safe handling of ammonia & reporting leaks … · safe handling of ammonia & reporting...

20
MECHANICAL INTEGRITY Safe Handling of Ammonia & Reporting Leaks October 17, 2013 Andrew Keeley, Senior Project Professional

Upload: vonhan

Post on 28-Apr-2018

217 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Safe Handling of Ammonia & Reporting Leaks … · Safe Handling of Ammonia & Reporting Leaks October 17, 2013 ... Vessel U-1A Forms ... The Cal-OSHA PEL is 25 PPM while the OSHA PEL

MECHANICAL INTEGRITY

Safe Handling of Ammonia & Reporting Leaks

October 17, 2013

Andrew Keeley, Senior Project Professional

Page 2: Safe Handling of Ammonia & Reporting Leaks … · Safe Handling of Ammonia & Reporting Leaks October 17, 2013 ... Vessel U-1A Forms ... The Cal-OSHA PEL is 25 PPM while the OSHA PEL

Ammonia is used as a refrigerant at a large

number of industrial facilities. Industrial facilities

that typically use ammonia refrigeration systems

include:

Cold storage warehouses and ice plants,

Meat, poultry, or fish processing centers,

Dairy and ice cream plants,

Wineries and breweries,

Fruit/vegetable juice and soft drink processing

facilities,

Petrochemical facilities.

Page 3: Safe Handling of Ammonia & Reporting Leaks … · Safe Handling of Ammonia & Reporting Leaks October 17, 2013 ... Vessel U-1A Forms ... The Cal-OSHA PEL is 25 PPM while the OSHA PEL

Enhancing safety, on- and off-site; Improving system efficiency; Prolonging equipment life; Assuring regulatory compliance.

International Institute of Ammonia Refrigeration (IIAR) Recommendation, Bulletin 110

− Five Year Mechanical Integrity Inspection

− IIAR is developing a new bulletin to address the five year inspection

Industry Standards

− Manufacturer Recommendations

− Facility History

− OSHA & EPA Citations

AMMONIA REFRIGERATION

SYSTEM INTEGRITY

Page 4: Safe Handling of Ammonia & Reporting Leaks … · Safe Handling of Ammonia & Reporting Leaks October 17, 2013 ... Vessel U-1A Forms ... The Cal-OSHA PEL is 25 PPM while the OSHA PEL

Materials of Construction Piping Criteria: ANSI B31.5, Refrigeration Piping provides

clarification on schedule, grade, etc. for various sizes / applications.

Welding Specifications

Shop Drawings

Equipment Criteria, ANSI/IIAR 2-2008

– Evaporators

– Condensers

– Jacketed Tanks

– Compressors

Vessel U-1A Forms (National Board Information)

Manufacturer Specifications

– Valves / Gauges

– Regulators, Float Switches / Level Controls, etc.

Page 5: Safe Handling of Ammonia & Reporting Leaks … · Safe Handling of Ammonia & Reporting Leaks October 17, 2013 ... Vessel U-1A Forms ... The Cal-OSHA PEL is 25 PPM while the OSHA PEL
Page 6: Safe Handling of Ammonia & Reporting Leaks … · Safe Handling of Ammonia & Reporting Leaks October 17, 2013 ... Vessel U-1A Forms ... The Cal-OSHA PEL is 25 PPM while the OSHA PEL
Page 7: Safe Handling of Ammonia & Reporting Leaks … · Safe Handling of Ammonia & Reporting Leaks October 17, 2013 ... Vessel U-1A Forms ... The Cal-OSHA PEL is 25 PPM while the OSHA PEL
Page 8: Safe Handling of Ammonia & Reporting Leaks … · Safe Handling of Ammonia & Reporting Leaks October 17, 2013 ... Vessel U-1A Forms ... The Cal-OSHA PEL is 25 PPM while the OSHA PEL
Page 9: Safe Handling of Ammonia & Reporting Leaks … · Safe Handling of Ammonia & Reporting Leaks October 17, 2013 ... Vessel U-1A Forms ... The Cal-OSHA PEL is 25 PPM while the OSHA PEL

Install, Maintain, and Inspect Ammonia Detector

Systems

It is good practice to use ammonia detectors to

help monitor anhydrous ammonia systems for

leaks. Detectors are installed in areas where a leak

is likely to occur. The detectors could be monitored

by a local alarm company or linked into an

automated system that contacts offsite personnel.

Operation of ammonia sensors and alarms should

be checked and calibrated regularly to ensure the

alarms are set to alert personnel of a release.

Page 10: Safe Handling of Ammonia & Reporting Leaks … · Safe Handling of Ammonia & Reporting Leaks October 17, 2013 ... Vessel U-1A Forms ... The Cal-OSHA PEL is 25 PPM while the OSHA PEL

Emergency Ventilation Switches

Some facilities have installed manual switches to remotely activate ventilation fans. Others have their ammonia detectors activate the fans at a certain parts per million (ppm) level, and some facilities use continuous ventilation. It is recommended to have the remote switches located near, yet at a safe distance from, the compressor room. Post placards to explain their operation.

Page 11: Safe Handling of Ammonia & Reporting Leaks … · Safe Handling of Ammonia & Reporting Leaks October 17, 2013 ... Vessel U-1A Forms ... The Cal-OSHA PEL is 25 PPM while the OSHA PEL
Page 12: Safe Handling of Ammonia & Reporting Leaks … · Safe Handling of Ammonia & Reporting Leaks October 17, 2013 ... Vessel U-1A Forms ... The Cal-OSHA PEL is 25 PPM while the OSHA PEL

Why Is Anhydrous Ammonia So Dangerous?

Anhydrous ammonia is very corrosive, and

exposure to it may result in chemical -type burns to

skin, eyes, and lungs. It may also result in

frostbite, since its boiling point is -28°F.

Ammonia is hygroscopic, which means it has a high

affinity for water, and migrates to moist areas like

the eyes, nose, mouth, throat, and moist skin.

Page 13: Safe Handling of Ammonia & Reporting Leaks … · Safe Handling of Ammonia & Reporting Leaks October 17, 2013 ... Vessel U-1A Forms ... The Cal-OSHA PEL is 25 PPM while the OSHA PEL

PR Pressure/Temperature

Page 14: Safe Handling of Ammonia & Reporting Leaks … · Safe Handling of Ammonia & Reporting Leaks October 17, 2013 ... Vessel U-1A Forms ... The Cal-OSHA PEL is 25 PPM while the OSHA PEL

Released anhydrous

ammonia will rapidly

absorb moisture from air

and form a dense,

visible white cloud. This

dense cloud tends to

travel along the ground

on a cool day.

Do not enter a visible

cloud of ammonia. It will

damage your lungs.

Page 15: Safe Handling of Ammonia & Reporting Leaks … · Safe Handling of Ammonia & Reporting Leaks October 17, 2013 ... Vessel U-1A Forms ... The Cal-OSHA PEL is 25 PPM while the OSHA PEL

Escaping Ammonia

Page 16: Safe Handling of Ammonia & Reporting Leaks … · Safe Handling of Ammonia & Reporting Leaks October 17, 2013 ... Vessel U-1A Forms ... The Cal-OSHA PEL is 25 PPM while the OSHA PEL

First Alarm: SMELL 5 to 50 PPM

Second Alarm: Eye itch and respiratory tingling 150 to 750

PPM

Third Alarm: Eye injury, coughing, and gagging 750 to

2,500 PPM

Fourth Alarm: Skin burning 10,000 PPM

The Cal-OSHA PEL is 25 PPM while the OSHA PEL is 50

PPPM

Four Alarm NH3 Readiness

Page 17: Safe Handling of Ammonia & Reporting Leaks … · Safe Handling of Ammonia & Reporting Leaks October 17, 2013 ... Vessel U-1A Forms ... The Cal-OSHA PEL is 25 PPM while the OSHA PEL
Page 18: Safe Handling of Ammonia & Reporting Leaks … · Safe Handling of Ammonia & Reporting Leaks October 17, 2013 ... Vessel U-1A Forms ... The Cal-OSHA PEL is 25 PPM while the OSHA PEL
Page 19: Safe Handling of Ammonia & Reporting Leaks … · Safe Handling of Ammonia & Reporting Leaks October 17, 2013 ... Vessel U-1A Forms ... The Cal-OSHA PEL is 25 PPM while the OSHA PEL

An emergency action plan must be specific to the operations and layout of a facility and must be maintained and kept at the facility. Each emergency response plan is to include:

Procedures for informing the public and local emergency response agencies about accidental releases.

Documentation of proper first -aid and emergency medical treatment for accidental human exposure.

Procedures and measures for emergency action after an accidental release.

Emergency Action Plan

Page 20: Safe Handling of Ammonia & Reporting Leaks … · Safe Handling of Ammonia & Reporting Leaks October 17, 2013 ... Vessel U-1A Forms ... The Cal-OSHA PEL is 25 PPM while the OSHA PEL

For any release involving Ammonia

Contact 9-1-1

Local and State Environmental (OES & CUPA): Any

significant release. − Office of Emergency Services

− Certified Unified Program Agency

National Response Center: Reportable quantity

(RQ)100 lbs/18 gal released within a 24 -hour

period

Notification