sat tm 1703 acp pdf 745kb

6
Automation Unit TM 1703 ACP Flexible automation and telecontrol Power Transmission and Distribution

Upload: ibrar-h-malik

Post on 14-Apr-2015

204 views

Category:

Documents


11 download

TRANSCRIPT

Page 1: Sat Tm 1703 Acp PDF 745kb

Automation UnitTM 1703 ACPFlexible automation and telecontrol

Power Transmission and Distribution

Page 2: Sat Tm 1703 Acp PDF 745kb

Outstanding performance:TM 1703 ACP

Rising demands for effi ciency in nearly all processes require increasingly innovative auto-mation solutions to achieve a more comprehensive and safer utilization of primary equipment. A prerequisite for this is automation systems such as TM 1703 ACP with various communications interfaces and peripheral elements that can be ex-panded by adding modules.

Flash Card

Automate simply – with TM 1703 ACPHighly complex and yet fully transparent automation solutions are not a

problem with the new TM 1703 ACP automation unit. The ACP 1703 sys-

tem concept creates the necessary technological conditions for combining

automation and telecontrol in one device. The mechanical design is based

on intelligent terminal modules that can be readily mounted on 35-mm

rails.

Versatility is essentialTM 1703 ACP permits systematic reduction of hard-wired I/O interfaces

through the direct connection of actuators and sensors with wire cross-

sections of up to 2.5 mm2. Modules for binary input and output up to

220 VDC also open up streamlining potentials on the interposing level.

For decentral input/output, individual modules can be distributed as much

as 200 m from the master controller.

TM 1703 ACP puts everything on one cardThe TM 1703 ACP receives parameter data via a

fl ash card. That means the required parameters

will always be available locally and loading via PCs

is no longer necessary. In the event that servicing

is required, replacing the component is a simple

matter of plug & play, because you can very easily

import the parameter confi guration into the re-

placement component using the fl ash card.

Therefore – and also thanks to the comprehensive

remote diagnostics functions – you can do more

to reduce downtimes to a minimum.

TM 1703 ACP understands your systemTM 1703 ACP allows you to utilize a host of different media for local and

remote communication. The universal use of the IEC 60870-5-101/103/104

standards guarantees consistent addressing from acquisition to output.

IEC 61850 is also supported. The use of many third-party protocols, how-

ever, also ensures the seamless integration into existing automation

networks, thereby guaranteeing the long-term protection of your previous

investments.

Consistently simple engineeringAn essential aspect in the overall economic assessment of a process is the

costs for the erection and maintenance of automation systems. You’re es-

pecially on the safe side with the SAT 1703 automation family. That’s be-

cause the use of the object-oriented engineering system SAT Toolbox II

makes it possible to utilize the properties of the same types of primary

units and equipment (such as pumps, circuit-breakers, feeders, etc.) also

for the parameter confi guration.

In addition, the close interfacing with the design tool such as ELCAD en-

sures the consistent, uniform documentation of the global system all the

way down to the circuit diagram level. Open-loop and closed-loop control

functions are created in CAEx plus according to IEC 61131-3, thereby con-

siderably reducing the necessary staff training times. SAT Toolbox II

allows you to carry out all engineering, from system diagnostics to online

testing, also from remote locations.

Page 3: Sat Tm 1703 Acp PDF 745kb

TM 1703 ACP:The main benefi ts at a glance

TM 1703 ACP offers you automation

with integrated telecontrol for hydro-

electric power stations (such as the

TC 1703 turbine controller), distributi-

on and transmission of electric power,

oil and gas pipelines, traffi c (railroads,

tunnels, etc.).

TM 1703 ACP provides powerful

communication with up to four serial

interfaces, serial and LAN/WAN

communication according to

IEC 60870-5-101/103/104, IEC 61850,

Profi bus DP, and many third-party

protocols.

Simple engineering thanks to the crea-

tion of open-loop and closed-loop con-

trol functions according to IEC 61131-3,

object orientation, and consistent data

management, as well as the option to

perform all engineering tasks from

remote locations as well.

Simplifi ed service through storing of

parameters and fi rmware on fl ash

card; thus modules can be replaced via

plug & play, even without a tool.

TM 1703 ACP, the intelligent terminal

on 35-mm rails: direct connection of

actuators and sensors through wire

cross-sections of up to 2.5 mm2,

distributable peripherals, and binary

input/output also for 110/220 VDC.

Page 4: Sat Tm 1703 Acp PDF 745kb

TM 1703 ACP in practical use

A TM 1703 ACP is an automa-tion unit within the SAT 1703 system family, consisting of the master control element and the peripheral elements that can be expanded by add-ing modules and arranged in distributed locations.

Master control element Up to four communications interfaces via

insertable serial interface modules for:

– serial communication (point-to-point,

multipoint, and dial-up traffi c)

– LAN/WAN (Ethernet)

– Profi bus DP

Interfacing of up to 16 peripheral elements

via the serial Ax-1703 peripherals bus

(16 mbps)

Function diagram design according to

IEC 61131-3 with CAEx plus for open-loop

and closed-loop control functions

Confi gurable telecontrol functions with

and without time tagging

Time synchronization via minute pulse,

time signal receiver, serial communications

link or NTP server (LAN/WAN)

Parameter setting, diagnostics, and testing

by SAT Toolbox II, both locally or from

remote locations

Storing of parameters and fi rmware on

fl ash card

Peripheral element One peripheral element consists of a

power supply, peripheral interface and

up to eight I/O modules

Direct connection of the signal cables

via pull-off screw terminals

Acquisition, processing, and output of

process data

Exchange of process data with the

master control element via the serial

Ax-1703 peripheral bus

IEC 60870-5-104

Peripheral elements

Process control system

NTP

SAT Toolbox II

Master control element

16 mbps

Profi bus DP(optional)

IEC 60870-5-101

TM 1703 ACP

Page 5: Sat Tm 1703 Acp PDF 745kb

Technical dataModel number

Master control element CP-6003/CPC65 Processing and communication

Peripheral elements Periphery interfacing

Power supply

I/O modules

PE-6400

PE-6401

PS-6620

PS-6630

PS-6632

DI-6100

DI-6101

DI-6102

DI-6103

DO-6200

DO-6212

AI-6300

AI-6303

AI-6307

AI-6310

AO-6380

TE-6420

TE-6450

Periphery interfacing for A x 1703 electrical peripherals bus

Periphery interfacing for A x 1703 optical peripherals bus

Power supply module 24–60 VDC

Power supply module 24–60 VDC EMC+

Power supply module 110–220 VDC EMC+

Binary input 2 x 8, 24/60 VDC

Binary input 2 x 8, 110–220 VDC

Binary input 2 x 8, 24–60 VDC 1ms

Binary input 2 x 8, 110/220 VDC 1ms

Binary output transistor 2 x 8, 24–60 VDC

Binary output relay 1 x 8, 24–220 VDC/230 VAC

Analog input 2 x 2, ±20 mA/±10 mA/±10 V

Direct transformer input (4 x 220 V, 3 x 6 A)

Analog input 2 x 2, ±5 mA

Analog input 2 x 2 Pt100

Analog output 4 x ±20 mA/±10 mA/±10 V

Speed measurement 2 x 2 5 VDC/24 VDC/NAMUR

Position measurement 2 x 2 SSI/RS-422

Open-loop and closed-loop control functions

256 kB for user programs, approx. 50,000 variables and signals,

2,000 of which buffered, 250 buffered setpoint values

Third-party protocols Modbus, DNP 3.0, IEC 61107, ...

EMC IEC 60870-2, IEC 60255, IEC 61000, EN 50082, ...

Supply voltage 24–60 VDC +30 %/–20 %

Temperature range Master control element: –25 ... +65 °C (depending on hardware confi guration)

Peripheral element: –25 ... +70 °C

Relative humidity 5 to 95 % non-condensing (IEC 60654, IEC 60870-2)

Vibration and shock resistance IEC 60068-2, IEC 60870-2-2 Cl. Bm, IEC 60255-21 Cl. 1

Dimensions Master control element: 306 x 155 x 75 (W x H x D)

Peripheral element: 630 x 127 x 72 (W x H x D) = fully equipped peripheral element with 8 I/O modules

Page 6: Sat Tm 1703 Acp PDF 745kb

Siemens AG

Power Transmission

and Distribution

Energy Automation Division

P.O. Box 4806

90026 Nuremberg

Germany

www.siemens.com/energy

The information in this document contains general

descriptions of the technical options available, which

do not always have to be present in individual cases.

The required features should therefore be specified

in each individual case at the time of closing the

contract.

Subject to change without prior notice

Order-No. E50001-U321-A252-X-7600

Printed in Germany

Dispo 06200

TH 345-060135 101790 PA 04062.0

If you have any question about

Power Transmission and Distribution,

our Customer Support Center

is available around the clock.

Tel.: +49 180/524 70 00

Fax: +49 180/524 24 71

(Subject to changes, e.g.: 12 ct/min.)

E-mail: [email protected]

www.siemens.com/energy-support