PROVIDE AND INSTALL A NEW AUTOMATIC AND MANUAL FIRE ALARM SYSTEM AS SHOWN ON DRAWINGS. ALL WIRING TO BE CLASS B. WIRING IS STYLE Y FOR NOTIFICATION APPLIANCE CIRCUITS, STYLE B FOR INITIATING DEVICE CIRCUITS, AND STYLE 4 FOR SIGNALING LINE CIRCUITS. AUTOMATIC FIRE ALARM SYSTEM SHALL TRANSMIT THE ALARM, SUPERVISORY AND TROUBLE SIGNALS TO AN APPROVED SUPERVISING STATION. THE SUPERVISING STATION SHALL BE LISTED AS EITHER UUFX OR UUJS UNDERWRITERS LABORATORY OR SHALL MEET THE REQUIREMENTS OF FACTORY MUTUAL RESEARCH APPROVAL STANDARD 3011. SUPERVISION OF SYSTEM AND LEASED TELEPHONE LINES SHALL BE ARRANGED BY THE OWNER. SUPERVISORY ALARM TROUBLE MISC. EFFECT AL A RM AT F A CP SINGLE GROUND WIRE-TO-WIRE SHORT NOTIFICATION APPLIANCE CIRCUIT (NAC) - CLASS B: SINGLE OPEN CAUSE WATERFLOW SWITCH SINGLE GROUND FIRE ALARM WIRING: AC POWER FAILURE WIRE-TO-WIRE SHORT SIGNALING LINE CIRCUIT (SLC) - CLASS B: SYSTEM RESET TAMPER SWITCH SINGLE OPEN SIGNAL SILENCE ACT IVATE A UDIBL E AND VIS I B LE ALARM S THRO UGO UT AL A RM AT ANNUNC I ATOR SMOKE DETECTOR ELEV. LOBBY RECA L L ELEVATOR TO DESI G NATED FLOO R MANUAL PULL STATION SMOKE DETECTOR ELEV. MACH. ROOM HEAT DETECTOR EL E V AT OR POWER S H UNT T R I P AREA SMOKE DETECTOR HEAT DETECTOR ELEV. MACH. ROOM DEAC T I VATE A U DIB L E AND VI SI B L E ALARM S T RO U BL E AT F ACP T RO U BL E SIGNAL T O CENTR A L MON I T O RI N G S TA TION T RO U BLE A T ANNUNCIATOR SUPE RV I SO R Y S I GNAL T O CEN T RA L M ONITORI NG STA TION SUP ERVISORY A T A N NUNC I ATOR SUP ERVISORY A T FACP SY ST E M NO R MAL REMARKS ACTI VATE F I REMAN 'S HAT I NSI DE E LEV. C A B AL AR M SIGNAL T O CEN T RAL M ONITORI NG S TATI ON SHUT DO W N H V A C UN IT DUCT MOUNTED SMOKE DETECTOR DI SPLAY C HANGE OF STATUS FIRE ALARM SYSTEM LOW BATTERY POST INDICATOR VALVE SWITCH # P C # # # # #W C C # WP #W WP #W AOM AIM WF VS LIM 10K # = CANDELA RATING WALL MOUNT MULTI-CANDELA WEATHERPROOF STROBE ONLY, WHITE SIMPLEX 49VO-WWFO-BA 49WPBB-AVVOWW BACK BOX SUPPLIED BY SIMPLEXGRINNELL WBB-W SPEAKER ONLY, WALL MOUNT, WEATHERPROOF WHEELOCK ET-1010W #W=SPEAKER TAP 7320-0785:0105 AREA=0.0196 SQ. INCH SG ANIX./PAIGE 740214L B SG ANIX./PAIGE 740215 AREA=0.0196 SQ. INCH RUI/N2 COMMUNICATION 1 PAIR 18 AWG TWISTED OVERALL SHIELD ANIXTER PART NUMBER T740215 FAMC-1802C-1-2S-03B5 ANIXTER PART NUMBER CONDUCTOR AREA 0.12 SQ INCH * 0.21 SQ INCH * 0.34 SQ INCH * CONDUIT SIZE 1" 3/4" 1/2" * 40% FILL PER N.E.C. 2" CONDUIT SIZE 1-1/4" 1-1/2" CONDUCTOR AREA 0.60 SQ INCH * 0.82 SQ INCH * 1.34 SQ INCH * THE CABLES SPECIFIED HERE ARE FOR REFERENCE OF REQUIRED ELECTRICAL CHARACTERISTICS AS WELL AS CODE REQUIREMENTS. ALTERNATE SUPPLIERS MAY BE SUBSTITUTED PROVIDING EQUIVALENT CHARACTERISTICS ARE MAINTAINED. ITEMS SUCH AS CAPACITANCE BETWEEN CONDUCTORS AND WIRE GAUGE CAN BE CRUCIAL TO THE CIRCUIT DESIGN OF THIS SYSTEM INSTALLATION. REFERENCE https://www.anixter.com/customer/tycofs FOR SG ANIXTER CABLE DATA S AUDIO CIRCUIT 1 PAIR 16 AWG TWISTED UNSHIELDED SG ANIX./PAIGE 454731ARE AREA=0.0272 SQ. INCH AREA=0.0209 SQ. INCH SG ANIX./PAIGE 454740ARE FA-1602C-1-1N-03-BX ANIXTER PART NUMBER FA-1602C-1-2N-03 ANIXTER PART NUMBER R RELAY CIRCUIT 2 CONDUCTOR 14 AWG SOLID AREA=0.0097 SQ. INCH (EACH) (2) #14 AWG SG ANIX./PAIGE 454718ARE AREA=0.0380 SQ. INCH AREA=0.0333 SQ. INCH SG ANIX./PAIGE 454719ARE ANIXTER PART NUMBER FA-1402C-1-1N-03-BX FA-1402C-1-2N-03 ANIXTER PART NUMBER AREA=0.0272 SQ. INCH SG ANIX./PAIGE 454731ARE P AREA=0.0208 SQ. INCH SG ANIX./PAIGE 454740ARE POWER CIRCUIT 2 CONDUCTOR 16 AWG SOLID (SUBSCRIPT "r" IF RESETTABLE) FA-1602C-1-1N-03-BX ANIXTER PART NUMBER FA-1602C-1-2N-03 ANIXTER PART NUMBER AREA=0.0072 SQ. INCH (EACH) (4) #16 AWG M MAPNET/IDNET CIRCUIT 1 PAIR 18 AWG TWISTED OVERALL SHIELD AREA=0.0196 SQ. INCH SG ANIX./PAIGE 740214L SG ANIX./PAIGE 740215 AREA=0.0196 SQ. INCH ANIXTER PART NUMBER T740215 FAMC-1802C-1-2S-03B5 ANIXTER PART NUMBER L REMOTE LED CIRCUIT 2 CONDUCTOR 16 AWG SOLID AREA=0.0072 SQ. INCH (EACH) (2) #16 AWG AREA=0.0272 SQ. INCH SG ANIX./PAIGE 454731ARE AREA=0.0208 SQ. INCH SG ANIX./PAIGE 454740ARE FA-1602C-1-1N-03-BX ANIXTER PART NUMBER FA-1602C-1-2N-03 ANIXTER PART NUMBER K REMOTE TEST SWITCH/ LED CIRCUIT - (2) 2 CONDUCTOR 18 AWG SOLID AREA=0.0055 SQ. INCH (EACH) (4) #18 AWG SG ANIX./PAIGE 454703ARE AREA=0.0204 SQ. INCH AREA=0.0141 SQ. INCH SG ANIX./PAIGE 740132R ANIXTER PART NUMBER FA-1802C-1-1N-03-BX FA-1802C-1-2N-03 ANIXTER PART NUMBER SG ANIX./PAIGE 454720ARE AREA=0.0491 SQ. INCH A AREA=0.0468 SQ. INCH SG ANIX./PAIGE 454725ARE ANIXTER PART NUMBER ANIXTER PART NUMBER ADDRESSABLE NOTIFICATION CIRCUIT 12 AWG SOLID UNSHIELDED TWISTED PAIR FA-1202C-1-1N-03 FA-1202C-1-2N-03 SINGLE CONDUCTOR(THHN,TFFN) PLENUM RATED: FPLP FIRE ALARM WIRE LIST RISER RATED: FPLR CIRCUIT DESCRIPTION END-OF-LINE RESISTOR 6.8K (EOL) SIMPLEX 4081-9004 END-OF-LINE RESISTOR 4.7K (EOL) END-OF-LINE RESISTOR 3.3K (EOL) END-OF-LINE RESISTOR 10K (EOL) SIMPLEX 4081-9003 SIMPLEX 4081-9002 SIMPLEX 4081-9008 SINGLE GANG BOX 2 1/8" DEEP W/COVER ENCAPSULATED RELAY SIMPLEX 4098-9843 SINGLE GANG BOX 2 1/2" DEEP REMOTE TEST STATION W/ LED AND KEY SWITCH SIMPLEX 2098-9806 MOUNT TO DUCTWORK DUCT SMOKE SENSOR SIMPLEX 4098-9756 WATERFLOW SWITCH INSTALLED BY MECHANICAL CONTRACTOR SUPPLIED BY OTHERS TAMPER SWITCH INSTALLED BY MECHANICAL CONTRACTOR SUPPLIED BY OTHERS SERIAL LCD ANNUNCIATOR SIMPLEX 4603-9101 6 GANG BOX 3 1/2" DEEP 4" SQUARE BOX 1 1/2" DEEP W/ 1 1/2" RING SPEAKER ONLY, CEILING MOUNT SIMPLEX 4902-9721 #W = SPEAKER TAP W/4905-9942 ADAPTER SKIRT WHEN SURFACE MOUNTED 4" SQUARE BOX 1 1/2" DEEP W/ 1 1/2" RING SPEAKER ONLY, WALL MOUNT SIMPLEX 4902-9717 #W = SPEAKER TAP # =CANDELA RATING ADDRESSABLE CEILING MOUNT MULTI-CANDELA STROBE ONLY WHITE SIMPLEX 4906-9204 HANDY BOX 1 1/2" DEEP W/4905-9940 ADAPTER SKIRT WHEN SURFACE MOUNTED # = CANDELA RATING WALL MOUNT MULTI-CANDELA STROBE ONLY, WHITE SIMPLEX 49VO-WWF 4" SQUARE BOX 1 1/2" DEEP 4" SQUARE BOX 1 1/2" DEEP W/ 1 1/2" EXTENSION RING # =CANDELA RATING, #W = SPEAKER TAP SIMPLEX 4906-9254 CEILING MOUNT, WHITE ADDRESSABLE MULTI-CANDELA SPEAKER/STROBE, W/4905-9946 ADAPTER SKIRT WHEN SURFACE MOUNTED 4" SQUARE BOX 1 1/2" DEEP W/ 1 1/2" EXTENSION RING # =CANDELA RATING, #W = SPEAKER TAP SIMPLEX 4906-9253 WALL MOUNT, WHITE ADDRESSABLE MULTI-CANDELA SPEAKER/STROBE, 4" SQUARE BOX 2 1/8" DEEP W/TWO GANG COVER RELAY IAM SIMPLEX 4090-9002 SINGLE GANG BOX 2 1/2" DEEP WITH COVER INDIVIDUAL ADDRESSABLE MODULE SIMPLEX 4090-9001 HEAT SENSOR / BASE SIMPLEX 4098-9792 BASE SIMPLEX 4098-9733 4" OCTAGONAL BOX 1 1/2" DEEP SMOKE SENSOR / BASE 4" OCTAGONAL BOX 1 1/2" DEEP SIMPLEX 4098-9792 BASE SIMPLEX 4098-9714 NO GRIP MANUAL PULL STATION 4" SQUARE BOX 2 1/8" DEEP W/SINGLE GANG COVER SIMPLEX 4099-9020 (REFER TO MOUNTING DETAIL FOR SPECIFIC DIMENSIONS) SUPPLIED BY SIMPLEXGRINNELL SIMPLEX 4100-9111 FIRE ALARM CONTROL PANEL FIRE ALARM SYMBOLS LEGEND SYMBOL DESCRIPTION MODEL# BACKBOX 7300-0026:0150 3240-0026:0241 7120-0026:0179 7125-0026:0371 7320-0026:0242 7320-0026:0242 7125-0026:0235 7125-0026:0373 7320-0026:0322 7320-0026:0322 7300-0026:0223 7300-0026:0223 7270-0026:0216 7300-0026:0217 7300-0026:0217 7272-0026:0218 7150-0026:0224 7165-0026:0251 CSFM # **USE 70 VOLT TAP** **USE 70 VOLT TAP** **USE 70 VOLT TAP** **USE 70 VOLT TAP** REFER TO BATTERY CHARTS W / VARIOUS BATTERY SETS DEVICE DESIGNATOR S2-1 SPEAKER DEVICE SPEAKER CIRCUIT DEVICE ADDRESS A1:2-1(1) ADDRESSABLE NOTIFICATION DEVICE ADDRESSABLE POWER SUPPLY CHANNEL DESIGNATOR (EPS, TPS) BRANCH/REPEATER DESIGNATOR (OPT.) (#) BRANCH, (E#:#) REPEATER:BRANCH DEVICE ADDRESS M2-1 ADDRESSABLE DEVICES NUMBERING ADDRESSABLE CARD (IDNET OR MAPNET) 1. THESE DRAWINGS DEPICT GENERAL LOCATIONS OF LIFE SAFETY EQUIPMENT & FIELD DEVICES. EXACT ROUTING OF CONDUITS TO BE DETERMINED IN THE FIELD BY THE INSTALLING CONTRACTOR TO SUIT CONDITIONS. ALL CHANGES SHALL BE CLEARLY INDICATED ON THE RECORD DRAWINGS. 2. SHOULD ANY CONDITIONS EXIST THAT DIFFER FROM WHAT IS INDICATED ON THESE DRAWINGS WHICH CAUSE MAJOR DEVIATIONS IN THE WORK SHOWN, THE CONTRACTOR SHALL CONTACT SIMPLEXGRINNELL IN A TIMELY MANNER SO AS NOT TO IMPAIR THE CONSTRUCTION SCHEDULE. 3. CONTRACTOR IS RESPONSIBLE FOR MAKING AND OBTAINING APPROVAL FOR ALL NECESSARY ADJUSTMENTS IN CIRCUITING AS REQUIRED TO ACCOMMODATE THE RELOCATION OF EQUIPMENT AND/OR DEVICES WHICH ARE AFFECTED BY ANY AUTHORIZED CHANGE. ALL CHANGES SHALL BE CLEARLY INDICATED ON THE RECORD DRAWINGS. 4. A STAMPED SET OF APPROVED FIRE ALARM DRAWINGS SHALL BE AT THE JOB SITE AND SHALL BE USED FOR INSTALLATION. 5. THE POWER CIRCUIT TO THE FACP AND TO THE FIRE ALARM POWER SUPPLIES SHALL BE ON A DEDICATED 120V, 20A BRANCH CIRCUIT BREAKER, AND SHALL HAVE A RED MARKING, LOCK-ON PROVISION AND SHALL BE IDENTIFIED AS "FIRE ALARM CIRCUIT CONTROL." THE LOCATION OF THE CIRCUIT DISCONNECT MEANS (CIRCUIT BREAKER) SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM CONTROL UNIT. 6. UPDATE THE AS-BUILT DRAWING SET DAILY WITH JOB PROGRESS. RETURN THE AS-BUILT DRAWING SET TO SIMPLEXGRINNELL NO LATER THAN 7 DAYS AFTER FINAL TEST. 7. THE CONTRACTOR WILL MAINTAIN ALL AREAS OF THE BUILDING IN A NEAT AND WORKMAN LIKE MANNER. 8. DO NOT APPLY POWER EXCEPT IN THE PRESENCE OF A FACTORY TRAINED SIMPLEXGRINNELL TECHNICAL REPRESENTATIVE. 9. ANY SMOKE DETECTOR HEAD INSTALLED BEFORE THE BUILDING IS CLEANED AND ACCEPTED SHALL BE COVERED TO PROTECT FROM DUST. ANY FALSE ALARMS DUE TO DIRT CONTAMINATED HEADS SHALL BE THE RESPONSIBILITY OF THE FIRE ALARM INSTALLER. 10. THE FIRE ALARM INSTALLER WILL MAINTAIN THE FIRE RESISTANCE INTEGRITY OF ALL WALL, CEILING, AND ROOF ASSEMBLIES ANY TIME THAT WORK IS NOT ACTIVELY BEING PERFORMED. 11. INSTALLATION OF DEVICES SHALL BE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. POWER LIMITED AND NON-POWER LIMITED FIELD WIRING MUST BE INSTALLED WITHIN THE FACP ENCLOSURE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND NEC. 12. ALL WIRING SHALL BE INSTALLED ACCORDING TO NFPA 70 (NEC). 13. FIRE ALARM CIRCUITS SHALL BE IDENTIFIED IN ACCORDANCE WITH APPROPRIATE SECTION OF NEC 760. MARK ALL FIRE ALARM WIRES IN ACCORDANCE WITH NEC 760 SECTIONS FOR POWER LIMITED AND NON-POWER LIMITED WIRE. 14 FIRE ALARM CABLE INSTALLED IN DUCTS, PLENUM, AND OTHER SPACES USED FOR ENVIRONMENTAL AIR SHALL BE TYPE FPLP. 15. FIRE ALARM CABLE INSTALLED IN THE VERTICAL RUNS AND PENETRATE MORE THAN ONE FLOOR OR CABLES INSTALLED IN VERTICAL RUNS IN SHAFTS SHALL BE TYPE FPLR. 16. FIRE ALARM CABLE INSTALLED IN UNDERGROUND CONDUIT OR OTHER WET LOCATIONS SHALL BE UL LISTED FOR WET LOCATIONS. 17. FIRE ALARM CIRCUITS EXTENDING BEYOND ONE BUILDING AND RUN OUTDOOR SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 70 ARTICLES 760, 770, 725 AND 800 WHERE APPLICABLE. 18. ALL WIRING, INCLUDING SHIELDS MUST BE DRY AND FREE OF SHORTS AND GROUNDS. 19. ALL SHIELDED WIRE MUST HAVE SHIELD CONTINUITY AT FULL LENGTH OF THE WIRE. 20. ONLY SYSTEM WIRING CAN BE RUN IN THE SAME CONDUIT. 21. 120VAC IS NOT PERMITTED IN THE SAME CONDUIT WITH LOW VOLTAGE WIRING. 22. MAINTAIN 40 PERCENT CONDUIT FILL RATIO AS PER NEC REQUIREMENTS. 23. EXISTING CONDUITS MAY BE USED BY THE INSTALLATION CONTRACTOR AS DEEMED NECESSARY, HOWEVER, ANY EXISTING CONDUIT WILL BE USED ONLY IF CONDUITS MEET CURRENT STANDARDS AND CODES. SIMPLEXGRINNELL MAKES NO STATEMENTS WRITTEN OR VERBAL AS TO THE CONDITION OF EXISTING CONDUITS. SYMBOL KEY SYSTEM DESCRIPTION / SCOPE OF WORK GENERAL NOTES FIRE ALARM APPLICABLE CODES & STANDARDS SEQUENCE OF OPERATION DEVICE ADDRESSING LEGEND ABBREVIATIONS LEGEND = = = = = = = = = = = = = = = = = = = = = = = = = W/ TYP UON VT WF W VCC TRBL MAX NIC NTS SMK SLC NPU SCC TAC SUPV MIN N/A NAC NEC NDU NFPA HT HVAC UNLESS OTHERWISE NOTED VOICE COMMAND CENTER WITH VALVE TAMPER WATER FLOW (eg. 1/2W) WATT TROUBLE TYPICAL MAXIMUM NOTIFICATION APPLIANCE CIRCUIT EXTENDER SIGNALING LINE CIRCUIT NATIONAL ELECTRICAL CODE NETWORK PROCESSING UNIT NETWORK DISPLAY UNIT STATUS COMMAND CENTER NATIONAL FIRE PROTECTION ASSOCIATION TRUEALERT ADDRESSABLE CONTROLLER NOT IN CONTRACT NOT TO SCALE SUPERVISORY SMOKE NOT APPLICABLE MINIMUM HEATING, VENTILATION, & AIR CONDITIONING HEIGHT = W/O WITH OUT = TS TAMPER SWITCH = IMS INFORMATION MANAGEMENT SYSTEM = PAP PRE-ACTION PANEL JURISDICTIONS WITHIN THE STATE MAY HAVE AMENDMENTS TO THE STATE ADOPTED CODE. CHECK WITH THE LOCAL JURISDICTION AUTHORITY FOR MORE DETAILS. END OF LINE EXPLOSION PROOF EMERGENCY POWER OFF FIRE ALARM CONTROL PANEL FIRE ALARM TERMINAL CABINET FURNISHED BY OTHERS FIRE COMMAND CENTER EOL = XP = EPO = FACP = FATC = FBO = FCC = WEATHERPROOF DETECTOR (eg. 15CD) CANDELA ANNUNCIATOR ALARM ABOVE FINISHED FLOOR CALIFORNIA BUILDING CODE CALIFORNIA STATE FIRE MARSHAL AUTHORITY HAVING JURISDICTION BUILDING MANAGEMENT SYSTEM DATA GATHERING PANEL = ALM CBC = DET = CSFM = CD = ANN = BMS = = DGP WP = = AFF AHJ = = FSD FIRE SMOKE DAMPER FIRE ALARM ANNUNCIATOR FAA = FIRE ALARM TRANSPONDER FTR = HIGH HUMIDITY H = EXISTING TO REMAIN CEILING MOUNTED ABOVE CEILING RELOCATED DEVICE EXISTING DEVICE TO BE RELOCATED REMOVE EXISTING AND REPLACE W/NEW EXISTING TO REMOVE AND COVER RC RD = RR = = RL = C = E = AC = SHEET INDEX WELLNESS CENTER SHEET INDEX VISUAL/SIGNAL CIRCUIT - 2 CONDUCTOR 12 AWG STRANDED, UNSHEILDED DIRECT BURIAL/UNDERGROUND IN CONDUIT/AERIAL (REQUIRES MESSENGER) - CABLE ANIXTER PART NUMBER 2A-1202 AREA=0.0820 SQ. INCH Vb CONDUIT ONLY: THWN (2) #12 AWG (RED/BLACK) AREA=0.0133 SQ. INCH (EACH) DIRECT BURIAL/UNDERGROUND IN CONDUIT/AERIAL (REQUIRES MESSENGER) - CABLE SPEAKER CIRCUIT - 1 PAIR 18 AWG TWISTED OVERALL SHIELD ANIXTER PART NUMBER 2AS-1801POS AREA=0.0615 SQ. INCH Sb DIRECT BURIAL/UNDERGROUND IN CONDUIT/AERIAL (REQUIRES MESSENGER) - CABLE MAPNET/IDNET CIRCUIT - 1 PAIR 18 AWG TWISTED OVERALL SHIELD ANIXTER PART NUMBER 2AS-1801POS AREA=0.0615 SQ. INCH Mb WIRING THAT LEAVES THE BUILDING WIRE SCHEDULE DSA NOTES 4" SQUARE BOX 2 1/8" DEEP W/TWO GANG COVER LINE ISOLATOR MODULE SIMPLEX 4090-9116 7300-0026:0252 P FAA OCCUPANCY TYPE: A-3 ASSEMBLY GROUP A-4 ASSEMBLY GROUP SPRINKLER PROTECTION: BUILDING IS FULLY SPRINKLED CALIFORNIA BUILDING CODE, 2013 EDITION, TITLE 24, PART 2 CALIFORNIA FIRE CODE, 2013 EDITION, TITLE 24, PART 9 CALIFORNIA ELECTRIC CODE, 2013 EDITION, TITLE 24, PART 3 CALIFORNIA ELEVATOR SAFETY CONSTRUCTION CODE, 2013 EDITION NFPA 72, 2013 EDITION WITH CALIFORNIA AMENDMENTS B BUSINESS GROUP S-1 STORAGE GROUP 1. APPLICABLE STANDARD AND CODES: 2013 NFPA 72 2013 CALIFORNIA FIRE CODE 2013 CALIFORNIA BUILDING CODE 2013 CALIFORNIA MECHANICAL CODE 2013 CALIFORNIA ELECTRICAL CODE 2. INSTALLATION OF THE SYSTEM SHALL NOT BE STARTED UNTIL DETAILED DESIGN DOCUMENTS AND SPECIFICATIONS, INCLUDING STATE FIRE MARSHAL LISTING NUMBERS FOR EACH COMPONENT OF THE SYSTEM, HAVE BEEN APPROVED BY DSA. 3. UPON COMPLETION OF THE INSTALLATION OF THE SYSTEM, A SATISFACTORY TEST OF THE ENTIRE SYSTEM SHALL BE MADE IN THE PRESENCE OF A DSA PROJECT INSPECTOR. 4. A STAMPED SET OF APPROVED FIRE ALARM DESIGN DOCUMENTS SHALL BE MAINTAINED ON THE JOB SITE AND USED FOR INSTALLATION. 5. ANY DISCREPANCIES BETWEEN THE DRAWINGS AND THE CODE OR RECOGNIZED STANDARDS SHALL BE BROUGHT TO THE ATTENTION OF DSA AND THE ARCHITECT/ENGINEER OF THE PROJECT. 6. DSA, ARCHITECT/ENGINEER AND OWNER SHALL BE NOTIFIED A MINIMUM OF 48 HOURS PRIOR TO THE FINAL INSPECTION AND /OR TESTING. 7. ALL PENETRATIONS THROUGH RATED ASSEMBLIES REQUIRING OPENING PROTECTION SHALL BE PROVIDED WITH A PENETRATION FIRE STOP SYSTEM AS IDENTIFIED IN CBC CHAPTER 7, UL OR OTHER LAB TESTING CRITERIA. 8. WALL MOUNTED VISUAL NOTIFICATION APPLIANCES SHALL HAVE THEIR BOTTOMS MOUNTED AT 80” MINIMUM AND 96” MAXIMUM ABOVE FINISHED FLOOR. 9. WALL MOUNTED AUDIBLE NOTIFICATION APPLIANCES SHALL HAVE THEIR TOPS MOUNTED AT 90” MINIMUM AND 96” MAXIMUM ABOVE FINISHED FLOOR AND NO CLOSER THEN 6” TO A HORIZONTAL STRUCTURE. 10. AUDIBLE APPLIANCES TO PROVIDE SOUND LEVEL AT LEAST 15 dB ABOVE THE AVERAGE AMBIENT SOUND LEVEL BUT NOT LESS THAN 75 dB AT 10 FEET OR MORE THAN 110 dB AT THE MINIMUM HEARING DISTANCE . SOUND LEVEL SHALL ACHIEVE 5 dB ABOVE MAXIMUM SOUND LEVEL HAVING DURATION OF AT LEAST 60 SECONDS. MEASURE SOUND LEVEL AT FIVE FEET ABOVE FINISHED FLOOR. 11. AUDIBLE APPLIANCES SHALL BE SYNCHRONIZED TEMPORAL CODE 3 PATTERN. 12. THE CONTRACTOR SHALL ADJUST/INSTALL ALL DEVICES TO MAXIMIZE PERFORMANCE AND TO MINIMIZE FALSE ALARMS. 13. VISUAL APPLIANCES SHOULD NOT EXCEED 2 FLASHES PER SECOND AND SHOULD NOT BE SLOWER THAN 1 FLASH EVERY SECOND. THE DEVICE SHALL HAVE A PULSING LIGHT SOURCE NOT LESS THAN 15 CANDELA. VISUAL APPLIANCES WITHIN 55' FROM EACH OTHER SHALL BE SYNCHRONIZED. 14. UNDERGROUND AND EXTERIOR CONDUITS TO HAVE WATERTIGHT FITTINGS AND WIRE TO BE APPROVED FOR WET LOCATIONS. 15. ALL FIRE ALARM WIRING SHALL BE FLP OR FPLP (FIRE POWER LIMITED OR FIRE POWER LIMITED PLENUM) AS REQUIRED FOR APPLICATION. WIRING IN CONDUIT ABOVE GROUND MAY BE THHN OR THWN. 16. PER CEC STANDARDS, ALL WIRING IS TO BE PULLED THROUGH EACH JUNCTION BOX AND CONNECTED DIRECTLY TO EACH FIRE DEVICE. DO NOT SPLICE THE WIRE. THERE MUST BE AT LEAST 6" OF LEAD WIRE FROM THE BOX TO THE DEVICE. ALL BOXES TO BE SIZED PER CEC. 17. SMOKE DETECTORS SHALL NOT BE INSTALLED CLOSER THAN 1' FROM FIRE SPRINKLERS OR 3' FROM ANY SUPPLY DIFFUSER. IN AREA OF CONSTRUCTION OR POSSIBLE DAMAGE/CONTAMINATION, NEWLY INSTALLED FIRE ALARM DEVICES SHALL BE COVERED UNTIL THAT AREA IS READY TO BE TURNED OVER TO THE OWNER. 18. ALL FIRE ALARM CIRCUITS SHALL BE IN CONDUIT, SURFACE RACEWAY OR OPEN RUN ABOVE CEILINGS, UNDER FLOORS AND IN WALLS IN A NEAT AND PROTECTED MANNER AS INDICATED ON DESIGN DOCUMENTS. EXPOSED CIRCUITS ARE ONLY PERMITTED WHEN NOTED AS EXPOSED ON DESIGN DOCUMENTS. 19. FIRE ALARM PANEL, REMOTE PANELS, POWER SUPPLIES AND COMPONENTS SHALL BE SECURED TO MOUNTING SURFACES PER MANUFACTURERS SPECIFICATIONS. NO SINGLE DEVICE SHALL EXCEED THE WEIGHT OF 20 LBS. WITHOUT SPECIAL MOUNTING DETAILS. 20. A DEDICATED BRANCH CIRCUIT SHALL BE PROVIDED FOR FIRE ALARM EQUIPMENT. THIS CIRCUIT SHALL BE ENERGIZED FROM THE COMMON USE AREA PANEL AND SHALL HAVE NO OTHER OUTLETS. THE BREAKER SHALL HAVE A RED LOCKING DEVICE TO BLOCK THE HANDLE IN THE “ON” POSITION. THE CIRCUIT BREAKER SHALL BE LABELED “FIRE ALARM CIRCUIT CONTROL”. CIRCUIT ID TO BE LABELED AT FIRE PANEL/EXTENDERS. 21. THE INSTALLING CONTRACTOR SHALL PROVIDE A RECORD OF COMPLETION PER NFPA 72, FIGURE 10.18.2.1.1. 22. CONTROL PANELS AND REMOTE ANNUNCIATORS SHALL BE INSTALLED WITH THEIR BOTTOMS MOUNTED AT 48” ABOVE FINISHED FLOOR. 23. THE INSTALLING CONTRACTOR SHALL PROVIDE SYSTEM PROGRAMMING FOR SUPERVISORY MONITORING PER CBC SECTION 901.6.2. 24. SUPERVISORY MONITORING SHALL BE TESTED AND VERIFIED AS SENDING CORRECT SIGNALS IN CONJUNCTION WITH FINAL ACCEPTANCE TEST. 25. OWNER SHALL BE RESPONSIBLE FOR ESTABLISHING A FIRE SYSTEM MONITORING CONTRACT OR PROVISIONS. E F O R P D E R E T S I G E R R E E N I G N E L A N O I S S C A L I F O R N I A S T A T E O F R I C A L E L E C T No. E16806 J A S O N L A U E N G I N E E R I N G I N T E R F A C E TEL FAX PROJECT CONTACT www.interfaceengineering.com 717 Market Street Suite 500 San Francisco, CA 94103 415.489.7240 415.489.7289 SHEET NO: DATE: PROJECT NO: THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2009. THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. CONSULTANT 6 9 10 5 3 11 12 8 7 4 2 1 J K H G F E D C B A B A J K H G F E D C 6 9 10 5 3 11 12 8 7 4 2 1 NO. ISSUE DATE ARCHITECT'S STAMP APPROVAL Joe Ripp 2014-0174 SAN JOSE CITY COLLEGE PHYSICAL EDUCATION BUILDING AND RENOVATED LAB BUILDING SAN JOSE, CALIFORNIA SYMBOLS LISTS, GENERAL NOTES AND SHEET INDEX - FIRE ALARM FA0.01 1.12.2015 1089-0001 DSA SUBMITTAL FA0.01 SYMBOLS LISTS, GENERAL NOTES AND SHEET INDEX - FIRE ALARM FA1.01 SITE PLAN - FIRE ALARM FA2.01 1ST FLOOR PLAN - PHYSICAL EDUCATION BUILDING - FIRE ALARM FA2.02 2ND FLOOR PLAN - PHYSICAL EDUCATION BUILDING - FIRE ALARM FA4.01 ONE-LINE DIAGRAM - FIRE ALARM FA5.01 CONTROL PANEL DIAGRAM - FIRE ALARM FA6.01 CALCULATIONS - FIRE ALARM FA6.02 CALCULATIONS - FIRE ALARM FA7.01 DETAILS - FIRE ALARM FA7.02 DETAILS - FIRE ALARM FA7.03 DETAILS - FIRE ALARM FA7.04 DETAILS - FIRE ALARM WFA2.03 FLOOR PLANS - WELLNESS CENTER - FIRE ALARM

Upload: vanliem

Post on 09-Sep-2018

217 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: SAN JOSE CITY - SJECCD Fire Alarm.pdf · relay iam simplex 4090-9002 4" square box 2 1/8" deep w/two gang cover individual addressable module simplex 4090-9001 single gang ... installation

PROVIDE AND INSTALL A NEW AUTOMATIC AND MANUAL FIRE ALARM SYSTEM AS SHOWN ON DRAWINGS.

ALL WIRING TO BE CLASS B. WIRING IS STYLE Y FOR NOTIFICATION APPLIANCE CIRCUITS, STYLE B FOR INITIATING DEVICE CIRCUITS, AND STYLE 4

FOR SIGNALING LINE CIRCUITS.

AUTOMATIC FIRE ALARM SYSTEM SHALL TRANSMIT THE ALARM, SUPERVISORY AND TROUBLE SIGNALS TO AN APPROVED SUPERVISING STATION. THE

SUPERVISING STATION SHALL BE LISTED AS EITHER UUFX OR UUJS UNDERWRITERS LABORATORY OR SHALL MEET THE REQUIREMENTS OF FACTORY

MUTUAL RESEARCH APPROVAL STANDARD 3011. SUPERVISION OF SYSTEM AND LEASED TELEPHONE LINES SHALL BE ARRANGED BY THE OWNER.

SUPERVISORYALARM TROUBLE MISC.

EFFECT

ALARM A

T FACP

SINGLE GROUND

WIRE-TO-WIRE SHORT

NOTIFICATION APPLIANCE CIRCUIT (NAC) - CLASS B:

SINGLE OPEN

CAUSE

WATERFLOW SWITCH

SINGLE GROUND

FIRE ALARM WIRING:

AC POWER FAILURE

WIRE-TO-WIRE SHORT

SIGNALING LINE CIRCUIT (SLC) - CLASS B:

SYSTEM RESET

TAMPER SWITCH

SINGLE OPEN

SIGNAL SILENCE

ACTIVATE A

UDIBLE

AND V

ISIB

LE A

LARMS T

HROUGOUT

ALARM A

T ANNUNCIA

TOR

SMOKE DETECTOR ELEV. LOBBY

RECALL E

LEVATOR T

O DESIG

NATED FLO

OR

MANUAL PULL STATION

SMOKE DETECTOR ELEV. MACH. ROOMHEAT DETECTOR

ELEVATO

R POW

ER SHUNT

TRIP

AREA SMOKE DETECTOR

HEAT DETECTOR ELEV. MACH. ROOM

DEACTIVATE A

UDIBLE

AND V

ISIB

LE A

LARM

S

TROUBLE A

T FACP

TROUBLE S

IGNAL

TO C

ENTRAL MONIT

ORING S

TATION

TROUBLE A

T ANNUNCIA

TOR

SUPERVISORY S

IGNAL T

O CENTRAL

MONITORIN

G STATIO

N

SUPERVISORY A

T ANNUNCIA

TOR

SUPERVISORY A

T FACP

SYSTEM NORMAL

REMARKSACTIVATE

FIR

EMAN'S H

AT INSID

E ELE

V. CAB

ALARM S

IGNAL T

O CENTRAL

MONITORIN

G STATIO

N

SHUT DOW

N HVAC U

NIT

DUCT MOUNTED SMOKE DETECTOR

DISPLA

Y CHANGE O

F STATUS

FIRE ALARM SYSTEM LOW BATTERY

POST INDICATOR VALVE SWITCH

#

P

C

#

#

#

#

#WCC

#WP

#WWP

#W

AOM

AIM

WF

VS

LIM

10K

# = CANDELA RATING

WALL MOUNT MULTI-CANDELA WEATHERPROOF STROBE ONLY, WHITE SIMPLEX 49VO-WWFO-BA 49WPBB-AVVOWW BACK BOX SUPPLIED BY SIMPLEXGRINNELL

WBB-WSPEAKER ONLY, WALL MOUNT, WEATHERPROOF WHEELOCK ET-1010W

#W=SPEAKER TAP7320-0785:0105

AREA=0.0196 SQ. INCHSG ANIX./PAIGE 740214LB SG ANIX./PAIGE 740215

AREA=0.0196 SQ. INCHRUI/N2 COMMUNICATION 1PAIR 18 AWG TWISTEDOVERALL SHIELD ANIXTER PART NUMBER

T740215 FAMC-1802C-1-2S-03B5ANIXTER PART NUMBER

CONDUCTOR AREA

0.12 SQ INCH *0.21 SQ INCH *

0.34 SQ INCH *

CONDUIT SIZE

1"3/4"1/2"

* 40% FILL PER N.E.C.

2"

CONDUIT SIZE

1-1/4"1-1/2"

CONDUCTOR AREA

0.60 SQ INCH *0.82 SQ INCH *1.34 SQ INCH *

THE CABLES SPECIFIED HERE ARE FOR REFERENCE OF REQUIRED ELECTRICAL CHARACTERISTICS

AS WELL AS CODE REQUIREMENTS. ALTERNATE SUPPLIERS MAY BE SUBSTITUTED PROVIDING

EQUIVALENT CHARACTERISTICS ARE MAINTAINED. ITEMS SUCH AS CAPACITANCE BETWEEN

CONDUCTORS AND WIRE GAUGE CAN BE CRUCIAL TO THE CIRCUIT DESIGN OF THIS SYSTEM

INSTALLATION.

REFERENCE https://www.anixter.com/customer/tycofs FOR SG ANIXTER CABLE DATA

S AUDIO CIRCUIT1 PAIR 16 AWG TWISTEDUNSHIELDED

SG ANIX./PAIGE 454731AREAREA=0.0272 SQ. INCH AREA=0.0209 SQ. INCH

SG ANIX./PAIGE 454740ARE

FA-1602C-1-1N-03-BXANIXTER PART NUMBER

FA-1602C-1-2N-03ANIXTER PART NUMBER

R RELAY CIRCUIT2 CONDUCTOR14 AWG SOLID

AREA=0.0097 SQ. INCH (EACH)(2) #14 AWG

SG ANIX./PAIGE 454718AREAREA=0.0380 SQ. INCH AREA=0.0333 SQ. INCH

SG ANIX./PAIGE 454719ARE

ANIXTER PART NUMBERFA-1402C-1-1N-03-BX FA-1402C-1-2N-03

ANIXTER PART NUMBER

AREA=0.0272 SQ. INCHSG ANIX./PAIGE 454731AREP

AREA=0.0208 SQ. INCHSG ANIX./PAIGE 454740AREPOWER CIRCUIT

2 CONDUCTOR16 AWG SOLID (SUBSCRIPT"r" IF RESETTABLE)

FA-1602C-1-1N-03-BXANIXTER PART NUMBER

FA-1602C-1-2N-03ANIXTER PART NUMBER

AREA=0.0072 SQ. INCH (EACH)(4) #16 AWG

M MAPNET/IDNET CIRCUIT1 PAIR 18 AWG TWISTEDOVERALL SHIELD

AREA=0.0196 SQ. INCHSG ANIX./PAIGE 740214LSG ANIX./PAIGE 740215

AREA=0.0196 SQ. INCH

ANIXTER PART NUMBERT740215 FAMC-1802C-1-2S-03B5

ANIXTER PART NUMBER

L REMOTE LED CIRCUIT2 CONDUCTOR 16 AWGSOLID

AREA=0.0072 SQ. INCH (EACH)(2) #16 AWG

AREA=0.0272 SQ. INCHSG ANIX./PAIGE 454731ARE

AREA=0.0208 SQ. INCHSG ANIX./PAIGE 454740ARE

FA-1602C-1-1N-03-BXANIXTER PART NUMBER

FA-1602C-1-2N-03ANIXTER PART NUMBER

K REMOTE TEST SWITCH/LED CIRCUIT - (2) 2CONDUCTOR 18 AWG SOLID

AREA=0.0055 SQ. INCH (EACH)(4) #18 AWG

SG ANIX./PAIGE 454703AREAREA=0.0204 SQ. INCH AREA=0.0141 SQ. INCH

SG ANIX./PAIGE 740132R

ANIXTER PART NUMBERFA-1802C-1-1N-03-BX FA-1802C-1-2N-03

ANIXTER PART NUMBER

SG ANIX./PAIGE 454720AREAREA=0.0491 SQ. INCH

AAREA=0.0468 SQ. INCHSG ANIX./PAIGE 454725ARE

ANIXTER PART NUMBER ANIXTER PART NUMBER

ADDRESSABLENOTIFICATION CIRCUIT12 AWG SOLIDUNSHIELDED TWISTED PAIR FA-1202C-1-1N-03 FA-1202C-1-2N-03

SINGLE CONDUCTOR(THHN,TFFN) PLENUM RATED: FPLP

FIRE ALARM WIRE LISTRISER RATED: FPLRCIRCUIT DESCRIPTION

END-OF-LINE RESISTOR 6.8K (EOL) SIMPLEX 4081-9004

END-OF-LINE RESISTOR 4.7K (EOL)

END-OF-LINE RESISTOR 3.3K (EOL)

END-OF-LINE RESISTOR 10K (EOL)

SIMPLEX 4081-9003

SIMPLEX 4081-9002

SIMPLEX 4081-9008

SINGLE GANG BOX 2 1/8" DEEP W/COVERENCAPSULATED RELAY SIMPLEX 4098-9843

SINGLE GANG BOX 2 1/2" DEEPREMOTE TEST STATION W/ LED AND KEY SWITCH SIMPLEX 2098-9806

MOUNT TO DUCTWORKDUCT SMOKE SENSOR SIMPLEX 4098-9756

WATERFLOW SWITCH INSTALLED BY MECHANICAL CONTRACTORSUPPLIED BY OTHERS

TAMPER SWITCH INSTALLED BY MECHANICAL CONTRACTORSUPPLIED BY OTHERS

SERIAL LCD ANNUNCIATOR SIMPLEX 4603-9101 6 GANG BOX 3 1/2" DEEP

4" SQUARE BOX 1 1/2" DEEP W/ 1 1/2" RINGSPEAKER ONLY, CEILING MOUNT SIMPLEX 4902-9721

#W = SPEAKER TAP

W/4905-9942 ADAPTER SKIRT WHEN SURFACE MOUNTED

4" SQUARE BOX 1 1/2" DEEP W/ 1 1/2" RINGSPEAKER ONLY, WALL MOUNT SIMPLEX 4902-9717

#W = SPEAKER TAP

# =CANDELA RATING

ADDRESSABLE CEILING MOUNT MULTI-CANDELA STROBE ONLY WHITE SIMPLEX 4906-9204 HANDY BOX 1 1/2" DEEP

W/4905-9940 ADAPTER SKIRT WHEN SURFACE MOUNTED# = CANDELA RATING

WALL MOUNT MULTI-CANDELA STROBE ONLY, WHITE SIMPLEX 49VO-WWF 4" SQUARE BOX 1 1/2" DEEP

4" SQUARE BOX 1 1/2" DEEP W/ 1 1/2" EXTENSION RING

# =CANDELA RATING, #W = SPEAKER TAP

SIMPLEX 4906-9254CEILING MOUNT, WHITE

ADDRESSABLE MULTI-CANDELA SPEAKER/STROBE,

W/4905-9946 ADAPTER SKIRT WHEN SURFACE MOUNTED

4" SQUARE BOX 1 1/2" DEEP W/ 1 1/2" EXTENSION RING

# =CANDELA RATING, #W = SPEAKER TAP

SIMPLEX 4906-9253WALL MOUNT, WHITE

ADDRESSABLE MULTI-CANDELA SPEAKER/STROBE,

4" SQUARE BOX 2 1/8" DEEP W/TWO GANG COVERRELAY IAM SIMPLEX 4090-9002

SINGLE GANG BOX 2 1/2" DEEP WITH COVERINDIVIDUAL ADDRESSABLE MODULE SIMPLEX 4090-9001

HEAT SENSOR / BASE

SIMPLEX 4098-9792 BASE

SIMPLEX 4098-9733

4" OCTAGONAL BOX 1 1/2" DEEP

SMOKE SENSOR / BASE

4" OCTAGONAL BOX 1 1/2" DEEPSIMPLEX 4098-9792 BASE

SIMPLEX 4098-9714

NO GRIP MANUAL PULL STATION 4" SQUARE BOX 2 1/8" DEEP W/SINGLE GANG COVERSIMPLEX 4099-9020

(REFER TO MOUNTING DETAIL FOR SPECIFIC DIMENSIONS)SUPPLIED BY SIMPLEXGRINNELL

SIMPLEX 4100-9111FIRE ALARM CONTROL PANEL

FIRE ALARM SYMBOLS LEGEND

SYMBOL DESCRIPTION MODEL# BACKBOX

7300-0026:0150

3240-0026:0241

7120-0026:0179

7125-0026:0371

7320-0026:0242

7320-0026:0242

7125-0026:0235

7125-0026:0373

7320-0026:0322

7320-0026:0322

7300-0026:0223

7300-0026:0223

7270-0026:0216

7300-0026:0217

7300-0026:0217

7272-0026:0218

7150-0026:0224

7165-0026:0251

CSFM #

**USE 70 VOLT TAP**

**USE 70 VOLT TAP**

**USE 70 VOLT TAP**

**USE 70 VOLT TAP**

REFER TO BATTERY CHARTSW / VARIOUS BATTERY SETS

DEVICE DESIGNATOR

S2-1

SPEAKER DEVICE

SPEAKER CIRCUIT

DEVICE ADDRESS

A1:2-1(1)

ADDRESSABLE NOTIFICATION DEVICE

ADDRESSABLE POWER SUPPLY

CHANNEL DESIGNATOR

(EPS, TPS)BRANCH/REPEATER DESIGNATOR (OPT.)(#) BRANCH, (E#:#) REPEATER:BRANCH

DEVICE ADDRESS

M2-1

ADDRESSABLE DEVICES NUMBERING

ADDRESSABLE CARD (IDNET OR MAPNET)

1. THESE DRAWINGS DEPICT GENERAL LOCATIONS OF LIFE SAFETY EQUIPMENT & FIELD DEVICES. EXACT ROUTING OF CONDUITS TO BE

DETERMINED IN THE FIELD BY THE INSTALLING CONTRACTOR TO SUIT CONDITIONS. ALL CHANGES SHALL BE CLEARLY INDICATED ON

THE RECORD DRAWINGS.

2. SHOULD ANY CONDITIONS EXIST THAT DIFFER FROM WHAT IS INDICATED ON THESE DRAWINGS WHICH CAUSE MAJOR DEVIATIONS IN

THE WORK SHOWN, THE CONTRACTOR SHALL CONTACT SIMPLEXGRINNELL IN A TIMELY MANNER SO AS NOT TO IMPAIR THE

CONSTRUCTION SCHEDULE.

3. CONTRACTOR IS RESPONSIBLE FOR MAKING AND OBTAINING APPROVAL FOR ALL NECESSARY ADJUSTMENTS IN CIRCUITING AS

REQUIRED TO ACCOMMODATE THE RELOCATION OF EQUIPMENT AND/OR DEVICES WHICH ARE AFFECTED BY ANY AUTHORIZED

CHANGE. ALL CHANGES SHALL BE CLEARLY INDICATED ON THE RECORD DRAWINGS.

4. A STAMPED SET OF APPROVED FIRE ALARM DRAWINGS SHALL BE AT THE JOB SITE AND SHALL BE USED FOR INSTALLATION.

5. THE POWER CIRCUIT TO THE FACP AND TO THE FIRE ALARM POWER SUPPLIES SHALL BE ON A DEDICATED 120V, 20A BRANCH CIRCUIT

BREAKER, AND SHALL HAVE A RED MARKING, LOCK-ON PROVISION AND SHALL BE IDENTIFIED AS "FIRE ALARM CIRCUIT CONTROL." THE

LOCATION OF THE CIRCUIT DISCONNECT MEANS (CIRCUIT BREAKER) SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM

CONTROL UNIT.

6. UPDATE THE AS-BUILT DRAWING SET DAILY WITH JOB PROGRESS. RETURN THE AS-BUILT DRAWING SET TO SIMPLEXGRINNELL NO

LATER THAN 7 DAYS AFTER FINAL TEST.

7. THE CONTRACTOR WILL MAINTAIN ALL AREAS OF THE BUILDING IN A NEAT AND WORKMAN LIKE MANNER.

8. DO NOT APPLY POWER EXCEPT IN THE PRESENCE OF A FACTORY TRAINED SIMPLEXGRINNELL TECHNICAL REPRESENTATIVE.

9. ANY SMOKE DETECTOR HEAD INSTALLED BEFORE THE BUILDING IS CLEANED AND ACCEPTED SHALL BE COVERED TO PROTECT FROM

DUST. ANY FALSE ALARMS DUE TO DIRT CONTAMINATED HEADS SHALL BE THE RESPONSIBILITY OF THE FIRE ALARM INSTALLER.

10. THE FIRE ALARM INSTALLER WILL MAINTAIN THE FIRE RESISTANCE INTEGRITY OF ALL WALL, CEILING, AND ROOF ASSEMBLIES ANY TIME

THAT WORK IS NOT ACTIVELY BEING PERFORMED.

11. INSTALLATION OF DEVICES SHALL BE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. POWER LIMITED AND NON-POWER

LIMITED FIELD WIRING MUST BE INSTALLED WITHIN THE FACP ENCLOSURE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS

AND NEC.

12. ALL WIRING SHALL BE INSTALLED ACCORDING TO NFPA 70 (NEC).

13. FIRE ALARM CIRCUITS SHALL BE IDENTIFIED IN ACCORDANCE WITH APPROPRIATE SECTION OF NEC 760. MARK ALL FIRE ALARM WIRES

IN ACCORDANCE WITH NEC 760 SECTIONS FOR POWER LIMITED AND NON-POWER LIMITED WIRE.

14 FIRE ALARM CABLE INSTALLED IN DUCTS, PLENUM, AND OTHER SPACES USED FOR ENVIRONMENTAL AIR SHALL BE TYPE FPLP.

15. FIRE ALARM CABLE INSTALLED IN THE VERTICAL RUNS AND PENETRATE MORE THAN ONE FLOOR OR CABLES INSTALLED IN VERTICAL

RUNS IN SHAFTS SHALL BE TYPE FPLR.

16. FIRE ALARM CABLE INSTALLED IN UNDERGROUND CONDUIT OR OTHER WET LOCATIONS SHALL BE UL LISTED FOR WET LOCATIONS.

17. FIRE ALARM CIRCUITS EXTENDING BEYOND ONE BUILDING AND RUN OUTDOOR SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 70

ARTICLES 760, 770, 725 AND 800 WHERE APPLICABLE.

18. ALL WIRING, INCLUDING SHIELDS MUST BE DRY AND FREE OF SHORTS AND GROUNDS.

19. ALL SHIELDED WIRE MUST HAVE SHIELD CONTINUITY AT FULL LENGTH OF THE WIRE.

20. ONLY SYSTEM WIRING CAN BE RUN IN THE SAME CONDUIT.

21. 120VAC IS NOT PERMITTED IN THE SAME CONDUIT WITH LOW VOLTAGE WIRING.

22. MAINTAIN 40 PERCENT CONDUIT FILL RATIO AS PER NEC REQUIREMENTS.

23. EXISTING CONDUITS MAY BE USED BY THE INSTALLATION CONTRACTOR AS DEEMED NECESSARY, HOWEVER, ANY EXISTING CONDUIT

WILL BE USED ONLY IF CONDUITS MEET CURRENT STANDARDS AND CODES. SIMPLEXGRINNELL MAKES NO STATEMENTS WRITTEN OR

VERBAL AS TO THE CONDITION OF EXISTING CONDUITS.

SYMBOL KEYSYSTEM DESCRIPTION / SCOPE OF WORKGENERAL NOTES

FIRE ALARM APPLICABLE CODES & STANDARDS

SEQUENCE OF OPERATIONDEVICE ADDRESSING LEGEND

ABBREVIATIONS LEGEND

=

=

=

=

=

=

=

=

=

=

=

=

=

=

=

=

=

=

=

=

=

=

=

=

=W/

TYP

UON

VT

WF

W

VCC

TRBL

MAX

NIC

NTS

SMK

SLC

NPU

SCC

TAC

SUPV

MIN

N/A

NAC

NEC

NDU

NFPA

HT

HVAC

UNLESS OTHERWISE NOTED

VOICE COMMAND CENTER

WITH

VALVE TAMPER

WATER FLOW

(eg. 1/2W) WATT

TROUBLE

TYPICAL

MAXIMUM

NOTIFICATION APPLIANCE CIRCUIT EXTENDER

SIGNALING LINE CIRCUIT

NATIONAL ELECTRICAL CODE

NETWORK PROCESSING UNIT

NETWORK DISPLAY UNIT

STATUS COMMAND CENTER

NATIONAL FIRE PROTECTION ASSOCIATION

TRUEALERT ADDRESSABLE CONTROLLER

NOT IN CONTRACT

NOT TO SCALE

SUPERVISORY

SMOKE

NOT APPLICABLE

MINIMUM

HEATING, VENTILATION, & AIR CONDITIONING

HEIGHT

=W/O WITH OUT

=TS TAMPER SWITCH

=IMS INFORMATION MANAGEMENT SYSTEM

=PAP PRE-ACTION PANEL

JURISDICTIONS WITHIN THE STATE MAY HAVE AMENDMENTS TO THE STATE ADOPTED CODE. CHECKWITH THE LOCAL JURISDICTION AUTHORITY FOR MORE DETAILS.

END OF LINE

EXPLOSION PROOF

EMERGENCY POWER OFF

FIRE ALARM CONTROL PANEL

FIRE ALARM TERMINAL CABINET

FURNISHED BY OTHERS

FIRE COMMAND CENTER

EOL =

XP =

EPO =

FACP =

FATC =

FBO =

FCC =

WEATHERPROOF

DETECTOR

(eg. 15CD) CANDELA

ANNUNCIATOR

ALARM

ABOVE FINISHED FLOOR

CALIFORNIA BUILDING CODE

CALIFORNIA STATE FIRE MARSHAL

AUTHORITY HAVING JURISDICTION

BUILDING MANAGEMENT SYSTEM

DATA GATHERING PANEL

=ALM

CBC =

DET =

CSFM =

CD =

ANN =

BMS =

=DGP

WP =

=AFF

AHJ =

=FSD FIRE SMOKE DAMPER

FIRE ALARM ANNUNCIATORFAA =FIRE ALARM TRANSPONDERFTR =

HIGH HUMIDITYH =

EXISTING TO REMAINCEILING MOUNTED

ABOVE CEILING

RELOCATED DEVICE

EXISTING DEVICE TO BE RELOCATED

REMOVE EXISTING AND REPLACE W/NEW

EXISTING TO REMOVE AND COVERRC

RD =

RR =

=

RL =

C =E =

AC =

SHEET INDEX

WELLNESS CENTER SHEET INDEX

VISUAL/SIGNAL CIRCUIT - 2 CONDUCTOR 12 AWG STRANDED, UNSHEILDEDDIRECT BURIAL/UNDERGROUND IN CONDUIT/AERIAL (REQUIRES MESSENGER) - CABLE

ANIXTER PART NUMBER 2A-1202AREA=0.0820 SQ. INCH

Vb

CONDUIT ONLY: THWN(2) #12 AWG (RED/BLACK)AREA=0.0133 SQ. INCH (EACH)

DIRECT BURIAL/UNDERGROUND IN CONDUIT/AERIAL (REQUIRES MESSENGER) - CABLESPEAKER CIRCUIT - 1 PAIR 18 AWG TWISTED OVERALL SHIELD

ANIXTER PART NUMBER 2AS-1801POSAREA=0.0615 SQ. INCH

Sb

DIRECT BURIAL/UNDERGROUND IN CONDUIT/AERIAL (REQUIRES MESSENGER) - CABLEMAPNET/IDNET CIRCUIT - 1 PAIR 18 AWG TWISTED OVERALL SHIELD

ANIXTER PART NUMBER 2AS-1801POSAREA=0.0615 SQ. INCH

Mb

WIRING THAT LEAVES THE BUILDING

WIRE SCHEDULE

DSA NOTES

4" SQUARE BOX 2 1/8" DEEP W/TWO GANG COVERLINE ISOLATOR MODULE SIMPLEX 4090-9116 7300-0026:0252

P

FAA

OCCUPANCY TYPE: A-3 ASSEMBLY GROUPA-4 ASSEMBLY GROUP

SPRINKLER PROTECTION: BUILDING IS FULLY SPRINKLED

CALIFORNIA BUILDING CODE, 2013 EDITION, TITLE 24, PART 2

CALIFORNIA FIRE CODE, 2013 EDITION, TITLE 24, PART 9

CALIFORNIA ELECTRIC CODE, 2013 EDITION, TITLE 24, PART 3

CALIFORNIA ELEVATOR SAFETY CONSTRUCTION CODE, 2013 EDITION

NFPA 72, 2013 EDITION WITH CALIFORNIA AMENDMENTS

B BUSINESS GROUPS-1 STORAGE GROUP

1. APPLICABLE STANDARD AND CODES:2013 NFPA 722013 CALIFORNIA FIRE CODE2013 CALIFORNIA BUILDING CODE2013 CALIFORNIA MECHANICAL CODE2013 CALIFORNIA ELECTRICAL CODE

2. INSTALLATION OF THE SYSTEM SHALL NOT BE STARTEDUNTIL DETAILED DESIGN DOCUMENTS ANDSPECIFICATIONS, INCLUDING STATE FIRE MARSHALLISTING NUMBERS FOR EACH COMPONENT OF THESYSTEM, HAVE BEEN APPROVED BY DSA.

3. UPON COMPLETION OF THE INSTALLATION OF THESYSTEM, A SATISFACTORY TEST OF THE ENTIRE SYSTEMSHALL BE MADE IN THE PRESENCE OF A DSA PROJECTINSPECTOR.

4. A STAMPED SET OF APPROVED FIRE ALARM DESIGNDOCUMENTS SHALL BE MAINTAINED ON THE JOB SITEAND USED FOR INSTALLATION.

5. ANY DISCREPANCIES BETWEEN THE DRAWINGS ANDTHE CODE OR RECOGNIZED STANDARDS SHALL BEBROUGHT TO THE ATTENTION OF DSA AND THEARCHITECT/ENGINEER OF THE PROJECT.

6. DSA, ARCHITECT/ENGINEER AND OWNER SHALL BENOTIFIED A MINIMUM OF 48 HOURS PRIOR TO THE FINALINSPECTION AND /OR TESTING.

7. ALL PENETRATIONS THROUGH RATED ASSEMBLIESREQUIRING OPENING PROTECTION SHALL BE PROVIDEDWITH A PENETRATION FIRE STOP SYSTEM AS IDENTIFIEDIN CBC CHAPTER 7, UL OR OTHER LAB TESTINGCRITERIA.

8. WALL MOUNTED VISUAL NOTIFICATION APPLIANCESSHALL HAVE THEIR BOTTOMS MOUNTED AT 80” MINIMUMAND 96” MAXIMUM ABOVE FINISHED FLOOR.

9. WALL MOUNTED AUDIBLE NOTIFICATION APPLIANCESSHALL HAVE THEIR TOPS MOUNTED AT 90” MINIMUM AND96” MAXIMUM ABOVE FINISHED FLOOR AND NO CLOSERTHEN 6” TO A HORIZONTAL STRUCTURE.

10. AUDIBLE APPLIANCES TO PROVIDE SOUND LEVEL ATLEAST 15 dB ABOVE THE AVERAGE AMBIENT SOUNDLEVEL BUT NOT LESS THAN 75 dB AT 10 FEET OR MORETHAN 110 dB AT THE MINIMUM HEARING DISTANCE .SOUND LEVEL SHALL ACHIEVE 5 dB ABOVE MAXIMUMSOUND LEVEL HAVING DURATION OF AT LEAST 60SECONDS. MEASURE SOUND LEVEL AT FIVE FEETABOVE FINISHED FLOOR.

11. AUDIBLE APPLIANCES SHALL BE SYNCHRONIZEDTEMPORAL CODE 3 PATTERN.

12. THE CONTRACTOR SHALL ADJUST/INSTALL ALL DEVICESTO MAXIMIZE PERFORMANCE AND TO MINIMIZE FALSEALARMS.

13. VISUAL APPLIANCES SHOULD NOT EXCEED 2 FLASHESPER SECOND AND SHOULD NOT BE SLOWER THAN 1FLASH EVERY SECOND. THE DEVICE SHALL HAVE APULSING LIGHT SOURCE NOT LESS THAN 15 CANDELA.VISUAL APPLIANCES WITHIN 55' FROM EACH OTHERSHALL BE SYNCHRONIZED.

14. UNDERGROUND AND EXTERIOR CONDUITS TO HAVEWATERTIGHT FITTINGS AND WIRE TO BE APPROVED FORWET LOCATIONS.

15. ALL FIRE ALARM WIRING SHALL BE FLP OR FPLP (FIREPOWER LIMITED OR FIRE POWER LIMITED PLENUM) ASREQUIRED FOR APPLICATION. WIRING IN CONDUITABOVE GROUND MAY BE THHN OR THWN.

16. PER CEC STANDARDS, ALL WIRING IS TO BE PULLEDTHROUGH EACH JUNCTION BOX AND CONNECTEDDIRECTLY TO EACH FIRE DEVICE. DO NOT SPLICE THEWIRE. THERE MUST BE AT LEAST 6" OF LEAD WIRE FROMTHE BOX TO THE DEVICE. ALL BOXES TO BE SIZED PERCEC.

17. SMOKE DETECTORS SHALL NOT BE INSTALLED CLOSERTHAN 1' FROM FIRE SPRINKLERS OR 3' FROM ANYSUPPLY DIFFUSER. IN AREA OF CONSTRUCTION ORPOSSIBLE DAMAGE/CONTAMINATION, NEWLY INSTALLEDFIRE ALARM DEVICES SHALL BE COVERED UNTIL THATAREA IS READY TO BE TURNED OVER TO THE OWNER.

18. ALL FIRE ALARM CIRCUITS SHALL BE IN CONDUIT,SURFACE RACEWAY OR OPEN RUN ABOVE CEILINGS,UNDER FLOORS AND IN WALLS IN A NEAT ANDPROTECTED MANNER AS INDICATED ON DESIGNDOCUMENTS. EXPOSED CIRCUITS ARE ONLY PERMITTEDWHEN NOTED AS EXPOSED ON DESIGN DOCUMENTS.

19. FIRE ALARM PANEL, REMOTE PANELS, POWER SUPPLIESAND COMPONENTS SHALL BE SECURED TO MOUNTINGSURFACES PER MANUFACTURERS SPECIFICATIONS. NOSINGLE DEVICE SHALL EXCEED THE WEIGHT OF 20 LBS.WITHOUT SPECIAL MOUNTING DETAILS.

20. A DEDICATED BRANCH CIRCUIT SHALL BE PROVIDEDFOR FIRE ALARM EQUIPMENT. THIS CIRCUIT SHALL BEENERGIZED FROM THE COMMON USE AREA PANEL ANDSHALL HAVE NO OTHER OUTLETS. THE BREAKER SHALLHAVE A RED LOCKING DEVICE TO BLOCK THE HANDLE INTHE “ON” POSITION. THE CIRCUIT BREAKER SHALL BELABELED “FIRE ALARM CIRCUIT CONTROL”. CIRCUIT IDTO BE LABELED AT FIRE PANEL/EXTENDERS.

21. THE INSTALLING CONTRACTOR SHALL PROVIDE ARECORD OF COMPLETION PER NFPA 72, FIGURE10.18.2.1.1.

22. CONTROL PANELS AND REMOTE ANNUNCIATORS SHALLBE INSTALLED WITH THEIR BOTTOMS MOUNTED AT 48”ABOVE FINISHED FLOOR.

23. THE INSTALLING CONTRACTOR SHALL PROVIDE SYSTEMPROGRAMMING FOR SUPERVISORY MONITORING PERCBC SECTION 901.6.2.

24. SUPERVISORY MONITORING SHALL BE TESTED ANDVERIFIED AS SENDING CORRECT SIGNALS INCONJUNCTION WITH FINAL ACCEPTANCE TEST.

25. OWNER SHALL BE RESPONSIBLE FOR ESTABLISHING AFIRE SYSTEM MONITORING CONTRACT OR PROVISIONS.

EFORPDERETSI

GER

REEN

IGN

E

LANOISS

C A L I F OR N I AS T A T E O F

R I C A LE L E C T

No. E16806

JASON LAU

E N G I N E E R I N GI N T E R F A C E

TEL

FAX

PROJECT

CONTACT

www.interfaceengineering.com

717 Market Street

Suite 500

San Francisco, CA 94103

415.489.7240

415.489.7289

SHEET NO:

DATE:

PROJECT NO:

THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THEPURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVEAND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THEWRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONALSERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2009.

THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECTAND ENGINEER.

CONSULTANT

6910 5 31112 8 7 4 2 1

J

K

H

G

F

E

D

C

B

A

B

A

J

K

H

G

F

E

D

C

6910 5 31112 8 7 4 2 1

NO. ISSUE DATE

ARCHITECT'S STAMP APPROVAL

Joe Ripp

2014-0174

SAN JOSE CITYCOLLEGE

PHYSICAL EDUCATION BUILDING ANDRENOVATED LAB BUILDING

SAN JOSE, CALIFORNIA

SYMBOLS LISTS, GENERALNOTES AND SHEET INDEX -FIRE ALARM

FA0.01

1.12.2015

1089-0001

DSA SUBMITTAL

FA0.01 SYMBOLS LISTS, GENERAL NOTES AND SHEET INDEX - FIRE ALARM

FA1.01 SITE PLAN - FIRE ALARM

FA2.01 1ST FLOOR PLAN - PHYSICAL EDUCATION BUILDING - FIRE ALARM

FA2.02 2ND FLOOR PLAN - PHYSICAL EDUCATION BUILDING - FIRE ALARM

FA4.01 ONE-LINE DIAGRAM - FIRE ALARM

FA5.01 CONTROL PANEL DIAGRAM - FIRE ALARM

FA6.01 CALCULATIONS - FIRE ALARM

FA6.02 CALCULATIONS - FIRE ALARM

FA7.01 DETAILS - FIRE ALARM

FA7.02 DETAILS - FIRE ALARM

FA7.03 DETAILS - FIRE ALARM

FA7.04 DETAILS - FIRE ALARM

WFA2.03 FLOOR PLANS - WELLNESS CENTER - FIRE ALARM

Page 2: SAN JOSE CITY - SJECCD Fire Alarm.pdf · relay iam simplex 4090-9002 4" square box 2 1/8" deep w/two gang cover individual addressable module simplex 4090-9001 single gang ... installation

D

D

D

D

UP

DY

H

##

#

#

#

#

##

##

##

##

#

#

#

#

##

##

#####

#

RAMP∀

LAMPΑ

DC

DA

FH

FH

WV

WV

T

PIV

2" FA CONDUIT 1" FA CONDUIT

VT

2" FA CONDUIT

FAA

FACP

Mb,Sb,Vb

Mb

Mb,Sb,Vb

PHYSICAL EDUCATION BUILDING

WELLNESS BUILDING

EFORPDERETSI

GER

REEN

IGN

E

LANOISS

C A L I F OR N I AS T A T E O F

R I C A LE L E C T

No. E16806

JASON LAU

E N G I N E E R I N GI N T E R F A C E

TEL

FAX

PROJECT

CONTACT

www.interfaceengineering.com

717 Market Street

Suite 500

San Francisco, CA 94103

415.489.7240

415.489.7289

SHEET NO:

DATE:

PROJECT NO:

THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THEPURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVEAND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THEWRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONALSERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2009.

THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECTAND ENGINEER.

CONSULTANT

6910 5 31112 8 7 4 2 1

J

K

H

G

F

E

D

C

B

A

B

A

J

K

H

G

F

E

D

C

6910 5 31112 8 7 4 2 1

NO. ISSUE DATE

ARCHITECT'S STAMP APPROVAL

Joe Ripp

2014-0174

SAN JOSE CITYCOLLEGE

PHYSICAL EDUCATION BUILDING ANDRENOVATED LAB BUILDING

SAN JOSE, CALIFORNIA

SITE PLAN - FIRE ALARM

FA1.01

1.12.2015

1089-0001

DSA SUBMITTAL

0' 20' 40'

1" = 20'-0"

1 SITE PLAN - FIRE ALARM

Page 3: SAN JOSE CITY - SJECCD Fire Alarm.pdf · relay iam simplex 4090-9002 4" square box 2 1/8" deep w/two gang cover individual addressable module simplex 4090-9001 single gang ... installation

P

P

P

P

P

PP

P

P

P

P

ELEV.

E1.1

HALL

167

PUBLIC WOMEN'SRESTROOM

122

SPECTATOR GYMNASIUM

160

PUBLIC MEN'S RESTROOM

126

MEN'S TEAM SHOWER

147

FOOTBALL LOCKER ROOM

146

TEAM DRESSING ROOM

148

VEST.

149

TEAM DRESSING ROOM

155

HYDRONICS

157

WOMEN'S STUDENTLOCKERS

129

MEN'S STUDENT LOCKERS

132

MULTIPURPOSE CLASSROOM

141

SOUTH CORRIDOR

150

TRAINING ROOM

138

EQUIPMENT STORAGE

133

TICKETS/ CONCESSIONS

124

TELECOM

125

LOBBY

101

OPEN OFFICE

102

WOMEN'S STUDENTRESTROOM

130

MEN'S STUDENT RESTROOM

131

EAST CORRIDOR

137

MEN'S TEAM TOILETS

145WOMEN'S TEAM TOILETS

153

MACH. ROOM

120 RISER

123

TRAINING STAFF ROOM

139

DEAN'S OFFICE

104

OFFICE

111

OFFICE

112 OFFICE

113

OFFICE

110OFFICE

109

AIM

AOM AOM

AOM

AOM

FAA

FACP

JAN.

140

ELEC.

136

VEST.

128

OFFICE

103

E F GA.5 F.2 JH

5

6

7

8

9

B C D

STAFF LOCKER

105

MENS

106

WOMENS

107

STAFF LOCKER

108

ELEC.

151

VEST.

144

CC

C

C

C

C

C

C

C

C

C

C

C

C

C C

C

C

C C

C

C

C

C

CC

C

C C C C

WPWP

WP

WPWG

WGWG

WG

WGWG

WG WG

WG

WG

WG

WG

WF

VS

A

1

2

3

4

C

C

2

AIM

AIM

EOL

EOL

EOL

OPENTO

ABOVE

30

30

75 30

75

75

30

75

30

30

110

15

135

15

15

30 30

135

15

30 30

3030

15

15

15

15

30

15

15

15

15

15

15

135

135

UP TO2NDFLOOR

30

30

WP

WP

WP

WP

3030

WP

15

C

A1:1-17(1)S1-18

A1:1-18(1)S1-19

A1:1-16(1)S1-17

A1:1-15(1)S1-15

A1:1-14(1)S1-14

A1:1-13(1)S1-13

A1:1-12(1)S1-12

A1:1-11(1)S1-11

A1:1-10(1)S1-10

A1:1-9(1)S1-9

A1:1-8(1)S1-8

A1:1-7(1)S1-7

A1:1-1(1)S1-1

A1:1-2(1)S1-2

A1:1-3(1)S1-3

A1:1-4(1)S1-4

A1:1-5(1)S1-5

A1:1-6(1)S1-6

A1:2-1(1)S2-1

A1:2-2(1)S2-3

A1:2-3(1)S2-5

A1:2-4(1)

A1:2-5(1)S2-7

A1:2-6(1)

A1:2-7(1)S2-9

A1:2-8(1)S2-10

A1:2-9(1)S2-11

A1:2-10(1)

A1:2-11(1)S2-12

A1:2-12(1)

A1:2-13(1)S2-14

A1:2-14(1)S2-15

A1:2-15(1)S2-16

A1:2-16(1)

A1:2-17(1)S2-18

A1:2-18(1)S2-19

A1:2-19(1)S2-20

1/2W

1/2W

1/4W 1/4W 1/4W

1/2W

1/2W

1/4W

1/2W

1/2W

1/2W

1/2W

1/2W

1/2W

1/4W

1/2W 1/2W

1/2W1/2W

1/4W

1/4W

1/4W

1/4W

1/4W

2W

2W

2W

2W

2W2W

2W

2W

2W

2W

WG

WG

WG

WG

TOFACP

S1-16

S2-2

S2-4

S2-6

S2-8

S2-13

S2-17

1/4W

1/2W

1/2W

1/2W1/2W

1/2W

1/4W1/4W

1/2W

1/2W

1/2W

1/2W

1/4W

1/2W

1/2W

S3-1

S3-2

S3-3

S3-4

S3-5S3-6

S3-7

S3-8

S3-9

S3-10

1

A,M,S

A,M,S

A,M,S

A,M,S

A,M,S A,M,S

A,M,S

A,M,S

A,M,S

A,M,S

A,M,S

A,M,S

A,M,S

A,M,S

A,M,S

A,M,S

A,M,S

A,M,S

A,M,S

A,M,S

A,M,S

A,M,S

A,M,SA,M,SA,M,SA,M,S

A,M,S

A,S

M

A,2S

A,2S

A,2S

A,2S

A,2S

A,2S

A,2S

A,2S

A,M,2S

A,M,2S

A,M,2S

A,M,2S

M

M

M

A,2S

A,M,2S

M

A,M,2SA,M,2S

A,M,2S

3A,B,M,P,3S3A,B,M,P,3S

3A,B,M,P,3S

A,2S

3A,B,M,P,3S

3A,B,M,P,3S

2A,B,M,P,2S

2A,B,M,P,2S2A,B,M,P,2S2A,B,M,P,2S

M

M

A,M,S

Mb,Sb,Vb

A,2S

M

2A,M,P,2S

2A,M,2S

2A,M,2S

LIM

GYM EQUIPMENT

134

OFFICE

135

LAUNDRY

159

M1-4

M1-5

M1-6

M1-7M1-8M1-9M1-10M1-11

M1-3

M1-12

M1-13

M1-1M1-2

M1-19

M1-20M1-14

M1-15

M1-16

M1-17

M1-18

M1-21

M1-22

M1-31

M

TO PIVMb

AIM

M1-32

EFORPDERETSI

GER

REEN

IGN

E

LANOISS

C A L I F OR N I AS T A T E O F

R I C A LE L E C T

No. E16806

JASON LAU

E N G I N E E R I N GI N T E R F A C E

TEL

FAX

PROJECT

CONTACT

www.interfaceengineering.com

717 Market Street

Suite 500

San Francisco, CA 94103

415.489.7240

415.489.7289

SHEET NO:

DATE:

PROJECT NO:

THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THEPURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVEAND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THEWRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONALSERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2009.

THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECTAND ENGINEER.

CONSULTANT

6910 5 31112 8 7 4 2 1

J

K

H

G

F

E

D

C

B

A

B

A

J

K

H

G

F

E

D

C

6910 5 31112 8 7 4 2 1

NO. ISSUE DATE

ARCHITECT'S STAMP APPROVAL

Joe Ripp

2014-0174

SAN JOSE CITYCOLLEGE

PHYSICAL EDUCATION BUILDING ANDRENOVATED LAB BUILDING

SAN JOSE, CALIFORNIA

1ST FLOOR PLAN -PHYSICAL EDUCATIONBUILDING - FIRE ALARM

FA2.01

1.12.2015

1089-0001

DSA SUBMITTAL

0' 4' 8' 16'

1/8" = 1'-0"

1 1ST FLOOR PLAN - PHYSICAL EDUCATION BUILDING - FIRE ALARM

SHEET KEYNOTES1 PROVIDE (1) 2" CONDUIT TO WELLNESS CENTER. PROVIDE CONNECTION

FROM 2" CONDUIT TO RESTROOM BUILDING VIA HANDHOLE, 2" CONDUIT,AND A WEATHERPROOF JUNCTION BOX. IF WELLNESS CENTER IS NOTCONSTRUCTED, CONDUIT AND WIRING TO STOP AT RESTROOM BUILDING.

2 MULLION MOUNT PULL STATION. USE MANUFACTURER'S SURFACE MOUNTBACK BOX AND CONCEAL WIRING WITHIN MULLION.

Page 4: SAN JOSE CITY - SJECCD Fire Alarm.pdf · relay iam simplex 4090-9002 4" square box 2 1/8" deep w/two gang cover individual addressable module simplex 4090-9001 single gang ... installation

P

P

CORRIDOR

201

JANITOR

203

ELEV.

E1.1

TERRACE

T1

E F GA.5 F.2 JH

5

6

7

8

9

B C D

C

C C

C

CC C

C

C

C C

OPENTO

BELOW

OPENTO

BELOW

1

FA7.01AHU-3

ON ROOF

1

FA7.01AHU-1

A

1

2

3

4

15

75 75

7575

11011015

15

75 75

75

DOWN TO1ST FLOOR

1/4W

1/4W

1/4W

1/4W

1/4W

2WWPEOL

1/2W 1/2W

1/2W1/2W

1/2W 1/2W

1/2W1/2WEOL

A2:1-8(1)S4-1

A2:1-7(1)S4-2

A2:1-6(1)S4-3

A2:1-5(1)S4-4

A2:1-4(1)S4-5

A2:1-1(1)S4-6

A2:1-2(1)S4-7

A2:1-3(1)S4-8

A2:2-1(1)S5-1

A2:2-2(1)S5-3

A2:2-3(1)S5-5

A2:2-4(1)S5-6

1

FA7.01AHU-2

ON ROOF

S5-2

S5-4

M,P A,M,P,S

A,M,P,S

A,M,P,S

A,M,P,S

A,M,2S

A,M,P,S

A,M,P,S

A,M,P,S

A,M,2S

A,M,2S

M

M

A,S

A,S

A,S

A,S

A,M,P,S

A,2S

A,2S

A,2S

EXERCISE LAB

205

SPECTATOR GYMNASIUM

160

FITNESS CENTER

202

M1-29

M1-28

M1-27

M1-26

M1-25

M1-30

EFORPDERETSI

GER

REEN

IGN

E

LANOISS

C A L I F OR N I AS T A T E O F

R I C A LE L E C T

No. E16806

JASON LAU

E N G I N E E R I N GI N T E R F A C E

TEL

FAX

PROJECT

CONTACT

www.interfaceengineering.com

717 Market Street

Suite 500

San Francisco, CA 94103

415.489.7240

415.489.7289

SHEET NO:

DATE:

PROJECT NO:

THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THEPURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVEAND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THEWRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONALSERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2009.

THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECTAND ENGINEER.

CONSULTANT

6910 5 31112 8 7 4 2 1

J

K

H

G

F

E

D

C

B

A

B

A

J

K

H

G

F

E

D

C

6910 5 31112 8 7 4 2 1

NO. ISSUE DATE

ARCHITECT'S STAMP APPROVAL

Joe Ripp

2014-0174

SAN JOSE CITYCOLLEGE

PHYSICAL EDUCATION BUILDING ANDRENOVATED LAB BUILDING

SAN JOSE, CALIFORNIA

2ND FLOOR PLAN -PHYSICAL EDUCATIONBUILDING - FIRE ALARM

FA2.02

1.12.2015

1089-0001

DSA SUBMITTAL

0' 4' 8' 16'

1/8" = 1'-0"

1 2ND FLOOR PLAN - PHYSICAL EDUCATION BUILDING - FIRE ALARM

Page 5: SAN JOSE CITY - SJECCD Fire Alarm.pdf · relay iam simplex 4090-9002 4" square box 2 1/8" deep w/two gang cover individual addressable module simplex 4090-9001 single gang ... installation

AIM AOM AOM AOM AOM

AIMAIM

4100ES

P P P

1

A. ONE-LINE DIAGRAM IS DIAGRAMMATIC. REFER TO FLOOR PLANS FOREXACT NUMBER AND LOCATION OF DEVICES AND APPLIANCES.

1 IF WELLNESS CENTER IS NOT CONSTRUCTED, WIRING AND CONDUIT IS TOSTOP AT THE RESTROOM BUILDING.

LIM

SHEET KEYNOTES

GENERAL SHEET NOTES

C

110

WP

TRANSMITTER

TO/FROM CAMPUS

FA NETWORKFUTURE

CHANNEL 3 (A2:3)

ROOF PE BUILDINGROOF PE BUILDING

2ND FLOOR PE BUILDING2ND FLOOR PE BUILDING

1ST FLOOR PE BUILDING

CHANNEL 3 (A1:3)

CHANNEL 2 (A1:2)

CHANNEL 1 (A1:1)

1ST FLOOR PE BUILDING

TO WELLNESS CENTERVIA PULL BOX ATRESTROOM BUILDING

CCCCC

1530303030

A1:1-1A1:1-2A1:1-3A1:1-4A1:1-5A1:1-6

C

3075

A1:1-7

30

WP

75

A1:1-9A1:1-10A1:1-11A1:1-12A1:1-13A1:1-14A1:1-15A1:1-16 A1:1-8A1:1-17A1:1-18

75307575303030 75

CCCCCCC

C

15

A1:2-1

C

15

A1:2-2

C

15

A1:2-3

JBC

15

A1:2-5WP

75

A1:2-6

CC

3030

A1:2-7A1:2-8

C

15

A1:2-9

C

30

A1:2-11 A1:2-4A1:2-10

JB

A1:2-12

JBCC

3030

A1:2-13A1:2-14

1515

WP

75

A1:2-16

C

15

A1:2-15

C

15

A1:2-17

C

15

A1:2-9A1:2-18

C

15

A1:2-19

135

A1:3-1

135

A1:3-2

135

A1:3-3

135

A1:3-4WGWGWGWG

CCCCCC

S1-1S1-2S1-3S1-4S1-5S1-6

C

S1-7

C

S1-9

CCCC

S1-11S1-12S1-13S1-14S1-15

CCC

S1-17S1-18S1-19 S1-8S1-10S1-16

1/2W1/2W1/2W1/2W1/2W1/2W1/2W1/2W1/2W1/2W1/2W1/2W1/2W1/2W1/4W1/2W1/2W 1/4W1/4W

SPEAKER CIRCUIT(S1)

S2-1S2-2S2-3S2-4S2-5S2-6S2-7S2-8S2-9S2-10S2-11S2-12S2-13S2-14S2-15S2-16S2-17S2-18S2-19S2-20

1/4W1/2W1/2W 1/4W 1/4W 1/4W 1/4W1/4W1/4W1/4W1/4W 1/2W1/2W1/2W1/2W1/2W1/2W1/2W1/2W1/2W

S4-1

2W

S4-2

2W

S4-3

2W

S4-4

2W

S4-5

2W

S4-6

2W

S4-7

2W

S4-8

2W

S4-9

2W

S4-10

2W

SPEAKER CIRCUIT(S2)

SPEAKER CIRCUIT(S3)

CCC

A2:1-1A2:1-2A2:1-3A2:1-4

75757575

CCC

A2:1-5A2:1-6A2:1-7A2:1-8

75757575

CC

A2:2-1A2:2-2A2:2-3

151515

WP

75

A2:2-4

CCCCC

S3-1S3-2S3-3S3-4S3-5S3-6

C

S3-7

1/2W1/2W1/2W1/2W1/2W1/2W1/2W

C

S3-8

1/2W

CHANNEL 2 (A2:2)

CHANNEL 1 (A2:1)

S5-1S5-2

1/4W 1/4W

S5-3S5-4

1/4W 1/4W

S5-5

1/4W

S5-6

2W

WP

SPEAKER CIRCUIT(S5)

M1-1 M1-2 M1-3 M1-4 M1-5 M1-6

M1-12M1-14 M1-13M1-16 M1-15

M1-7 M1-8 M1-9 M1-10 M1-11

M1-17M1-18

M1-27 M1-28 M1-29

M1-25 M1-26 M1-30

SPEAKER CIRCUIT(S4)

M1-20 M1-19

M1-31

TO EXISTING CAMPUS NETWORK

FROM EXISTING CAMPUS NETWORK

M1-21M1-22

120 VOLT AC

CAT5 CABLE ETHERNET DROPTERMINATE W/RJ-45 FEMALE JACK

POWERMONITOR

PRIMARYRECALL

ALTERNRECALL

HATFLASH

SHUNTTRIP

10K 10K

10K

10K

10K

10K

6.8K 6.8K

10K

A,S

M

M

P

P

M

M

A

A

A

A

A

A

S

S

S

S

S

M

DATA JACKFIBER

FIBER

P P P

P PP P

P P

P PPP

WF VS

Y

Y

RK

RK

RK

EFORPDERETSI

GER

REEN

IGN

E

LANOISS

C A L I F OR N I AS T A T E O F

R I C A LE L E C T

No. E16806

JASON LAU

E N G I N E E R I N GI N T E R F A C E

TEL

FAX

PROJECT

CONTACT

www.interfaceengineering.com

717 Market Street

Suite 500

San Francisco, CA 94103

415.489.7240

415.489.7289

SHEET NO:

DATE:

PROJECT NO:

THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THEPURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVEAND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THEWRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONALSERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2009.

THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECTAND ENGINEER.

CONSULTANT

6910 5 31112 8 7 4 2 1

J

K

H

G

F

E

D

C

B

A

B

A

J

K

H

G

F

E

D

C

6910 5 31112 8 7 4 2 1

NO. ISSUE DATE

ARCHITECT'S STAMP APPROVAL

Joe Ripp

2014-0174

SAN JOSE CITYCOLLEGE

PHYSICAL EDUCATION BUILDING ANDRENOVATED LAB BUILDING

SAN JOSE, CALIFORNIA

ONE-LINE DIAGRAM - FIREALARM

FA4.01

1.12.2015

1089-0001

DSA SUBMITTAL

NO SCALE

1 ONE-LINE DIAGRAM - FIRE ALARM

Page 6: SAN JOSE CITY - SJECCD Fire Alarm.pdf · relay iam simplex 4090-9002 4" square box 2 1/8" deep w/two gang cover individual addressable module simplex 4090-9001 single gang ... installation

POWERAUX

- +

1

OV

TB2

+24

2 3 4 5 6 7 8 9 10 11 12

B+ B- A+ A-

4100-5101XPS POWER SUPPLY

120VAC 60Hz

B+ B- A+ A- B+ B- A+ A-

SW1

5

6

7

8

1

2

3

4

P1

NACNACNAC

10K10K10K

CLICK HERETO ADJUST

510X CKTS

ME

SS

AG

E M

EM

OR

Y E

XP

AN

SIO

N

PORT 2

REMOTE MICROPHONE

SH

LD

MIC

(WH

T)

MIC

(WH

T)

45 3

RT

N (B

LK)

PT

T (R

ED

)

12TB1

LOCAL SPEAKER/MIC

P1

2

1

ON

SW1 1

INPUT OPTION CARD

76 843 5

P4

INPUT OPTION CARDPORT 1

P6

CONTROLLER

4100-9621/-1311DIGITAL AUDIO

P11

B-

B+A-

A+

DARPRIMARY SECONDARY

DAR

TB2 46 3 2 15

STYLE 4

-+

PRIMARY2

ONLY

4100-6078

FOR NETWORK INTERFACE

DAUGHTER CARD

INSTALLED IN SLOT J1

RCV XMIT

FIBER4100-6057

J11

2

U4

J2

39

40

U3

U1

OPTION BD.

4100

-124

1 8

MIN

UTE

ME

SS

AG

E E

XP

AN

SIO

N M

OD

ULE

R

R

R

R

R

R

R

R

G

G

G

G

G

G

G

G

+

2081-9296

50 Ah BATTERY

-

50 Ah BATTERY

2081-9296

+ -

45 3 2 1

IDNet+250 DEVICES

SW19600/OFF

16

8

4

2

1

64

32

1

8

2

3

4

5

6

7

TB1

SHIELD JUMPER

IDN

et A

+

IDN

et A

-

SH

LD

IDN

et B

+

IDN

et B

-

P1

120VAC 60HzENHANCED TA POWER SUPPLY

4100-5311

ON1

24

35

76

8

EARTH FAULTJUMPER

B-B-B+B+

IDNAC 1

B+B+ B- B-

IDNAC 2

B+B+ B- B-

IDNAC 3

BTRY (+)

BTRY (-)

RECT (-)

RECT (+)

POWERAUX

-+

OV+24

TB1 TB2 TB3 TB4

CLICK HERETO ADJUST

CKT SHIELDS

4100-1327

DIGITAL AMP70V RMS

FLEX 50 WATT

B-

B+

1TB1

4

B+

2

B-

3

SH

LD

8

B-

7

B+

5 6

SH

LD

NACNAC NAC

DIG

ITA

L A

UD

IO D

EC

OD

ER

CLICK HERETO ADJUST

CKT SHIELDS

4100-1327

DIGITAL AMP70V RMS

FLEX 50 WATT

B-

B+

1TB1

4

B+

2

B-

3

SH

LD

8

B-

7

B+

5 6

SH

LD

NACNAC NAC

DIG

ITA

L A

UD

IO D

EC

OD

ER

FIBER4100-6057

J11

2

U4

J2

39

40

U3

U1

OPTION BD.

45 3 2 1

IDNet+250 DEVICES

SW19600/OFF

16

8

4

2

1

64

32

1

8

2

3

4

5

6

7

TB1

SHIELD JUMPER

IDN

et A

+

IDN

et A

-

SH

LD

IDN

et B

+

IDN

et B

-

P1

120VAC 60HzENHANCED TA POWER SUPPLY

ON1

24

35

76

8

EARTH FAULTJUMPER

B-B-B+B+

IDNAC 1

B+B+ B- B-

IDNAC 2

B+B+ B- B-

IDNAC 3

BTRY (+)

BTRY (-)

RECT (-)

RECT (+)

POWERAUX

-+

OV+24

TB1 TB2 TB3 TB4

R+

OV

-1

RS

RV

D

GN

DR- RUI

P7

POWER

RC

V

RT

S

XM

IT

24C

GN

D

CT

S

PIE

ZO

RS

RV

D

TB1

RS232

NETWORK

L+

RS

RV

D

GN

D

L-

OV

-2

P4

P5

P6

COMM

P8

NE

TW

OR

K/R

S23

2 D

AU

GH

TE

R C

AR

D

CP

U D

AU

GH

TE

R C

AR

D

MOTHERBOARD

NETWORK

CPU

XM

IT

TB3

RU

I B

+

RC

V

RS232

RT

S

CT

S

GN

D

TB2

RU

I B

-

RU

I A

+

SH

LD

RU

I A

-

1 32 4 5 1 32 4 5

P6

1 2 3

P5

1 2 3

S

CLICK HERETO ADJUSTCKT WIRING

P7

P6

P1

P424V

P2

P3

OVP5

P7

P6

P1

P424V

P2

P3

OVP5

P7

P6

P1

P424V

P2

P3

OVP5

R

BA

TT

ER

Y

CONNECT TO 120VAC 60HZ

P2

P3

P4

P1

AC

NE

UT

RA

L

MOUNTS TO BACKBOX

RU

I CO

NN

EC

TOR

4100

CO

MM

P1

P2

RU

I CO

NN

EC

TOR

SW1

P3

SW3

SW2

P4

21

34

SW4

5678/OFF

BRACKET

MOUNTS ON

DACT

EVENTREPORTING

4100-6052

RIN

G2

RIN

GH

OU

SE

2TIP

HO

US

E 2

TIP2

RIN

GH

OU

SE

1R

ING

1TIP

1TIP

HO

US

E 1

AC Power

ResetSystemFire Alarm

EventTime

Enable

Disable Lamp

More

OffDisarm

OnArm

Auto

Priority 2Ack Ack

SupvAck

Menu

Test

Next

TroubleAck

Info

Previous

SilenceAlarm

Fire Alarm

SYSTEM WARNINGS

Priority 2 Alarm

ALARMS

Supervisory Alarm SilencedTrouble

P

P

SS

S

A

A

A

M

A

A

A

56

24DO NOT LOCATE POWER-LIMITED WIRING IN THE SHADED AREAS

OF THE BACKBOX, THIS AREA IS RESERVED FOR NON-POWER

LIMITED CIRCUITRY SUCH AS AC POWER, BATTERIES AND CITY

CONNECTION.

1 2 3

CA

CA

CA

LabelLabel

LabelLabelLabel

LabelLabelLabel

LabelLabelLabel

LabelLabelLabel

LabelLabelLabel

LabelLabelLabel

LabelLabelLabel

LabelLabelLabel

CA

CA CA

CA

TO LCD ANNUNCIATOR LOBBY 101

FERRITE BEAD

TO SPEAKER CIRCUIT S4TO SPEAKER CIRCUIT S5TO SPEAKER CIRCUIT S6

FROM EXISTINGCAMPUS NETWORK

TO EXISTINGCAMPUS NETWORK

TO SPEAKER CIRCUIT S1TO SPEAKER CIRCUIT S2TP SPEAKER CIRCUIT S3

TO SPEAKER CIRCUIT S1TO SPEAKER CIRCUIT S2TP SPEAKER CIRCUIT S3 TO SPEAKER CIRCUIT S4

TO SPEAKER CIRCUIT S5TO SPEAKER CIRCUIT S6

SCALE: NTS

FIRE ALARM CONTROL PANELCABINET # 1 - FIRST FLOOR

RECEPTION AREA B230

SYSTEM CONDUIT, 3/4" MIN. (2" SHOWN)REFER TO MOUNTING DETAIL FOR TYP.CONDUIT PENETRATION LOCATIONS

TO IDNET (M1)FERRITE BEAD

CLICK HERETO ADJUSTCKT WIRING

CLICK HERETO ADJUSTCKT WIRING

CLICK HERETO ADJUSTCKT WIRING

CLICK HERETO ADJUSTCH1 CKTS

CLICK HERETO ADJUSTCH2 CKTS

CLICK HERETO ADJUSTCH3 CKTS

CLICK HERETO ADJUSTIDNet CKT

CLICK HERETO ADJUSTCH1 CKTS

CLICK HERETO ADJUSTCH2 CKTS

CLICK HERETO ADJUSTCH3 CKTS

TO 1ST FLOOR (A1:1)

TO 1ST FLOOR (A1:2)

TO 1ST FLOOR GYM (A1:3)

TO 2ND FLOOR (A2:1)

TO 2ND FLOOR (A2:2)

TO WELLNESS CENTER (A2:3)

EFORPDERETSI

GER

REEN

IGN

E

LANOISS

C A L I F OR N I AS T A T E O F

R I C A LE L E C T

No. E16806

JASON LAU

E N G I N E E R I N GI N T E R F A C E

TEL

FAX

PROJECT

CONTACT

www.interfaceengineering.com

717 Market Street

Suite 500

San Francisco, CA 94103

415.489.7240

415.489.7289

SHEET NO:

DATE:

PROJECT NO:

THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THEPURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVEAND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THEWRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONALSERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2009.

THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECTAND ENGINEER.

CONSULTANT

6910 5 31112 8 7 4 2 1

J

K

H

G

F

E

D

C

B

A

B

A

J

K

H

G

F

E

D

C

6910 5 31112 8 7 4 2 1

NO. ISSUE DATE

ARCHITECT'S STAMP APPROVAL

Joe Ripp

2014-0174

SAN JOSE CITYCOLLEGE

PHYSICAL EDUCATION BUILDING ANDRENOVATED LAB BUILDING

SAN JOSE, CALIFORNIA

CONTROL PANEL DIAGRAM- FIRE ALARM

FA5.01

1.12.2015

1089-0001

DSA SUBMITTAL

Page 7: SAN JOSE CITY - SJECCD Fire Alarm.pdf · relay iam simplex 4090-9002 4" square box 2 1/8" deep w/two gang cover individual addressable module simplex 4090-9001 single gang ... installation

4100 FACP 1ST FLOOR ELECTRICAL ROOM 136 4100es FACP

Standby Total Alarm Total

Module Qty Description Current Standby Current Alarm

Panel Equipment

4100-9311 1 4100 CONFIG. DOMESTIC 120V * 0.4250 0.4250 0.7350 0.7350

4100-1327 2 DIGITAL FLEX 50W AMP W/3 NACS - 70V 0.0850 0.1700 2.2700 4.5400

4100-5101 1 EXPANSION PWR SUPPLY (XPS) - 120VAC 60HZ 0.0500 0.0500 0.0500 0.0500

4100-6057 2 NETWORK MEDIA CARD FIBER OPTIC 0.0250 0.0500 0.0250 0.0500

4100-5311 1 ENHANCED POWER SUPPLY, 3 CHANNELS, IDNet1+, 120V 0.2250 0.2250 0.4900 0.4900

4100-6078 1 NETWORK IF CARD, MODULAR 0.0460 0.0460 0.0460 0.0460

4100-9621 1 BASIC AUDIO WITH MICROPHONE - DIGITAL 0.0750 0.0750 0.0820 0.0820

4100-6052 1 EVENT REPORTING DACT 0.0300 0.0300 0.0400 0.0400

4100-1241 1 MESSAGE EXPANSION BOARD - 8 MINUTES 0.0020 0.0020 0.0170 0.0170

4100-1288 1 64/64 LED/SWITCH CONTROLLER 0.0200 0.0200 0.0200 0.0200

4100-1279 13 2" BLANK DISPLAY MODULE 0.0000 0.0000 0.0000 0.0000

4100-0634 1 POWER DISTRIBUTION MODULE 120V 0.0000 0.0000 0.0000 0.0000

4100-2320 1 AUDIO EXPANSION BAY KIT 0.0000 0.0000 0.0000 0.0000

4100-0636 1 BOX TO BOX HARNESS KIT 0.0000 0.0000 0.0000 0.0000

4100-1284 1 8 SW, 16 RED/GREEN LED MODULE 0.0000 0.0000 0.0240 0.0240

Panel Totals 1.0930 6.0940

IDNet Addressable Devices (SLC)

4099-9004 13 ADDRESSABLE SINGLE ACTION MANUAL STATION *

Device Current Draw on the IDNet Addressable Channel(s) is included inthe Battery Selection Set below.

4090-9001 3 IDNET SUPERVISED IAM *

4090-9002 4 IDNET RELAY IAM *

4098-9714 24 TRUEALARM PHOTO SMOKE SENSOR

4098-9733 2 TRUEALARM HEAT SENSOR

4098-9756 3 TRUEALARM DUCT SMOKE SENSOR W/ RELAY OUTPUT *

4098-9792 26 TRUEALARM SENSOR BASE *

Miscellaneous Peripheral Devices That May Require System Power

4098-9843 3 ENCAPSULATED RELAY PAM-SD 0.0000 0.0000 0.0150 0.0450

4098-9756 3 TRUEALARM DUCT SMOKE SENSOR W/ RELAY OUTPUT 0.0030 0.0090 0.0150 0.0450

Notification Appliances

4906-9204 3 ADDRESSABLE CEILING MNT MC V/O, WHITE 15 0.0002 0.0006 0.0600 0.1800

4906-9253 1 ADDRESSABLE WALL MNT MC S/V, WHITE 75 0.0002 0.0002 0.1370 0.1370

4906-9254 3 ADDRESSABLE CEILING MNT S/V 25V/70VRMS WHITE 110 0.0002 0.0006 0.2400 0.7200

4906-9254 15 ADDRESSABLE CEILING MNT S/V 25V/70VRMS WHITE 15 0.0002 0.0030 0.0600 0.9000

4906-9254 13 ADDRESSABLE CEILING MNT S/V 25V/70VRMS WHITE 30 0.0002 0.0026 0.0920 1.1960

4906-9254 17 ADDRESSABLE CEILING MNT S/V 25V/70VRMS WHITE 75 0.0002 0.0034 0.1800 3.0600

49VO-WWFO-BA 6 VO, WALL MT, WHITE, FIRE LABEL, WEATHERPROOF WP75 0.0008 0.0048 0.2120 1.2720

49VO-WWF 4 VO, WALL MT, WHITE, FIRE LABEL 135 0.0008 0.0032 0.1600 0.6400

Peripheral Totals 0.0290 8.2890

Added Current for EPS Conversion of 24 to 29 Volt IDNac Devices 0.0000 3.0336

RUI Totals 0 0.0000 0.0000

Address Totals 49 Addresses 0.0392 0.0490

* Device Address current draw included below (See Additional Current Draws): Total Standby 1.1612 Total Alarm 17.4656

2. Backup Amplifier assumes Main Amplifier alarm current on failure.

Standby Standby Alarm Alarm

Battery Set #1 (Cabinet/Charger #1) Current Total Current Total

Select ALL Power Supplies on this battery set:

EPS-1 0.7040 5.6300

EPS-2 0.2320 4.1880

XPS-3 0.1950 4.5650

Sub Total 1.1310 14.3830

Additional Current Draws:

Current for Conversion of Battery Voltage to 29 volt EPS IDNAC Devices 0.0000 3.0336

MAPNET/IDNet Device Address Communication Current 49 x 0.000800 = 0.0392 x 0.001000 = 0.0490

Sub Total 1.1702 17.4656

Spare addressable point capacity 0% 0 x 0.0008 = 0.0000 x 0.001 = 0.0000

Total 1.1702 17.4656

Standby Time = 24 Hrs x 1.1702 = 28.0848 Standby Ah

Alarm Time = 15 Min 0.25 x 17.4656 = 4.3664 Alarm Ah

32.4512

Additional Spare Battery Capacity = 0% + 0.0000

32.4512

Battery Discharge Factor = 20% + 6.4902

Minimum Battery Required 2081-9296 50AH (2x) 38.9414

Battery Supplied 2081-9296 50AH (2x)

A1:1 Notification SLC Distributed Load Voltage Drop

Allowable % Drop: 20.7% Wire Res. Per Ft. 0.0019 @ 75° Celsius

Wire Gauge: 12ga Min. Device Voltage: 23.vdcStarting Voltage: 29vdc

Class B Calculations

Distance Device Current Voltage Voltage Branch

Branch Device # From (Feet) PID Candela Draw at Device Drop at Device % Drop

1 A1:1-1 PANEL 30 4906-9254 110cd 0.2400 2.321 0.269 28.731 Branch 1: 4.44%

1 A1:1-2 A1:1-1 37 4906-9254 15cd 0.0600 0.428 0.061 28.670

1 A1:1-3 A1:1-2 18 4906-9254 30cd 0.0920 0.368 0.026 28.645

1 A1:1-4 A1:1-3 24 4906-9254 30cd 0.0920 0.276 0.026 28.619

1 A1:1-5 A1:1-4 27 4906-9254 30cd 0.0920 0.184 0.019 28.600

1 A1:1-6 A1:1-5 25 4906-9254 30cd 0.0920 0.092 0.009 28.591

1 A1:1-7 A1:1-1 30 4906-9254 30cd 0.0920 1.653 0.191 28.540

1 A1:1-8 A1:1-7 46 49VO-WWFO-BA WP75 0.2120 0.212 0.038 28.502

1 A1:1-9 A1:1-7 17 4906-9254 30cd 0.0920 1.349 0.089 28.451

1 A1:1-10 A1:1-9 46 49VO-WWFO-BA WP75 0.2120 0.212 0.038 28.414

1 A1:1-11 A1:1-9 21 4906-9254 75cd 0.1800 1.045 0.085 28.367

1 A1:1-12 A1:1-11 117 4906-9254 30cd 0.0920 0.865 0.391 27.976

1 A1:1-13 A1:1-12 17 4906-9254 75cd 0.1800 0.773 0.051 27.925

1 A1:1-14 A1:1-13 39 4906-9253 75cd 0.1370 0.593 0.089 27.836

1 A1:1-15 A1:1-14 25 4906-9254 30cd 0.0920 0.456 0.044 27.792

1 A1:1-16 A1:1-15 39 4906-9254 75cd 0.1800 0.364 0.055 27.737

1 A1:1-17 A1:1-16 25 4906-9254 30cd 0.0920 0.184 0.018 27.719

1 A1:1-18 A1:1-17 21 4906-9254 30cd 0.0920 0.092 0.007 27.712

Totals: 604 Ft.

A1:2 Distributed Load Voltage Drop

Allowable % Drop: 20.7% Wire Res. Per Ft. 0.0019 @ 75° Celsius

Wire Gauge: 12ga Min. Device Voltage: 23.vdcStarting Voltage: 29vdc

Class B Calculations

Distance Device Current Voltage Voltage Branch

Branch Device # From (Feet) PID Candela Draw at Device Drop at Device % Drop

1 A1:2-1 PANEL 239 4906-9254 15cd 0.0600 1.540 1.421 27.579 Branch 1: 7.89%

1 A1:2-2 A1:2-1 42 4906-9254 15cd 0.0600 1.480 0.240 27.339

1 A1:2-3 A1:2-2 48 4906-9254 15cd 0.0600 1.420 0.263 27.076

1 TAP1 A1:2-3 26 JBOX 0.0000 1.360 0.136 26.940

1 A1:2-4 TAP1 25 4906-9204 15cd 0.0600 0.516 0.050 26.890

1 A1:2-5 A1:2-4 14 4906-9254 15cd 0.0600 0.060 0.003 26.887

1 A1:2-6 A1:2-4 18 49VO-WWFO-BA WP75 0.2120 0.396 0.028 26.862

1 A1:2-7 A1:2-6 15 4906-9254 30cd 0.0920 0.184 0.011 26.852

1 A1:2-8 A1:2-7 20 4906-9254 30cd 0.0920 0.092 0.007 26.845

1 A1:2-9 TAP1 34 4906-9254 15cd 0.0600 0.844 0.111 26.829

1 A1:2-10 A1:2-9 12 4906-9204 15cd 0.0600 0.152 0.007 26.822

1 A1:2-11 A1:2-10 16 4906-9254 30cd 0.0920 0.092 0.006 26.816

1 TAP2 A1:2-9 31 JBOX 0.0000 0.632 0.076 26.753

1 A1:2-12 TAP2 14 4906-9204 15cd 0.0600 0.452 0.024 26.729

1 TAP3 A1:2-12 4 JBOX 0.0000 0.392 0.006 26.723

1 A1:2-13 TAP3 12 4906-9254 15cd 0.0600 0.120 0.006 26.717

1 A1:2-14 A1:2-13 9 4906-9254 15cd 0.0600 0.060 0.002 26.715

1 A1:2-15 TAP3 9 4906-9254 15cd 0.0600 0.060 0.002 26.721

1 A1:2-16 TAP3 14 49VO-WWFO-BA WP75 0.2120 0.212 0.011 26.711

1 A1:2-17 TAP2 26 4906-9254 15cd 0.0600 0.180 0.018 26.735

1 A1:2-18 A1:2-17 16 4906-9254 15cd 0.0600 0.120 0.007 26.728

1 A1:2-19 A1:2-18 19 4906-9254 15cd 0.0600 0.060 0.004 26.723

Totals: 663 Ft.

A1:3 Distributed Load Voltage Drop

Allowable % Drop: 20.7% Wire Res. Per Ft. 0.0019 @ 75° Celsius

Wire Gauge: 12ga Min. Device Voltage: 23.vdcStarting Voltage: 29vdc

Class B Calculations

Distance Device Current Voltage Voltage Branch

Branch Device # From (Feet) PID Candela Draw at Device Drop at Device % Drop

1 A1:3-1 PANEL 105 49VO-WWF 135cd 0.1600 0.640 0.259 28.741 Branch 1: 2.13%

1 A1:3-2 A1:3-1 55 49VO-WWF 135cd 0.1600 0.480 0.102 28.639

1 A1:3-3 A1:3-2 180 49VO-WWF 135cd 0.1600 0.320 0.222 28.416

1 A1:3-4 A1:3-3 54 49VO-WWF 135cd 0.1600 0.160 0.033 28.383

Totals: 394 Ft.

4100 FACP 1ST FLOOR ELECTRICAL ROOM 136 - EPS-1 CIRCUIT SUMMARY & VOLTAGE DROP

Alarm Unit Wire Spare

Channel Description Current % Drop Load* Length Capacity

A1:1 1ST FLOOR 2.321A 4.44% 18 604 23%

A1:2 1ST FLOOR 1.540A 7.89% 19 663 49%

A1:3 1ST FLOOR GYM 0.640A 2.13% 4 394 79%

EFORPDERETSI

GER

REEN

IGN

E

LANOISS

C A L I F OR N I AS T A T E O F

R I C A LE L E C T

No. E16806

JASON LAU

E N G I N E E R I N GI N T E R F A C E

TEL

FAX

PROJECT

CONTACT

www.interfaceengineering.com

717 Market Street

Suite 500

San Francisco, CA 94103

415.489.7240

415.489.7289

SHEET NO:

DATE:

PROJECT NO:

THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THEPURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVEAND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THEWRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONALSERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2009.

THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECTAND ENGINEER.

CONSULTANT

6910 5 31112 8 7 4 2 1

J

K

H

G

F

E

D

C

B

A

B

A

J

K

H

G

F

E

D

C

6910 5 31112 8 7 4 2 1

NO. ISSUE DATE

ARCHITECT'S STAMP APPROVAL

Joe Ripp

2014-0174

SAN JOSE CITYCOLLEGE

PHYSICAL EDUCATION BUILDING ANDRENOVATED LAB BUILDING

SAN JOSE, CALIFORNIA

CALCULATIONS - FIREALARM

FA6.01

1.12.2015

1089-0001

DSA SUBMITTAL

Page 8: SAN JOSE CITY - SJECCD Fire Alarm.pdf · relay iam simplex 4090-9002 4" square box 2 1/8" deep w/two gang cover individual addressable module simplex 4090-9001 single gang ... installation

4100 FACP 1ST FLOOR ELECTRICAL ROOM 136 - EPS-2 CIRCUIT SUMMARY & VOLTAGE DROP

Alarm Unit Wire Spare

Channel Description Current % Drop Load* Length Capacity

A2:1 2ND FLOOR 1.592A 3.15% 8 343 47%

A2:2 2ND FLOOR 0.392A 0.67% 4 215 87%

A2:3 WELLNESS CENTER 1.714A 7.12% 11 479 43%

4100 FACP 1ST FLOOR ELECTRICAL ROOM 136 4100es FACP Speaker Db Loss Calculations

*Circuit Voltage = 70vrms [Et] MAXIMUM -3 dB DROP

Total Total Wire Est. Ckt. Wire Res. Circuit Speaker Speaker Voltage Watts Actual Max Allowable

Plan Speaker Speaker Speaker Speaker Spkrs Watts Gauge Length Per Foot Resistance Current Resistance At End At End dB Loss Ckt. Length

SPEAKER CIRCUIT DESCRIPTION Circuit Tap Tap Tap Tap per [P] [D] in [Rw] [Rl=2D*Rw] [I=P/Et] [Rs=Et/I] [Es=(Et*Rs) [Pe=(Es) [dB=Log10 [ML=(0.414*Rs)Amp # Number .25 Watt .5 Watt 1. Watt 2. Watt Circuit Feet /(Rs+Rl)] *2/Rs] (Pe/P)*10] /(2*Rw)]

1ST FLOOR Amp-1 S1 5 14 19 8.25 Watts 16ga 620 0.0049 6.064 0.118 593.939 69.293 8.084 -.09 db 25142 Ft.

1ST FLOOR Amp-1 S2 9 11 20 7.75 Watts 16ga 680 0.0049 6.650 0.111 632.258 69.271 7.590 -.09 db 26764 Ft.

2ND FLOOR Amp-1 S3 8 8 4. Watts 16ga 447 0.0049 4.372 0.057 1225.000 69.751 3.972 -.03 db 51856 Ft.

1ST FLOOR GYM Amp-2 S4 10 10 20. Watts 16ga 410 0.0049 4.010 0.286 245.000 68.873 19.361 -.14 db 10371 Ft.

2ND FLOOR Amp-2 S5 5 1 6 3.25 Watts 16ga 158 0.0049 1.545 0.046 1507.692 69.928 3.243 -.01 db 63823 Ft.

WELLNESS CENTER Amp-2 S6 2 6 1 9 4.5 Watts 16ga 500 0.0049 4.890 0.064 1088.889 69.687 4.460 -.04 db 46094 Ft.

Amplifier Watts Alarm Expansion Avail. Used %Wattage Used Card? Ckts. Ckts. Used

Amp-1 50 20.W 2.270A Yes 6 4 40.00%

Amp-2 50 27.75W 2.270A Yes 6 3 55.50%

IDNET CHANNEL M1 SWITCH SETTINGS

Address Device Type Point Type Location Description 1 2 3 4 5 6 7 8

M1-1 PHOTO SMOKE 1ST FLR ELEC 136 XX X X X X X X

ON

M1-2 ADRPUL PULL 1ST FLR ELEC 136 XX

X X X X X XON

M1-3 ADRPUL PULL 1ST FLR TICKETS/CONCESSION 124 X XX X X X X X

ON

M1-4 ADRPUL PULL 1ST FLR MACH RM 120 X XX

X X X X XON

M1-5 HEAT HEAT 1ST FLR MACH RM 120 XX

XX X X X X

ON

M1-6 PHOTO SMOKE 1ST FLR MACH RM 120 XX X

X X X X XON

M1-7 IAM SUPERV 1ST FLR MACH RM 120 POWER MONITOR X X XX X X X X

ON

M1-8 RIAM PRIMARY 1ST FLR MACH RM 120 PRIMARY RECALL X X XX

X X X XON

M1-9 RIAM ALTERN 1ST FLR MACH RM 120 ALTERN RECALL XX X

XX X X X

ON

M1-10 RIAM RELAY 1ST FLR MACH RM 120 HAT FLASH XX

XX

X X X XON

M1-11 RIAM RELAY 1ST FLR MACH RM 120 SHUNT TRIP X XX

XX X X X

ON

M1-12 PHOTO SMOKE 1ST FLR ELEV E1.1 LOBBY X XX X

X X X XON

M1-13 ADRPUL PULL 1ST FLR HALL 137 XX

X XX X X X

ON

M1-14 ADRPUL PULL 1ST FLR EAST CORRIDOR 137 XX X X

X X X XON

M1-15 ADRPUL PULL 1ST FLR FOOTBALL LOCKER RM 146 X X X XX X X X

ON

M1-16 ADRPUL PULL 1ST FLR SOUTH CORRIDOR 150 X X X XX

X X XON

M1-17 IAM SO 1ST FLR LAUNDRY 159 XX X X

XX X X

ON

M1-18 IAM WATER 1ST FLR LAUNDRY 159 XX

X XX

X X XON

M1-19 ADRPUL PULL 1ST FLOOR TRAINING ROOM138 X XX X

XX X X

ON

M1-20 ADRPUL PULL 1ST FLOOR MULTIPURPOSE 141 X XX

XX

X X XON

M1-21 XX

XX

XX X X

ON

M1-22 XX X

XX

X X XON

M1-23 X X XX

XX X X

ON

M1-24 X X XX X

X X XON

M1-25 RPHOTO DUCT 2ND FLR FITNESS CENTER 202 AHU-3 XX X

X XX X X

ON

M1-26 RPHOTO DUCT 2ND FLR FITNESS CENTER 202 AHU-2 XX

XX X

X X XON

M1-27 PHOTO SMOKE 2ND FLR ELEV E1.1 LOBBY X XX

X XX X X

ON

M1-28 ADRPUL PULL 2ND FLR CORRIDOR 201 X XX X X

X X XON

M1-29 ADRPUL PULL 2ND FLR CORRIDOR 201 XX

X X XX X X

ON

M1-30 RPHOTO DUCT 2ND FLR AHU-1 XX X X X

X X XON

M1-31 X X X X XX X X

ON

M1-32 X X X X XX

X XON

M1-33 XX X X X

XX X

ON

M1-34 XX

X X XX

X XON

M1-35 X XX X X

XX X

ON

M1-36 X XX

X XX

X XON

M1-37 XX

XX X

XX X

ON

M1-38 XX X

X XX

X XON

M1-39 X X XX X

XX X

ON

M1-40 X X XX

XX

X XON

M1-248 X X XX X X X X ON

M1-249 THRU SPARE XX X

X X X X X ON

M1-250 XX

XX X X X X ON

NOTE: THE LABELS SHOWN ABOVE WILL BE USED FOR PROGRAMMING PURPOSES.

THE LABELS ARE BASED UPON INFORMATION SHOWN ON THE ARCHITECTURAL DRAWINGS.

ANY CHANGES TO THESE LABELS MUST BE NOTED ON THE SUBMITTAL REVIEW, PRIOR TO PROGRAMMING.

POINTS SHOWN IN ITALIC TEXT REFER TO EXISTING DEVICES.

A2:1 Notification SLC Distributed Load Voltage Drop

Allowable % Drop: 20.7% Wire Res. Per Ft. 0.0019 @ 75° Celsius

Wire Gauge: 12ga Min. Device Voltage: 23.vdcStarting Voltage: 29vdc

Class B Calculations

Distance Device Current Voltage Voltage Branch

Branch Device # From (Feet) PID Candela Draw at Device Drop at Device % Drop

1 A2:1-1 PANEL 103 4906-9254 110cd 0.2400 1.592 0.633 28.367 Branch 1: 3.15%

1 A2:1-2 A2:1-1 26 4906-9254 110cd 0.2400 0.600 0.060 28.307

1 A2:1-3 A2:1-2 51 4906-9254 75cd 0.1800 0.360 0.071 28.236

1 A2:1-4 A2:1-3 24 4906-9254 75cd 0.1800 0.180 0.017 28.219

1 A2:1-5 A2:1-1 51 4906-9254 75cd 0.1800 0.752 0.148 28.219

1 A2:1-6 A2:1-5 29 4906-9254 75cd 0.1800 0.572 0.064 28.155

1 A2:1-7 A2:1-6 30 4906-9254 75cd 0.1800 0.392 0.045 28.110

1 A2:1-8 A2:1-7 29 49VO-WWFO-BA WP75 0.2120 0.212 0.024 28.086

Totals: 343 Ft.

A2:2 Distributed Load Voltage Drop

Allowable % Drop: 20.7% Wire Res. Per Ft. 0.0019 @ 75° Celsius

Wire Gauge: 12ga Min. Device Voltage: 23.vdcStarting Voltage: 29vdc

Class B Calculations

Distance Device Current Voltage Voltage Branch

Branch Device # From (Feet) PID Candela Draw at Device Drop at Device % Drop

1 TAP1 PANEL 84 JBOX 0.0000 0.392 0.127 28.873 Branch 1: 0.67%

1 A2:2-1 TAP1 18 4906-9254 15cd 0.0600 0.120 0.008 28.865

1 A2:2-2 A2:2-1 41 4906-9254 15cd 0.0600 0.060 0.009 28.855

1 A2:2-3 TAP1 41 4906-9254 15cd 0.0600 0.272 0.043 28.830

1 A2:2-4 A2:2-3 31 49VO-WWFO-BA WP75 0.2120 0.212 0.025 28.804

Totals: 215 Ft.

A2:3 Distributed Load Voltage Drop

Allowable % Drop: 20.7% Wire Res. Per Ft. 0.0019 @ 75° Celsius

Wire Gauge: 12ga Min. Device Voltage: 23.vdcStarting Voltage: 29vdc

Class B Calculations

Distance Device Current Voltage Voltage Branch

Branch Device # From (Feet) PID Candela Draw at Device Drop at Device % Drop

1 A2:3-1 PANEL 200 4906-9254 75cd 0.1800 1.714 1.323 27.677 Branch 1: 7.12%

1 A2:3-2 A2:3-1 17 4906-9254 75cd 0.1800 1.534 0.101 27.576

1 A2:3-3 A2:3-2 29 4906-9254 75cd 0.1800 1.354 0.152 27.425

1 A2:3-4 A2:3-3 29 4906-9254 75cd 0.1800 1.174 0.131 27.293

1 A2:3-5 A2:3-4 12 4906-9254 75cd 0.1800 0.994 0.046 27.247

1 A2:3-6 A2:3-5 29 49VO-WWF 15cd 0.0470 0.814 0.091 27.156

1 TAP1 A2:3-6 23 JBOX 0.0000 0.767 0.068 27.088

1 A2:3-7 TAP1 27 49VO-WWF 15cd 0.0470 0.587 0.061 27.027

1 A2:3-8 A2:3-7 21 4906-9254 75cd 0.1800 0.540 0.044 26.983

1 A2:3-9 A2:3-8 20 4906-9254 75cd 0.1800 0.360 0.028 26.955

1 A2:3-10 A2:3-9 30 4906-9254 75cd 0.1800 0.180 0.021 26.934

1 A2:3-11 TAP1 42 4906-9254 75cd 0.1800 0.180 0.029 27.059

Totals: 479 Ft.

IDNET CHANNEL M2 SWITCH SETTINGS

Address Device Type Point Type Location Description 1 2 3 4 5 6 7 8

M2-1 ADRPUL PULL 1ST FLR WELLNESS CNTR VEST 10 XX X X X X X X

ON

M2-2 PHOTO SMOKE 1ST FLR WELLNESS CNTR VEST 10 XX

X X X X X XON

M2-3 ADRPUL PULL 1ST FLR WELLNESS CNTR VEST 115 X XX X X X X X

ON

M2-4 PHOTO SMOKE 1ST FLR WELLNESS CNTR VEST 115 X XX

X X X X XON

M2-5 PHOTO SMOKE 1ST FLR WELLNESS CNTR TOILET 14 XX

XX X X X X

ON

M2-6 PHOTO SMOKE 1ST FLR WELLNESS CNTR TOILET 13 XX X

X X X X XON

M2-7 HEAT HEAT 1ST FLR WELLNESS CNTR JANITOR 12 X X XX X X X X

ON

M2-8 PHOTO SMOKE MEZZANINE WELLNESS CNTR STORAGE 22 X X XX

X X X XON

M2-9 PHOTO SMOKE MEZZANINE WELLNESS CNTR MECH 24 XX X

XX X X X

ON

M2-10 PHOTO SMOKE MEZZANINE WELLNESS CNTR EXERCISE LAB 16 XX

XX

X X X XON

M2-11 PHOTO SMOKE MEZZANINE WELLNESS CNTR EXERCISE LAB 16 X XX

XX X X X

ON

M2-12 PHOTO SMOKE MEZZANINE WELLNESS CNTR EXERCISE LAB 16 X XX X

X X X XON

M2-13 PHOTO SMOKE MEZZANINE WELLNESS CNTR EXERCISE LAB 16 XX

X XX X X X

ON

M2-14 PHOTO SMOKE MEZZANINE WELLNESS CNTR EXERCISE LAB 16 XX X X

X X X XON

M2-15 PHOTO SMOKE MEZZANINE WELLNESS CNTR EXERCISE LAB 16 X X X XX X X X

ON

M2-16 PHOTO SMOKE MEZZANINE WELLNESS CNTR STORAGE 22 X X X XX

X X XON

M2-17 PHOTO SMOKE MEZZANINE WELLNESS CNTR MECH 27 XX X X

XX X X

ON

M2-18 PHOTO SMOKE MEZZANINE WELLNESS CNTR EXERCISE LAB 11 XX

X XX

X X XON

M2-19 PHOTO SMOKE MEZZANINE WELLNESS CNTR EXERCISE LAB 11 X XX X

XX X X

ON

M2-20 PHOTO SMOKE MEZZANINE WELLNESS CNTR EXERCISE LAB 11 X XX

XX

X X XON

M2-21 PHOTO SMOKE MEZZANINE WELLNESS CNTR EXERCISE LAB 11 XX

XX

XX X X

ON

M2-22 PHOTO SMOKE MEZZANINE WELLNESS CNTR EXERCISE LAB 11 XX X

XX

X X XON

M2-23 PHOTO SMOKE MEZZANINE WELLNESS CNTR EXERCISE LAB 11 X X XX

XX X X

ON

M2-24 X X XX X

X X XON

M2-25 XX X

X XX X X

ON

M2-26 XX

XX X

X X XON

M2-27 X XX

X XX X X

ON

M2-28 X XX X X

X X XON

M2-29 XX

X X XX X X

ON

M2-30 XX X X X

X X XON

M2-249 THRU SPARE XX X

X X X X X ON

M2-250 XX

XX X X X X ON

NOTE: THE LABELS SHOWN ABOVE WILL BE USED FOR PROGRAMMING PURPOSES.

THE LABELS ARE BASED UPON INFORMATION SHOWN ON THE ARCHITECTURAL DRAWINGS.

ANY CHANGES TO THESE LABELS MUST BE NOTED ON THE SUBMITTAL REVIEW, PRIOR TO PROGRAMMING.

POINTS SHOWN IN ITALIC TEXT REFER TO EXISTING DEVICES.

EFORPDERETSI

GER

REEN

IGN

E

LANOISS

C A L I F OR N I AS T A T E O F

R I C A LE L E C T

No. E16806

JASON LAU

E N G I N E E R I N GI N T E R F A C E

TEL

FAX

PROJECT

CONTACT

www.interfaceengineering.com

717 Market Street

Suite 500

San Francisco, CA 94103

415.489.7240

415.489.7289

SHEET NO:

DATE:

PROJECT NO:

THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THEPURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVEAND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THEWRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONALSERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2009.

THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECTAND ENGINEER.

CONSULTANT

6910 5 31112 8 7 4 2 1

J

K

H

G

F

E

D

C

B

A

B

A

J

K

H

G

F

E

D

C

6910 5 31112 8 7 4 2 1

NO. ISSUE DATE

ARCHITECT'S STAMP APPROVAL

Joe Ripp

2014-0174

SAN JOSE CITYCOLLEGE

PHYSICAL EDUCATION BUILDING ANDRENOVATED LAB BUILDING

SAN JOSE, CALIFORNIA

CALCULATIONS - FIREALARM

FA6.02

1.12.2015

1089-0001

DSA SUBMITTAL

Page 9: SAN JOSE CITY - SJECCD Fire Alarm.pdf · relay iam simplex 4090-9002 4" square box 2 1/8" deep w/two gang cover individual addressable module simplex 4090-9001 single gang ... installation

581PW57PW

5751

ABILITY TO CONNECT USING "T" TAPPING FOR CLASS B/STYLE 4CIRCUITS TO SIMPLIFY WIRING

TrueAlert ES (STYLE 4 SLC) VISIBLE ONLY NOTIFICATION APPLIANCES 49VO SERIESTM

6. THE TrueAlert V/O CAN ONLY BE OPERATED THROUGH A 4009 TrueAlert ADDRESSABLE CONTROLLER OR TrueAlert COMPATIBLE FACP.

TO THE V/O UNIT.

5. POWERING THE V/O FROM AN APPLIANCE POWER SOURCE LESS THAN 17 VDC OR GREATER THAN 32 VDC MAY CAUSE PERMANENT DAMAGE.

4. ALL TrueAlert SLC WIRING CONNECTIONS ARE SUPERVISED AND POWER-LIMITED.

3. MAINTAIN CORRECT POLARITY ON TERMINAL CONNECTIONS. DO NOT LOOP WIRES UNDER TERMINALS.

2. NOTIFICATION APPLIANCES ARE RATED PER INDIVIDUAL NAMEPLATE LABEL.

TrueAlert V/O UNITS- DIP SWITCH ADDRESS CHART

CONNECTIONS: TERMINAL BLOCKS FOR 18 TO 12 AWG

HUMIDITY RANGE: 10% TO 93% NON-CONDENSING AT 104° F (40° C)

(130 mm X 127 mm X 67 mm)HOUSING DIMENSIONS (INCLUDING LENS): 5 1/8" H X 5" W X 2 5/8" D

TEMPERATURE RANGE: -31° TO 120° F (-35° TO 49° C)

GENERAL SPECIFICATIONS:

WIRING NOTES:

FLEXIBLE, EASY, AND CONVENIENT FLUSH OR SURFACE WALL BOX MOUNTING

TrueAlert NOTIFICATION APPLIANCE DESIGN PROVIDES

CONTINUOUSLY, CONTROLLED SEPARATELY FROM VISIBLE APPLIANCESHORNS SOUNDED AS TEMPORAL OR MARCH TIME PATTERN, OR ON

AND AUDIBLE NOTIFICATION ACTIVATES APPLIANCES WITH:TrueAlert 2-WIRE ADDRESSABLE CONTROL OF VISIBLE

AND IS SELECTABLE TO ALSO BRIEFLY FLASH THE STROBE TO

MAGNETIC TEST PULSES THE LED TO INDICATE APPLIANCE ADDRESS

WHEN THE TrueAlert CONTROLLER IS IN DIAGNOSTIC MODE, THE

LED INDICTOR CAN BE ELECTED TO DISPLAY EACH POLLING CYCLE

MAGNETIC TEST DIAGNOSTICS TO ASSIST CHECKOUT AND TESTINGEASY ACCESS FOR INSTALLATION, INSPECTION, AND TESTING

IN/OUT WIRING ACCESSIBILITY FROM FRONT OF HOUSING PROVIDES

HIGH INTENSITY XENON STROBE PROVIDES:NOTIFICATION APPLIANCES WITH EFFICIENT ELECTRONIC

HORNS CONTROLLED SEPARATELY FROM STROBES ON THE SAME

INDIVIDUALLY ADDRESSED WALL MOUNT VISIBLE

SUPERVISION OF EACH INDIVIDUAL APPLIANCE'S WIRING AND

UL LISTED TO STANDARD 1971

SPECIFICATIONS:

LED INDICATOR AND MAGNETIC TEST FEATURE:

STROBE:

STROBE FLASH RATE: 1 HzSUPERVISORY REQUIREMENTS: 1 UNIT LOAD

ON THE SAME TWO-WIRE CIRCUIT

RATED VOLTAGE RANGE: 23 TO 31 VRMS

TO INDICICATE APPLIANCE SUPERVISION

OF APPLIANCES AND WIRING

CONFIRM OPERATION

FEATURES:

PRODUCT INFORMATION

"ON-UNTIL RESET".

2-WIRE CIRCUIT ALLOWING "ON-UNTIL-SILENCED" AND

CONNECTIONS

110, 135 AND 185 CANDELA OR "FACP". THE "FACP" SETTING ALLOWS

XENON STROBE OUTPUT IS MANUALLY SELECTABLE FOR 15, 30, 75,

THE 4100 TO PROGRAM THE CANDELA SETTING.

1. REFER TO FIELD WIRING DIAGRAMS OF THE DRIVING TrueAlert COMPATIBLE CONTROLLER FOR ADDITIONAL SLC WIRING INFORMATION.

WEATHER PROOF BOX 1-5/8" DEEP

SURFACE MOUNTING

SIMPLEX 49WPBB-AVVOWR

ADDRESS SETTING

DIP SWITCH

CONFIGURATIONDIP SWITCH

ACCESSABLE FROM REAR

LOCATIONMAGNETIC TEST

SIMPLEX 4905-9899

4603-9101 REMOTE ANNUNCIATOR

FEATURES:

PRODUCT INFORMATION

UL LISTED

SPECIFICATIONS:

FLUSH MOUNT ON STANDARD ELECTRICAL BOXES

FM APPROVED

TB1

TB2

TO ADDITIONAL 24VDC POWERED DEVICES IF USED

FROM 24 VDC POWER SOURCE

FOR RUI ADDRESSABLE SETUPSEE INSTALLATION INSTRUCTIONS579-

ON

OF F

FLUSH MOUNTING

++ - -

++-- SS

4.29

4.29

4.094.29

4.29

COM +

SLC +SLC +SLC CONTROLLER (SEE NOTES)FROM TrueAlert COMPATIBLE SLC -

SLC +

-1

CKT +2

SLC -

49VO

-1

CKT

SLC -

+2

SLC +

-1 2

CKT +1

SLC -

- CKT +2

49VO 49VO 49VO

-1

CKT +2

49VO

CURRENT: ALARM 140mA

OPERATING TEMPERATURE: 32° F TO 120° F

FINISH: LIGHT BROWN ENAMEL

VOLTAGE: 24VDC NOMINAL

HUMIDITY RANGE: 10% TO 90% RH FROM 32° F TO 104° F

OPTIONS

BRUSHED ALUMINUM TRIM: 4603-9111

DIMENSIONS 11 31/32"L X 4 5/8" W X 2 3/4"D

SURFACE BOX: 2975-9206

STANDARD TRIM: BEIGE (SUPPLIED WITH BOTH SLOTTED AND

TAMPERPROOF SCREWS)

TO FLUSH-MOUNT IN MASONRY WALLS, USE AA RAYCO 965 (3-1/2" DEEP) MASONRY BOX ORITS EQUIVALENT.

STEEL CITY GW-635-G OR A RAYCO EQUIVALENT.TO FLUSH-MOUNT IN PLASTERBOARD WALLS, USE A

TO SURFACE-MOUNT, USE A SIMPLEX 2975-9206BACK BOX

NOTES:

ALL WIRING TO BE No. 18 AWG OR TO LOCAL CODE.

ALL WIRING SUPERVISED

WIRE TO BE 18 AWG TWISTED SHIELDED PAIR RECOMMENDEDCONSULT SALES ENGINEERING FOR EXCEPTIONS.2500 FT ONE WAY MAX COMMUNICATION LINE POWER32 VDC MAX130 mA MAX1200 OR 9600 BAUD

WHEN WIRING LEAVES THE BUILDING, OVER VOLTAGEPROTECTORS ARE REQUIRED; USE 2081-9044 ONE ISINSTALLED WHERE IT LEAVE THE BUILDING AND ONEWHERE IT ENTERS THE NEXT BUILDING. TWO 2081-9044(MAX)

1.

2.

3.

4.

TO NEXT RUI DEVICE OR RETURN TOFIRE ALARM CONTROL PANEL IN STYLE 6 SYSTEM

FROM PREVIOUS RUI DEVICE ORFIRE ALARM CONTROL PANEL

SUPERVISORY 65mA

FROM PRECEDING SPEAKER

CONTROL PANEL (FACP)OR FIRE ALARM OR END OR LINE RESISTOR

TO NEXT SPEAKER

(EOLR)

ET-1010/ET-1011 SPEAKER ASSEMBLY

6

0=OFF

1 2

LSB

43 5

USEDNOT

87

MSB

DIP SWITCHES 5 & 6

353433

32

0100

383736

4140

39

444342

474645

259

11110111101100111101

0101

3115

12

1413

1110

28

3029

2726

1010

1001

0001

11100110

0010110001001000

0000

1 THRU 4DIP SWITCHES

87

56

4

2423

2122

20

23

1

0000

0

1819

17

1000

16

FUTURE USERESERVED FOR

57

63

60

6261

5958

56

55

5354

52

5051

49

1100

48

WALL MOUNT INSTALLATIONHEIGHT REFERENCE

NFPA 72 REQUIRES THAT

THE ENTIRE LENS BE NOT

LESS THAN 80" AND NOT

GREATER THAN 96" ABOVE

THE FINISHED FLOOR.

IMPORTANT!

80"

MIN.

ELECTRICALBOX OUTLINE

BOTTOM OF LENS

IS EITHER EVEN WITH

OR SLIGHTLY ABOVE

BOTTOM OF

COMPATABLE BOXES

MODEL NUMBERLETTERING

WHITE

COLOR

49VO-WWFO-BA

49VO-WRFO(-BA)

COLOR

RED

HOUSING

WHITE RED

0.160

WP 75cd75cd

0.1600.060

15cd

0.185

WP 185cd

0.212 0.23923 VRMS

23 VRMS

VOLTAGE

49VO-APPLW-CO SEPARATELY0.1680.1500.14323 VRMS

1=ON

POSITION 1: CONFIGURATION CONTROL - LOCAL (OFF), PANEL (ON)POSITION 2: AUDIBLE VOLUME - HIGH (OFF), LOW (ON)POSITION 3: CANADIAN HORN MODE - SET TO OFFPOSITION 4: LEGACY NAC MODE - SET TO OFFPOSITION 5,6,7: UNUSED - SET TO OFFPOSITION 8: CLEAR/COLOR LENS - ALARM (OFF), ALERT (ON)

APPLIANCE CONFIGURATION SETTINGS

CONDUIT CUTOUTS ARE PROVIDED

ON ALL FOUR SIDES.

MOUNTING INSTRUCTIONS:

3. ASSEMBLE THE HOUSING ONTO THE WEATHERPROOF BACKBOX ASSURING

4. USING THE MOUNTING HOLES INDICATED IN THE FIGURE ABOVE, ASSEMBLE THE

HOUSING TO THE BACKBOX. TIGHTEN THE SCREWS TO RECOMMENDED TORQUE

5. ASSEMBLE THE COVER TO THE WEATHERPROOF BACKBOX USING THE

SCREWS PROVIDED. TIGHTEN THE SCREWS TO RECOMMENDED TORQUE.

EVEN CONTACT WITH THE GASKET AROUND THE PERIPHERY.

WEATHERPROOF

1. SET THE APPLIANCE ADDRESS AND CONFIGURATION SETTINGS.

WP 75cd WP 185cd

0°-49° C TO 0° C TO -35° C

0.1600.1600.060 0.185 0.212 0.239

UL 1971 UL 1638 UL 1638

30cd20cd 75cd

ULC RATINGSVOLTAGE

WP BACKBOX ANDCOVER ORDERED

2. BRING THE BUILDING WIRING THROUGH THE RECTANGULAR OPENING IN THE APPLIANCE.

PCAF

INTENSITY SELECTIONPLUG, ACCESSIBLEONLY FROM REAR OFHOUSING; FACTORY

STROBE INTENSITY SETTING

SETTING IS FACP.CONTROLLED BY PANEL.

49VO-APPLW-O 23 VRMS 0.1600.1600.060 0.185 0.212 0.239

0.1680.1500.14323 VRMSWHITE49VO-WRFO-C RED

DETAIL 1 KEYNOTES

3

2

5

4

1

1 AIR HANDLING UNIT (AHU) STARTER/VFD.

2 FIRE ALARM ADDRESSABLE RELAY. CONNECT TO EMERGENCY STOPINPUT ON FAN CONTROLLER. PROGRAM TO STOP FAN ON ACTIVATIONOF ASSOCIATED SMOKE DETECTION. PROVIDE RELAY FOR EACH FANCONTROLLER.

3 FIRE ALARM ADDRESSABLE DUCT SMOKE DETECTOR.

4 FIRE ALARM ADDRESSABLE RELAY. DIGITAL INPUT TO BAS TO INITIATEADDITIONAL AHU SHUT DOWN SEQUENCE.

5 BAS CONNECTION TO FAN UNIT CONTROLLER.

FACP

DETAIL 1 KEYNOTES

3

2

5

4

1

1 AIR HANDLING UNIT (AHU) STARTER/VFD.

2 FIRE ALARM ADDRESSABLE RELAY. CONNECT TO EMERGENCY STOPINPUT ON FAN CONTROLLER. PROGRAM TO STOP FAN ON ACTIVATIONOF ASSOCIATED SMOKE DETECTION. PROVIDE RELAY FOR EACH FANCONTROLLER.

3 FIRE ALARM ADDRESSABLE AREA SMOKE DETECTION SYSTEM.

4 FIRE ALARM ADDRESSABLE RELAY. DIGITAL INPUT TO BAS TO INITIATEADDITIONAL AHU SHUT DOWN SEQUENCE.

5 BAS CONNECTION TO FAN UNIT CONTROLLER.

FACP

PHYSICAL EDUCATION BUILDING WELLNESS CENTER BUILDING

EFORPDERETSI

GER

REEN

IGN

E

LANOISS

C A L I F OR N I AS T A T E O F

R I C A LE L E C T

No. E16806

JASON LAU

E N G I N E E R I N GI N T E R F A C E

TEL

FAX

PROJECT

CONTACT

www.interfaceengineering.com

717 Market Street

Suite 500

San Francisco, CA 94103

415.489.7240

415.489.7289

SHEET NO:

DATE:

PROJECT NO:

THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THEPURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVEAND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THEWRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONALSERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2009.

THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECTAND ENGINEER.

CONSULTANT

6910 5 31112 8 7 4 2 1

J

K

H

G

F

E

D

C

B

A

B

A

J

K

H

G

F

E

D

C

6910 5 31112 8 7 4 2 1

NO. ISSUE DATE

ARCHITECT'S STAMP APPROVAL

Joe Ripp

2014-0174

SAN JOSE CITYCOLLEGE

PHYSICAL EDUCATION BUILDING ANDRENOVATED LAB BUILDING

SAN JOSE, CALIFORNIA

DETAILS - FIRE ALARM

FA7.01

1.12.2015

1089-0001

DSA SUBMITTAL

NO SCALE

1 HVAC FAN SHUT DOWN DIAGRAM

Page 10: SAN JOSE CITY - SJECCD Fire Alarm.pdf · relay iam simplex 4090-9002 4" square box 2 1/8" deep w/two gang cover individual addressable module simplex 4090-9001 single gang ... installation

AIR PRODUCTS PAM-SD 24VDC POLARIZED RELAY MODULE

SPECIFICATIONS:

SUPPLIED BY CONTRACTOR

ANY SINGLE GANG BOX

COVER PLATE

SUPPLIED BY CONTRACTOR

N/CC N/O

24VDC @ 0.015A

10.0 AMPCONTACTS

(18 VDC TO 32 VDC)

WHT RED

BLU YEL ORG

MOUNTING SCREW

FEATURES:

SINGLE SPDT RELAY

DOUBLE-SIDED ADHESIVE TAPE

5 WIRE NUTS

WHT RED

(+)(-)

(SIMPLEX 4098-9843)

2098-9806 REMOTE ALARM INDICATOR/KEY SWITCH

FEATURES:

PRODUCT INFORMATION

UL LISTED

SPECIFICATIONS:

WIRING:

DESCRIPTION:

CALIFORNIA STATE FIRE MARSHAL LISTING NUMBERS:2908-9806 ALARM INDICATOR 7300-0026:150

MOUNTING: FLUSH

FLUSH MOUNTING

2098-9806

FINISH: CHROME OR STAINLESS STEEL SUPPLIED BY CONTRACTOR

STANDARD SINGLEGANG BOX 2" X 3"MINIMUM DEPTH 2"

BACK VIEW

ONE INDICATOR MAY BE INSTALLED PER DETECTOR.

CONDUCTORS MUST TEST FREE OF ALL GROUNDS.REMOTE ALARM LED IS POLARIZED, OBSERVE

MINIMUM 18 AWG OR TO LOCAL CODE.

COLOR CODED WIRING.

4098-9756 ADDRESSABLE ANALOG 4-WIRE DUCT SENSOR MAPNET II/IDNet SLC WITH 24VDC RELAY

GENERAL SPECIFICATIONS

COMPACT AIR DUCT SENSOR HOUSING WITH CLEAR COVERTO MONITOR FOR THE PRESENCE OF SMOKE

PRODUCT INFORMATION

FEATURES:

INDIVIDUAL SENSOR INFORMATION PROCESSED BY THE HOST

SPECIFICATIONS:

INCLUDES FACTORY INSTALL TRUEALARM PHOTOELECTRIC SMOKEDETECTOR AND FEATURES:

CONTROL PANEL T0 DETERMINE SENSOR STATUSDIGITAL TRANSMISSION OF ANALOG SENSOR VALUES VIA

PROGRAMMABLE SENSITIVITY, CONSISTENT ACCURACY,ENVIRONMENTAL COMPENSATION, STATUS TESTING, ANDMONITORING OF SENSOR DIRT ACCUMULATION

DUCT SENSOR HOUSING WITH SUPERVISED OUTPUT FORMULTIPLE REMOTE RELAYS, REQUIRES SEPARATE 24 VDC

GENERAL FEATURES:UL LISTED TO STANDARD 268ACLEAR COVER ALLOWS VISUAL INSPECTION

MAGNETIC TEST FEATURE FOR ALARM INITIATION AT HOUSING

DIAGNOSTIC LEDS (ON INTERFACE BOARD):RED ALARM/TROUBLE LED FOR SENSOR STATUS ANDCOMMUNICATIONS POLLING DISPLAY

SAMPLING TUBES (ORDERED SEPARATELY):AVAILABLE IN MULTIPLE LENGTHS TO MATCH DUCT SIZEINSTALLED AND SERVICED WITH HOUSING IN PLACE

AIR VELOCITY RANGE (LINEAR FT/MIN)

UL LISTED TEMPERATURE RANGE

OPERATING TEMPERATURE RANGESTORAGE TEMPERATURE RANGEHUMIDITY RANGEHOUSING COLORWIRING CONNECTIONS

300 TO 4000 FT/min (91 TO 1220 m/min)

32° F TO 100° F (0° C TO 38° C)

10% TO 95% RH, NON-CONDENSINGBLACK BASE WITH CLEAR COVERTERMINAL BLOCKS, 18 TO 12 AWG

32° F TO 122° F (0° C TO 50° C)0° F TO 140° F (-18° C TO 60° C)

REMOTE STATUS/ALARM LED AND TEST STATION WITH REMOTE STATUS/ALARM LED

REMOTE ALARM LED CURRENT 1.2 mA, NO IMPACT TO ALARM CURRENT (2098-9808

250 FT. (76m) MAXIMUMREMOTE ALARM LED AND TEST

DUCT SMOKE SENSOR HOUSING WITH PHOTOELECTRIC SENSOR

DUCT DETECTOR SELECTION CHART

MODEL DESCRIPTION

MOUNTING

4098-9756DUCT HOUSING WITH SUPERVISED MULTIPLE RELAY CONTROL FOR UPTO 15, 4098-9843 RELAYS (ORDERED SEPARATELY), REQUIRES SIMPLEX FIRE ALARM CONTROL MODELS

4008, 4010, 4020, 4100, AND 4120.

REMOTE LED INDICATOR AND TEST STATION, SELECT ONE IF REQUIRED

MODEL

2098-9808

DESCRIPTION

RED LED STATUS INDICATOR USE SINGLE GANG BOX,3" H X 2" W X 2" D

(76 mm X 51 mm X 51 mm)

4-WIRE DUCT SENSOR4098-9756

TB1

LED TEST

1 2 3

+ MAP -

4 5 7

ON

8

NORMAL

TEST

TEST STATION

MAPNET II OR IDNET SLC 2-WIRE COMMUNICATIONS

MODEL:

WITH COVER IN PLACETEST PORTS PROVIDE FUNCTIONAL SMOKE TESTING ACCESS

MOUNTS TO RECTANGULAR DUCTS OR ROUND DUCTS(MINIMUM SIZE 8" SQUARE OR 18" DIAMETER)

OPTIONAL WEATHERPROOF ENCLOSURE IS AVAILABLESEPARATELY (REFER TO DATA SHEET S4098-0032)

REMOTE MODULE OPTIONS (ORDERED SEPARATELY):

RED STATUS/ALARM LED (2098-9808)TEST STATION WITH LED (2098-9806)

SENSOR SENSITIVITY RANGE 0.2% TO 3.7% PER FOOT OF OBSCURATION, SELECTABLEAT HOST CONTROL PANEL

OR 2098-9806)3.3 mA, NO IMPACT TO ALARM CURRENT (2098-9806)TEST STATION KEYSWITCH CURRENT

STATION DISTANCEADDRESSABLE OPERATION

DATA COMMUNICATIONSMAPNETII OR IDNET SLC COMMUNICATION, AUTO-SELECT1 ADDRESS PER HOUSING, PROVIDES OPERATING POWERTO MODEL 4098-9755

TEST STATION WITH KEYSWITCH AND RED LED STATUS (TURNINGSWITCH TO TEST INITIATES ALARM FOR SYSTEM TESTING

COMPATIBILITY

2098-9806

ALARM

R

R

ALARM

REMOTE STATUS/ALARM2098-9808

INDICATOR

2098-9806

12345678

- MAP +

ADDRESSSWITCH

2098-9808ALARM INDICATOR

REDALARM

LED

(OPTIONAL)

REDALARM

LED

REMOTE ALARM2098-9806

INDICATOR/KEYSWITCH

UL LISTED

4008, 4100+ OR 4120SIMPLEX 4010, 4020

CONTROL PANEL

SHIELD(OPTIONAL)

MAPNET II/IDNet+

-

RED

BLK

SEE NOTES3, 4

6

RED

BLK

TEST

SEE NOTES 3,4

(OPTIONAL)

SHIELDSHIELD

+

-

(RELAYS ARE UNDER PANEL CONTROL AND CAN BEACTIVATED MANUALLY OR BY A SEPARATE ALARM/INPUT)

YELLOW LED FOR OPEN OR SHORTED TROUBLE INDICATIONOF SUPERVISED RELAY CONTROL

RELAYS USED (4098-9843)

MODEL 4098-9756 WITH SUPERVISED MULTIPLE RELAY CONTROL, REQUIRES SEPARATE FUSED24 VDC FROM FIRE ALARM POWER SUPPLYINPUT VOLTAGE 17-32 VDC (24 VDC NOMINAL)

3 mA @ 24 VDCSTANDBY CURRENT

15 mA @ 24 VDC, ADD 15 mA ADDITIONAL FOR EACHALARM CURRENT4098-9843 RELAY

4098-9843 RELAY OUTPUT RATINGS, SINGLE FORM C

COIL CURRENT

RELAY CONTACTS, RESISTIVE RATINGS

LOCATION DISTANCE500 FT. (152m) MAX. TO RELAY COILS, RELAY MUST BE

15 mA @ 24 VDC UP TO 15 MAX. PER RELAY CONTROLOUTPUT7 A @ 28 VDC & 120 VAC; 250 uA @ 5 VDC

WITHIN 3 FT. (1m) OF DEVICE BEING CONTROLLED PERNFPA 72, SECTION 3-9.2.1

SEPARATE 24 VDC FIRE ALARM POWER AND RELAY END-OF-LINERESISTOR

9 10 11 1612 13 14 15

ALM-+24C+24V

4-WIRE DUCT SENSOR

TEST

8

LED+ -

ADDRESS

TB1 1 2 3

SWITCH

2

567

43

4098-9756

1 ON

MAP -

8

MAP +

4 5 6 7

+24V

9 10 11 12

24C ALM+ -

13 14 1615

-

+

24 VDCPOWER CIRCUIT

SW2 SW2

PAM-SDRELAY

BLU4098-9843

YEL

ORG

C

N.C.

N.O.

WHT

RED

1/2 W 10K EOLRESISTOR4081-9008

RED

WHT

+

-SEE NOTE 1

PAM-SDRELAY

BLU4098-9843

YEL

ORG

C

N.C.

N.O.+

-

WHT

RED

1/2 W 10K EOLRESISTOR

4081-9008RED

WHT

4090-9002 IDNet SLC, INDIVIDUAL ADDRESSABLE OUTPUT MODULE RELAY (AOM)PRODUCT INFORMATION

FEATURES:UL LISTED

SPECIFICATIONS:

WIRING NOTES:

DESCRIPTION:

"C" CONTACT AND TRACKS ITS STATUS

BOTH SUPPLIED BY IDNet COMMUNICATIONS

A SINGLE ADDRESSABLE POINT BOTH CONTROLS A 2A FORM

LATCHING RELAY DESIGN ALLOWS DATA AND POWER TO BE

2-GANG BACK BOX COVERSUPPLIED BY CONTRACTOR

RELAY IAM

4" SQUARE X 2 1/8" DEEP BOXSUPPLIED BY CONTRACTOR

COMPACT, SEALED CONSTRUCTION:- SCREW TERMINALS FOR WIRING CONNECTIONS- REDUCES DUST INFILTRATION

COMPATIBLE WITH SIMPLEX 2081-9044 OVER VOLTAGE PROTECTORS

ADDRESS SETTING UNDERRE-SEALABLE LABEL

COMPATIBLE WITH SIMPLEX MODEL 4010 AND 4100 ADDRESSABLEFIRE ALARM CONTROL PANEL

SEMI-FLUSH TRIM PLATE 4090-9801 (SHOWN)

BACK BOX COVER OPTIONS;

WITH LIGHT PIPE FOR LED VIEWING

WITH LIGHT PIPE FOR LED VIEWINGSURFACE TRIM PLATE 4090-9802

WITH LIGHT PIPE FOR LED VIEWINGSURFACE TRIM PLATE 4090-9807WITH LIGHT PIPE FOR LED VIEWING

BACK BOX COVER OPTIONS;

SEMI-FLUSH TRIM PLATE 4090-9806 (SHOWN)

4090-9810 BRACKET

A CONTRACTOR SUPPLIEDOPTIONAL WHEN USINGTHE SIMPLEX TRIM PLATESREQUIRED WHEN USING

(1.8K 1/2W)

733-984

733-896(4.7K 1/2W) (6.8K 1/2W)

733-886

4" X 1 1/2" DEEP OCTAGONAL

FLUSH MOUNTING

BOX SUPPLIED BY CONTRACTOR

4" SQUARE X 1 1/2" DEEP, WHICH REQUIRES

4098-9792 STANDARD SENSOR BASE

6. REFER TO INSTALLATION INSTRUCTIONS (574-707)

2. CONDUCTORS MUST TEST FREE OF ALL GROUNDS.

4. MAPNETII/IDNet SLC WIRING TO BE #18 AWG TWISTED SHIELDED PAIR

7. REFER TO APPLICATION MANUAL (574-709)

3. MAINTAIN CORRECT POLARITY

1. ALL WIRING TO COMPLY WITH LOCAL CODE.

FEATURES:

PRODUCT INFORMATION

SPECIFICATIONS:

WIRING:

DESCRIPTION:

TRUEALARM ANALOG SENSING PROVIDES DIGITAL TRANSMISSION OF ANALOGUL LISTED, FM APPROVED

SENSOR VALUES VIA MAPNETII, OR IDNet SLC TWO WIRE COMMUNICATIONS

INTEGRAL RED LED FOR POWER-ON (PULSING), OR ALARM OR TROUBLE (STEADY ON)

MOUNTING: CEILING OR WALLCOLOR : FROST WHITE

-ADDRESS REMAINS WITH ITS PROGRAMMED LOCATION

BASE MOUNTED ADDRESS SELECTION:

4098-9714 PHOTOELECTRIC SMOKE SENSOR

FIRE ALARM CONTROL PANEL PROVIDES:-INDIVIDUAL SENSITIVITY SELECTION FOR EACH SENSOR-PEAK VALUE LOGGING ALLOWING ACCURATE ANALYSIS FOR SENSITIVITY SELECTION-AUTOMATIC ENVIRONMENTAL COMPENSATION-DISPLAY OF SENSITIVITY IN PERCENT PER FOOT-MULTISTAGE ALARM OPERATION-ABILITY TO DISPLAY AND PRINT DETAILED SENSOR INFORMATION IN PLAIN ENGLISH LANGUAGE

PHOTOELECTRIC SMOKE SENSOR 4098-9714:SEVEN LEVELS OF SENSITIVITY FROM 0.2% TO 3.7%

-ACCESSIBLE FROM FRONT (DIP SWITCH UNDER SENSOR)

-RATE-OF-RISE TEMPERATURE DETECTION IS SELECTABLE AT THE CONTROL PANEL FOR EITHER 15°FHEAT SENSOR 4098-9733:

OR 20°F PER MINUTE-FIXED TEMPERATURE SENSING IS INDEPENDENT OF RATE-OF-RISE AND PROGRAMMABLE TO OPERATE

AT 135°F OR 155°F

FOR USE WITH SIMPLEX 4010, 4100, 4020, AND 4120 SERIES CONTROL PANELS.

SEE BASE INSTALLATION INSTRUCTIONS574-709 FOR SETTINGS

MAPNETII/IDNet ADDRESS DIP SWITCHES

FOUR LEVELS OF SENSITIVITY FROM 0.5% TO 1.7%.IONIZATION SMOKE SENSOR 4098-9717:

4098-9717 IONIZATION SMOKE SENSOR

-TRUEALARM HEAT SENSORS CAN BE PROGRAMMED AS A UTILITY DEVICE TO MONITORFOR TEMPERATURE EXTREMES IN THE RANGE FROM 32° F TO 120° F.

A 4098-9832 ADAPTER PLATE (6-3/8" X 1/4")

OR

(BOX TO BE FLUSH OR RECESSED 1/4" MAXIMUM)MAXIMUM QUANTITY OF DEVICES:-127 FOR 4020, 4100, 4120-250 FOR 4010, 4100

BASE DIMENSIONS: 15/16" X 4-7/8"

-40 FT SPACING FOR 155° F-60 FT SPACING FOR 135° FUL STANDARD SPACING:

4098-9733 HEAT SENSOR

WIRING FOR CURRENT LIMITED OPERATION

3

4

MAPNETII/IDNet DEVICEOR FIRE ALARM

TRUEALARM SENSOR BASES CONTAIN INTEGRAL ADDRESSABLE ELECTRONICSTHAT CONSTANTLY MONITOR THE STATUS OF THE DETACHABLE PHOTOELECTRIC,IONIZATION, OR HEAT SENSORS. EACH SENSOR'S OUTPUT IS DIGITIZED ANDTRANSMITTED TO THE SYSTEM FIRE ALARM CONTROL PANEL EVERY FOUR SECONDS.

FEATURE ALLOWS INTENTIONAL SENSOR SUBSTITUTION DURING BUILDING CONSTRUCTION.

SINCE TRUEALARM SENSORS USE THE SAME BASE, DIFFERENT SENSOR TYPES

WHEN CONDITIONS ARE TEMPORARILY DUSTY, INSTEAD OF COVERING THE SMOKE SENSORS.HEAT SENSORS MAY BE INSTALLED WITHOUT REPROGRAMMING THE CONTROL PANEL,

UL LISTED TEMPERATURE RANGE: 32°F TO 100°F

WIRING CONNECTIONS: SCREW TERMINALS FOR IN/OUT WIRING, #18 TO #14 AWG

ALTHOUGH THE CONTROL PANEL WILL INDICATE AN INCORRECT SENSOR TYPE, THE HEAT

OPERATING TEMPERATURE RANGE: 32°F TO 120°FHUMIDITY RANGE: 10% TO 95% RH

SENSOR WILL OPERATE AS A DEFAULT SENSITIVITY PROVIDING HEAT DETECTION FOR

CAN BE EASILY INTERCHANGED TO MEET SPECIFIC LOCATION REQUIREMENTS. THIS

TO ADDITIONAL MAPNETII/IDNet DEVICES

PANEL FOR A STYLE 6 APPLICATIONOR RETURN TO FIRE ALARM CONTROL

BUILDING PROTECTION AT THAT LOCATION.

-

+

-

+

VOLTAGE (MAPNETII/IDNet SLC): 24-40VDCCOMMUNICATIONS MAPNETII/IDNet SLC: 1 ADDRESS PER BASE

PHOTOELECTRIC SENSOR AIR VELOCITY RANGE: 0-2000 FT/MIN

IONIZATION SENSOR AIR VELOCITY RANGE: 0-300 FT/MIN

CURRENT: 400uA TYPICAL

FROM PREVIOUS

CONTROL PANEL5. IF SHIELD IS PRESENT, CONNECT TO THE OUTGOING IDNet SLC SHIELDTO PROVIDE A CONTINUOUS SHIELD OVER THE LENGTH OF THE

IDNet SLC CHANNEL. METHOD OF SPLICE DETERMINED BY AHJ.

OPTIONAL SHIELD

4090-9001 IDNET SLC, SUPERVISED ADDRESSABLE INPUT MODULE (AIM)

THE 4090-9001 IS AN ADDRESSABLE INPUT MODULE (AIM)

2. CONDUCTORS MUST TEST FREE OF ALL GROUNDS.

1. ALL WIRING TO COMPLY WITH LOCAL CODE.

PROVIDES CURRENT LIMITED MONITORING

FEATURES:

PRODUCT INFORMATION

UL LISTED

- COMMUNICATIONS WIRING USING ONE TWISTED, SHIELDED WIRE PAIR.

SPECIFICATIONS:

WIRING NOTES:

DESCRIPTION:

WIRE CONNECTIONS: SCREW TERMINALS FOR IN/OUT WIRING

COMPATIBLE WITH SIMPLEX ADDRESSABLE FIRE ALARM CONTROL PANELS.

COMPACT, SEALED CONSTRUCTION:

DIMENSIONS: 1 9/16" X 1 3/4" X 1 1/4"

TEMPERATURE RANGE: 32° F TO 158° F (0° C TO 70° C)

HUMIDITY: UP TO 93% RH AT 100° F

7. REFER TO INSTALLATION INSTRUCTIONS 574-331.

8. MAXIMUM ALLOWABLE LINE RUN FROM THE F.A.C.P. TO THEFARTHEST DEVICE, NOT TO EXCEED 2500 FEET.

9. MAXIMUM TOTAL WIRE (INCLUDING ALL T-TAPS) FROM THEFIRE ALARM CONTROL PANEL

10. FOR STYLE 6 CIRCUIT WIRING IT IS RECOMMENDEDTHAT THE PRIMARY 1 AND THE BACK-UP 2 LINESBE IN SEPARATE WIRE RUNS AND IN COMPLIANCE

4. MAXIMUM WIRE LENGTH (NO. 18 AWG) IS 400 FT. W/2081-9044

5. A MAXIMUM QUANTITY OF DEVICES PER CIRCUIT: CONTROL PANEL

3. ONLY N.O. DRY CONTACTS ARE ALLOWED.

(574-331) FOR SETTINGSSEE INSTALLATION INSTRUCTIONS

ADDRESS DIP SWITCHES UNDER

SELECTABLE LATCHING OPERATION

WITH LOCAL REQUIREMENTS.11. REFER TO FIELD WIRING DIAGRAM 842-073

WITH POWER AND COMMUNICATIONS SUPPLIED BY A TWO WIRE ADDRESSABLECIRCUIT. IT PROVIDES LOCATION SPECIFIC ADDRESSABILITYTO A SINGLE INITIATING DEVICE (SUCH AS SINGLE STATION SMOKEDETECTOR ALARM CONTACTS OR HEAT DETECTOR CONTACTS) ORMULTIPLE DEVICES AT THE SAME LOCATION BY MONITORING

F.A.C.P. OR

SLC DEVICEPREVIOUS

FROM UL-LISTED

PRIMARY IDNet/MAPNET SLC LINES

8

IDNet/MAPNET +B

S

R

3 4

6

RR BB

2SECONDARY IDNet/MAPNET SLC LINES

R

S

B+ IDNet/MAPNET

10

1

SHIELD

TO ADDITIONAL

RE-SEALABLE LABEL

CONTROL PANEL FORSTYLE 6 SYSTEMAPPLICATION

4

3

105

2

AND POWER TO PROVIDE:

- ALLOWS MOUNTING IN A SINGLE GANG BOX- REDUCES DUST INFILTRATION

ADDRESSABLE COMMUNICATIONS SUPPLY BOTH DATA

- SUPERVISED STYLE B MONITORING OF NORMALLY OPEN DRY CONTACTS.

- TO MONITOR TAMPER SWITCH (SUPERVISORY) ANDWATER FLOW SWITCH (ALARM) ON SAME CIRCUIT

- REQUIRES ONLY ONE ADDRESSABLE POINT

- MONITORS MOMENTARY CONTACT CLOSURES SUCH ASRATE-OF RISE HEAT DETECTORS

FOR WIRE FROM #18 TO #14 AWG.

SUPERVISION RESISTOR: 6.8k 1/2W, (SUPPLIED)SIMPLEX PART NO. 733-886

WITH A 1.8k 1/2W

RESISTOR FOR CURRENT LIMITED OPERATION: 4.7k 1/2W,

HOUSING MATERIAL: BLACK THERMOPLASTIC

INPUT REQUIREMENTS: NORMALLY OPEN, DRY CONTACTS

NORMALLY OPEN, DRY CONTACTS AND THE WIRING TO AN END-OF-LINE RESISTOR.CLOSURE OF THE MONITORED CONTACTS INITIATES AN ALARM OROTHER RESPONSE AS PROGRAMMED AT THE FIRE ALARMCONTROL PANEL. AN OPEN IN THE MONITORED CIRCUIT WIRINGWILL CAUSE A TROUBLE TO BE REPORTED.

FROM A RATE-OF-RISE HEAT DETECTOR, ENABLING THE LATCHFEATURE WILL MAINTAIN THE ALARM CONDITION UNTIL THE SYSTEM

IF THE INITIATING DEVICE CONTACTS ARE MOMENTARY, SUCH AS

IS RESET. FOR APPLICATIONS WHERE THE CONTACT CLOSURE LATCHES,OR IF ITS CONDITION NEEDS TO BE TRACKED AT THE CONTROL PANELNON-LATCHING OPERATION MAY BE ENABLED.

SHIELD

GANG ELECTRICAL BOX (2 1/8" MIN. DEPTH)UL LISTED SINGLE

(SUPPLIED BY CONTRACTOR)

(SUPPLIED BY CONTRACTOR)FLATHEAD SCREWS

SINGLE GANG COVER W/ 2 6/32

OVER VOLTAGE PROTECTORS OR 400 FT. W/O PROTECTORS.

I

8 9

9

43

2I

R BR B

6DEVICES OR RETURNTO FIRE ALARM

MODULE DEPENDENT

IDNet/MAPNET - - IDNet/MAPNET

SINGLE GANG COVER

T-SENSING OPERATION:SUPERVISED INPUT:- 4090-9001 AIM WITH T-SENSE CAPABILITY HAS A

CURRENT LIMITED CONTACT CLOSURE.BETWEEN A SHORT CIRCUIT CONTACT CLOSURE AND ATO AN END-OF-LINE RESISTOR AND CAN DIFFERENTIATESUPERVISED INPUT THAT MONITORS FOR CONTINUITY

- NORMAL IS WHEN ALL CONTACTS ARE OPEN AND THEREFOUR STATE OPERATION:

IS CONTINUITY TO THE END-OF-LINE RESISTOR.- OPEN IS WHEN CONTINUITY DOES NOT EXIST TO THE END-OF-LINE

RESISTOR, CAUSING A TROUBLE CONDITION.

- SHORT, INDICATES THAT A CONTACT HAS CLOSED THAT ISDIRECTLY CONNECTED TO THE INPUT CIRCUIT.

CLOSED BEYOND A SERIES CONNECTED CURRENT- CURRENT LIMITED INDICATES THAT A CONTACT HAS

LIMITING RESISTOR. THIS OPERATION ALLOWSDIFFERENTIATION BETWEEN TWO DIFFERENT CONTACTTYPES DUE TO THEIR WIRING LOCATION, AND REPORTINGAS A SINGLE IDNET ADDRESSABLE POINT TO A4100U FIRE ALARM CONTROL PANEL.

6. IF SHIELD IS PRESENT, CONNECT TO THE OUTGOING IDNet SHIELDTO PROVIDE A CONTINUOUS SHIELD OVER THE LENGTH OF THE

IDNet CHANNEL. METHOD OF SPLICE DETERMINED BY AHJ.

OPTIONAL SHIELD

RELAY IAM CONTACTS (FORM "C", SPDT)

POWER LIMITED RATING: 2A @ 24VDC, TRANSIENT SUPPRESSED

NON POWER LIMITED RATING: 1/2A @ 24VAC, TRANSIENT SUPPRESSED

WIRE CONNECTIONS: SCREW TERMINALS FOR IN/OUT

RELAY IAM POWER: SUPPLIED BY IDNet COMMUNICATIONS

DIMENSIONS: 4 1/8"H x 4 1/8"W x 1 3/8"D (105mm x 105mm x 35mm)

MOUNTING PLATE MATERIAL: SHEET METAL, GALVANIZEDHOUSING MATERIAL: BLACK THERMOPLASTIC

LOADS, 1A @ 24VDC FOR INDUCTIVE LOADS

LOADS, 1A @ 24 VDC FOR INDUCTIVE LOADS

WIRING, #18 TO #14 AWG WIRE

HUMIDITY RANGE UP TO 93% RH AT 100° F (38° C)

TEMPERATURE RANGE: 32° F TO 120° F (0° C TO 49° C)INTENDED FOR INDOOR OPERATION

IDNet SLC RELAY MODULES ALLOW THE SIMPLEX FIRE ALARMCONTROL PANEL TO CONTROL A REMOTELY LOCATED FORM"C" CONTACT USING IDNet ADDRESSABLE COMMUNICATIONSFOR BOTH DATA AND POWER. TYPICAL APPLICATIONSWOULD BE FOR SWITCHING LOCAL POWER FOR CONTROLFUNCTIONS SUCH AS ELEVATOR CAPTURE, OR CONTROL OF

HVAC COMPONENTS, PRESSURIZATION FANS, DAMPERS, ETC.RELAY STATUS IS ALSO COMMUNICATED REQUIRING ONLY ONEDEVICE ADDRESS.

1. IDNet LINES ARE TO BE #18 AWG TWISTED PAIR (CONSULTSG SALES ENGINEERING FOR EXCEPTIONS).

2. MAXIMUM ALLOWABLE LINE RUN, FROM THE F.A.C.P. TO THE FARTHEST

DEVICE, NOT TO EXCEED 2500 FEET.

3. MAXIMUM QUANTITY OF DEVICES PER CIRCUIT: CONTROL PANEL

4. CONTRACTOR WIRING TO RELAY CONTACTS IS UNSUPERVISED.USE #14 AWG WIRE TO LOCAL CODE.

5. RELAY CONTACTS RATED 2A, 24VDC (1A FOR INDUCTIVE LOAD)

RELAY CONTACTS RATED 0.5A 120VAC (NON POWER LIMITED)FOR POWER-LIMITED OPERATION, POWER MUST BE PROVIDED

FROM FACP OR POWER-LIMITED POWER SUPPLY LISTED FOR FIREPROTECTIVE SIGNALING USE.

6. SEE INSTALLATION INSTRUCTIONS 574-184.

8. WHEN CONNECTED TO A NON POWER-LIMITED SOURCE, THE WIRINGMUST MAINTAIN A MINIMUM 1/4 INCH SEPARATION FROM IDNet WIRING.

9. WHEN USED WITH NON POWER-LIMITED SOURCE, THE "POWER LIMITEDWIRING" INDICATION ON THE DEVICE LABEL MUST BE OBLITERATED.

10. WHEN BOTH POWER-LIMITED AND NON POWER-LIMITED SOURCES

ARE PRESENT, USE TYPE FPL, FPLR OR FPLP POWER LIMITED

CABLE FOR POWER-LIMITED CIRCUITS.11. MAXIMUM TOTAL WIRE (INCLUDING ALL T-TAPS) ON CIRCUIT, FROM THE

F.A.C.P. NOT TO EXCEED 10,000 FEET OR .58uF. (CLASS B ONLY)

+ - -+

R B BR

FROM PREVIOUS SLC DEVICE

OR F.A.C.P. TO F.A.C.P.

IDNet SLC33

SECONDARY IDNet SLC LINES

321

PRIMARY

IDNet SLC LINES

1 2

S SOPTIONAL SHIELD 7

NORMALLY CLOSED (N.C.)

COMMON

NORMALLY OPEN (N.O.)

NOT USED NOT USED

NORMALLY OPEN (N.O.)

COMMON

NORMALLY CLOSED (N.C.)

4090 -90 02 4090 -90 02

574- 184 REV A574- 184 REV A

1111

4 5 8 9 4 5 8 9

12. REFER TO FIELD WIRING DIAGRAM 842-073

RELAY IAM RELAY IAM

MODULE DEPENDENT

7. IF SHIELD IS PRESENT, CONNECT TO THE OUTGOING IDNet SHIELDTO PROVIDE A CONTINUOUS SHIELD OVER THE LENGTH OF THE

IDNet CHANNEL. METHOD OF SPLICE DETERMINED BY AHJ.

R

R

8" TO 3'

FOR DUCT WIDTHS

FOR DUCTS MORE THAN 3 FEET WIDETUBE SUPPORT HOLE SHALL BE USED

3' TO 95"

FOR DUCT WIDTHS

RUBBER PLUGDO NOT INSERTDUCT WHEN < 24"CUT TO 1/2 OFEXHAUST TUBE

INSERT RUBBER PLUG

TO OTHER MAPNETII/IDNET SLC DEVICESSEE NOTE 2 ORRETURN TO FACPFOR STYLE 6 SLC

FIRESMOKE

DAMPER

WIRING NOTES:1. DUCT SENSOR WIRING IS 12 TO 18 AWG.

2. MAXIMUM QUANTITY OF DEVICES PER CIRCUIT IS 127 FOR 4020,

3. THE 2098-9806 AND 2098-9808 ARE POLARIZED, OBSERVE COLOR-CODED WIRING.

4. MAXIMUM WIRE LENGTH TO TEST TERMINALS AND REMOTE LED IS 250 FEET.4098-9843 PAM-SD RELAY (AIR PRODUCTS & CONTROL LIMITED) ARE RATED AT7 AMPS 28 VDC/10 AMPS @ 115 VAC. MAXIMUM WIRE LENGTH TO PAM-SD RELAYS IS

DEVICE IT IS CONTROLLING SHOULD BE NO MORE THAN 3 FT. (PER NFPA 72).

FSD POWER(BY OTHERS)

AIRHANDLING

UNIT

AHU POWER(BY OTHERS)

5

4100+, OR 4120, AND 250 FOR THE 4010 PANEL

500 FT. (15 PAM-SD RELAYS MAX.). WIRING FROM THE RELAY TO THE

5

5

DIMENSIONS OF BOX: 2 "W X 3"H X 2"D

RED

BLACK (-)

(+)

ALARM CURRENT: 2.8 mA

2098-9806 REMOTE TEST STATION, PROVIDES A REMOTE RED ALARM LEDSTATUS INDICATOR AND A REMOTE TEST KEY ACTIVATED SWITCHMOUNTED ON A SINGLE GANG STAINLESS STEEL PLATE. THE LED WILLPULSE TO INDICATE NORMAL OPERATION OF THE DUCT DETECTOR ANDWILL ENERGIZE CONTINUOUS WHEN IN ALARM OR IN TROUBLE. (THEEXACT STATUS OF THE SENSOR WILL BE DISPLAYED AT THE FIRE ALARMCONTROL PANEL.) TURNING THE TEST SWITCH TO "TEST" WILL INITIATE ANALARM AND ALLOW THE RESULTING SYSTEM RESPONSES TO BE VERIFIED.

CONNECT TO REMOTEALARM LED OUTPUT OFAPPROPRIATEINITIATING DEVICES

CONNECT TO REMOTETEST SWITCH INPUT ONAPPROPRIATEINITIATING DEVICES

RELAY: U.L. RECOGNIZED SPDT

AMBIENT TEMPERATURE: -50° F TO 85 °F (-50°C TO 85°C)

CONTACT RATING: 7 AMPS @ 120VAC & 28 VDC

APPROVALS: UNDERWRITERS LABORATORIES LISTED

DIMENSIONS: 1-1/2"H X 1 7/8" W X 13/16" D

POWER REQUIREMENTS: 0.015 AMP @ 24VDC

(17 VDC TO 32 VDC)

12" 18 AWG WIRE LEADS

250 MICRO AMPS @ 5 VDC

(38.1mm H X 47.625mm W X 20.638mm D)

EFORPDERETSI

GER

REEN

IGN

E

LANOISS

C A L I F OR N I AS T A T E O F

R I C A LE L E C T

No. E16806

JASON LAU

E N G I N E E R I N GI N T E R F A C E

TEL

FAX

PROJECT

CONTACT

www.interfaceengineering.com

717 Market Street

Suite 500

San Francisco, CA 94103

415.489.7240

415.489.7289

SHEET NO:

DATE:

PROJECT NO:

THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THEPURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVEAND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THEWRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONALSERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2009.

THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECTAND ENGINEER.

CONSULTANT

6910 5 31112 8 7 4 2 1

J

K

H

G

F

E

D

C

B

A

B

A

J

K

H

G

F

E

D

C

6910 5 31112 8 7 4 2 1

NO. ISSUE DATE

ARCHITECT'S STAMP APPROVAL

Joe Ripp

2014-0174

SAN JOSE CITYCOLLEGE

PHYSICAL EDUCATION BUILDING ANDRENOVATED LAB BUILDING

SAN JOSE, CALIFORNIA

DETAILS - FIRE ALARM

FA7.02

1.12.2015

1089-0001

DSA SUBMITTAL

Page 11: SAN JOSE CITY - SJECCD Fire Alarm.pdf · relay iam simplex 4090-9002 4" square box 2 1/8" deep w/two gang cover individual addressable module simplex 4090-9001 single gang ... installation

6. THE TrueAlert S/V CAN ONLY BE OPERATED THROUGH A 4009 TrueAlert ADDRESSABLE CONTROLLER OR TrueAlert COMPATIBLE FACP.

TO THE S/V UNIT.5. POWERING THE S/V FROM AN APPLIANCE POWER SOURCE LESS THAN 17 VDC OR GREATER THAN 32 VDC MAY CAUSE PERMANENT DAMAGE

4. ALL TrueAlert SLC AND NAC WIRING CONNECTIONS ARE SUPERVISED AND POWER-LIMITED.3. MAINTAIN CORRECT POLARITY ON TERMINAL CONNECTIONS. DO NOT LOOP WIRES UNDER TERMINALS.2. NOTIFICATION APPLIANCES ARE RATED PER INDIVIDUAL NAMEPLATE LABEL.

REFER TO THE FIELD WIRING DIAGRAMS SUPPLIED WITH THE 4100/4003 FOR ADDITIONAL NAC WIRING INFORMATION.1. REFER TO FIELD WIRING DIAGRAMS OF THE DRIVING TrueAlert COMPATIBLE CONTROLLER FOR ADDITIONAL SLC WIRING INFORMATION.

CONNECTIONS: TERMINALS FOR 18 TO 12 AWG, SEPARATE TERMINALS

- ANECHOIC CHAMBER, ON-AXIS, 1kHz INPUT 87 90 93 96

- REVERBERANT CHAMBER, UL 1480 TEST 76 79 82 85

- WATTAGE TAP (25 VRMS OR 70.7 VRMS INPUT) 1/4W 1/2W 1W 2W

SPEAKER OUTPUT RATINGS (dBA @ 10 FT. (3m)

GENERAL SIGNALING: 125 TO 12 kHz

FIRE ALARM: 400 TO 4000 Hz

FOR SPEAKER AND TrueAlert STROBE CONNECTION

- SPEAKERS ARE NOT ADDRESSABLE AND ARE FOR CONNECTION TO CONVENTIONAL FIRE ALARM AUDIO CIRCUITS.

- UL STANDARD 1480 SPEAKER OUTPUT RATING CATEGORIES ARE BASED UPON 3 dBA INCREMENTS.

- INPUT VOLTAGE: 25 OR 70.7 VRMS, SEE NOTE 4

- POWER TAPS: 1/4, 1/2, 1W, AND 2W

- FREQUENCY RESPONSE:

SPEAKER

- STROBE FLASH RATE: 1Hz

STROBE

- SUPERVISORY REQUIREMENTS: 1 UNIT LOAD

- RATED VOLTAGE: 17 TO 31 VRMS

WIRING NOTES:

ATTACHES TO ONE OF 8 TERMINALS

SPEAKER TAP SELECTION: SINGLE JUMPER WIRE WITH PRESSURE CONNECTOR

TO ALSO BRIEFLY FLASH THE STROBE TO CONFIRM OPERATIONTEST PULSES THE LED TO INDICATE APPLIANCE ADDRESS AND IS SELECTABLEWHEN THE TRUEALERT CONTROLLER IS IN DIAGNOSTIC MODE, THE MAGNETIC

LED INDICATOR CAN BE SELECTED TO DISPLAY EACH POLLING CYCLE

HOUSING AVAILABLE IN RED OR WHITE (COVERS ARE AVAILABLERUGGED, HIGH IMPACT, FLAME RETARTANT THERMOPLASTIC

MAGNETIC TEST DIAGNOSTICS TO ASSIST CHECKOUT AND TESTING

SUPERVISION OF EACH INDIVIDUAL STROBE'S WIRING ANDCONNECTIONS WITH ACTIVATION AT A SYNCHRONIZED 1 Hz

75, 110 CANDELA OR "FACP". THE "FACP" SETTING ALLOWS THEXENON STROBE OUTPUT IS MANUALLY SELECTABLE FOR 15, 30,

TrueAlert VISIBLE NOTIFICATION APPLIANCE (STROBE)

HIGH QUALITY VOICE AND TONE REPRODUCTION WITH TAPS

DIMENSIONS (INCLUDING LENS) : 7 1/4" (184mm) H X 5" (127mm) W X 2 5/8" (67mm) D

HUMIDITY RANGE: 10% TO 93% NON-CONDENSING AT 100° F (38° C)

GENERAL SPECIFICATIONS:

DEPTH INTO BOX: 2 1/2" (64mm)

TEMPERATURE RANGE: 32° F TO 122° F (0° TO 50° C)

TO INDICATE APPLIANCE SUPERVISION

OF TRUEALERT STROBE AND WIRING

UL LISTED TO STANDARD 1971

SEPARATELY TO CONVERT COLORS)

FLASH RATE

AUDIBLE NOTIFICATION APPLIANCE (SPEAKER)

FEATURES:

PRODUCT INFORMATION

SPEAKERS ARE WIRED SEPARATELY FROM TRUEALERT

UL LISTED TO STANDARD 1480

FOR 1/4, 1/2, 1W, OR 2W AT 25 OR 70.7 VRMS

STROBE WIRING

TrueAlert S/V UNITS- DIP SWITCH ADDRESS CHART

TM

UP THE COVER WITH THE OTHER HAND. ADDRESS SWITCH (SW1 IS ACCESSIBLE WITH THE COVER REMOVED).3. TO REMOVE THE COVER, PRESS THE SNAP RELEASE IN (ONE AT A TIME) WITH A FLAT TIP SCREWDRIVER WHILE PULLING

TWO MOUNTING SCREWS. THE TWO MOUNTING SCREWS ARE PLACED CROSS CORNER (OPPOSITE TOP AND BOTTOM HOLES)2. THERE ARE FOUR HOLES FOR 4-INCH SQUARE ELECTRICAL BOX MOUNTING. SECURE THE HOUSING TO THE BOX USING

1. THE TrueAlert S/V ATTACHES DIRECTLY TO A STANDARD 4-INCH ELECTRICAL BOX (NOT SUPPLIED), FLUSH MOUNTED

SEMI-FLUSH MOUNTING

OR SURFACE MOUNTED.

MOUNTING NOTES:

MAGNETIC TEST LOCATION

BACK OF ELECTRICAL BOX.CAUTION: DO NOT BRING CONDUIT THROUGH

1 1/2" DEEP EXTENSION

(RACO NO. 203)

SUPPLIED BY CONTRACTOR

(SW1)

DIP SWITCHES

(38.1mm)

JUMPER LOCATED ON BACK

OF APPLIANCE

(101.6mm X 38.1mm)(RACO NO. 191)

4" SQ. X 1 1/2" DEEP BOX

SUPPLIED BY CONTRACTOR

- SYNCHRONIZED SLC LOADING: UP TO 43 TrueAlert ADDRESSABLE SYNCHRONIZED STROBESMAXIMUM PER SLC

4100 TO PROGRAM THE CANDELA SETTING.

7. WHEN CONTROLLED FROM A 4009 TrueAlert ADDRESSABLE CONTROLLER, THE FACP SETTINGS ARE NOT SUPPORTED.

FOR VISIBLE LENS MOUNTING HIEGHT TO MEET "ADA" 80" MINIMUM, THE 4" SQUARE BACKBOX

IS TO BE INSTALLED AT A HIEGHT OF 82" FROM THE FLOOR TO THE BOTTOM OF THE BOX.

JUMPER SETTINGS

TrueAlert SPEAKER

8. MAXIMUM T-TAPPING LENGTH IS 100 FEET.

TrueAlert ADDRESSABLE (STYLE 4) SPEAKER/VISIBLE NOTIFICATION APPLIANCES 4906 SERIES

6. THE TrueAlert S/V CAN ONLY BE OPERATED THROUGH A 4009 TrueAlert ADDRESSABLE CONTROLLER OR TrueAlert COMPATIBLE FACP.

TO THE S/V UNIT.5. POWERING THE S/V FROM AN APPLIANCE POWER SOURCE LESS THAN 17 VDC OR GREATER THAN 32 VDC MAY CAUSE PERMANENT DAMAGE

4. ALL TrueAlert SLC AND NAC WIRING CONNECTIONS ARE SUPERVISED AND POWER-LIMITED.3. MAINTAIN CORRECT POLARITY ON TERMINAL CONNECTIONS. DO NOT LOOP WIRES UNDER TERMINALS.2. NOTIFICATION APPLIANCES ARE RATED PER INDIVIDUAL NAMEPLATE LABEL.

REFER TO THE FIELD WIRING DIAGRAMS SUPPLIED WITH THE 4100/4003 FOR ADDITIONAL NAC WIRING INFORMATION.1. REFER TO FIELD WIRING DIAGRAMS OF THE DRIVING TrueAlert COMPATIBLE CONTROLLER FOR ADDITIONAL SLC WIRING INFORMATION.

CONNECTIONS: TERMINALS FOR 18 TO 12 AWG, SEPARATE TERMINALS

- ANECHOIC CHAMBER, ULC-S541 TESTING, 25 VRMS 81.6 84.3 87.1* 89.7*

- REVERBERANT CHAMBER, UL 1480 TEST 76 79 82 85

- WATTAGE TAP (25 VRMS OR 70.7 VRMS INPUT) 1/4W 1/2W 1W 2W

SPEAKER OUTPUT RATINGS (dBA @ 10 FT. (3m)

FIRE ALARM: 400 TO 4000 Hz

FOR SPEAKER AND TrueAlert STROBE CONNECTION

- SPEAKERS ARE NOT ADDRESSABLE AND ARE FOR CONNECTION TO CONVENTIONAL FIRE ALARM AUDIO CIRCUITS.

- UL STANDARD 1480 SPEAKER OUTPUT RATING CATEGORIES ARE BASED UPON 3 dBA INCREMENTS.

- INPUT VOLTAGE: 25 OR 70.7 VRMS, SEE NOTE 4

- POWER TAPS: 1/4, 1/2, 1W, AND 2W

- FREQUENCY RESPONSE:

SPEAKER

- STROBE FLASH RATE: 1Hz

STROBE

- SUPERVISORY REQUIREMENTS: 1 UNIT LOAD

- RATED VOLTAGE: 17 TO 31 VRMS

WIRING NOTES:

ATTACHES TO ONE OF 8 TERMINALS

SPEAKER TAP SELECTION: SINGLE JUMPER WIRE WITH PRESSURE CONNECTOR

TO ALSO BRIEFLY FLASH THE STROBE TO CONFIRM OPERATIONTEST PULSES THE LED TO INDICATE APPLIANCE ADDRESS AND IS SELECTABLEWHEN THE TRUEALERT CONTROLLER IS IN DIAGNOSTIC MODE, THE MAGNETIC

LED INDICATOR CAN BE SELECTED TO DISPLAY EACH POLLING CYCLE

HOUSING AVAILABLE IN RED OR WHITE (COVERS ARE AVAILABLERUGGED, HIGH IMPACT, FLAME RETARTANT THERMOPLASTIC

MAGNETIC TEST DIAGNOSTICS TO ASSIST CHECKOUT AND TESTING

SUPERVISION OF EACH INDIVIDUAL STROBE'S WIRING ANDCONNECTIONS WITH ACTIVATION AT A SYNCHRONIZED 1 Hz

75, 110 CANDELA OR "FACP". THE "FACP" SETTING ALLOWS THEXENON STROBE OUTPUT IS MANUALLY SELECTABLE FOR 15, 30,

TrueAlert VISIBLE NOTIFICATION APPLIANCE (STROBE)

HIGH QUALITY VOICE AND TONE REPRODUCTION WITH TAPS

HUMIDITY RANGE: 10% TO 93% NON-CONDENSING AT 100° F (38° C)

GENERAL SPECIFICATIONS:

TEMPERATURE RANGE: 32° F TO 122° F (0° TO 50° C)

TO INDICATE APPLIANCE SUPERVISION

OF TRUEALERT STROBE AND WIRING

UL LISTED TO STANDARD 1971

SEPARATELY TO CONVERT COLORS)

FLASH RATE

AUDIBLE NOTIFICATION APPLIANCE (SPEAKER)

FEATURES:

PRODUCT INFORMATION

SPEAKERS ARE WIRED SEPARATELY FROM TRUEALERT

UL LISTED TO STANDARD 1480

FOR 1/4, 1/2, 1W, OR 2W AT 25 OR 70.7 VRMS

STROBE WIRING

TrueAlert S/V UNITS- DIP SWITCH ADDRESS CHART

TM

BACK OF ELECTRICAL BOX.CAUTION: DO NOT BRING CONDUIT THROUGH

1 1/2" DEEP EXTENSION

(RACO NO. 203)

SUPPLIED BY CONTRACTOR

JUMPER SETTINGS

TrueAlert SPEAKER

(38.1mm)

(101.6mm X 38.1mm)(RACO NO. 191)

4" SQ. X 1 1/2" DEEP BOX

SUPPLIED BY CONTRACTOR

- SYNCHRONIZED SLC LOADING: UP TO 43 TrueAlert ADDRESSABLE SYNCHRONIZED STROBESMAXIMUM PER SLC

4100U TO PROGRAM THE CANDELA SETTING.

MAGNETIC TESTLOCATION

7. WHEN CONTROLLED FROM A 4009 TrueAlert ADDRESSABLE CONTROLLER, THE FACP SETTING IS NOT SUPPORTED.

- ANECHOIC CHAMBER, ULC-S541 TESTING, 70.7 VRMS 80.9 84.1 87.3* 90.2*

- SELECT TAPS AS INDICATED TO SATISFY FOR ULC FIRE ALARM APPLICATION REQUIREMENT OF 85 dBA MINIMUM.8. MAXIMUM T-TAPPING LENGTH IS 100 FEET.

TrueAlert SLC (STYLE 4) SPEAKER/VISIBLE NOTIFICATION APPLIANCES 4906 SERIES

TrueAlert STROBE UNIT REAR VIEW

6. THE TrueAlert STROBE CAN ONLY BE OPERATED THROUGH A 4009 TrueAlert ADDRESSABLE CONTROLLER OR TrueAlert COMPATIBLE FACP.

THE STROBE.

5. POWERING THE STROBE FROM AN APPLIANCE POWER SOURCE LESS THAN 17 VDC OR GREATER THAN 32 VDC MAY CAUSE PERMANENT DAMAGE TO

4. ALL TrueAlert SLC WIRING CONNECTIONS ARE SUPERVISED AND POWER-LIMITED.

3. MAINTAIN CORRECT POLARITY ON TERMINAL CONNECTIONS. DO NOT LOOP WIRES UNDER TERMINALS.

2. NOTIFICATION APPLIANCES ARE RATED PER INDIVIDUAL NAMEPLATE LABEL.

TrueAlert STROBE UNITS- DIP SWITCH ADDRESS CHART

CONNECTIONS: TERMINAL BLOCKS FOR 18 TO 12 AWG

HUMIDITY RANGE: 10% TO 93% NON-CONDENSING AT 100° F (38° C)

(121 mm x 75 mm x 67 mm)

HOUSING DIMENSIONS (INCLUDING LENS): 4 3/4" x 2 5/16" x 2 5/8" D

SPECIFICATION NOTES:

TEMPERATURE RANGE: 32° TO 122° F (O° TO 50° C)

GENERAL SPECIFICATIONS:

STROBE FLASH RATE: 1 HzSUPERVISORY REQUIREMENTS: 1 UNIT LOAD

WIRING NOTES:

MAGNETIC TEST DIAGNOSTICS TO ASSIST CHECKOUT AND

REAR OF HOUSING DOES NOT EXTEND INTO BOX AND EASILY MOUNTS

FLEXIBLE, EASY, AND CONVENIENT FLUSH OF SURFACETrueAlert NOTIFICATION APPLIANCE DESIGN PROVIDES

AND IS SELECTABLE TO ALSO BRIEFLY FLASH THE STROBE TOMAGNETIC TEST PULSES THE LED TO INDICATE APPLIANCE ADDRESSWHEN THE TrueAlert CONTROLLER IS IN DIAGNOSTIC MODE, THE

LED INDICTOR CAN BE SELECTED TO DISPLAY EACH POLLING CYCLE

INDIVIDUALLY ADDRESSED HIGH INTENSITY VISIBLE

SUPERVISION OF EACH INDIVIDUAL APPLIANCE'S WIRING AND

UL LISTED TO STANDARD 1971

SPECIFICATIONS:

WALL BOX MOUNTING:

LED INDICATOR AND MAGNETIC TEST FEATURE:

STROBE:

TO SINGLE GANG ELECTRICAL BOX

RATED VOLTAGE RANGE: 17 TO 31 VDC

TESTING OF APPLIANCES AND WIRING

TO INDICATE APPLIANCE SUPERVISION

CONFIRM OPERATION

NOTIFICATION APPLIANCE (STROBE) PROVIDES:

FEATURES:

PRODUCT INFORMATION

COMPATIBILITY WITH ADA REQUIREMENTS

CONNECTIONS

MOUNTING NOTES:

4. ADDRESS SWITCH SW2 IS ACCESSIBLE WITH THE CEILING-MOUNT STROBE REMOVED.

3. IT IS RECOMMENDED THAT THE STROBE ADDRESS BE SET BEFORE THE APPLIANCE IS SNAPPED TO THE

OF THE STROBE UNIT TO THE HOUSING SLOTS AND SNAP INTO PLACE.

USING 2 MOUNTING SCREWS (#6/32-INCH x 1 1/8-INCH LONG SUPPLIED) LINE THE MOUNTING TABS

2. THERE ARE TWO HOLES FOR ELECTRICAL BOX MOUNTING. SECURE THE HOUSING TO SINGLE-GANG BOX

ELECTRICAL BOX (NOT SUPPLIED), SEMI-FLUSH OR SURFACE MOUNTED.1. THE TrueAlert CEILING STROBE UNIT ATTACHES DIRECTLY TO A STANDARD SINGLE-GANG,

HOUSING.

CEILING MOUNTSTROBE LED

MAGNETIC TESTLOCATION

(88.9 mm x 38.1 mm)

THE REAR OF THE ELECTRICAL BOX

3 1/2" X 1 1/2 " OR EQUAL

HANDY BOX SUPPLIED BY CONTRACTOR

NOTE: DO NOT BRING CONDUIT THROUGH

(RACO NO. 650)

SUPPLIED BY CONTRACTORWITH CLIPS AND SCREWS(ERICO NO. 512), T-BAR

(TrueAlert ADDRESSABLE CONTROLLER) FOR ADDITIONAL INFORMATION ABOUT WIRING RULES AND DISTANCEBOTH POWER AND ADDRESSED COMMUNICATIONS ARE SUPPLIED. REFER TO DATA SHEET S4009-0003,

1. TrueAlert APPLIANCES ARE REQUIRED TO BE CONNECTED TO A TrueAlert ADDRESSABLE CHANNEL WHERE

LIMITATIONS.

3. VOLTAGE DROPS AND STANDBY BATTERY CALCULATIONS SHOULD BE MADE USING ANTICIPATED OPERATING CONDITIONS.

SETTING DRAWS APPROXIMATELY 5 mA LESS CURRENT AT EACH VOLTAGE LISTED.BATTERY CALCULATIONS SHOULD BE MADE USING ANTICIPATED OPERATING CONDITIONS. "LOW" HORN

2. THE RATED RANGE LISTED IS THE ABSOLUTE OPERATING VOLTAGE RANGE. OPERATION OUTSIDE OFTHIS RANGE MAY CAUSE PERMANENT DAMAGE TO THE APPLIANCE. PLEASE NOTE THAT 17 VRMS ISTHE LOWEST OPERATING VOLTAGE THAT IS ALLOWED AT THE LAST APPLIANCE ON THE TRUEAlertNOTIFICATION APPLIANCE CIRCUIT UNDER WORST CASE CONDITIONS. VOLTAGE DROP AND STANDBY

OPERATION ABOVE 24VRMS DRAWS LESS CURRENT.

SYNCHRONIZED SLC LOADING: UP TO 43 TRUEAlert ADDRESSABLE SYNCHRONIZED STROBES MAXIMUM PER SLC

75, 110 CANDELA OR "FACP". THE "FACP" SETTING ALLOWS THE

XENON STROBE OUTPUT IS MANUALLY SELECTABLE FOR 15, 30,

4100U TO PROGRAM THE CANDELA SETTING.

1. REFER TO FIELD WIRING DIAGRAMS OF THE DRIVING TRUEALERT COMPATIBLE CONTROLLER FOR ADDITIONAL SLC WIRING INFORMATION.

7. WHEN CONTROLLED FROM A 4009 TrueAlert ADDRESSABLE CONTROLLER, THE FACP SETTINGS ARE NOT SUPPORTED.

8. MAXIMUM T-TAPPING LENGTH IS 100 FEET.

TrueAlert (STYLE 4) VISIBLE NOTIFICATION APPLIANCES 4906 SERIES

ABILITY TO CONNECT USING "T" TAPPING FOR CLASS B/STYLE 4CIRCUITS TO SIMPLIFY WIRING.

TM

TrueAlert (STYLE Y) SPEAKER NOTIFICATION APPLIANCES 4902 SERIES

5. END-OF-LINE RESISTOR VALUE DEPENDENT ON CONTROL PANEL.

TM

(0 ° TO 50° C)

ANECHOIC CHAMBER, ON-AXIS, ULC S541 79 dBA 82 dBA 85 dBA 88 dBA

REVERBERANT CHAMBER, UL 1480 TEST 79 dBA 82 dBA 85 dBA 88 dBA

SELECTED TAP 1/4W 1/2W 1W 2W

SOUND OUTPUT RATINGS @ 10 FT. (3m)

ROUND HOUSING4902-9721(CA)

MODEL

HUMIDITY RANGE: 10% TO 95% RH FROM 32° TO 122° F

TEMPERATURE RANGE: 32° TO 100 ° F ( 0° TO 38° C)

RESPONSE (GENERAL SIGNALING): 125 TO 12 kHz

FREQUENCY (FIRE ALARM): 400 TO 4000 Hz

MOUNTS TO 4" SQUARE OUTLET BOX, 1 1/2' DEEP WITH

RUGGED , HIGH IMPACT, FLAME RETARDANT THERMOPLASTIC

CAPACITOR INPUT FOR CONNECTION TO SUPERVISED NOTIFICATION

MULTI-TAPPED DESIGN PROVIDES OUTPUT POWER OF 1/4,

FOUR INCH CONE (102mm) PROVIDES HIGH QUALITY TONE

FIRE ALARM SPEAKERS WITH MODELS FOR WALL MOUNTING

SPECIFICATIONS:

INPUT TERMINAL RATINGS: 18 TO 12 AWG

POWER TAPS: 1/4, 1/2, 1 AND 2W

INPUT VOLTAGE: 25 OR 70.7 VRMS

DEPTH INTO BOX: 2 3/4" (70 MM)

COMPATIBLE WITH OPTIONAL TILE BRIDGE 2905-9946

1 1/2" DEEP BOX EXTENSION

FLUSH MOUNT ON CEILING OR WALL

OFF-WHITE COLOR (NO LETTERING)

APPLIANCE CIRCUIT

HOUSING

FEATURES:

PRODUCT INFORMATION

IN/OUT WIRING TERMINALS FOR 18 AWG TO 12 AWG

1/2, 1, OR 2 W WITH EITHER 25 OR 70.7 VRMS INPUT

UL LISTED TO STANDARD 1480

AND VOICE REPRODUCTION

(SHOWN TAPPED AT 1/2 WATT @ 25VRMS)

TrueAlert CEILING MOUNTED SPEAKER REAR VIEW

THAT RESTS ON TILE SUPPORT BOX WITH EXTENSION.OR WITH MAXIMUM 1/4 INCH RECESS; FOR SUSPENDED CEILING, USE A SUITABLE BRIDGE

3. FOR INSTALLATION IN PLASTER OR CONCRETE CEILING, MOUNT BOX WITH EXTENSION FLUSH

2. ENSURE CORRECT ORIENTATION OF BOX WITH EXTENSION IN RELATION TO LOCATION OF

4. ALL NAC WIRING CONNECTIONS ARE SUPERVISED AND POWER-LIMITED.

3. MAINTAIN CORRECT POLARITY ON TERMINAL CONNECTIONS. DO NOT LOOP WIRES UNDER TERMINALS.2. NOTIFICATION APPLIANCES ARE RATED PER INDIVIDUAL NAMEPLATE LABEL.

1. REFER TO FIELD WIRING DIAGRAMS SUPPLIED WITH THE 4100/4003 FOR ADDITIONAL NAC WIRING INFORMATION.

MOUNTING SCREWS.

(101.6 mm x 38.1 mm)(RACO NO. 191 OR EQUAL)SUPPLIED BY CONTRACTOR

4" SQ. x 1 1/2" DEEP BOX

CEILING OR WALLSEMI-FLUSH MOUNTING

1. THE TrueAlert CEILING-MOUNT SPEAKER ATTACHES DIRECTLY TO A STANDARD 4-INCHSQUARE ELECTRICAL BOX WITH EXTENSION RING (NOT SUPPLIED) SEMI-FLUSH MOUNTED

MOUNTING NOTES:

OR SURFACE MOUNTED.

JUMPER SETTINGS

TrueAlert SPEAKER (38.1 mm)

SUPPLIED BY CONTRACTOR(RACO NO. 203 OR EQUAL)1 1/2" EXTENSION RING

NOTE: ULC LISTED MODELS ARE DESIGNATED WITH A "CA" SUFFIX.

ULC LISTED MODEL (CA SUFFIX FOLLOWING THE MODEL NUMBER)

ANECHOIC CHAMBER, ON-AXIS, 1kHz INPUT 87 dBA 90 dBA 93 dBA 96 dBA

REVERBERANT CHAMBER, UL 1480 TEST 78 dBA 81 dBA 84 dBA 87 dBA

SELECTED TAP 1/4W 1/2W 1W 2W

SOUND OUTPUT RATINGS @ 10 FT. (3m)

RECT. HOUSING

4902-9716(CA),

MODEL

(0 ° TO 50° C)HUMIDITY RANGE: 10% TO 95% RH FROM 32° TO 122° F

TEMPERATURE RANGE: 32° TO 100 ° F ( 0° TO 38° C)

OPTIONAL MATCHING ADAPTER SKIRTS FOR COVERING SURFACE

MOUNTS TO 4" SQUARE OUTLET BOX, 1 1/2' DEEP WITH

APPEARANCE THAT COMPLEMENTS TrueAlert STROBES AND

RUGGED, HIGH IMPACT, FLAME RETARDANT THERMOPLASTIC

CAPACITOR INPUT FOR CONNECTION TO SUPERVISED NOTIFICATION

MULTI-TAPPED DESIGN PROVIDES OUTPUT POWER OF 1/4,

FOUR INCH CONE (102mm) PROVIDES HIGH QUALITY TONE

FIRE ALARM SPEAKERS WITH MODELS FOR WALL MOUNTING

SPECIFICATIONS:

RESPONSE (GENERAL SIGNALING): 125 TO 12 k Hz

FREQUENCY (FIRE ALARM): 400 TO 4000 Hz

INPUT TERMINAL RATINGS: 18 TO 12 AWG

POWER TAPS: 1/4, 1/2, 1 AND 2W

INPUT VOLTAGE: 25 OR 70.7 VRMS

DEPTH INTO BOX: 2 3/4" (70 MM)

MOUNTED ELECTRICAL BOXES

SURFACE OR SEMI-FLUSH WALL MOUNT

RED OR WHITE HOUSING WITH "FIRE" LETTERING

SPEAKER/STROBES

APPLIANCE CIRCUIT

HOUSING

FEATURES:

PRODUCT INFORMATION

1 1/2" DEEP BOX EXTENSION

IN/OUT WIRING TERMINALS FOR 18 AWG TO 12 AWG

1/2, 1, 2 W WITH EITHER 25 OR 70.7 VRMS INPUT

UL LISTED TO STANDARD 1480

AND VOICE REPRODUCTION

(SHOWN TAPPED AT 1/2 WATT @ 25 VRMS)

TrueAlert WALL MOUNTED SPEAKER BACK VIEW

MOUNTING.

3. MAINTAIN CORRECT POLARITY ON TERMINAL CONNECTIONS. DO NOT LOOP WIRES UNDER TERMINALS.2. NOTIFICATION APPLIANCES ARE RATED PER INDIVIDUAL NAMEPLATE LABEL.

1. REFER TO FIELD WIRING DIAGRAMS SUPPLIED WITH THE 4100/4003 FOR ADDITIONAL NAC WIRING INFORMATION.

4. ALL NAC WIRING CONNECTIONS ARE SUPERVISED AND POWER-LIMITED.

WIRING NOTES:

WITH A FLAT TIP SCREWDRIVER WHILE PULLING THE COVER UP WITH THE OTHER HAND.

ATTACH THE SPEAKER TO THE ELECTRICAL BOX USING TWO SCREWS (SUPPLIED) MOUNTED

MOUNTED. MOUNTING THE SPEAKER TO THE 4-INCH SQUARE ELECTRICAL BOX IS SHOWN.

2. TO REMOVE THE COVER PRESS THE SNAP RELEASE IN THE BOTTOM OF THE SPEAKER

1. THE TrueAlert WALL-MOUNT SPEAKER ATTACHES DIRECTLY TO A STANDARD 4-INCHELECTRICAL BOX WITH EXTENSION RING (NOT SUPPLIED) FLUSH MOUNTED OR SURFACE

3. NAC TERMINALS (CKT+, CKT-) ARE NOT ACCESSIBLE THROUGH THE FRONT AFTER

SEMI-FLUSH MOUNTING

MOUNTING NOTES:

CROSS CORNER.

JUMPER SETTINGS

TrueAlert SPEAKER

1 1/2" DEEP EXTENSION

(RACO NO. 203)

(38.1mm)

SUPPLIED BY CONTRACTOR

(101.6mm X 38.1mm)

4" SQ. X 1 1/2" DEEP BOX

SUPPLIED BY CONTRACTOR(RACO NO. 191)

4902-9717(CA)

NOTE: ULC LISTED MODELS ARE DESIGNATED WITH A "CA" SUFFIX.

ULC LISTED MODELS (CA SUFFIX FOLLOWING THE MODEL NUMBER)

TrueAlert (STYLE Y) SPEAKER NOTIFICATION APPLIANCES 4902 SERIESTM

5. END-OF-LINE RESISTOR VALUE DEPENDENT ON CONTROL PANEL.

011570351

531581

011570351

011570351

011570351

ABILITY TO CONNECT USING "T" TAPPING FOR CLASS B/STYLE 4CIRCUITS TO SIMPLIFY WIRING

TrueAlert ES (STYLE 4 SLC) VISIBLE ONLY NOTIFICATION APPLIANCES 49VO SERIESTM

6. THE TrueAlert V/O CAN ONLY BE OPERATED THROUGH A 4009 TrueAlert ADDRESSABLE CONTROLLER OR TrueAlert COMPATIBLE FACP.

TO THE V/O UNIT.

5. POWERING THE V/O FROM AN APPLIANCE POWER SOURCE LESS THAN 17 VDC OR GREATER THAN 32 VDC MAY CAUSE PERMANENT DAMAGE.

4. ALL TrueAlert SLC WIRING CONNECTIONS ARE SUPERVISED AND POWER-LIMITED.

3. MAINTAIN CORRECT POLARITY ON TERMINAL CONNECTIONS. DO NOT LOOP WIRES UNDER TERMINALS.

2. NOTIFICATION APPLIANCES ARE RATED PER INDIVIDUAL NAMEPLATE LABEL.

TrueAlert V/O UNITS- DIP SWITCH ADDRESS CHART

CONNECTIONS: TERMINAL BLOCKS FOR 18 TO 12 AWG

HUMIDITY RANGE: 10% TO 93% NON-CONDENSING AT 104° F (40° C)

(130 mm X 127 mm X 67 mm)HOUSING DIMENSIONS (INCLUDING LENS): 5 1/8" H X 5" W X 2 5/8" D

TEMPERATURE RANGE: 32° TO 120° F (O° TO 49° C)

GENERAL SPECIFICATIONS:

WIRING NOTES:

CONTINUOUSLY, CONTROLLED SEPARATELY FROM VISIBLE APPLIANCESHORNS SOUNDED AS TEMPORAL OR MARCH TIME PATTERN, OR ON

AND AUDIBLE NOTIFICATION ACTIVATES APPLIANCES WITH:TrueAlert 2-WIRE ADDRESSABLE CONTROL OF VISIBLE

AND IS SELECTABLE TO ALSO BRIEFLY FLASH THE STROBE TO

MAGNETIC TEST PULSES THE LED TO INDICATE APPLIANCE ADDRESS

WHEN THE TrueAlert CONTROLLER IS IN DIAGNOSTIC MODE, THE

LED INDICTOR CAN BE ELECTED TO DISPLAY EACH POLLING CYCLE

MAGNETIC TEST DIAGNOSTICS TO ASSIST CHECKOUT AND TESTINGEASY ACCESS FOR INSTALLATION, INSPECTION, AND TESTING

IN/OUT WIRING ACCESSIBILITY FROM FRONT OF HOUSING PROVIDES

HIGH INTENSITY XENON STROBE PROVIDES:NOTIFICATION APPLIANCES WITH EFFICIENT ELECTRONIC

HORNS CONTROLLED SEPARATELY FROM STROBES ON THE SAME

INDIVIDUALLY ADDRESSED WALL MOUNT VISIBLE

SUPERVISION OF EACH INDIVIDUAL APPLIANCE'S WIRING AND

UL LISTED TO STANDARD 1971

SPECIFICATIONS:

LED INDICATOR AND MAGNETIC TEST FEATURE:

STROBE:

STROBE FLASH RATE: 1 HzSUPERVISORY REQUIREMENTS: 1 UNIT LOAD

ON THE SAME TWO-WIRE CIRCUIT

RATED VOLTAGE RANGE: 17 TO 31 VRMS

TO INDICICATE APPLIANCE SUPERVISION

OF APPLIANCES AND WIRING

CONFIRM OPERATION

FEATURES:

PRODUCT INFORMATION

"ON-UNTIL RESET".

2-WIRE CIRCUIT ALLOWING "ON-UNTIL-SILENCED" AND

CONNECTIONS

LOCATION

NOTE: NO CONDUIT ENTRY IN

OR WHITE SKIRT NO. 4905-9940

4" SQUARE x 1 1/2" DEEP BOX

RED SKIRT NO. 4905-9937WHEN SURFACE MOUNTING USE

MAGNETIC TEST

ADDRESS SETTING

DIP SWITCH

(RACO NO. 231 OR 232)

SUPPLIED BY CONTRACTOR

THE REAR OF THE BACK BOX

SEMI-FLUSH MOUNTING

110, 135 AND 185 CANDELA OR "FACP". THE "FACP" SETTING ALLOWSXENON STROBE OUTPUT IS MANUALLY SELECTABLE FOR 15, 30, 75,

THE 4100 TO PROGRAM THE CANDELA SETTING.

1. REFER TO FIELD WIRING DIAGRAMS OF THE DRIVING TrueAlert COMPATIBLE CONTROLLER FOR ADDITIONAL SLC WIRING INFORMATION.

COVER

APPLIANCE

BACKPLATECONFIGURATION CONTROLDIP SWITCH

ACCESSABLE FROM REAR

ACCESSABLE FROM REAR

* VISIBLE OUTPUT RATING FOR THE GIVEN LENS COVER COLOR AT THE APPLIANCE SETTING.** 17 VOLT CURRENT SHOWN AT THE HIGH CANDELA SETTINGS IS FOR USE WITH 4009T ONLY.

LENS COVER FOR

COLORED LENS

OPTIONAL

AUDIO INPUT FROM 4100/400325 VRMS OR 70.7 VRMS

RED

BLACK

SPKR -

SPKR +

RED

BLACK

(SEE WIRING NOTES)

IF LAST APPLIANCESPKR -

SPKR +

CONNECT EOLRON CIRCUIT,AUDIO INPUT FROM

25 VRMS OR 70.7 VRMS

4100/4003

RED

BLACK

SPKR -

SPKR +

RED

BLACK

(SEE WINING NOTES)

IF LAST APPLIANCESPKR -

SPKR +

CONNECT EOLR

ON CIRCUIT,

(SEE WIRING NOTES)

SLC CONTROLLER (SEE WIRING NOTES)SLC +SLC +

4906 STROBE

FROM TrueAlert COMPATIBLE SLC -SLC +

-1

CKT +2

SLC -

-1

CKT

SLC -

+2

4906 STROBE

SLC +

+-1 2

CKT +

4906 STROBE

1

SLC -

- CKT2

4906 STROBE

SLC +SLC +SLC CONTROLLER (SEE NOTES)FROM TrueAlert COMPATIBLE SLC -

SLC +

-1

CKT +2

SLC -

-1

CKT

SLC -

+2

49VO

SLC +

-1 2

CKT +1

SLC -

- CKT +2

49VO 49VO 49VO

-1

CKT +2

49VO

FROM TRUEALERT-COMPATIBLESLC CONTROLLER (SEE WIRING NOTES)

(4100/4003) (SEE WIRING NOTES)FROM AUDIO NAC CHANNEL

SLC +

SLC -

SLC +

SLC -

SPKR +

SPKR -

STROBE -

STROBE +SLC -

SLC +

SPKR -

SPKR +

4906 S/V

SPKR +

SPKR -

STROBE +

STROBE -

SPKR -

SPKR +

4906 S/V

SPKR +

SPKR -

DEPENDANT ON

4906 S/V

STROBE +

STROBE -

SPKR -

RESISTOR (VALUEEND-OF-LINE

SPKR +

FACP)

FROM TRUEALERT-COMPATIBLESLC CONTROLLER (SEE WIRING NOTES)

(4100/4003) (SEE WIRING NOTES)FROM AUDIO NAC CHANNEL

SLC +

SLC -

SLC +

SLC -

SPKR +

SPKR -

STROBE -

STROBE +SLC -

SLC +

SPKR -

SPKR +

4906 S/V

SPKR +

SPKR -

STROBE +

STROBE -

SPKR -

SPKR +

4906 S/V

SPKR +

SPKR -

DEPENDANT ON

4906 S/V

STROBE +

STROBE -

SPKR -

RESISTOR (VALUEEND-OF-LINE

SPKR +

FACP)

DIP SWITCHES 5 & 6

353433

32

0100

383736

4140

39

444342

47

4645

259

11110111101100111101

0101

3115

12

1413

1110

28

3029

2726

1010

1001

0001

11100110

0010110001001000

0000

1 THRU 4DIP SWITCHES

87

56

4

2423

2122

20

23

1

0000

0

1819

17

1000

16

FUTURE USERESERVED FOR

57

63

60

6261

5958

56

55

5354

52

5051

49

1100

48

PCAF

INTENSITY SELECTIONPLUG, ACCESSIBLEONLY FROM REAR OFHOUSING; FACTORY

STROBE INTENSITY SETTINGVIEWABLE THROUGH THE

SETTING IS FACP.

WALL MOUNT INSTALLATIONHEIGHT REFERENCE

NFPA 72 REQUIRES THAT

THE ENTIRE LENS BE NOT

LESS THAN 80" AND NOT

GREATER THAN 96" ABOVE

THE FINISHED FLOOR.

IMPORTANT!

80"

MIN.

ELECTRICALBOX OUTLINE

BOTTOM OF LENS

IS EITHER EVEN WITH

OR SLIGHTLY ABOVE

BOTTOM OF

COMPATABLE BOXES

RIGHT SIDE OF THE COVER

CONTROLLED BY PANEL.

POSITION 1: CONFIGURATION CONTROL - LOCAL (OFF), PANEL (ON)POSITION 2: AUDIBLE VOLUME - HIGH (OFF), LOW (ON)POSITION 3: CANADIAN HORN MODE - SET TO OFFPOSITION 4: LEGACY NAC MODE - SET TO OFFPOSITION 5,6,7: UNUSED - SET TO OFFPOSITION 8: CLEAR/COLOR LENS - ALARM (OFF), ALERT (ON)

APPLIANCE CONFIGURATION SETTINGS

MOUNTING INSTRUCTIONS:

1. BRING THE BUILDING WIRING THROUGH THE RECTANGULAR OPENING IN THE BACKPLATE.

2. CONNECT THE BUILDING WIRES TO THE BACKPLATE.

3. SECURE THE BACKPLATE TO THE ELECTRICAL BOX BY USING THE PROVIDED HARDWARE.

4. ATTACH THE COVER TO THE APPLIANCE.

5. SET THE APPLIANCE ADDRESS AND CONFIGURATION SETTINGS.

6. ATTACH THE ASSEMBLED APPLIANCE ONTO THE BACKPLATE.

INSTALLED WITH THE WRITING "INSTALL THIS SIDE UP" AT THE TOP.

MODEL NUMBERLENS

COLOR

0.100

75cd30cd

CURRENT VALUES ARE UL 1971 MAX RATING FOR THE GIVEN VOLTAGE LEVEL

0.0570.047

15cd

0.132

110cd

0.160

135cd

0.208

185cd

23 VRMS

VOLTAGE

17 VRMS 0.1330.0750.062 0.178

23 VRMS

17 VRMS

CLEAR

AMBER/BLUE

GREEN

23 VRMS

17 VRMSRED

0.1280.0780.054 0.18423 VRMS

17 VRMS 0.1710.1030.067 0.250

0.211

SUPPORTED*45cd*20cd*10cd *75cd *95cd

*15cd*7cd*3cd *30cd *37cd

**0.214

NOT**0.282

0.1280.0780.054 0.1840.1710.1030.067 0.250

0.211**0.282

0.1280.0780.054 0.1840.1710.1030.067 0.250

0.211**0.282

6

0=OFF

1 2

LSB

43

5

USEDNOT

87

MSB

1=ON

COLOR COLORCOVER LETTERING

WHITE49VO-WRF(-BA) RED

WHITE RED49VO-WWF(-BA)

**0.281

J1 TO TAP G

J1 TO TAP FJ1 TO TAP EJ1 TO TAP DJ1 TO TAP DJ1 TO TAP CJ1 TO TAP BJ1 TO TAP A

ALL EXTERNAL TO WALL1 1/2" DEEP WITH 1 1/2" DEEP EXTENSION,

USE TO COVER SURFACE MOUNTED

DESCRIPTION

WHITE SPEAKER COVER WITH RED "FIRE" LETTERING

DESCRIPTION

COVERS (FOR REPLACEMENT OR COLOR CONVERSION)

RED SPEAKER COVER WITH WHITE "FIRE" LETTERING

DESCRIPTION

RECTANGULAR HOUSING, WALL

PRODUCT SELECTION SPEAKER MOUNTING ADAPTERS AND BOXES

4905-9989

MODELNUMBER

4905-9988

NUMBERMODEL

MOUNTING ADAPTERS

4905-9942

4905-9941

NUMBERMODEL

4902-9717(CA)

4902-9716(CA)

SKIRTS (DEEP)SURFACE MOUNT ADAPTER

MOUNT SPEAKER

WHITE

RED

(130 mm X 127 mm X 38 mm)5 1/8"" H x 5" W x 1 1/2"D

DIMENSIONS

RED WITH WHITE "FIRE" LETTERING

WHITE WITH RED "FIRE" LETTERING

SPEAKER = 4 5/8" (117 mm)

DIMENSIONS

TOTAL SURFACE DEPTH WITH(136 mm x 133 mm x 81 mm)

5 3/8" H x 5 1/4" W x 3 3/16" D

5 1/8" H x 5 " W x 1 1/2" D

(130 mm X 127 mm X 38 mm)

DIMENSIONS

SP

KR

-T

B1

G

70.7V

EF

25V

CD

J1

AB

SP

KR

+

25VRMS

POSITIONJUMPER

70.7VRMS

VOLTAGE

2

12

1/21/4

1/41/21

WATTAGESETTING

DESCRIPTION

DESCRIPTION

PRODUCT SELECTION SPEAKER MOUNTING ADAPTERS AND BOXES

TILE BRIDGE2905-9946

NUMBERMODEL

MOUNTING ADAPTERS

NUMBERMODEL

4902-9721(CA)OR WALL MOUNTROUND HOUSING SPEAKER, CEILING

(602 mm x 340 mm x .508 mm)

OFF-WHITE (NO LETTERING)

23 11/16" L x 13 3/8" W x .024" THK

DIMENSIONS

DIMENSIONS

7 1/2" DIA x 1/2"D(191mm x 13mm)

25

V

F

TB1SPKR- SPKR+

J1

70

.7V

CA

BD

EG

WIRING NOTES

1/4

J1 TO TAP G

J1 TO TAP FJ1 TO TAP E

J1 TO TAP DJ1 TO TAP DJ1 TO TAP CJ1 TO TAP BJ1 TO TAP A

21

25VRMS

70.7VRMS

1/21/42

1/21

POSITIONJUMPER

VOLTAGEWATTAGESETTING

SW

2A

DD

RE

SS

SW

ITC

H

13

25

47

68

INPUTCKT

-

INPUTCKT+

TB

1

1=ON

1 2 3

LSB

0=OFFUSEDNOT

4 5 6 7 8

MSB

* PERFORMANCE REFERENCE, NOMINAL AVERAGE CURRENTS WITH STROBES FLASHING

*CURRENT DRAWS REFLECT STROBE FLASHING

DIP SWITCHES 5 & 6

353433

32

0100

383736

4140

39

444342

474645

259

111101111011001111010101

3115

12

1413

1110

28

3029

2726

1010

1001

0001

11100110

0010110001001000

0000

1 THRU 4DIP SWITCHES

87

56

4

2423

2122

20

23

1

0000

0

1819

17

1000

16

FUTURE USERESERVED FOR

57

63

60

6261

5958

56

55

5354

52

5051

49

1100

48

WHITE

4906-9204

4906-9202 RED

WHITE RED

PCAF

INTENSITY SELECTIONPLUG, ACCESSIBLEONLY FROM REAR OFHOUSING; FACTORY

STROBE INTENSITY SETTINGVIEWABLE THROUGH THE LENS

SETTING IS FACP

CANDELA SELECTION PLUG

0.1800.0920.060 0.240

MODEL NUMBER COLORCOVER

75cd30cd

CURRENT VALUES ARE UL 1971 MAX RATING

15cd 110cdVOLTAGECOLOR

23 VRMS17 VRMS

17 VRMS

23 VRMS

LETTERING

0.2420.1280.076 0.328

0.2420.1280.076 0.328

0.1800.0920.060 0.240

DIP SWITCHES 5 & 6

353433

32

0100

383736

4140

39

444342

47

4645

259

111101111011001111010101

3115

12

1413

1110

28

3029

2726

1010

1001

0001

11100110

0010110001001000

0000

1 THRU 4DIP SWITCHES

87

56

4

2423

2122

20

23

1

0000

0

1819

17

1000

16

FUTURE USERESERVED FOR

57

63

60

6261

5958

WATTAGESETTING

J1 TO TAP GJ1 TO TAP FJ1 TO TAP EJ1 TO TAP DJ1 TO TAP DJ1 TO TAP CJ1 TO TAP BJ1 TO TAP A

POSITIONJUMPER

56

55

5354

52

5051

49

1100

48

2

25VRMS1

2

1/41/2

70.7VRMS

VOLTAGE

1/41/21

4906-9254 WHITE RED

USEDNOT

1=ON 0=OFF

1 2 3

LSB

4 5 6 7 8

MSB

0.1800.0920.060 0.240

WIRING INPUT TERMINALS AND SPEAKERTAP SELECTION ARE ACCESSIBLE FROM

REAR OF SPEAKER HOUSING.

ADDRESS SETTING DIP SWITCH IS BEHINDSTROBE ASSEMBLY; SELECT ADDRESS BEFOREINSERTING INTO HOUSING.DIP SWITCHES 1 ~ 6 ARE USED TO SET ADDRESS.DIP SWITCHES 7 AND 8 ARE NOT USED ANDSHOULD BE SET TO "OFF".

INTENSITY SELECTIONPLUG, ACCESSIBLEONLY FROM REAR OFHOUSING; FACTORY

STROBE INTENSITY SETTINGVIEWABLE THROUGH THE LENS

SETTING IS FACPPCAF

STROBE LENS PROTRUSION DIMENSIONS : 2 5/8" (67MM) ABOVE SPEAKER HOUSING

SPEAKER HOUSING DIMENSIONS : 7 1/2" DIA. X 1/2"D (191MM X 13MM)

DEPTH INTO BOX 2 3/4" (70MM)

4906-9255 WHITE

4906-9256 WHITE RED

FIRE

BLANK

ALERT

4906-9257 WHITE REDFIRE

MODEL NUMBER LETTERINGCOLORCOVER

75cd30cd

CURRENT VALUES ARE UL 1971 MAX RATING

15cd 110cdVOLTAGECOLOR

23 VRMS

17 VRMS

17 VRMS

23 VRMS

17 VRMS

23 VRMS

17 VRMS

23 VRMS

LETTERING

0.2420.1280.076 0.328

0.2420.1280.076 0.328

0.2420.1280.076 0.328

0.2420.1280.076 0.328

0.1800.0920.060 0.240

0.1800.0920.060 0.240

0.1800.0920.060 0.240

DIP SWITCHES 5 & 6

353433

32

0100

383736

4140

39

444342

47

4645

WHITE S/V COVER WITH RED "FIRE" LETTERING

RED S/V COVER WITH WHITE "FIRE" LETTERING

4905-9903 (THIS BOX MAY BE AVAILABLE FOR RETROFIT APPLICATIONS)MOUNTING BOX, RED FOR SURFACE OR FLUSH MOUNT REQUIRES ADAPTER PLATE

ADAPTER PLATE, RED, REQUIRED TO MOUNT S/V ON 2975-9145

1 1/2" DEEP EXTENSION4" SQUARE, 1 1/2" DEEP WITH

SURFACE MOUNTED ELECTRICAL BOXREQUIRED WHEN MOUNTING TO

259

*CURRENT DRAWS REFLECT STROBE FLASHING

111101111011001111010101

3115

12

1413

1110

28

3029

2726

COVERS (FOR REPLACEMENT OR COLOR CONVERSION)

4905-9997

4905-9996

NUMBERMODEL

1010

1001

0001

11100110

0010110001001000

0000

1 THRU 4DIP SWITCHES

87

56

4

2423

2122

20

23

1

0000

0

1819

17

1000

16

FUTURE USERESERVED FOR

SURFACE MOUNT WHITE ADAPTER SKIRT

SURFACE MOUNT RED ADAPTER SKIRT

MOUNTING ADAPTERS AND BOXES

2975-9145

4905-9903

4905-9947

4905-9946

NUMBERMODEL

57

63

60

6261

5958

(184 mm X 127 mm X 35 mm)7 1/4" H X 5" W X 1 3/8"D

DIMENSIONS

56

55

5354

52

5051

49

1100

48

DIMENSIONS

(200 mm X 130 mm X 70 mm)

7 7/8" H X 5 1/8" W X 2 3/4"D

(211 mm X 146 mm X 1.5 mm)8 5/16" H X 5 3/4" W X 0.060" THICK

7 3/4" H X 5 3/8" W X 3 3/16"D

(197 mm X 137 mm X 81 mm)

DEPTH WITH S/V=5 7/8" (149mm)

WHITE

4906-9253

4906-9251 RED

WHITE RED

USEDNOT

1=ON 0=OFF

1 2 3

LSB

4 5 6 7 8

MSB

INTENSITY SELECTIONPLUG, ACCESSIBLEONLY FROM REAR OFHOUSING; FACTORY

STROBE INTENSITY SETTINGVIEWABLE THROUGH THE LENS

SETTING IS FACPPCAF

WATTAGESETTING

J1 TO TAP GJ1 TO TAP FJ1 TO TAP EJ1 TO TAP DJ1 TO TAP DJ1 TO TAP CJ1 TO TAP BJ1 TO TAP A

POSITIONJUMPER

2

25VRMS12

1/41/2

70.7VRMS

VOLTAGE

1/41/21

WALL MOUNT INSTALLATIONHEIGHT REFERENCE

NFPA 72 REQUIRES THAT

THE ENTIRE LENS BE NOT

LESS THAN 80" AND NOT

GREATER THAN 96" ABOVE

THE FINISHED FLOOR.

IMPORTANT!

CL

82"

MIN.

78-1/2"

MIN.

2975-9145BOX OUTLINE

4" SQUARE BOX OUTLINE

4"

1-1/2"

0.1800.0920.060 0.240

MODEL NUMBER COLORCOVER

75cd30cd

CURRENT VALUES ARE UL 1971 MAX RATING

15cd 110cdVOLTAGECOLOR

23 VRMS17 VRMS

17 VRMS

23 VRMS

LETTERING

0.2420.1280.076 0.328

0.2420.1280.076 0.328

0.1800.0920.060 0.240

EFORPDERETSI

GER

REEN

IGN

E

LANOISS

C A L I F OR N I AS T A T E O F

R I C A LE L E C T

No. E16806

JASON LAU

E N G I N E E R I N GI N T E R F A C E

TEL

FAX

PROJECT

CONTACT

www.interfaceengineering.com

717 Market Street

Suite 500

San Francisco, CA 94103

415.489.7240

415.489.7289

SHEET NO:

DATE:

PROJECT NO:

THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THEPURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVEAND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THEWRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONALSERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2009.

THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECTAND ENGINEER.

CONSULTANT

6910 5 31112 8 7 4 2 1

J

K

H

G

F

E

D

C

B

A

B

A

J

K

H

G

F

E

D

C

6910 5 31112 8 7 4 2 1

NO. ISSUE DATE

ARCHITECT'S STAMP APPROVAL

Joe Ripp

2014-0174

SAN JOSE CITYCOLLEGE

PHYSICAL EDUCATION BUILDING ANDRENOVATED LAB BUILDING

SAN JOSE, CALIFORNIA

DETAILS - FIRE ALARM

FA7.03

1.12.2015

1089-0001

DSA SUBMITTAL

Page 12: SAN JOSE CITY - SJECCD Fire Alarm.pdf · relay iam simplex 4090-9002 4" square box 2 1/8" deep w/two gang cover individual addressable module simplex 4090-9001 single gang ... installation

END-OF-LINE RESISTOR CODES

66"

3 17/32"

6 29/32" 24"1 7/16"

16"

SEECHART

5 17/32"

11 11/16"

4 3/4"

(TYPICAL, FOR5 FOOT HEIGHTTO LCD DISPLAY

CENTERLINE)

3 1/4" MIN.10" MAX.

4100ES BACKBOX INSTALLATION

SIDE WALL

CEILING

DEVICE MOUNTING HEIGHT REFERENCE (PER NFPA 72)

OR RETURNDIFFUSER

ACCEPTED HERE

NOTE: MEASUREMENTSSHOWN ARE TO THECLOSEST EDGE OF THE

42" MIN (NFPA)

48" MAX (ADA)

DOORWIDTH

80" MIN (NFPA)

SYNCHRONIZE MORE THAN

TWO APPLIANCES IN ANY

FIELD OF VIEW.

DETECTOR.

LESS 3"

5"

TO EXIT DOOR

80" MIN (ADA)

A/C SUPPLY

(1067mm MIN)

(1219mm)

(2032mm MIN)

(2032mm MIN)

REF. 80" MIN (IBC)

(2032mm MIN)

ABOVE FINISHED FLOOR

REF. 96" MAX (IBC)

(2440mm MAX)

ABOVE FINISHED FLOOR

96" MAX (NFPA, ADA)

(2440mm MAX)

NOTE: REFER TO THE PROPER DEVICE

FOR BACKBOX MOUNTING HEIGHT.

INSTALLATION INSTRUCTIONS

FOR CEILING HEIGHTS LESS THAN 86" (2180mm),

THE VISUAL LENS MOUNTING HEIGHT SHALL BEWITHIN 6" (150mm) OF THE CEILING.

ABOVE FINISHED FLOOR

90" MIN (2286mm MIN)

BELOW FINISHED CEILING6" MIN (152.4mm MIN)

NFPA 72 AUDIBLE APPLIANCE

(OTHER MOUNTING HEIGHTS SHALL BEPERMITTED BY THE AHJ PROVIDING ITMEETS THE SOUND LEVEL OUTPUT REQUIRED.)

BEEN REMOVED FROM THE 2010 EDITION OF NFPA 72

THE 4" REQUIREMENT FOR SMOKE DETECTORS HAS

48" MAX (NFPA, ADA) (1219mm MAX)

MEASUREMENTS SHOWN ARE

TO TOP OF PULL HANDLE

TO TOP OF LENS

TO BOTTOM OF LENS

NO. 5747 SUPPLIED

2975-9178 OR

WIREMOLD BOX

BY CONTRACTOR

FROM SIMPLEX OR2975-9022 BOXES

4099-9020 SINGLE ACTION NO GRIP IDNet SLC ADDRESSABLE MANUAL STATION

2. CONDUCTORS MUST TEST FREE OF ALL GROUNDS.

4. IDNet SLC LINES ARE TO BE 18 AWG TWISTED SHIELDED PAIR

8. TERMINALS 1 AND 2 FOR FIELD WIRING. TERMINALS 3 AND

APPLICATION:

CONSTRUCTION:

WIRING:1. ALL WIRING TO COMPLY WITH LOCAL CODE.

3. MAINTAIN CORRECT POLARITY

PRODUCT INFORMATION

FEATURES:

TAMPER RESISTANT RESET KEY LOCK

MOUNTING: SEMI-FLUSH, SURFACE

OPERATING HUMIDITY RANGE: 0 - 93% RH

OPERATING TEMPERATURE RANGE: 32 - 120° F

PULL LEVEL PROTRUDES WHEN ALARMED

UL LISTED

SINGLE ACTION, NO GRIP, IDNet SLC ADDRESSABLE

5. MAXIMUM LINE RUN FROM PANEL TO FARTHEST DEVICE NOT

6. MAXIMUM TOTAL WIRE (INCLUDING ALL T-TAPS) FROM PANEL NOT TO

EXCEED 10,000 FEET.

7. MAXIMUM QUANTITY OF DEVICES PER CIRCUIT: 250

SURFACE MOUNTING

TOP AND BOTTOM OF BOXKNOCKOUTS FOR 3/4" CONDUIT

SEMI-FLUSH MOUNTING

INTRODUCTION:

4 ARE FACTORY WIRING.

TO EXCEED 2500 FEET.

9. WIRE NUT, SPLICE, OR SOLDER THE SHIELD WIRES.

OPERATION:ADDRESS DIP SWITCHES UNDER RE-SEALABLE LABEL

SEE INSTALLATION INSTRUCTIONS (574-332 FOR SETTINGS

4" SQUARE x

(RACO NO. 231 OR 232)SINGLE GANG EXTENSION RING 3/4"

SUPPLIED BY CONTRACTOR

(RACO NO. 773)

SCREW TERMINALS FOR 18 TO 14 AWG WIRE

ADDRESSED BY MEANS OF AN 8 POSITION DIP SWITCH

5" HIGH X 3 3/4" WIDE X 1' DEEP

ADAPTER PLATES 2099-9813 OR 2099-9814 CAN BEUSE FOR RETROFIT APPLICATIONS.

COMPATIBLE WITH IDNet SLC/MAPNET

10. IF SHIELD IS PRESENT, IT SHOULD BE CONNECTED TO THEOUTGOING IDNet SLC SHIELD TO PROVIDE A CONTINUOUS SHIELD OVERTHE LENGTH OF THE IDNet SLC CHANNEL. SHIELD SHOULD BEINSULATED FROM THE ELECTRICAL BOX.

11. SEE INSTALLATION INSTRUCTIONS 574-332

OR (RACO NO. 500)SINGLE GANG SWITCH BOX

SUPPLIED BY CONTRACTOR

2 1/8" DEEP BOX

2 1/2" DEEP

AND ADA GUIDE LINES.PULL STATIONS SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 72

STATION HOUSING AND PULL LEVER ARE CONSTRUCTED OF CHIPRESISTANT AND DIRT RESISTANT, HIGH IMPACT LEXAN.

HOUSING IS RED WITH RAISED WHITE LETTERING AND PULL LEVER ISWHITE WITH RED RAISED LETTERING.* LEXAN IS A REGISTERED TRADEMARK OF THE GENERAL ELECTRIC CO.

MOUNTING INSTRUCTIONS:1. COVER & BACKPLATE COME ASSEMBLED.2. UNLOCK STATION, DROP COVER FORWARD

TO EXPOSE MOUNTING SCREWS.

OTHER IDNet SLC DEVICES ON CIRCUITFROM FIRE ALARM CONTROL PANEL OR

SHIELDSHIELD SHIELD

APPLICATION.TO FIRE ALARM CONTROL PANEL FOR STYLE 6TO ADDITIONAL IDNet SLC DEVICES OR RETURN

-+

THE 4099-9020 ADDRESSABLE PULL STATION PROVIDES TWO-STATESTATUS INFORMATION (NORMAL AND SHORT) TO THE IDNet SLC COMPATIBLE FIREALARM CONTROL PANEL (FACP) VIA THE IDNet SLC CHANNEL. THE IDNet SLCCHANNEL PROVIDES THE COMMUNICATION LINK BETWEEN PULL STATIONAND THE FACP AND POWERS THE ENTIRE CIRCUITRY.

PULL LEVER (USE OF PLASTIC ROD IS OPTIONAL). THE PULL LEVEL LATCHESBREAKS AN INTERNAL PLASTIC BREAK-ROD THAT IS VISIBLE BELOW THE

ACTIVATED PULL LEVER FOR ANTICIPATED USERS MAY FIND THE STANDARD4099-9020 NO GRIP SINGLE ACTION STATION PROVIDES A MORE EASILY

HOUSING TO PROVIDE A VISIBLE INDICATION.INTO THE ALARM POSITION AND REMAINS EXTENDED OUT OF THE

+-

21

3 4

1

3

2

4

7

4321IDNet SLC 9

5 6 65

ACTIVATION:

(IF OPTIONAL PLASTIC BREAK ROD WAS USED IT MUST BE REPLACED)THE ACTIVATION LEVER AND DEACTIVATE THE ALARM SWITCH.4099-9020 SINGLE ACTION STATION REQUIRES A KEY TO RESETRESETTING

FLUSH MOUNTING 6" HIGH BY 5" WIDE

CUTOUT MUST BE A MINIMUM

NOTE: BOX MUST BE RECESSEDINTO WALL 1" TO 1 1/8".

SUPPLIED BY CONTRACTOR4 11/16" SQUARE x 2 1/8" DEEP BOX

1. COVER & BACKPLATE COME ASSEMBLED.2. UNLOCK STATION, DROP COVER FORWARD

TO EXPOSE MOUNTING SCREWS.

MOUNTING INSTRUCTIONS:

FLUSH ADAPTOR AVAILABLE2099-9820 (BEIGE)2099-9819 (BLACK) OR

FROM SIMPLEX

1. COVER & BACKPLATE COME ASSEMBLED.2. UNLOCK STATION, DROP COVER FORWARD

TO EXPOSE MOUNTING SCREWS.

MOUNTING INSTRUCTIONS:

STATION LEVER DIFFICULT TO ACTIVATE. COMPLETING THIS ACTION

IDNET DIP SWITCH SETTINGS

0=OFF1=ON

1111

241

242

244

245

243

240

247

248

250

251

249

253

254

255

252

246

0011 1011

193

194

196

197

195

209

210

211

212

213

192 208

11011001 0101

145

146

148

149

147

161

162

163

164

165

144 160 176

177

178

179

180

181

199

200

202

203

201

215

216

217

218

219

205

206

207

221

222

223

204 220

151

152

154

155

153

167

168

169

170

171

157

158

159

173

174

175

156 172

183

184

185

186

187

188

189

190

191

150 166 182 198 214

0111

224

225

226

227

228

229

230

231

232

233

234

235

236

237

238

239

1286432

7 86

842

42 3 5

16

ADDRESS SHOWN ABOVE IS 120

1ON

1OFF

00010110 1110

129

130

132

133

131

97

98

100

101

99

113

114

115

116

117

96 112 128

10100010

81

82

84

85

83

49

50

52

53

51

65

66

67

68

69

48 64 80

135

136

139

138

137

103

104

106

107

105

119

120

121

122

123

142

141

143

109

110

111

125

126

127

108 124 140

87

88

91

90

89

55

56

58

59

57

71

72

73

74

75

94

93

95

61

62

63

77

78

79

60 76 92

54 70 86 102 118 134

01001000

33

34

36

37

35

1

2

4

5

3

17

18

19

20

21

0 16 32

1000

0100

0010

1010

1100

DIP

0000

0000

39

40

43

42

41

7

8

10

11

9

23

24

25

26

27

46

45

47

13

14

15

29

30

31

12 28 44

1110

0001

0101

1101

1001

1011

0111

1111

0011

0110 6 22 38

1100

DIP SWITCHES 5 THRU 8

IDNET ADDRESSINGDO NOT USE ADDRESS 0 FOR AN IDNET ADDRESS

SWITCHES

1 THRU 4

INSTRUCTIONS

FLOOR

REFER TO FIG.1 FOR TYP. CONDUITPENETRATION LOCATIONS

FOR SURFACE MOUNTUSE 4 HOLES TO SECURE

BACKBOX TO WALL

BATTERY AREA

(IF APPLICABLE)

NO CONDUIT ENTRY OR

WIRING IN THIS AREA

REMOVE ELECTRONIC CARD CAGE (IF PRESENT)

AND STORE IT IN A SAFE DRY AREA.

1.

NO KNOCKOUTS PROVIDED. CUT CONDUIT/SERVICE ENTRANCE

OPENINGS. REFER TO FIG.1 FOR PROPER LOCATIONS.

2.

CONDUIT PROTRUSION INTO BOX 1/2" MAX.

MOUNT BOX TO WALL: BOX MUST BE LEVEL AND PLUMB.

FOR SURFACE MOUNT USE TEAR DROP AND CLEARANCE HOLES

3.

ON BACK SURFACE.

FOR SEMI-FLUSH MOUNT: USE WALL STUD GUIDES FOR MAXIMUM

USE KNOCKOUTS ON SIDE WALL, SCREW OR NAIL BOX TO WALL STUDS.

IF PRESENT, USE WIRE MANAGEMENT BRACKETS ON BOX SIDES

TO SECURE WIRE RUNS.

4.

NEMA RATING: NEMA 1 - GENERAL PURPOSE.

5.

PID NUMBER BOX HEIGHT

2975-9407 22"

2975-9408 40"

2975-9409 56"

2975-9410 22"

2975-9411 40"

2975-9412 56"

WALL STUD GUIDES

(SEE NOTE 3.)

WALL

KNOCKOUT

(SEE NOTE 3.)

SCREW/NAIL

HOLES FOR

SEMI-FLUSH

MOUNT

FIG. 1

DO NOT LOCATE POWER-LIMITED WIRING IN THE SHADED AREAS

6.

OF THE BACKBOX, THIS AREA IS RESERVED FOR NON-POWER

LIMITED CIRCUITRY SUCH AS AC POWER, BATTERIES AND CITY

CONNECTION.

MINIMUM DISTANCE BETWEEN ANY TWO BOXES IS 3 1/4" (6" MAXIMUM).

7.

REFER TO SIMPLEX BACKBOX INSTALLATION DOCUMENT

579-117 FOR DETAILED INSTRUCTIONS.

8.

PID NUMBER BOX HEIGHT BOX LENGTH BOX DEPTH

2081-9280 12" 26 1/2" 12"

4081-9306 13 1/2" 27 7/8" 14 5/8"

4081-9308 13 1/2" 27 7/8" 14 5/8"

2975-9438 22"

2975-9439 40"

2975-9440 56"

PKG. SIZE

1 BAY

2 BAY

3 BAY

1 BAY

2 BAY

3 BAY

1 BAY

2 BAY

3 BAY

ADA REQUIREMENTS LIMIT THE ALLOWABLE PROTRUSION OF OBJECTSMOUNTED IN PUBLIC ACCESSIBLE WALKS, HALLS, CORRIDORS,PASSAGEWAYS OR AISLES. THE 4 INCH (100mm) RESTRICTION APPLIES TOANY ITEM IN WHICH THE MEASUREMENT FROM THE FLOOR TO THE BOTTOMOF THE UNIT IS MORE THAN 27 INCHES.

NOTE:

ALLOWABLE BOX DEPTH TO PROVIDE OPEN DOOR CLEARANCE.

TYPICAL CONDUIT LOCATION FORPWR. LIMITED FIELD WIRING

EXAMPLE OFADDITIONAL CABINETMOUNTING LOCATION

CONDUIT FOR INTERNALPANEL HARNESSES ORNPL WIRING.

3RD BAND

REDRED

2ND BAND

RED

1ST BAND 5TH BAND

GOLDREDVIOLET4.7K YELLOW

GOLDREDGREY6.8K BLUE

GOLDREDGREY1.8K BROWN

GOLDBROWNBLUE560 GREEN

GOLDREDRED1.2K BROWN

GOLDORANGEBLACK10K BROWN

GOLDBLACKBLACK20 RED

GOLDREDBLACK1K BROWN

GOLDBROWNBLACK100 BROWN

GOLDORANGERED22K RED

BROWNWHITEWHITE4.99K YELLOW

GOLDREDYELLOW2.4K RED

GOLDREDGREEN1.5K BROWN

GOLDYELLOWGREEN150K BROWN

GOLDREDWHITE3.9K ORANGE

GOLDORANGEBLACK10K BROWN

733-893

733-892

NUMBER

733-896

733-886

733-984

733-890

733-891

733-894

733-912

733-973

733-974

733-985

734-086

734-092

734-093

734-149

734-171

734-168

4081-9001

MODELREFERENCE

4081-9002

4081-9003

4081-9004

4081-9005

4081-9006

4081-9007

4081-9008

4081-9009

4081-9010

4081-9011

4081-9012

4081-9013

4081-9014

4081-9015

4081-9016

4081-9017

4081-9018

1

1/2

WATTS

1/2

1/2

1/2

1

1

1/2

1

1

1/2

1/2

1/2

1/2

1/2

1/2

1

1

4TH BAND

GOLD

GOLD

REDORANGE3.3K ORANGE

2.2K

OHMS

BROWN

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

CIRCUIT TYPE FIRE ALARM PANEL/MODULE

ANNUNCIATOR (4300) 4004, 4010 (TROUBLE)

N.O. INITIATING 4004*, 4004R, 4005*, 4006,

WATERFLOW, TAMPER, ETC.

4100, 4120, 4100U, ZAM'S

* USE WITH RETROFIT OR HIGH CURRENT MODULE

SPEAKER CIRCUIT 4003

NOTIFICATION (DACT)

4090-9001 IDNET IAM (EOLR)

ANNUNCIATOR (N2) 4006, 4008, 4010

4004, 4005,

PULL, SMOKE, HEAT,

CURRENT LIMITED N.O. INITIATING

2080-9024

4090-9001 IDNET IAM2190-9173 MAPNETII 2 PT I/O

N.O. INITIATING

WATERFLOW, TAMPER, ETC.

PULL, SMOKE, HEAT,

4090-9001 IDNET IAMCURRENT LIMITED N.O. INITIATING

4605-7401, 4100 SERIES24 PT. I/O SWITCH SUPV.

NOTE: REFER TO PANEL/MODULE AND DEVICE INSTALLATIONINSTRUCTIONS FOR PROPER TERMINATIONS.

4-20MA ZAM (TROUBLE)

N.C. INITIATING (EOLR) 4005*, 4090-9001 IDNET IAM

N.C. INITIATING (ACROSS CONTACTS) 4005*, 4090-9001 IDNET IAM

(IN LINE)

N.C. INITIATING (EOLR) 4005

NOTIFICATION4004, 4005, 4006, 4008,4009, 4010, 4100, 4100U

4090-9001 IDNET IAMCURRENT LIMITED N.O. INITIATING

(IN SERIES WITH CONTACT)

TO MR-101 RELAY COIL 4005 8 POINT I/O

70VRMS CONSTANT SUPV. NACS 4100-1260

4100, 4100U

4090-9001 IDNET IAMCURRENT LIMITED N.O. INITIATING

(SECURITY MONITORING EOLR)

N.C. INITIATING4090-9001 IDNET IAM(SECURITY MONITORING EOLR)

4605-7401, 4100 SERIES24 PT. I/O (ACROSS CONTACTS)

GOLDREDRED8.2K GRAY

GOLDREDBLUE5.6K GREEN

GOLDORANGERED12K BROWN

378-090

378-046

378-069

1/2

1/2

1/2

N/A

N/A

N/A N.C. SECURITY MON. (SHUNT) 4100, 4100U

4100, 4100U

4100, 4100UN.O. SECURITY MON. (SERIES)

SECURITY MONITORING (EOLR)

SIGNALING LINE (ADDRESSABLE) CIRCUITS SHIELDING EXAMPLE

BY CREATING A PROPER PROCEDURE FOR WIRE

MOST GROUNDS AND SHORTS CAN BE ELIMINATED.

WIRING TECHNIQUES FOR SHIELDED CABLE:

PRODUCT INFORMATION

MOST SHORTS ARE SHIELD TO CONDUCTOR.

MOST GROUNDS ARE DUE TO SHIELDING ISSUES.

THE CONNECTORDRAIN WIRES INTO

SECURE THE

UL LISTED FIRE PROTECTIVE SIGNALING CABLES MAY BE SELECTED FROM THE SIMPLEXGRINNELL WIRE & CABLE TABLE, #WIRE TABLE

6

ONLY CLASS B IDNET, MAPNET OR

DATA COMM. CABLE MAY BE

TAPE WRAPPED AS SHOWN HERE.

CORD CLAMP/BUSHING, AND

T-TAPPED. IT MUST BE DONE

CABLE STRAIN RELIEF I.E.

IN A JUNCTION BOX WITH

7

MIN. SIZE IS 18-2 AWG SOLID STP.

#18-2 AWG SHIELDEDTWISTED-PAIR CABLE

PREPARE THE CABLE BY

JACKET AS NEEDED.REMOVING 2" TO 4" OF

2

1USE ONLY UL LISTED FIRE ALARMTWISTED SHIELDED PAIR CABLE

WIRING IN A FIRE ALARM SYSTEM.LINES, AUDIO, PHONE & SPEAKER(TSP) FOR IDNETS, DATA COMM.

4

DRAIN WIRE

KEEP THE DRAINTHE SHIELD ANDTRIM AWAY ONLY

WIRE UNDAMAGED.3

SHIELD

5

HANDLING WITH ADDRESSABLE CIRCUITS

SHIELDS AND DRAINS MUST NEVER TOUCH GROUND.

1. ALL WIRING IS TO BE COPPER CONDUCTOR. ALL EQUIPMENT MUSTBE INSTALLED IN ACCORDANCE WITH THE MANUFACTURERSRECOMMENDATIONS AND THE SPECIFICATIONS AND STANDARDSOF THE AUTHORITY HAVING JURISDICTION. THE INSTALLATION OFALL WIRING, CABLE AND EQUIPMENT MUST BE IN ACCORDANCE

WITH NFPA 70, NATIONAL ELECTRICAL CODE NEC), AND SPECIFICALLY

WITH ARTICLE 760, FIRE ALARM PROTECTIVE SIGNALING SYSTEMS;

2. IF SHIELDED WIRE IS USED, THE FOLLOWING MUST BE OBSERVED:A. METALLIC CONTINUITY OF THE SHIELD MUST BE MAINTAINED AND

INSULATED THROUGHOUT THE ENTIRE LENGTH OF THE CABLE.B. SHIELDS SHALL ONLY BE CONNECTED AT THE CONTROL UNIT.

4. WIRING OTHER THAN THAT CONNECTED TO ELEVATOR CABS MUST NOT BE RUN

5. WIRING IN DUCTS, PLENUMS AND OTHER AIR HANDLING SPACES MUST BE LISTEDFOR PLENUM USE AND INSTALLED IN ACCORDANCE WITH NFPA 70, ARTICLE 300.

6. SPLICING IS PERMITTED IN ACCORDANCE WITH NFPA 70. ALL JUNCTIONS MUSTBE INSULATED AS SOUNDLY AS THE ORIGINAL JACKET. CONTINUITY OF ANY SHIELD

7. ONLY SYSTEM WIRING CAN BE RUN IN THE SAME CONDUIT.

AND STYLE 6 SIGNALING LINE CIRCUIT. MAXIMUM WIRE RUN NOT TO EXCEED 2500 FT.

9. ALL CIRCUITS ARE SUPERVISED AND POWER-LIMITED UNLESS OTHERWISE INDICATED. SHIELD WIRES ARE NOT SUPERVISED.

10. OPERATING POWER, FOR IDNet DEVICES, MUST ORIGINATE FROM A POWER-LIMITED POWER SUPPLY LISTED FOR FIRE

PROTECTIVE SIGNALING USE OR, FROM THE F.A. CONTROL PANEL POWER SUPPLIES INDICATED IN THE APPROPRIATEDIAGRAM. MAXIMUM WIRE NOT TO EXCEED 1KM (3270 FT).

11. WHEN COMMUNICATION WIRING OR OPERATING WIRING LEAVES THE BUILDING, OVERVOLTAGE PROTECTORS ARE

REQUIRED; USE 2081-9044, INSTALL ONE WHERE IT LEAVES THE BUILDING AND ONE WHERE IT ENTERS THE NEXT BUILDING.

15. IDNET MAXIMUM NUMBER OF DEVICES:NON-CODED 250

CODED PIEZO BASES 43 MAX.

(WHERE USED) MUST BE MAINTAINED.

8. THE COMMUNICATION CIRCUIT MEETS THE OPERATIONAL CHARACTERISTICS DEFINED FOR A STYLE 4

14. IDNet COMMUNICATION LINE SPECS.:MAX. 36 VDC @ .5A

3333 BAUD

33 MAX. LINE RESISTANCE

ARTICLE 800, COMMUNICATION CIRCUITS, WHERE APPLICABLE.

SHIELD MUST NOT BE CONNECTED TO, OR TOUCH CONDUIT, ELECTRICAL

3. UNDERGROUND WIRING MUST BE LISTED FOR APPLICATION AND FREE OF ALL WATER.

IN ELEVATOR SHAFTS (REF.NFPA 70, ARTICLE 620).

217 ADDRESSES STILL AVAILABLE FOR OTHER DEVICES.

EXAMPLE:CUT

DRAIN WIRE

SHIELD

BLACK INSULATION TOSLIDE ONTO DRAIN WIRE.

STRIP OFF APPROX.1-2 INCHES OF

DISCARDREUSE INSULATION

DRAIN WIRE

JACKET. SECURE WITHCAREFULLY DOWN INTOPUSH REUSED INSULATION

ELECTRICAL TAPE.

BLACK(-)

(+)RED

ABOUT 5/16" TO 3/8" FORINSERTION INTO BOX-TYPEOR SCREW-CLAMP TERMINALS.

REDUCE EXPOSED WIRES TODRAIN WIRE

ELECTRICAL TAPE.

+ --+

SEPARATELY UNDER TERMINALS.A CONTINUOUS WIRE LOOPIS NOT ALLOWED.

WIRES MUST BE CONNECTED

CONNECTOR LISTED AND

TO ABOUT 1-1/2". JOINTHEM WITH AN ELECTRICAL

TRIM THE BARE DRAIN

THE SHIELD/DRAIN IS NEVERCONNECTED TO THE DEVICE.

THE ADDRESSABLE DEVICE.

ABOUT 5/16" TO 3/8" FOR

INSERTION INTO BOX-TYPE ORSCREW-CLAMP TERMINALS ON

STRIP THE INSULATED WIRES

CLASS 'B'

+CLASS 'A'

--+

8

9

9.A

ALL UNSHIELDED WIRE MUST BE ENTIRELY IN GROUND CONDUIT.

CONDUIT SYSTEM MUST HAVE A GOOD REFERENCE TO EARTH GROUND

TAGWIRE

N1:M2

EXAMPLE FOR

WIRING LABELING

D. ALL CONDUCTORS ARE TO BE FREE OF SHORTS AND GROUNDS.

C. THE ENTIRE LENGTH OF THE CABLE MUST HAVE A RESISTANCE GREATERTHAN 1 MEGOHM TO EARTH.

BOXES, OR ASSOCIATED HARDWARE AT ANY POINT.

GENERAL WIRING GUIDELINES

ERRORS, ALL WIRES MUST BE TAGGED.TO PREVENT CONFUSION AND POSSIBLE

SEE WIRE LEGEND FOR TYPES.

12. TO PREVENT CONFUSION AND POSSIBLE ERRORS, TAG ALL CONDUCTORS, CODE AT INSTALLATION, TO IDENTIFYCIRCUIT ASSIGNMENT, POLARITY AND IN OR OUT DIRECTION OF THE WIRING. LOG ON AS-BUILTS.

SIMPLEXGRINNELL IS NOT RESPONSIBLE FOR ELECTRICAL CONTRACTOR'S WIRE CONDITIONS.13. LEAVE ADEQUATE SLACK IN THE WIRING TO ALLOW FOR TROUBLE SHOOTING.

WIRES MUST BETIGHT ENOUGHTO HOLD SECURELYAND NOT SLIP OUTOF THE CONNECTION.

PIGTAILS, (T-TAP) WIRING IS PERMITTED TO ADDRESSABLE DEVICES

FOR CLASS B CIRCUIT WIRING.

APPROVED FOR WIRE SPLICING.

APPROVED FORTHE PURPOSE.

UNABLE TO MAKEARE SECURED AND

ENSURE BARE DRAINS

EXTERNAL CONTACT.SEE NOTE 2

12" (MAX)

4"

3' (MIN)

AUDIBLE/VISUAL

& VISUAL ONLY

APPLIANCES

MANUAL

PULL

STATION

FINISHED

FLOOR

FINISHED

WALL

4"

FIREPHONE

JACKMAGNETIC

DOOR

HOLDER

WALL MOUNTED

SMOKE/HEAT

DETECTOR

CEILING MOUNTED

SMOKE/HEAT

DETECTOR

5' (MAX.)

(914mm MIN)

FIRE FIRE

SIMPLEX

(102mm)

(102mm)

(305mm MAX)

(76mm)

(127mm)

(1524mm)

VISUAL APPLIANCE MOUNTING HEIGHT CONSIDERATIONS IN SLEEPING ROOMS

1. MIN DISTANCE IN SLEEPING ROOMS IS 24" (610mm) FROM CEILING TO TOP OF

LENS FOR 110CD STROBES WITHIN 16' OF THE PILLOW

2. 177CD STROBES, USED IN SLEEPING ROOMS, CAN BE WITHIN THE 24" (610mm)

MINIMUM DISTANCE FROM THE CEILING. THE HIGHER INTENSITY IS TO

COMPENSATE FOR A POSSIBLE SMOKE LAYER.

FIRE

AUDIBLE ONLY

HEAT DETECTORSNEVER HERE

EFORPDERETSI

GER

REEN

IGN

E

LANOISS

C A L I F OR N I AS T A T E O F

R I C A LE L E C T

No. E16806

JASON LAU

E N G I N E E R I N GI N T E R F A C E

TEL

FAX

PROJECT

CONTACT

www.interfaceengineering.com

717 Market Street

Suite 500

San Francisco, CA 94103

415.489.7240

415.489.7289

SHEET NO:

DATE:

PROJECT NO:

THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THEPURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVEAND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THEWRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONALSERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2009.

THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECTAND ENGINEER.

CONSULTANT

6910 5 31112 8 7 4 2 1

J

K

H

G

F

E

D

C

B

A

B

A

J

K

H

G

F

E

D

C

6910 5 31112 8 7 4 2 1

NO. ISSUE DATE

ARCHITECT'S STAMP APPROVAL

Joe Ripp

2014-0174

SAN JOSE CITYCOLLEGE

PHYSICAL EDUCATION BUILDING ANDRENOVATED LAB BUILDING

SAN JOSE, CALIFORNIA

DETAILS - FIRE ALARM

FA7.04

1.12.2015

1089-0001

DSA SUBMITTAL