sa engineering

35
Previous Issue: 19 January 2009 Next Planned Update: 19 January 2014 Revised paragraphs are indicated in the right margin Page 1 of 35 Primary contact: Mulhim, Khalid Abdul Aziz on 966-3-876-0211 Copyright©Saudi Aramco 2009. All rights reserved. Engineering Standard SAES-S-020 16 September 2009 Oily Water Drainage Systems Plumbing and Utilities Standards Committee Members Mulhim, Khalid Abdul Aziz, Chairman Hamid, Adel Sulaiman, Vice Chairman Churches, David Kenneth Cole, Anthony Richard Dbass, Saad Mohammed Evans, David George Fadley, Gary Lowell Magtanong, Enrique Lim Ugla, Ali Abdulaziz Salour, Sassan Sultan, Sultan Abdul Hadi Zahrani, Saleh Abdullah Saudi Aramco DeskTop Standards Table of Contents 1 Scope............................................................. 2 2 Conflicts and Deviations................................ 2 3 References..................................................... 3 4 Design............................................................ 5 5 Installation.................................................... 31

Upload: chris-echavari

Post on 10-Sep-2015

48 views

Category:

Documents


2 download

DESCRIPTION

sa engineering

TRANSCRIPT

  • Previous Issue: 19 January 2009 Next Planned Update: 19 January 2014 Revised paragraphs are indicated in the right margin Page 1 of 35 Primary contact: Mulhim, Khalid Abdul Aziz on 966-3-876-0211

    CopyrightSaudi Aramco 2009. All rights reserved.

    Engineering Standard SAES-S-020 16 September 2009 Oily Water Drainage Systems

    Plumbing and Utilities Standards Committee Members Mulhim, Khalid Abdul Aziz, Chairman Hamid, Adel Sulaiman, Vice Chairman Churches, David Kenneth Cole, Anthony Richard Dbass, Saad Mohammed Evans, David George Fadley, Gary Lowell Magtanong, Enrique Lim Ugla, Ali Abdulaziz Salour, Sassan Sultan, Sultan Abdul Hadi Zahrani, Saleh Abdullah

    Saudi Aramco DeskTop Standards Table of Contents 1 Scope............................................................. 2 2 Conflicts and Deviations................................ 2 3 References..................................................... 3 4 Design............................................................ 5 5 Installation.................................................... 31

  • Document Responsibility: Plumbing and Utilities SAES-S-020

    Issue Date: 16 September 2009

    Next Planned Update: 19 January 2014 Oily Water Drainage Systems

    Page 2 of 35

    1 Scope

    1.1 This Saudi Aramco Engineering Standard sets forth the minimum requirements

    for oily water drainage systems in the following Saudi Aramco onshore and

    offshore facilities.

    a) Areas involved in the processing or handling of hydrocarbons and their

    derivatives.

    b) Oil-filled transformer areas.

    1.2 This standard does not apply to sanitary sewer systems. Sanitary Sewers is

    specified in SAES-S-010.

    1.3 This standard does not cover the treatment of industrial drainage and sewerage,

    nor does it cover the use and disposal of oily waste sludge. These are specified

    in SAES-A-104.

    1.4 This standard does not cover industrial process equipment waste drainage

    systems and closed drain systems other than oily water as defined in section 4.1.

    For these systems refer to SAES-A-400.

    Exception:

    For building industrial drainage, other than oily water, such as acid waste and corrosive chemicals refer to SAES-S-060.

    Commentary Note:

    The newly proposed Industrial Drainage Standards Committee will develop the proposed standard SAES-A-400 tilted Industrial Drainage Systems. Expected issuance date of this subject standard is 2009. Until the subject standard is issued, any queries in regard to industrial drainage systems shall be forwarded to the following:

    o Manager, Process & Control Systems Department

    o Chairman, Industrial Drainage Standards Committee

    2 Conflicts and Deviations

    2.1 Any conflicts between this standard and other applicable Saudi Aramco

    Engineering Standards (SAESs), Materials System Specifications (SAMSSs),

    Standard Drawings (SASDs), or industry standards, codes, and forms shall be

    resolved in writing by the company or buyer representative through the

    Manager, Consulting Services Department of Saudi Aramco, Dhahran.

    2.2 Direct all requests to deviate from this standard in writing to the company or

    buyer representative, who shall follow internal company procedure SAEP-302

  • Document Responsibility: Plumbing and Utilities SAES-S-020

    Issue Date: 16 September 2009

    Next Planned Update: 19 January 2014 Oily Water Drainage Systems

    Page 3 of 35

    and forward such requests to the Manager, Consulting Services Department of

    Saudi Aramco, Dhahran.

    3 References

    The selection of material and equipment, and the design, construction, maintenance, and

    repair of equipment and facilities covered by this standard shall comply with the latest

    edition of the references listed below unless otherwise noted.

    3.1 Saudi Aramco References

    Saudi Aramco Engineering Procedures

    SAEP-20 Equipment Inspection Schedule

    SAEP-302 Instructions for Obtaining a Waiver of a

    Mandatory Saudi Aramco Engineering

    Requirement

    Saudi Aramco Engineering Standards

    SAES-A-100 Survey Coordinates and Datums

    SAES-A-102 Air Pollutant Emission Source Control

    SAES-A-103 Discharges to the Marine Environment

    SAES-A-104 Wastewater Treatment, Reuse and Disposal

    SAES-A-112 Meteorological and Seismic Design Data

    SAES-A-400 (under development) Industrial Drainage Systems

    SAES-A-401 (under development) Closed Drain Systems

    SAES-B-005 Spacing and Diking for Atmospheric and

    Low-Pressure Tanks

    SAES-B-006 Fireproofing for Plants

    SAES-B-009 Fire Protection and Safety Requirements for

    Offshore Production Facilities

    SAES-B-017 Fire Water System Design

    SAES-B-055 Plant Layout

    SAES-B-068 Electrical Area Classification

    SAES-B-070 Fire and Safety Requirements for Bulk Plants, Air

    Fueling and Sulfur Loading Facilities

    SAES-G-005 Centrifugal Pumps

  • Document Responsibility: Plumbing and Utilities SAES-S-020

    Issue Date: 16 September 2009

    Next Planned Update: 19 January 2014 Oily Water Drainage Systems

    Page 4 of 35

    SAES-H-002 Internal and External Coatings for Steel Pipelines

    and Piping

    SAES-H-003 Protective Coatings for Industrial Concrete

    Structures

    SAES-H-101 Approved Protective Coating Systems for

    Industrial Plants & Equipment

    SAES-J-300 Level

    SAES-L-100 Applicable Codes and Standards for Pressure

    Piping Systems

    SAES-L-105 Piping Materials Specifications

    SAES-L-132 Material Selection for Piping Systems

    SAES-L-350 Construction of Plant Piping

    SAES-L-610 Nonmetallic Piping

    SAES-P-100 Basic Power System Design Criteria

    SAES-Q-001 Criteria for Design and Construction of Concrete

    Structures

    SAES-Q-005 Concrete Foundations

    SAES-S-010 Sanitary Sewers

    SAES-S-030 Storm Water Drainage Systems

    SAES-S-060 Saudi Aramco Plumbing Code

    SAES-S-070 Installation of Utility Piping Systems

    SAES-X-600 Cathodic Protection of Plant Facilities

    Saudi Aramco Materials System Specifications

    01-SAMSS-034 RTR (Fiberglass) Pressure Pipe and Fittings

    09-SAMSS-106 Epoxy Coating of Steel Reinforcing Bars

    Saudi Aramco Standard Drawings

    AB-036013 Cast Iron Catch Basin for 8 inch Sewer

    Connection (for Refinery Use)

    AB-036054 Oily Water Sewer Manholes Miscellaneous Details

    AB-036402 Details Cast Iron Catch Basin with Side Inlets

    AC-036078 Details Cast Iron Catch Basin for 6 Inches Sewer

    Connection

  • Document Responsibility: Plumbing and Utilities SAES-S-020

    Issue Date: 16 September 2009

    Next Planned Update: 19 January 2014 Oily Water Drainage Systems

    Page 5 of 35

    AE-036038 Funnel with " to 2" Pipe Connections

    Saudi Aramco Engineering Report

    SAER-5248 Saudi Aramco Water Terminology

    General Instruction

    GI-0151.006 Implementing the Saudi Aramco Sanitary Code

    3.2 Industry Codes and Standards

    American Petroleum Institute

    API SPEC 5L Specification for Line Pipe

    American Society for Testing and Materials

    ASTM A53 Pipe, Steel, Black and Hot-Dipped Zinc-Coated

    (Galvanized) Welded and Seamless

    ASTM A74 Cast Iron Soil Pipe and Fittings

    ASTM A377 Ductile Iron Pressure Pipe

    ASTM A746 Ductile Iron Gravity Sewer Pipe

    ASTM D3350 Polyethylene Plastics Pipe and Fittings

    ASTM F714 Polyethylene Plastic Pipe, Based on Outside

    Diameter

    ASTM F1248 Environmental stress Crack Resistance of

    Polyethylene Pipe

    International Organization for Standardization

    ISO 2531 Ductile Iron Pipes, Fittings and Accessories for

    Pressure Pipelines

    National Fire Protection Association

    NFPA 30 Flammable Liquids Code

    NFPA 70 National Electric Code (NEC)

    4 Design

    4.1 Definitions

    Air Gap: An air gap is the unobstructed vertical distance through the free

    atmosphere from the lowest opening from any pipe, equipment, or appurtenance

    conveying waste to the flood level rim of the receptor. Air gap shall be a

  • Document Responsibility: Plumbing and Utilities SAES-S-020

    Issue Date: 16 September 2009

    Next Planned Update: 19 January 2014 Oily Water Drainage Systems

    Page 6 of 35

    minimum of 25 mm (1 inch) and shall not exceed 100 mm (4 inch).

    Catch Basin: A device with an integral sediment trap and outlet liquid seal for

    the collection of surface runoff and effluent (grate at top).

    Cleanout: A resealable port that allows for cleaning of piping within oily water

    drainage systems.

    Closed Drain System: As defined in SAES-A-401.

    Drain Pipe: An outlet pipe that collects product waste and effluents from

    points such as pump bases, drain points, vessel drains, or other equipment, and

    discharges those effluents through a sealed connection at a catch basin, or

    through a sealed connection at a manhole, into the oily water drainage system.

    Drainage: A drainage is a system of vessels and a piping network used to

    collect and transport effluents, such as oily water, spillage from hydrocarbon

    processing units, and rainwater runoff within a plot limit area, to a final disposal

    facility.

    Drainage Piping Network: A network of drainage piping consisting of

    sublaterals, laterals, submains, and mains.

    Dike: A low wall enclosing an area built to contain effluent.

    Effluent: Non-flammable liquid industrial waste, or accidental spillage, non-

    flammable process flow releases, cooling water, firewater, or storm water that

    enters and passes through an oily water drainage system.

    Force Main: A discharge pipe that is in full flow condition and that extends

    from a lift station carrying oily water drainage under pressure.

    Funnel: A fitting having a conical inlet and a narrow pipe outlet. Funnels are

    used to collect and channel the flow of oily water waste effluent from drain

    points to drain pipe.

    Invert: The lowest point of the internal surface of a oily water drainage pipe or

    open channel.

    Lateral: A branch of oily water drainage piping that collects effluent from two

    or more sublaterals, and discharges them into a submain, or main.

    Lift Station: A facility to pump effluent from a sump to a point of higher

    elevation.

    Main: The central branch for one or more oily water drainage piping networks.

  • Document Responsibility: Plumbing and Utilities SAES-S-020

    Issue Date: 16 September 2009

    Next Planned Update: 19 January 2014 Oily Water Drainage Systems

    Page 7 of 35

    Effluents from all of submains, within these piping networks, are emptied into

    the main through branch connections along its length of piping. A main may

    run through or around plot areas to an off-plot ponding area, disposal facility, or

    lift station.

    Manhole: A device on the drainage lines not designed for the collection of

    surface water (solid cover on top). It permits changes of direction, diameter and

    slope of oily water drainage; also provides access and maintenance to oily water

    drainage.

    Manned Platform: As defined in SAES-B-009.

    Off Plot: Any area outside of plot limits. Off plot can include plant areas such

    as roads, pipeways and open lots between plant units. Refer to SAES-L-100.

    Oily Water: Mixtures of non-flammable hydrocarbon residues and water. Oily

    water is considered to be contaminated water released during normal operation.

    Note: Due to unforeseen conditions and during uncontrollable accidental situations such as during fire or spill-containment, the oily water system may receive oil-contaminated wastewater with hydrocarbon flammables as well.

    Oily Water Drainage System: A system that removes surface runoffs and

    effluents from process areas within a plot limit to a disposal facility, or off-plot

    ponding area. It operates either by gravity or pumping force. This oily water

    drainage system consists of catch basins, manholes, and a network of drainage

    piping consisting of sublaterals, laterals, submains and mains.

    Open Channel: A continuous trench (gutter) that directs effluent to an

    impounding area.

    Plant: One or more plot areas. Refer to SAES-L-100.

    Plot: An individual process area made up of one or more risk area.

    See SAES-L-100 also.

    Potable Water: Refer to Chapter SASC-S-01 Water Section of Saudi Aramco Sanitary Code, GI-0151.006 and SAER-5248 titled Saudi Aramco Water Terminology or any other requirements set by Environmental Compliance Division of Environmental Protection Department.

    Risk Area: Refer to SAES-B-017 for onshore facilities and SAES-B-009 for

    offshore facilities.

    Sublateral: A sublateral is a branch of the oily water drainage piping network,

    which conveys effluent from a single catch basin to a run of piping called the

  • Document Responsibility: Plumbing and Utilities SAES-S-020

    Issue Date: 16 September 2009

    Next Planned Update: 19 January 2014 Oily Water Drainage Systems

    Page 8 of 35

    lateral branch of the oily water drainage piping system, or serves several drains

    that tie directly through a sealed connection at a manhole.

    Submain: A submain is a branch of an oily water drainage - piping network

    that connects sublateral and lateral branches of oily water drainage piping.

    Submains are subsequently connected to the main branch of oily water drainage

    piping network.

    Toe Wall: A raised curb that controls and directs effluent to a catch basin.

    Unmanned Platform: An unmanned platform is either a single or a continuous

    complex of offshore platforms, upon which operators are not present on a

    continuous basis.

    4.2 General Requirements

    4.2.1 All plot areas in hydrocarbon plants shall be equipped with an oily

    water drainage system for the safe removal of effluent, fire water and

    rain water from process areas.

    Exception:

    Where an oily water drainage system is neither justified nor desirable, a storm surface drainage system shall be provided. Approval to use a storm surface drainage system shall be obtained from the Chief Fire Prevention Engineer, Loss Prevention Department, Dhahran with the concurrence of the Proponent Department Manager. The design shall be in accordance with SAES-S-030 and Section 4.3 of this standard and with other details as specified by the Chairman of Civil Standards Committee, Consulting Services Department.

    4.2.2 New increments added to a facility that has only surface drainage shall

    incorporate an oily water drainage system in accordance with this

    standard, unless this facility complies with the exception stated in

    Paragraph 4.2.1 above.

    4.2.3 A closed drain system shall be provided where flammable liquids, as

    defined in SAES-B-005, are expected. The closed drain system is

    considered a pressure piping system and the design, construction and

    inspection shall be in accordance with SAES-L-100 and SAES-A-401.

    4.2.4 Any surface drainage flows, liquid industrial waste or spillage, or process

    flow releases from one risk area, shall not affect any other areas.

    4.2.5 Effluent shall not stand in open ponds, ditches, or trenches in plant

    areas. Solid matter carried with the effluent shall be trapped as close as

    possible to the source. The surface slope of trenches to catch basins or a

  • Document Responsibility: Plumbing and Utilities SAES-S-020

    Issue Date: 16 September 2009

    Next Planned Update: 19 January 2014 Oily Water Drainage Systems

    Page 9 of 35

    disposal point as agreed upon by Chief Fire Prevention Engineer or his

    designated representative shall be not less than 1:65 (1.5%).

    4.2.6 All oily water drainage and drain systems shall be identified on plant

    drawings in accordance with SAES-A-100, Survey Coordinates and Datum. Inverts and locations of seals, vents, and cleanouts shall be shown on the design drawings.

    4.2.7 Oily water drainage systems shall not be located in areas where access

    for modification or maintenance purpose is made difficult, such as

    under foundations, bases, or slabs.

    4.2.8 Oily water drainage piping at road crossings shall be installed in

    accordance with SAES-S-070.

    4.2.9 Oily water drainage piping shall not be located under buildings, except

    as may be permitted in Paragraph 4.8.10 of this standard.

    4.2.10 Corrosive chemicals shall not be discharged into an oily water drainage

    system without prior neutralization. Refer to SAES-S-060 for the

    handling and neutralization of acid wastes.

    4.2.11 No building sewer (sanitary) or building drains (sanitary) as defined in

    SAES-S-010 shall be connected to any part of an oily water drainage

    system. Refer to Paragraph 4.8.10 of this Standard for oily wastes from

    buildings.

    4.2.12 Effluent temperature shall not be higher than the temperature rating of

    the drainage piping.

    4.2.13 Branches of oily water drainage piping network, such as sublaterals,

    laterals, submains, and mains, shall be run in straight lines between their

    connections, except as permitted in Paragraph 4.2.14 of this standard.

    4.2.14 Lateral, sublateral, or submain piping in sizes up to 400 mm (16 inch) in

    nominal pipe diameter of gravity drainages shall not have more than

    two horizontal bends. No bend shall exceed 45 degrees without having

    a cleanout as per Section 4.11 of this standard.

    4.2.15 The layout of a drainage piping network shall be designed to minimize

    any disruptions, caused by maintenance and T & I (Testing and

    Inspection) operations, to any other area of the plant.

    4.2.16 An oily water drainage line shall be separated from a parallel potable

    water line by a minimum of 3 meters (10 feet).

  • Document Responsibility: Plumbing and Utilities SAES-S-020

    Issue Date: 16 September 2009

    Next Planned Update: 19 January 2014 Oily Water Drainage Systems

    Page 10 of 35

    4.2.17 An oily water drainage line crossing a potable water line shall be

    oriented such that the drainage line crosses under the potable water line

    with a minimum vertical surface clearance of 300 mm (12 inch).

    4.2.18 Any one of the following requirements must apply to drainage piping

    that, due to existing conditions must crossover a potable water line

    regardless of vertical separation; and must have less than 300 mm

    (12 inch) clear separation even though running beneath the potable

    water line.

    a) The oily water drainage piping crossing a potable water line shall

    be one continuous joint of pipe and both ends of the oily water

    drainage pipe shall be at least 3 meters (10 feet) beyond the point

    of crossing.

    b) If the oily water drainage piping is lined steel pipe it shall be joined

    together by full penetration butt-welds.

    c) The oily water drainage piping shall be encased in a concrete

    sheath for a minimum distance of 3 meters (10 feet) in both

    directions beyond the crossing point. The concrete sheath shall be

    at least 150 mm (6 inch) thick. Plastic pipes such as RTR

    (fiberglass) piping and fittings shall be wrapped with neoprene

    wrapping at the edges of concrete encasement. The wrapping must

    protrude slightly from the concrete encasement. The thickness and

    the width of wrap shall comply with Table 4 of SAES-S-070.

    d) The drainage line shall be encased in a sealed casing of either steel

    sleeve or RTR (fiberglass) pressure pipe per 01-SAMSS-034 for a

    minimum distance of 3 meters (10 feet), in both directions beyond

    the point of crossing. Steel sleeve shall be coated in accordance with

    SAES-H-002 for corrosion protection.

    4.2.19 All gravity flow drainage -piping networks shall be designed to be free-

    flowing and self-draining to ensure that no effluents remain in the

    piping during no-flow conditions.

    Exception:

    Effluent standing in a water seal and in a seal inlet pipe is permissible, provided that the overall intent of having all parts of the oily water drainage system be free-draining, is preserved.

    4.2.20 Catch basins and manholes shall be designed and located for ease of

    human and equipment access and cleanout.

    4.2.21 All effluents in an oily water drainage system shall enter the drainage -

  • Document Responsibility: Plumbing and Utilities SAES-S-020

    Issue Date: 16 September 2009

    Next Planned Update: 19 January 2014 Oily Water Drainage Systems

    Page 11 of 35

    piping network through a sealed catch basin, or as permitted in

    Paragraph 4.8.1 of this standard. All catch basins shall be equipped

    with a water seal that is a minimum of 150 mm (6 inch).

    4.2.22 Sanitary sewer systems shall not be combined with oily water drainage

    systems.

    4.2.23 Storm water runoffs from off-plot areas and uncontaminated water shall

    not be discharged into oily water drainage system.

    4.2.24 Electrical area classification for oily water drainage system shall be in

    accordance with the requirements of SAES-B-068.

    4.2.25 Electrical and electronic equipment and associated wiring in oily water

    drainage systems shall be suitable for the electrical area classification in

    accordance with SAES-P-100 and NFPA 70 National Electric Code.

    4.2.26 Drawings depicting oily water drainage system shall show risk areas

    approved by Loss Prevention Department.

    4.2.27 Oily water drainages shall be flushed with water to remove foreign

    matter before putting it into service.

    4.2.28 Metallic buried flanges, if used, shall be externally coated with

    APCS-113 per SAES-H-002.

    4.2.29 Sublaterals shall have a minimum nominal pipe diameter of 200 mm

    (8 inch).

    4.2.30 Effluents shall be contained within sealed and vented oily water

    drainage system to disposal facilities.

    4.2.31 All dimensions stated with in parenthesis are considered as reference

    only.

    4.2.32 Wherever economically feasible the designer shall strive to insure the

    oily water drainage system to flow due to gravity without making use of

    lift stations and their associated pumps.

    4.3 Surface Drainage

    4.3.1 All effluents shall be directed away from all buildings, substations, power

    poles, towers, access roads, diked or racked incoming and outgoing

    hydrocarbon lines, on-site pipeways, flares, and process equipment.

    4.3.2 Foundations supporting steel bases, including structural columns, pipe

  • Document Responsibility: Plumbing and Utilities SAES-S-020

    Issue Date: 16 September 2009

    Next Planned Update: 19 January 2014 Oily Water Drainage Systems

    Page 12 of 35

    supports, process equipment, vessels and towers shall be in accordance

    with SAES-Q-005.

    4.3.3 The ground level of the area surrounding a flare shall be graded to slope

    down and away from the flare and any associated equipment. The slope

    down shall not be less than one degree from horizontal grade.

    4.3.4 Surface drainage from unpaved areas shall not drain over paved areas.

    4.4 Flow Rates

    4.4.1 Each risk area oily water drainage - piping network shall be designed to

    handle the larger of the following design flow rates:

    a) Flow rate caused by the cumulative releases of hydrocarbon during

    normal operation or maintenance, plus maximum firewater flow

    from the risk area, as determined per SAES-B-017. Design shall

    prevent ponding during maximum firewater flow.

    b) Cumulative storm water flow, based on a 5-year return frequency

    per SAES-A-112, to prevent flooding of buildings or equipment

    that would disrupt operations or prevent a safe shutdown of the

    plant. Design may allow ponding during rainstorms as long as

    flooding of such building or equipment is prevented. Refer to

    SAES-S-030.

    4.4.2 Unless the flow rates determined under Paragraph 4.4.1 are larger, each

    branch of an oily water drainage network shall be capable of handling

    the following minimum flow rates:

    a) Sublaterals: 31.5 L/s (500 gpm) from each catch basin.

    b) Laterals: The cumulative flow from the catch basins served, but

    not less than 63 L/s (1000 gpm).

    c) Submains: The maximum flow produced by the calculated

    maximum allowable discharge of effluents in a risk area, but not

    less than 63 L/s (1000 gpm).

    d) Mains: The total flow produced as per Paragraph 4.4.1.b of this

    standard, but not less than the maximum firewater flow required by

    any single risk area.

    4.5 Line Sizing

    4.5.1 Gravity flow piping shall be sized to maintain a minimum flow velocity

    of 0.9 meters per second (3 feet per second) at the peak flow rate under

    full flow condition.

  • Document Responsibility: Plumbing and Utilities SAES-S-020

    Issue Date: 16 September 2009

    Next Planned Update: 19 January 2014 Oily Water Drainage Systems

    Page 13 of 35

    4.5.2 Forced main sizing shall be based on a minimum flow velocity of

    0.9 meter per second (3 fps), and a maximum velocity as listed in

    SAES-L-132 under Water Sea/Saline for different piping material.

    4.5.3 Pipe shall not reduce in size in the direction of flow.

    4.5.4 DWV (drain, waste and vent) type fittings shall be used in gravity flow

    system.

    4.5.5 90 degree sharp mitered fittings and short elbows are not permitted,

    except at funnels and as per approved designs at lift stations.

    4.6 Drainage Collection Areas

    4.6.1 The area served by a single catch basin shall not exceed 232 square

    meters (2500 square feet) within any plot location.

    4.6.2 The maximum surface travel of any liquid to a catch basin shall not be

    greater than 15 meters (50 feet).

    4.6.3 The surface slope to catch basins shall be not less than 1:65 (1.5%).

    Paving shall conform to SAES-Q-001; and maximum drop to catch

    basins from high point of paving shall be 200 mm (8 inch).

    Exception:

    This does not apply to:

    1. Offshore platforms covered in Section 4.15.

    2. Diked area covered in Section 4.13 of this standard.

    3. Surface grading within the diked areas of oil filled transformers shall be in accordance with NFPA 30.

    4.6.4 Catch basins, or other collection points in each drainage area shall not

    be located directly beneath any equipment. They shall be located such

    that the drainage path from a source of spillage does not pass beneath

    any other equipment or vessels containing hydrocarbons, pipeway, pipe

    rack, stairs or ladders.

    4.7 Toe Walls

    4.7.1 Toe walls shall be provided at hydrocarbon pump bases if the boiling

    point of the hydrocarbon exceeds 5C (41F) at atmospheric pressure

    and at oil-filled transformers, at furnaces burning liquid fuels, and at

    furnaces with flammable liquid in the tubes.

  • Document Responsibility: Plumbing and Utilities SAES-S-020

    Issue Date: 16 September 2009

    Next Planned Update: 19 January 2014 Oily Water Drainage Systems

    Page 14 of 35

    4.7.2 Surface area within toe walls shall be graded to direct effluent to the

    nearest catch basin, and to divert surface flow safely away from

    equipment.

    4.7.3 Toe walls are not designed to contain effluent.

    4.7.4 Toe walls shall have a minimum height of 150 mm (6 inch).

    4.8 Drain Pipes / Funnels

    4.8.1 Drain pipes, as defined in Paragraph 4.1 shall not be less than 100 mm

    (4 inch), it shall run to the nearest catch basin or manhole through a

    sealed connection at the catch basin or at the manhole.

    4.8.2 The horizontal distance between a drain opening and catch basin or

    manhole shall not exceed 15 meters (50 feet).

    4.8.3 All drain points shall have an air gap between point of discharge and the

    flood level rim of the receptors point of collection. Air gap shall be a minimum of 25 mm (1 inch) and shall not exceed 100 mm (4 inch).

    4.8.4 Funnels, collecting waste effluent, shall be visible from the drain valve

    and shall be of sufficient size to prevent overflow during maximum

    flow rates.

    4.8.5 The lip of a drain funnel shall be elevated 80 mm (3 inch) above the

    ground to prevent surface drainage from entering the drain.

    4.8.6 RTR (fiberglass) material may be used for drain funnel.

    4.8.7 Funnels, as shown in Saudi Aramco Standard Drawing AE-036038,

    may be used to collect effluents from equipment drain points, fluid

    sample collection points, drips from pumps, equipment, vessels and

    other such areas. RTR (fiberglass) funnels are acceptable.

    4.8.8 No more than six (6) funnels shall be allowed to collectively discharge

    effluents into a single catch basin, through side inlets of the catch basin

    per Saudi Aramco Standard Drawing AB-036402 or to a sealed

    manhole via a sealed connection.

    4.8.9 Funnels shall be located within 15 meters (50 feet) of sealed manholes

    or within the drainage area served by the catch basin.

    4.8.10 Drains from laboratory sinks, analyzer houses, or other facilities where

    oil releases are possible shall be connected:

    a) through a liquid trap seal connection to a vented manhole of the

  • Document Responsibility: Plumbing and Utilities SAES-S-020

    Issue Date: 16 September 2009

    Next Planned Update: 19 January 2014 Oily Water Drainage Systems

    Page 15 of 35

    oily water drainage system or

    b) to a vented holding tank. Holding tanks shall be provided with

    electronic or manual means of gauging contents.

    4.9 Catch Basins

    4.9.1 Catch basins shall be provided on plot areas for the collection of surface

    runoff and effluent.

    4.9.2 Catch basins shall be of the following types:

    a) Catch basins with beehive covers for unpaved areas.

    b) Cast iron catch basins per Saudi Aramco Standard Drawings

    AC-036078 and AB-036402 in nontraffic areas.

    c) Catch basins per Saudi Aramco Standard Drawing AB-036013 in

    traffic areas.

    d) Catch basins per Saudi Aramco Standard Drawing AB-036402

    may be used for collecting drain or sample wastes from

    equipment, and vessels (subsequent to thorough purging and

    flushing).

    e) Custom-designed catch basins shall be per the following

    requirements:

    i) It shall be provided with not less than a 150 mm (6 inch)

    liquid seal.

    ii) The bottom of the catch basin shall be not less than

    150 mm ( 6 inch) in depth below the bottom of the seal.

    iii) The catch basin outlet shall be accessible for cleaning.

    iv) Side inlets into the catch basin shall be provided with a

    minimum 150 mm (6 inch) seal.

    v) The catch basin structure and grating cover shall be able to

    withstand the maximum expected traffic loads.

    vi) Custom-designed catch basins shall have prior approval from

    the Chairman of Plumbing & Utilities Standards Committee.

    4.9.3 The number of catch basins provided in a plot area shall have a total

    outlet flow capacity equal to or greater than the maximum effluent flow.

    4.9.4 A standard catch basin shall be provided for each 31.5 L/s (500 gpm) of

    effluent flow within a plot area, or custom designed catch basins for

    effluent flows larger than 31.5 L/s (500 gpm).

  • Document Responsibility: Plumbing and Utilities SAES-S-020

    Issue Date: 16 September 2009

    Next Planned Update: 19 January 2014 Oily Water Drainage Systems

    Page 16 of 35

    4.9.5 Catch basins used for paved area drainage shall be installed flush with

    the low point of the finished surface.

    4.9.6 The flow from one catch basin shall not run into another catch basin.

    4.9.7 Connection of catch basin's outlet and inlet stubs with RTR (fiberglass)

    drainage piping shall be made in accordance with the RTR (fiberglass)

    piping manufacturer's recommendations. Metallic adapters, if used,

    shall be suitable for buried application.

    4.10 Manholes

    4.10.1 Sealed and vented manholes conforming to Saudi Aramco Standard

    Drawing AB-036054 shall be used for oily water drainage. Any other

    design of water seal in a manhole shall have prior approval from Chief

    Fire Prevention Engineer and the Chairman of Plumbing and Utilities

    Standards Committee.

    4.10.2 Manholes shall be sized to permit entrance for cleaning.

    4.10.3 Manholes are required at the following locations:

    a) At the junction of oily water drainage from different risk areas.

    Seal and vent shall be provided.

    b) At any change in horizontal direction whatsoever of any main,

    regardless of size; any sublateral, lateral, or submain larger than

    400 mm (16 inch) nominal pipe diameter. Here, liquid seal maybe

    eliminated however vent shall comply with section 4.12.

    c) At maximum intervals of 90 meters (300 feet) for any main,

    regardless of size; any sublateral, lateral, or submain larger than

    400 mm (16 inch) nominal pipe diameter. Here, liquid seal maybe

    eliminated however vent shall comply with section 4.12.

    d) At the junction of any drainages where the lesser drainage line is

    larger than 400 mm (16 inch) nominal pipe diameter. Liquid seal

    and vent shall be provided.

    e) At the dead ends of mains. Vent shall be provided.

    4.10.4 Invert of the outlet in a manhole shall be at least 25 mm (1 inch) lower

    than the invert of the lowest incoming drainage in the manhole.

    Whenever the total available fall is limited, the outlet may be raised until

    the invert is flush with the lowest inlet invert. Under no circumstances

    shall the outlet invert be higher than the lowest inlet invert.

  • Document Responsibility: Plumbing and Utilities SAES-S-020

    Issue Date: 16 September 2009

    Next Planned Update: 19 January 2014 Oily Water Drainage Systems

    Page 17 of 35

    4.10.5 Manholes shall be constructed of concrete. Concrete manhole shall be

    coated internally with APCS-3 epoxy and externally below grade with

    APCS-10 bituminous paint per SAES-H-101 or better. Exterior concrete

    surfaces above grade shall be coated with APCS-1B coating system per

    SAES-H-003. Before coating, concrete surfaces shall be sealed with a

    low molecular weight epoxy sealer. (Refer to SAES-A-104).

    4.10.6 Steel reinforcing bars in concrete shall be epoxy coated per

    09-SAMSS-106.

    4.11 Cleanouts

    4.11.1 Cleanouts shall be provided at following locations to facilitate

    inspection and cleaning of the oily water drainage piping.

    a) At the upper terminal of each run of piping of each section of the

    oily water drainage system.

    b) At 30 meters (100 feet) intervals or fraction thereof in a straight

    length of drainage piping network for oily water drainage 400 mm

    (16 inch) or less nominal pipe diameter.

    Commentary Note:

    Inside plot limits; cleanouts may be used in lieu of manholes, where seals, and vents may be omitted per Paragraph 4.10.3 and at a change of direction of 45 degree or smaller.

    c) Manholes may be used in lieu of cleanouts. In this case, the

    maximum distance between manholes shall not exceed 90 meters

    (300 feet).

    d) For each horizontal change of direction exceeding 45 degree for

    drainages 400 mm (16 inch) or less nominal pipe diameter.

    4.11.2 The total oily water drainage pipe length between the cleanout and the

    next manhole or a cleanout on the downstream shall not be more than

    30 meters (100 feet).

    4.11.3 Cleanouts shall be 100 mm (4 inch) for drainages 250 mm (10 inch) and

    smaller nominal pipe diameter, and 150 mm (6 inch) for larger drainages.

    4.11.4 Cleanouts shall be designed to be gastight and watertight without the

    use of any gasket, packing, or washer.

    4.11.5 Each cleanout shall be installed so that it opens to allow cleaning in the

    direction of flow of drainage, and shall be installed vertically above the

    flow line of the pipe.

  • Document Responsibility: Plumbing and Utilities SAES-S-020

    Issue Date: 16 September 2009

    Next Planned Update: 19 January 2014 Oily Water Drainage Systems

    Page 18 of 35

    4.11.6 Each cleanout shall be accessible and shall be extended to the grade

    level. Each 90-degree cleanout extension shall be extended from a wye

    type fitting or other approved fitting of equivalent sweep.

    4.12 Vents

    4.12.1 Vents shall be installed on the following locations in the oily water

    drainage system:

    a) All sealed manholes.

    b) All lift station. Vent connection shall be installed at the top of lift

    station.

    c) Those sections of the drainage line located between liquid seals.

    d) Upstream of the first sealed manhole in an oily water drainage

    system.

    e) Downstream of the farthest catch basin.

    4.12.2 Vents shall be 100 mm (4 inch) minimum nominal pipe diameter.

    4.12.3 Vents shall be properly supported at horizontal-to-vertical transitions.

    4.12.4 Vents shall be protected against mechanical accidental damage.

    4.12.5 Vent Termination

    4.12.5.1 Vents shall not be closer than 15 meters (50 feet) horizontally

    from a furnace or other source of ignition.

    4.12.5.2 Vents within 30 meters (100 feet) of a furnace or other source

    of ignition shall terminate at least 15 meters (50 feet) above

    grade. Refer to SAES-B-068 for Electrical Area

    Classification around vents.

    4.12.5.3 Vents shall terminate at least 3 meter (10 feet) above grade.

    4.12.5.4 Vents shall terminate at least 3 meters (10 feet) above any

    equipment handling hydrocarbons or their derivatives,

    piperacks, or any platforms.

    4.12.5.5 Terminating points of adjacent vents shall be separated by a

    horizontal distance of not less than 1.0 meter (3.3 feet), unless

    a prior approval is obtained from the Chief Fire Prevention

    Engineer or his designated representative.

  • Document Responsibility: Plumbing and Utilities SAES-S-020

    Issue Date: 16 September 2009

    Next Planned Update: 19 January 2014 Oily Water Drainage Systems

    Page 19 of 35

    4.12.6 Vents' openings shall not have any restrictions such as flame arrestors,

    goosenecks, birdscreens or raincaps.

    4.12.7 Vents from different risk areas shall not be combined.

    4.12.8 Vent piping installation details shall be in accordance with Standard

    Drawing # AB-036054.

    Commentary Note:

    The horizontal part of the vent pipe shall be sloped back to the lift station, manholes, etc.

    4.13 Tank Farm Areas

    4.13.1 A diked area, if provided as per SAES-B-005, shall have an oily water

    drainage system.

    4.13.2 Drainage from a tank water draw-off point shall have an air gap and

    shall pass through a drainpipe or concrete gutter to the required catch

    basin within the diked area. The catch basin outlet shall discharge into

    an oily water drainage system outside the diked area.

    Exception:

    Hard piped automated tank dewatering system may be used with prior approval by Chief Fire Prevention Engineer, Loss Prevention Department, Dhahran, and the Chairman of Plumbing and Utilities Standards Committee and concurrence by Proponent with following design details:

    A detailed drawing showing the arrangement for the automated tank dewatering system.

    A detailed P&ID and sequence of operation for the automated tank dewatering system. Note: Sequence should include but not limited to the following failure modes:

    o If the automated tank dewatering has a malfunction.

    o if the motorized valve on the hard-pipe draw-off has a malfunction.

    o HAZOP study shall be conducted to confirm use of automated tank dewatering system shall not have any impact on the plant safety.

    Commentary Note:

    The use of hard piped automated tank dewatering system is subject to the following conditions:

  • Document Responsibility: Plumbing and Utilities SAES-S-020

    Issue Date: 16 September 2009

    Next Planned Update: 19 January 2014 Oily Water Drainage Systems

    Page 20 of 35

    Drain valve shall be provided with a timer (manual open the drain valve and automatic closure on a specified time interval or oil detected in the water). Note: The timer setting shall be based upon size of tank, type of fluid and drain line size.

    25 mm (1 inch) sample drain valve located on the tank drain piping to a funnel within the tank diked area shall be provided. This basically meets the intent of the standard as it will allow an operator to visually confirm the quality of water being drained.

    Backflow prevention device shall be provided in order to insure no backflow through the system occurs.

    The automated drain valve shall be safe-close position type in the event of power loss.

    Provide bypass around automated tank dewatering installation.

    The hard-pipe drain network shall be sized for closed drainage system and not for gravity.

    Provide guard-rails around the automated tank dewatering and its associated probes to be protected from mechanical damage.

    If instrumentations/probes for automated tank dewatering requires penetration/protrusion on the outer tank wall then prior approval from the Chairman of Vessels Standards Committee shall be obtained.

    The automated tank dewatering shall be monitored and operated via Distributed Control System (DCS) operator interface/display in the control room.

    Provide long term maintainability of the system such as preventive maintenance, yearly calibration, etc.

    The power supply, instrumentation, etc., shall be explosion proof and suitable for the specific hazardous area.

    Note the above conditions are generic and may vary based on case by case and installation by installation basis.

    4.13.3 The outlet drain line from the catch basin within the diked area shall be

    valved outside the diked area. Use direct buried valve with position

    indicator.

    4.13.4 Direct buried valve location shall be reviewed and approved by Chief

    Fire Prevention Engineer, Loss Prevention Department, Dhahran.

    4.13.5 Surface grading within a diked area shall be in accordance with

    SAES-B-005.

  • Document Responsibility: Plumbing and Utilities SAES-S-020

    Issue Date: 16 September 2009

    Next Planned Update: 19 January 2014 Oily Water Drainage Systems

    Page 21 of 35

    4.13.6 Provide at least one catch basin per diked area.

    4.13.7 Lift stations installations are not allow inside the diked area.

    4.14 Lift Stations and Force Mains

    4.14.1 Lift stations shall be installed to meet the required flow velocities

    specified in Section 4.5 of this standard.

    4.14.2 The selection and installation of oily water lift station pumps shall be in

    accordance with SAES-A-104 and SAES-G-005 as applicable.

    4.14.3 Each lift station shall have two sets of pumps, one set to handle normal

    incoming flow, and the other set to handle the maximum incoming flow.

    Exceptions:

    1. This requirement is not applicable to the controlled drainage of diked areas. In this case, the lift station shall have at least one set of pumps to handle normal incoming flow.

    2. Lift stations, outside diked areas, for bulk plants and air fueling operations shall be sized to hold 32000 liters plus a maximum of five minutes of deluge flow as specified in SAES-B-070 as a minimum.

    3. Refer to Paragraph 4.14.6 of this Standard.

    4.14.4 The Pump set handling normal flow shall meet the following

    requirements:

    a) The Pump set shall consist of one pump or a group of pumps of

    equal operating capacity and one equal capacity standby pump.

    b) The total capacity of operating pumps shall be based on normal

    washdown, sampling, vessel drainage, etc.

    c) The pumps may have a common power source.

    4.14.5 The Pump set handling maximum flow shall meet the following

    requirements.

    a) The Pump set shall consist of one pump or a group of pumps of

    equal operating capacity and one equal capacity standby pump.

    b) The total capacity of operating pumps shall be based on the flows

    stated in Section 4.4 of this standard.

    Exception:

    Lift stations for bulk plants and air fueling operations shall have at

  • Document Responsibility: Plumbing and Utilities SAES-S-020

    Issue Date: 16 September 2009

    Next Planned Update: 19 January 2014 Oily Water Drainage Systems

    Page 22 of 35

    least one maximum flow pump, sized to handle the design basis of the foam system but in no case less than 63 L/s (1000 gpm).

    c) Two independent power sources, each with its own transformer,

    shall be supplied.

    d) The transformer shall be interconnected with an automatic transfer

    switch to provide a continuous source of power to the pumps motors.

    4.14.6 If the difference between normal and maximum flows is 10% or less, a

    single set of pumps sized for the maximum flow condition may be used.

    The power supply requirements of Paragraph 4.14.5 of this standard

    shall apply.

    4.14.7 The lift station operating volume shall be sized according to the

    following equation:

    V = CT(Q)/4 (1)

    Where: V = minimum required capacity m (gallons)

    CT = minimum time in minutes of one pumping cycle

    between successive motor starts. Minimum CT shall be

    15 minutes

    Q = maximum flow pump capacity, m/min (gallon/minute),

    or increment in pumping capacity when multiple

    operating pumps are used

    Reference: Wastewater Engineering-Collection & Pumping of Wastewater by Metcalf & Eddy, Inc.

    4.14.8 Lift Station Instrumentation, Monitoring and Control

    4.14.8.1 Lift Station Instrumentation

    4.14.8.1.1 The lift station shall be provided with not less

    than two radar level transmitters, in a redundant

    configuration, for level measurement and control

    of the normal and high flow pumps. The level

    transmitters can be either:

    a) Guided wave radar (GWR) or

    b) 4-wire non-contact radar transmitters.

    c) Ultrasonic level transmitters shall not be used

    per SAES-J-300.

  • Document Responsibility: Plumbing and Utilities SAES-S-020

    Issue Date: 16 September 2009

    Next Planned Update: 19 January 2014 Oily Water Drainage Systems

    Page 23 of 35

    4.14.8.1.2 Additional radar level transmitters may be

    included for pump control, if required by the

    specific lift station internal weir design.

    Commentary Note:

    Experience indicates that the best GWR level instrument installation practice is to use single Teflon coated flexible rope probes. The probe should be installed in a 80 mm (3 inch) slotted still well (unless the GWR vendor has field experience proving the well is not necessary). This design reduces the impact of water induced deposits that can foul other designs and the flexible rope probe allows easier shipping and installation. The end of the GWR rope probe can be fitted with a weight that will hold the probe in position.

    If non-contact radar is used, externally powered four-wire type is necessary (rather than loop powered two-wire) to provide adequate power for lift station depth and signal update rate.

    4.14.8.1.3 Each lift station normal and high flow pump shall

    be fitted with a dedicated flow transmitter. This

    flow transmitter shall be installed on the pump

    discharge piping, upstream of connection to

    common pump header piping. The flow

    transmitter shall be designed for this service.

    Commentary Note:

    A pressure transmitter may be used in lieu of a flow transmitter, if flow can be reliably inferred from the pump head.

    4.14.8.2 Lift Station Local Monitoring

    4.14.8.2.1 The lift station shall be supplied with a control

    panel mounted at least 3 meters (10 feet) away

    from the closest edge of the lift station.

    4.14.8.2.2 Each lift station level transmitter and pump flow

    transmitter shall have an analog local indicator

    mounted on the control panel.

  • Document Responsibility: Plumbing and Utilities SAES-S-020

    Issue Date: 16 September 2009

    Next Planned Update: 19 January 2014 Oily Water Drainage Systems

    Page 24 of 35

    4.14.8.2.3 Each pump shall be provided with a local hand-

    off-auto (HOA) switch and start pushbutton,

    mounted on the panel.

    Commentary Note:

    Since operating the pumps in manual mode increases the risk of pumps dry running, this switch should be locked or car-sealed in the auto mode, and should require written approval to move to hand (manual) mode.

    4.14.8.3 Lift Station Monitoring and Control in the Control Room

    4.14.8.3.1 A manual-selector switch or a low-signal selector

    shall be provided to select the level transmitter to

    be used for pump start-stop control. The low

    level pump trip shall be active regardless if the

    pump is in automatic or manual control.

    4.14.8.3.2 Each flow transmitter shall be configured to trip

    its associated pump on low flow. Low flow

    tripping shall be active regardless if the pump is

    in automatic or manual control.

    4.14.8.3.3 Each lift station level transmitter shall display its

    level indication on the control room Distributed

    Control System (DCS) operator interface/display.

    The display shall indicate which level transmitter

    is controlling the pump start/stop sequence and

    shall clearly indicate start and stop level setpoints

    for each pump.

    Commentary Note:

    The two lift station level transmitters shall be displayed side-by-side on the DCS operator interface/display, so the operator can compare them. In addition, the two levels shall be configured to alarm on deviation. The purpose is to allow the Operator to see both LTs trending together so he will have confidence in the level signal.

    4.14.8.3.4 Each pump flow transmitter shall display its flow

    indication and alarm/trip setpoints on the control

    room DCS operator interface/display.

  • Document Responsibility: Plumbing and Utilities SAES-S-020

    Issue Date: 16 September 2009

    Next Planned Update: 19 January 2014 Oily Water Drainage Systems

    Page 25 of 35

    4.14.8.3.5 Each pump shall display its running and stopped

    indicator on the control room DCS interface /

    display.

    4.14.8.3.6 Each pump hand-off-auto (HOA) position switch

    shall display its position on the control room

    DCS operator interface/display. An alarm shall

    be configured when this switch is placed in the

    hand position.

    4.14.8.4 Lift Station Pump Level Sequencing

    4.14.8.4.1 The following lift station level setpoints shall be

    configured for starting and stopping pumps set to

    handle normal incoming flow, and the other

    pumps set to handle the maximum incoming flow:

    a) Low Level: All pumps off.

    b) First Level: Primary normal flow pump

    on (if primary pump does not

    start, standby normal flow

    pump shall start).

    c) Second Level: Actuate high level alarm in

    DCS operator interface /

    display.

    d) Third Level: Primary high flow pump on

    and primary normal flow

    pump off (if primary high

    flow pump does not start,

    standby high flow pump shall

    start).

    e) Fourth Level: Actuate high high level alarm

    at DCS operator interface /

    display.

    4.14.8.4.2 Each pump shall trip on low level/no water, or on

    low flow, when in either automatic or manual

    mode.

    4.14.8.4.3 The start and stop level settings for the normal

    flow pumps shall allow for five minutes

    minimum run time.

  • Document Responsibility: Plumbing and Utilities SAES-S-020

    Issue Date: 16 September 2009

    Next Planned Update: 19 January 2014 Oily Water Drainage Systems

    Page 26 of 35

    4.14.8.4.4 If the primary pump fails to start when requested,

    an alarm shall be annunciated and the standby

    secondary pump shall be started. If the standby

    secondary pump fails to start when requested, an

    alarm shall be annunciated and additional standby

    tertiary pumps will start if available/applicable.

    4.14.8.5 Lift Station Instrument and Control Documentation

    Logic drawings and sequence of operation drawings,

    including narratives, shall be prepared for each lift station.

    These documents shall include descriptions of all control

    requirements, equipment specifications, and operating

    setpoints for lift station controls, and shall be provided in

    addition to normally required conventional instrumentation

    and control documentation.

    4.14.9 Incoming oily water drainage lines shall remain dry when not in use. The

    maximum liquid level in the lift station shall not impede incoming flow.

    Exception:

    Effluent standing in a water seal and in a seal inlet pipe, is permissible provided that the overall intent of having all parts of the drainage system be free-draining, is preserved.

    4.14.10 The incoming drainage to a lift station shall be provided with a water

    seal similar to that provided on sealed manholes per Section 4.10.1.

    4.14.11 The outlet of incoming drainage shall terminate not less than 150 mm

    (6 inch) below the pump shut-off liquid level.

    4.14.12 The lift station shall be of airtight construction and shall be provided

    with a vent per Section 4.12 of this standard.

    4.14.13 Pumps shall be specifically designed for pumping sewage. Pumps

    shall be non-clog type and shall comply with SAES-G-005.

    4.14.14 Lift station pumps with suction lifts are prohibited.

    Exception:

    Self priming pumps as per SAES-G-005 are acceptable.

    4.14.15 The pumps shall be spaced to prevent vortexing cavitations when the

    pumps are operating.

  • Document Responsibility: Plumbing and Utilities SAES-S-020

    Issue Date: 16 September 2009

    Next Planned Update: 19 January 2014 Oily Water Drainage Systems

    Page 27 of 35

    4.14.16 The pumps shall be removable without disturbing the discharge piping.

    4.14.17 Interior of concrete lift station shall be painted in accordance with

    SAES-H-101, APCS-3.

    4.14.18 Exterior concrete surfaces exposed to ground water shall be protected

    with a 3-coat mastic, 2-layer felt or a 2-coat mastic and polyethylene

    coating.

    4.14.19 Force Main

    4.14.19.1 Force mains in plants shall be installed above ground.

    Exception:

    Force mains made of non-metallic materials such as RTR (fiberglass) can be installed underground.

    4.14.19.2 Burial of force mains outside plant areas is allowed.

    4.14.19.3 Force mains shall be provided with cleanout entries at not

    more than 30 meters (100 feet) intervals.

    4.14.19.4 All force main connections to a gravity drainage system

    shall be through a sealed connection at a vented manhole.

    4.14.19.5 Force main shall be a minimum of 100 mm (4 inch) in

    diameter.

    4.14.19.6 Thrust blocks shall be provided for underground force

    mains in accordance with SAES-S-070.

    4.14.20 Pumps on lift stations shall comply with electrical area classification

    requirements per SAES-B-068.

    4.14.21 Pipe supports shall comply with the fireproofing requirements stated in

    SAES-B-006.

    4.14.22 All lift station shall have facilities for bypassing the sump and pumps.

    4.14.23 Pump lift station head shall not exceed 6 meters (20 feet).

    Exception:

    In case the available area for the proposed lift station stated is restricted the pump lift station head may exceed 6 meters (20 feet) requires prior approval by Chairman of Plumbing & Utilities Standards Committee, Consulting Services Department and the Chief Fire Prevention Engineer, Loss Prevention Department, Dhahran.

  • Document Responsibility: Plumbing and Utilities SAES-S-020

    Issue Date: 16 September 2009

    Next Planned Update: 19 January 2014 Oily Water Drainage Systems

    Page 28 of 35

    4.14.24 Equipment Inspection Schedule (EIS) shall be established for lift

    station per SAEP-20.

    4.15 Offshore Platforms

    4.15.1 The following requirements shall apply to both manned and unmanned

    platforms:

    a) All offshore plate deck platforms handling hydrocarbons shall

    have a gravity oily water drainage system for the safe removal of

    spills, storm water, and fire water. The system shall be designed

    using the same minimum requirements as stated in this standard

    for onshore systems.

    b) A helideck with fueling facilities is a hydrocarbon-handling deck.

    c) Deck edge drainage troughs with toe walls shall be installed in

    accordance with SAES-B-009.

    d) The top of the toe wall shall be 150 mm (6 inch) above the deck

    level, and shall be located along the outer edge of the drainage

    trough.

    e) Handrails along the inboard side of the deck edge trough shall not

    have kick plates.

    f) Each deck penetration shall be surrounded by sleeve that shall

    extend a minimum of 150 mm (6 inch) above the deck level, and

    which shall provide the amount of clearance necessary to allow

    free movement between the sleeve and piping, conduit, cable, or

    equipment in the penetration.

    g) Each plate deck handling hydrocarbons shall constitute at least

    one surface drainage collection area.

    h) The maximum plate deck and trough travel distance of any liquid

    as well as the subdivision of plate deck areas shall be in

    accordance with SAES-B-009.

    i) The plate deck shall have a slope of not less than 1:100 (1%) to a

    trough.

    j) In-deck troughs shall not be more than 300 mm (12 inch) wide

    and shall be covered with grating.

    k) All troughs shall have a minimum pitch of 1:65 (1.5%).

    l) A baffle plate shall be installed at the high point of each trough

    section.

  • Document Responsibility: Plumbing and Utilities SAES-S-020

    Issue Date: 16 September 2009

    Next Planned Update: 19 January 2014 Oily Water Drainage Systems

    Page 29 of 35

    m) Area and equipment drainage shall include sublaterals and

    laterals tying into a submain.

    n) Submains from each deck shall be connected via a sealed a

    minimum of 150 mm (6 inch) and vented drain box (which has

    the same function as an onshore manhole) to a common main or

    riser discharging to the slop tank, or caisson.

    o) Cleanouts shall be provided per Section 4.11 of this standard.

    p) All lines discharging into a slop tank, or caisson shall terminate a

    minimum of 150 mm (6 inch) below the lowest possible slop

    tank liquid level, or caisson liquid level.

    q) Each slop tank, or caisson shall be vented. Vents of slop tanks,

    or slop caissons shall be routed free of pockets and shall

    terminate as specified in SAES-B-009.

    r) Vents shall be provided per Section 4.12 of this standard.

    s) Vents protecting liquid seals shall terminate at least 3 meters

    (10 feet) above the highest process pipe, process equipment, or

    platform on the uppermost deck within 7.6 meters (25 feet)

    horizontally.

    t) All types of flows, such as surface runoff and effluent that flow

    into the gravity oily water drainage system shall be through

    sealed catch basins, or sealed and vented drain box including

    entries from drainage troughs.

    u) Catch basins for drain troughs shall be incorporated into the drain

    trough, or bolted directly onto the bottom of the drain trough.

    v) Catch basins shall be accessible for cleaning from the deck

    containing the drain trough.

    w) Catch basins shall meet the requirements of Section 4.9 of this

    standard.

    x) A minimum liquid seal height of 150 mm (6 inch) shall be

    provided in all individual drains prior to their entering sublaterals

    or laterals.

    4.15.2 The following requirements shall apply only to manned platforms:

    a) Oily water drainage system from each platform deck shall be

    vented.

    b) Vents shall be located immediately before the last catch basin in

    a deck drainage system.

  • Document Responsibility: Plumbing and Utilities SAES-S-020

    Issue Date: 16 September 2009

    Next Planned Update: 19 January 2014 Oily Water Drainage Systems

    Page 30 of 35

    c) The maximum anticipated volume of firewater may require two

    slop tanks or two caissons. This shall be determined via

    calculations and reviewed by Loss Prevention Department.

    d) Where two tanks or caissons are provided, there shall be two

    drainage systems per deck, each with a dedicated sublateral,

    lateral, and submain system to the respective slop tank or caisson.

    e) Slop tanks or caissons shall be part of the gravity oily water

    drainage system, and shall not be used as part of the closed drain

    system.

    f) Slop tanks or caissons shall be provided with normal flow pumps

    for pumping recovered oil to the Production Trap or another safe

    location. Refer to Paragraph 4.14.4 of this standard for normal

    flow pump requirements.

    g) Sizing of slop tank or caisson shall be based upon maximum fire

    water demand. Discharge into the sea shall be by an overflow or

    maximum flow pumps. The use of an overflow is preferred.

    Refer to Paragraph 4.14.5 of this standard for maximum flow

    pump requirements.

    h) The overflow pipe shall be sized to handle the volume of water

    without affecting any incoming oily water drainage. It shall have

    a submerged inlet of sufficient depth to prevent the spillage of oil

    within the tank or caisson.

    i) If maximum flow pumps are required, the slop tank or caisson

    and the pumps shall be designed as set forth in Paragraph 4.14.7

    of this standard.

    4.15.3 The following specific requirements shall apply only to unmanned

    platforms:

    a) A separate drainage system shall be provided for each risk area,

    which shall independently discharge through an inlet into the

    required slop tank or caisson. The capacity of each drainage

    system shall be designed to ensure that anticipated spills will not

    overflow the toe walls.

    b) Sealed catch basins as inlets to each drainage system are not

    required.

    c) Any pressure blowdown may be directed to the slop tank or

    caisson.

  • Document Responsibility: Plumbing and Utilities SAES-S-020

    Issue Date: 16 September 2009

    Next Planned Update: 19 January 2014 Oily Water Drainage Systems

    Page 31 of 35

    d) The slop tank or caisson shall be provided with a single pump for

    pumping recovered oil to a safe location downstream of the

    isolation valve on the main outlet header of the platform.

    f) The slop tank or caisson pump shall be sized as a normal flow

    pump as set forth in Paragraph 4.14.4 of this standard.

    d) All lines discharging into a slop tank shall terminate a minimum of

    150 mm (6 inch) below the lowest possible slop tank liquid level.

    4.16 Treatment and Disposal of Effluent

    4.16.1 The treatment of oily wastewater shall be in accordance per SAES-A-104.

    4.16.2 Where economically practical, oil, other hydrocarbons, or chemicals

    shall be recovered from the effluent and returned to process streams.

    4.16.3 The disposal of either treated or untreated effluent shall comply with

    Saudi Aramco and governmental environmental standards. Refer to

    SAES-A-102, SAES-A-103, SAES-A-104, and SAES-B-055.

    5 Installation

    5.1 Materials

    General: Drainage fittings shall have a smooth interior waterway of the same

    diameter as the piping served and all such fittings shall be compatible with the

    type of pipe used. All fittings shall be DWV (drainage, waste and vent) type,

    such as 45 Ys, long 90 elbows, sixth, eighth and sixteenth bends, and

    combinations of such fittings.

    5.1.1 Following are the acceptable materials for gravity oily water drainage

    piping:

    5.1.1.1 New Piping

    a) Cement Lined Steel Pipe

    12LC0U per SAES-L-105, steel pipe, ASTM A53, or

    API SPEC 5L Grade B, Standard Weight, cement lined

    and externally coated in accordance with SAES-H-002.

    b) Cast Iron Soil Pipe & Fittings

    80DC0D per SAES-L-105, cast iron soil pipe and

    fittings, ASTM A74, service (SV) weight.

    c) RTR (fiberglass) Pipe & Fittings

  • Document Responsibility: Plumbing and Utilities SAES-S-020

    Issue Date: 16 September 2009

    Next Planned Update: 19 January 2014 Oily Water Drainage Systems

    Page 32 of 35

    12FE0U per SAES-L-105, 01-SAMSS-034 RTR

    (fiberglass) pipe and fittings with restrained joints.

    Such pipe shall be used only below ground.

    Temperature ratings and chemical resistance of pipe,

    fittings and jointing compounds shall be compatible

    with the effluent.

    d) Cement Lined Ductile Iron Pipe

    Ductile iron pipe, ASTM A746, cement lined and

    externally coated in accordance with SAES-H-002.

    5.1.1.2 Repair Piping Section

    High Density Polyethylene (HDPE) pipe liner, per

    ASTM D3350, ASTM F1248, and ASTM F714 - for

    sliplining of existing oily water drainage pipes only.

    Temperature ratings and chemical resistance of the liner

    shall be compatible with the effluent.

    5.1.2 Following are the acceptable materials for force main piping:

    5.1.2.1 New Piping

    a) Cement Lined Steel Pipe

    12LC0U per SAES-L-105, steel pipe, ASTM A53, or

    API SPEC 5L Grade B, Standard Weight or heavier as

    required by the system pressure, cement lined, above or

    below ground. All buried piping shall be externally

    coated as per SAES-H-002 and piping up to and

    including 150 mm (6 inch) above the finished surface.

    b) Fusion Bonded Epoxy (FBE) Lined Carbon Steel Pipe

    12LE0U per SAES-L-105, steel pipe, ASTM A53, or

    API SPEC 5L Grade B, Standard Weight or heavier as

    required by the system pressure, fusion bonded epoxy

    (FBE) internally coated per SAES-H-002, above or

    below ground. All buried piping shall be externally

    coated as per SAES-H-002 and piping up to and

    including 150 mm (6 inch) above the finished surface.

    c) RTR (fiberglass) Pipe & Fittings

    12FE0U per SAES-L-105, 01-SAMSS-034 RTR

    (fiberglass) pipe and fittings with restrained joints. Such

  • Document Responsibility: Plumbing and Utilities SAES-S-020

    Issue Date: 16 September 2009

    Next Planned Update: 19 January 2014 Oily Water Drainage Systems

    Page 33 of 35

    pipe shall be used only below ground. Temperature

    ratings and chemical resistance of pipe, fittings and

    jointing compounds shall be compatible with the effluent.

    d) Cement Lined Ductile Iron Pipe

    Ductile iron pipe, ASTM A377, or ISO 2531, cement

    lined and externally coated in accordance with

    SAES-H-002. Flanged joints shall be used above

    ground.

    5.1.2.2 Repair Piping Section

    High Density Polyethylene (HDPE) pipe liner, per

    ASTM D3350, ASTM F1248, and ASTM F714 - for slip

    lining of existing oily water drainage pipes only.

    Temperature ratings and chemical resistance of the liner

    shall be compatible with the effluent.

    5.1.3 Following are the acceptable materials for vent piping:

    a) Galvanized Steel Pipe

    80CG0D1 per SAES-L-105, Steel pipe, ASTM A53, galvanized,

    above and below ground. All belowground piping and piping not

    less than 150 mm (6 inch) above the finished surface shall be

    coated externally in accordance with SAES-H-002.

    b) Cast Iron Soil Pipe & with a Steel Pipe Riser

    80DC0D per SAES-L-105, cast iron soil pipe, ASTM A74,

    service (SV) weight below ground with a steel pipe riser,

    80CG0D1 steel pipe, ASTM A53 galvanized, above and below

    ground. All buried steel piping and piping up to and including

    150 mm (6 inch) above the finished surface shall be externally

    coated in accordance with SAES-H-002.

    c) RTR (fiberglass) Pipe & Fittings & with a Steel Pipe Riser

    12FE0U per SAES-L-105, 01-SAMSS-034 RTR (fiberglass) pipe

    and fittings with restrained joints below ground with a steel pipe

    riser, 80CG0D1 steel pipe, ASTM A53, galvanized, above and

    below ground.

    The connection between RTR (fiberglass) pipe and steel pipe

    shall be in accordance with SAES-L-610; and shall be a flanged

  • Document Responsibility: Plumbing and Utilities SAES-S-020

    Issue Date: 16 September 2009

    Next Planned Update: 19 January 2014 Oily Water Drainage Systems

    Page 34 of 35

    connection. It shall be installed in such a way that the weight of

    steel piping shall not be transferred to RTR (fiberglass) piping.

    All buried steel piping and piping up to and including 150 mm

    (6 inch) above the finished surface shall be externally coated in

    accordance with SAES-H-002.

    5.2 Installation

    5.2.1 Oily water drainage shall be installed in accordance with the following

    standards:

    a) Steel pipe shall be installed in accordance with SAES-L-350.

    In addition, refer to SAES-X-600 to determine if cathodic

    protection is necessary.

    b) Ductile iron pipe, cast iron soil pipe, and 01-SAMSS-034

    RTR (fiberglass) pipe shall be installed in accordance with

    SAES-S-070.

    5.2.2 Manufacturer's installation instructions shall be followed for the

    installation of all equipment that falls under the scope of this standard.

    5.3 Testing, Inspection and Backfilling

    5.3.1 Oily water drainage system shall be tested for water tightness in

    accordance with SAES-S-070, unless otherwise stated below.

    5.3.1.1 Vents shall be hydrostatically tested by filling the vent pipe

    from its connection to the oily water drainage system to the

    top of the pipe. The vent shall be proven watertight for a

    period of not less than 4 hours.

    Exception:

    If hydrotesting of above ground metallic vent pipe is deemed impractical, then it could be substituted with 10% radiography; and all welds shall be 100% visually inspected. However a prior approval of the Chief Fire Prevention Engineer is required.

    5.3.1.2 Drain lines shall be tested from the funnel or catch basin to

    the connection with a catch basin or manhole by filling the

    line with water to the top of the funnel or catch basin. Drains

    that have not been backfilled shall be watertight for a period

    of not less than 4 hours. Drains that have been backfilled

    shall be watertight for a period of not less than 24 hours.

  • Document Responsibility: Plumbing and Utilities SAES-S-020

    Issue Date: 16 September 2009

    Next Planned Update: 19 January 2014 Oily Water Drainage Systems

    Page 35 of 35

    5.3.1.3 Gravity oily water drainage systems shall be tested from the

    catch basin to the first manhole connection and from

    manhole to manhole, by filling the line to the top of the catch

    basin, or the upper manhole. Drainages that have not been

    backfilled shall be watertight for a period of not less than 4

    hours. Drainages that have been backfilled shall be

    watertight for a period of not less than 24 hours.

    5.3.1.4 Force mains shall be hydrostatically tested at a minimum of

    1034 kPa (150 psig) or 345 kPa (50 psig) above the pump

    shut-off head, whichever is greater. Aboveground force

    mains shall be watertight for a period of not less than 4 hours.

    Exception:

    If hydrotesting of above ground metallic force main piping is deemed impractical, then it could be substituted with 100% radiography. However a prior approval of the Chief Fire Prevention Engineer is required.

    5.3.1.5 Prefabricated catch basins and manholes may be hydrotested at

    the manufacturing site as standard quality control procedures,

    prior to shipment to the location specified on the purchase order

    form. Such catch basins and manholes are exempted from the

    site hydrotest requirements. However, the joints and piping

    thereafter shall be hydrotested as per Section 5.3.

    5.3.2 Oily water drainage systems shall be inspected, repaired and backfilled

    in accordance with SAES-S-070.

    Revision Summary

    19 January 2009 Major revision. 16 September 2009 Editorial revision.