safe operation and maintenance of circuit breakers and switchgear
DESCRIPTION
Switchgear plays an important role in electricity distribution and its performance significantly affects the overall performance of the system. Failure to efficiently disconnect faults elsewhere in the network or failure in switchgear itself is costly, resulting in additional loss of supply, damage to equipment and possibly fatal injury to personnel. It is therefore critically important that switchgear is operated and maintained correctly, within an overall asset management regime that is both economic and effective in securing a high level of system reliability. This comprehensive workshop focuses on medium voltage switchgear, which comprises by far the bulk of switchgear on most electricity distribution systems. The emphasis is primarily on oil, air blast, SF6 and vacuum circuit breakers, but other forms of MV switchgear, for example ring main units and auto-reclosers will also be described. MORE INFORMATION: http://www.idc-online.com/content/safe-operation-and-maintenance-circuit-breakers-and-switchgear-3TRANSCRIPT
Technology Training that WorksTechnology Training that Workswww.idc-online.com/slideshare
Safe Operation and Maintenance of Circuit Breakers and
Switchgear
Technology Training that WorksTechnology Training that Workswww.idc-online.com/slideshare
Topics
• Single line diagrams• Active and passive components• Circuit breaker utilization• Forms of medium voltage switchgear• Basic circuit breaker design• Auto re-closing
Technology Training that WorksTechnology Training that Workswww.idc-online.com/slideshare
Single line diagrams
•Typical example: high voltage distribution network
•Single line diagram
•Three phase nature of circuit is ignored
Technology Training that WorksTechnology Training that Workswww.idc-online.com/slideshare
Active and Passive Components
• ACTIVE components (continuously in use) = transformers, cables, overhead lines and metering equipment
• PASSIVE components (function only when required to) = switchgear including breakers, links, disconnects, earth switches
Technology Training that WorksTechnology Training that Workswww.idc-online.com/slideshare
Circuit Breaker Utilization
• In a perfect world we wouldn’t need switchgear!
• Do not install more switchgear than is absolutely required
• No more functionally than is necessary
Economics dictates:
Technology Training that WorksTechnology Training that Workswww.idc-online.com/slideshare
Circuit Breaker Utilization
• Two most common forms of medium voltage switchgear are automatic circuit breakers and non-automatic, load breaking, fault making switches.
• Main function of a circuit breaker is to
automatically interrupt fault current and to close onto a fault and thereby make fault current.
Technology Training that WorksTechnology Training that Workswww.idc-online.com/slideshare
Fuse switch in cross section
Note:
If used to feed a transformer all three phases must be disconnected (three phase disconnector) when a single phase trips
Technology Training that WorksTechnology Training that Workswww.idc-online.com/slideshare
Basic Circuit Breaker Design
• Primary purpose =
to interrupt fault current automatically
Technology Training that WorksTechnology Training that Workswww.idc-online.com/slideshare
Supplementary circuit breaker
• If time graded protection were used at XFaults after X will not affect loads between X and Y• However, Y must be set to trip in a longertime
Technology Training that WorksTechnology Training that Workswww.idc-online.com/slideshare
Local and distant faults
Fault at A
Waveform at switch
Technology Training that WorksTechnology Training that Workswww.idc-online.com/slideshare
Local and distant faults• Distant fault shown at A, circuit impedance, mainly resistance, acts
to limit the fault current and bring the power to a value close to unity.
• As the voltage and current are in phase, the voltage across the open contacts of the circuit breaker is low at the time of current zero, hence the probability of arc extinction is high.
Technology Training that WorksTechnology Training that Workswww.idc-online.com/slideshare
Local and distant faults contd..
Fault at B
Waveform at switch
Technology Training that WorksTechnology Training that Workswww.idc-online.com/slideshare
Local and distant faults
Close in Fault
• Fault at B – generator reactance limits If and causes pf to be low ~
0,15
• As the contacts open the current and voltage are almost 90 degrees out of phase
• therefore as the contacts open the voltage across the contacts is high at the time of current zero – probability of RE-STRIKING is increased
Technology Training that WorksTechnology Training that Workswww.idc-online.com/slideshare
Current Interruption
Therefore with all circuit breakers current interruption (and arc extinction) does not always occur on the first current zero crossing the following factors influence this:
• design of breaker
• magnitude of the fault current
• power factor
Several current cycles may occur before interruption is achieved
Technology Training that WorksTechnology Training that Workswww.idc-online.com/slideshare
Current Chopping
• Current chopping is the interruption of the current before or after the natural current zero crossing
• This can cause severe over-voltages on the system and damage due to over stressing of insulation levels
• This is an acute problem when loads are low as in:
• transformer magnetising currents
• capacitive line charging currents
Technology Training that WorksTechnology Training that Workswww.idc-online.com/slideshare
Variation of arc voltage with time
• During arcing the voltage across the open contacts is known as the arc voltage
• At the instant of current zero the voltage rises to the peak value of the re-striking transient voltage which oscillates at a frequency dependant on system resonant frequency
• This resonant voltage is dampened by the system impedances
Technology Training that WorksTechnology Training that Workswww.idc-online.com/slideshare
Effects of different clearance times on three-phase fault
• Blue phase clears first, other two phases still arcing
• The voltage across the first contacts to clear will be 50% greater than the peak line to neutral voltage
Technology Training that WorksTechnology Training that Workswww.idc-online.com/slideshare
RRRV
•Rate of Rise of Recovery Voltage greatly affects circuit breaker performance
• Some designs are particularly susceptible to re-striking voltage (Air Blast)
• In Air blast (axial blast designs) breakers resistors are switched in during the arc interruption process
Technology Training that WorksTechnology Training that Workswww.idc-online.com/slideshare
Auto Re-closing• Many of the faults that occur will be transient in
nature (over 90% of all faults are earth faults)
• These are caused by branches blowing across lines, insulators flashing over etc.
• Controlling circuit breaker (at R in next figure) to re-close automatically after a fault occurs
Technology Training that WorksTechnology Training that Workswww.idc-online.com/slideshare
Re-closed overhead line network
Using an Auto-recloser here improves the reliability of
supply
Technology Training that WorksTechnology Training that Workswww.idc-online.com/slideshare
Typical auto re-close sequence
Dead-time
Reclose Time delayed trip allows time for a
fuse to blow
Technology Training that WorksTechnology Training that Workswww.idc-online.com/slideshare
Successful implementation of auto reclosers
• Can be used on overhead lines only
• If cables and lines are combined – use breakers on cable sections
• Check grading with fuses on transformers and spurs to ensure successful reclosing operations
Technology Training that WorksTechnology Training that Workswww.idc-online.com/slideshare
Pole mounted auto-re-closer (at A)
Cabled network – no recloser
Recloser on overhead lines
Technology Training that WorksTechnology Training that Workswww.idc-online.com/slideshare
Pole mounted, oil filled re-closerOvercurrent coils
Technology Training that WorksTechnology Training that Workswww.idc-online.com/slideshare
Vacuum interrupter in SF6
auto-re-closer
• Maintenance is lower than oil filled
• Replacement of battery every 5 years
• Elastomeric bushings are more resistant to damage
• Control box normally situated at ground level
Technology Training that WorksTechnology Training that Workswww.idc-online.com/slideshare
DO YOU WANT TO KNOW MORE?
If you are interested in further training or information, please visit:
http://idc-online.com/slideshare