saudi aramco engineering standards-electrical-commissioning

Upload: syedsalmanali91

Post on 09-Feb-2018

430 views

Category:

Documents


24 download

TRANSCRIPT

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    1/61

    Note: The source of the technical material in this volume is the ProfessionalEngineering Development Program (PEDP) of Engineering Services.

    Warning: The material contained in this document was developed for SaudiAramco and is intended for the exclusive use of Saudi Aramcos

    employees. Any material contained in this document which is notalready in the public domain may not be copied, reproduced, sold, given,

    or disclosed to third parties, or otherwise used in whole, or in part,

    without the written permission of the Vice President, Engineering

    Services, Saudi Aramco.

    Chapter : Electrical For additional information on this subject, contact

    File Reference: EEX20304 W.A. Roussel on 874-1320

    Engineering EncyclopediaSaudi Aramco DeskTop Standards

    Directing The Startup AndCommissioning Of Motors

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    2/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards

    CONTENTS PAGE

    Pre-Energization Requirements 1

    Energization Tests 15

    Evaluating the Results of Motor Commissioning for

    Acceptability or Unacceptability 28

    WORK AID

    Work Aid 1: Procedure and Acceptable Values for Evaluatingthe

    Results of Motor Commissioning Compiled fromSADP-P-113, NEMA MG-1, and Established

    Engineering Practices 44

    GLOSSARY 54

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    3/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 1

    PRE-ENERGIZATION REQUIREMENTS

    Pre-energization requirements are the inspections and the tests that must be performed prior to

    the initial application of power to a new motor. The overall purpose of the pre-energization

    requirements is to verify that the motor can be safely energized with no danger to personnel or

    to equipment. The following pre-energization requirements will be discussed in this section:

    _Verification of Electrical Connections/Interlocks

    _Verification of Mechanical Integrity

    _Lubrication System Checks

    _Insulation Resistance (IR) and Polarization Index (PI) Checks

    _Air Gap Check

    _Verification of Protective Relay Setpoints

    _Phase Rotation Test

    Verification of Electrical Connections/Interlocks

    A verification of the electrical connections/interlocks that are associated with a motor is

    performed for the following reasons:

    _To ensure that all of the individual electrical components that are shown on

    the project electrical wiring diagrams and on the project elementary diagrams

    are actually installed.

    _To ensure that the power cable runs and that the power cable terminations are

    in accordance with the project drawings.

    _To ensure that all of the wired connections are accurate (e.g., the wires are

    labeled in accordance with the project drawings, and the wires are terminated at

    the locations that are specified on the project drawings) and are tight.

    _To ensure that electrical continuity, as specified in the project electrical wiring

    diagrams and in the project elementary diagrams, exists between all of the

    wired connections.

    _To ensure that electrical continuity exists across all of the control and the

    interlock contacts when the contacts are manually operated.

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    4/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 2

    Verification of Electrical Connections/Interlocks (Contd)

    The following inspections, checks, and tests must be performed to verify electrical

    connections/interlocks:

    _Visual Inspection

    _Torque Check

    _Resistance Test

    Before the visual inspection can be performed, the most recent revision of the project

    electrical wiring diagrams and the project elementary diagrams must be obtained. These

    diagrams are used to visually verify the following items through comparison of the actual

    installation to the installation that is specified in the drawings:

    _That the specified electrical components actually are installed.

    _That the power cable runs and the power cable terminations are correct._That the wired connections are accurate.

    Torque checks are performed to verify that all of the wired connections (power and control)

    are tight. Torque checks are performed in the following way: an applicable tool (screwdriver,

    torque wrench, barrel nut driver) is placed on the connection hardware and the proper torque

    is subsequently applied to the connection hardware to verify that the connection is tight. Care

    should be taken in the performance of torque checks to ensure that excessive torque is not

    applied to the connection hardware.

    Resistance tests are performed to verify that electrical continuity exists between all of the

    wired connections. Resistance tests also are performed to ensure that electrical continuityexists across all of the control and the interlock contacts when the contacts are manually

    operated. The following major steps are involved in the performance of a resistance test to

    verify that electrical continuity exists between two points in a circuit:

    _A multimeter and copies of the project electrical wiring diagrams and the

    project elementary wiring diagrams must be obtained to perform the tests.

    _The project elementary wiring diagram is used to identify the various points in

    the motor circuit between which electrical continuity should exist. Because the

    continuity between numerous individual points (paths) must be verified, a

    highlighter should be used to mark, on the elementary wiring diagram, thepaths that have been verified.

    _The project electrical wiring diagram is used to identify the physical location

    in the installed equipment that corresponds to the points that are identified on

    the project elementary wiring diagrams.

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    5/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 3

    Verification of Electrical Connections/Interlocks (Contd)

    _The leads of the multimeter are connected to the physical locations in the

    installed equipment that correspond to the first set of points between which

    electrical continuity should exist.

    _The resistance between the points to which the multimeter leads are connected

    is read on the scale of the multimeter. Proper electrical continuity normally is

    indicated by a resistance reading that is less than 1_. If the path between the

    points to which the multimeter leads are connected contains components such

    as relay coils or transformer windings, proper electrical continuity will be

    indicated by a resistance reading that approximately corresponds to the

    resistance of the components that are in the path.

    _The process of connecting of the multimeter leads and measuring resistance isrepeated for the remaining points in the circuit between which electrical

    continuity should exist.

    Verification of Mechanical Integrity

    A verification of the mechanical integrity of a new motor is performed for the following

    reasons:

    _To ensure that there are no damaged parts, loose parts, or missing parts on the

    motor.

    _To ensure that all of the mechanical components of the motor freely operate.

    _To ensure that the general physical condition of the motor is satisfactory for

    operation.

    The verification of mechanical integrity is performed through a combination of visual and

    physical inspections. The visual inspection should include the following items:

    _A verification that all accessory equipment is installed and is properly aligned.

    _A verification that the motor is properly anchored and properly mounted.

    _A verification that there is no water damage or corrosion.

    _A verification that the motor is free from dust and from dirt.

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    6/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 4

    Verification of Mechanical Integrity (Cont'd)

    _A verification that all packing, shipping braces, blocking, shipping tags, or

    other equipment that could impede proper mechanical operation or proper

    electrical operation has been removed.

    _A verification that all screens, guards, and other protective devices are

    properly installed.

    The physical inspection should include the following items:

    _A verification that all mechanical parts that move are operable in accordance

    with the manufacturer's requirements.

    _A verification that the motor shaft freely rotates.

    Lubrication System Checks

    Lubrication system checks are performed to ensure that the motor bearings will be provided

    with proper lubrication upon energization of the motor. The items that are inspected in the

    performance of lubrication system checks are dependent on the type of lubrication system

    with which the motor is equipped. Motors can be equipped with the following types of

    lubrication systems:

    _Self-contained lubrication systems_External lubrication systems

    Most motors are equipped with self-contained lubrication systems. These systems use grease

    or oil to provide the required lubrication to the motor bearings. The lubrication system check

    that is performed on a self-contained lubrication system should consist of a visual inspection

    of the following items:

    _The motor installation records should be reviewed to ensure that the proper

    lubricant (grease or oil) was used to initially lubricate the bearings.

    _As applicable, the bearing cavity or the oil reservoir should be inspected toensure that it contains the proper amount of lubrication. The bearing or the oil

    reservoir also should be inspected to ensure that it does not contain moisture.

    _If the bearings are equipped with dirt seals and/or dirt shields, these devices

    should be inspected to ensure that they are properly installed.

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    7/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 5

    Lubrication System Checks (Cont'd)

    _All of the components such as pipes, plugs, drains, and sightglasses should be

    inspected to ensure that these components are properly installed.

    Large motors can be equipped with external lubrication systems. These systems use an oil

    pump and associated oil pipes to provide the motor bearings with a continuous supply of

    lubrication. External lubrication systems usually contain the following major components:

    _An oil pump that is driven by the motor shaft or one that is driven by a

    separate motor.

    _An oil sump.

    _An oil filter.

    _The associated oil system pipes.

    _Oil system monitoring equipment such as oil flow indicators, oil pressure

    gauges, and oil temperature indicators.

    The lubrication system check that is performed on an external lubrication system should

    consist of the following major steps (if the lubrication system uses an oil pump that is driven

    by the motor shaft, the steps that are marked with an asterisk must be performed during the

    no-load run test):

    _The motor installation records should be reviewed to ensure that the oil sump

    was initially filled with the correct lubricant.

    _The level of oil in the oil sump should be checked to ensure that the level is in

    the normal operational band.

    _An oil sample should be drawn from the oil sump, and the oil sample should

    be checked to ensure that it does not contain water or foreign material.

    _A visual inspection of all of the oil system components should be performedto verify the mechanical integrity of the system.

    _The oil system should be started, and it should be allowed to heat up to the

    normal temperature of operation. While the oil system heat up is in progress,

    all of the components of the oil system should be inspected for leaks.*

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    8/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 6

    Lubrication System Checks (Cont'd)

    _After the system has reached the normal temperature of operation, the oil flow

    indicators and the oil pressure gauge should be checked to ensure that the

    indications are in the normal operational band.*

    _The motor and the oil system should be shut down, or if the oil system is

    equipped with a standby oil filter, the standby oil filter should be placed in

    service, and the oil filter should be inspected for foreign material.*

    Insulation Resistance (IR) and Polarization Index (PI) Checks

    The purpose of insulation resistance checks is to determine the integrity of the motor's

    insulation system. Insulation resistance checks consist of the megohmmeter test, thepolarization index check, and the high potential (hi-pot) test. The sections that follow provide

    a more detailed discussion of the following topics:

    _Megohmmeter

    _High Potential Test

    Megohmmeter

    The results of a megohmmeter test are used to determine whether a motor's insulation system

    has any gross defects and to calculate the polarization index. The polarization index provides

    a quantitative appraisal of the condition of a motor's insulation with respect to moisture and toother contaminants. This section will discuss the performance of megohmmeter tests on the

    following types of motors and motor components:

    _Induction Motors

    _Synchronous Motors

    _Bearing Insulation

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    9/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 7

    Insulation Resistance (IR) and Polarization Index (PI) Checks (Cont'd)

    Induction Motors - Figure 1 shows the Saudi Aramco Motor Test Record (Part One).

    This test record contains the procedural steps that should be followed to perform a

    megohmmeter test on an induction motor. The test record is divided into the following

    sections and tables:

    _Preparation for Test

    _Test Procedure for Insulation Resistance (e.g., megohmmeter test)

    _Test Procedure for Polarization Index

    _Table I

    _Table II

    The Preparation for Test section provides the preliminary steps that must be performed

    prior to an insulation resistance test.

    The Test Procedure for Insulation Resistance section provides the procedural steps that

    must be followed to perform an insulation resistance test. This section also provides

    the equation that must be used to correct the value of insulation resistance that is

    obtained from the test for temperature.

    The Test Procedure for Polarization Index section provides the procedural steps and

    the equation for determination of the polarization index.

    Table I shows the test voltage that should be used in the performance of an insulation

    resistance test. The test voltage that should be used is dependent on the rated voltageof the motor.

    Table II shows the various values of the insulation resistance temperature coefficient

    (Kt). Kt is used in the equation for temperature correction of insulation resistance

    values.

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    10/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 8

    Insulation Resistance (IR) and Polarization Index (PI) Checks (Cont'd)

    Saudi Aramco Motor Test Record (Part One)

    Figure 1

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    11/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 9

    Insulation Resistance (IR) and Polarization Index (PI) Checks (Cont'd)

    Synchronous Motors -Figure 2 shows the Saudi Aramco Motor Test Record (Part Two).

    This portion of the test record contains the procedural steps that should be followed to

    perform a megohmmeter test on a synchronous motor. This portion of the test record

    is divided into the following major sections:

    _Procedure for Exciter and Rotor Insulation Test (e.g., megohmmeter

    test)

    _Procedure for Bearing Insulation Resistance Test

    _Rotating Rectifier

    _Air Gap

    _Notes

    The Procedure for Bearing Insulation Resistance Test section and the Air Gap section

    do not apply to the performance of megohmmeter tests on synchronous motors. These

    sections of the test record will be discussed later in this module.

    The Procedure for Exciter and Rotor Insulation Resistance Test section provides the

    procedural steps that must be followed to perform an insulation resistance test on a

    synchronous motor. The polarization index check for a synchronous motor should be

    performed through use of the test procedure for polarization index that previously wasshown in Figure 1, except that the test voltage should be 500 volts.

    The Rotating Rectifier section provides the procedural steps that should be followed to

    perform an insulation resistance test on the rotating rectifier of a synchronous motor.

    This section also provides the procedural steps for performance of a resistance test on

    the rotating rectifier diodes to ensure that the diodes are properly connected.

    The Notes section applies both to induction and to synchronous motors. This section

    contains the minimum acceptable values for insulation resistance and for polarization

    index. This section also contains additional guidance for the performance of insulation

    resistance tests on motors in which the neutral point cannot be disconnected.

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    12/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 10

    Insulation Resistance (IR) and Polarization Index (PI) Checks (Cont'd)

    Saudi Aramco Motor Test Record (Part Two)

    Figure 2

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    13/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 11

    Insulation Resistance (IR) and Polarization Index (PI) Checks (Cont'd)

    Bearing Insulation Resistance - A bearing insulation resistance test should be performed

    on motors that have insulated bearings. The procedural steps that must be followed to

    perform a bearing insulation resistance test previously were shown in Figure 2. The

    minimum acceptable value of bearing insulation resistance is 200 k_. The preferred

    value of bearing insulation resistance is 1M_ or above.

    High-Potential Test

    The high potential (hi-pot) test is performed to provide positive proof that a motor's insulation

    has sufficient voltage strength to ride out overvoltage surges. Before a hi-pot test can be

    performed on a motor, a megohmeter test must be performed to prove that the motor's

    insulation resistance and polarization index are above the minimum acceptable values.

    The following major steps are involved in the performance of a hi-pot test:

    _The maximum DC voltage for the test must be calculated through use of the

    following formula:

    Maximum Voltage = 85% {1.7(2 _ Rated Voltage + 1kV)}

    _The DC high potential test set must be connected between the motor phase

    leads and ground.

    _After the test set is connected, the initial test voltage, which is equal to 33% ofthe maximum test voltage, is applied to the motor. The initial test voltage is

    constantly held for ten minutes, and the leakage current, as read on the

    ammeter that is on the face of the high potential test set, is monitored. The

    value of leakage current should be recorded at the end of each one minute

    interval.

    _When the first ten minutes of the test is complete, the test voltage should be

    raised from the initial value of 33% to the maximum value in ten equal steps.

    After each step increase in voltage, the voltage should be held at the new level

    for a period of one minute, and the leakage current should be recorded at the

    end of each minute.

    The results of a hi-pot test are not compared to a specific value to determine whether the

    results are acceptable. Instead, the results of a hi-pot test are analyzed for trends that indicate

    whether the insulation has sufficient strength to ride out overvoltage surges. Figure 3 shows

    a graphic display of the typical results of hi-pot tests for both good and bad insulation.

    The graph that is shown in Figure 3A is for the first ten minutes of a hi-pot test. The curve

    that represents good insulation shows a steep rise in leakage current over the first one minute

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    14/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 12

    interval that is followed by a steady decrease in the value of leakage current over the

    remainder of the ten minute interval.

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    15/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 13

    Insulation Resistance (IR) and Polarization Index (PI) Checks (Cont'd)

    The curve that represents bad insulation shows a steady increase in the value of leakage

    current throughout the ten minute interval. Such a curve indicates unsatisfactory insulation,

    and the hi-pot test should be stopped.

    The graph that is shown in Figure 3B is for the last ten minutes of the hi-pot test. The curve

    that represents good insulation shows a slow, steady increase in the value of leakage current

    as the test voltage is raised from 33% to 100%. The curve that represents bad insulation

    shows a sharp upturn or knee when the test voltage is increased to the point at which the

    insulation starts to break down. A knee in the leakage current curve indicates unsatisfactory

    insulation, and the hi-pot test should be stopped.

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    16/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 14

    Typical Results of Hi-Pot Tests

    Figure 3

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    17/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 15

    Air Gap Check

    The radial air gap should be checked on motors that are rated at 5000 hp or above to ensure

    that the air gap is uniform and that it is within the manufacturer's specifications. An unequal

    air gap can cause unequal currents in the stator windings that will result in unequal heating of

    the stator windings. The unequal currents in the stator windings also can result in an

    unbalanced magnetic pull between the stator and the rotor, and an unbalanced magnetic pull

    increases the possibility of contact between the stator and the rotor while the motor is in

    operation. Such contact can result in catastrophic damage to the motor.

    The radial air gap should be checked at eight different points around the circumference of the

    stator. The radial air gap is checked through insertion of a feeler gauge between the rotor and

    the stator windings of a motor. The feeler gauge size that just bridges the gap between the

    rotor winding and the stator winding is the size of the radial air gap.

    Verification of Protective Relay Setpoints

    A verification of protective relay setpoints must be performed to ensure that the protective

    relays will actuate and that they will deenergize the motor when the parameters that are

    monitored by the relays reach an unacceptable value (e.g., the relay setpoints). The following

    is a summary of the major steps that must be performed to verify protective relay setpoints:

    _The manufacturer's technical literature for each relay that is to be tested

    should be obtained. The manufacturer's technical literature contains the

    time/current curves, the tolerances, and the special precautions/procedures that

    apply to the specific relays to be tested.

    _The source of the input signal to each of the protective relays must be checked

    to ensure that each relay senses the correct motor parameter.

    _Relay test apparatus such as AC power supplies, ammeters, phase shifters,

    variacs, phase angle meters, and electronic timers must be obtained. The test

    apparatus must be able to simulate the actual operational conditions under

    which each relay is designed to operate. The test apparatus also must be able to

    accurately indicate the point at which each relay actuates.

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    18/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 16

    Verification of Protective Relay Setpoints (Cont'd)

    _The appropriate test apparatus is connected to one of the relays, and then the

    test apparatus is operated so that it simulates the operational conditions under

    which the connected relay is designed to operate. After the relay operates, the

    following items should be verified:

    - That the relay operated at the correct setpoint.

    - That the target indicators and the seal-in units properly operated.

    - That the contact that is used to deenergize the motor contactor or to

    open the motor circuit breaker properly operated.

    This step must be repeated for each protective relay that is part of the motor

    protection scheme.

    Phase Rotation Test

    Phase rotation tests are performed to ensure that the motor will rotate in the correct direction

    and that the motor leads are properly marked to coincide with the power system leads. If the

    motor rotates in the wrong direction, damage can occur to the motor bearings and to the

    connected load.

    The phase rotation test is the final pre-energization requirement because this test actually is

    performed through energization of the motor. The phase rotation test consists of a visual

    verification that the motor leads are properly marked to coincide with the power system leads

    and that the motor shaft rotates in the correct direction.

    The phase rotation test is performed through a momentary application of power to the motor

    while the load is disconnected, and through observation of the direction of shaft rotation. If

    the shaft rotates in the wrong direction, the connection between two of the motor leads and

    two of the power system leads must be switched. After the leads are switched, the phase

    rotation test should be repeated to verify that the direction of shaft rotation has been corrected.

    After the verification is complete, the motor lead markers also should be switched.

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    19/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 17

    ENERGIZATION TESTS

    Energization tests are performed on a new motor to verify that the motor installation is free

    from defects, to verify that the motor operates within its design limits, and to establish

    baseline motor operational data. Before energization tests are performed on a motor, all of the

    discrepancies that were identified during the pre-energization tests must have been corrected.

    This section of the Module provides information on the following topics that are pertinent to

    energization tests:

    _No Load Run Test

    _Load Run Test

    No Load Run Test

    For an electric motor, a no load run test consists of the measurement of various operationalparameters of the motor while the motor is in operation but before the motor is connected to

    the load that it was installed to drive. The no load run test is performed prior to connection of

    the motor to its load to ensure that the information that is obtained from the test only applies

    to the motor. If the information that is obtained from the test is unsatisfactory and if the test is

    conducted with the motor being connected to the load, the cause of the unsatisfactory

    condition would be more difficult to determine. Also, if a problem does exist with the motor,

    performance of the test with the motor being connected to the load would be more likely to

    aggravate the problem.

    The operational parameters that are measured during a no load run test vary with the type of

    motor to be tested. This section will discuss the no load run tests that are performed on thefollowing types of motors:

    _Induction Motors

    _Synchronous Motors

    Before a no load run test is performed on a motor that is equipped with space heaters, the

    space heaters must be turned on and the space heater current must be measured. The space

    heater current is measured to verify that the space heaters properly operate (e.g., that there are

    no burned out units or loose connections). In order to ensure that condensation does not form

    inside of the motor when the motor cools off after the test, the space heaters must be

    operational before the no load run test is performed.

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    20/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 18

    No Load Run Test (Cont'd)

    Induction Motors

    For an induction motor, the following operational parameters should be monitored during a

    no load run test:

    _Phase Current Balance

    _Voltage Balance

    _Vibration Level

    _RTD Readings for Bearings and Stator Windings

    Phase Current Balance - The phase current balance of induction motors is monitored

    during the no load run test through measurement and comparison of the individual

    phase current values. The individual phase current values of properly designed three-phase induction motors that are connected to balanced three-phase power sources

    should be equal. If the individual phase current values are not equal, one or more of

    the following problems can exist with the motor and/or the motor installation:

    _A high resistance connection in the motor circuit or in the motor supply circuit

    _A partial short-circuit or ground-fault in the motor circuit or in the motor

    supply circuit

    _An open in the motor circuit or in the motor supply circuit

    _A supply voltage unbalance

    The phase current balance of induction motors is monitored during the no load run test

    to verify that the above problems do not exist and to establish the baseline no load

    phase current values. If the cause of a phase current unbalance is not corrected and a

    motor is operated with unbalanced phase currents for prolonged periods of time,

    permanent motor damage can result.

    The mechanism through which unbalanced phase currents cause permanent damage is

    excessive heat. One of the individual phase current magnitudes will likely exceed the

    nameplate current rating in a motor that operates at or near full load with unbalancedphase currents. The phase current magnitude that exceeds the nameplate current rating

    will cause localized heating in the motor that may or may not be detected by the

    motor's protective devices. If the localized heating is not detected by the motor's

    protective devices, this heating eventually will result in damage to the motor's

    insulation.

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    21/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 19

    No Load Run Test (Cont'd)

    Voltage Balance- The voltage balance of the power source to which an induction motor

    is connected is monitored through measurement and through comparison of the

    individual phase voltages of the power source during the no load run test. If the

    individual phase voltages of the power source are not equal, one of the following

    problems may exist:

    _An open in one phase of the power source

    _Unequal power source phase impedances

    The voltage balance of the power source to which the motor is connected is monitored

    during the no load run test to verify that the above problems do not exist. If the cause

    of a power source voltage unbalance is not corrected and a motor is operated from apower source that has unbalanced phase voltages, the unbalanced phase voltages will

    result in unbalanced phase currents. The unbalanced phase currents can result in

    permanent motor damage as previously discussed.

    The magnitude of the phase current unbalance that can result from operation of a

    motor that is connected to a power source that has unbalanced phase voltages is on the

    order of six to ten times the magnitude of the voltage unbalance.

    Vibration Level -The vibration levels of induction motors are monitored during the no

    load run test through use of the permanently installed vibration monitoring equipment,

    or in cases where motors are not equipped with permanently installed vibrationmonitoring equipment, through use of portable vibration monitoring equipment. If the

    motor exhibits excessive levels of vibration, one of the following problems can exist

    with the motor and/or with the motor installation:

    _The motor is not properly balanced.

    _The motor is not properly mounted.

    _The motor shaft is bent.

    _The motor bearings are defective or are improperly installed.

    The vibration levels of induction motors are monitored during the no load run test to

    verify that the above problems do not exist and to establish the baseline no loadvibration levels for the motor. If motors are operated with vibration problems, a

    variety of motor problems can result dependent on the severity of the vibrations.

    Minor vibrations cause a reduction in bearing life and an increase in the overall stress

    that is placed on the motor components. The increased stress that is placed on the

    motor components eventually can lead to fatigue failures. Severe vibrations can

    quickly cause catastrophic motor failures such as rotor contact with the stator.

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    22/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 20

    No Load Run Test (Cont'd)

    RTD Readings for Bearings and Stator Windings -RTD readings (temperature) for bearing

    and stator windings are monitored during the no load run test through use of the

    permanently installed monitoring equipment. Because these readings are monitored

    under no load conditions, the readings should be significantly less than the full load

    limits. A high rate of bearing and/or stator temperature rise would indicate a serious

    problem with the lubrication system and/or the cooling system.

    The RTD readings for bearings and stator windings are monitored during the no load

    run test for the following reasons:

    _To verify that serious problems do not exist with the lubrication or with thecooling system.

    _To verify proper operation of the installed temperature monitoring equipment.

    _To establish baseline no load temperature values for the bearings and stator

    windings.

    Test Duration - The no load run test for an induction motor should last for

    approximately four hours. The value of each parameter that is monitored during a no

    load run test should be recorded every 30 minutes. If the parameters that are being

    monitored have not reached steady state values after four hours, the test should beextended until the parameters stabilize.

    Synchronous Motors

    For a synchronous motor, the following operational parameters should be monitored during a

    no load run test:

    _Phase Current Balance

    _Voltage Balance

    _Vibration Level

    _RTD Readings for Bearings and Stator Windings_Field Current

    _Power Factor and kVAR Control

    Phase Current Balance-The phase current balance of a synchronous motor is monitored

    in the same way and for the same reasons as previously described for an induction

    motor.

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    23/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 21

    No Load Run Test (Cont'd)

    Voltage Balance-The voltage balance of a synchronous motor is monitored in the same

    way and for the same reasons as previously described for an induction motor.

    Vibration Level -The vibration levels of a synchronous motor are monitored in the same

    way and for the same reasons as previously described for an induction motor.

    RTD Readings for Bearings and Stator Windings -The RTD readings (temperatures) of the

    bearing and the stator windings of a synchronous motor are monitored in the same way

    and for the same reasons as previously described for an induction motor.

    Field Current- Large synchronous motors have two separate fields: the exciter field and

    the motor field. The exciter field current is the DC current that is supplied to the

    exciter of a synchronous motor. The motor field current is the rectified output of the

    exciter. The amount of motor field current that is produced by the exciter is controlled

    through variance of the exciter field current.

    The following field current parameters should be monitored during the no load run test

    of a synchronous motor:

    _The speed of the motor when DC current is first supplied to the exciter field

    (i.e., the exciter is excited).

    _The no load exciter field current.

    _The no load motor field current.

    The speed at which the exciter is excited is monitored through connection of an

    oscillograph to monitor the speed of the motor and the point at which the exciter

    contactor operates during the no load run test. The speed at which the exciter is

    excited must be correct because if the exciter is excited before the motor attains

    sufficient speed, the motor's rotor will not be able to synchronize with the stator field.

    If the rotor does not synchronize with the stator field, large pulsating torques will beproduced, and these torques will cause excessive mechanical stresses to be placed on

    the motor's shaft.

    The no load exciter field current is monitored through use of the installed ammeter

    during the no load run test. The no load exciter field current is monitored to verify the

    proper setup and proper operation of the excitation control circuit.

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    24/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 22

    No Load Run Test (Cont'd)

    The no load motor field current is monitored through use of the installed ammeter

    during the no load run test. The no load motor field current is monitored to verify the

    proper operation of the AC exciter and the rotating rectifier.

    Power Factor and kVAR Control - The power factor and the kVAR of a synchronous

    motor are directly related to each other, to the motor's excitation, and to the motor's

    load.

    When the load that is on the motor remains constant, a change in the motor's excitation

    should cause a corresponding change in the motor's power factor and in the motor's

    kVAR. If the motor's excitation is increased and the motor's load remains constant, the

    motor's power factor should become more "leading" and the motor should supply more

    kVAR (leading VAR's). If the motor's excitation is decreased and the motor's loadremains constant, the motor's power factor should become less "leading" and the motor

    should supply less kVAR (leading VAR's). If the motor's excitation is continually

    decreased, the motor's power factor eventually will pass through "unity" and become

    "lagging." Correspondingly, when the power factor is at "unity," the motor should

    supply zero kVAR, and when the motor's power factor becomes "lagging," the motor

    should start to draw kVAR (lagging VAR's) from the power supply.

    The power factor and the kVAR of a synchronous motor are monitored through use of

    the installed power factor and kVAR meters during the no load run test. If the motor

    does not have a kVAR meter, an indication of kVAR can be obtained from the AC

    amperes of the motor.

    The power factor and the kVAR of a synchronous motor are monitored during the no

    load run test to verify the proper setup and the proper operation of the excitation

    control circuit. If the excitation control circuit does not supply sufficient excitation,

    the motor's power factor can become lagging, the motor can start to draw reactive

    power, and in cases of extremely low excitation, the rotor can lose synchronization. If

    the excitation control circuit supplies too much excitation, the motor's power factor

    can become excessively leading and the motor will supply excessive kVAR. Such

    conditions will cause the motor to overheat.

    Test Duration - The no load run test for a synchronous motor should last forapproximately four hours. The value of each parameter that is monitored during a no

    load run test should be recorded every 30 minutes. If the parameters that are being

    monitored have not reached steady state values after four hours, the test should be

    extended until the parameters stabilize.

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    25/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 23

    Load Run Test

    For an electric motor, a load run test consists of the measurement of various operational

    parameters of the motor while the motor is in operation and while it is connected to the load

    that it was installed to drive. The load run test should be conducted after all of the necessary

    repairs/adjustments that were identified during the no load run test have been completed.

    The operational parameters that are measured during a load run test vary with the type of

    motor to be tested. This section will discuss the load run tests that are performed on the

    following types of motors:

    _Induction Motors

    _Synchronous Motors

    Induction Motors

    The following operational parameters should be monitored during a load run test for an

    induction motor:

    _Verify Motor Alignment

    _Phase Current Balance

    _Voltage Balance

    _Vibration Level

    _RTD Readings for Bearings and Stator Windings

    _Voltage Dip on Start_Acceleration Time

    _Test Duration

    Verify Motor Alignment -The motor alignment must be verified after the motor shaft is

    coupled to the load shaft. This verification should be performed before the motor is

    started with the connected load. The motor alignment verification is performed to

    ensure that the following types of misalignment do not exist:

    _Angular misalignment

    _Parallel misalignment

    Angular misalignment is the amount by which the face of the motor half of the

    coupling is out of parallel with the face of the load half of the coupling. Angular

    misalignment can be checked through use of a dial indicator.

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    26/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 24

    Load Run Test (Cont'd)

    Parallel misalignment is the amount by which the centerline of the motor half of the

    coupling is offset from the centerline of the load half of the coupling. Parallel

    misalignment also can be checked through use of a dial indicator.

    The motor alignment must be verified before the motor is operated because any

    amount of misalignment will result in the placement of increased stresses on the

    bearings and the couplings. Such increased stresses will result in reduced bearing life

    and in reduced coupling life. Motor misalignment also will cause motor vibration

    levels to increase. An increase in motor vibration levels places additional stress on

    motor components such as mounting bolts and winding supports, and this additional

    stress can result in a premature failure of the motor.

    Phase Current Balance- The phase current balance is monitored during the load run testof an induction motor in the same way and for the same reasons as previously

    described for the no load run test of an induction motor. The only change that should

    be noted during the load run test is an increase in the individual values of phase

    current because the motor is loaded. The variation (in percent) between the individual

    phase currents should remain the same.

    Voltage Balance - The voltage balance is monitored during the load run test of an

    induction motor in the same way and for the same reasons as previously described for

    the no load run test of an induction motor. The only change that should be noted

    during the load run test is a possible decrease in the individual values of phase voltage

    because of supply system voltage droop under load. The variation (in percent)between the individual phase voltages should remain the same.

    Vibration Level -The vibration levels of induction motors again are monitored during

    the load run test through use of the permanently installed vibration monitoring

    equipment, or in cases where motors are not equipped with permanently installed

    vibration monitoring equipment, through use of portable vibration monitoring

    equipment. If the motor exhibits excessive levels of vibration during the load run test,

    one of the following problems may exist with the load or with the installation:

    _The motor is not properly aligned with the load.

    _The load is not properly mounted._The load shaft is bent.

    _The load bearings are defective or are improperly installed.

    _The installation produces mechanical resonance vibrations.

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    27/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 25

    Load Run Test (Cont'd)

    The vibration levels of induction motors are monitored during the load run test to

    verify that the above problems do not exist and to establish the baseline vibration

    levels for the motor under loaded conditions. If motor/load installation is operated

    with excessive levels of vibration, a variety of problems can result dependent on the

    severity of the vibrations. Minor vibrations cause a reduction in bearing life and an

    increase in the overall stress that is placed on the motor/load components. The

    increased stress that is placed on the motor/load components eventually can lead to

    fatigue failures. Severe vibrations quickly can cause catastrophic motor/load failures.

    RTD Readings for Bearings and Stator Windings -The RTD readings for bearings and for

    stator windings are monitored during the load run test of an induction motor in the

    same way and for the same reasons as previously described for the no load run test of

    an induction motor. The changes that should be noted during the load run test arefaster rates of temperature increase and higher steady state temperatures. These

    changes occur because the motor is loaded.

    Voltage Dip on Start -The amount with which the terminal voltage of an induction motor

    drops when the motor is started is monitored at the start of the load run test. As

    previously explained in Module EEX 203.03, all motors cause the terminal voltage of

    the power source to drop by some amount. The actual amount of voltage drop that

    occurs will depend on the following factors:

    _The size (hp/kW) of the motor.

    _The minimum short-circuit kVA of the power source._The method (full- or reduced-voltage) that is used to start the motor.

    _The number of other loads that are in operation when the motor is started.

    The calculation of voltage dip is performed when the initial specifications for a new

    motor are determined. The calculation is used to determine the method that should be

    used to start the motor. The actual voltage dip on start is monitored at the start of the

    load run test to verify that the actual drop in voltage does not exceed the allowable

    drop in voltage. If the actual drop in voltage exceeds the allowable drop in voltage,

    the cause of the excessive voltage drop must be identified and corrected before the

    motor is placed in normal operation.

    Acceleration Time-The acceleration time of an induction motor also is monitored at the

    start of the load run test. The acceleration time of a motor is the elapsed time (in

    seconds) between the point at which power is applied to the motor and the point at

    which the load reaches normal operational speed.

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    28/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 26

    Load Run Test (Cont'd)

    The acceleration time of an induction motor must be monitored at the start of the load

    run test to verify that the actual acceleration time is less than the maximum allowable

    acceleration time. If the actual acceleration time exceeds the maximum allowable

    acceleration time, the motor can overheat because of the extended length of time with

    which the motor is subjected to starting current.

    Test Duration -The load run test for an induction motor should last for approximately

    four hours. The value of the following parameters that are monitored during the load

    run test should be recorded every 30 minutes:

    _Phase current balance

    _Voltage balance

    _Vibration levels_RTD readings for bearings and stator windings

    If the parameters that are monitored have not reached steady state values after four

    hours, the test should be extended until the parameters stabilize.

    Synchronous Motors

    The following operational parameters should be monitored during a load run test for a

    synchronous motor:

    _Verify Motor Alignment_Phase Current Balance

    _Voltage Balance

    _Vibration Level

    _RTD Readings for Bearings and Stator Windings

    _Voltage Dip on Start

    _Acceleration Time

    _Field Current

    _Power Factor and kVAR Control

    _Test Duration

    Verify Motor Alignment- The motor alignment for synchronous motors is verified in thesame way and for the same reasons as previously described for an induction motor

    load run test.

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    29/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 27

    Load Run Test (Cont'd)

    Phase Current Balance- The phase current balance is monitored during the load run test

    of a synchronous motor in the same way and for the same reasons as previously

    described for the no load run test of a synchronous motor. The only change that

    should be noted during the load run test is an increase in the individual values of phase

    current because the motor is loaded. The variation (in percent) between the individual

    phase currents should remain the same.

    Voltage Balance - The voltage balance is monitored during the load run test of a

    synchronous motor in the same way and for the same reasons as previously described

    for the no load run test of a synchronous motor. The only change that should be noted

    during the load run test is a possible decrease in the individual values of phase voltage

    because of supply system voltage droop under load. The variation (in percent)

    between the individual phase voltages should remain the same.

    Vibration Level - The vibration levels are monitored during the load run test of a

    synchronous motor in the same way and for the same reasons as previously described

    for the load run test of an induction motor.

    RTD Readings for Bearing and Stator Windings -The RTD readings for bearings and for

    stator windings are monitored during the load run test of a synchronous motor in the

    same way and for the same reasons as previously described for the no load run test of

    a synchronous motor. The changes that should be noted during the load run test are

    faster rates of temperature increase and higher steady state temperatures. These

    changes occur because the motor is loaded.

    Voltage Dip on Start - The amount with which the terminal voltage of a synchronous

    motor drops when the motor is started is monitored at the start of the load run test for

    the same reasons as previously described for the load run test of an induction motor.

    Acceleration Time - The acceleration time of a synchronous motor is monitored at the

    start of the load run test for the same reasons as previously described for the load run

    test of an induction motor.

    Field Current - The following field current parameters should be monitored during the

    load run test of a synchronous motor:

    _The speed of the motor when DC current is first supplied to the exciter field

    (e.g., the exciter is excited).

    _The full load exciter field current.

    _The full load motor field current.

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    30/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 28

    Load Run Test (Cont'd)

    The speed at which the exciter is excited is monitored through connection of an

    oscillograph to monitor the speed of the motor and the point at which the exciter

    contactor operates during the load run test. The speed at which the exciter is excited

    must be correct because if the exciter is excited before the motor attains sufficient

    speed, the motor's rotor will not be able to synchronize with the stator field. If the

    rotor does not synchronize with the stator field, large pulsating torques will be

    produced, and these torques will cause excessive mechanical stresses to be placed on

    the motor's shaft.

    The full load exciter field current is monitored through use of the installed ammeter

    during the load run test. The full load exciter field current is monitored to verify the

    proper setup and proper operation of the excitation control circuit.

    The full load motor field current is monitored during the load run test through use of

    the installed ammeter. The full load motor field current is monitored to verify the

    proper operation of the AC exciter and the rotating rectifier.

    Power Factor and kVAR Control - The power factor and the kVAR of a synchronous

    motor are monitored through use of the installed power factor and kVAR meters

    during the load run test. If the motor does not have a kVAR meter, an indication of

    kVAR can be obtained from the AC amperes of the motor.

    The power factor and the kVAR of a synchronous motor are monitored during the loadrun test to verify the proper setup and the proper operation of the excitation control

    circuit. If the excitation control circuit does not supply sufficient excitation, the

    motor's power factor can become lagging, the motor can start to draw reactive power,

    and in cases of extremely low excitation, the rotor can lose synchronization. If the

    excitation control circuit supplies too much excitation, the motor's power factor can

    become excessively leading, and the motor will supply excessive kVAR. Such

    conditions will cause the motor to overheat.

    Test Duration -The load run test for a synchronous motor should last for approximately

    four hours. The value of the following parameters that are monitored during the load

    run test should be recorded every 30 minutes:

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    31/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 29

    Load Run Test (Cont'd)

    _Phase current balance

    _Voltage balance

    _Vibration levels

    _RTD readings for bearings and stator windings

    _Field current (exciter field and motor field)

    _Power factor and kVAR control

    If the parameters that are monitored have not reached steady state values after four

    hours, the test should be extended until the parameters stabilize.

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    32/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 30

    EVALUATING THE RESULTS OF MOTOR COMMISSIONING FORACCEPTABILITY OR UNACCEPTABILITY

    The final aspect of directing the startup and commissioning of electric motors is to evaluate

    the results of the commissioning for acceptability or unacceptability. To aid in the

    performance of the evaluation, the results of the motor commissioning are recorded on

    standardized commissioning forms as the individual inspections, checks, and tests are

    completed. To perform the evaluation, the Electrical Engineer must compare the actual

    results against the acceptable results to determine whether the motor is acceptable or

    unacceptable. The sections that follow provide information on the following topics that are

    pertinent to evaluating the results of motor commissioning for acceptability or

    unacceptability:

    _Motor Commissioning Form

    _Evaluating the Results of Induction Motor Commissioning_Evaluating the Results of Synchronous Motor Commissioning

    Motor Commissioning Form

    The purpose of a motor commissioning form is to provide a single, comprehensive record of

    the pertinent data that is collected when a new motor is commissioned. The motor

    commissioning form is divided into the following major sections:

    _Motor Identification Data

    _Pre-Energization Data

    _No Load Test Run Data_Load Run Test Data

    The motor identification data section is on page one of the motor commissioning form. Page

    one of the motor commissioning form is shown in Figure 4. This section provides a place to

    record information such as the make, type, serial number, ratings, and plant. This information

    can be used to positively identify this motor from other similar motors. This information also

    can be used to aid in the determination of which inspections, checks, and tests should have

    been performed.

    The pre-energization data section also is on page one of the motor commissioning form. This

    section provides a place to record the results of each of the pre-energization inspections,checks, and tests that were previously described in this module. The results that are recorded

    in this section are used in the evaluation of acceptability or unacceptability. The results that

    are recorded in this section also are used as the baseline data for future trend analysis.

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    33/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 31

    Motor Commissioning Form (Cont'd)

    Motor Commissioning Form (Page One)

    Figure 4

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    34/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 32

    Motor Commissioning Form (Cont'd)

    The no load run test data section is on page two of the motor commissioning form. Page two

    of the motor commissioning form is shown in Figure 5. This section provides a place to

    record the values of each of the no load run test parameters that were previously described in

    this module. The values that are recorded in this section are used in the evaluation of

    acceptability or unacceptability. The results that are recorded in this section also are used as

    the baseline data for future trend analysis.

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    35/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 33

    Motor Commissioning Form (Cont'd)

    Motor Commissioning Form (Page Two)

    Figure 5

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    36/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 34

    Motor Commissioning Form (Cont'd)

    The load run test data section is on page three of the motor commissioning form and is shown

    in Figure 6. This section provides a place to record the values of each of the load run test

    parameters that were previously described in this module. The values that are recorded in this

    section are used in the evaluation of acceptability or unacceptability. The results that are

    recorded in this section also are used as the baseline data for future trend analysis.

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    37/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 35

    Motor Commissioning Form (Page Three)

    Figure 6

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    38/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 36

    Evaluating the Results of Induction Motor Commissioning

    The procedure and the acceptable values for evaluating the results of motor commissioning

    are located in Work Aid 1. This section of the Module will provide a brief explanation of

    how to use the procedure and the acceptable values that are located in Work Aid 1 to evaluate

    the results of induction motor commissioning.

    Example Evaluation

    Figure 7A, Figure 7B, and Figure 7C show the results of the inspections, checks, and tests

    that were performed to commission a hypothetical induction motor. From the procedure that

    is located in Work Aid 1, the first step in the evaluation is to review the motor identification

    data to determine the type and the size of the motor. Figure 7A shows that the motor type is

    induction and that the motor size is 3000 hp (2200 kW).

    The motor type and the motor size are used to determine whether all of the applicable

    inspections, checks, and tests were performed on the motor. Because this motor is a 3000 hp

    induction motor, the following inspections, checks, and tests should have been performed:

    _Inspection/check of electrical connections/interlocks

    _Inspection/check of mechanical integrity

    _Inspection/check of lubrication system

    _Phase to ground, phase to phase, and bearing insulation resistance readings

    _High potential test

    _Inspection/check of protective relays

    _Phase rotation test_No load run test that monitored the following parameters

    - Phase current

    - Phase voltage

    - % voltage unbalance

    - Bearing vibration

    - Bearing, ambient, and winding temperatures

    _Load run test that monitored the following parameters

    - Inspection/check of motor alignment

    - Phase current

    - Phase voltage

    - % voltage unbalance- Bearing vibration

    - Bearing, ambient, and winding temperature

    - Voltage dip on start

    - Acceleration time

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    39/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 37

    Evaluating the Results of Induction Motor Commissioning (Cont'd)

    Figures 7A, 7B, and 7C show that all of the applicable inspections, checks, and tests were

    performed on this motor.

    Because all of the applicable inspections, checks, and tests were performed, the next step of

    the procedure that is located in Work Aid 1 is to compare the pre-energization data with the

    acceptable values to determine whether the pre-energization data are acceptable. The

    acceptable values to which the pre-energization data are compared also are located in Work

    Aid 1. Through comparison of the data that are shown in Figure 7A with the acceptable

    values for pre-energization data that are located in Work Aid 1, the determination can be

    made that all of the pre-energization data for the motor are acceptable.

    Because all of the pre-energization data for the motor are acceptable, the next step of theprocedure that is located in Work Aid 1 is to compare the no load run test data with the

    acceptable values to determine whether the no load run test data are acceptable. The

    acceptable values to which the no load run test data are compared also are located in Work

    Aid 1. Through comparison of the data that are shown in Figure 7B with the acceptable

    values for no load run test data that are located in Work Aid 1, the determination can be made

    that all of the no load run test data for the motor are acceptable.

    Because all of the no load run test data for the motor are acceptable, the next step of the

    procedure that is located in Work Aid 1 is to compare the load run test data with the

    acceptable values to determine whether the load run test data are acceptable. The acceptable

    values to which the load run test data are compared also are located in Work Aid 1. Throughcomparison of the data that are shown in Figure 7C with the acceptable values for load run

    test data that are located in Work Aid 1, the determination can be made that the results of the

    motor commissioning are acceptable.

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    40/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 38

    Evaluating the Results of Induction Motor Commissioning (Cont'd)

    Example Motor Commissioning Form (Page One)

    Figure 7A

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    41/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 39

    Evaluating the Results of Induction Motor Commissioning (Cont'd)

    Example Motor Commissioning Form (Page Two)

    Figure 7B

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    42/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 40

    Evaluating the Results of Induction Motor Commissioning (Cont'd)

    Example Motor Commissioning Form (Page Three)

    Figure 7C

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    43/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 41

    Evaluating the Results of Synchronous Motor Commissioning

    The procedure and the acceptable values for evaluating the results of motor commissioning

    are located in Work Aid 1. This section of the Module will provide a brief explanation of

    how to use the procedure and the acceptable values that are located in Work Aid 1 to evaluate

    the results of synchronous motor commissioning.

    Example Evaluation

    Figure 8A, Figure 8B, and Figure 8C show the results of the inspections, checks, and tests

    that were performed to commission a hypothetical synchronous motor. From the procedure

    that is located in Work Aid 1, the first step in the evaluation is to review the motor

    identification data to determine the type and the size of the motor. Figure 8A shows that the

    motor type is synchronous and that the motor size is 15000 hp (11300 kW).

    The motor type and the motor size are used to determine whether all of the applicable

    inspections, checks, and tests were performed on the motor. Because this motor is a 15000 hp

    synchronous motor, the following inspections, checks, and tests should have been performed:

    _Inspection/check of electrical connections/interlocks

    _Inspection/check of mechanical integrity

    _Inspection/check of lubrication system

    _Phase to ground and phase to phase insulation resistance readings

    _Exciter winding to ground insulation resistance reading

    _Rotor winding to ground insulation resistance reading

    _Rotating rectifier to ground insulation resistance reading_Bearing insulation resistance readings

    _High potential test

    _Rotating rectifier diode check

    _Air gap check

    _Inspection/check of protective relays

    _Phase rotation test

    _No load run test that monitored the following parameters

    - Phase current

    - Phase voltage

    - % voltage unbalance

    - Bearing vibration- Bearing, ambient, and winding temperatures

    - % Nswhen excited

    - Exciter and motor field currents

    - Power factor

    - Reactive power

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    44/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 42

    Evaluating the Results of Synchronous Motor Commissioning (Cont'd)

    _Load run test that monitored the following parameters

    - Inspection/check of motor alignment

    - Phase current

    - Phase voltage

    - % voltage unbalance

    - Bearing vibration

    - Bearing, ambient, and winding temperature

    - Voltage dip on start

    - Acceleration time

    - % Nswhen excited

    - Exciter and motor field currents

    - Power factor - Reactive power

    Figures 8A, 8B, and 8C show that all of the applicable inspections, checks, and tests were

    performed on this motor.

    Because all of the applicable inspections, checks, and tests were performed, the next step of

    the procedure that is located in Work Aid 1 is to compare the pre-energization data with the

    acceptable values to determine whether the pre-energization data are acceptable. The

    acceptable values to which the pre-energization data are compared also are located in Work

    Aid 1. Through comparison of the data that are shown in Figure 8A with the acceptable

    values for pre-energization data that are located in Work Aid 1, the determination can bemade that all of the pre-energization data for the motor are acceptable.

    Because all of the pre-energization data for the motor are acceptable, the next step of the

    procedure that is located in Work Aid 1 is to compare the no load run test data with the

    acceptable values to determine whether the no load run test data are acceptable. The

    acceptable values to which the no load run test data are compared also are located in Work

    Aid 1. From a review of the acceptable values for no load run test data that are located in

    Work Aid 1, the acceptable values for the following parameters must be obtained from the

    manufacturer's technical manual:

    _% Nswhen excited_Exciter field current

    _Motor field current

    _Power factor

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    45/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 43

    Evaluating the Results of Synchronous Motor Commissioning (Cont'd)

    For this example evaluation, the following are the acceptable values for these parameters from

    the manufacturer's technical manual:

    _% Nswhen excited should be a minimum of 98%.

    _No load exciter field current should be approximately 1.0 to 1.2 amps.

    _No load motor field current should be approximately 145 amps.

    _The design power factor is .9 leading.

    Through comparison of the data that are shown in Figure 8B with the acceptable values for no

    load run test data that are located in Work Aid 1, the determination can be made that all of the

    no load run test data for the motor are acceptable.

    Because all of the no load run test data for the motor are acceptable, the next step of theprocedure that is located in Work Aid 1 is to compare the load run test data with the

    acceptable values to determine whether the load run test data are acceptable. The acceptable

    values to which the load run test data are compared also are located in Work Aid 1. From a

    review of the acceptable values for no load run test data that are located in Work Aid 1, the

    acceptable values for the following parameters must be obtained from the manufacturer's

    technical manual:

    _Acceleration time

    _% Nswhen excited

    _Exciter field current

    _Motor field current_Power factor

    For this example evaluation, the following are the acceptable values for these parameters from

    the manufacturer's technical manual:

    _Acceleration time should be approximately 6 to 7 seconds.

    _% Nswhen excited should be a minimum of 98%.

    _The rated exciter field current is 4.3 amps.

    _The rated motor field current is 490.

    _The design power factor is .9 leading.

    Through comparison of the data that are shown in Figure 8C with the acceptable values for

    load run test data that are located in Work Aid 1, the determination can be made that the

    results of the motor commissioning are acceptable.

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    46/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 44

    Evaluating the Results of Synchronous Motor Commissioning (Cont'd)

    Example Motor Commissioning Form (Page One)

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    47/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 45

    Figure 8A

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    48/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 46

    Evaluating the Results of Induction Motor Commissioning (Cont'd)

    Example Motor Commissioning Form (Page Two)

    Figure 8B

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    49/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 47

    Evaluating the Results of Induction Motor Commissioning (Cont'd)

    Example Motor Commissioning Form (Page Three)

    Figure 8C

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    50/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 48

    WORK AID 1: PROCEDURE AND ACCEPTABLE VALUES FOR EVALUATINGTHE RESULTS OF MOTOR COMMISSIONING COMPILED FROMSADP-P-113, NEMA MG-1, AND ESTABLISHED ENGINEERINGPRACTICES

    Work Aid 1 is designed to help the Parti cipants complete Exercise 1.

    Procedure

    1. Review the motor identification data to determine the type and the size of the motor.

    2. Determine whether all of the applicable inspections, checks, and tests have been

    performed. This determination is based on the type and the size of the motor.

    2A. If all of the inspections, checks, and tests have not been performed, the results areunacceptable.

    2B. If all of the inspections, checks, and tests have been performed, continue with step

    three of this procedure.

    3. Compare the pre-energization data with the acceptable values for this data to

    determine whether the pre-energization data are acceptable.

    3A. If all of the pre-energization data are not within the acceptable values, the results are

    unacceptable.

    3B. If all of the pre-energization data are within the acceptable values, continue with step

    four of this procedure.

    4. Compare the no load run test data with the acceptable values for this data to determine

    whether the no load run test data are acceptable.

    4A. If all of the no load run test data are not within the acceptable values, the results are

    unacceptable.

    4B. If all of the no load run test data are within the acceptable values, continue with step

    five of this procedure.

    5. Compare the load run test data with the acceptable values for this data to determine

    whether the load run test data are acceptable.

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    51/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 49

    WORK AID 1 (Cont'd)

    5A. If all of the load run test data are not within the acceptable values, the results are

    unacceptable.

    5B. If all of the load run test data are within the acceptable values, the results of the motor

    commissioning are acceptable.

    Acceptable Values for Pre-Energization Data

    Inspection/Check of Electrical Connection/Interlocks

    The acceptable results for this inspection/check are that the inspection/check was

    satisfactorily completed. Satisfactory completion is indicated by an "X" in the YES column.

    Inspection/Check of Mechanical Integrity

    The acceptable results for this inspection/check are that the inspection/check was

    satisfactorily completed. Satisfactory completion is indicated by an "X" in the YES column.

    Inspection/Check of Lubrication System

    The acceptable results for this inspection/check are that the inspection/check was

    satisfactorily completed. Satisfactory completion is indicated by an "X" in the YES column.

    Insulation Resistance Readings

    The acceptable values of insulation resistance only apply to insulation resistance readings that

    have been temperature corrected to 50oC. Before the temperature corrected insulation

    resistance readings are evaluated for acceptability or unacceptability, these values must be

    verified through use of the following formula and table:

    Rc= Kt_ Rt

    Where: R cis the insulation resistance corrected to 50oC.

    Rtis the direct insulation resistance reading.

    Ktis the insulation resistance temperature coefficient from the following table:

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    52/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 50

    Winding

    Temp.

    10o 20o

    30o

    40o 50o 60o 70o 80o 90o 100o 110o

    Kt .06 .12 .25 .5 1 2 4 8 16 32 64

    WORK AID 1 (Cont'd)

    The following are the minimum acceptable temperature corrected values of insulation

    resistance:

    Windings - Minimum acceptable Voltage Min. IR (M_)

    13,200 15

    4,000 5.5

    2,400 3.5

    460 1.5

    Bearings - Minimum acceptable value is 200 k_, but > 1 M_ is preferred

    Polarization Index

    Before the calculated values of polarization index can be evaluated, these calculated values

    must be verified through use of the following formula:

    The minimum acceptable value of polarization index for Class B and for Class F insulation is

    2.0; however, polarization index values of 2.5 to 3.0 are preferred.

    High Potential Test

    Before the results of the high potential test can be evaluated, the maximum and the initial test

    voltages that were used must be verified through use of the following formula:

    Maximum Voltage = 85%{1.7(2 _ Rated Voltage + 1 kV)}

    Initial Voltage = 33%(Maximum Voltage)

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    53/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 51

    The following are the acceptable results of a high potential test:

    The microamperes leakage current should decrease in value during the initial ten

    minutes of the test at 33% test voltage. The microamperes leakage current should

    show a steady rise for the remainder of the test until the maximum test voltage is

    reached.

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    54/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 52

    WORK AID 1 (Cont'd)

    A steady-state or rising value during the initial ten minutes of the test indicates poor

    insulation and, as a result, the insulation should be rejected. A sharp or an exponential

    rise in leakage current during the step voltage changes and prior to the application of

    the maximum test voltage also indicates poor insulation and, as a result, the insulation

    should be rejected.

    Rotating Rectifier Diode Check

    The exact values of diode resistance vary from one diode to another diode. For purposes of

    motor commissioning, the acceptable values of diode resistance are a low resistance in the

    forward direction and a high resistance in the reverse direction.

    Air Gap Check

    The minimum acceptable values for radial air gap are shown in the following table:

    Motor Rating Minimal Radial Air Gap

    kW H.P. (NEMA) mm (mil)

    601 - 900

    901 -1350

    1350 - 2000

    2001 - 2900

    2901 and up

    801 - 1250

    1250 - 1750

    1751 - 2500

    2501 - 4000

    4001 and up

    3.4

    3.6

    3.9

    3.9

    4.6

    134

    142

    154

    154

    181

    Inspection/Check of Protective Relays

    The acceptable results for this inspection/check are that the inspection/check was

    satisfactorily completed. Satisfactory completion is indicated by an "X" in the YES column.

    Phase Rotation Test

    The acceptable results for this test are that the test was satisfactorily completed. Satisfactory

    completion is indicated by an "X" in the YES column.

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    55/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 53

    WORK AID 1 (Cont'd)

    Acceptable Values for No Load Run Test Data

    Phase Current

    The maximum phase current values normally range from five to seven times the full load

    current of the motor when the motor is started under loaded conditions. The actual phase

    current values when the motor is started under no load conditions should be below this range

    and, in no case, can the values exceed this range. The running values of phase current should

    be approximately equal to and should be less than the full load nameplate current rating.

    Phase Voltage

    The individual phase voltages (A-B, B-C, and A-C) should be equal to the nameplate voltage

    rating _10%.

    Percent Voltage Unbalance

    Before the percent voltage unbalance can be evaluated, the percent voltage unbalance

    calculation must be verified through use of the following formula:

    %VU= 100(Vd/ Vavg)

    Where: %VUis the percent voltage unbalance.

    Vd is the maximum phase voltage deviation (VA-B, VB-C, or VA-Cminus Vavg, whichever yields the highest deviation).

    Vavgis the average of the individual phase voltages.

    The maximum allowable percent voltage unbalance cannot exceed 1% for continuous

    operation. A percent voltage unbalance of 1.5% is acceptable for periods of time that are less

    than three minutes.

    Vibration Levels

    The maximum allowable vibration levels for horizontal motors that are equipped with

    proximity probes are as follows:

  • 7/22/2019 Saudi Aramco Engineering Standards-Electrical-Commissioning

    56/61

    Engineering Encyclopedia Electrical

    Directing the Startup and Commissioning of Motors

    Saudi Aramco DeskTop Standards 54

    WORK AID 1 (Cont'd)

    Motor Speed (RPM) Max. Vibration Level (Mils)

    3600 2.0

    1800 2.5

    1200 or less 3.0

    The maximum allowable vibration level for vertical and for horizontal motors that are

    equipped with seismic velocity transducers is 4.6 mm/s.

    Winding Temperature

    The maximum winding temperature of a motor with Class B or with Class F insulation is

    125

    o

    C at full