask to ensure no cuts or tears that could cause failure
Check nose cup and inhalation check valves
Check voice amplifier for operation
After use, clean by spraying disinfectant on the interior and wait at least 10 minutes before wiping the mask dry
PASS AlarmPASS Alarm
Audible warning device that signals for assistance when a fire fighter goes down or becomes incapacitated.
Should always be activated BEFORE entering an IDLH environment.
Operation should be tested weekly and battery replaced at regular interval.
Field Function Test of Air PackField Function Test of Air Pack
Ensure that the unit is clean – no loose debris, system wiped down to clean off any debris or unburned products of combustion
Turn on air cylinder – ensure pressure at cylinder gauge and remote gauge is equal or fairly close – if big difference tag and take out of service
Listen for activation of low air warning system
Field Function Test of Air PackField Function Test of Air Pack
Attach mask to regulator Place mask on face and inhale to start air
flow, ensuring smooth air flow in system Check purge valve to ensure proper
operation Turn off air cylinder and bleed down system
– listen for activation of low air warning system
Activate donning switch
Field Function Test of Air PackField Function Test of Air Pack
Extend all straps. Check PASS alarm for proper function. Extend straps on face piece. Check voice amplifier for operation. Bag face piece to keep it clean and dust
free. Log inspection in the SCBA log book.
Fill StationFill Station
The fill station is located in the workshop area of the hall.
The actual compressor is located in the back room.
Filling An Air CylinderFilling An Air Cylinder
Turn on compressor. Open main valve on fill station. Allow system
to charge. Adjust Regulator Output Pressure to 4500
psi. Open door to fill station and place bottle in
fragmentation container. Secure bottle with retainer clip then attach whip to bottle. Ensure that bleeder valve is closed.
Filling An Air CylinderFilling An Air Cylinder
Open valve on fill station and slowly fill to 4500 psi.
When all bottles are filled, shut off valves. Open fill station door. Shut off air bottle
valves, and open bleeder valve allowing excess air pressure to drain down.
Remove air bottles, and repeat filling process as required.
Filling An Air CylinderFilling An Air Cylinder
Once all cylinders are filled, shut off compressor.
Drain the system down to ensure all pressure is taken off of springs.
Ensure all filled bottles are entered on the log. Place completed log in SCBA Committee basket in training office for entry into computer.
Fill Station SafetyFill Station Safety
Always wear safety glasses when using the fill station. High pressure air, along with dust or other airborne particles can harm your eyes.
Secure the bottle in the fragmentation container with retainer clips. Should an air bottle fail while being filled, the retainer clips will confine most of the debris within the container.
SummarySummary
The SCBA system contains five components:
Air cylinder Regulator Backpack Facepiece PASS Alarm
SummarySummary
Proper care and maintenance of the system will reduce or eliminate the possibility of failure when being used in a hazardous environment.
Where to Get More InformationWhere to Get More Information