  • 8/22/2019 Safie Commissioning

    1/31

    www.gst.uk.com GST SMOKE AND FLAME INTELLIGENT EYE

    SAFIE Commissioning Operation

  • 8/22/2019 Safie Commissioning

    2/31

    www.gst.uk.com

    SAFIE EQUIPMENT REQUIRED

    GST SMOKE AND FLAME INTELLIGENT EYE

    Appropriate installers manual

    Copy of commissioning checklist/CCTV

    Test apparatus

    SAFIE Commissioning Operation

  • 8/22/2019 Safie Commissioning

    3/31

    www.gst.uk.com

    BASIC CCTV INSTALLATION GUIDE

    GST SMOKE AND FLAME INTELLIGENT EYE

    SAFIE Commissioning Operation

    Image Graber Card

    Using proper tools, fitting way of connector and complying with

    standard recommendation helps to reduce the signal loss

  • 8/22/2019 Safie Commissioning

    4/31

    www.gst.uk.com

    BASIC CCTV INSTALLATION GUIDE

    GST SMOKE AND FLAME INTELLIGENT EYE

    SAFIE Commissioning Operation

    Coax Cable RG59 RG6U RG11

    Max Working Distance (meter) 245 365 500

    Coax Cable Signal Loss (Attenuation) in dB per 100ft* (30m)

    Loss* RG-59 RG-6 RG-11

    1MHz 0.4dB 0.2dB 0.2dB

    10MHz 1.4dB 0.6dB 0.4dB

    Since losses in cables need to be considered, obviously for

    longer cable runs a lower loss per metre cable should be used

    to keep overall losses within acceptable limits. A 6dB loss is

    generally considered acceptable dB meter

  • 8/22/2019 Safie Commissioning

    5/31

    www.gst.uk.com

    BASIC HARDWARE INSTALLATION

    GST SMOKE AND FLAME INTELLIGENT EYE

    SAFIE Commissioning Operation

    Insert the Graphics Acquisition card(s) and relay output card into the PCI slot on the main

    board of the industrial PC one by one, and tight them with screws. Then, connect the relay

    output card and the terminal block with the accessory cable.

  • 8/22/2019 Safie Commissioning

    6/31

    www.gst.uk.com

    BASIC SOFTWARE INSTALLATION

    GST SMOKE AND FLAME INTELLIGENT EYE

    SAFIE Commissioning Operation

    Install the SAFIE SETUP

    software

    Note: Drivers for Graphic Acquisition card and Relay

    Output card are packed with SAFIE setup

    Make sure the dongle is fixed on the PC

  • 8/22/2019 Safie Commissioning

    7/31www.gst.uk.com

    BASIC SOFTWARE INSTALLATION

    GST SMOKE AND FLAME INTELLIGENT EYE

    SAFIE Commissioning Operation

    Hardware Update Wizard

    Select a hardware to be updated,

    The right click select

    update Drivers

    Window update to search for

    software, tick No

    Tick Installed from a list..

    1 2 3

  • 8/22/2019 Safie Commissioning

    8/31www.gst.uk.com

    BASIC SOFTWARE INSTALLATION

    GST SMOKE AND FLAME INTELLIGENT EYE

    SAFIE Commissioning Operation

    Hardware Update Wizard

    Tick Search for the best driver in these

    location Tick Include this location ,

    then select the path

    c:\WINDOWS\system 32

    Repeat the

    wizard until

    the

    hardware's

    were all

    update!!

    4 5 6

    Finish

  • 8/22/2019 Safie Commissioning

    9/31www.gst.uk.com

    BASIC SOFTWARE INSTALLATION

    GST SMOKE AND FLAME INTELLIGENT EYE

    SAFIE Commissioning Operation

    SAFIE will enter to the detection mode automatically after the system starts

  • 8/22/2019 Safie Commissioning

    10/31www.gst.uk.com

    BASIC CONFIGURATION

    GST SMOKE AND FLAME INTELLIGENT EYE

    SAFIE Commissioning Operation

    1. Password Configuration

    2. Setting camera number and name

    3. Configure the zones and sensitivity of each camera

    4. Setting of Relay Output Cause and Effect

  • 8/22/2019 Safie Commissioning

    11/31www.gst.uk.com

    SAFIE MAIN WINDOW

    GST SMOKE AND FLAME INTELLIGENT EYE

    SAFIE Commissioning Operation

    Channel Status

    Alarm Indicator

    To enter into the programming menu

    Operation Menu

    Visual Confirmation

  • 8/22/2019 Safie Commissioning

    12/31www.gst.uk.com

    PASSWORD CONFIGURATION

    GST SMOKE AND FLAME INTELLIGENT EYE

    SAFIE Commissioning Operation

    Factory default value

    Greenwell

    Two levels of password

    1. User Password

    2. System Password

  • 8/22/2019 Safie Commissioning

    13/31

    www.gst.uk.com

    BASIC CONFIGURATION

    GST SMOKE AND FLAME INTELLIGENT EYE

    SAFIE Commissioning Operation

    GENERAL

    On the Setup

    General

    to configure the basic

    system information

  • 8/22/2019 Safie Commissioning

    14/31

    www.gst.uk.com

    BASIC CONFIGURATION

    GST SMOKE AND FLAME INTELLIGENT EYE

    SAFIE Commissioning Operation

    GENERAL

    Video Channel

    Valid ticked to register and

    allow particular camera in the

    system

    Text box- allowed 40 characters

    for camera location details

  • 8/22/2019 Safie Commissioning

    15/31

    www.gst.uk.com

    BASIC CONFIGURATION

    GST SMOKE AND FLAME INTELLIGENT EYE

    SAFIE Commissioning Operation

    GENERAL

    Relay Output

    Valid ticked to enable the

    function of relay out put

    Text box- allowed 10 characters

    for relay details

    Read- to validate the changes in

    the relays details

    Okto confirm

  • 8/22/2019 Safie Commissioning

    16/31

    www.gst.uk.com

    BASIC CONFIGURATION

    GST SMOKE AND FLAME INTELLIGENT EYE

    SAFIE Commissioning Operation

    GENERALOther Options

    Video Switch Interval duration in second before the

    display switch to the next channel

    Auto Switch Waiting Timeduration in second before

    allowed 40 characters for camera location details

    Log Save Path the location of local disk you wish to save

    the history

    Log Save Time

    Setting the time in month for saving ahistory

    Log Save Number- to validate the changes in the relays

    details

    Okto confirm

  • 8/22/2019 Safie Commissioning

    17/31

    www.gst.uk.com

    BASIC CONFIGURATION

    GST SMOKE AND FLAME INTELLIGENT EYE

    SAFIE Commissioning Operation

    PARAMETER

    Under the Setup

    PARAMETERfor setting

    the parameters of each

    channel

  • 8/22/2019 Safie Commissioning

    18/31

    www.gst.uk.com

    BASIC CONFIGURATION

    GST SMOKE AND FLAME INTELLIGENT EYE

    SAFIE Commissioning Operation

    PARAMETER

    Current Channelselection of

    channels to be configured

  • 8/22/2019 Safie Commissioning

    19/31

    www.gst.uk.com

    BASIC CONFIGURATION

    GST SMOKE AND FLAME INTELLIGENT EYE

    SAFIE Commissioning Operation

    PARAMETER

    Parameterdetailed parameters setting of

    each channel such as signal algorithm, fire

    algorithm, sensitivity and programs

    Warning: changing the parameter will inhibitthe performance of the system

  • 8/22/2019 Safie Commissioning

    20/31

    www.gst.uk.com

    BASIC CONFIGURATION

    GST SMOKE AND FLAME INTELLIGENT EYE

    SAFIE Commissioning Operation

    PARAMETER

    A Grideach grid can set the sensitivity

    Note:

    To set sensitivitymouse left click

    To set the groupmouse right click

    Grid Definition assigning to the numbers of grid particular

    channel (a grid= a zone)

    4 x 3 = 12 zones

    8 x 6 = 48 zones

    12 x 9 = 108 zones16 x 12 = 192 zones

    20 x 15 = 300 zones

    Grid Sensitivityfor smoke or flame

    Sensitivity Levels: High, Normal, Low, Disabble

  • 8/22/2019 Safie Commissioning

    21/31

    www.gst.uk.com

    BASIC CONFIGURATION

    GST SMOKE AND FLAME INTELLIGENT EYE

    SAFIE Commissioning Operation

    PARAMETER

    Grid Groupgroup of zones and the maximum

    groups can be set up is 24

    Note:

    To set sensitivitymouse left click

    To set the groupmouse right click

  • 8/22/2019 Safie Commissioning

    22/31

    www.gst.uk.com

    BASIC CONFIGURATION

    GST SMOKE AND FLAME INTELLIGENT EYE

    SAFIE Commissioning Operation

    PARAMETER

    Relay Output Each group can be linked in one

    or more relays by ticking the box.

    Output Condition - is the cause and effect for

    each groupFor example: the group A0 has 9 zones, and set the output

    condition into 1 of 9, it means any zones goes into an alarm in

    group A0 will activate the relay of DO.1

    TESTto test the setting

    SAVE-To save the setting

    Okto confirm

  • 8/22/2019 Safie Commissioning

    23/31

    www.gst.uk.com GST SMOKE AND FLAME INTELLIGENT EYE

    SAFIE Commissioning Operation

  • 8/22/2019 Safie Commissioning

    24/31

    www.gst.uk.com

    BASIC OPERATION

    GST SMOKE AND FLAME INTELLIGENT EYE

    SAFIE Commissioning Operation

    1. System Silence

    2. Disable the Alarm

    3. Manual Operation of Relay Output

    4. History Log

    5. Basic Trouble Shooting

  • 8/22/2019 Safie Commissioning

    25/31

    www.gst.uk.com

    BASIC OPERATION

    GST SMOKE AND FLAME INTELLIGENT EYE

    SAFIE Commissioning Operation

    Channel StatusNormal Disable NotProgram

    FaultFire

    Alarm Indicator

    Operation

    MenuVisual Confirmation

  • 8/22/2019 Safie Commissioning

    26/31

    www.gst.uk.com

    BASIC CONFIGURATION

    GST SMOKE AND FLAME INTELLIGENT EYE

    SAFIE Commissioning Operation

    MUTE

    Mute Manual Start and Stop

    command of relay output.

    Note: by default, relay output 1 is set

    to sounder relay (latching), once the

    mute pressed it stop.

  • 8/22/2019 Safie Commissioning

    27/31

    www.gst.uk.com

    BASIC CONFIGURATION

    GST SMOKE AND FLAME INTELLIGENT EYE

    SAFIE Commissioning Operation

    DISABLE THE ALARM

    Disable to stop detecting fire

    even from the display video image

    Enable To resume the channel

    into operating mode

    Pink

    Pink

  • 8/22/2019 Safie Commissioning

    28/31

    www.gst.uk.com

    BASIC CONFIGURATION

    GST SMOKE AND FLAME INTELLIGENT EYE

    SAFIE Commissioning Operation

    MANUAL OPERATION OF RELAY OUTPUT

    Manual

    Manual Start and Stopcommand of relay output.

    Note: by default, relay output 1 is

    set to sounder relay (Latching) and

    relay 16 is set to fault relay.

  • 8/22/2019 Safie Commissioning

    29/31

    www.gst.uk.com

    BASIC CONFIGURATION

    GST SMOKE AND FLAME INTELLIGENT EYE

    SAFIE Commissioning Operation

    HISTORY LOG

    Log two types of history log:

    Image or Text

  • 8/22/2019 Safie Commissioning

    30/31

    www.gst.uk.com

    BASIC TROUBLESHOOTING

    GST SMOKE AND FLAME INTELLIGENT EYE

    SAFIE Commissioning Operation

    No. Fault indication Possible Cause Solution1 Access device failed The address of the relay output card is

    incorrect. See , go into the System Settingdialog and press the Read button.

    2 Relay Output Card Fault! The driver of the relay output card is notinstalled or incorrect. Reinstall/update the driver.

    3 Hardware key not found. The dongle is not connected or thedongle driver is installed incorrect. Check the parallel port connection ofthe PC or reinstall/update the dongle

    driver.

    4 The number of the video channels isreduced.

    The PCI slot is loose or the incorrect

    installation of the driver.Make sure the connection is good or

    reinstall/update the driver.5 Not enough virtual memory for video card,

    please reset it! The memory allocated for the card is toosmall. Go to the path:C:\windows\system32\, and executefile okdevman.exe, select the Buffer

    Allocator tag and input the size of the

    memory and restart the PC.

  • 8/22/2019 Safie Commissioning

    31/31

    t k

    ANSWER AND QUESTION

    GST SMOKE AND FLAME INTELLIGENT EYE

    SAFIE Commissioning Operation