Page 1: S crJ ACO - Wastewater Products Somerset UK by … - 150 Oil storage capacity (litres) 300 - 1000 Silt storage capacity (litres) *NSB 10 Aca Q-Ceptor bypass oil separators fully treat

(52.7)

I I

ACO Water Management:Civils + Infrastructure

CI/SfB

Uniclass IJR12/JR23L731

I

ACO Q-Ceptor

Bypass and full retention oil separators

Synerg~~'''''S'C.W\lCl< ,.••• ""1»01 crJrROOUCTS ACO

Page 2: S crJ ACO - Wastewater Products Somerset UK by … - 150 Oil storage capacity (litres) 300 - 1000 Silt storage capacity (litres) *NSB 10 Aca Q-Ceptor bypass oil separators fully treat

ACO Q-Ceptor bypass oil separators

e.s'"iijCo

'"enVIVI

'"Co>-

IX!

BYPASS SEPARATORS

In this scenario it is deemed acceptable not to treat the full flow, andwhere the worst pollutants will be carried off by the initial flow, forexample car parks, roadways and some commercial areas.

Once 10% of the peak flow rate is exceeded, the flow bypasses theseparation chamber and discharges directly into the drainage system.

•• I

INominal sizeI•• bypass (NSB)III

•5560* Area drained (m2)

--

3 - 10 Treated flow (I/s)

30 - 100 Peak flow (l/s)

1 & 2 PerformanceClass-

45 - 150 Oil storagecapacity (litres)

300 - 1000 Silt storagecapacity (litres)

*NSB 10

Aca Q-Ceptor bypass oil separators fully treat allflows caused by rainfall up to 6.5mm per hour whichincludes the vast majority of rainfall events in the UK.

Page 3: S crJ ACO - Wastewater Products Somerset UK by … - 150 Oil storage capacity (litres) 300 - 1000 Silt storage capacity (litres) *NSB 10 Aca Q-Ceptor bypass oil separators fully treat

Aca Q-Ceptor

Aca Q-Ceptor bypass oil separator - Design principles

Oil

]

90% entersthe bypasschamber

Peakflow100%---l--

10% entersthe treatmentchamber

Key:Bypass flow - - -Treated flow - __

Water

In

ACO Q-Ceptor bypass oil separators aredesigned to treat 10% of the peak flowinto the unit. This 10% is known as thetreated flow. Flows in excess of this 10%are allowed to bypass the treatmentchamber.

Runoff entering the unit is retained withinthe treatment chamber for sufficient timeto allow the oil carried in it to float to thetop and for any silt in the water to settleto the bottom of the tank. The cleanwater remaining below the layer offloating oil discharges through the outlet.

The ACO Q-Ceptor bypass separator isdesigned with a bypass chamber aroundthe top of the unit that permits flows inexcess of the treated flow to bypass thetreatment chamber.

Bypass units are permitted in locationswhere the risk of pollution is low, and inparticular where the risk of a largevolume of pollution is low. The reasoningbehind this is that most rainfall in the UKis at an intensity of 0.0018 IIsm2 or less,and all runoff from this light rain will passthrough the treatment chamber.

In heavier rain, most of the pollution willbe carried by the initial first flush ofrunoff, which will all be treated. As aresult of this any pollution in the bypassflow at the peak of the storm will havebeen massively diluted.

ACO's design of bypass chamber ensuresthat no bypass will occur before thedesigned treated flow is reached.Thereafter, the treated flow will continueto pass through the unit, with excess flow(of up to 9 times the treated flow rate)allowed to bypass the treatment chamber.

ACO Q-Ceptor bypass oil separators areavailable to BS EN 858-1 :2002 Class 1or Class 2. When Class 1 effluent (betterthan 5 rng/l) is required, a coalescingfilter is fitted to the unit. Without thecoalescing filter the separators operate toClass 2 and achieve a treatment standardof better than 100 rng/l.

Bypass

190%bypass flow

Dischargeflow 100~ _;.--~.

- L% treated flow

"':.

Maintenance

Regular maintenance is essential toensure that a separator continues tooperate to its full design capabilitythroughout its working life. Thismaintenance includes monitoring the oiland silt levels, and removing anyaccumulated waste. Alarm systems arefitted to carry out this monitoring on acontinuous basis. BS EN 858-2:2003requires that a physical inspection musttake place at intervals of no more than 6months. The standard also requires thatevery five years the separator must beemptied and given a general inspection totest the integrity and performance of thesystem. The separator must be refilledwith clean water following such aninspection.

Page 4: S crJ ACO - Wastewater Products Somerset UK by … - 150 Oil storage capacity (litres) 300 - 1000 Silt storage capacity (litres) *NSB 10 Aca Q-Ceptor bypass oil separators fully treat

Aca Q-Ceptor bypass oil separators

How to choose the correct size

ACO Q-Ceptor bypass separators shouldbe sized in accordance with the guidancein PPG3.

The appropriate size of separator iscalculated by applying a standard formulato the area to be treated. The preciseformula depends on whether a fullretention or bypass separator is to beused. In all cases the area to be drainedis referred to as A.

The Nominal Size (NS) is the flow rate, inlitres per second, which can be treated bythe unit to the specified standard, Class 1or Class 2. Bypass separators are referredto as NSB (Nominal Size Bypass).

Bypass separator chambers

Design Example 1:Sizing a bypass separator

Assume you have a car park of 3,000m'.This is area A.

The nominal size of a bypass separatorfor a catchment of area A (m') isobtained using the following formula:

NSB = 0.0018 x A

Applying this formula to the car park of3000m' gives a result of 5.4. Thereforethis car park would require a bypassseparator of size NSB6.

ACO Q-Ceptor bypass separators areavailable as Class 1 or Class 2performance types. They are alsoavailable with or without a samplingpump pre-fitted to the units.

Part numbers for chambers withouta sampling pump can be found incolumn A.

Part numbers for chambers witha sampling pump pre fitted can befound in column B. e.s

III(ijC.

'"Vl

'"'"IIIC.,.,tIl

Oil Silt PipeTreated Area Storage Storage Length Width Depth Inlet Outlet Internal

Product Product Nominal Flow Peak Performance Drained Capacity Capacity Overall Overall Overall Height Height Diameter* WeightCode A Code B Size (Vs) Flow (Ifs) Class m' (litres) (litres) (mm) (mm) (mm) (mm) (mm) (mm) (kg)

34500 34560 NSB3 3 30 Class 1 1670 45 300 2300 1200 1580 1067 917 300 10234501 34561 NSB6 6 60 Class 1 3335 90 600 2300 1200 1800 1287 1137 300 11634502 34562 NSB8 8 80 Class 1 4445 120 1000 2300 1200 2100 1587 1437 375 13034503 34563 NSBlO 10 100 Class 1 5560 150 1000 2300 1200 2100 1587 1437 375 130

-----------------34505 34565 NSB3 3 30 Class 2 1670 45 300 2300 1200 1580 1067 917 300 9934506 34566 NSB6 6 60 Class 2 3335 90 600 2300 1200 1800 1287 1137 300 11134507 34567 NSB8 8 80 Class 2 4445 120 1000 2300 1200 2100 1587 1437 375 12534508 34568 NSBlO 10 100 Class 2 5560 150 1000 2300 1200 2100 1587 1437 375 125

III

101;s:~Cl

s:OD

~"E

1550mm

ACO Q-Ceptor bypass oil separator

*For optimum performance of each separator the pipe diameter stated in the chart must be used. Using pipe diameters less than those stated will reduce the efficiency of theseparator. Stated pipe diameters must not be exceeded. Pipe internal diameters in the chart refer to twinwal! or clay pipe work.

These products are subject to weight and dimensional tolerances. The dimensions shown on this page are for guidance purposes only_

Page 5: S crJ ACO - Wastewater Products Somerset UK by … - 150 Oil storage capacity (litres) 300 - 1000 Silt storage capacity (litres) *NSB 10 Aca Q-Ceptor bypass oil separators fully treat

Aca Q-Ceptor

Aca Q-Ceptor bypass oil separators

Cover and frame

Product Code DescriptionLength Width Overall Depth Overall Weight(mm) (mm) (mm) (kg)

34625 Ductile iron solid cover and frame D 400 0750 100 87.0

Cover and frame

Extension shaft

Product Code DescriptionInternal Diameter(mm)

Length Width Overall Depth Overall Weight(mm) (mm) (mm) (kg)

34520 Extension shaft 0716 0865 1059 19.1.o~

I 0865mm IExtension shaft

III

Ancillaries- DescriptionLength Width Overall Depth Overall Weight(mm) (mm) (mm) (kg)

700745 Coalescing filter for NSB3 0230 660 1.2

700748 Coalescing filter for NSB6, 8 & 10 0360 790 3.6

418094 Sampling pump with 4m hose 3.5

Width overall

ffiDJCoalescing filter

Stainless steel sampling pump with 4m hose

These products are subject to weight and dimensional tolerances. The dimensions shown on this page are for guidance purposes only.

Page 6: S crJ ACO - Wastewater Products Somerset UK by … - 150 Oil storage capacity (litres) 300 - 1000 Silt storage capacity (litres) *NSB 10 Aca Q-Ceptor bypass oil separators fully treat

ACO Q-Ceptor full retention oil separators

1

I

FULL RETENTIONSEPARATORS

~

'*iiic.

'"enr=o~~

~ /-,.,.0 --.,11-,-"1.~~ ',,---~:;LL

ACO Q-Ceptor full retention oil separators treat thecomplete flow caused by rainfall up to 65mm perhour and where there is a high risk of contamination.

These separators hold the contaminated water for a period longenough to ensure that the lighter contaminates separate from thewater and rise above it within the separation chamber. Microparticles are collected and combine on the coalescing filter until theyare large enough to float free by themselves.

Full retention separators are used for example in vehicle maintenanceand refuelling areas or scrapyards.

aa Nominal size(NS)D&':' '~~

II III

555* Area drained (m')

--

3-10 Peak flow (Ifs)

1&2 Performanceclass

30-100 Oil storagecapacity (litres)

---300-1000 SiIt storage

capacity (litres)

'NS 10

Page 7: S crJ ACO - Wastewater Products Somerset UK by … - 150 Oil storage capacity (litres) 300 - 1000 Silt storage capacity (litres) *NSB 10 Aca Q-Ceptor bypass oil separators fully treat

Aca Q-Ceptor

ACO Q-Ceptor full retention oil separator - Design principles

100% enters thetreatment chamber

Peakflow 100% - - --

Key:Treated flow - - -

ACO Q-Ceptor full retention oil separatorstreat all flows to the required effluentstandard, up to the designed flow rate ofthe unit.

UI

Thereafter, in extreme rainfall events andat flow rates in excess of the design flow,the runoff will still flow into the treatmentchamber until the maximum hydrauliccapacity of the unit is reached.

Runoff entering the unit is retained withinthe treatment chamber for sufficient timeto allow the oil carried in it to float to thetop and for any silt in the water to settleto the bottom of the tank.

Oil

~

ACO Q-Ceptor full retention oil separatorsare available to BS EN 858-1:2002Class 1 or Class 2. When Class 1 effluent(better than 5 mgll) is required, acoalescing filter is fitted to the unit. Thisfilter allows very small drops of oil that aretoo small to float upwards independentlyto coalesce into drops which are largeenough to float up into the retained oil.Without the coalescing filter the separatorsoperate to Class 2 and achieve a treatmentstandard of better than 100 mgll.

ACO full retention separators are fitted withan Automatic Closure Device (ACD). Thisis a float which is weighted so that it floatsin water but not in oil. The ACD ensuresthat if there is a large pollution event thatfills the oil capacity of the separator (or ifthe unit is not being regularly maintainedand the oil level builds up) then the outletof the unit is closed and the oil retained inthe unit cannot be washed out into theoutflow system.

100% treated flow

__ Discharge flow 100%

Maintenance

Regular maintenance is essential toensure that a separator continues tooperate to its full design capabilitythroughout its working life. Thismaintenance includes monitoring the oiland silt levels, and removing anyaccumulated waste. Alarm systems arefitted to carry out this monitoring on acontinuous basis. BS EN 858-2:2003requires that a physical inspection musttake place at intervals of no more than 6months. The standard also requires thatevery five years the separator must beemptied and given a general inspection totest the integrity and performance of thesystem. The separator must be refilledwith clean water following such aninspection.

Page 8: S crJ ACO - Wastewater Products Somerset UK by … - 150 Oil storage capacity (litres) 300 - 1000 Silt storage capacity (litres) *NSB 10 Aca Q-Ceptor bypass oil separators fully treat

ACO Q-Ceptor full retention oil separators

How to choose the correct size

ACO Q-Ceptor full retention separatorsshould be sized in accordance with theguidance in PPG3.

The appropriate size of separator iscalculated by applying a standard formulato the area to be treated. The preciseformula depends on whether a fullretention or bypass separator is to beused. In all cases the area to be drainedis referred to as A.

The Nominal Size (NS) is the flow rate, inlitres per second, which can be treated bythe unit to the specified standard, Class 1or Class 2. Full retention separators arereferred to as NS (Nominal Size).

Aeo full retention separator chamber

Design Example 2:Sizing a full retention separator

Assume you have an HGV yard of 500m2.This is area A.

The nominaI size of a fu 11 retentionseparator for a catchment of area A (rn")is obtained using the following formula:

NS = 0.018 x A

Applying this formula to the HGV yard of500m2 gives a result of 9. Therefore thisyard wou Id require a fu 11 retentionseparator of size NSlO.

ACO Q-Ceptor full retention separatorsare available as Class 1 or Class 2performance types. They are alsoavailable with or without a samplingpump pre-fitted to the units.

Part numbers for chambers withouta sampling pump can be found incolumn A.

Part numbers for chambers with asampling pump pre-fitted can be foundin column B.

Oil SiltArea Storage Storage

Product Product Nominal Peak Performance Drained Capacity CapacityCode A Code B Size Flow (Ifs) Class m2 (litres) (litres)

Depth Inlet Outlet PipeOverall Height Height Diameter Weight(mm) (mm) (mm) (mm) (kg)

~.se'"0-il:co~~

34510 34570 NS3 3 Class 1 167 30 300 1730 1200 1580 970 950 110 7834511 34571 NS6 6 Class 1 333 60 600 1730 1200 1800 1218 1198 160 9934512 34572 NS8 8 Class 1 444 80 1000 1730 1200 2100 1518 1498 160 11334513 34573 NSlO 10 Class 1 555 100 1000 1730 1200 2100 1518 1498 160 113

34515 34575 NS3 3 Class 2 167 30 300 1730 1200 1580 970 950 110 7734516 34576 NS6 6 Class 2 333 60 600 1730 1200 1800 1218 1198 160 9634517 34577 NS8 8 Class 2 444 80 1000 1730 1200 2100 1518 1498 160 11034518 34578 NSlO 10 Class 2 555 100 1000 1730 1200 2100 1518 1498 160 110

.s:cci;;:s

f"~s:o.~o

:;LI..

III

~~o

1550mm

Length overall

:l"eci!

Width overall

These products are subject to weight and dimensional tolerances. The dimensions shown on this page are for guidance purposes only.

ACO Q-Ceptor full retention separator

Page 9: S crJ ACO - Wastewater Products Somerset UK by … - 150 Oil storage capacity (litres) 300 - 1000 Silt storage capacity (litres) *NSB 10 Aca Q-Ceptor bypass oil separators fully treat

Aca Q-Ceptor

Aca Q-Ceptor full retention oil separators

Cover and frame

Product Code DescriptionLength Width Overall Depth Overall Weight(mm) (mm) (mm) (kg)

34625 Ductile iron solid cover and frame D 400 0750 100 87.0

Cover and frame

Extension shaft,

Product Code DescriptionInternal Diameter(mm)

Length Width Overall Depth Overall Weight(mm) (mm) (mm) (kg)

34520 Extension shaft 0716 0865 1059 19.1.e~

I 0865mm IExtension shaft

AncillariesIII - Description

Length Width Overall Depth Overall Weight(mm) (mm) (mm) (kg)

700745 Coalescing filter for NS3 0230 660 1.2

700748 Coalescing filter for NS6, 8 & 10 0360 790 3.6

701580 Automatic Closure Device (ACD) for NS3 0160 265 2.8

701583 Automatic Closure Device (ACD) for NS6, 8 & 10 0220 420 7.1

418094 Sampling pump with 4m hose 3.5

Width overall

ffi[J]

Width overall

iC1lliI=-~D.~

~ >00

Coalescing filter Automatic Closure Device (ACD) Stainless steel sampling pump with 4m hose

These products are subject to weight and dimensional tolerances. The dimensions shown on this page are for guidance purposes only.

Page 10: S crJ ACO - Wastewater Products Somerset UK by … - 150 Oil storage capacity (litres) 300 - 1000 Silt storage capacity (litres) *NSB 10 Aca Q-Ceptor bypass oil separators fully treat

Aca Q-Ceptor alarm systems

BS EN 858-1 :2002 and the EnvironmentAgency's Pollution Prevention guidelines(PPG3) require that all oil separators mustbe fitted with an automatic alarm/warningdevice to provide visual and audiblewarning when the level of oil reaches 90%of the storage volume under static liquidlevel conditions, These alarms/warningdevices indicate that the separator is inneed of immediate emptying for it tocontinue to work effectively,

In order to meet this requirement, ACOoffer a full range of Pepperl + Fuchsvisual and audible electronic alarmsystems. The alarms are designed tocontinuously monitor the critical operatingconditions of the separator and provide awarning early enough to prevent anydischarge of pollutants into theenvironment. All the alarm systems canbe fitted either during installation andcommissioning of a new oil separator, orto existing installations.

The standard range of mains poweredanalogue alarm systems provides highlevels of environmental safety, is simple toinstall and provides an economical solutionwhere the necessary cabling and ductingcan be provided. To ensure precisemonitoring in any situation, all of thealarm systems can be fitted with up tothree sensor probes within the separatorfor oil, silt and high liquid levels.

SPECIFICATION PROCESS

To simplify specification and orderingACO provide alarm systems as completeinstallation sets. Each alarm system setconsists of the following components:

~ Sensor probes

~ Control unit(with audible and visual warning)

ACO Q-Ceptor standard alarm system installation sets-Housing for control unit

~ Assembly accessories(including cable connector, fastenersand hangers)

Description -34601 Separator alarm set with oil sensor probe 230V AC

34602 Separator alarm set with oil, silt and high liquid level sensor probes 230V AC

34603 Separator alarm set with oil and high liquid level sensor probes 230V AC

,'-•itNote: All sensor probes of the alarm systems feature ATEX-approval, meaning they are approved for use in explosive areas of zone O.

•, •...

11a~xl xl xl

----.,,~

xl xl

Separator alarm set with oil sensor probe

Alarm options

ACO can supply digital GSM alarmsystems including mains, battery or solarpowered units. GSM alarm systems areideal for areas where people are notpresent and send an SMS (text) warningmessage via a GSM mobile phonenetwork, offering 24/7 protection.

~ ~Standard visual and

audible warning function

x2 x2 xl

/.,"

xl xl xl

Separator alarm set with oil, silt andhigh liquid level sensor probes

Battery and solar powered units givegreater installation flexibility where oilseparators are used in areas without areadily available power supply. For fulldetails of available options please contactthe ACO Water Management DesignServices Team on 01462 816666.

Standard mains power(230 VAC)

Optional battery poweroperation (9 V DC)

Optional solar poweroperation 02-30 V DC)

Optional GSM TEXTwarning to mobile phone

'"E~~E

~,

xl xl xl xl

--III~~

x3 xl xl x2

separator alarm set with oil andhigh liquid level sensor probes

Page 11: S crJ ACO - Wastewater Products Somerset UK by … - 150 Oil storage capacity (litres) 300 - 1000 Silt storage capacity (litres) *NSB 10 Aca Q-Ceptor bypass oil separators fully treat

Aca Q-Ceptor

Installation notes

This section provides general installation notes for ACa Q-Ceptorsthat should be followed before installation. These notes should beread together with the recommended installation detail shown inthe drawing on the following page.

Site conditions Flotation

These recommendations indicatethe requirements for installation ofACO Q-Ceptors in typical site conditions.The customer should ensure that therequirements for their particular siteconditions and anticipated loadings aremet, taking Engineering advice wherenecessary.

These recommendations assume that theunit is to be installed with a concretebackfill. Even with the minimumrecommended thickness of concrete, theunits, when empty, are vulnerable toflotation if the ground water level is high.Care must therefore be taken duringinstallation, and consideration given as towhether additional concrete should beprovided in wet locations.

R~

In lightly loaded situations, the units canbe installed without concrete backfill,using a suitable granular material asbackfill. However a concrete slab is likelyto be required over the unit and the unitwill be particularly vulnerable to flotationin grou ndwater. Engi neeri ng adviceshou Id be sought.

The ACO Q-Ceptor range of separators isEnvironment Agency compliant andconforms fully to the requirements ofPPG3. In addition, all ACO Q-Ceptorseparators have been designed andindependently tested to BS EN 858-1 :2002 and BS EN 858-2:2003. Thecustomer (or their client) is responsiblefor ensuring that the installation of theunit is in compliance with any regulatoryrequirements of the planning authorities,Building Control, Environment Agency,Water Company, national and Europeanstandards, etc.

Installation should only be carried outby an experienced and competentcontractor. Electrical work (e.g, alarms)must only be carried out by a suitablyqualified electrician.

Contractors are advised to obtain a copy of the full installation recommendations. To do so, please contactthe ACO Water Management Design Services Team

»:St~;~~00Tel: 01278 671927

Page 12: S crJ ACO - Wastewater Products Somerset UK by … - 150 Oil storage capacity (litres) 300 - 1000 Silt storage capacity (litres) *NSB 10 Aca Q-Ceptor bypass oil separators fully treat

Installation detail

. ACO Q-CEPTOR OIL SEPARATORS

l. The customer shou Id ensu re that therequirements for their particular siteconditions are met, taking engineeringadvice where necessary. Theserecommendations assume that the unit isto be installed with a concrete backfill.

2. Lift using a forklift through the slotsunder the base or webbing slings fixedthrough the lifting holes on the sides of theunit. Do not lift the unit using slingsaround the bypass channel. Take care thatthe units do not tip during handling. Donot drag, drop or roll the units. Store theunits on firm level ground.

3. Excavate a hole to receive the unit,allowing for a minimum of 200mmthickness of concrete below and all aroundthe unit and with sufficient working spacefor the connection of pipework, ducts andvents. Any unsuitable ground is to beremoved and replaced. Engineering advicemay be necessary. The excavation is to bekept free of water.

4. All concrete used in the installation is tobe of minimum grade C15/20. Wherenecessary a higher specification ofconcrete may be required. Engineeringadvice should be sought. Pour a minimum200mm thickness of concrete onto thebase of the excavation, and whilst theconcrete is still wet carefully lower theseparator unit onto the concrete. Checkthat the unit is fully supported by the

concrete, is level and at the correct height.Check the orientation. Allow the concreteto harden.

5. Add 500mm depth of water to theinside of the unit. Carefully placeadditional concrete to the sides of the unitto a level between 400mm and 500mmabove the base of the unit. Do not usevibrating pokers. Check that the unit is stillcorrectly positioned and level. Allow thisconcrete to harden.

5. Add water to fill the unit to the invert ofthe outlet pipe. Carefully place additionalconcrete to the sides of the unit to a leveljust below the outlet pipe level, ensuringthere is sufficient room left for theinstallation of the pipework. Allow thisconcrete to harden.

7. Connect the inlet and outlet pipework,vent pipe and bypass access pipe. Thebypass separators have four possible pipediameter connections. Cut the connectionspigot at the appropriate location - see fullinstallation recommendations for furtherguidance. Using pipe diameters other thanthose stated in the brochure and guidancewill reduce the efficiency of the separator.

8. If an extension shaft is required, cut theshaft to the correct length and fit it to thetop of the unit with sealant 8- 10mm thick.

Vent pipe height and locationto comply with local regulation

Alarm cable duct throughextension shaft (or single collar of unit)

Alarm configurationo High level alarm sensor probe

o Oil level sensor probe (mandatory)

e Silt level sensor probe

ACO Q-Ceptor Bypass chamberdetail only

Bypass access socket

9. Install a duct (with drawstrings) for theelectrical cabling to the alarm.

10. Place further concrete backfill to theunit, in pours of maximum 500mm heightallowing the concrete to harden betweenpours.

11. Fit the cover and frame.

12. If a sampling pump is to be fitted, fixthe top hose clamp near to the undersideof the cover and attach the hose to the tophose clamp.

13. Fit the alarrnts), This work is to becarried out by a qualified electrician. Thealarm probes are to be hung at the correctlevels, as shown in the detailed installationinstructions.

III

14. Ensure any debris is cleared frominside the unit. Top up the unit with cleanwater. Fit the float (only required in fullretention separators) and the coalescingfilter (only required in Class 1 separators).Ensure that the float has floated up off itsseating, (and if necessary lift it off itsseating so that it is floating).

~~An electronic version of theACa Q-Ceptor installation

detail is available to down load from theACa website. Visit www.aco.co.uk.

Page 13: S crJ ACO - Wastewater Products Somerset UK by … - 150 Oil storage capacity (litres) 300 - 1000 Silt storage capacity (litres) *NSB 10 Aca Q-Ceptor bypass oil separators fully treat

ACO Q-Ceptor

Guide to installing the ACO Q-Ceptor

Step 1:

+-«,

For a bypass separator, cut theconnection collar to suit the required sizeof connecting pipework.

Step 4:

01

Add more water to the separator andbackfill with concrete, keeping the waterapproximately 500mm above theconcrete level. Fill the unit with water tothe invert level of the outlet pipe. Backfillwith concrete until the concrete is justbelow the outlet pipe level, ensuring thatthere remains adequate working room tofit the pipework.

Step 2:

Excavate a hole 200mm wider anddeeper than the separator chamber. Setthe chamber to reqi ired level on aminimum 200mm cleep bed of concrete(minimum grade 16(20). Ensure inlet andoutlet are at the correct orientation andlevel. Allow concrete to harden.

Step 5:

/-G-. :a:rt'to"rf"

.--~-ix-"""~

Push connecting pipe into the collar andmake good a joint with caulking and asuitable mortar or sealant. Fit bypass accesspipe if required. Connect the vent pipe.Connect alarm cable duct through extensionshaft (or neck of separator) and seal.

Step 3:

Check the level of the inlet and outletpipes and add approximately 500mm ofwater to the chamber. Haunch withbetween 400mm and 500mm ofconcrete. Once completed, check levels.Allow concrete to harden.

Step 6:

Fit extension shaft if required and cut tocorrect height, using sealant to ensure awatertight joint between the shaft and theseparator. Complete fitti ng of thesampling pump hose (if required). Backfillwith concrete in 500mm steps, allowingconcrete to harden between pours. Bracethe inside of the extension shaft ifnecessary to avoid distortion during theconcrete pours. Continue until finalconcrete level is reached (just belowunderside of cover frame).

Page 14: S crJ ACO - Wastewater Products Somerset UK by … - 150 Oil storage capacity (litres) 300 - 1000 Silt storage capacity (litres) *NSB 10 Aca Q-Ceptor bypass oil separators fully treat

Step 7:

Trim extension shaft to correct height. Fitthe cover frame. Fit the alarm system inaccordance with the manufacturer'sinstallation recommendations - this shouldbe carried out by a qualified electrician.Lower the ACD into position (full retentionseparators only). Lower the filter intoposition (Class 1 separators only).

Step 8:

Ensure that the unit is free from all debrisand fill with water to the outlet level.Ensure that the float is floating (ifapplicable) and the filter is correctlypositioned (if applicable). Fit the cover.

III

Page 15: S crJ ACO - Wastewater Products Somerset UK by … - 150 Oil storage capacity (litres) 300 - 1000 Silt storage capacity (litres) *NSB 10 Aca Q-Ceptor bypass oil separators fully treat

ACO Q-Ceptor

Maintenance and servicing

In order to ensure the reliable functioningof oil separators and ongoingenvironmental protection they requireregular maintenance and servicing.Unless this is done, environmentaldamage and the resulting risk of liabilitycannot be prevented.

ACO service partners work closely withthe UK Environment Agencies and areable to offer ongoing maintenance andservicing programmes, waste disposal,inspection, testing and full installationand commissioning of oil separators andalarms. For further details please contactthe ACO Water Management DesignServices Team on 01462 816666.

22

III

Certification

Model specification clause

The oil separator shall be an ACOQ-Ceptor Oil Separator supplied byACO Water Management, [Full Retentionor Bypass], [size NS* or NSB*], [Class 1or Class 2#]. The unit shall bemanufactured from High DensityPolyethylene and include (for Class 1separators) a coalescing filtermanufactured from polypropylene fibresreinforced with stainless steel wire andinclude (for full retention separators) aweighted float automatic closure device.The unit is to be designed andmanufactured in accordance withBS EN 858-1, and is to conform to therecommendations in the EnvironmentAgency Guidelines PPG3.

The oil separator is to be installed inaccordance with the manufacturer'srecommendations.

* insert nominal size as required# insert the required option

NBS Specifications

ACO Q-Ceptor Oil Separator should bespecified in section R12:421. Assistancein completing this clause can be found inthe ACO Water Management entry in NBSPlus, or please contact the ACO WaterManagement Design Services Team.

Note: A specification in NBS formal isavailable 10 down load from www.lhenbs.comor www.aco.co.uk.

o Recycling

All the components of ACO Q-Ceptor arerecyclable. Separate the units into theplastic and metal parts and recycle inaccordance with local regulations.

ACO Q-Ceptor oil separators are fully certified to BS EN 858-1:2002 and BS EN 858-2:2003.

Test certificates are available on request. Please contact the ACO Water Management Design Services Team on 01462816666 for further information.

BS EN 858-1: 2002BS EN 858-2:2003