IntroductionProSafe-RS has a feature for integration with a CENTUM system, which allows access to ProSafe-RS SCS from the HIS and FCS of the CENTUM VP or CS 3000 (hereafter, referred to as “CENTUM”) system through control bus.This manual describes how to integrate ProSafe-RS and a CENTUM system. It is important to fully understand the contents in this manual for the engineering or maintenance works. There may be some differences in the behavior on the CENTUM side, depending on the software release number of the CENTUM to which ProSafe-RS is connected. See Appendix for the differences in behavior between different CENTUM software release numbers.For details of engineering CENTUM VP, see user’s manuals for CENTUM VP. For details of engineering CENTUM CS 3000, see user’s manuals for CENTUM CS 3000.This manual consists of the following chapters:
• Chapter 1 This chapter explains the overview of integration of CENTUM and ProSafe-RS.
• Chapter 2 This chapter explains the engineering works regarding the integration of CENTUM and ProSafe-RS
• Chapter 3 This chapter explains how to operate and monitor the ProSafe-RS using HIS.
3rd Edition : Dec.22,2009-00Media No. IM 32S01E10-21E (CD) 3rd Edition : Dec. 2009 (YK)All Rights Reserved Copyright © 2008, Yokogawa Electric Corporation
ii
IM 32S01E10-21E
ProSafe-RS Document Map
EngineeringGuide
Utilities andMaintenance
Reference
EngineeringReference
Manual
Software Help
Read Me First
Safety ControlStations
(Hardware)
Installation
ProSafe-RSSystem Test
Reference
Safety Control StationReference
Integration withCENTUM VP/CS 3000
CommunicationDevices
Open Interfaces
IM 32S01C10-21E
IM 32S01C50-21E
IM 32S06C10-21E IM 32S06H10-21E
IM 32S05B10-21EIM 32S01E10-21E
Integration withFAST/TOOLS
IM 32S56H20-21E
IM 32S04B20-21E
IM 32S03B10-21E
IM 32S04B30-21E
Safety System
Software
Installation
Hardware
ProSafe-RSVnet/IP
IM 32S56H10-21E
Vnet/IP
Safety Manual
IM 32S01S10-21E
Workbench User’s Guide
Messages
IM 32S02B10-21EIM 32S04B10-21E
2nd Edition : Dec.15,2008-00
iii
IM 32S01E10-21E
Safety Precautions
n Safety,Protection,andModificationoftheProduct• In order to protect system controlled by this product, the product itself and ensure safe
operation, observe the safety precautions described in this user’s manual. We assume no liability for safety if users fail to observe these instructions when operating the product.
• You must use this product according to the instructions described in user manuals. If not, protective functions of this product may not work as expected.
• If any protection or safety circuit is required for system controlled by the product or for the product itself, prepare it separately.
• Be sure to use the parts approved by Yokogawa Electric Corporation (hereafter simply referred to as YOKOGAWA) when replacing parts or consumables.
• Modificationoftheproductisstrictlyprohibited.
• The following symbols are used on the product and in this user manual to indicate that safety precautions are required:
Indicates that user must take caution. The symbol on the equipment refers the user to the relevant manual to avoid potentially hazardous situations that may result in injury or death. The symbol appears next to the cautionary information in user manuals required to avoid harm to personnel and to the equipment.
Indicates a protective grounding terminal. Before using the product, ground the terminal.
Indicates a functional grounding terminal. Before using the product, ground the terminal.
Indicates an AC supply.
Indicates a DC supply.
Indicates that main switch is ON.
Indicates that main switch is OFF.
1st Edition : May 30,2008-00
iv
IM 32S01E10-21E
n Notes on Handling User Manuals• Please hand over user manuals to your end users so that they can have them on hand for
convenient reference.
• Please read the user manuals thoroughly before using the product.
• The purpose of these user manuals is not to warrant that the product is well suited to any particular purpose but rather to describe the functional details of the product.
• YOKOGAWA reserves the right to make improvements in the user manuals and product at any time, without notice or obligation.
• Ifyouhaveanyquestions,oryoufindmistakesoromissionsintheusermanuals,pleasecontact our sales representative or your local distributor.
n Warning and DisclaimerThe product is provided on an “as is” basis. YOKOGAWA shall have neither liability nor responsibility to any person or entity with respect to any direct or indirect loss or damage arising from using the product or any defect of the product that YOKOGAWA can not predict in advance.
n Notes on Software• YOKOGAWA makes no warranties, either expressed or implied, with respect to the
software’smerchantabilityorsuitabilityforanyparticularpurpose,exceptasspecifiedintheterms of warranty.
• This software may be used on one machine only. If you need to use the software on another machine, you must purchase another copy of the software.
• It is strictly prohibited to reproduce the product except for the purpose of backup.
• Store the CD-ROM (the original medium) in a safe place.
• It is strictly prohibited to perform any reverse-engineering operation, such as reverse compilation or reverse assembling on the product.
• No part of the product may be transferred, converted or sublet for use by any third party, without prior written consent from YOKOGAWA.
1st Edition : May 30,2008-00
v
IM 32S01E10-21E
Documentation Conventions
n Typographical ConventionsThe following typographical conventions are used throughout the user manuals:
l Commonly used Conventions throughout User manuals:
Character strings in the following font and style:Indicatethatusermustenterthemintherelevantfieldortextboxinthecontext.Example: FIC100.SV=50.0
“Δ”Mark:Indicates a space between character strings that must be entered.Example: Calling the tuning view with the tag name of S0001 on HIS (Human Interface Station of the integrated CENTUM). S0001ΔTUN
Characterstringenclosedbybrackets({}):Indicates an option that can be omitted.Example: Parameters for calling the tuning view on HIS. TagnameΔTUN{Δ-windowsize}{Δ=Displayposition}
l Conventions used to show Key or Button Operations:
Charactersenclosedbysquarebrackets([]):Characters enclosed by square brackets within any description of a key or button operation, indicate either a key on the keyboard, a button name on a window, or an item displayed on a window.Example: Click the [OK] button.
l ConventionsofUserDefinedFolderUser-DefinedFolderNameIfthepathofafoldercanbedefinedbyusers,itiswrittenwithinaparentheses.Example: (RS Project Folder) \SCS0101If the RS Project Folder is C: \MYRSPJT, the above path becomes: C: \MYRSPJT\SCS0101
2nd Edition : Dec.15,2008-00
vi
IM 32S01E10-21E
n SymbolMarksThroughoutthisusermanual,youwillfindthatseveraltypesofsymbolsareusedtoidentifydifferent sections of text. This section describes these icons.
CAUTION:
Indicates instructions that must be observed in order to prevent physical injury and death of operator.
WARNING:
Indicates instructions that must be observed in order to prevent software or hardware from being damaged or system from becoming faulty.
IMPORTANT:
Indicates important information required to understand operations or functions.
TIP: Indicates additional information.
SEE ALSO :
Indicates a source to be referred to.
Clicking a reference displayed in green can call up its source, while clicking a reference displayed in black cannot.
n Drawing ConventionsSomedrawingsintheusermanualmaybepartiallyemphasized,simplified,oromitted,fortheconvenience of description.Note that screen images in user manuals may be slightly different from the actual ones (for example, display positions and case differences), and some show only example images.
n Integration with CENTUMProSafe-RS can be used by integrating with CENTUM VP or CENTUM CS 3000. In the User’s Manuals of ProSafe-RS, the integration with CENTUM VP or CENTUM CS 3000 is referred to as “Integration with CENTUM.” For the same features of CENTUM VP and CENTUM CS 3000 that have different feature names, the name used in CENTUM VP will be referred to in the explanations. (For example, CENTUM CS 3000 System Alarm Window and CENTUM VP System Alarm View have the same functions, but only System Alarm View will be referred to when explaining this feature.) Nevertheless, if there is any difference in functionality according to whether ProSafe-RS is integrated with CENTUM VP or CENTUM CS 3000, the feature will be explained separately for both cases.
SEE ALSO • For information about the functions and usage of CENTUM VP components, see CENTUM VP User’s
Manuals(IM)andrelatedTechnicalInformation(TI)andGeneralSpecifications(GS).
• For information about the functions and usage of CENTUM CS 3000 components, see CENTUM CS 3000 User’sManuals(IM)andrelatedTechnicalInformation(TI)andGeneralSpecifications(GS).
2nd Edition : Dec.15,2008-00
vii
IM 32S01E10-21E
n About Explanation of System BehaviorIn this manual, system behavior is explained assuming the use of the latest software and hardware that Yokogawa provides at the publication of the manual. Wherever a topic needs explanation of earlier revisions of software or hardware, a link to the required explanation is provided so that you can read them according to your system.
n About Station TypesSafety control stations (SCS) are named as follows according to the CPU node (SSCx0S/SSCx0D) and CPU module (SCP4x1) mounted in them.
• SCSV1-S : SCS that uses SSC10S/SSC10D (SCP401 is installed)
• SCSP1-S : SCS that uses SSC50S/SSC50D (SCP451 is installed)
• SCSP2-S : SCS that uses SSC60S/SSC60D (SCP461 is installed)
To explain the functions of these different types of SCS, the following generic terms or abbreviations may be used in this manual.
• SCS : Generic term that denotes all types of SCS
• SCSV : SCS connected on V net (this denotes SCSV1-S)
• SCSP : SCS connected on Vnet/IP (this denotes SCSP1-S and SCSP2-S)
• SCSV1 : Abbreviation for SCSV1-S
• SCSP1 : Abbreviation for SCSP1-S
• SCSP2 : Abbreviation for SCSP2-S
3rd Edition : Dec.22,2009-00
viii
IM 32S01E10-21E
CopyrightandTrademarkNotices
n All Rights ReservedThe copyright of the programs and online manuals contained in the DVD-ROM or CD-ROM shall remain in Yokogawa.You are allowed to print out the required pages of the online manuals for using the product, however, you are not allowed to print out the entire document. Except as stated above, no part of the online manual may be reproduced, either in electronic or written form, registered, recorded, transferred, sold or distributed (in any manner including withoutlimitation,intheformsofpaperdocuments,electronicmedia,filmsortransmissionviathenetwork).
n TrademarkAcknowledgments• CENTUM, ProSafe, Vnet/IP and STARDOM are registered trademarks of YOKOGAWA.
• Microsoft, Windows, Windows Vista, Visual Basic, Visual C++ and Visual Studio are either registered trademarks or trademarks of Microsoft Corporation in the United States and/or other countries.
• Adobe, Acrobat and Acrobat Reader are either registered trademarks or trademarks of Adobe Systems Incorporated in the United States and/or other countries.
• Ethernet is a registered trademark of XEROX Corporation.
• Modicon and Modbus are registered trademarks of Schneider Electric SA.
• PLC is a registered trademark of Rockwell Automation, Inc.
• HART is a registered trademark of the HART Communication Foundation.
• All other company and product names mentioned in this user’s manual are trademarks or registered trademarks of their respective companies.
• We do not use TM or ® mark to indicate those trademarks or registered trademarks used in this user’s manual.
3rd Edition : Dec.22,2009-00
Toc-1
IM 32S01E10-21E
ProSafe-RSIntegrationwith CENTUM VP/CS 3000
3rd Edition : Dec.22,2009-00
CONTENTS
IM 32S01E10-21E 3rd Edition
1. Overview of CENTUM Integration .......................................................... 1-12. Engineering for CENTUM Integration ................................................... 2-1
2.1 Engineering on the SENG Side .......................................................................2-22.1.1 Setting of SCS Project Property ........................................................2-2
2.1.2 DefinitionofAlarmPriorities ............................................................... 2-3
2.1.3 DefiningAlarmProcessingTable ....................................................... 2-8
2.1.4 DefinitionofTagNames .................................................................... 2-9
2.1.5 Engineering for Overriding from HIS................................................2-22
2.1.6 Settings for Exchanging Data between FCS and SCS ...................2-24
2.1.7 Accessing Subsystem’s Data from CENTUM .................................2-26
2.1.8 Plant Hierarchy ................................................................................2-28
2.1.9 Save and Download Operation Marks .............................................2-29
2.2 Engineering on the CENTUM Side ................................................................2-302.2.1 SCS Creation ...................................................................................2-30
2.2.2 SCS Taglist Generation ...................................................................2-33
2.2.3 Other Builders .................................................................................2-35
2.2.4 Items to Note on CENTUM Engineering..........................................2-38
2.3 Tests in the CENTUM Integration Structure .................................................2-39
3. Operation and Monitoring of Safety Systems Using HIS .................... 3-13.1 Windows Used in SCS Operation and Monitoring ....................................... 3-3
3.1.1 System Alarm View ...........................................................................3-3
3.1.2 Process Alarm View ..........................................................................3-7
3.1.3 Instrument Faceplate ....................................................................... 3-11
3.1.4 SCS Station Status Display View ....................................................3-15
3.1.5 Adjust Time Dialog Box ...................................................................3-22
3.1.6 Message Monitor of CAMS for HIS..................................................3-23
3.2 OtherFunctionsUsedinOperationandMonitoringfromHIS ..................3-26
Appendix. Limitations for Each Software Release Number of CENTUM ..............................................................................................................App.-1
<1. Overview of CENTUM Integration> 1-1
IM 32S01E10-21E
1. Overview of CENTUM Integration TheCENTUMIntegrationFunctionofProSafe-RSprovidesacommunicationinterfaceforaccessingSCSofProSafe-RSfromHISandFCSofCENTUMVPorCS3000system(hereinafterreferredtoas“CENTUM”).Bythisfunction,youcanoperateandmonitorSCSfromHISusingthesameinterfaces(windows)foroperatingandmonitoringFCS.YoucanalsoaccessSCSdatafromFCSusingthesameinterface(tagnames)usedbyanFCStoaccessotherFCS.
n CENTUMVP/CS3000-IntegratedSystemConfigurationTheconfigurationofasystemconsistingofProSafe-RSandCENTUMVPorProSafe-RSandCS 3000 is called the “CENTUM integration structure”. The role of each station in the CENTUM integration structure is as follows:
• SCS: To shut down the plant safely if a fault occurs in the plant.
• FCS: To perform process control.
• HIS: To provide user interfaces for accessing FCS and SCS data.
ThefigurebelowshowsanexampleoftheCENTUMintegrationstructure.IntheCENTUMintegration structure, both SCS and FCS can be operated and monitored from HIS. It is also possible to access SCS data from FCS.
Control Bus
CENTUMIntegrationFunction
Mapping
Read/Write
Tag nameRelated
Applicationfor CENTUMIntegration
Applicationlogic
Variables
010001E.ai
SENG HIS
SCSFCS FCS
Figure CENTUMIntegrationFunction
SEE ALSO It is possible for SENG, HIS, SCS, FCS to connect to Vnet/IP. You can connect Vnet/IP with V net domain using
Vnet router.
For more information about Vnet/IP, see the following:
A2, “Vnet/IP Network Connections” of the “CS 1000/CS 3000 Vnet/IP” (IM 33Q06H90-31E)
A2, “Vnet/IP Network Connections” of the “CENTUM VP Vnet/IP” (IM 33L01A10-40E)
2nd Edition : Dec.15,2008-01
<1. Overview of CENTUM Integration> 1-2
IM 32S01E10-21E
n Overview of Engineering for CENTUM Integration The SENG is a general-purpose PC on which the engineering functions to build SCS applications are installed. SCS applications written in languages that conform to IEC 61131-3 and used for ProSafe-RS such as Function Block Diagram (FBD) are called application logics. Each application logic is managed as part of the SCS project. The ENG is a general-purpose PC on which the CENTUM system generation function is installed. Each CENTUM application generated on the ENG is managed as part of a CENTUM project (project of CENTUM VP or CS 3000).
Applications to be downloaded to SCS are created on the SENG. One of such applications relates to tag names. A part of the tag-name-related application used for CENTUM integration is also written in the CENTUM project. Thetag-name-relateddefinitiondatawrittenintheCENTUMprojectisusedintheengineeringtasks, so that you can operate and monitor SCS from HIS and can access SCS data from FCS.
Downloaded to SCS Downloadedto FCS
Downloadedto HIS
SCS Project
SCS Application
Applicationlogic
Variables
CENTUM Project
FCSApplication
Part of SCSTag name Related
Definition data usedto create HIS and FCS
application
SENG Function CENTUM ENGFunction
Write
SENG ENG
Write Write Write WriteRead
Tag nameRelated
Applicationfor CENTUMIntegration
010002E.ai
HISApplication
Figure SCSProjectandCENTUMProject
2nd Edition : Dec.15,2008-00
<1. Overview of CENTUM Integration> 1-3
IM 32S01E10-21E
n Overview of Operation and Monitoring from HISIn the CENTUM integration, the following operations are possible from HIS to SCS:
• To use tag names to operate and monitor SCS data via the same interface used to monitor FCS data.
• To monitor the status of process alarms and annunciators generated on SCSs in HIS’s Process Alarm view.
• To monitor the system alarms generated on SCS in HIS’s System Alarm view.
• To display the status of each SCS in HIS’s SCS Status Display view.
• To override the application logic variables.
• To set output of the application logics.
SEE ALSO For more information on overriding, see the following:
7.2.3, “Forcing and Override” of the Engineering Guide (IM 32S01C10-21E)
2nd Edition : Dec.15,2008-00
<2. Engineering for CENTUM Integration> 2-1
IM 32S01E10-21E
2. Engineering for CENTUM Integration TorealizetheCENTUMintegration,youneedtoconnectaCENTUMprojectandanSCSproject.YouneedtoengineerboththeSCSprojectandtheCENTUMprojecttoconnecttheseprojects.ThischapterdescribestheengineeringtasksrequiredfortheCENTUMintegration.
SEE ALSO • FormoreinformationabouttheflowofengineeringforCENTUMIntegration,seethefollowing:
“n Engineering Procedure of CENTUM Integration Configuration” in 2.15, “CENTUM Integration” of the Engineering Guide (IM 32S01C10-21E)
• For more information about the relationship between CENTUM projects and SCS projects, see the following:“n Relationship between Projects” in 2.15, “CENTUM Integration” of the Engineering Guide (IM 32S01C10-21E)
SENG
SCS Project Properties
Alarm priority builder
SCS Link Transmission
SCS Link Transmission Builder
Alarm Processing Table Builder
Tag Name builder
CENTUM ENG
Taglist generation tool
CENTUM Alarm priority builderand Alarm Processing Table Builder
CENTUM HIS
Taglist for SCS
Instrument faceplates
Application logic
Variablesor
Instances
SCS
CENTUM connection application
Commonparameters
Alarm prioritytable
Alarm Processing
Table
MappingBlocks / Elements
Tag name Alarm priority
CENTUM FCS
Alarm ProcessingTable
Alarm prioritytable
Block / Elements
Key : tagname
020002E.ai
Figure TargetsofEngineeringonSENGandCENTUM
2nd Edition : Dec.15,2008-00
<2.1 Engineering on the SENG Side> 2-2
IM 32S01E10-21E
2.1 Engineering on the SENG SideThissectiondescribestheengineeringtasksperformedontheSENGside,whichisoneofthetasksrequiredtoconnectanSCSprojectandaCENTUMproject.
2.1.1 SettingofSCSProjectPropertyAnSCSprojectandaCENTUMprojectcanbeconnectedusingSCSProjectPropertiesinanSCSmanager.InSCSProjectProperties,specifythefolderoftheCENTUMprojectyouwanttoconnecttotheSCSproject.TheinformationforCENTUMintegrationthathasbeensetintheSCSprojectcanbecopiedtotheCENTUMprojectfolder.
TheconnectionofanSCSprojectandaCENTUMprojectissetonlyinonedirection:fromtheSCSprojecttotheCENTUMproject.
020101E.ai
SCS Project (SCS0201)
SENG
SCS Project (SCS0102) CENTUM Project
CENTUM System Generation Function
CENTUM Connection datafrom SCS0101
SCS Project (SCS0101)
CENTUM Connection datafrom SCS0102
CENTUM Connection datafrom SCS0201
(Specify the CENTUM project folder)
Figure SettingsfortheConnectionBetweenSCSProjectandCENTUMProject
SEE ALSO • For more information about the relationship of an SCS project and a CENTUM project, see the following:
“n Type of Project” in 1.3, “Type of Project” of the Engineering Guide (IM 32S01C10-21E)
• For more information about specifying project folders, see the following: 3.1.2, “SCS Project Properties Dialog Box” of the Engineering Reference (IM 32S04B10-21E)
2nd Edition : Dec.15,2008-00
<2.1 Engineering on the SENG Side> 2-3
IM 32S01E10-21E
2.1.2 DefinitionofAlarmPrioritiesProcess alarms occurred on SCS can be monitored in the Process Alarm view of CENTUM HIS.
ThissectiondescribesthedefinitionofAlarmPrioritiesusingAlarmPriorityBuilder.
n ProSafe-RS Alarm Priority Builder AlarmPriorityBuilderdefinesthealarmoutputformat,alarmactionandothersettingsrequiredfor each SCS when an alarm has occurred and returned to a normal state. Five levels of alarm priorities are set: high-priority alarm, medium-priority alarm, low-priority alarm, logging alarm and reference alarm. To start the Alarm Priority Builder, do the following: From the SCS Manager, click [Tools] - [Engineering] to start the Engineering Launcher, and select [Alarm Priority Builder] from the menu.Thealarmflashingaction,rewarningandflashingactionuponreturningtoNRaresetforeachalarm priority. The setting of [NR (Flashing)] from the Alarm Priority Builder on SENG must be the same as the setting of [NR] from the Alarm Priority Builder on the CENTUM ENG.
TIPThe ProSafe-RS Alarm Priority Builder is different from the CENTUM Alarm Priority Builder. You cannot set the behavior of HIS from the ‘Alarm Priority Builder on SENG’.
n Downloading to an SCS Whenalarmprioritiesaredefined,theinformationisreflectedintheSCSdownloaddatabase.Perform off-line download of the database to the SCS using SCS Manager on SENG.
SEE ALSO Formoreinformationaboutofflinedownload,seethefollowing:
9.1, “Off-line Download” of the Engineering Reference (IM 32S04B10-21E)
2nd Edition : Dec.15,2008-00
<2.1 Engineering on the SENG Side> 2-4
IM 32S01E10-21E
n Differences from CENTUM Alarm Priority Builder When connecting an SCS project to a CENTUM project, two alarm priority builders must be used properly: one is ProSafe-RS Alarm Priority Builder launched from SCS Manager on the SENG, the other is Alarm Priority Builder launched from CENTUM System View. Each alarm priority builder is used for each project, with the following differences between the two:
• Target station ProSafe-RSAlarmPriorityBuildercanbeusedtochangedefinitionsforeachSCS. CENTUM Alarm Priority Builder is common throughout the CENTUM project, and the definitionssetinthisbuilderapplytoallHISandFCS.
• Setting items ProSafe-RS Alarm Priority Builder is used to set SCS data, while CENTUM Alarm Priority Builder is used to set HIS and FCS data. Accordingly, the setting items are different between the two alarm priority builders.
Table Setting Items in ProSafe-RS and CENTUM Alarm Priority Builders
Title Item ProSafe-RS Alarm Priority Builder
CENTUM Alarm Priority Builder
CRT Window display x
PRT Printing x
Historical File Storinginfiles xBuzzer Sound Buzzer sound generation xAlarm Action Alarmflashingaction x x (*1)
Rewarning Rewarning x x (*1)
NR (Flashing) Flashing action upon returning to the NR state x (*2) x (*1)
x: Can be setBlank: Setting item not available*1: DefinedonlyforFCSs*2 Must be the same as settings on CENTUM Alarm Priority Builder
• File compatibility ThebuilderfilescreatedinProSafe-RSAlarmPriorityBuilderaswellastheircopiessavedin different names cannot be opened in or imported to CENTUM Alarm Priority Builder, or viceversa.CSVfilesmustbeusedtoexchangedatabetweenthetwobuilders.
• Other ProSafe-RS Alarm Priority Builder has no download menu. Downloading from this builder is performed in SCS Manager.
2nd Edition : Dec.15,2008-00
<2.1 Engineering on the SENG Side> 2-5
IM 32S01E10-21E
n Window of ProSafe-RS Alarm Priority Builder ThefollowingfigureshowsthemainwindowofAlarmPriorityBuilder:
020102E.ai
Alarm Priority Builder - [Pjt:MYPJT File:AlmPri.edf]
Alarm Action High-priority Alarm
Function
Occurrence
Recovery
Alarm Action
1
Lock Type
Rewarning
Yes
No
NR
On Alarm Depende
On Alarm Depende
Medium-priority Alarm
1:Lock Type
2:Non-lock Type
3:Self ACK Type
Message
Ready Position: Line 1 Column 5
Low-priority Alarm
File Edit View Tools Window Help
Title bar
Menu bar
Message display area Workspace
Status bar
Data menu area
Tool bar
Figure MainWindowofAlarmPriorityBuilder
1st Edition : May 30,2008-00
<2.1 Engineering on the SENG Side> 2-6
IM 32S01E10-21E
n Setting Items ProSafe-RS Alarm Priority Builder has tabs corresponding to different alarm priority levels. All or part of the following items can be set in each of these tabs:
Table Setting Items
Item Description Alarm Action Specifythealarmflashingaction.
Rewarning Specify whether to enable or disable rewarning.NR (Flashing) Specify the alarm action upon returning to the NR state.
In ProSafe-RS Alarm Priority Builder, set each action upon occurrence and recovery of alarms, for each alarm priority. Theactionscorrespondingtotheblankfieldsinthetablebelowcannotbeset:
Table Alarm Priorities and Settable Items
ItemHigh-priority alarm Medium-priority
alarm Low-priority alarm Logging alarm Reference alarm
Occurrence Recovery Occurrence Recovery Occurrence Recovery Occurrence Recovery Occurrence Recovery
Alarm Action x Lock x Lock x Non-lock Self ACK Self ACK Self ACK Self ACK
Rewarning x No
NR (Flashing) x On Alarm
Dependent
x: Can be setOtherthanx:Fixedvalue(cannotbespecified)
l Alarm Action InAlarmAction(alarmflashingaction),settheflashingindicationusedtonotifytheoperatorwhenanalarmhasoccurred.Thedesiredflashingindicationcanbeselectedfromthefollowingthree types:
Table TypesofFlashingIndication
Type Action
Lock TypeTheflashingindicationwillcontinueuntiltheoperatorperformsanacknowledgement operation, even after the alarm is reset upon returning to the NR state.
Non-lock TypeTheflashingindicationwillstopwithouttheoperatorperforminganacknowledgement operation, when the alarm is reset upon returning to the NR state.
Self ACK Type Flashing indication is not implemented, since the system will automatically acknowledge the alarm as soon as it is generated.
1st Edition : May 30,2008-00
<2.1 Engineering on the SENG Side> 2-7
IM 32S01E10-21E
l Rewarning Rewarningisthealarmthatnotifiestheoperatorofacontinuingalarmstate.Thisitemcanbespecifiedonlyforhigh-priorityalarms.Thealarmmessagewillbeoutputagainattherewarningperiodsorwhenspecifiedbycommand.
Table Types of Rewarning
Type Description0:No Rewarning is not issued
1:Yes Rewarning is issued
SEE ALSO The rewarning period is set in SCS Constants Builder. For more information about SCS Constants Builder, see
the following: 3.1.3, “SCS Constants Builder” of the Engineering Reference (IM 32S04B10-21E)
l NR(Flashing)NR(Flashing)definestheflashingindicationusedtonotifytheoperatorthatallalarmsinagivenfunctionblockhavebeenrecovereduponreturningtotheNRstate.Thisitemcanbespecifiedonly for high-priority alarms. A desired action can be selected from the following two types:
Table Types of Alarm Action upon Returning to NR
Type Description
On Alarm Dependent
When all alarms have been reset upon returning to the NR state, the current flashingstatuswillcontinue.IftheindicatorisflashingwhentheNRstateisrestored,theflashingwillcontinue.IftheindicatorisnotflashingwhentheNRstateisrestored,thenon-flashingstatuswillcontinue.
NotificationatReturn(*1)
When all alarms have been reset upon returning to the NR state, the flashingtoindicatetheNRstatewillstart.Evenwhenthisflashingisnotacknowledged,theflashingwillstopwhenanewalarmisgenerated.ReturnoftheentirefunctionblocktotheNRstateisnotifiedbyaNon-Lockaction.
*1: Must be the same as the settings on CENTUM Alarm Priority Builder. If the two settings are different: for example, the [NR] on CENTUM is set to [On Alarm Dependent] and the [NR (Flashing)] on the
ProSafe-RSissetto[NotificationatReturn],theprocessalarmLEDontheSCSblinksaccordingto[NotificationatReturn],butno sound is output.
IfAlarmActionissetto“SelfACK”andalarmtypeuponreturningtoNRissetto“NotificationatReturn,”anerrormessagewillbeoutputwhenafileissaved.
2nd Edition : Dec.15,2008-00
<2.1 Engineering on the SENG Side> 2-8
IM 32S01E10-21E
2.1.3 DefiningAlarmProcessingTableYoucanmonitortheprocessalarmsraisedbytheSCSfromtheProcessAlarmviewonthe CENTUM HIS. This section describes how to operate Alarm Processing Table Builder.
TIPThe Alarm Processing Table Builder on the ProSafe-RS and the Alarm Processing Table Builder on CS 3000 are two different entities.
n Alarm Processing Table BuilderThe Alarm Processing Table Builder determines the priority of alarms raised by Mapping block on SCS. The priority levels are 1 to 16.Set the color and priority levels on the Alarm Processing Table Builder on the CENTUM and import the settings to the Alarm Processing Table Builder on ProSafe-RS because the builder on ProSafe-RS has no editing feature.
n EngineeringflowUnlike the other builders, the Alarm Processing Table Builder on the ProSafe-RS imports the contents of settings on the Alarm Processing Table Builder on CENTUM. If the settings for the table used by SCS are changed on the Alarm Processing Table Builder on CENTUM, be sure toimportthefilefortheAlarmProcessingTableBuilderonCENTUMtotheAlarmProcessingTableBuilderontheProSafe-RS.ToreflecttheimporteddataontheSCS,offline-downloadingisrequired.
Engineeringflowisasfollows:With the SCS Manager, display the [SCS Project Properties] dialog box, select the [Project] tab, andenterthe‘topfolderoftheCENTUMProject’intothefield[CENTUMProjectFolder].Dothisbefore going on to the following steps.1. Start the Alarm Processing Table Builder:
From the SCS Manager, click [Tools] - [Engineering] to start the Engineering Launcher, and select [Alarm Processing Table Builder] from the menu.
2. Fromthemenu,select[File]-[Externalfile]-[Import...]. The following Import dialog appears.
020107E.ai
Cancel
Open
Import
Look in:
MATRIXAlmPri.edfAlmStsLabel.edfAlmTbl.edfBlkStsLabel.edfCustomPlant.edf
AlmTbl.edfFile name:
Files of type:
Common
SysStsLabel.edfUserSec.edf
EngUnit.edfInstLabel.edfMultiPjt.edfOpeMarkDef.edfStnConf.edfStsChange.edf
Builder File(*.edf)
Figure ImportDialog
3. Select the AlmTbl.edf of a CETUM project and click the [Open] button.4. From the menu of the Alarm Processing Table Builder, select [File] - [Save]. The AlmTbl.edf
is saved in the SCS Project.5. ToreflectthecontentsintheAlmTbl.edffileontheSCS,execute[Build]inSCSManager
beforeoffline-downloading.
2nd Edition : Dec.15,2008-00
<2.1 Engineering on the SENG Side> 2-9
IM 32S01E10-21E
2.1.4 DefinitionofTagNamesWhenSCSprojectandCENTUMprojectareconnected,tagnamesmustbedefinedsothatapplicationlogicvariablesandfunctionblockscanbeaccessedfromHISorFCS. TagnamesaredefinedinTagNameBuilder.
n OverviewofTagNameDefinitionInTagNameBuilder,definetagnamesforapplicationlogicvariablesorfunctionblocks.FunctionblocksorvariableshavingadefinedtagnamecanbeaccessedfromHISsbasedontheircorrespondence to Mapping Block/Element. ThefollowinginformationisdefinedinTagNameBuilder:
• Tag name
• Parameters required by Mapping Block/Element on SCS
• Parameters required by instrument faceplates on HIS
Theflowoftagnamedefinitionisasfollows:1. DefineapplicationlogicvariablesorfunctionblockinstancesinDictionaryViewofSCS
Manager.2. DefinetagnamesandparametersinTagNameBuilder.
To start the Tag Name Builder, do the following: From the SCS Manager, click [Tools] - [Engineering] to start the Engineering Launcher, and select [Tag Name Builder] from the menu.
3. Execute [Build] in SCS Manager to generate SCS database.
SEE ALSO • Thetypesofvariablesforwhichatagnamecanbedefinedarelimited.Formoreinformationaboutthe
variablesforwhichatagnamecanbedefinedaswellastheapplicabledefinitionitems,seethefollowing:“n Setting Items”
• For more information about the mapping blocks/elements, see the following: C8, “External Communication Function Blocks” of the Safety Control Station Reference (IM 32S03B10-21E)
2nd Edition : Dec.15,2008-00
<2.1 Engineering on the SENG Side> 2-10
IM 32S01E10-21E
n Window of Tag Name Builder ThefollowingfigureshowsthemainwindowofTagNameBuilder:
020103E.ai
Title bar Menu bar
Message display areaWorkspaceStatus bar Data menu area
Tool bar
ABS001_Q@Select1FBABS002_Q@Select1FBACOS_Q@InterferenceANLGI001_HYS@HISIFANLGI001_IN@HISIFFBANLGI001_LL@HISIFFBANLGI001_OUT@HISIFANLGI001_PH@HISIFFANLGI001_PL@HISIFFBANLGI001_SH@HISIFFANLGI002_HH@HISIFF
IO_RE
Tag Name Builder - [Pjt:SCS1020 File:TAG.edf]
ABS001_IN@Select1FBD ABS001_IN %
%
%
%
%
4 Gener
Gener
Gener
Gener
Gener4
4
4
4
ABS002_IN@Select1FBD
ACOS_IN@InterferenceF
ANLGI001_HH@HISIFFB
Unit Level
BOOL/ECW_B
Message
Ready Position: Line 5 Column 1
DINT/REAL/ECW_I/ECW_R
File Edit View Tool Window
ANLGI VEL Variable Name
Variable Name Tag Name
ECW_R
ANN/ANN_FUP
Change
Figure MainWindowofTagNameBuilder
3rd Edition : Dec.22,2009-00
<2.1 Engineering on the SENG Side> 2-11
IM 32S01E10-21E
You can register a variable name in Tag Name Builder by dragging the variable name from DictionaryViewanddroppingitintoavariablenamefieldinTagNameBuilder.Whenmultiplevariable names are dragged and dropped, the variable names are registered in multiple variable fieldsstartingfromthetopfield.Ifavariablenameisalreadyregisteredinthevariablenamefield,thevariablenamefieldisoverwritten.
020104E.ai
File Edit View Tools Window Tag Name Builder - [ Pjt:SCS0101 File:Tag.edf ]
Message
Ready Position: Line 1 Column 3
DINT/ECW_I/REAL/ECW_R
File Edit Debug Tools Options Window Help ProSafe-RS - [SCS0101 (*Binding error management*) - Dictionary - Variables]
Variables Main (Config1)
BoundVariable BindingErrorAny Group
All variabl Global var Addition ( Main (*si Binding Te ComplexT
Test (Config1)
SENG001
ComplexTest
Name Alias
OK1
BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL DINT DINT
UserAcknowledgeOUT01InitBindText InitOKOK1OK3OK2ManualResetOKStartOKStopCopyOfval31CopyOBesAdd1
OK3OK2
Type
Variable Name ANN/ANN_FUP
Variable Name
OK1
OK2
Tag Name Type
BOOL
T101 ECW_B
BOOL
OK3 BOOL
Tag Commen
BOOL/ECW_B
AV_NR@An NR1@AnaloNR2@AnaloNR3@AnaloPermission
IO_REAL
Figure DraggingandDroppingfromDictionaryView
3rd Edition : Dec.22,2009-00
<2.1 Engineering on the SENG Side> 2-12
IM 32S01E10-21E
n Setting ItemsThefollowingtableshowsthevariabletypeswhosetagnamecanbedefinedwithTagNameBuilder. The setting items of Tag Name Builder vary depending on the variable type.
Table VariableTypesWhoseTagNameCanBeDefinedwithTagNameBuilder
Type Description BOOL BOOL variable
DINT Integer variable
REAL Real variable
ANLG_S ANLG_S function block instance
ANLGI ANLGI function block instance
VEL VEL function block instance
ANN ANN function block instance
ANN_FUP ANN_FUP function block instance
IO_REAL Analog real input variable
IO_BOOL Discrete BOOL I/O variable
GOV_B Grouping override function block instance (BOOL type)
GOV_IB Grouping override function block instance (discrete BOOL I/O variable)
OVR_B Override function block instance (BOOL type)
OVR_I Override function block instance (integer type)
OVR_R Override function block instance (real type)
OVR_IR Override function block instance (analog real input variable)
OVR_IB Override function block instance (discrete BOOL I/O variable)
PASSWD Password function block instance
ECW_B External communication function block instance (BOOL type)
ECW_I External communication function block instance (integer type)
ECW_R External communication function block instance (real type)
SCI_B Subsystem Communication function block instance (BOOL type input variable)
SCO_B Subsystem Communication function block instance (BOOL type output variable)
SCI_I Subsystem Communication function block instance (integer type input variable)
SCO_I Subsystem Communication function block instance (integer type output variable)
SCI_R Subsystem Communication function block instance (real type input variable)
SCO_R Subsystem Communication function block instance (real type output variable)
MOB_11 Data manual operation with two-position answerback function block instance (BOOL)
MOB_21 Data manual operation with three-position answerback function block instance (BOOL)
MOB_RS Auto-reset data manual operation function block instance (BOOL)
MOA Analog-type data manual operation function block instance
3rd Edition : Dec.22,2009-00
<2.1 Engineering on the SENG Side> 2-13
IM 32S01E10-21E
The following table shows the setting items of Tag Builder and whether or not each setting item can be changed online. In addition to the setting items, reference items are also provided for checking the settings in Dictionary View and I/O Wiring View. The reference items cannot be changed with Tag Name Builder. All items can be printed.
Table Items
Item Online change Remarks
Variable Name Permitted
Element NameThis item is only displayed in the ANN/ANN_FUP tab. The element names %AN0001 to %AN1000 are displayed for SCSP1 and SCSV1, and %AN0001 to %AN2000 for SCSP2.
Type ThevariabletypedefinedinDictionaryViewisdisplayed.Thisitemisnot displayed in the tab pages for a single variable type.
Comment AcommentfortheapplicablevariabledefinedinDictionaryViewisdisplayed.
Wiring PositionThe installation position of the channel wired to the applicable variable in I/O Wiring View is displayed. This item is displayed only for an I/O variable.
Tag Name PermittedEvenifthetagnamefieldisleftblank,ANNorANN_FUPcanbeaccessed from CENTUM by using its element name. With no tag namespecified,nothingisprintedforthetagname.
Tag Comment Permitted
Annunciator Message Permitted
Low Limit Permitted
High Limit Permitted
Unit Permitted
Level Permitted
Label Permitted
Button 1 Permitted
Button 2 Permitted
Button Top Permitted
Button Bottom Permitted
Switch Position Label Permitted
Tag Mark Permitted
Alarm Level Permitted Specify a value of 1 to 16.
Upper Window Permitted Set the upper window created on the CENTUM.
Help Permitted Set the help message created using CENTUM Help Builder.
Scale Reverse Permitted
Scale-division Permitted
Double Authentication Permitted
Alarm in Overriding Permitted
Answer-back Alarm Permitted
Password ON Alarm Permitted
Output High Limit Permitted
Output Low Limit Permitted
Output Scale High Limit Permitted
Output Scale Low Limit Permitted
Upper Equipment Name Permitted
Note: Below the double line are the advanced setting items. You can display them by placing a check mark next to [Detailed Setting Items] in the [View] menu.
3rd Edition : Dec.22,2009-00
<2.1 Engineering on the SENG Side> 2-14
IM 32S01E10-21E
The following table shows the setting items for each variable type:
Table Variable Types and Setting Items
Setting item
Variable type
BOOLECW_
B
DINTREALECW_
IECW_
R
ANLG_S
ANLGIVEL
ANNANN_FUP
IO_REAL
IO_BOOL
GOV_B GOV_IB OVR_B OVR_IB
OVR_IOVR_
ROVR_
IR
PASS-WD
SCI_B
SCO_B
SCI_ISCO_ISCI_
RSCO_
R
MOB_11
MOB_21
MOB_RS MOA
Variable Name x x x x x x x x x x x x x x x
Tag Name x x x x x
(*1) x x x x x x x x x x
Tag Comment x x x x - x x x x x x x x x x
Annun-ciator Message
- - - - x - - - - - - - - - -
Low Limit - - x (*2) - - - - - - - - - - -
High Limit - - x (*3) - - - - - - - - - - -
Unit - x x (*4) - x - - x - - x - - -
Level x x x x x x x x x x x x x x x
Label x - - - x - x x x x x - x x -
Button 1 x - - - - - x - - - x - - - -
Button 2 x - - - - - x - - - x - - - -
Button Top - - - - - - - x x x - - x x -
Button Bottom - - - - - - - x x x - - x x -
Switch Position Label
x - - - x - x x x x x - x x -
x: Can be set-: Setting item not available *1: Tagnamespecificationisnotrequired(evenifatagnameisnotdefined,thevariablecanstillbeaccessedfromHISsusingan
element number).*2: Fixed to 0.0. For display purpose only. *3: Fixed to 100.0. For display purpose only.*4: Fixed to %. For display purpose only.
3rd Edition : Dec.22,2009-00
<2.1 Engineering on the SENG Side> 2-15
IM 32S01E10-21E
Table VariableTypesandSettingItems(AdvancedSettingItems)
Setting item
Variable type
BOOLECW_
B
DINTREALECW_
IECW_
R
ANLG_S
ANLGIVEL
ANNANN_FUP
IO_REAL
IO_BOOL
GOV_B
GOV_IB
OVR_B OVR_
IB
OVR_IOVR_
ROVR_
IR
PASS-WD
SCI_B
SCO_B
SCI_ISCO_ISCI_
RSCO_
R
MOB_11
MOB_21
MOB_RS MOA
Tag Mark x x x x x x x x x x x x x x x
Alarm Level - - x x x - - x x x - - x x x
Upper Window x x x x x x x x x x x x x x x
Help x x x x x x x x x x x x x x x
ScaleReverse - - x x - - - - - - - - - - -
Scale-division - - x x - - - - - - - - - - -
Double Authenti-cation
- - - - - - - x x x - - x x x
Alarm in Overrid-ing
- - - - - - - x x - - - - - -
Answer-back Alarm
- - - - - - - x (*1) x - - - x x -
Pass-word ON Alarm
- - - - - - - - - x - - - - -
Output High Limit (%)
- - - - - - - - - - - - - - x
Output Low Limit (%)
- - - - - - - - - - - - - - x
Output Scale High Limit (%)
- - - - - - - - - - - - - - (*2)
Output Scale Low Limit (%)
- - - - - - - - - - - - - - (*3)
Upper Equip-ment Name
- - x x x - - x x x - - x x x
x: Can be set-: Setting item not available *1: For GOV_B and GOV_IB, no setting is required.*2: Fixed to 100.0. For display purpose only. *3: Fixed to 0.0. For display purpose only.
3rd Edition : Dec.22,2009-00
<2.1 Engineering on the SENG Side> 2-16
IM 32S01E10-21E
l Variable NameWhen assigning a tag name to a function block instances specify the instance name for a variable name.From the variable names created with SCS Manager, specify the variable name you want to assignatagnameto.Atagnamecanbedefinedregardlessofthescopeofthevariablename.In case of a local variable, enter a scope name after “@.”Incaseofaninternalvariableofauser-definedfunctionblock,assignaninstancenameusingDictionaryViewofSCSManager.Thevariablenameisspecifiedintheformatof“[InstanceName].[Internal Variable Name],” and up to two nests are permitted in each variable to which a tag name is assigned.
Table ExamplesofVariableSpecification
Variable Scope Description VAR1 Global Global variable
VAR2@PROG1 PROG1 Local variable of PROG1 function
FB01.VAR3 Global InternalvariableVAR3ofuser-definedfunctionblockinstanceFB01
FB01.VAR3@PROG1 PROG1 InternalvariableVAR3ofuser-definedfunctionblockinstanceFB01defined
locally in PROG1 function
FB01.FB2.VAR3 GlobalInternalvariableVAR3ofuser-definedfunctionblockinstanceFB2,whichisusedinuser-definedfunctionblockinstanceFB01(maximumlimitoffunctionblock nesting)
Note: The variable name can contain up to 69 single-byte characters. Tag Name Builder also checks the following items: • The variable name consists only of alphanumeric characters and “@”, “.” or “_”. If any other character is used, an error will
occur. • The variable name begins with an alphabetic character or “_”; otherwise, an error will occur. • In the above table, “FB01.VAR3” and “FB01.VAR3@PROG1” have one nest, while “FB01.FB2.VAR3” has two nests.
l Tag NameA name used to access each application logic variable from HIS. A tag name can contain up to 16 single-byte alphanumeric characters including “_” and “-”. Note that tag names cannot begin with “_”or“-”.Allcharactersareconvertedtouppercaseastheyareentered.Definetagnamesbypaying attention not to create duplications within the CENTUM project.
l Tag Comment Acommentassignedtoatagname.Atagcommentcanbedefinedusingupto24single-byteor12 double-byte characters.
l Annunciator Message Amessagenotifyinganerrorintheprocess.Anannunciatormessagecanbedefinedasanycharacter string consisting of up to 80 single-byte characters or 40 double-byte characters. Default: None
l Unit Asymbolindicatingtheunittoaccompanyeachdatasuchasflowrateorpressure.Anunitcanbedefinedusinguptosixsingle-byteorthreedouble-bytecharacters.Default: %
3rd Edition : Dec.22,2009-00
<2.1 Engineering on the SENG Side> 2-17
IM 32S01E10-21E
l Low LimitAlowlimit(SL)ofengineeringdata.Itcanbedefinedusinguptosevendigitsincludingasignand decimal point. The low limit set here is referenced for display on an HIS and is not used in calculationoralarmprocessingonSCS.Enterthesamevaluespecifiedas“Lowlimit”fortheSCS in Multi-Language Editor, although a different value can be set. Default: 0.0
l High LimitAhighlimit(SH)ofengineeringdata.Itcanbedefinedusinguptosevendigitsincludingasignand decimal point. The high limit set here is referenced for display on an HIS and is not used in calculationoralarmprocessingonanSCS.Enterthesamevaluespecifiedas“highlimit”fortheSCS in Multi-Language Editor, although a different value can be set.Default: 100.0
l LabelA display format applied to the switch position label displayed on each button on the instrument faceplates of HIS. Two label formats are available: Direct and Reverse. Either type can be specified.
Table Label
Number Description1 Direct
2 Reverse
Default: Direct
l Button 1 and 2AbuttoncolorcanbespecifiedforeachbuttonontheinstrumentfaceplatesofHIS.Selectoneofthe following 16 colors: R: Red N: Black G: Green Y: Yellow B: Blue M: Magenta C: Cyan W: White SB: Steel Blue PK: Pink SG: Spring Green OR: Orange YG: Yellow Green VO: Violet DB: Deep Sky Blue GR: GrayWheneachbutton(switch)ispressed,thebuttoncolorwillchangetothespecifiedcolor.Default: Red
l Button Top/Button BottomEach button on the instrument faceplates of HIS can be divided into the top and bottom sections anditscolorcanbespecifiedforeachsection.Sixteencolorsareavailable,correspondingtothe colors shown in “Button 1 and 2” above, except for “N: Black,” which is substituted by “N: Background color.”
2nd Edition : Dec.15,2008-00
<2.1 Engineering on the SENG Side> 2-18
IM 32S01E10-21E
l Level Variablescanbeclassifiedaccordingtotheirpriorities.Eightlevelsfrom1to8areavailable,andthe security level increases as the number increases. The operation and monitoring privileges on the HIS with respect to each data item will change depending on the function constraint level. Enter a number between 1 and 8. Default: 4
SEE ALSO For more information about function constraint levels, see the following:
F9.4, “Function Block Security” of the CS 1000/CS 3000 Reference Engineering (IM 33S01B30-01E)
F3.4, “Function Block Security” of the CENTUM VP Reference Engineering (IM 33M01A30-40E)
l Switch Position Label A label displayed on each button on the instrument faceplates of HIS. Switch position labels 1 to4canbedefinedusinguptoeightsingle-byteorfourdouble-bytecharacters.However,thefollowing characters cannot be used: , (comma), | (vertical bar), ' (single quotation), " (double quotation), \ (back slash), and #Default: ON,,OFF,ON
l TagMarkA tag mark indicating the tag name priority and process status. The following four tag name priorities are available:
• Important
• General
• Aux. 1
• Aux. 2
Eachprioritycanbefurtherdefinedby“withacknowledgement(withAck.)”and“withoutacknowledgement.” In other words, one of the following eight types of priorities can be selected by combining the above two. Enter a number between 1 and 8.
Table TagMarks
Number Type1 Important with Ack. Important tag with acknowledgement
2 General General tag
3 Aux.1 Auxiliary tag 1
4 Aux.2 Auxiliary tag 2
5 Important Important tag
6 General with Ack. General tag with acknowledgement
7 Aux.1 with Ack. Auxiliary tag 1 with acknowledgement
8 Aux.2 with Ack. Auxiliary tag 2 with acknowledgement
Default: 2 (General)
SEE ALSO Insomefunctionblocks,areconfirmationdialogboxalwaysappearsifyoutrytochangeanMV.Fordetails,see
the following:“lReconfirmationDialogBox”in“n Instrument Faceplate Display” in 3.1.3, “Instrument Faceplate”
2nd Edition : Dec.15,2008-00
<2.1 Engineering on the SENG Side> 2-19
IM 32S01E10-21E
l Alarm Level DefineaprocessinglevelonanHISforeachalarmgeneratedwithrespecttoagiventagname. You can specify alarm priority and display color for all alarms generated in relation to the applicable tag name. You can select a desired alarm processing level from 16 levels listed in the tablebelow.Thealarmlevels1to4arefixed.
Table Alarm Processing Levels
Number Type1 High High-priority alarm
2 Medium Medium-priority alarm
3 Low Low-priority alarm
4 Logging Logging alarm
5…16
User (5)…User (16)
Equalize to the setting from the ‘Alarm Processing Table Builders on CENTUM.
Default: 1 (High)
l Upper Window An upper window is a window that is called when the graphic button in a toolbox or graphic key on the operation keyboard is operated on HIS while a tag name is selected. The upper window canbespecifiedforeachtagname.Default: None
l HelpYoucanspecifyanumberforeachhelpmessagedisplayedonHIS.Theusercandefinedesiredhelp messages using CENTUM Help Builder and specify a number between HW0001 and HW9999 for each of these messages. Specify the applicable number to display the help dialog box showing the corresponding help message.Default: HW000 (no help message)
l Scale Reverse This display method causes the top of the scale shown on the instrument faceplates of HIS to become the low limit, and its bottom the high limit. Specifying “Yes” will activate reverse display. Either “Yes” or “No” can be selected. Default: No
l Scale Division You can select 1, 2, 3, 4, 5 or 7 divisions for the scale on the instrument faceplates of HIS. You can also set “AUTO” to let the system determine the division number automatically. Default: AUTO
l Double Authentication Use this function if you want to grant operation permission based on approvals of two users--the logged-in user and another user--when operating important tag names from an HIS. When the useofdoubleauthenticationisdefined,thereconfirmationdialogboxwithdoubleauthenticationappears. Specifying “Yes” will enable double authentication. Either “Yes” or “No” can be selected.Default: No
2nd Edition : Dec.15,2008-00
<2.1 Engineering on the SENG Side> 2-20
IM 32S01E10-21E
l Alarm in OverridingSpecify whether or not to generate a process alarm to notify that a grouping override function block or an override function block is overriding. Specifying “Yes” will cause an applicable process alarm to be generated. Either “Yes” or “No” can be selected.Default: Yes
SEE ALSO For more information about the overriding alarm, see the following:
“l Override ON Alarm” in “n Process Alarm” in D3.2, “Tag Name Interfaces and Process Alarms of Override Function Blocks” of the Safety Control Station Reference (IM 32S03B10-21E)
l Answer-backAlarmSpecify whether the process alarm is to be generated when the Override Operation or Manual Operation from HIS does not work properly. For example, a process alarm can be generated when the Manual Operation Function Block detects discrepancy between the output signal to a valve and the answerback input value from the limit switch of the valve. You can select “Both” (answerback error on both the ON and OFF sides), “ON”, “OFF” or “No”.Default: Both
Table OptionforAnswer-backAlarm
Variable type OVR_B, OVR_I, OVR_R, OVR_IR, OVR_IB,MOB_RS(*1) MOB_11, MOB_12
Option 0: No1: Both (Default)
0: No1: Both (Default)2: ON3: OFF
*1: For GOV_B, GOV_IB, and PASSWD, no setting is required.
SEE ALSO For more information about the answerback error alarm, see the following:
“n Process Alarm” in D3.2, “Tag Name Interfaces and Process Alarms of Override Function Blocks”of the Safety Control Station Reference (IM 32S03B10-21E)
l Password ON Alarm Specify whether or not to generate a process alarm when the PASSWD function block is outputting 1 as the result of overriding by HIS. Specifying “Yes” will cause an applicable process alarm to be generated. Either “Yes” or “No” can be selected.Default: Yes
SEE ALSO For more information about the password ON alarm, see the following:
D3.7, “Tag Name Interfaces and Process Alarms of Password Function Blocks” of the Safety Control Station Reference (IM 32S03B10-21E)
2nd Edition : Dec.15,2008-00
<2.1 Engineering on the SENG Side> 2-21
IM 32S01E10-21E
l Output High LimitSpecify the upper output limit within the range 0.0% to 100.0%.Default: 100.0%
l Output Low LimitSpecify the lower output limit within the range 0.0% to 100.0%Default: 0%
l Output Scale High LimitFixed to 100.0%.
l Output Scale Low LimitFixed to 0.0%.
l Upper Equipment NameSpecify the upper equipment name set on the CENTUM.Default: None
Site-A
Area-1Area-2Area-3Area-4Area-5
020109E.ai
2
Pjt: SCS1009 File:TAG.edf
Upper Equipment Name BOOL/ECW_B ANLGIDINT/REAL/ECW_I/ECW_R
Variable Name
CUR1CUR2
EC_CUR1EC_CUR2THERMO1 THERMO1
Tag Name Level Upper Equipment Name
Area-2Area-2
VEL ANN IO_REAL
Site-B
Figure SettingofUpperEquipmentName
2nd Edition : Dec.15,2008-00
<2.1 Engineering on the SENG Side> 2-22
IM 32S01E10-21E
2.1.5 Engineering for Overriding from HISForoverridingfromHIS,useoneofthefollowingtwotypesoffunctionblocks.
• GroupingOverrideFunctionBlock• OverrideFunctionBlock
Selectoneoftheabovefunctionblocksaccordingtothedatatypeofvariables.
SEE ALSO For more information about the names and details of override function blocks, see the following:
7.2.3, “Forcing and Override” of the Engineering Guide (IM 32S01C10-21E)
n Engineering for Overriding from HIS Theflowofengineeringforoverrideoperationisasfollows:
l GroupingOverrideFunctionBlock1. DefineagroupingoverridefunctionblockinstanceusingDictionaryViewofSCSManager.2. UseMulti-LanguageEditortoplacethegroupingoverridefunctionblockinstancedefinedin
step 1 into the application logic. For the grouping override function block, connect the normal input value to the IN terminal and specify the VAL terminal for the value to be output during override. SettheGroupnumberofgroupingoverridefunctionblockinafixedvaluetotheGRPterminal.
3. UseTagNameBuildertodefineatagnamefortheinstancedefinedinstep1. You can use the tag name to perform grouping override from HIS.
l OverrideFunctionBlock1. DefineanoverridefunctionblockinstanceusingDictionaryViewofSCSManager.2. UseMulti-LanguageEditortoplacetheoverridefunctionblockinstancedefinedinstep1
into the application logic. For the override function block, connect the normal input value to the IN terminal and specify the VAL terminal for the value to be output during override.
3. UseTagNameBuildertodefineatagnamefortheinstancedefinedinstep1. Now, override can be performed from HIS using the tag name.
2nd Edition : Dec.15,2008-00
<2.1 Engineering on the SENG Side> 2-23
IM 32S01E10-21E
n EngineeringforOverridingUsingaPasswordFunctionBlockThefollowingdescribestheflowofengineeringforoverridingusingapasswordfunctionblock:1. DefineapasswordfunctionblockinstanceusingDictionaryViewofSCSManager.2. UseMulti-LanguageEditortoplacethepasswordfunctionblockinstancedefinedinstep1
into the application logic. Connect the output parameter OUT of the password function block to the SW input parameter of the override function block. This allows for enabling/disabling of the override function block from the password function block.
3. InMulti-LanguageEditor,defineapasswordcharacterstringthatwillbeinputfromHISforthe password function block.
4. If necessary, use Resource Editor of SCS Manager to set a password for the POU that contains the password function block created in step 2. This will restrict referencing and printing of the password function block by opening the POU.
5. UseTagNameBuildertospecifyatagnamefortheinstancedefinedinstep1.
SEE ALSO For more information about engineering for Password Function Block, see the following:
C9.10, “SYS_PSWD (Password Function Blocks Management)” of the Safety Control Station Reference (IM 32S03B10-21E)
3rd Edition : Dec.22,2009-00
<2.1 Engineering on the SENG Side> 2-24
IM 32S01E10-21E
2.1.6 SettingsforExchangingDatabetweenFCSandSCSForsettingdatafromFCStoSCS,useSCSlinktransmissionorexternalcommunicationfunctionblock.TheSCSlinktransmissionallowsdataexchangesbetweenFCSandSCS.
SEE ALSO • For more information about SCS link transmission, see the following:
2.9, “SCS Link Transmission” of the Engineering Guide (IM 32S01C10-21E)
A6, “SCS Link Transmission” of the Safety Control Station Reference (IM 32S03B10-21E)
• For more information about the names and details of function blocks, see the following: C8, “External Communication Function Blocks” of the Safety Control Station Reference (IM 32S03B10-21E)
• For more information about the details of data setting from FCS, see the following: D5, “Data Setting Using External Communication Function Blocks” of the Safety Control Station Reference (IM 32S03B10-21E)
n SCSLinkTransmissionTo exchange data between SCS and FCS, APCS, or GSGW, communications data must be assignedtotheSCSlinktransmissionfunctionblock.YoucandefinetheassignmentusingSCSLink Transmission Builder.TheengineeringflowforenablingdataexchangesusingtheSCSLinkTransmissionisasfollows:
SEE ALSO For more information about using SCS Link Transmission Builder, see the following:
5.3,“SCSLinkTransmissionDefinition”oftheEngineeringReference(IM32S04B10-21E)
l EngineeringflowforsendingdatafromSCStoFCS1. OpentheSCSLinkTransmissionBuilder.SelecttheSCSLinkTransmissionDefinitionand
then the Self Station tab. In the tab, set the [Send] to [Yes]. 2. OpentheDictionaryViewintheSCSManager,definetheLTSND(linktransmissiondata
output) function block. 3. IntheSCSLinkTransmissionBuilder,selecttheDataWiringDefinitionandthentheSelf
Station number. DefinetheLTSNDfunctionblockforthebitnumber(bitNo).
4. Open the Multi-Language Editor and place the LTSND function block in the application logic.
2nd Edition : Dec.15,2008-00
<2.1EngineeringontheSENGSide> 2-25
IM 32S01E10-21E
l EngineeringflowforreceivingdatafromFCS1. OpentheSCSLinkTransmissionBuilder.SelecttheSCSLinkTransmissionDefinitionand
thentheSelfStationtab.Inthetab,set[Receive]to[Yes]. IntheOtherStationstab,selectthestationnumberofFCSandset[Type]to[2:FCS].
2. OpentheDictionaryViewintheSCSManager,definetheLTFCS(Interference-freelinktransmissiondatainput)functionblock.
3. IntheSCSLinkTransmissionBuilder,selecttheDataWiringDefinitionandthentheFCSstationnumber. DefinetheLTFCSfunctionblockforthebitnumber(bitNo).
4. OpentheMulti-LanguageEditorandplacetheLTFCSfunctionblockintheapplicationlogic.
ExternalCommunicationFunctionBlocks
l EngineeringFlowThefollowingdescribestheflowofengineeringforsettingdatausinganexternalcommunicationfunctionblock:1. DefineanexternalcommunicationfunctionblockinstanceusingDictionaryViewofSCS
Manager.2. UseMulti-LanguageEditortoinserttheexternalcommunicationfunctionblockinstance
definedinstep1intotheapplicationlogic.3. UseTagBuildertodefineatagnamefortheinstancedefinedin1.
IMPORTANTDonotsetdataperiodicallytoSCSsfromPID,MLDandotherregulatorycontrolblocksorCALCUandotherarithmetic/logiccalculationblocksusingtheinter-stationdatalinkblocks(ADLs)ofFCSs.Doingsocanresultinawritingerror.
SEEALSO Formoreinformationaboutdatasettingthroughatagnameinterface,seethefollowing:
“LimitationsontheNumberofDataSettingRequestsviaTagNameInterfaces”in2.15,“CENTUMIntegration”ofProSafe-RSEngineeringGuide(IM32S01C10-21E)
3rdEdition:Dec.22,2009-00
<2.1 Engineering on the SENG Side> 2-26
IM 32S01E10-21E
2.1.7 Accessing Subsystem’s Data from CENTUMCENTUM can access the subsystem data after the names of the communication input functionblocksandthecommunicationoutputfunctionblocksaredefined.Moreover,CENTUM can set data to the subsystem through the external communication function blocks(ECW_*).
n Reading Subsystem’s Data by CENTUMCENTUM can read data in the subsystem through a tag name interface. You need to assign tag names to the instances of the function blocks for subsystem communication in advance. The communication data read by CENTUM are logical data.
020106E.ai
CENTUM
Subsystem
SCI_B SCO_B
POU(Interference-free)
SCS
Access by tag names
Mapping Elements(tag name)
Communicationdata area
Logical Data
Physical Data
Copy
CENTUM Integration
Figure ReadingSubsystem’sDatabyCENTUM
2nd Edition : Dec.15,2008-00
<2.1 Engineering on the SENG Side> 2-27
IM 32S01E10-21E
n Setting Subsystem’s Data by CENTUMThrough the external communication function block (ECW_*), CENTUM can set data in the subsystem through a tag name interface. The logic between the external communication function blocks and the subsystem communication output function blocks needs to be created.
IMPORTANTDo not frequently set data from CENTUM to the subsystem through the external communication function blocks using tag name interfaces. Doing so can result in a writing error.
SEE ALSO • For more information about setting data using tag name interfaces, see the following:
“n Limitations on the Number of Data Setting Requests via Tag Name Interfaces” in 2.15, “CENTUM Integration” of ProSafe-RS Engineering Guide (IM 32S01C10-21E)
• For more information about external communication function blocks, see the following:C8, “External Communication Function Blocks” of the Safety Control Station Reference (IM 32S03B10-21E)
020105E.ai
CENTUM
Subsystem
ECW_B SCO_B
SCS
POU(Interference-free)
External Communication Function
Figure SettingSubsystem’sDatabyCENTUM
3rd Edition : Dec.22,2009-00
<2.1 Engineering on the SENG Side> 2-28
IM 32S01E10-21E
2.1.8 Plant HierarchyThe Plant hierarchy shows the equipment and devices on a control system in a hierarchicalstructureconformingtothephysicalmodelspecifiedintheISAS88.01.FunctionblocksnamedfromtheTagNameBuilderontheProSafe-RScanberegisteredasequipmentobjectsinthePlanthierarchyontheControlsystem.HISiscapableoffilteringprocessalarmsbasedontheplanthierarchyandofdisplayingprocessalarmsforanyequipmentobject.
SEE ALSO For more details on the Plant Hierarchy, see the following:
“n Plant Hierarchy” in D1, “Integration with CENTUM” of the Safety Control Station Reference (IM 32S03B10-21E)
E10, “Plant Hierarchy” of the CS 1000/CS 3000 Reference Human Interface Station (IM 33S01B30-01E)
E7, “Plant Hierarchy” of the CENTUM VP Reference Human Interface Station (IM 33M01A30-40E)
l Plant hierarchy engineering1. Setting Upper equipment names for SCS station
WhenanewSCSisdefinedfromtheSystemViewontheCENTUMENG,theequipmentobject of SCS is automatically registered in the Plant hierarchy.
Open the SCS Properties from the System View on the CENTUM ENG to specify the name of the Upper equipment name than SCS.
2. Setting Upper equipment name for SCS tag name TheupperequipmentnameforeachMappingBlock/ElementonSCScanbespecifiedfromtheTagNameBuilder.ThespecifiableUpperequipmentnamesarelimitedtothose(Customequipmentname)definedfromthePlantHierarchyBuilderontheCENTUM.Youcannot specify the default equipment name.
3. DefiningUpperequipment Use the Plant Hierarchy Builder on the CENTUM ENG.
020110E.ai
SCS 01 SCS 02
Upper equipment 3(Custom equipment)
Upper equipment 1(Custom equipment)
Upper equipment 2(Custom equipment)
Mapping block/element
Mapping block/element
Mapping block/element
Mapping block/element
3. Defining Upper equipment CENTUM Plant Hierarchy Builder
1. Setting Upper equipment name for SCS CENTUM System View SCS Properties
2. Setting Upper equipment name for SCS tag name ProSafe-RS Tag Name Builder
Engineering functions to be usedStructure
Figure ExampleofSCSPlantHierarchy
SEE ALSO For more details on the Plant Hierarchy engineering, see the following:
E10.2, “Plant Hierarchy Engineering” of the CS 1000/CS 3000 Reference Human Interface Station (IM 33S01B30-01E)
E7.2, “Plant Hierarchy Engineering” of the CENTUM VP Reference Human Interface Station (IM 33M01A30-40E)
2nd Edition : Dec.15,2008-00
<2.1 Engineering on the SENG Side> 2-29
IM 32S01E10-21E
2.1.9 SaveandDownloadOperationMarksTheoperationmarkssetontheHISforthetagscanbesavedinSENG.ThesavedoperationmarkscanbedownloadedtotheSCS.
l SaveOperationMarks• The operation marks for the tagged elements and annunciators can be saved.
• The operation marks can be saved by SCS Manager at any time. The dialog box that prompts for saving the operation marks will be displayed before Off-line Download, Master Database Off-line Download and SCS Restart. On the dialog box, choose [Yes], then the operation marks will be saved.
l ProcedureofSavingOperationmarks1. On SCS Manager, choose [Tools] - [Controller] - [Save Operation Marks] to start.2. Then,adialogboxwillbedisplayedforconfirmationofsavingtheoperationmarks.Click
[Yes], then saving will start with a progress bar.
l DownloadOperationMarks• The saved operation marks of the tagged data and annunciators can be downloaded.
• Only the saved operation marks of the tag names that are consistent with the tag names intheSCScanbedownloaded.Ifthetagnamesaremodifiedaftersavingtheoperationmarks, the operation marks of the inconsistent tag names will not be downloaded.
IMPORTANT• When Off-line Download, Master Database Off-line Download, SCS manual restart or
SCS auto restart after power failure is performed; the operation marks in the SCS will be initialized. When performing the above operations (except SCS auto restart after power failure), a dialog box will be displayed prompting for saving the operation marks.
• For Off-line Download or Master Database Off-line Download, when SCS shifts to Waiting mode,itisnecessarytosetsecuritypasswordfirstandthendownloadtheoperationmarks.
• For SCS Restart, downloading the operation marks should be performed after the SCS shifts to Waiting mode.
l ProcedureofdownloadOperationmarks1. On SCS Manager, choose [Tools] - [Controller] - [Download Operation Marks] to start.2. Then,adialogboxwillbedisplayedforconfirmationofdownloadingtheoperationmarks.
Click [Yes], then download will start with a progress bar.
1st Edition : May 30,2008-00
<2.2 Engineering on the CENTUM Side> 2-30
IM 32S01E10-21E
2.2 Engineering on the CENTUM SideThissectiondescribesengineeringtasksperformedontheCENTUMside,oneofthetasksrequiredtoconnectanSCSprojectandaCENTUMproject.
2.2.1 SCS CreationToconnecteachSCSprojecttoaCENTUMproject,acorrespondingSCSmustbecreatedinCENTUMSystemViewfirst.
n Creating an SCSCreate SCSs on CENTUM System View. The procedure is explained below:
Select [File] - [Create New] - [SCS (E)] in System View. The New Station dialog box appears.
Type
020201E.ai
Create SCS
CancelOK
Station TypeSSC10D-S Duplexed standard type safety control unit
Type
Domain Number
Station Address
Station Comment
Station Number
1
4
Number
Component
SCS
Alias of Station
Station Status Display
Upper
Figure DisplayExampleoftheNewStationDialogBox(TypeTab)
TIPDo not select “SCS01 Safety Control Station” as the station type.
2nd Edition : Dec.15,2008-00
<2.2 Engineering on the CENTUM Side> 2-31
IM 32S01E10-21E
Thefollowingdescribestheitemsdefinedineachtab.
n DefinitionItemsintheTypeTabThefollowingdescribestheitemsdefinedinTypetab.Thestationtypeandstationaddressaremandatory.
l Station Type Select the station type from the following choices:[SSC60D-S Duplexed Safety Control Unit (for Vnet/IP, Standard Type)] [SSC60D-F Duplexed Safety Control Unit (for Vnet/IP, Wide Range Temperature Type)] [SSC60S-S Safety Control Unit (for Vnet/IP, Standard Type)] [SSC60S-F Safety Control Unit (for Vnet/IP, Wide Range Temperature Type)] [SSC50D-S Duplexed Safety Control Unit (for Vnet/IP, Standard Type)] [SSC50D-F Duplexed Safety Control Unit (for Vnet/IP, Wide Range Temperature Type)] [SSC50S-S Safety Control Unit (for Vnet/IP, Standard Type)] [SSC50S-F Safety Control Unit (for Vnet/IP, Wide Range Temperature Type)] [SSC10D-S Duplexed Safety Control Unit (Standard Type)] [SSC10D-F Duplexed Safety Control Unit (Wide Range Temperature Type)] [SSC10S-S Safety Control Unit (Standard Type)] [SSC10S-F Safety Control Unit (Wide Range Temperature Type)]
l Station Address Set the station address. A station address consists of a domain number and a station number. Although any domain number from 1 to 31 can be set for a ProSafe-RS station, set only a value between 1 and 16 when the station is used in the CENTUM integration structure. The default domain number is the number set in the applicable project. The station number should be set between 1 and 64. The default station number is the next available blank number found in a search in ascending order from 1. Once a station address is set, it cannot be changed.The only way to change the station address is to delete the existing station and then create a new one with new address.
l Component Number You can set a component number between 0 and 9999. The setting of component number may be omitted.
l Station Comment You can set a comment for the station. The setting of station comment may be omitted. Set the comment using up to 24 single-byte or 12 double-byte characters.
l Station Alias NameYou can set an alias for the station. When an alias is set, all names of the station displayed on an HIS will be replaced by the alias. Set the alias using up to eight single-byte alphanumeric characters.
l Station Status Display Set the name of the window you want to display on an HIS in place of the Station Status Display view. The name of the Station Status Display view is set using up to 16 single-byte alphanumeric characters. Double-click the SCS icon in the System Status Overview view to display the window set here.
3rd Edition : Dec.22,2009-00
<2.2 Engineering on the CENTUM Side> 2-32
IM 32S01E10-21E
l Upper Equipment Name Specify the name of the equipment located in a level above the station. The upper equipment name should use the corresponding equipment name set in Plant Hierarchy Builder. WhenanewSCSisdefined,anSCSequipmentobjectisregisteredintheplanthierarchyautomatically.DifferentequipmentcanbespecifiedforeachMappingBlocks/ElementsoftheSCS.
SEE ALSO For more information about Plant Hierarchy Builder, see the following:
E10.2.2, “Registering Custom Equipment (Other than Unit Equipment)” of the CS 1000/CS 3000 Reference Human Interface Station (IM 33S01B30-01E)
E7.2.2, “Registering Custom Equipment (Other than Unit Equipment)” of the CENTUM VP Reference Human Interface Station (IM 33M01A30-40E)
n DownloadingtheProjectCommonIn the engineering of HISs and FCSs in a CENTUM project, the common items in the project are definedastheprojectcommon(COMMON).Thedefinitionsintheprojectcommonaresharedbyall HISs and FCSs in the same CENTUM project. Accordingly, modifying the project common will alsomodifythecorrespondingHIS/FCSdefinitions.In the CENTUM integration structure, the project common is used to build a system for operating and monitoring SCSs from HISs.
TIPChanging the project common of a CENTUM project will not affect SCS applications. Therefore, reengineering is not required on an SENG after the project common has been changed.
2nd Edition : Dec.15,2008-00
<2.2 Engineering on the CENTUM Side> 2-33
IM 32S01E10-21E
2.2.2 SCS Taglist Generation Toaccessmappingblocks/elementsonanSCSfromanHISusingthecorrespondingtagnamesdefinedinProSafe-RSTagNameBuilder,ataglistfortheSCSmustbegeneratedon the CENTUM side. CENTUM taglists are generated using the Taglist Generation FunctionincludedintheCENTUMEngineeringFunction.
n Generating SCS Taglist on CENTUM Launch Taglist Generation Function from System View. 1. In System View, select the SCS you want to generate a taglist for. 2. Select [Tools] - [SCS Taglist Import] from the menu.
An HIS taglist is generated.
TaglistGenerationFunctiongeneratesanHIStaglistbasedonthecorrespondingSCStaglistfilegenerated in the Engineering Function of the ProSafe-RS. If the CENTUM project is the current project, the taglist is downloaded to the HIS. The result of Taglist Builder operation appears in the message area of System View.
l Engineering Unit Symbol and Switch Position Label Keep the engineering unit symbol and switch position label modes to AUTO while generating a SCS taglist. When an SCS taglist is generated in the MANUAL model, if engineering unit symbols and switch position labels not present in the CENTUM project are included in the engineering information (taglist, etc.) of the SCS, they will not be registered in the CENTUM project, and a warning message appears as a result. In this case, register the engineering unit symbols and switch position labels that generated the warning message in the respective builders, and then generate a taglist again.
SEE ALSO For more information about Engineering Unit Symbol and Switch Position Label, see the following:
F1.2, “Creating a New Project” of the CS1000/CS3000 Reference Engineering (IM 33S01B30-01E)
F2.2, “Creating a New Project” of the CENTUM VP Reference Engineering (IM 33M01A30-40E)
2nd Edition : Dec.15,2008-00
<2.2 Engineering on the CENTUM Side> 2-34
IM 32S01E10-21E
n Downloading a Taglist Each generated taglist can be downloaded to an HIS that requires it. Taglists can be downloaded using the TagList Down Load dialog box called from System View.
l Taglist Download Operation 1. Select [Load] - [Download Tag-List] in System View. The TagList Down Load dialog box
appears.
020202E.ai
TagList Down Load
Equalize Close
ALL
Tag List Station
ALL
Equalize To Station
FCS0101FCS0102FCS0103FCS0104SCS0105SCS0105
HIS0163HIS0164
Project
MYPJT View
Reference project : MYPJT
HIS which downloads a tag list
SCS name
Figure DisplayExampleoftheTagListDownLoadDialogBox
2. Select the desired project, and then click the [View] button. A list of stations appears.
3. Select the SCS, and the HIS you want to download the taglist to, and then click the [Equalize] button. The generated taglist is downloaded to the selected HIS.
l Cautions after downloading databaseIntheCENTUMintegrationstructure,ifadatabaseisdownloaded(offlineoronline-change)fromthe SENG to SCS, be sure to generate a SCS Tag List from the System View on the CENTUM ENG.Otherwise,databasesonHISorExaopcconflict,andtriggerasystemalarmmessageprompting you to equalize the database in the startup process of HIS or Exaopc.
2nd Edition : Dec.15,2008-00
<2.2 Engineering on the CENTUM Side> 2-35
IM 32S01E10-21E
2.2.3 Other Builders ToconnectSCSprojectwithCENTUMproject,thefollowingbuildersandviewerarerequired.
• OperationMarkBuilder• Plant Hierarchy Builder• Plant Hierarchy Viewer• FCSConstantsBuilder
n OperationMarkBuilderSetting operation marks using Operation Mark Builder of the CENTUM ENG allows the assignment of tag with comment in the instrument faceplate or the change of operation privileges over mapping blocks/elements. ThedefinitionssetinOperationMarkBuilderareusedcommonlybyallFCSs,HISsandSCSsinthe CENTUM project. IfanoperationmarkisaddedormodifiedinOperationMarkBuilder,theactionoftheoperationmarkonHISswillchangeoncetheaddition/modificationisdownloadedtotheHISs.
SEE ALSO For more information about operation marks, see the following:
F9.5, “Operation Mark” of the CS 1000/CS 3000 Reference Engineering (IM 33S01B30-01E)
F3.5, “Operation Mark” of the CENTUM VP Reference Engineering (IM 33M01A30-40E)
IMPORTANT• The initial value of operation marks for mapping blocks/elements is 0 (no operation mark).
When the SCS is restarted, the setting of operation marks will return to the initial value.
• An off-line download (or master database off-line download) to the SCS will cause the setting of operation marks to return to the initial value.
SEE ALSO For how to restore the operation marks, see the following:
2.1.9, “Save and Download Operation Marks”
• Valuescannotbespecifiedforoperationmarksformappingblocks/elementsusingtheProSafe-RS Engineering Function.
• Operation mark values cannot be changed using the SCS application logic.
2nd Edition : Dec.15,2008-00
<2.2 Engineering on the CENTUM Side> 2-36
IM 32S01E10-21E
n Plant Hierarchy BuilderUse the Plant Hierarchy Builder for registering Custom equipment. To activate the Plant Hierarchy Builder, start from the System View window on the CENTUM ENG: From the List View, select [Common] - [Custom Plant].
020204E.ai
Ready
Message
Upper Equipment
Position Line 1 Column 3
File Edit View Tools Window Help
No.
Plant Hierarchy Builder - [Pjt:MYPJT-X File:CustomPlant.edf]
Equipment ID12345678910111213141516171819
Equipment name Comment Equipment Format Upper Equipment Name
Figure PlantHierarchyBuilder
2nd Edition : Dec.15,2008-00
<2.2 Engineering on the CENTUM Side> 2-37
IM 32S01E10-21E
n Plant Hierarchy ViewerInthePlantHierarchyViewer,youcanconfirmtheCustomequipmentnameregisteredfromthe Plant Hierarchy Builder. The Plant Hierarchy Viewer shows the plant hierarchy of the entire projects. From the menu on the System View window on the CENTUM ENG, select [Tool] - [Plant Hierarchy Viewer]. SCS tags are shown in the Plant Hierarchy Viewer window.
TIPThe version of CENTUM must be R3.08 or higher. The SCS tag is not shown in the version R3.07 or lower.
-
Plant Hierarchy Viewer [Pjt:PJT01]
020203E.ai
+
PJT01
FCS0615STN0101SCS0102FCS0103
-%AN0001%AN0002%AN0003%AN0004%AN0005TAG-PID-02TAG-PID-03TAG-PID-04TAG-PID-05TAG-PID-06
----------
---
AN Message 1AN Message 2AN Message 3AN Message 4AN Message 5
%AN/%AN%AN/%AN%AN/%AN%AN/%AN%AN/%AN%BL/PID%BL/PID%BL/PID%BL/PID%BL/PID
SCS0102SCS0102SCS0102SCS0102SCS0102SCS0102SCS0102SCS0102SCS0102SCS0102
NUMReady
+
File Edit View Tools Window Help
Equipment name Equipm... StatusEquipment Comment Equipment Format Upper EquipmentSelected Hierarchy: ROOT Open Folder: PJT01
Figure ExampleofPlantHierarchyViewerinR3.08
SEE ALSO For more details on the Plant Hierarchy Viewer, see the following:
E10.3, “Plant Hierarchy Viewer” of the CS 1000/CS 3000 Reference Human Interface Station (IM 33S01B30-01E)
E7.3, “Plant Hierarchy Viewer” of the CENTUM VP Reference Human Interface Station (IM 33M01A30-40E)
n FCSConstantsBuilderIfSCSexchangesdatawithFCSusingtheSCSlinktransmission,setpresentstationdefinitionandstationdefinitionofscantransmissiondefinition.The SCS data that can be referenced at FCS are %GS001 to %GS128.
SEE ALSO For more details about FCS Constants Builder, see the following:
“nScanTransmissionDefinitions”inA4.2,“GlobalSwitch”oftheCS1000/CS3000ReferenceFieldControl Station Basics (IM 33S01B30-01E)
“nScanTransmissionDefinitions”inA4.2,“GlobalSwitch”oftheCENTUMVPReferenceFieldControlStation Basics (IM 33M01A30-40E)
2nd Edition : Dec.15,2008-00
<2.2 Engineering on the CENTUM Side> 2-38
IM 32S01E10-21E
2.2.4 Items to Note on CENTUM EngineeringThis section describes the items to be noted in CENTUM engineering.
n Software I/Os Supported on SCSAmong the various software I/Os of CENTUM FCS, common switches and annunciators can be used on SCS.
l Common Switches The SCS common switches having an element number between %SW0001 and %SW0400 aresystemcommonswitches.Thesystemcommonswitchesareelementshavingapredefinedpurpose,suchasidentificationofSCSstatus.AllcommonswitchesofSCSsaresystemcommonswitches. TagnamescannotbedefinedforSCScommonswitches.Also,valuescannotbesetincommonswitches.
SEE ALSO For more information about the content of each SCS common switch element number, see the following:
“l Common Switches (Common Switches for System)” in “n Software Inputs/Outputs” in D1, “Integration with CENTUM” of the Safety Control Station Reference (IM 32S03B10-21E)
l Annunciators Annunciators are used as mapping elements for ANN and ANN_FUP function blocks. Each messagecanbedefinedusingupto80single-byteor40double-bytecharacters.
n DataSettingfromFCStoSCSUsing SFC (Sequential Function Chart) can set data from FCS to SCS. All the SCS data are accessible by assigning the tag names to the mapping elements on the Tag Name Builder of SENG. And the SCS data can be written from FCS by assigning the data to the external communication function blocks.
SEE ALSO For more information about data setting, see the following:
• 2.1.6, “Settings for Exchanging Data between FCS and SCS”
• D5.1,“ConfirmationofSettingData”oftheSafetyControlStationReference(IM32S03B10-21E)
• “l Communication between FCS and SCS” in “n Functions in CENTUM Integration Structure” in 2.15, “CENTUM Integration” of the Engineering Guide (IM 32S01C10-21E)
3rd Edition : Dec.22,2009-00
<2.3 Tests in the CENTUM Integration Structure> 2-39
IM 32S01E10-21E
2.3 Tests in the CENTUM Integration StructureThefollowingtwotypesoftestsbetweenSCSandFCS/HISintheCENTUMintegrationstructure are available.
• Target test using the target SCS• SCS simulation test with the CENTUM virtual test combined
n Target Tests in the CENTUM Integration Structure The target tests in the CENTUM integration structure are conducted with a CENTUM target test environment combined.
ENGSENG
SCS FCSCommunication between SCS and CENTUM
Control Bus
CENTUMPJT
System View
SCSManager
Test Te
st
Test
Test
020301E.ai
SCSPJT
HIS
Figure TargetTestsintheCENTUMIntegrationStructure
IMPORTANTIf you use the application debug function in the target tests, set the SCS security level to “Level 0.”To return to the online level after the target tests, an off-line download has to be executed.
SEE ALSO For more information about target test, see the following:
4, “Target Tests” of the ProSafe-RS System Test Reference (IM 32S04B30-21E)
2nd Edition : Dec.15,2008-00
<2.3 Tests in the CENTUM Integration Structure> 2-40
IM 32S01E10-21E
n SCS Simulation Tests in the CENTUM Integration StructureIn the SCS simulation tests, you can test using an SCS simulator instead of the target SCS.
020302E.ai
CENTUM
PC
Creation
Creation
Operation andMonitoring Function
Test Function
CENTUMProjectDataStandard Builder
Function
Safety System Generation
and Maintenance
CENTUM VP/CS 3000 Integration
Engineering
ProSafe-RS
Copy
Databasefor
SCSSimulator
Figure SCSSimulationTestsintheCENTUMIntegrationStructure
SEE ALSO For more information about SCS simulation test, see the following:
3.6, “Testing CENTUM Integration in Virtual Tests” of the ProSafe-RS System Test Reference (IM 32S04B30-21E)
2nd Edition : Dec.15,2008-00
<3. Operation and Monitoring of Safety Systems Using HIS> 3-1
IM 32S01E10-21E
3. Operation and Monitoring of Safety Systems Using HIS
In the CENTUM integration structure, HIS can operate and monitor SCS data through tag namesinthesameinterfaceasthatofFCSdata.BecauseSCSapplicationlogiciscreatedwithIEC61131-3language,itisnecessarytodefinemappingblocks/elementsintheSCSand assign tag names with Tag Name Builder to realize the tag name interface. In addition, it is possible to monitor the SCS status and alarms by HIS standard windows.
SEE ALSO For more information about mapping blocks/elements, see the following:
D2, “Tag Name Interfaces for CENTUM” of the Safety Control Station Reference (IM 32S03B10-21E)
n Overview of Safety System Operation and Monitoring Using HISIn the CENTUM integration structure, an HIS can operate and monitor SCS in the following manners:
• Operate and monitor SCS data using tag names via the same interface used for operating and monitoring FCS data. Data can be referenced using the instrument faceplate, and SCS data can be displayed in the Graphic view.
• Monitor in HIS’s Process Alarm view both occurrence and recover of process alarms and annunciators detected by SCSs.
• Monitor in HIS’s System Alarm view all system alarms occurred on SCS.
• Display in HIS’s SCS Station Status Display view the operating status of SCS.
n Windows Used for Operation and Monitoring of SCSThe following HIS windows are used for operation and monitoring of SCS.
Table Windows Used for Operation and Monitoring of SCS
Window name Description System Alarm view Check system alarms generated on SCSs
Process Alarm view Check process alarms and annunciator messages generated on SCSs
SCS Station Status Display view Monitor the operating status of SCSs
Instrument faceplate Operate and monitor SCSs using the instrument faceplates of mapping blocks/elements
Graphic view Monitor the data of mapping blocks/elements
The following functions can be implemented from an HIS by using the above windows: • Learn SCS alarms in real time
• Check the status of each SCS controller
• Perform maintenance override of SCSs from an HIS
2nd Edition : Dec.15,2008-00
<3. Operation and Monitoring of Safety Systems Using HIS> 3-2
IM 32S01E10-21E
n Items to Note on On-line Change While operating a grouping override function block, override function block, or password function block from an HIS, do not perform on-line change download.Even if the target of operation from the HIS is a function block or mapping block not subject to online change, the override operation itself may generate an error. In this case however, the on-line change communication will not be affected. Wait for the communication for online change to end, and then operate the grouping override function block, override function block or password function block again.
l ErrorNotificationMethodWhenanyoperationfromHISgeneratesanerrorduringon-linechangedownload,itisnotifiedinthe following ways: • Notificationbyasystemalarm
• Notificationbyananswerbackerroralarmfromthetagnameoftheapplicablemappingblock(basedonnotificationenablingspecificationinTagBuilder)
SEE ALSO FormoreinformationaboutthedefinitionoftheanswerbackerrorinTagBuilder,seethefollowing:
“nSettingItems”in2.1.4,“DefinitionofTagNames”
1st Edition : May 30,2008-00
<3.1 Windows Used in SCS Operation and Monitoring> 3-3
IM 32S01E10-21E
3.1 Windows Used in SCS Operation and Monitoring
This section describes the primary windows used in the operation and monitoring of SCSs from an HIS.
3.1.1 System Alarm View The System Alarm view displays a list of diagnostic information messages that notify hardware and communication errors in the system as system alarm messages. The systemalarmmessagesarepredefinedinthesystem.
SEE ALSO For more information about the System Alarm view, see the following:
E7.2, “System Alarm Window” of the CS 1000/CS 3000 Reference Human Interface Station (IM 33S01B30-01E)
E4.2, “System Alarm View” of the CENTUM VP Reference Human Interface Statio (IM 33M01A30-40E)
n Overview of the System Alarm View TheSystemAlarmviewdisplaysandmanagesthesystemalarminformationnotifiedbySCSsand FCSs as system alarm messages. Both SCS and FCS system alarm messages can be displayed in the same window. When an SCS detects an error by its diagnostic functions, the SCS issues a system alarm message. When the error is recovered, a recovery message is issued. Each SCS also issues asystemalarmasaconfirmationofanoperationperformedtotheSCS,suchassecuritylevelchange or forcing of variables. The System Alarm view displays these messages as system alarms. An overview of the System Alarm view is summarized below: • WhenanalarmhasoccurredinSCS,the[SCSAlarmoccurrenceNotification]buttononthe
toolbar changes to notify the occurrence of an SCS alarm. When the button is clicked, the messageisdisplayedafterbeingfilteredbythe[SafetyControlStation]filter.
• Once the operator acknowledges the system alarm, the system alarm message will stop flashing.
• When the system alarm is cleared, the corresponding system alarm message is deleted from the window.
• The corresponding alarm class information managed by the SCS is displayed together with each system alarm.
• SystemalarmmessagesgeneratedonSCSscanbefilteredintoaseparategroupfordisplay. This function allows for easy distinction of SCS alarms from FCS alarms even when a large number of system alarm messages have been generated on FCSs.
• IfSCSalarmsarepresent,callingtheSystemAlarmviewwillautomaticallyfilterthealarmmessagesbythe[SafetyControlStation]filterbeforethewindowisdisplayed.
2nd Edition : Dec.15,2008-00
<3.1 Windows Used in SCS Operation and Monitoring> 3-4
IM 32S01E10-21E
n Selection of Display ItemsCall the Window Setting dialog box from the applicable tool button in the System Alarm view. Whenthisdialogboxisfirstopened,the[Item]checkboxisunchecked.Checkingthisboxwillenable the selection of items you want to display in the System Alarm view.
CancelOK
030101E.ai
Window Setup
Item
No.
MsgNo
Level
Message
Date
Figure WindowSetupDialogBox
The following table shows the default display items in the System Alarm view and items whose display attribute (displayed/not displayed) can be selected:
Table Display Items in the System Alarm View
Display item name Default window setting Selection Item Displayed Permitted
MsgNo Displayed Permitted
Date Displayed Not permitted
Level (*1) Not displayed Permitted
Message Displayed Not permitted
*1: The displayed level corresponds to the SCS alarm class (1 to 4).
2nd Edition : Dec.15,2008-00
<3.1 Windows Used in SCS Operation and Monitoring> 3-5
IM 32S01E10-21E
n Split Display The System Alarm view can be displayed into two frames. Whenafilterisset,theviewissplithorizontally,withthemessagesmatchingthefilterconditiondisplayed in the top frame and all messages displayed in the bottom frame.
Date Level Message 1 0303 07/25 14:11:58 2 SCS0101 Number of Overrides Exceeds the Limit=3
030102E.ai
.SA System Alarm Message
Ready
HELP
Date Level Message 1 0303 07/25 14:11:58 2 SCS0101 Number of Overrides Exceeds the Limit=3 2 0451 07/25 14:12:57 FCS0102 RIGHT Control 3 0001 07/25 14:12:57 FCS0102 RIGHT ManualReset Start 4 0011 07/25 14:12:57 FCS0102 RIGHT Fail (SW STOP Code=0000 0000) 5 0304 07/25 14:12:54 FCS0102 Recover 6 0303 07/25 14:12:58 FCS0102 Fail
1/1 6/6Range:STN name:SCS0101
MsgNo
MsgNo
Figure SplitDisplayoftheSystemAlarmView
SEE ALSO For more information about the split display of the System Alarm view, see the following:
“n Splitting System Alarm Window” in E7.2.3, “System Alarm Message Search and Display” of the CS 1000/CS 3000 Reference Human Interface Station (IM 33S01B30-01E)
“n Splitting System Alarm View” in E4.2.3, “Filter and Display System Alarm Messages” of the CENTUM VP Reference Human Interface Station (IM 33M01A30-40E)
2nd Edition : Dec.15,2008-00
<3.1 Windows Used in SCS Operation and Monitoring> 3-6
IM 32S01E10-21E
n SpecificationofSystemAlarmFiltersThefollowingfilterscanbespecifiedintheSystemAlarmview:
• All All system alarm messages are displayed.
• Station Name System alarm messages generated in the selected station are displayed.
• Current Station Alarm messages generated in the current station are displayed.
• Safety Control Station System alarm messages generated on SCS are displayed. AllProSafe-RSSCSsbecomethetargetoffiltering.
CancelOK
All
Station Name
Current Station
Safety Control Station
FCS0101
030103E.ai
Filter
Range
Figure SystemAlarmFilterSettingDialogBox
2nd Edition : Dec.15,2008-00
<3.1 Windows Used in SCS Operation and Monitoring> 3-7
IM 32S01E10-21E
3.1.2 Process Alarm View The Process Alarm view displays process alarms including annunciator messages.
SEE ALSO For more information about the Process Alarm view, see the following:
E4.6, “Process Alarm Window” of the CS 1000/CS 3000 Reference Human Interface Station (IM 33S01B30-01E)
E3.6, “Process Alarm View” of the CENTUM VP Reference Human Interface Station (IM 33M01A30-40E)
n Overview of the Process Alarm ViewTheProcessAlarmviewdisplaysandmanagestheprocessalarminformationnotifiedbySCSsand FCSs as process alarm messages and annunciator messages.• WhenaprocessalarmhasoccurredinSCS,the[SCSAlarmoccurrenceNotification]
button display on the toolbar changes to notify the occurrence of an SCS alarm. When the [SCSAlarmoccurrenceNotification]buttonisclicked,themessageisdisplayedafterbeingfilteredbythe[SafetyControlStation]filter.
• SCS process alarms can be acknowledged and deleted in the Process Alarm view. Acknowledging or deleting an SCS process alarm on an HIS will change the corresponding process alarm information managed on the SCS.
• ProcessalarmmessagesoccurredinSCSscanbefilteredintoaseparategroupfordisplay.This function allows for easy distinction of SCS alarms from FCS alarms even when a large number of process alarm messages have been generated on FCSs.
• IfSCSalarmsarepresent,callingtheProcessAlarmviewwillautomaticallyfilterthealarmmessagesbythe[SafetyControlStation]filterbeforethewindowisdisplayed.
2nd Edition : Dec.15,2008-00
<3.1 Windows Used in SCS Operation and Monitoring> 3-8
IM 32S01E10-21E
n Selection of Display ItemsCall the Window Setting dialog box from the applicable tool button in the Process Alarm view. Whenthisdialogboxisfirstopened,the[DisplayItemname]checkboxisunchecked.Checkingthis box will enable the selection of items you want to display in the Process Alarm view.
CancelOK
030104E.ai
Window Setup
Item
Display order number
Date
Level
Message
Figure WindowSettingDialogBox
The following table shows the default display items in the Process Alarm view and items whose display attribute (displayed/not displayed) can be selected:
Table Display Items in the Process Alarm View
Display item name Default window setting Selection Display order number Displayed Permitted
Date Displayed Not permitted
Level (*1) Not displayed Permitted
Message Displayed Not permitted
*1: The displayed level corresponds to the alarm priority level.
2nd Edition : Dec.15,2008-00
<3.1 Windows Used in SCS Operation and Monitoring> 3-9
IM 32S01E10-21E
n Split Display The Process Alarm view can be displayed into two frames. Whenafilterisset,theviewissplithorizontally,withthemessagesmatchingthefilterconditiondisplayed in the top frame and all messages displayed in the bottom frame. However, if an alarm priorityfilterisselectedintheAlarmtabontheHISSetupwindow,boththetopandbottomframesdisplayonlythemessagesofthespecifiedpriorities.
Date Level Message 1 07/25 15:05:32 2 SIS1000 Flow Control NR 2 07/25 15:05:32 2 SIS1000 Flow Control LO 3 07/25 15:05:30 2 SIS1000 Flow Control LO
030105E.ai
.AL SIS1000 Process Alarm
Ready
Date Level Message 1 07/25 15:05:32 2 SIS1000 Flow Control NR 2 07/25 15:05:32 2 SIS1000 Flow Control LO 3 07/25 15:05:30 2 SIS1000 Flow Control LO 4 07/25 15:05:45 2 TIC1000 Primary Temperature Control NR 5 07/25 15:05:45 2 TIC1000 Primary Temperature Control LO 6 07/25 15:05:43 2 TIC1000 Primary Temperature Control LO
3/3 6/6Type:AllRange:Tag name:SIS1000
1.0m3/s
Figure SplitDisplayoftheProcessAlarmView
SEE ALSO For more information about the split display of the Process Alarm view, see the following:
“n Splitting Process Alarm Window” in E4.6.3, “Process Alarm Message Search and Display” of the CS 1000/CS 3000 Reference Human Interface Station (IM 33S01B30-01E)
“n Splitting Process Alarm View” in E4.6.3, “Filter and Display Process Alarm Messages” of the CENTUM VP Reference Human Interface Station (IM 33M01A30-40E)
2nd Edition : Dec.15,2008-00
<3.1 Windows Used in SCS Operation and Monitoring> 3-10
IM 32S01E10-21E
n Search and Display of Process Alarm Messages Process alarm messages and annunciator messages can be searched using the keywords specifiedbelow.
l SearchRangeSpecification• All
All process alarm messages and annunciator messages are displayed.
• FCS Name Process alarm messages and annunciator messages generated in the selected control station are displayed.
• Plant Hierarchy Name Process alarm messages and annunciator messages generated in the selected control drawing name or unit instrument tag name are displayed.
• Tag Name Processalarmmessagesandannunciatormessagesrelatingtothespecifiedfunctionblockare displayed.
• Batch ID ProcessalarmmessagesandannunciatormessagesrelatingtothespecifiedbatchIDaredisplayed.
• Safety Control Station Process alarm messages and annunciator messages generated on SCSs are displayed. AllProSafe-RSSCSsbecomethetargetoffiltering.
l Search Types• All
Process alarm messages and annunciator messages are displayed.
• Function Block Only Only process alarm messages are displayed.
• Annunciator Only Only annunciator messages are displayed.
CancelOK
All
Function Block Only
Annunciator Only
Filter
Type
FCS0101
%DR0001S010101
Range
All
FCS Name
Equipment Name
Tag Name
Batch ID
Safety Control Station
...
030106E.ai
Figure AlarmFilterSettingDialogBox
1st Edition : May 30,2008-00
<3.1 Windows Used in SCS Operation and Monitoring> 3-11
IM 32S01E10-21E
3.1.3 InstrumentFaceplateInstrumentfaceplatesdisplaystatusesanddataoffunctionblocks,mappingblocks,andelementsassignedontheTagNameBuilder.InstrumentfaceplatesofSCSandFCSaredistinguished by the color of the markinthebottomofthefaceplate.
IMPORTANTThe operator must utilize the SCS instrument faceplate mainly for monitoring. Follow the predefinedproceduretooperateanSCSinstrumentfaceplate.
n InstrumentFaceplateDisplayMapping blocks can be called from an HIS as the instrument faceplate. The function block types are displayed as follows (corresponding mapping block types are shown after the colon “:”).
• BOOL/ECW_B, DINT/ECW_I, REAL/ECW_R, IO_REAL, SCI_B, SCO_B, SCI_I, SCO_I, SCI_R, SCO_R : %WB
• IO_BOOL : %Z
• ANN, ANN_FUP : %AN
• ANLG_S : S_ANLG_S
• ANLGI : S_ANLGI
• VEL : S_VEL
• OVR_B, OVR_I, OVR_R, OVR_IB, OVR_IR : S_OVR_B, S_OVR_I, S_OVR_R, S_OVR_IB, S_OVR_IR
• PASSWD : S_PASSWD
030107E.ai
ON
PV
WB - DIGITALBit Data
0
OFF
PV %
ANLG_SANLG_S TEST
80.0
100.0
80.0
60.0
40.0
20.0
0.0
PVF32
WB - ANALOGReal Data
55.0
ON
PV
DIContact Input
0
OFF
ON
PV
NRHTRP
ANAnnunciatorMessage
0
OFF
WB - DI... ANLG_S... WB - AN... DI Conta... AN Ann...
Figure ImageofInstrumentFaceplateDisplay(ExistingInstrument)
3rd Edition : Dec.22,2009-00
<3.1 Windows Used in SCS Operation and Monitoring> 3-12
IM 32S01E10-21E
• GOV_B, GOV_IB : S_GOV_B, S_GOV_IB
• MOB_21 : S_MOB_21
• MOB_11 : S_MOB_11
• MOB_RS : S_MOB_RS
• MOA : S_MOA
030120E.ai
ON
PV
MOB_21MOB_21 TEST
MOB_11MOB_11 TEST
MOB_RSMOB_RS TEST
0
OFF
FV %
MOAMOA TEST
40.0
100.0
80.0
60.0
40.0
20.0
0.0
ON
PV0
OFF
ON
PV
MANNR
MANNR
MANNR
MANNR
0
MV0
MV %40.0
MV0
MV0
OFF
ON
INV
GOV_01Override G01
0VAL
1
OFF
AUTNR
OUTV0
GOV_01 ... MOB_21 ... MOB_11 ... MOB_RS ... MOA MO...
Figure ImageofInstrumentFaceplateDisplay(ExistingInstrument)
SEE ALSO For more information about Instrument Faceplate, see the following:
E8, “Instrument Faceplate” of the CS 1000/CS 3000 Reference Human Interface Station (IM 33S01B30-01E)
E6, “Instrument Faceplate” of the CENTUM VP Reference Human Interface Station (IM 33M01A30-40E)
l PasswordFunctionBlockorManualOperationBlock• PASSWD, MOB_21, MOB_11, MOA
If you set values of MV, enter the password in the password dialog box. If you enter the wrong password, MV values are reset to the previous values before the change.
• MOA If you close the INC/DEC dialog box, click anywhere outside the dialog box. If no action is made, the dialog box disappears in about 30 seconds.
2nd Edition : Dec.15,2008-00
<3.1 Windows Used in SCS Operation and Monitoring> 3-13
IM 32S01E10-21E
l InstrumentFaceplateOn the instrument faceplates of SCS and FCS, the mark in the bottom is displayed in different colors.
Table MarkColors
Stationmarkcolor
CENTUM VP HIS CS 3000 HISFCS Dark Blue Red
SCS Orange Green
TIPRelated builders cannot be called using a tag name.
l OperationMarksOperation marks provide the function to notify the operator of various statuses of equipment, such as under maintenance, out of order or operation prohibited. When an operation mark is set, a tag with comment is set in the instrument faceplate. By assigning an operation mark, the operation privileges over the instrument faceplate can be changed temporarily.
SEE ALSO For more information about the Operation Marks, see the following:
“n Toolbar of Tuning Window” in E4.3.1, “Components of Tuning Window” of the CS 1000/CS 3000 Reference Human Interface Station (IM 33S01B30-01E)
“n Toolbar of Tuning Window” in E3.3.1, “Components of Tuning View” of the CENTUM VP Reference Human Interface Station (IM 33M01A30-40E)
l Two-StepOperationSettingforSwitchFaceplatesThe operation on the instrument faceplate buttons in the following function blocks is always two-step.ThesettingsintheinstrumentfaceplateoperationdefinitiontabintheHISconstantsbuilderare ignored.
• Grouping Override Function Block (GOV_*)
• Override Function Block (OVR_*)
• Password Function Block (PASSWD)
• Data Manual Operation with Answerback Function Block (MOB_*)
• Auto-reset Data Manual Operation Function Block (MOB_RS)
SEE ALSO For more information about the two-step operation, see the following:
“nTwo-StepOperation”inE8.5,“SpecificationofInstrumentFaceplateOperation”oftheCS1000/CS3000 Reference Human Interface Station (IM 33S01B30-01E).
“n Twice-Pressed Operation” in E6.5, “Operation Type on Instrument Faceplate” of the CENTUM VP Reference Human Interface Station (IM 33M01A30-40E)
2nd Edition : Dec.15,2008-00
<3.1 Windows Used in SCS Operation and Monitoring> 3-14
IM 32S01E10-21E
l ReconfirmationDialogBoxIf you try to change MV of the following function blocks on the instrument faceplate and data input dialogbox,thereconfirmationdialogboxalwaysappears.Thesettingoftagmarkisignored.Youcannotdisablethereconfirmationdialogboxbythetagmarksetting.
• Grouping Override Function Block (GOV_*)
• Override Function Block (OVR_*)
• Password Function Block (PASSWD)
• Data Manual Operation with Answerback Function Block (MOB_*)
• Auto-reset Data Manual Operation Function Block (MOB_RS)
• Analog-type Data Manual Operation Function Block (MOA)
1st Edition : May 30,2008-00
<3.1 Windows Used in SCS Operation and Monitoring> 3-15
IM 32S01E10-21E
3.1.4 SCS Station Status Display View The SCS Station Status Display view displays the operating status of each SCS, such as scan period and security level.
IMPORTANTSCSs cannot be started or stopped from the SCS Station Status Display view, regardless of the roles assigned to the operator on the HIS.
n System Status Overview View The System Status Overview view displays the status of the system over the control bus, including SCS, HIS and FCS. SCS icons are the same as FCS icons, except SCS icons are shown in orange in HIS for CENTUM VP, and in green in HIS for CS 3000.
030108E.ai
MYPJT
SCS0101 FCS0105
HIS0124
Ready
Domain : 01 Vnet/IP1 Vnet/IP2
.SO System Status Overview
Figure SystemStatusOverviewView
030109E.ai
SCS icon CPU status
(a) Normal (b) Faulty (c) Left CPU is faulty
Fail
Figure SCSIcons
2nd Edition : Dec.15,2008-00
<3.1 Windows Used in SCS Operation and Monitoring> 3-16
IM 32S01E10-21E
n SCS Station Status Display View The SCS Station Status Display view displays the status of an SCS in details. Operating mode, scan period and security level are shown in this window. In this window, whether or not the operating status and connection status of CPU and I/O modules is normal is shown in different colors.
IMPORTANTThe HIS’s SCS Station Status Display view displays the information that has been read from each SCS. However, the Diagnostic Information Operating dialog box in SCS Maintenance Tool cannot be opened from this window.
030110E.ai
BKDCS Domain : 01 Vnet/IP1 Vnet/IP2IOM
01
PSU PSU
PSU PSUCOM COM02
PSU PSUCOM COM03
PSU PSUCOM COM04
10
PSU PSUCOM COM05
PSU PSUCOM COM06
PSU PSUCOM COM07
PSU PSUCOM COM08
PSU PSUCOM COM09
1 2
CP U
CP U
P SU
P SU
PSU PSUCOM COM
SCS0104SCS CommentStation No : 4Type : SSC50D-F
Revision : R2.03.00Generation : POU DB :
2009/12/05 14:08:15Variable DB :
2009/12/05 14:08:17System DB :
2009/12/05 14:10:20Integration DB :
2009/12/05 14:12:10
CPU Idle Time : 34secComm Load Ave : 0%
Cur : 0%ControlStatus : RUN
Scan Period : 100msecScan Period Setup : 100msecExecution Time : 40%Operating Mode : RUNNINGSecurity Level : 1
Forcing : 5Link Trans Lock : 3stnInter-SCS Comm Lock : 2stnComm I/O Lock : Yes
Time Sync : Vnet/IP
TEMP Air In Air Out Battery (L, R)Fan SCU (N1, N2)
Battery (L,R)
■ X Not Ready ■ Stand-By ■ Control ■ Hard Ready ■ Maintenance
Control Bus
I/O Node Status Display
ESB Bus Status Display
.SF SCS0104 Station Status Display
Station nameStation CommentStation numberStation typeSCS system programrevisionLast generationdate & timeAppllication dataSymbol table data
Safety System data
CENTUM Integrationdata
CPU idle timeComm loadControl status
Scan period (*1)Set scan periodProgram run timeOperating ModeSecurity levelNumber of points under forcingNumber of stations locked in SCS link transmissionNumber of stations locked in Inter-SCS safety communicationCommunication I/O lock statusTime Sync (*2)Temperature
Intake temperatureExhaust temperatureBattery temperature
FanSCU fan
Battery status
*1: For SCS with system program R2.02 or earlier, the set scan period is displayed.*2: When V net is used, the “IRIG-B : Ready” is displayed instead of “Time Sync : Vnet/IP.”
Figure SCSStationStatusDisplayView
3rd Edition : Dec.22,2009-00
<3.1 Windows Used in SCS Operation and Monitoring> 3-17
IM 32S01E10-21E
l Toolbar of the SCS Station Status Display ViewThe following operations can be performed from the toolbar of the SCS Station Status Display view:
030111E.ai
Selecting this button will call the System Alarm view where alarm details can be checked. If a systemalarmmessageispresent,thebuttonwillflashinred.
030112E.ai
Selecting this button will call the HIS Setup window.
030113E.ai
Selecting this button will call the Adjust Time dialog box.
030114E.ai
Selecting this button will call the System Status Overview view.
030115E.ai
The SCS report dialog box to show the station information. The contents in the dialog box can be printedoutorexportedintoafile.
2nd Edition : Dec.15,2008-00
<3.1 Windows Used in SCS Operation and Monitoring> 3-18
IM 32S01E10-21E
l Station Information Display The following information is displayed regarding the selected SCS:
• Station name
• Station comment
• Station number
• Station type
• SCS system program revision
• Last generated date/time The date and time of the last download to the SCS is displayed for each of the following DBs: - POU DB (application data) - Variable DB (symbol table data) - System DB (safety system data) - Integration DB (CENTUM integration data)
• CPU idling time (seconds) The CPU idling time per minute is displayed.
• Communication load (%) The V net communication load against CPU load of the safety control station is displayed in percentage. The displayed values are current load and the moving average load against minute.
• Control status [RUN] is displayed when the SCS is running, and [STOP] is displayed when the SCS is stopped, both in cyan color.
• Scan period (milliseconds) This is the actual scan period of the SCS. Note that the set scan period is displayed for SCS with system program R2.02 or earlier.
• Set scan period (milliseconds) This is the scan period set in the SCS.
SEE ALSO For more information about the actual and set scan period, see the following:
A3.1.2, "Automatic Extension Function for Scan Period of the Application Logic Execution Function" of the Safety Control Station Reference (IM 32S03B10-21E)
• Program execution time (%)• Operating mode
[RUNNING] is displayed when the SCS in the Running mode, [WAITING] is displayed when the SCS is in the Waiting mode, and [INITIAL] is displayed when the SCS is in the Initial mode.
• Security level• Number of points under forcing • Number of stations locked in SCS Link Transmission• Number of stations locked in Inter-SCS Safety Communication• Communication I/O lock status
[Yes] is displayed when the communication I/O data is locked, and [No] is displayed when the communication I/O data is not locked.
• IRIG-B connection status ThisitemisnotdisplayedifVnettimesynchronizationisspecified.
3rd Edition : Dec.22,2009-00
<3.1 Windows Used in SCS Operation and Monitoring> 3-19
IM 32S01E10-21E
• Time Synchronization Method This is displayed only when the control bus is Vnet/IP. If the SCS is synchronized with SNTP server, [SNTP] is displayed; if it is not synchronized with SNTP server, [Vnet/IP] is displayed.
l Station Status Display The following station statuses are displayed regarding each SCS. The character string representing each item is displayed in green if the status is normal, or red if faulty. If the status is faulty, a mark indicating fault is displayed.
Battery (XL, R)030118E.ai
Figure TheMarkStandsforAbnormal(BatteryTemperatureAbnormal)
• Intake temperature
• Exhaust temperature
• Battery temperature
• SCU fan This item is displayed only when the station is of the wide range temperature type (SSC60S-F, SSC60D-F, SSC50S-F, SSC50D-F, SSC10S-F, SSC10D-F).
• Battery status
l StationConfigurationDisplayThefollowingstatusesinthestationconfigurationaredisplayedregardingeachSCS:
• CPU status The character string is displayed in green, red, yellow or blue when the CPU is normal, faulty, on standby or hardware ready, respectively. The white character string [COPY] will flashwhileaprogramisbeingcopied.WhiletheFLASHmemoryisbeingwritten,[FLASH]willflashinwhite.
• Power supply status Displayed in green if the power supply is normal, or red if faulty.
l ESB Bus Status Display Displayed in green if the ESB bus is normal, or red if faulty.But the status of the Optical ESB Bus Repeater modules is not displayed.
l NodeConfigurationDisplay• Node number
• Communication status The character string [COM] is displayed in green if the node is normal, or red if faulty. Note that the communication status of node 1 (CPU node) is not displayed.
• Power supply status The character string [PSU] is displayed in green if the power supply is normal, or red if faulty.
• I/O module status [I/O FAIL] is shown in red if the I/O module is faulty, and nothing is displayed if the module is normal.
3rd Edition : Dec.22,2009-00
<3.1 Windows Used in SCS Operation and Monitoring> 3-20
IM 32S01E10-21E
n SCS Report Dialog Box The SCS Report dialog box showing the status of each SCS can be called from the SCS Station Status Display view. To call the SCS Report dialog box, use the following button on the toolbar:
030115E.ai
ThefollowingfigureshowsadisplayexampleoftheSCSReportdialogbox:
SCS Report
030116E.ai
Station Name : SCS0108 Type : SSC50D-F Address : 01-08 Comment : SCS CommentRevision : R2.03.00Generation :POU DB : 2009/12/05 14:08:15Variable DB : 2009/12/05 14:08:15Safety DB : 2009/12/05 14:10:20Integration DB : 2009/12/05 14:12:10CPU Idle Time : 56secComm Load Ave : 0% Cur : 0%Control Status : RUNScan Period : 100msecScan Period Setup : 100msecExecution Time : 40%Operating Mode : RunningSecurity Level : 1Forcing : 5Link Trans Lock : 3stnInter-SCS Comm Lock : 2stnComm I/O Lock : YesIRIG-B :Time Sync : Vnet/IPTemperature: Air in : Ready Air out : Ready Battery: L : Ready R : ReadyBattery: L : Ready R : Ready
Print File Close
Figure SCSReportDialogBox
• Print Clicking this button prints the content currently displayed in the SCS Report dialog box. The displayedcontentwillbeoutputtotheprinterspecifiedintheHISSetupwindow.
• Create File Clicking this button saves the content currently displayed in the SCS Report dialog box to a FDC.Thedefaultnameofthesavefileis“SCSRevlnf.txt.”
• Close Clicking this button closes the SCS Report dialog box.
3rd Edition : Dec.22,2009-00
<3.1 Windows Used in SCS Operation and Monitoring> 3-21
IM 32S01E10-21E
n SCS Node Status Display Dialog Box The SCS Node Status Display dialog box is used to display the node status of each SCS in details. ThefollowingfigureshowsadisplayexampleoftheSCSNodeStatusDisplaydialogbox:
I/O UNIT
030117E.ai
Node No. :
Comment :
IOM LOAD Report Close
2
1
SDV144
SDV531
SAI143
ALR111
SAV144
SSB401
SSB401
PSU
PSU
2
DCCH 2C1C
Always disabled
24 VDC supply status, “DC (red)” if faulty
Bus status
Bus status
Channel status, “CH (red)” if faulty
Serial communication status“nC (n : port no.) (red)”, if faulty
Figure SCSNodeStatusDisplayDialogBox
TIPBut the status of the Optical ESB Bus Repeater modules is not displayed.
l Node Status Display The communication status and power supply status of each node are displayed.
• Power supply status The character string [PSU] is displayed in green if the power supply is normal, or red if faulty.
• 24 VDC supply status [DC] is displayed in red if the power supply status is abnormal.
• SSB401 status The color of [SSB401] changes to green if the unit is normal, and red if faulty. When the SSB401 is faulty, a mark is displayed.
• Bus status The color of the bus system number changes to green if the bus is normal, and red if faulty. When the bus is faulty, a mark is displayed.
• I/O module status The color of the I/O module varies with module status. Green indicates Normal. Red indicates Abnormal. Blue indicates Ready and yellow indicate Standby. The bus status is also displayed by a red-colored number. The “-” in the I/O module name is not displayed.
• Channel status [CH] is displayed in red if any assigned channel is faulty.
• Serial communication status [nC] (n: port number) is displayed in red if the serial communication status with subsystem is faulty.
1st Edition : May 30,2008-00
<3.1 Windows Used in SCS Operation and Monitoring> 3-22
IM 32S01E10-21E
3.1.5 AdjustTimeDialogBoxYoucansetorchangethesystemdateandtimeintheAdjustTimedialogbox.
n Time Setting from an HIS You can change the current time of the V net from an HIS using the time setting function.
• Vnet/IP Network time on the Vnet/IP (including V net router) is synchronized with the time set on HIS. Therefore, the time on the following stations is synchronized with the time set on HIS:
- SCS (CPU module and digital input module (SDV144))
- SENG, FCS, HIS
If the time synchronization is based on an SNTP server, the time set on HIS is ignored.
• V net Network time in one V net domain and other V net domains where [Transfer/Receive System Time] is specified for BCV/CGW is synchronized with the time set on HIS. Therefore, the time on the following stations is synchronized with the time set on HIS:
- SCS (CPU module and digital input module (SDV144))
- SENG, FCS, HIS
However, Vnet I/P network time is not synchronized even if it is connected to the V net with a V net router.
SCS time with IRIG-B time synchronization is unaffected by the time change on the HIS.
SEE ALSO • For more information about the SCS time management function, see the following:
A3.2, “Time Synchronization of SCS” of the Safety Control Station Reference (IM 32S03B10-21E)
• For more information about the Adjust Time dialog box, see the following:
E7.11, “Adjust Time Dialog Box” of the CS 1000/CS 3000 Reference Human Interface Station (IM 33S01B30-01E)
E4.4, “Adjust Time Dialog Box” of the CENTUM VP Reference Human Interface Station (IM 33M01A30-40E)
• For how to set time for the Vnet/IP or for a system connected to the Vnet/IP, see the following:A4, “Time Synchronization of Vnet/IP” of the ProSafe-RS Vnet/IP (IM 32S56H10-21E)
2nd Edition : Dec.15,2008-00
<3.1 Windows Used in SCS Operation and Monitoring> 3-23
IM 32S01E10-21E 2nd Edition : Dec.15,2008-00
3.1.6 Message Monitor of CAMS for HISCAMSforHIS(ConsolidatedAlarmManagementSoftwareforHIS)isasoftwareprogramfor managing the alarms on HIS comprehensively. This section provides information you needformonitoringaProSafe-RSsysteminaHISconfiguredtousetheCAMSforHIS.
SEE ALSO For more information about CAMS for HIS, see the following:
M13, “Consolidated Alarm Management Software” of the CS 1000/CS 3000 Reference Options (IM 33S01B30-01E)
E12, “Consolidated Alarm Management Software” of the CENTUM VP Reference Human Interface Station (IM 33M01A30-40E)
n How CAMS for HIS Monitors the ProSafe-RS System If you are using CENTUM VP, you need to enable CAMS for HIS. If you are using CS 3000, you need to install the CAMS for HIS package and enable it. The System Alarm view and Process Alarm view for displaying the system alarm messages and process alarm messages from ProSafe-RS stations will be integrated by the CAMS for HIS window.If integrated with ProSafe-RS, CAMS for HIS Message Monitor selects and displays messages of ProSafe-RS in the same manner as the System Alarm view and Process Alarm view, enabling youtoviewSCSmessagesfirst.
IMPORTANTItispossibletofilteroutlessimportantalarmmessagesonthiswindowsoastomakecriticalalarmsmorenoticeable.However,itisrecommendedthatmessagesfromSCSbeleftunfiltered.
SEE ALSO For more information about CAMS for HIS, see the following:
2.15, “CENTUM Integration” of the Engineering Guide (IM 32S01C10-21E)
<3.1 Windows Used in SCS Operation and Monitoring> 3-24
IM 32S01E10-21E
l Display Example of the Message Monitor of CAMS for HISThefigurebelowshowstheMessageMonitorofCAMSforHIS.
030121E.ai
File Edit View Operation Tools
Shelving
Filters
All Filters FavoritesDate Message
System � SIS System Alarm
Shelves Pane
Filter Pane
A&E Browser Pane
ENGUSER(12/30/30)SIS (2/2/2)
System (2/2/2) Process (0/0/0)
��
System (12/30/30) Process (0/0/0) Operator Guide (0/0/0) ?
A&E Message Pane
2009/12/05 8:03:14 SCS0362 Variable Locked Variable=ANG_LLL@ANGI2009/12/05 8:03:20 SCS0362 Variable Unlocked Variable=ANG_LLL@ANGI
Date Message2009/12/05 8:03:14 SCS0362 Variable Locked Variable=ANG_LLL@ANGI2009/12/05 8:03:20 SCS0362 Variable Unlocked Variable=ANG_LLL@ANGI2009/12/05 5:33:57 DataBase Equalize Complete2009/12/05 5:33:54 DataBase Download from RHDB007 File = TFAR036301.odb2009/12/05 5:33:54 DataBase Download from RHDB007 File = OGAR036301.odb2009/12/05 5:33:54 DataBase Download from RHDB007 File = SDAR036301.odb
CAMS for HIS : Message Monitor
FigureMessageMonitorofCAMSforHIS
SEE ALSO For more information about the Message Monitor of CAMS for HIS, see the following:
M13.2, “Message Monitor of CAMS for HIS” of the CS 1000/CS 3000 Reference Options (IM 33S01B30-01E)
E12.2, “Message Monitor of CAMS for HIS” of the CENTUM VP Reference Human Interface Station (IM 33M01A30-40E)
3rd Edition : Dec.22,2009-00
<3.1 Windows Used in SCS Operation and Monitoring> 3-25
IM 32S01E10-21E
l FilteringItispossible,withtheuseoffilters,toconfigurethewindowtoonlydisplayimportantalarmmessages.• TheSafetyInstrumentedSystem(SIS)filterisgiventhehighestprioritybydefault,suchthat
onlymessagesfromSCSswillbedisplayed.Thedetailsofthefiltersettingsaredisplayedinthe Filter pane.
• WhenopeningtheMessageMonitorofCAMSforHIS,ifSISmessagesexist,theSISfilterwill automatically take effect, such that messages from SCS are displayed with the highest precedence.
SEE ALSO Formoreinformationaboutfiltering,seethefollowing:
M13.3.2, “Filtering” of the CS 1000/CS 3000 Reference Options (IM 33S01B30-01E)
E12.3.2, “Filtering” of the CENTUM VP Reference Human Interface Station (IM 33M01A30-40E)
l ShelvingThe messages with lower priorities can be temporarily shelved (put aside as if put on a shelf) so that the A&E Message Pane can be freed for other purposes.
IMPORTANTThe messages from SCSs should always be handled with the highest priority. These messages should never be put on the shelves.
SEE ALSO For more information about shelving, see the following:
M13.3.1, “Shelving” of the CS 1000/CS 3000 Reference Options (IM 33S01B30-01E)
E12.3.1, “Shelving” of the CENTUM VP Reference Human Interface Station (IM 33M01A30-40E)
l Suppression The messages with lower priorities can be suppressed, e.g. to be silenced.
IMPORTANTThe messages from SCSs should always be handled with the highest priority. These messages should never be suppressed.
SEE ALSO For more information about suppression, see the following:
M13.3.5, “Suppression” of the CS 1000/CS 3000 Reference Options (IM 33S01B30-01E)
E12.3.5, “Suppression” of the CENTUM VP Reference Human Interface Station (IM 33M01A30-40E)
1st Edition : May 30,2008-00
<3.2OtherFunctionsUsedinOperationandMonitoringfromHIS> 3-26
IM 32S01E10-21E
3.2 OtherFunctionsUsedinOperationandMonitoring from HIS
In addition to the Override function described in the preceding section, Equalizing and trend recording are another HIS functions that can be used in the operation and monitoringofSCS.ThissectiondescribestheCENTUMSecurityFunctionandAlarmInhibition.
SEE ALSO For information about Override from HIS, see the following:
“n Override” in 7.2.3, “Forcing and Override” of the Engineering Guide (IM 32S01C10-21E)
n Equalizing The [SCS Taglist Import] command, which is run on System View, generates a taglist database fromtheinformationdefinedusingtheProSafe-RS’sEngineeringFunctionandthegeneratedtaglist database is downloaded to each HIS in the system. As a result, taglist databases on the SCS and HIS are equalized.
IMPORTANTWhenyouhaveaddedorchangedanytagdefinitionsusingtheTagNameBuilderontheSENGand downloaded the changes to the SCS, there is inconsistency between the databases in the SCS and HIS. You need to run the [SCS Taglist Import] command on System View to equalize the database.
SEE ALSO For how to run the [SCS Taglist Import] command on System View, see the following:
“n Generating SCS Taglist on CENTUM” in 2.2.2, “SCS Taglist Generation”
n SCS Monitoring Each HIS function communicates with SCSs based on the equalized information. In a CENTUM system, SCSs are handled in the following manner on the HIS:
• SCSs are not included in the number of FCS units operated and monitored.
• SCS tags are included in the tag monitoring points.
n Trend Recording SCS tag names can be assigned for trend data recording. However, since SCSs do not support high-speed (1-second) trend recording, assigning an SCS tag name to a high-speed trend recording block will not display data. Do not assign SCS tag names to high-speed trend recording blocks.
3rd Edition : Dec.22,2009-00
<3.2OtherFunctionsUsedinOperationandMonitoringfromHIS> 3-27
IM 32S01E10-21E
n SecurityFunctionoftheCENTUMThe CENTUM provides a security function that changes access privileges with respect to FCS data according to the account of the operator working on each HIS. This function can be utilized for SCSs in the same manner. These access privileges can be restricted further using the Security Function of the CENTUM. For example, an HIS account permitted to write data assigned to external communication function blocks and an HIS account not permitted to write such data can be set up using the Security Function of the CENTUM.
• The Security Function of the CENTUM is completely independent of the security levels of SCSs. SCS security levels cannot be manipulated from HISs.
• The Security Function of the CENTUM is completely independent of the SENG’s Engineering Security Management Function.
n Alarm InhibitionThis is a function to inhibit the display, printing, and beeping sounds of the process alarm messages temporarily. It is useful when many process alarm messages are generated during the startup of SCS. System alarm messages cannot be inhibited.
l How to activate/deactivate Suppress Alarm functionYou can turn on the Alarm Inhibition function (AOF) from HIS or from FCS targeting the Mapping block/element on the SCS. Every time the SCS is restarted, the Alarm Inhibition function (AOF) is turned off. The switch between activate and deactivate the Alarm Inhibition function is allowed only by applications on the FCS or on the HIS. Neither the applications on the SCS nor the applications on the SENG are allowed to do so.
SEE ALSO Formoredetailsonalarminhibitionspecification,seethefollowing:
E12.3.3, “Alarm Inhibition (AOF)” of the CS 1000/CS 3000 Reference Human Interface Station (IM 33S01B30-01E).
E10.3.3, “Alarm Inhibition (AOF)” of the CENTUM VP Reference Human Interface Station (IM 33M01A30-40E).
2nd Edition : Dec.15,2008-01
<3.2OtherFunctionsUsedinOperationandMonitoringfromHIS> 3-28
IM 32S01E10-21E
l Alarm Inhibition from HISIf you want to inhibit alarms on the Tag data on SCS, do so from the Tuning view on HIS. Press the [AOF] button on the window to activate the function. The Tag mark color is shown in blue while the function is on.
SH : SL :PV :HYS :
030201E.ai
0362ANALGI ANALGI
Ready 100%00:04:20
PV %
0362ANALGI ANALGI
100.0
100.0
0.0
HTRP
100.00.0
100.02.0
90.080.020.010.0
%
HH : PH :PL :LL :
ALRM:HTRP
AOF Button
0
PV
16:01 16:02 16:03 16:04
0362ANALGI TUN ANALGI
Figure SuppressAlarminTuningView
TIPThe AOF button only appears when the mapping block/element corresponding to the tag name has the data item of AOFS.
l Outputting Suppressed Alarm MessagesOn releasing the Alarm Inhibition, the suppressed alarm messages can be output for the process alarmsthatarestillraised.Thismeansthatyoucanconfirmthesuppressedmessagesfortheprocess alarms occurred during Alarm Inhibition. The time stamp of a suppressed message shows the time when the message is output upon the release of Alarm Inhibition.WhethertooutputthesuppressedalarmmessagescanbespecifiedontheSCSConstantsBuilder.
SEE ALSO For how to make settings required for outputting the suppressed messages, see the following:
3.1.3, “SCS Constants Builder” of the Engineering Reference (IM 32S04B10-21E)
2nd Edition : Dec.15,2008-00
<Appendix Limitations for Each Software Release Number of CENTUM> App.-1
IM 32S01E10-21E
Appendix. Limitations for Each Software Release Number of CENTUM
n LimitationsRelatedtotheNewFeaturesofProSafe-RSR2.03The table below shows the limitations related to the new features of ProSafe-RS R2.03 for different software release numbers of CENTUM.
Table LimitationsRelatedtotheNewFeaturesofProSafe-RSR2.03
Feature CENTUM VP R4.02
CS 3000/CENTUM VP earlier than
R4.02
Behavior on the CENTUM side when the feature is not supported
New SCS (SCSP2) X -
SCSP2 cannot be monitored or operated because the station type of SCSP2 is not available on the System View.
Support of 14 nodes (SCSP2 only) X - Same as above
Expanded capacity for %AN, mapping blocks/elements, and number of tags (SCSP2 only)
X - Same as above
First-up Alarm Annunciator(ANN_FUP) X - Messages of ANN_FUP are not
displayed.
Online change of scan period X - Related system alarm messages are not displayed.
Locking of Inter-SCS Safety Communication FB X -
• On the SCS Status Display view, the number of stations locked in Inter-SCS Safety Communication is not displayed.
• Related system alarm messages are not displayed.
Automatic IOM download X -The same system alarm message that is displayed when IOM download is manually executed is displayed.
Automatic scan period extension during high CPU load X -
• On the SCS Status Display view, only the actual scan period is displayed; the set scan period is not displayed. (*1)
• Related system alarm messages are not displayed.
Selection of SCS behavior at abnormal calculation(divisionby0,overflow,access to the outside of an array)
X - Related system alarm messages are not displayed.
X: Supported-: Not supported*1: Tofindoutthesetscanperiod,opentheSCSprojectontheR2.03.00orlaterSENGandseetheCycleTimingsettinginthe
Settings tab of Resource Properties of the SCS Manager.
3rd Edition : Dec.22,2009-00
Rev-1
IM 32S01E10-21E
Revision Informationl Title : Integration with CENTUM VP/CS 3000l Manual No. : IM 32S01E10-21E
Dec.2009/3rdEdition/R2.03orlater**: Denotes the release number of the software corresponding to the contents of this user’s manual. The
revised contents are valid until the next edition is issued.2.1.4 Changed for newly added ANN_FUP and SCSP2.2.2.1 Added SSC60S/SSC60D.2.2.4 Added ANN_FUP.3.1.3 Added ANN_FUP.3.1.4 Changed scan period display. Added indication of the number of stations locked in Inter-SCS Safety
Communication. Added SSC60S/SSC60D. Changed Figure “SCS Station Status Display View” and Figure “SCS Report Dialog Box.”Appendix Newly added.
Dec. 2008/2nd Edition/R2.02 or laterOverall Changed “CS 3000” to “CENTUM” to refer to both CENTUM VP and CS 3000.Overall ChangedaccordingtothespecificationsofCENTUMVP.2.1 Added the procedures for starting various builders.
May 2008/1st Edition/R2.01 or laterNewly published
3rd Edition : Dec.22,2009-00
n For Questions and More Information Online Query: A query form is available on the following URL for online query. http://www.yokogawa.com/iss/ If you want more information about Yokogawa products, you can visit Yokogawa’s homepage at the following web site. Homepage: http://www.yokogawa.com/n Written by Process Automation Product Marketing Dept. Industrial Automation Systems Business Div. Yokogawa Electric Corporation n Published by Yokogawa Electric Corporation 2-9-32 Nakacho, Musashino-shi, Tokyo 180-8750, JAPAN