russell binscarth regional water system … · 8 4866-01-d-301 0 binscarth reservoir sections ......
TRANSCRIPT
P:\20164866\00_M
WS
B_R
ussell_W
TP
\W
orking_D
wgs\900_P
roject_S
tandards\03 R
oss-B
ins-B
S\4866-00-g-001.dw
g
DA
TE
: 2017-06-28
, D
esiree P
astorin
DRAWING REVISION SHEET
DRAWNDESIGN DESCRIPTIONDATEREV
www.ae.ca
203 - Five Donald Street, Winnipeg, Manitoba, R3L 2T4
Ph: 204 942 6391 Fax: 204 942 6399
0 2017JUN26 K. ANDERSON D. PASTORIN
ISSUED FOR TENDER &
CONSTRUCTION
0
1
26
4866-00-G-001ISSUED FOR TENDER & CONSTRUCTION - JUNE 2017
BINSCARTH & ROSSBURN RESERVOIR UPGRADES &
NEW BOOSTER STATION ON ROAD 117N
M.W.S.B. #: 1368
DISCIPLINE:
G GENERAL
C CIVIL
A BUILDING
S STRUCTURAL
P PROCESS MECHANICAL
M BUILDING MECHANICAL
E ELECTRICAL
I INSTRUMENTATION
DRAWING SERIES:
000 GENERAL, LEGENDS, P&IDs
100 PLANS
200 ELEVATIONS
300 SECTIONS
400 LARGE SCALE VIEWS
500 DETAILS
600 SCHEDULES, DIAGRAMS
700 FIGURES, SKETCHES, ETC.
800 CUSTOM
900 PHOTOS, 3D VIEWS, ETC.
SITE:
00 GENERAL (ENTIRE PROJECT)
01 BINSCARTH WTP
02 ROSSBURN WTP
03 BOOSTER STATION
RUSSELL BINSCARTH REGIONAL WATER SYSTEM
AE PROJECT NUMBER
DRAWING INDEX
SHEET DRAWING NAME REVISION DRAWING TITLE DRAWING DESCRIPTION
GENERAL
1 4866-00-G-001 0 COVER
BINSCARTH WTP: CIVIL
2 4866-01-C-101 0 BINSCARTH RESERVOIR SITE PLAN & DETAILS
BINSCARTH WTP: PROCESS
3 4866-00-D-001 0 BINSCARTH RESERVOIR PID LEGEND
4 4866-00-D-002 0 BINSCARTH RESERVOIR PID LEGEND
5 4866-01-D-003 0 BINSCARTH RESERVOIR PROCESS & INSTRUMENTATION DIAGRAM
6 4866-01-D-101 0 BINSCARTH RESERVOIR EXISTING MAIN FLOOR & DEMOLITION PLAN
7 4866-01-D-102 0 BINSCARTH RESERVOIR PROPOSED MAIN FLOOR PLAN
8 4866-01-D-301 0 BINSCARTH RESERVOIR SECTIONS & ISOMETRIC VIEW
BINSCARTH WTP: ELECTRICAL
9 4866-01-E-101 0 BINSCARTH RESERVOIR EXISTING MAIN FLOOR & DEMOLITION PLAN
10 4866-01-E-102 0 BINSCARTH RESERVOIR PROPOSED MAIN FLOOR PLAN
11 4866-01-E-601 0 SCHEMATICS SINGLE LINE DIAGRAM
ROSSBURN WTP: CIVIL
12 4866-02-C-101 0 ROSSBURN RESERVOIR EXISTING SITE PLAN
ROSSBURN WTP: PROCESS
13 4866-02-D-001 0 ROSSBURN RESERVOIR PROCESS & INSTRUMENTATION DIAGRAM
14 4866-02-D-101 0 ROSSBURN RESERVOIR EXISTING MAIN FLOOR PLAN
15 4866-02-D-102 0 ROSSBURN RESERVOIR PROPOSED MAIN FLOOR PLAN
16 4866-02-D-301 0 ROSSBURN RESERVOIR SECTIONS & ISOMETRIC VIEW
ROSSBURN WTP: ELECTRICAL
17 4866-02-E-101 0 ROSSBURN RESERVOIR MAIN FLOOR PLAN
BOOSTER STATION: CIVIL
18 4866-03-C-101 0 ROAD 117N BOOSTER STATION SITE PLAN & DETAILS
BOOSTER STATION: BUILDING
19 4866-03-A-101 0 ROAD 117N BOOSTER STATION MAIN FLOOR PLAN & SECTION
20 4866-03-A-201 0 ROAD 117N BOOSTER STATION ELEVATIONS
21 4866-03-A-601 0 ROAD 117N BOOSTER STATION SCHEDULES
BOOSTER STATION: STRUCTURAL
22 4866-03-S-101 0 ROAD 117N BOOSTER STATION MAIN FLOOR PLAN & SECTIONS
BOOSTER STATION: PROCESS
23 4866-03-D-001 0 ROAD 117N BOOSTER STATION PROCESS & INSTRUMENTATION DIAGRAM
24 4866-03-D-101 0 ROAD 117N BOOSTER STATION MAIN FLOOR PLAN & SECTIONS
BOOSTER STATION: MECHANICAL
25 4866-03-M-101 0 ROAD 117N BOOSTER STATION MAIN FLOOR PLAN
BOOSTER STATION: ELECTRICAL
26 4866-03-E-101 0 ROAD 117N BOOSTER STATION MAIN FLOOR PLAN & SCHEDULES
1S
T A
VE
T
H
A
C
K
E
R
S
T
C
R
E
R
A
R
S
T
PR 478
R
U
S
S
E
L
L
S
T
2
N
D
A
V
E
3
R
D
A
V
E
1
S
T
A
V
E
2
N
D
A
V
E
3
R
D
A
V
E
1
S
T
A
V
E
4
T
H
A
V
E
4
T
H
A
V
E
5
T
H
A
V
E
T
H
A
C
K
E
R
S
T
R
U
S
S
E
L
L
S
T
W
I
L
L
I
A
M
S
T
JE
MIM
A S
T
PR 478
EXISTING
RESERVOIR
150Ø RURAL WATER
PIPELINE (FROM RUSSELL)
150Ø WATER
DISTRIBUTION LINE
200Ø SANITARY SEWER
3
.8
0
5
.1
0
NEW STANDBY GENERATOR
ON CONCRETE PAD
(CONFIRM LOCATION ON SITE
w/ OWNER & ENGINEER)
EXISTING
WTP
BOLLARD,
TYP OF 7
1
S
T
A
V
E
PROPERTY LIMIT
100Ø RURAL WATER
PIPELINE (TO GAMBLER FN)
150Ø RAW WATER
SUPPLY LINE
ABANDONED
WATER LINES
150Ø RESERVOIR
FILL LINE
150Ø & 75Ø RESERVOIR
SUCTION LINES
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
U
T
G
G
G
G
G
G
G
G
G
G
G
W
R
W
FO
EXISTING
RESERVOIR
150Ø RURAL WATER
PIPELINE (FROM RUSSELL)
150Ø WATER
DISTRIBUTION LINE
200Ø SANITARY SEWER
3
.
8
0
5
.
1
0
NEW STANDBY GENERATOR
ON CONCRETE PAD
(CONFIRM LOCATION ON SITE
w/ OWNER & ENGINEER)
EXISTING
WTP
BOLLARD,
TYP OF 7
1
S
T
A
V
E
PROPERTY LIMIT
OP
OP
100Ø RURAL WATER
PIPELINE (TO GAMBLER FN)
150Ø RAW WATER
SUPPLY LINE
ABANDONED
WATER LINES
150Ø RESERVOIR
FILL LINE
150Ø & 75Ø RESERVOIR
SUCTION LINES
P:\20164866\00_M
WS
B_R
ussell_W
TP
\W
orking_D
wgs\400_P
rocess_M
ech\03 R
oss-B
ins-B
S\01-B
insW
TP
\4866-01-c-101.dw
g
DA
TE
: 2017-06-26
, D
esiree P
astorin
DRAWING REVISION
DESCRIPTIONDRAWNDESIGNDATEREV
SHEET
IF
N
OT
5
0 m
m A
DJU
ST
S
CA
LE
S
SC
AL
E(S
) S
HO
WN
A
RE
IN
TE
ND
ED
F
OR
A
NS
I D
(2
2X
34
) S
IZ
E D
RA
WIN
GS
, T
AB
LO
ID
(1
1X
17
) S
IZ
E D
RA
WIN
GS
A
RE
1
/2
O
F S
CA
LE
(S
) S
HO
WN
U
NL
ES
S N
OT
ED
O
TH
ER
WIS
E
SCALE:
50
m
m
www.ae.ca
203 - Five Donald Street, Winnipeg, Manitoba, R3L 2T4
Ph: 204 942 6391 Fax: 204 942 6399
ORIGINAL SEALED BY:
K. ANDERSON, P.ENG.
DATED: JUNE 26, 2017
RUSSELL BINSCARTH
REGIONAL WATER SYSTEM
BINSCARTH & ROSSBURN
RESERVOIR UPGRADES &
NEW BOOSTER STN ON ROAD 117N
M.W.S.B. # 1368 / AE # 20164866-03
AS SHOWN
CIVIL
BINSCARTH RESERVOIR
SITE PLAN & DETAILS
4866-01-C-101 0
2
26
0 2017JUN26 K. ANDERSON T. DYCHKO
ISSUED FOR TENDER &
CONSTRUCTION
PLAN
1
-
KEY
1:5000
PLAN
2
-
EXISTING SITE
1:200
WORK AREA
FENCE
RAILWAY
LINETYPES
SANITARY SEWER
BOLLARD
BUSH
SYMBOLS
GAS
UNDERGROUND POWER
OVERHEAD POWER
UNDERGROUND TELEPHONE
FIBRE OPTIC CABLE
WATER MAIN
MANHOLE
METER
FIRE HYDRANT
GATE VALVE
HYDRO / UTILITY POLE
GUY WIRE
TELEPHONE PEDESTAL
FLUSHOUT
LEGEND
EXISTING PROPOSED
EXISTING PROPOSED
NOTES:
1. ALL MATERIALS AND INSTALLATION PRACTICES SHALL
CONFORM TO M.W.S.B. STANDARD CONSTRUCTION
SPECIFICATIONS.
2. DECIMALIZED NUMBERS INDICATE METERS AND WHOLE
NUMBERS INDICATE MILLIMETERS.
3. LOCATION OF UNDERGROUND SERVICES AS SHOWN ARE
BASED ON THE BEST INFORMATION AVAILABLE, BUT NO
GUARANTEE IS GIVEN THAT ALL EXISTING SERVICES ARE
SHOWN OR THAT THE GIVEN LOCATIONS ARE EXACT.
4. CONTRACTOR MUST CONFIRM WITH THE INDIVIDUAL
UTILITIES FOR EXISTENCE AND EXACT LOCATIONS OF ALL
THE SERVICES PRIOR TO CONSTRUCTION.
5. ALL SITE LAYDOWN AREAS SHALL BE AS NOTED IN THE
SPECIFICATIONS AND APPROVED BY THE OWNER AND
ENGINEER.
EXCAVATE EXISTING SOIL TO A DEPTH OF 600 AND REPLACE w/ NON-WOVEN
GEOTEXTILE AND GRANULAR BASE COURSE IN 150 LIFTS COMPACTED TO 95% S.P.D.
VERIFY SUBGRADE w/ ENGINEER PRIOR TO CONSTRUCTION.
15
0
PAD TO BE 250 LARGER THAN
GENSET ALL AROUND
300 THICK CONCRETE PAD
R/W 15M @ 300 E.W.
TOP & BOTTOM
20
0
70
09
00
10
00
HDPE BOLLARD SLEEVE
YELLOW w/ RED REFLECTIVE BANDS
(ENCORE COMMERCIAL PRODUCTS, OR EQUAL)
150Ø - 6 THK GALV. SCH40 PIPE
CONCRETE FILLED
20 mm DOWN CRUSHED LIMESTONE
300Ø CONCRETE BASE
100 LONG, 50x50x6 STRAIGHT
ANGLE ANCHOR CLIPS
(2 PER POST)
DETAIL
3
-
GENERATOR PAD
NTS DETAIL
4
-
BOLLARD
NTS
VILLAGE OF
BINSCARTH
LINE SYMBOLS
HEAT TRACE - ELECTRIC
INSULATION
DIRECTION OF FLOW
SECONDARY FLOW
PRIMARY FLOW
-2% SLOPE
LINE SPECIFICATION CHANGE
CONNECTING LINES
MEDIUM FLOW
VENDOR PACKAGE
REMOVED OR DEMOLISHED PIPING
CROSSOVER LINES
LINE CONTINUATION TO
ANOTHER DRAWING
EXISTING OR NOT INCLUDED IN
THIS CONTRACT
PIPE TO PIPE (OR FITTINGS) CONNECTIONS
VALVE SYMBOLS AND IDENTIFICATION TAGS
PIPE TO VALVE CONNECTIONS
FLANGE TO FLANGE (SLIP ON)
DESCRIPTION
THREADED
DESCRIPTION
UNION
SLIP ON FLANGE
WELDED
BLIND FLANGE OR CAPPED
BELL AND SPIGOT,
SCREWED CONNECTION
(DRESSER STYLE 38 eg)
FLEXIBLE COUPLING
VICTAULIC COUPLING
(DRESSER STYLE 128 eg)
FLANGED/FLEXIBLE COUPLING
DIAPHRAGM SEAL
RUPTURE DISC
ECCENTRIC REDUCER
CONCENTRIC REDUCER
SAFETY SHOWER
REDUCER BUSHING
EYE WASH
PIPE ACCESSORY SYMBOLS
STRAINER Y TYPE
SINGLE LINEDOUBLE LINE
SINGLE LINE 50mm
OR LESS
DOUBLE LINE 65mm
OR LARGER
FLEXIBLE COUPLING
(SINGLE BOOT)
FBS
RD-
HC HOSE CONNECTION
HB HOSE BIBB
OPEN DRAIN TO SEWER
OR FLOOR DRAIN
STRAINER
BASKET TYPE
E
DWG No.
VCVC
FCCFCC
GOOSE NECK
VENT (PIPE)
1 (ONE) FOR EACH DIFFERENT PIECE OF EQUIPMENT)
SEQUENCE NUMBER (IN NUMERICAL ORDER STARTING WITHCOMMODITY
PIPE MATERIAL CODE
LINE SIZE (IN MILLIMETRES)
DCW
CD
DOMESTIC COLD WATER
CENTRIFUGE DECANT
AVL
AL
AS
AIR VACUUM LINE
ALUM SOLUTION
ALUM LIQUID
300 - PW - A1
LINE IDENTIFICATION
UNDER DRAIN (WEEPING TILE)UD
SHS SODIUM HYPOCHLORITE
ASP
COMPONENT NUMBER
AREA NUMBER
PWP - _401 (A,B etc)
EQUIPMENT IDENTIFICATION
ALUM SOLUTION PUMP
COMPONENT NUMBER
1 (ONE) FOR EACH DIFFERENT PIECE OF EQUIPMENT)
SEQUENCE NUMBER (IN NUMERICAL ORDER STARTING WITH
VALVE IDENTIFICATION
AREA NUMBER
GAV - _401
BLOCK & BLEED VALVE
SG
NEV
PLV
ROV
PV
NEEDLE VALVE
PLUG VALVE
PINCH VALVE
ROTARY VALVE
SLUICE GATE VALVE
FV
GAV
GLV
KGV
MUV
CHV
DIV
FGV
BAV
BBV
BUV
BV
AVV
ARV
CHECK VALVE
DIAPHRAGM VALVE
FLAP GATE VALVE
FOOT VALVE
GATE VALVE
GLOBE VALVE
KNIFE GATE VALVE
MUD VALVE
AIR RELIEF VALVE
AIR/ VACUUM VALVE
BALL VALVE
BUTTERFLY VALVE
BLOCK VALVE
DUPLICATION IDENTIFIER (OPTIONAL USAGE)
CITRIC ACIDCR
CIP CLEAN IN PLACE
PERW PERMEATE WATER
CAV
SERVICE AIR
SENSING LINE
SUPERNATANT OVERFLOW
SURGE RELIEF LINE
SANITARY WASTE (RAW SEWAGE)
SRL
SW
SO
SEL
SA
HOT WATER SUPPLY
INSTRUMENT AIR (FILTERED
NATURAL GAS MEDIUM PRESSURE
OVERFLOW PIPE
PRESSURE RELIEF LINE
PLANT SERVICE WATER (USUALLY
POTABLE WATER (SAFE FOR
HUMAN CONSUMPTION)
RAW SANITARY WASTE
RAW WATER (NOT SAFE FOR
HUMAN CONSUMPTION)
RSW
RW
PPSW
PW
PRF
OV
NGM
IA
HWS
MOTOR (ELECTRIC)
METER VAULT
PUMP (UNSPECIFIED SERVICE)
PULSATION DAMPER
PROPANE GAS TANK
PD
PGT
P
MH
MWA
MV
M
MANHOLE
MANWAY ACCESS
GENERATOR
HOIST (ELECTRIC OR MANUAL)
HOSE CONNECTION
HEAT EXCHANGERHEX
HC
HD HUB DRAIN
H
HB
GEN
HOSE BIBB
ANTISCALENT
CHEMICAL WASTE
CHLORINE GAS
CHLORINE LIQUID
COOLING WATER RETURN
COOLING WATER SUPPLY
COOLING WATER WASTE
DRAINDR
CWS
CWW
CLL
CWR
CHW
CLG
ASC
ZEOLITE SOFTENED WATERZW
VACUUM LINE
VENTILATION PIPE
VA
VE
AIR RECEIVER TANK
BACK FLOW PREVENTER
BLO
BFP
BLOWER
ART
AIR LIFT PUMPALP
AER AERATOR
VALVE BOX
VALVE VAULTVV
VB
P1
J2
H3
J1
H1
H2
G1
G2
F2
F3
E7
F1
E6
E5
E4
E3
E1
E2
D1
A1G
A1A
A8
A7
A5
A6
A4
A3
CODE
PIPE MATERIAL CODES
A2
A1
MATERIAL AND FLANGE RATING
HOSE REELHR
MIXER (MECHANICAL)MX
VARIABLE FREQUENCY DRIVE (ELEC)VFD
SODIUM HYDROXIDESHDS
AIR SCRUBBERASC
VB VACUUM BREAKER
DHW DOMESTIC HOT WATER
EQUIPMENT SYMBOL
VALVE SYMBOL
PID TAGGING
SEQUENCE NUMBER (IN NUMERICAL ORDER STARTING WITH
1 (ONE) FOR EACH DIFFERENT PIECE OF EQUIPMENT)
AREA NUMBER
INSTRUMENT SYMBOL
COMPONENT NUMBER
LIT - -701
STORM DRAINSD
AMLAMMONIA LIQUID (ANHYDROUS)
AMGAMMONIA GAS (ANHYDROUS)
BWW BACK WASH WASTE
BWS BACK WASH SUPPLY
CG CARBON DIOXIDE GAS
COAGULANT AIDCOA
DFS DIESEL FUEL SUPPLY
DHWR DOMESTIC HOT WATER
EFF EFFLUENT
HYDROCHLORIC ACIDHDCA
HYDRATED LIME SLURRYHLS
LIME SOLUTIONLS
POWDER ACTIVATED CARBON (DRY)PAC
PLS PRIMARY LIME SLUDGE
POTASSIUM PERMANGANATEPPS
PLANT SERVICE WATERPSW
QUICK LIME (DRY)QL
SULPHURIC ACIDSLPA
SAMPLE LINESAM
SODA ASH SOLUTIONSOS
SODIUM BISULFITE SOLUTIONSBS
TREATED WATER (PRIMARYTW
TREATMENT, NOT YET SAFE FOR
WASTE WATER (EFFLUENT)WW
AIR COMPRESSORAC
LSK LIME SLAKER
LS LIME SILO
POWDER CARBON FEEDERPCF
OXYGEN GASOG
RINSE TO WASTERTW
SEQUESTERANTSEQ
ACTIVATED CARBON FEEDERACF
BSP BACKWASH SUPPLY PUMP
BRT BRINE TANK
OXYGEN REDUCTION POTENTIALORP
FCV FLOW CONTROL VALVE
TWV THREE (3) WAY VALVE
WG WEIR GATE
EQUIPMENT CODES
EQUIPMENTCODE CODE
VALVE CODES
VALVE
ALSALUM SLUDGE
ASV ANTI-SYPHON VALVE
BACK FLOW PREVENTERBFP
BCV BALL CHECK VALVE
FCC FLANGED/ FLEXIBLE DRESSER COUPLING
PIV POST INDICATOR VALVE
PRV PRESSURE RELIEF VALVE
VC VICTAULIC COUPLING
RECIRCULATION
& DRIED)
PW)
(NON-DRINKABLE WATER)
SOLUTION
(CAUSTIC SODA)
HUMAN CONSUMPTION)
DWH
COMP
CO
CSP CAUSTIC SODA PUMP
COMPRESSOR (INSTRUMENT AIR)
DOMESTIC WATER HEATER
CLEAN OUT
CITRIC ACID PUMPCRSP
CR CRANE
DECHLORINATOR
DT DAY TANK
DEC
CHLORINE CONTACT CHAMBER
CHLORINE GAS CYLINDER
CHLORINE GAS DETECTOR
CGC
CGD
CEF
CB
CCC
CENTRIFUGE
CATCH BASIN
CL CLARIFIER
COAP COAGULANT AID PUMP
SEWAGE PUMPSEP
SIGHT GLASS
SILENCER
SLUDGE PUMP
SPRAY NOZZLE
SEWAGE PUMP
SLP
SP
SN
SG
SIL
PWP POTABLE WATER PUMP
RAW WATER PUMPRWP
SHSP SODIUM HYPOCHLORITE PUMP
PPP POTASSIUM PERMANGANATE PUMP
RESERVOIRRES
SULPHURIC ACID PUMPSACP
SODA ASH FEEDERSOF
SODA ASH HOPPERSOH
SODA ASH SOLUTION PUMPSOSP
SODA ASH SOLUTION TANKSPST
SEQUESTERANT PUMPSEQP
STOP LOGSSL
PIG LAUNCHERPL
SUMP PUMPSUP
STEEL PIPE 900mm Dia AND SMALLER
150 POUND FLANGE RATING
STEEL PIPE 900mm Dia AND SMALLER
300 POUND FLANGE RATING
STEEL PIPE 1050mm Dia AND LARGER
150 POUND FLANGE RATING
STEEL PIPE 1050mm Dia AND LARGER
300 POUND FLANGE RATING
STEEL PIPE 600mm Dia AND SMALLER
150 POUND FLANGE RATING
STEEL PIPE 600mm Dia AND SMALLER
300 POUND FLANGE RATING
STEEL PIPE 300mm Dia AND SMALLER A1 PIPE
CODE VICTAULIC COUPLED
STEEL PIPE 100mm Dia AND SMALLER A2 PIPE
CODE CHLORINE GAS, CARBON DIOXIDE GAS
STEEL PIPE 200mm Dia AND SMALLER 150
POUND FLANGE RATING GAS SERVICE ONLY
GALVANIZED STEEL PIPE 100mm Dia AND
SMALLER 150 POUND FLANGE RATING
CONCRETE PIPE - PRESSURE PIPE
PVC PIPE (PRESSURE PIPE)
PVC PIPE - GRAVITY SERVICE
POLYETHYLENE PIPE
CPVC PIPE (PRESSURE PIPE)
PLASTIC FLEXIBLE TUBING
RUBBER HOSE
PVDF PIPE (PRESSURE PIPE)
CAST IRON PRESSURE PIPE
CAST IRON DRAINAGE PIPE
DUCTILE IRON PIPE - PRESSURE SERVICE
COPPER PIPE - TYPE K
COPPER PIPE - TYPE L
STAINLESS STEEL PIPE
STAINLESS STEEL TUBING
STEEL TUBING
CORRUGATED METAL PIPE - GALVANIZED
CORRUGATED METAL PIPE (WEEPING TILE)
PLASTIC DWV, COPPER DWV, CAST IRON DWV
PLUMBING SERVICE
CONCRETE PIPE - REINFORCEDD2
CONCRETE PIPE - NON REINFORCEDD3
BACK PRESSURE VALVEBPV
HWT HOT WATER TANK
END CAP
AIR RELIEF VALVE
AIR/ VACUUM VALVE
EQUALIZING VALVE
ON MAIN
VALVE BODY
NEEDLE VALVE
FLAP GATE
PINCH VALVE
CHECK VALVE
BUTTERFLY VALVE DIAPHRAGM VALVE
BLOCK VALVE
DRAIN VALVE ON
MAIN VALVE BODY
KNIFE GATE VALVE
GLOBE VALVE
PLUG VALVE
BLOCK &
BLEED VALVE
BALL CHECK
VALVE
CHV-
BCV-
KGV-
FGV-
BUV-
GLV-
PLV-
NEV-
DIV-
PV-
BBV-
AVV-
ARV
CAV-
VB-
BFP-
ASV-
PV3-
BACKFLOW PREVENTOR
(REDUCED PRESSURE
PRINCIPLE)
COMBINATION AIR
RELIEF & AIR/
VACUUM VALVE
VACUUM
BREAKER
ANTI-SIPHON
VALVE
THREE WAY VALVE
FOOT VALVE
(CHECK)
BAV-
BALL VALVE
BFP-
BACKFLOW
PREVENTOR
(ANTI-SIPHON)
FV-
SLUICE GATE
SG-
GATE VALVE
GAV-
FLEXIBLE CONNECTION
FILTRATEFLT
FLW FLUSHING WATER
FILTERED WATERFIL
FILTER TO WASTE DRAINFTW
FIRE WATERFW
FLUOSILICIC ACID (FLUORIDE)FLU
LE LEVEL ELEMENT
FC FLEXIBLE DRESSER COUPLING
COMBINATION AIR RELIEF & AIR/ VACUUM
VALVE
MECHANICAL JOINT
FUNNEL DRAINFUD
FUEL TANK
ESH EMERGENCY SHOWER UNIT
FLOOR BOX (VALVE)
FIRE EXTINGUISHER
FIXED SCREEN (BAR OR MESH)FS
FD
FEX
FB
FLOOR DRAIN
EDUCTOR OR EJECTORED
ENG ENGINE
FLUOSILICIC ACID (FLUORIDE) PUMPFAP
FILTER (PROCESS WATER)FIL
FIRE HOSE CONNECTIONFHC
FIRE HYDRANTFH
FT
TANK (UNSPECIFIED SERVICE)T
UV ULTRAVIOLET
TRAVELING WATER SCREENTWS
TRANSFER PUMPTP
INQ INJECTION QUILL
M
M
M
M
M
M
AIR
M
M
M
M
M
M
EQUIPMENT SYMBOLS
ROTARY
COMPRESSOR
RECIPROCATING
COMPRESSOR
CENTRIFUGAL
FAN
(OR BLOWER)
CENTRIFUGAL
PUMP
VERTICAL
TURBINE
PUMP
ROTARY
PUMP
PROPORTIONING
PUMP
FIXED
SCREEN
CLOSED
STORAGE
TANK
PRESSURE
TANK
OPEN
STORAGE TANK
ELECTRIC
MOTOR
TANK
MIXER
STATIC
MIXER
IN-LINE
MIXER
INJECTION QUILL
(CHEM. INJECTION
NOZZLE)
JET MIXER
EDUCTOR
EJECTOR
SCREW
CONVEYOR
SUBMERSIBLE
PUMP
PROGRESSIVE CAVITY
PUMP
WELL
PUMP
AIR DRIVEN
PUMP
M
AERATION AIR SUPPLY
COMMODITY
COMMODITY CODES
CODE
AAS
AQUEOUS AMMONIAAA
CORROSION INHIBITORCI
NORMALLY CLOSEDNORMALLY OPEN
CONTROL VALVE AND ACTUATOR SYMBOLS
CYLINDER
MOTORIZED
DIAPHRAGM ACTUATED GLOBE BODY
RELIEF VALVE
PSV - PRESSURE SUSTAINING VALVE
PRV - PRESSURE RELIEF VALVE
PCV - PRESSURE CONTROL VALVE
DIRECT ACTING SAFETY RELIEF VALVE
GLOBE BODY
PSV - PRESSURE RELIEF VALVE
PRV - PRESSURE REDUCING VALVE
DIAPHRAGM SPRING OPPOSED
WITH PILOT AND POSITIONER
DIAPHRAGM ACTUATED PRESSURE
REDUCING VALVE (FLAG IN
DIRECTION OF REDUCED PRESSURE)
SOLENOID VALVE
SOLENOID
S
S
HAND WHEEL
OPERATOR
IA
S
M
BPV-
BACK PRESSURE
VALVE
P:\20164866\00_M
WS
B_R
ussell_W
TP
\W
orking_D
wgs\400_P
rocess_M
ech\03 R
oss-B
ins-B
S\01-B
insW
TP
\4866-01-d-001.dw
g
DA
TE
: 2017-06-26
, D
esiree P
astorin
DRAWING REVISION
DESCRIPTIONDRAWNDESIGNDATEREV
SHEET
IF
N
OT
5
0 m
m A
DJU
ST
S
CA
LE
S
SC
AL
E(S
) S
HO
WN
A
RE
IN
TE
ND
ED
F
OR
A
NS
I D
(2
2X
34
) S
IZ
E D
RA
WIN
GS
, T
AB
LO
ID
(1
1X
17
) S
IZ
E D
RA
WIN
GS
A
RE
1
/2
O
F S
CA
LE
(S
) S
HO
WN
U
NL
ES
S N
OT
ED
O
TH
ER
WIS
E
SCALE:
50
m
m
www.ae.ca
203 - Five Donald Street, Winnipeg, Manitoba, R3L 2T4
Ph: 204 942 6391 Fax: 204 942 6399
ORIGINAL SEALED BY:
K. ANDERSON, P.ENG.
DATED: JUNE 26, 2017
RUSSELL BINSCARTH
REGIONAL WATER SYSTEM
BINSCARTH & ROSSBURN
RESERVOIR UPGRADES &
NEW BOOSTER STN ON ROAD 117N
M.W.S.B. # 1368 / AE # 20164866-03
AS SHOWN
PROCESS
BINSCARTH RESERVOIR
PID LEGEND
4866-00-D-001 0
3
26
0 2017JUN26 N/A N/A
ISSUED FOR TENDER &
CONSTRUCTION
FLOW TUBE
TARGET OR
MASS FLOWMETER
90
150
250
200
125
100
22
WITH INTEGRAL
MAGNETIC FLOWMETER
M
ULTRASONIC LEVEL
TRANSMITTER
FLOW AND METERING SYMBOLS
6 1/8
1/2
3
2
2
5
4
1/2
1
1/2
3/4
1/41
1
3/8
1/4
40
80
65
50
8
20
15
10
32
25
18
24
20
14
16
15
600
500
450
350
400
375
FE-
PIPE CONVERSION CHART
M
FLUME WEIR TURBINE OR
PROPELLER TYPE
PRIMARY ELEMENT
ROTAMETER TYPE
FLOW INDICATOR
PITOT TUBE OR PITOT
VENTURI TUBE
ORIFICE PLATE TYPE
FLOW INDICATOR RO -
RESTRICTION ORIFICE
FLOW SIGHT
GLASS
FLOW STRAIGHTENING
VANES
VENTURI TUBE
FLOAT SWITCH
(LEVEL BULBS)
VORTEX SENSOR
POSITIVE DISPLACEMENT
TYPE FLOW
TOTALIZING INDICATOR
CORIOLIS MASS
FLOWMETER
MAGNETIC FLOWMETER SONIC FLOWMETER
"DOPPLER" OR "TRANSIT
TIME" MAY BE ADDED
10
8
6
TRANSMITTER
3 1/2
550
PRESSURE TRANSMITTER
(BALL VALVE SHOWN, OTHER
VALVES ARE OPTIONAL)
PRESSURE INDICATOR
(BALL VALVE SHOWN, OTHER
VALVES ARE OPTIONAL)
NOTE: PIPE SIZE FROM 2" THROUGH TO 60" - CONVERSION
BASED ON CSA STANDARD Z245.1 PIPE SIZE 2" AND
SMALLER - CONVERSION BASED ON EUROPEAN ISO
STANDARD OTHER PIPE SIZES ARE U.S. CONVERSIONS TO
THE METRIC SYSTEM
NOMINAL
PIPE
DIAMETER
INCHES
NOMINAL
PIPE
DIAMETER
MILLIMETRES
NOMINAL
PIPE
DIAMETER
INCHES
NOMINAL
PIPE
DIAMETER
MILLIMETRES
BA
V-
BA
V-
FE
-
FE
-
FE
-
FE
-
FE
-
LS
-
FE
-
FE
-
FIT
- FE
-
30012
PIT
-
PI
-
FLOW
LEVEL
PRESSUREMISCELLANEOUS
TEMPERATURE
PANEL MOUNTED INSTRUMENT
UNDEFINED INTERLOCK LOGIC
BACK OF PANEL MOUNTED INSTRUMENT
PILOT LIGHT
I
LOCALLY MOUNTED INSTRUMENT
MAY BE DEPICTED BY USING THE SAME SYMBOLS BUT WITH DASHED HORIZONTAL
NORMALLY INACCESSIBLE OR BEHIND-THE-PANEL DEVICES OR FUNCTIONS
USED WHEN IT IS NECESSARY TO SPECIFY INSTRUMENT OR FUNCTION LOCATION.
IC2 (INSTRUMENT CONSOLE #2), CC3 (COMPUTER CONSOLE #3), ECT., MAY BE
ABBREVIATION OF THE USER'S CHOICE SUCH AS IPI (INSTRUMENT PANEL #1),
IS SHOWN ABOVE. CONSISTENCY IS RECOMMENDED.
DOCUMENT. A SUGGESTED SQUARE AND CIRCLE SIZE FOR LARGER DIAGRAMS
SYMBOL SIZE MAY VARY ACCORDING TO THE USER'S NEEDS AND THE TYPE OF
MOUNTED
FIELD
11.10.
BARS, I.E.
***
LOGIC CONTROL
PROGRAMMABLE
**
*
ACCESSIBLE TO
SHARED DISPLAY
SHARED CONTROL
FUNCTION
COMPUTER
INSTRUMENTS
DISCRETE
7. 8.
IP1**
OPERATOR
4.
1.
*
5.
2.
***NORMALLY
LOCATION
PRIMARY
12.
ACCESSIBLE TO
9.
OPERATOR
6.
3.
***NORMALLY
LOCATION
AUXILIARY
ELECTROMAGNETIC OR SONIC SIGNAL *** (NOT GUIDED)
CONNECTION TO PROCESS, MECHANICAL LINK, OR INSTRUMENT SUPPLY
THE FOLLOWING ABBREVIATIONS DENOTE TYPES OF POWER SUPPLY
AIR SUPPLY (PLANT AIR, HEADER SUPPLY REGULATED
FILTERED AIR SUPPLY (REGULATED eg ADJUSTED TO 138 kPa)
OPTIONAL BINARY (ON-OFF) SYMBOLS
OR
PNEUMATIC BINARY SIGNAL
INTERNAL SYSTEM LINK (SOFTWARE OR DATA LINK)
ELECTRIC BINARY SIGNAL
MECHANICAL LINK
ES
OR
WS
ELECTRIC SUPPLY
ELECTROMAGNETIC OR SONIC SIGNAL *** (GUIDED)
CAPILLARY TUBING (FILLED SYSTEM)
HYDRAULIC SIGNAL
UNDEFINED SIGNAL
WATER SUPPLY
1 PSI = 6.894 kPa
PNEUMATIC SIGNAL **
ELECTROMAGNETIC PHENOMENA INCLUDE HEAT, RADIO WAVES, NUCLEAR RADIATION,
MEDIUM. IF A GAS OTHER THAN AIR IS USED, THE GAS MAY BE IDENTIFIED BY A
THE PNEUMATIC SIGNAL SYMBOL APPLIES TO A SIGNAL USING ANY GAS AS THE
A 100-PSIG AIR SUPPLY; ES-24DC, A 24 VOLT DIRECT CURRENT POWER SUPPLY.
THE SUPPLY LEVEL MAY BE ADDED TO THE INSTRUMENT SUPPLY LINE, E.G., AS-100,
SUPPLY. THESE DESIGNATIONS MAY ALSO BE APPLIED TO PURGE FLUID SUPPLIES.
THE FOLLOWING ABBREVIATIONS ARE SUGGESTED TO DENOTE THE TYPES OF POWER
NOTE: `OR' MEANS USER'S CHOICE. CONSISTENCY IS RECOMMENDED.
NOTE ON THE SIGNAL SYMBOL OR OTHERWISE.
GS - GAS SUPPLY
ES - ELECTRICAL SUPPLY
PA - PLANT AIR
IA - INSTRUMENT AIR
AS - AIR SUPPLY
AND LIGHT.
***
**
*
HS - HYDRAULIC SUPPLY
OPTIONS
WS - WATER SUPPLY
SS - STEAM SUPPLY
NS - NITROGEN SUPPLY
ANALYZING ELEMENT / ALARM LEGEND
CHLORINE
TURBIDITY
pH
DISSOLVED OXYGEN
CONDUCTIVITY
etc
pH
ETC
DO
CON
CLA
TUR
START/STOP
PLC EQUIPMENT OPERATIONS STATUS LEGEND
XS
XA TRIP /UNDEFINED ALARM
XI RUN
CP CONTROL PANEL
ZI VALVE POSITION INDICATION
ZC VALVE POSITION CONTROL
SPEED CONTROLSC
HSI HAND SWITCH POSITION INDICATION
PROGRAMMABLE LOGIC CONTROL
TAG IDENTIFICATION
XXX-XXXX
PLC EQUIPMENT OPERATIONS STATUS TAG
EQUIPMENT TAG
SEQUENCE NUMBER
PLC TAG NUMBER
EXAMPLE XI-RWP-3401
DEVICENET
ETHERNET
FIELDBUS (FF)
MODBUS
PROFIBUS
ELECTRICAL CONTROL SIGNAL
VACUUM RELIEF
PRESSURE CONTROL VALVE LEGEND
VR
SA SURGE ANTICIPATING
RL RELIEVING
RF RATE OF FLOW
REDUCINGRD
SU SUSTAINING
FAL
-
FCV
-
FE
-
FG
-
FI
-
FIT
-
FO
-
FQS
-
FQI
-
FS
-
FT
-
FY
-
FY
-
FY
-
AE
-
AT
-
AIT
-
AAH
-
CI
-
GD
-
HC
-
HIC
-
HJS
-
HS
-
JS
-
KS
-
MOV
-
QS
-
SC
-
WR
-
XSO
-
XSC
-
YS
-
ZS
-
ZT
-
ZC
-
ANALYZING TRANSMITTER
ANALYZING ALARM - HIGH SET POINT
SPEED CONTROL (SCR DRIVE)
LOSS OF POWER SWITCH
MANUAL SELECTOR SWITCH
TIMER OR COUNTER
TORQUE SWITCH
LIMIT SWITCH
WEIGHT RECORDER
EVENT SWITCH
HAND SWITCH
CONDUCTIVITY INDICATOR
VALVE POSITION TRANSMITTER
VALVE POSITION CONTROLLER
LIMIT SWITCH CLOSED
LIMIT SWITCH OPEN
ANALYZING INDICATING TRANSMITTER
GAS DETECTOR
PAH
-
PAL
-
PC
-
PCV
-
PDSH
-
PDSL
-
PDT
-
PI
-
PIC
-
PIT
-
PS
-
PSH
-
PSL
-
PT
-
PY
-
PRESSURE SWITCH - HIGH SET POINT
PRESSURE SWITCH - LOW SET POINT
PRESSURE INDICATING TRANSMITTER
PRESSURE DIFFERENTIAL SWITCH - LOW
PRESSURE DIFFERENTIAL TRANSMITTER
PRESSURE INDICATING CONTROLLER
PRESSURE DIFFERENTIAL SWITCH - HIGH
PRESSURE SOLENOID VALVE
PRESSURE TRANSMITTER
PRESSURE SWITCH
PRESSURE INDICATOR
PRESSURE ALARM - HIGH
PRESSURE CONTROLLER
PRESSURE ALARM - LOW
FLOW SIGNAL INTEGRATOR
FLOW SWITCH
FLOW TRANSMITTER
FLOW SOLENOID VALVE
FLOW INDICATOR
FLOW RESTRICTION ORIFICE
FLOW INDICATING TRANSMITTER
FLOW TOTALIZING INDICATOR
LOW - FLOW ALARM
FLOW SIGHT GLASS
LAH
-
LAHH
-
LAL
-
LALL
-
LC
-
LE
-
LI
-
LIT
-
LSH
-
LSL
-
LS
-
LT
-
LEVEL ELEMENT
LEVEL SWITCH - HIGH SET POINT
LEVEL SWITCH - LOW SET POINT
LEVEL TRANSMITTER
LEVEL INDICATOR
LEVEL ALARM - HIGH
LEVEL CONTROLLER
LEVEL ALARM - VERY LOW
LEVEL ALARM - LOW
LEVEL ALARM - VERY HIGH
LEVEL INDICATING TRANSMITTER
LEVEL SWITCH
TAH
-
TAL
-
TI
-
TSH
-
TSL
-
TS
-
TT
-
TEMPERATURE TRANSMITTER
TEMPERATURE SWITCH - LOW SET POINT
TEMPERATURE SWITCH - HIGH SET POINT
TEMPERATURE SWITCH
TEMPERATURE ALARM - HIGH SET POINT
TEMPERATURE ALARM - LOW SET POINT
TEMPERATURE INDICATOR
HAND INDICATING CONTROLLER
(MANUAL LOADING STATION
WITH OUTPUT GAUGE)
HAND CONTROLLER
(MANUAL LOADING STATION)
MOTORIZED OPERATING VALVE
(OPEN/CLOSE)
ANALYZING ELEMENT
(REFER TO LEGEND)
PRESSURE CONTROL VALVE
(REFER TO LEGEND)
FLOW SIGNAL CONVERTER (CURRENT
INPUT / PNEUMATIC OUTPUT)
FLOW TOTALIZER SWITCH
(PREDETERMINING COUNTER)
FLOW ELEMENT (PRIMARY
ELEMENT WITHOUT TRANSMITTER)
FLOW CONTROL VALVE
(MODULATING)
eg ADJUSTED TO 552 kPa)
P:\20164866\00_M
WS
B_R
ussell_W
TP
\W
orking_D
wgs\400_P
rocess_M
ech\03 R
oss-B
ins-B
S\01-B
insW
TP
\4866-01-d-002.dw
g
DA
TE
: 2017-06-26
, D
esiree P
astorin
DRAWING REVISION
DESCRIPTIONDRAWNDESIGNDATEREV
SHEET
IF
N
OT
5
0 m
m A
DJU
ST
S
CA
LE
S
SC
AL
E(S
) S
HO
WN
A
RE
IN
TE
ND
ED
F
OR
A
NS
I D
(2
2X
34
) S
IZ
E D
RA
WIN
GS
, T
AB
LO
ID
(1
1X
17
) S
IZ
E D
RA
WIN
GS
A
RE
1
/2
O
F S
CA
LE
(S
) S
HO
WN
U
NL
ES
S N
OT
ED
O
TH
ER
WIS
E
SCALE:
50
m
m
www.ae.ca
203 - Five Donald Street, Winnipeg, Manitoba, R3L 2T4
Ph: 204 942 6391 Fax: 204 942 6399
ORIGINAL SEALED BY:
K. ANDERSON, P.ENG.
DATED: JUNE 26, 2017
RUSSELL BINSCARTH
REGIONAL WATER SYSTEM
BINSCARTH & ROSSBURN
RESERVOIR UPGRADES &
NEW BOOSTER STN ON ROAD 117N
M.W.S.B. # 1368 / AE # 20164866-03
AS SHOWN
PROCESS
BINSCARTH RESERVOIR
PID LEGEND
4866-00-D-002 0
4
26
0 2017JUN26 N/A N/A
ISSUED FOR TENDER &
CONSTRUCTION
. .
PW
FROM RUSSELL
100-PW-E1
FE
802
10
0x7
5
75
-P
W-E
1
BU
V-8
01
15
0-P
W-H
1
CAV-821
75-PW-H1
BUV-802
CAV-121
BUV-102
FE
102
CHLORINE CHLORINE CHLORINE CHLORINE
CH
LO
RIN
EC
HLO
RIN
E
M
BAV-501
BAV-801
CH
LO
RIN
E
CHLORINE CHLORINE CHLORINE CHLORINE
CH
LO
RIN
EC
HLO
RIN
E
CHLORINE
CH
LO
RIN
EC
HLO
RIN
EC
HLO
RIN
EC
HLO
RIN
E
CHLORINE
M
BU
V-1
01
75
-P
W-E
1
BA
V-8
20
BA
V-1
20
BA
V-1
22
CAV-123
. .
PW
TO GAMBLER
50x100
DP-101
Distribution Pump
.
10 L/sec @62 psi
DP-102
Distribution Pump
.
10 L/sec @62 psi
DP-103
Distribution Pump
.
10 L/sec @62 psi
BUV-5101
BUV-5201
BUV-5301
CHV-5102 BUV-5103
50x100
CHV-5202 BUV-5203
50x100
CHV-5302 BUV-5303
. .
PW
TO BINSCARTH DISTR.
150x100 100x150
FE
602
FCV-1101
BU
V-1
10
5
FE
702
. .
PW
TRUCK FILL
BU
V-5
00
2
BU
V-5
00
1
PE
666
.
AE
101
CL(FREE)
AIT
101
CL(FREE)
INCOMING
FREE CHLORINE
ANALYZER PANEL
NEV-9999
AE
601
CL(FREE)
AIT
601
CL(FREE)
OUTGOING
FREE CHLORINE
ANALYZER PANEL
NEV-9998
BA
V-6
00
BFP-601
. .
DCW
PLANT DOMESTIC WATER
LSH
662
.
LSL
663
.
FCV-880
FCV-180
BAV-150
BAV-151
PIT
860
.
PI
861
.
BB
V-8
22
SV
188
.
PI
161
.
PIT
160
.
BB
V-1
60
PIT
613
.
PIT
623
.
PIT
633
.
BB
V-5
15
0
EXISTING RESERVOIR
PUMP CONTROL
PANEL
PCP-101
TRI-PLEX PUMP
PACKAGE SKID
c/w CONTROL PANEL
AND VFDs
PIT
160
FI
802
BU
V-1
25
BA
V-6
21
CAV-622
PI
611
-
PI
621
.
PI
631
.
PI
612
-
PI
622
.
PI
632
.
INCOMING
PRESSURE
GAMBLER
PRESSURE
BUV-191
RESERVOIR BY-PASS - DIRECT TO DISTRIBUTION
N.C.
VALVE
100-PW-E1
150-PW-E1
15
0-P
W-H
1
AI
101
SV
188
PIT
860
XI
101
LSH
662
LSL
663
AI
601
FIT
602
FIT
702
FIT
102
FIT
802
NEW PRESSURE
TRANSDUCER MOUNTED IN
RESERVOIR
NEW LEVEL FLOATS
MOUNTED IN RESERVOIR
OPEN/CLOSE
SOLENOID VALVE
FOR FCV-180
OPERATION
CD
P-1
00
1
CD
P-8
00
1
AI
101A
XA
101
ph
INDICATE
FREE CL2
INDICATE
ALARM
FAULT
FQI
802
XA
802
XA
802A
XS
802
FLOW
INDICATE
FLOW
TOTALIZER
ALARM
EMPTY PIPE
ALARM
FAULT
RESET
FI
102
FQI
102
XA
102
XA
102A
XS
102
FLOW
INDICATE
FLOW
TOTALIZER
ALARM
EMPTY PIPE
ALARM
FAULT
RESET
PRESSURE
INDICATION
PRESSURE
INDICATION
SI
101
HSI
101
XS
101
XA
101
AI
601A
XA
601
ph
INDICATE
FREE CL2
INDICATE
ALARM
FAULT
RUN
STATUS
SPEED
INDICATION
HAND SWITCH
INDICATION
START/STOP
GENERAL
ALARM
XA
8001
XS
8001
ALARM
FAULT
RESET
XA
1001
XS
1001
ALARM
FAULT
RESET
PRESSURE
INDICATION
FI
702
FQI
702
XA
702
XA
702A
XS
702
FLOW
INDICATE
FLOW
TOTALIZER
ALARM
EMPTY PIPE
ALARM
FAULT
RESET
FI
602
FQI
602
XA
602
XA
602A
XS
602
FLOW
INDICATE
FLOW
TOTALIZER
ALARM
EMPTY PIPE
ALARM
FAULT
RESET
LEVEL SWITCH
HIGH
LEVEL SWITCH
LOW
PIT
666
PIT
666
.
PI
601
.
PIT
601
.
BB
V-6
01
OUTGOING
PRESSURE
PRESSURE
INDICATION
PIT
601.
150-PW-E1
75-PW-E1
150-PW-E1
CH
V-1
01
BUV-806
BA
V-6
25
CAV-626
M
SHELF SPARE
PLUG
NEW EX.
NE
WE
X.
NE
WE
X.
NE
WE
X.
NE
WE
X.
BFP-1100
RELOCATE EXISTING BFP
NE
WE
X.
BU
V-6
01
TK-601 TK-602
HYDRO P. TANKS
BA
V-7
03
BA
V-7
02
BA
V-7
01
50
-P
W-E
1
75
-P
W-E
1
PR
V-6
01
SAMPLE
TAP
SAMPLE
TAP
SAMPLE
TAP
SAMPLE
TAP
15
0-P
W-H
1
15
0-P
W-H
1
75-PW-E1
15
-S
AM
-E
1
10
0-P
W-E
1
15
0-P
W-E
11
50
-P
W-E
1
100-PW-H1
REVISE AND RE-USE EXISTING
PENETRATION TO SUIT NEW
EQUIPMENT
50-PW-E1
S
25
-P
W-E
1
SO
V-1
10
5
15
0-P
W-E
1
32-PW-G1
BA
V-2
63
15
-S
AM
-E
1
DISTRIBUTION PUMP
15 HP
10 L/SEC @ 65 PSI
DISTRIBUTION PUMP
15 HP
10 L/SEC @ 65 PSI
DISTRIBUTION PUMP
15 HP
10 L/SEC @ 65 PSI
P:\20164866\00_M
WS
B_R
ussell_W
TP
\W
orking_D
wgs\400_P
rocess_M
ech\03 R
oss-B
ins-B
S\01-B
insW
TP
\4866-01-d-003.dw
g
DA
TE
: 2017-06-26
, D
esiree P
astorin
DRAWING REVISION
DESCRIPTIONDRAWNDESIGNDATEREV
SHEET
IF
N
OT
5
0 m
m A
DJU
ST
S
CA
LE
S
SC
AL
E(S
) S
HO
WN
A
RE
IN
TE
ND
ED
F
OR
A
NS
I D
(2
2X
34
) S
IZ
E D
RA
WIN
GS
, T
AB
LO
ID
(1
1X
17
) S
IZ
E D
RA
WIN
GS
A
RE
1
/2
O
F S
CA
LE
(S
) S
HO
WN
U
NL
ES
S N
OT
ED
O
TH
ER
WIS
E
SCALE:
50
m
m
www.ae.ca
203 - Five Donald Street, Winnipeg, Manitoba, R3L 2T4
Ph: 204 942 6391 Fax: 204 942 6399
ORIGINAL SEALED BY:
K. ANDERSON, P.ENG.
DATED: JUNE 26, 2017
RUSSELL BINSCARTH
REGIONAL WATER SYSTEM
BINSCARTH & ROSSBURN
RESERVOIR UPGRADES &
NEW BOOSTER STN ON ROAD 117N
M.W.S.B. # 1368 / AE # 20164866-03
AS SHOWN
PROCESS
BINSCARTH RESERVOIR
PROCESS & INSTRUMENTATION DIAGRAM
4866-01-D-003 0
5
26
0 2017JUN26 K. ANDERSON K. ANDERSON
ISSUED FOR TENDER &
CONSTRUCTION
± 2300
± 300
± 500
100Ø GATE VALVE &
SCH40 S.S. PIPE SPOOL
INTO WTP (BY OTHERS)
TO GAMBLER
150Ø GATE VALVE &
SCH40 S.S. PIPE SPOOL
INTO WTP (BY OTHERS)
FROM RUSSELL
8
13
3 444
5
9
6
7
7
1
1
1
12
10
1
1
22
FILTER
OPERATOR / LAB AREA
CHEMICAL ROOM
EL
EC
TR
IC
AL
DISTRIBUTION PUMPS
BACKWASH PUMP STANDBY PUMP
FILTER
11
1
14 15 16
17
EXISTING 150Ø
RESERVOIR FILL
EXISTING 150Ø RAW
WATER SUPPLY
EXISTING 150Ø
SUCTION LINE FROM
RESERVOIR
EXISTING 150Ø
DISTRIBUTION SUPPLY
EXISTING 75Ø SUCTION
LINE FROM RESERVOIR
P:\20164866\00_M
WS
B_R
ussell_W
TP
\W
orking_D
wgs\400_P
rocess_M
ech\03 R
oss-B
ins-B
S\01-B
insW
TP
\4866-01-d-101.dw
g
DA
TE
: 2017-06-26
, D
esiree P
astorin
DRAWING REVISION
DESCRIPTIONDRAWNDESIGNDATEREV
SHEET
IF
N
OT
5
0 m
m A
DJU
ST
S
CA
LE
S
SC
AL
E(S
) S
HO
WN
A
RE
IN
TE
ND
ED
F
OR
A
NS
I D
(2
2X
34
) S
IZ
E D
RA
WIN
GS
, T
AB
LO
ID
(1
1X
17
) S
IZ
E D
RA
WIN
GS
A
RE
1
/2
O
F S
CA
LE
(S
) S
HO
WN
U
NL
ES
S N
OT
ED
O
TH
ER
WIS
E
SCALE:
50
m
m
www.ae.ca
203 - Five Donald Street, Winnipeg, Manitoba, R3L 2T4
Ph: 204 942 6391 Fax: 204 942 6399
ORIGINAL SEALED BY:
K. ANDERSON, P.ENG.
DATED: JUNE 26, 2017
RUSSELL BINSCARTH
REGIONAL WATER SYSTEM
BINSCARTH & ROSSBURN
RESERVOIR UPGRADES &
NEW BOOSTER STN ON ROAD 117N
M.W.S.B. # 1368 / AE # 20164866-03
AS SHOWN
PROCESS
BINSCARTH RESERVOIR
EXISTING MAIN FLOOR & DEMOLITION PLAN
4866-01-D-101 0
6
26
0 2017JUN26 D. PASTORIN D. PASTORIN
ISSUED FOR TENDER &
CONSTRUCTION
PLAN
1
-
EXISTING MAIN FLOOR &
DEMOLITION
1:25
KEYNOTE LEGEND
TAG DESCRIPTION
1
REMOVE PIPING, VALVES & SUPPORTS. REPAIR
CONCRETE & FILL WALL PENETRATIONS AS
REQUIRED.
2
REMOVE DISTRIBUTION PUMPS & ASSOCIATED
CONCRETE HOUSEKEEPING PADS. REPAIR
CONCRETE AS REQUIRED.
3 REPLACE EXISTING GRATING W/ NEW.
4
REMOVE CHEMICAL FEED SYSTEM INCLUDING ALL
ASSOCIATED EQUIPMENT, FEED TUBING/CONDUITS &
STORAGE BARRELS. CONCRETE CONTAINMENT CURB
TO REMAIN.
5
RELOCATE EXISTING CHLORINE FEED SYSTEM TO
CHEMICAL ROOM.
6
INSTALL 150Ø PVC BLIND FLANGE @ SPOOL IN FLOOR
& ABANDON EXISTING RAW WATER SUPPLY.
7
REMOVE FILTERS. CONCRETE HOUSEKEEPING PAD
TO REMAIN.
8
CONNECTION TO EXISTING 75Ø PVC RESERVOIR
SUPPLY PIPING AS SHOWN ON DWG 4866-01-D-102.
9
CONNECTION TO EXISTING 50Ø PVC OVERHEAD
TRUCK FILL HEADER AS SHOWN ON 4866-01-D-102.
10
REMOVE STANDBY PUMP & ASSOCIATED
VENTILATION. EXISTING CONCRETE HOUSEKEEPING
PAD & CONTAINMENT CURB MAY BE INCORPORATED
INTO PAD FOR NEW DISTRIBUTION PUMP SKID.
11
CONNECTION TO EXISTING 75Ø PVC RESERVOIR
SUCTION PIPING AS SHOWN ON DWG 4866-01-D-102.
12
CONNECTION TO EXISTING 150Ø PVC DISTRIBUTION
SUPPLY PIPING AS SHOWN ON DWG 4866-01-D-102.
13
CONNECTION TO EXISTING 150Ø PVC RESERVOIR
SUCTION PIPING AS SHOWN ON DWG 4866-01-D-102.
14 EMERGENCY EYEWASH STATION TO REMAIN.
15 HOT WATER TANK & ASSOCIATED PIPING TO REMAIN.
16 EMERGENCY EYEWASH/SHOWER TO REMAIN.
17 REMOVE ELECTRICAL/CONTROL PANELS
NOTES:
1. FOR CLARITY, NOT ALL PIPING AND EQUIPMENT SHOWN.
CONTRACTOR SHALL VISIT SITE TO FAMILIARIZE
THEMSELVES WITH THE FACILITY AND SCOPE OF WORK
PRIOR TO SUBMITTING A BID.
2. OWNER SHALL HAVE FIRST RIGHT OF REFUSAL FOR ALL
OBSOLETE EQUIPMENT AND MATERIALS. THE REMAINING
SHALL BE REMOVED AND DISPOSED OF BY THE
CONTRACTOR.
3
D-301
4
D-301
± 1550
± 500
± 2650
± 200
100Ø SCH80 PVC
RESERVOIR BYPASS
(RUSSELL TO BINSCARTH
DISTRIBUTION)
100Ø SCH80 PVC
RESERVOIR SUPPLY HEADER
(FROM RUSSELL)
75Ø SCH10 S.S.
GAMBLER SUPPLY HEADER
(FROM RUSSELL)
± 600
25Ø SCH80 PVC AIR RELEASE
DRAIN PIPING TO SUMP, TYP
FROM ALL AIR/VAC VALVES
EXISTING 150Ø SCH80 PVC
RAW WATER SUPPLY
BLIND FLANGED @ SPOOL
THROUGH FLOOR & ABANDONED
100Ø SCH80 PVC
RESERVOIR BYPASS
(RUSSELL TO BINSCARTH
DISTRIBUTION)
HYDRO
PNEUMATIC
TANKS
75Ø SCH80 PVC
SUCTION HEADER
(FROM RESERVOIR)
100Ø SCH80 PVC
MAG METER HEADER
(TO BINSCARTH
DISTRIBUTION)
75Ø SCH80 PVC
GAMBLER SUPPLY HEADER
150Ø SCH80 PVC
BINSCARTH
DISTRIBUTION SUPPLY
50Ø SCH80 PVC
CONNECTION TO EXISTING
TRUCK FILL HEADER
PRE-PACKAGED PUMP SKID
32Ø PLANT WATER SUPPLY
TAP OFF SIDE OF NEW HEADER,
INSTALL BACKFLOW PREVENTER
& CONNECT TO EXISTING PLANT
SUPPLY PIPING
RELOCATED CHLORINE
FEED SYSTEM
REPLACE EXISTING
GRATING w/ NEW
STRONGWELL DURAGRID
HD 6000 45 BEARING BAR IN
MAX 1.0 m LONG SECTIONS
100Ø SCH80 PVC
RESERVOIR BYPASS
(RUSSELL TO BINSCARTH
DISTRIBUTION)
75Ø SCH10 S.S. SHORT
RADIUS ELBOWS (DUE TO
TIGHT SPACING)
1.0 m X 2.0 m CONCRETE
HOUSEKEEPING PAD,
HEIGHT TO SUIT SUCTION
PIPING TIE-IN ELEVATION
(± 400 mm)
EXISTING
EMERGENCY
EYEWASH
EXISTING
HOT WATER
TANK
EXISTING EMERGENCY
EYEWASH & SHOWER
REPLACE EXISTING TRUCKFILL
PANEL & OPERATOR BOX w/ NEW
SMART CARD FIELD TERMINAL
1
D-301
RELOCATED 50Ø TRUCKFILL
BACKFLOW PREVENTER
(UPSTREAM OF MAG METER &
FLOW CONTROL VALVE)
75Ø SCH80 PVC
PRV PIPING DISCHARGE
TO SUMP
P:\20164866\00_M
WS
B_R
ussell_W
TP
\W
orking_D
wgs\400_P
rocess_M
ech\03 R
oss-B
ins-B
S\01-B
insW
TP
\4866-01-d-102.dw
g
DA
TE
: 2017-06-26
, D
esiree P
astorin
DRAWING REVISION
DESCRIPTIONDRAWNDESIGNDATEREV
SHEET
IF
N
OT
5
0 m
m A
DJU
ST
S
CA
LE
S
SC
AL
E(S
) S
HO
WN
A
RE
IN
TE
ND
ED
F
OR
A
NS
I D
(2
2X
34
) S
IZ
E D
RA
WIN
GS
, T
AB
LO
ID
(1
1X
17
) S
IZ
E D
RA
WIN
GS
A
RE
1
/2
O
F S
CA
LE
(S
) S
HO
WN
U
NL
ES
S N
OT
ED
O
TH
ER
WIS
E
SCALE:
50
m
m
www.ae.ca
203 - Five Donald Street, Winnipeg, Manitoba, R3L 2T4
Ph: 204 942 6391 Fax: 204 942 6399
ORIGINAL SEALED BY:
K. ANDERSON, P.ENG.
DATED: JUNE 26, 2017
RUSSELL BINSCARTH
REGIONAL WATER SYSTEM
BINSCARTH & ROSSBURN
RESERVOIR UPGRADES &
NEW BOOSTER STN ON ROAD 117N
M.W.S.B. # 1368 / AE # 20164866-03
AS SHOWN
PROCESS
BINSCARTH RESERVOIR
PROPOSED MAIN FLOOR PLAN
4866-01-D-102 0
7
26
0 2017JUN26 D. PASTORIN D. PASTORIN
ISSUED FOR TENDER &
CONSTRUCTION
PLAN
1
-
MAIN FLOOR
1:20
100Ø SCH80 PVC
RESERVOIR BYPASS
(RUSSELL TO
BINSCARTH
DISTRIBUTION)
CHLORINE INJECTION POINT IN
REMOVABLE PVC SPOOL
FLANGED CONNECTION TO
EXISTING 150Ø SCH40 S.S.
SUPPLY FROM RUSSELL WTP
w/ 150Ø VALVE
150Ø SCH10 S.S. PIPING
75Ø SCH10 S.S.
GAMBLER SUPPLY HEADER
(DIRECT FROM RUSSELL)
FLANGED CONNECTION TO
EXISTING 100Ø SCH40 S.S. SUPPLY
TO GAMBLER w/ 100Ø VALVE
75Ø SCH80 PVC
GAMBLER SUPPLY HEADER
(DIRECT FROM RUSSELL)
EXISTING FILTERS SHOWN FOR
ALIGNMENT PURPOSES ONLY.
FILTERS & ASSOCIATED PIPING TO BE
REMOVED FOLLOWING ESTABLISHMENT
OF NEW WATER SUPPLY FROM RUSSELL.
100Ø FLOW
CONTROL VALVE
100Ø MAG METER
100Ø MAG METER
100Ø FLOW
CONTROL VALVE
AIR/VACUUM VALVE
c/w DRAIN PIPING TO
EXISTING SUMP & UNIONS
FOR DISASSEMBLY, TYP
100Ø SCH80 PVC
RESERVOIR SUPPLY
(FROM RUSSELL)
CHLORINE INJECTION IN
REMOVABLE PVC SPOOL
EXISTING 150Ø PVC PIPE
SPOOL THROUGH FLOOR
EXISTING 75Ø PVC
RESERVOIR FILL PIPING
1.0 m X 2.0 m CONCRETE
HOUSEKEEPING PAD,
HEIGHT TO SUIT SUCTION
LINE TIE-IN ELEVATION
(± 400 mm)
TIE INTO EXISTING 50Ø PVC
TRUCK FILL HEADER
± 500
± 500
TIE INTO EXISTING 75Ø
SUCTION PIPE SPOOL
w/ 75Ø VALVE
TIE INTO EXISTING 150Ø
DISTRIBUTION SUPPLY PIPE
SPOOL w/ 150Ø VALVE
100Ø SCH80 PVC
MAG METER HEADER
150Ø SCH80 PVC
BINSCARTH
DISTRIBUTION
SUPPLY
32Ø PLANT WATER SUPPLY
TAP OFF NEW HEADER, INSTALL
BACKFLOW PREVENTER & TIE INTO
EXISTING PLANT SUPPLY PIPING
AIR/VACUUM VALVE
c/w DRAIN PIPING TO
EXISTING SUMP, TYP
100Ø SCH80 PVC
RESERVOIR BYPASS
(RUSSELL TO BINSCARTH DISTRIBUTION)
50Ø SCH80 PVC
TRUCK FILL SUPPLY
75Ø SCH80 PVC
RESERVOIR SUCTION
TIE INTO EXISTING 150Ø
SUCTION PIPE SPOOL
w/ 150Ø VALVE
150Ø SCH80 PVC
PUMP SUCTION
± 400
RELOCATED BACKFLOW
PREVENTER
75Ø SCH80 PVC
PRESSURE RELIEF
HEADER
75Ø SCH80 PVC
PRV DISCHARGE
PIPED TO SUMP
NOTE:
HYDRO PRESSURE TANKS
NOT SHOWN FOR CLARITY.
PRE-PACKAGED PUMP SKID
CONNECT TO EXISTING 75Ø
PVC PIPING w/ NEW TEE
(UPON COMPLETION OF ALL
PIPING/PUMPING UPGRADES,
EXISTING LEAD TO BE
PLUGGED)
EXISTING FILTERS SHOWN FOR
ALIGNMENT PURPOSES ONLY.
FILTERS & ASSOCIATED PIPING
TO BE REMOVED FOLLOWING
ESTABLISHMENT OF NEW
WATER SUPPLY FROM RUSSELL.
± 800
400
500
300
FLANGED CONNECTION TO
EXISTING 150Ø SCH40 S.S.
SUPPLY FROM RUSSELL WTP
w/ 150Ø CHECK VALVE &
BUTTERFLY VALVE
AIR/VACUUM VALVE
c/w DRAIN PIPING TO
EXISTING SUMP & UNIONS
FOR DISASSEMBLY, TYP
100Ø SCH80 PVC
RESERVOIR BYPASS
(RUSSELL TO BINSCARTH
DISTRIBUTION)
± 1200
EXISTING FILTER PIPING
NOTE:
NOT ALL EXISTING FILTER
PIPING & EQUIPMENT SHOWN.
EXISTING 150Ø PVC
RESERVOIR FILL PIPE
SPOOL THROUGH FLOOR
150Ø SCH10 S.S. PIPING
75Ø SCH10 S.S.
GAMBLER SUPPLY HEADER
(DIRECT FROM RUSSELL)
100Ø SCH80 PVC
RESERVOIR SUPPLY
(FROM RUSSELL)
CHLORINE INJECTION IN
REMOVABLE PVC SPOOL
100Ø SCH80 PVC
RESERVOIR BYPASS
(RUSSELL TO BINSCARTH
DISTRIBUTION)
P:\20164866\00_M
WS
B_R
ussell_W
TP
\W
orking_D
wgs\400_P
rocess_M
ech\03 R
oss-B
ins-B
S\01-B
insW
TP
\4866-01-d-301.dw
g
DA
TE
: 2017-06-26
, D
esiree P
astorin
DRAWING REVISION
DESCRIPTIONDRAWNDESIGNDATEREV
SHEET
IF
N
OT
5
0 m
m A
DJU
ST
S
CA
LE
S
SC
AL
E(S
) S
HO
WN
A
RE
IN
TE
ND
ED
F
OR
A
NS
I D
(2
2X
34
) S
IZ
E D
RA
WIN
GS
, T
AB
LO
ID
(1
1X
17
) S
IZ
E D
RA
WIN
GS
A
RE
1
/2
O
F S
CA
LE
(S
) S
HO
WN
U
NL
ES
S N
OT
ED
O
TH
ER
WIS
E
SCALE:
50
m
m
www.ae.ca
203 - Five Donald Street, Winnipeg, Manitoba, R3L 2T4
Ph: 204 942 6391 Fax: 204 942 6399
ORIGINAL SEALED BY:
K. ANDERSON, P.ENG.
DATED: JUNE 26, 2017
RUSSELL BINSCARTH
REGIONAL WATER SYSTEM
BINSCARTH & ROSSBURN
RESERVOIR UPGRADES &
NEW BOOSTER STN ON ROAD 117N
M.W.S.B. # 1368 / AE # 20164866-03
AS SHOWN
PROCESS
BINSCARTH RESERVOIR
SECTIONS & ISOMETRIC VIEW
4866-01-D-301 0
8
26
0 2017JUN26 D. PASTORIN D. PASTORIN
ISSUED FOR TENDER &
CONSTRUCTION
VIEW
2
-
3D ISOMETRIC
NTSSECTION
1
D-102
DISTRIBUTION HEADER
1:20
SECTION
3
D-102
SUPPLY HEADERS
1:20
NOTES:
1. 3D VIEWS ARE PROVIDED FOR
ILLUSTRATION PURPOSES ONLY.
2. NOT ALL PIPING, EQUIPMENT
AND SUPPORTS ARE SHOWN OR
LABELED.
3. REFER TO PROCESS AND
INSTRUMENTATION DIAGRAMS,
PROCESS DRAWINGS AND
SPECIFICATIONS FOR REQUIRED
PIPE CONNECTIONS, MATERIALS
AND SIZES.
SECTION
4
D-102
SUPPLY HEADER
1:20
EXISTING MAIN BREAKER
SEE NOTE 6
M
M
DP-1
M
DP-2
M
TP-1
M
CF-1
CB-1
A17
A1
A
A1
A
A1
A
A1
A
A1
A
A1
A
A1
A
A1
A
A1,A3,A12
C
A12
A4 A4
A4
UH
UH
UH
A7 A7 A7
A7
A7 A8 A5
A19
A3
A12
A16
A8
A8A8
A19
A6
A8
EXISTING HYDRO METER
EXISTING SERVICE ENTRANCE
A9
A9
A11,13,15
M
CP-3
M
CP-2
M
CP-1
M
M-1
A18
M
M-1
A18
EF-1
A20
M
HW-1
SOV
TRUCK FILL PANEL
& COIN OP BOX
A2
A19
EXISTING ELECTRICAL
PANELS TO BE REPLACED
M
CP-4
A16A16
A16
A16
HATCHED PIPING &
EQUIPMENT TO BE REMOVED
FILTER
OPERATOR / LAB AREA
CHEMICAL ROOM
EL
EC
TR
IC
AL
DISTRIBUTION PUMPS
BACKWASH PUMP STANDBY PUMP
FILTER
P:\20164866\00_M
WS
B_R
ussell_W
TP
\W
orking_D
wgs\400_P
rocess_M
ech\03 R
oss-B
ins-B
S\01-B
insW
TP
\4866-01-e-101.dw
g
DA
TE
: 2017-06-28
, D
esiree P
astorin
DRAWING REVISION
DESCRIPTIONDRAWNDESIGNDATEREV
SHEET
IF
N
OT
5
0 m
m A
DJU
ST
S
CA
LE
S
SC
AL
E(S
) S
HO
WN
A
RE
IN
TE
ND
ED
F
OR
A
NS
I D
(2
2X
34
) S
IZ
E D
RA
WIN
GS
, T
AB
LO
ID
(1
1X
17
) S
IZ
E D
RA
WIN
GS
A
RE
1
/2
O
F S
CA
LE
(S
) S
HO
WN
U
NL
ES
S N
OT
ED
O
TH
ER
WIS
E
SCALE:
50
m
m
www.ae.ca
203 - Five Donald Street, Winnipeg, Manitoba, R3L 2T4
Ph: 204 942 6391 Fax: 204 942 6399
ORIGINAL SEALED BY:
S. FRIEL, P.ENG.
DATED: JUNE 26, 2017
RUSSELL BINSCARTH
REGIONAL WATER SYSTEM
BINSCARTH & ROSSBURN
RESERVOIR UPGRADES &
NEW BOOSTER STN ON ROAD 117N
M.W.S.B. # 1368 / AE # 20164866-03
AS SHOWN
ELECTRICAL
BINSCARTH RESERVOIR
EXISTING MAIN FLOOR & DEMOLITION PLAN
4866-01-E-101 0
9
26
0 2017JUN26 K. ANDERSON T. DYCHKO
ISSUED FOR TENDER &
CONSTRUCTION
PLAN
1
-
EXISTING MAIN FLOOR &
DEMOLITION
1:20
NOTES:
1. FOR CLARITY, NOT ALL EQUIPMENT SHOWN AND
LOCATIONS THAT ARE SHOWN, ARE APPROXIMATE.
CONTRACTOR SHALL VISIT SITE TO FAMILIARIZE
THEMSELVES WITH THE FACILITY AND SCOPE OF WORK
PRIOR TO SUBMITTING A BID.
2. OWNER SHALL HAVE FIRST RIGHT OF REFUSAL FOR ALL
OBSOLETE EQUIPMENT AND MATERIALS. THE REMAINING
SHALL BE REMOVED AND DISPOSED OF BY THE
CONTRACTOR.
3. REMOVE, RELOCATE, REWIRE AND RECONNECT EXISTING
ELECTRICAL TO ALLOW FOR UPGRADES, FILTER
REMOVAL.
4. MINIMIZE SHUTDOWNS OF EXISTING EQUIPMENT AND
SYSTEMS. MAINTAIN OPERATION OF THE WATER
TREATMENT SYSTEM AND DISTRIBUTION PROCESS TO
THE EXTENT THAT IS PRACTICABLE. INTERRUPTIONS
MUST BE COORDINATED AND APPROVED BY THE OWNER
AND ENGINEER. PROVIDE MINIMUM TWO WEEKS' NOTICE.
5. REMOVE OBSOLETE EQUIPMENT. THE OWNER SHALL
HAVE FIRST RIGHT OF REFUSAL FOR ALL OBSOLETE
EQUIPMENT AND MATERIALS. THE REMAINING SHALL BE
REMOVED AND DISPOSED OF BY THE CONTRACTOR.
6. REPLACE MAIN SERVICE DISCONNECT WITH NEW.
NEW MAIN BREAKER
M
CB-1
A17
A1
A
A1
A
A1
A
A1
A
A1
A
A1
A
A1
A
A1
A
A1,A3,A12
C
A4 A4
A4
UH
UH
UH
A7 A7 A7
A7
A7 A8 A5
A19
A3
A12
A16
A8
A8A8
A19
A6
A8
EXISTING HYDRO METER
EXISTING SERVICE ENTRANCE
A9
A9
A11,13,15
M
CDP-8001
M
CDP-1001
EF-1
A20
M
HW-1
SOV
TRUCK FILL PANEL
& COIN OP BOX
A2
A19
A16A16
A16
A16
OPERATOR / LAB AREA
CHEMICAL ROOM
PRE-PACKAGED PUMP SKID
M
DP-101
M
DP-102
M
DP-103
FIT
602
SOV
SOV
FIT
101
FIT
802
M
CDP-SPARE
SCADA PANEL
NEW MAIN
CONTROL PANEL
NEW MILLTRONICS
NEW ELECTRICAL
PANEL
NEW CHLORINE
ANALYZER PANEL
w/ S.S STAND
PIT
602
PIT
613
TWO CONTROL VALVES,
ONE DRAIN VALVE
PIT
623
PIT
633
AIT
101AIT
601
FIT
702
PIT
160
SV
188
PIT
860
SV
-
NEW AUTOMATIC
TRANSFER SWITCH
PUMP SKID
CONTROL PANEL
REPLACE ALL INTERIOR
LIGHTS w/ NEW LED FIXTURES
P:\20164866\00_M
WS
B_R
ussell_W
TP
\W
orking_D
wgs\400_P
rocess_M
ech\03 R
oss-B
ins-B
S\01-B
insW
TP
\4866-01-e-102.dw
g
DA
TE
: 2017-06-28
, D
esiree P
astorin
DRAWING REVISION
DESCRIPTIONDRAWNDESIGNDATEREV
SHEET
IF
N
OT
5
0 m
m A
DJU
ST
S
CA
LE
S
SC
AL
E(S
) S
HO
WN
A
RE
IN
TE
ND
ED
F
OR
A
NS
I D
(2
2X
34
) S
IZ
E D
RA
WIN
GS
, T
AB
LO
ID
(1
1X
17
) S
IZ
E D
RA
WIN
GS
A
RE
1
/2
O
F S
CA
LE
(S
) S
HO
WN
U
NL
ES
S N
OT
ED
O
TH
ER
WIS
E
SCALE:
50
m
m
www.ae.ca
203 - Five Donald Street, Winnipeg, Manitoba, R3L 2T4
Ph: 204 942 6391 Fax: 204 942 6399
ORIGINAL SEALED BY:
S. FRIEL, P.ENG.
DATED: JUNE 26, 2017
RUSSELL BINSCARTH
REGIONAL WATER SYSTEM
BINSCARTH & ROSSBURN
RESERVOIR UPGRADES &
NEW BOOSTER STN ON ROAD 117N
M.W.S.B. # 1368 / AE # 20164866-03
AS SHOWN
ELECTRICAL
BINSCARTH RESERVOIR
PROPOSED MAIN FLOOR PLAN
4866-01-E-102 0
10
26
0 2017JUN26 K. ANDERSON T. DYCHKO
ISSUED FOR TENDER &
CONSTRUCTION
PLAN
1
-
PROPOSED MAIN FLOOR
1:25
NOTES:
1. FOR CLARITY, NOT ALL EQUIPMENT SHOWN AND
LOCATIONS THAT ARE SHOWN, ARE APPROXIMATE.
CONTRACTOR SHALL VISIT SITE TO FAMILIARIZE
THEMSELVES WITH THE FACILITY AND SCOPE OF WORK
PRIOR TO SUBMITTING A BID.
2. REMOVE OBSOLETE EQUIPMENT. OWNER SHALL HAVE
FIRST RIGHT OF REFUSAL FOR ALL OBSOLETE
EQUIPMENT AND MATERIALS. THE REMAINING SHALL BE
REMOVED AND DISPOSED OF BY THE CONTRACTOR.
3. REMOVE, RELOCATE, REWIRE AND RECONNECT EXISTING
ELECTRICAL TO ALLOW FOR UPGRADES AND FILTER
REMOVAL.
4. REPLACE ALL EXISTING INTERIOR OVERHEAD LIGHT
FIXTURES WITH NEW LED UNITS.
LIGHTING FIXTURE SCHEDULE
FIXTURE
TAG
No.
EQUIPMENT INFORMATION
REMARKS
DESCRIPTION MANUFACTURER & CATALOGUE No.
MOUNTING
TYPE
MOUNTING
HEIGHT
VOLTS
FIXTURE
SIZE
WATTS
LAMPS
No. TYPE K-VALUE
A, CVAPOUR TIGHT CHAIN MOUNT
METALUX:
4VT2-LD4-4-DR-UNV-L840-WL-U-VT2
CHAIN MOUNT 2500 AFF 120V 178X1265 138W 9 LED 5000 C/W STAINLES STEEL CHAINS
M
HYDRO METERING
120/208V, 3PH HYDRO
FEEDER
PANEL A, 3 PH, 4W,
120/208V 225A,
42 CCT PANEL c/w
100A MIN BREAKER
4-#1 RW90 IN CONDUIT
& GROUND
208V
125A
MAIN BREAKER
3P
GROUPED MOTOR
CONTROL CENTRE
CON: 31.00 kW
DEM: 15.35 kW
CON: 13.36 kW
DEM: 7.14 kW
4-#1 RW90 IN CONDUIT
& GROUND
CAP SPLITTER AT
CONDUIT EXIT TO MCC
208V 3 PHASE SPLITTER
(PROTECT AND REUSE)
M
NEW HYDRO
METERING
NEW 600//347V, 3PH
HYDRO FEEDER
NEW PANEL A, 3 PH,
4W, 120/208V 225A,
42 CCT PANEL c/w
100A MIN BREAKER
4-#1 RW90 IN CONDUIT
& GROUND
600V
100
AMP
NEW MAIN BREAKER
3P
CON: 13.36 kW
DEM: 7.14 kW
4-#1 RW90 IN CONDUIT
& GROUND
50AT
100AF
NEMA 12
3P
PUMP SKID
PACKAGE
PANEL 600 -
600V 3 PHASE PANEL
BOARD 42 CCT
22 KAIC
4-#1 RW90 IN 103 mm
CONDUIT & GROUND
600v, 3 POLE
100A MANUAL
TRANSFER SWITCH
3 POLE, SOLID
NEUTRAL
100A SPLITTER
3-#3/0 &
GROUND
15 KVA
600V:208V
3 PHASE
4 WIRE
XFMR-601
P:\20164866\00_M
WS
B_R
ussell_W
TP
\W
orking_D
wgs\400_P
rocess_M
ech\03 R
oss-B
ins-B
S\01-B
insW
TP
\4866-01-e-601.dw
g
DA
TE
: 2017-06-28
, D
esiree P
astorin
DRAWING REVISION
DESCRIPTIONDRAWNDESIGNDATEREV
SHEET
IF
N
OT
5
0 m
m A
DJU
ST
S
CA
LE
S
SC
AL
E(S
) S
HO
WN
A
RE
IN
TE
ND
ED
F
OR
A
NS
I D
(2
2X
34
) S
IZ
E D
RA
WIN
GS
, T
AB
LO
ID
(1
1X
17
) S
IZ
E D
RA
WIN
GS
A
RE
1
/2
O
F S
CA
LE
(S
) S
HO
WN
U
NL
ES
S N
OT
ED
O
TH
ER
WIS
E
SCALE:
50
m
m
www.ae.ca
203 - Five Donald Street, Winnipeg, Manitoba, R3L 2T4
Ph: 204 942 6391 Fax: 204 942 6399
ORIGINAL SEALED BY:
S. FRIEL, P.ENG.
DATED: JUNE 26, 2017
RUSSELL BINSCARTH
REGIONAL WATER SYSTEM
BINSCARTH & ROSSBURN
RESERVOIR UPGRADES &
NEW BOOSTER STN ON ROAD 117N
M.W.S.B. # 1368 / AE # 20164866-03
AS SHOWN
ELECTRICAL
BINSCARTH RESERVOIR
SINGLE LINE DIAGRAM
4866-01-E-601 0
11
26
0 2017JUN26 S. FRIEL T. DYCHKO
ISSUED FOR TENDER &
CONSTRUCTION
SCHEMATIC
1
-
SINGLE LINE DIAGRAM
EXISTING & DEMOLITION
NTS
LP 'A' 120/208 V 3PH 4W SN 225 A MAINS 100 A BREAKER
CONNECTED: 13.36 kW
DEMAND: 7.14 kW
FEEDER DESCRIPTION
PHASE
CCT
BREAKER
AMP
A B C
BREAKER
AMP
CCT
PHASE
DESCRIPTION FEEDER
A B C A B C
LIGHTING MAIN ROOM 1200 1 15 15 2 400 LIGHTING CHEM. FEED RM
LIGHTING DESK/LAB 100 3 15 15 4 450 EXTERIOR LIGHTING
BATTERY CHARGER 500 5 15 20 6 1500 HOT WATER HEATER HW-1
RECEPTACLES 1000 7 15 15 8 1000 RECEPTACLES
UNIT HEATERS UH-2 & UH-3 100 9 15 15 10 75 WALL EXHAUST FAN EF-1
UNIT HEATER UH-1
1650 11
20
15 12 200 CEILING FANS CF-1 & CF-2
1650 13 15 14 1200 CONTROL PANELS
1650 15 15 16 200 CHEM. FEED PUMPS
COIN BOX CB-1 100 17 15 15 18 375 MIXERS M-1 & M-2
OUTDOOR RECEPTACLES 600 19 15 15 20 NEW PLC CABINET
SI NEW CHEMICAL PUMP 2801 21 15 15 22 NEW AIT 2601 CL2
NEW CHEMICAL PUMP 2802 23 15 15 24 NEW AIT 2101 CL2
NEW PRE-PACKAGED PUMP
SKID
25
80
*CONFIRM W/
SUPPLIER
26 SPACE
27 28 SPACE
29 30 SPACE
SPACE 31 32 SPACE
SPACE 33 34 SPACE
SPACE 35 36 SPACE
SPACE 37 38 SPACE
SPACE 39 40 SPACE
SPACE 41 42 SPACE
NOTES:
1. ALL EXISTING BUILDING LOAD FEEDERS ARE #12 AWG RW90 IN CONDUIT.
2. REPLACE PANEL A WITH NEW 42 CCT 225 AMP 80% RATED WITH 125 AMPERE BREAKER
3. REPLACE MAIN SERVICE DISCONNECT 125 AMPERE BREAKER WITH NEW SERVICE RATED
600V 100 AMPERE BREAKER
4. PROTECT AND REUSE EXISTING WIRES AND CIRCUITS AND CONNECT TO NEW PANEL A
5. PROVIDE BACK UP POWER TO THE DISTRIBUTION PUMPS DURING THE CHANGING OF THE
SERVICE BREAKER. NO CONTINUE SERVICE OUTAGE WILL BE ALLOWED, ALL OUTAGES
MUST BE ACCEPTED BY THE OWNER A MINIMUM OF 2 WEEKS BEFORE THE PLANNED
OUTAGE.
6. DEMOLITION WILL INCLUDE REMOVAL OF UNUSED WIRE, CONDUIT, HANGERS, JUNCTION
BOXES ETC. CONTRACTOR TO REPAIR WALLS AND PENETRATIONS AND PAINT TO MATCH
EXISTING.
SCHEMATIC
2
-
SINGLE LINE DIAGRAM
PROPOSED
NTS
S
S
S
S
S
S
PR
264
OA
K S
T
PR
2
64
RETAINING WALL
RETAINING WALL
150Ø HDPE DR17
WATER SUPPLY PIPELINE
(FROM RUSSELL)
EXISTING RAW
WATER WELLS &
ISOLATION VALVES
EXISTING WATER
TREATMENT PLANT
& RESERVOIR
PROPERTY LIMIT
DISTRIBUTION SUPPLY
W
W
W
W
W
W
W
W
W
FO
W
UT
UT
UT
UT
UT
UT
UT
UT
UT
UT
UT
UT
UT
UT
UT
UT
UT
UT
UT
S
W
W
OP
OP
OP
X
X
X
X
X
X
X
X
X
X
X
X
X
XX
XX
X
X
X
OP
OP
OP
OP
OP
OP
OP
OP
O
P
O
P
PR
2
64
RETAINING WALL
RETAINING WALL
150Ø HDPE DR17
WATER SUPPLY PIPELINE
(FROM RUSSELL)
EXISTING RAW
WATER WELLS &
ISOLATION VALVES
EXISTING WATER
TREATMENT PLANT
& RESERVOIR
PROPERTY LIMIT
DISTRIBUTION SUPPLY
P:\20164866\00_M
WS
B_R
ussell_W
TP
\W
orking_D
wgs\400_P
rocess_M
ech\03 R
oss-B
ins-B
S\02-R
ossW
TP
\4866-02-c-101.dw
g
DA
TE
: 2017-06-26
, D
esiree P
astorin
DRAWING REVISION
DESCRIPTIONDRAWNDESIGNDATEREV
SHEET
IF
N
OT
5
0 m
m A
DJU
ST
S
CA
LE
S
SC
AL
E(S
) S
HO
WN
A
RE
IN
TE
ND
ED
F
OR
A
NS
I D
(2
2X
34
) S
IZ
E D
RA
WIN
GS
, T
AB
LO
ID
(1
1X
17
) S
IZ
E D
RA
WIN
GS
A
RE
1
/2
O
F S
CA
LE
(S
) S
HO
WN
U
NL
ES
S N
OT
ED
O
TH
ER
WIS
E
SCALE:
50
m
m
www.ae.ca
203 - Five Donald Street, Winnipeg, Manitoba, R3L 2T4
Ph: 204 942 6391 Fax: 204 942 6399
ORIGINAL SEALED BY:
K. ANDERSON, P.ENG.
DATED: JUNE 26, 2017
RUSSELL BINSCARTH
REGIONAL WATER SYSTEM
BINSCARTH & ROSSBURN
RESERVOIR UPGRADES &
NEW BOOSTER STN ON ROAD 117N
M.W.S.B. # 1368 / AE # 20164866-03
AS SHOWN
CIVIL
ROSSBURN RESERVOIR
EXISTING SITE PLAN
4866-02-C-101 0
12
26
0 2017JUN26 K. ANDERSON T. DYCHKO
ISSUED FOR TENDER &
CONSTRUCTION
WORK AREA
PLAN
1
-
KEY
1:5000
PLAN
2
-
EXISTING SITE
1:200
WATER WELL
FENCE
RAILWAY
LINETYPES
SANITARY SEWER
BOLLARD
BUSH
SYMBOLS
GAS
UNDERGROUND POWER
OVERHEAD POWER
UNDERGROUND TELEPHONE
FIBRE OPTIC CABLE
WATER MAIN
MANHOLE
METER
FIRE HYDRANT
GATE VALVE
HYDRO / UTILITY POLE
GUY WIRE
TELEPHONE PEDESTAL
FLUSHOUT
LEGEND
EXISTING PROPOSED
EXISTING PROPOSED
NOTES:
1. ALL MATERIALS AND INSTALLATION PRACTICES SHALL
CONFORM TO M.W.S.B. STANDARD CONSTRUCTION
SPECIFICATIONS.
2. DECIMALIZED NUMBERS INDICATE METERS AND WHOLE
NUMBERS INDICATE MILLIMETERS.
3. LOCATION OF UNDERGROUND SERVICES AS SHOWN ARE
BASED ON THE BEST INFORMATION AVAILABLE, BUT NO
GUARANTEE IS GIVEN THAT ALL EXISTING SERVICES ARE
SHOWN OR THAT THE GIVEN LOCATIONS ARE EXACT.
4. CONTRACTOR MUST CONFIRM WITH THE INDIVIDUAL
UTILITIES FOR EXISTENCE AND EXACT LOCATIONS OF ALL
THE SERVICES PRIOR TO CONSTRUCTION.
5. ALL SITE LAYDOWN AREAS SHALL BE AS NOTED IN THE
SPECIFICATIONS AND APPROVED BY THE OWNER AND
ENGINEER.
VENT PIPE
. .
PW
REGIONAL SUPPLY
CAV-2123
BU
V-2
10
4
CAV-2121
BUV-2103
FE
2102
CHLORINE CHLORINE CHLORINE CHLORINE CHLORINE
CH
LO
RIN
EC
HLO
RIN
EC
HLO
RIN
E
M
M
BU
V-2
10
2
BA
V-2
12
2
BA
V-2
12
0
. .
PW
ROSSBURN DISTRIBUTION
AE
2101
CL(FREE)
AIT
2101
CL(FREE)
INCOMING
FREE CHLORINE
ANALYZER PANEL
NEV-9999
AE
2601
CL(FREE)
AIT
2601
CL(FREE)
OUTGOING
FREE CHLORINE
ANALYZER PANEL
NEV-9998
BAV-2900
LAH
2106
.
LALL
2102
.
FCV-2180
BAV-2150
BAV-2151
SV
2188
.
PI
2161
.
PIT
2160
.
PIT
2160
BU
V-2
10
5
INCOMING
PRESSURE
N.C.
VALVE
BUV-2107
RESERVOIR BY-PASS - DIRECT TO DISTRIBUTION
AI
2101
SV
2188
CONNECT TO EXISTING
RESERVOIR LEVEL
CONTROLS
OPEN/CLOSE
SOLENOID VALVE
FOR FCV-180
OPERATION
CD
P-2
80
1
CD
P-2
80
2
AI
2101A
XA
2101
ph
INDICATE
FREE CL2
INDICATE
ALARM
FAULT
FI
2102
FQI
2102
XA
2102
XA
2102A
XS
2102
FLOW
INDICATE
FLOW
TOTALIZER
ALARM
EMPTY PIPE
ALARM
FAULT
RESET
PRESSURE
INDICATION
XA
2802
XS
2802
ALARM
FAULT
RESET
XA
2801
XS
2801
ALARM
FAULT
RESET
150-PW-E1
CH
V-2
10
1
15
0-P
W-H
1
BB
V-2
16
0
BA
V-2
16
1
10
0-P
W-E
1
EXISTING RESERVOIR
10
0-P
W-H
1
100-PW-E1
10
0-P
W-E
1
BAV-2125
LSH
2105
.
LSL
2104
.
LAL
2103
.
BAV-2152
25-PW-E1
AI
2601
AI
2601A
XA
2601
ph
INDICATE
FREE CL2
INDICATE
ALARM
FAULT
LALL
2102
LEVEL SWITCH
PUMP LOCK OUT
LAL
2103
LEVEL SWITCH
LOW LEVEL ALARM
LSL
2104
LEVEL SWITCH
START FILLING (OPEN FCV-2180)
LSH
2105
LEVEL SWITCH
STOP FILLING (CLOSE FCV-2180)
LAH
2106
LEVEL SWITCH
HIGH LEVEL ALARM
CONNECT TO EXISTING
PUMP HEADER UPSTREAM
OF FLOW METER.
CONNECT WITH S.S. SADDLE
10
0-P
W-E
1
CONNECT INTO EXITING
150Ø FLANGE CONNECTION.
8-S
HS
-E
5
8-S
HS
-E
5
FV-2811 FV-2812
25-SHS-E5
HIGH PRESSURE TUBING
RUN INSIDE PVC CONDUIT
RE-CHLORINATION
N.C.
VALVE
VC
10
0-P
W-E
1
P:\20164866\00_M
WS
B_R
ussell_W
TP
\W
orking_D
wgs\400_P
rocess_M
ech\03 R
oss-B
ins-B
S\02-R
ossW
TP
\4866-02-d-001.dw
g
DA
TE
: 2017-06-26
, D
esiree P
astorin
DRAWING REVISION
DESCRIPTIONDRAWNDESIGNDATEREV
SHEET
IF
N
OT
5
0 m
m A
DJU
ST
S
CA
LE
S
SC
AL
E(S
) S
HO
WN
A
RE
IN
TE
ND
ED
F
OR
A
NS
I D
(2
2X
34
) S
IZ
E D
RA
WIN
GS
, T
AB
LO
ID
(1
1X
17
) S
IZ
E D
RA
WIN
GS
A
RE
1
/2
O
F S
CA
LE
(S
) S
HO
WN
U
NL
ES
S N
OT
ED
O
TH
ER
WIS
E
SCALE:
50
m
m
www.ae.ca
203 - Five Donald Street, Winnipeg, Manitoba, R3L 2T4
Ph: 204 942 6391 Fax: 204 942 6399
ORIGINAL SEALED BY:
K. ANDERSON, P.ENG.
DATED: JUNE 26, 2017
RUSSELL BINSCARTH
REGIONAL WATER SYSTEM
BINSCARTH & ROSSBURN
RESERVOIR UPGRADES &
NEW BOOSTER STN ON ROAD 117N
M.W.S.B. # 1368 / AE # 20164866-03
AS SHOWN
PROCESS
ROSSBURN RESERVOIR
PROCESS & INSTRUMENTATION DIAGRAM
4866-02-D-001 0
13
26
0 2017JUN26 K. ANDERSON K. ANDERSON
ISSUED FOR TENDER &
CONSTRUCTION
STANDBY
PUMP
EXISTING 150Ø SCH40 S.S.
FLANGED PIPE SPOOL THROUGH FLOOR
(SUPPLY FROM RUSSELL WTP)
PRESSURE TANK
RESERVOIR
DISTRIBUTION
PUMPS
BACKWASH
PUMP
SOFTENER
BRINE
TANK
GREENSAND
FILTER
FLUORIDE FEED SYSTEM
KmNO4 FEED SYSTEM
CHLORINE FEED SYSTEM
OFFICE / LAB / ELECTRICAL
± 450
EXISTING
ELECTRICAL
PANEL TO REMAIN
EXISTING
CONTROL PANEL
TO REMAIN
P:\20164866\00_M
WS
B_R
ussell_W
TP
\W
orking_D
wgs\400_P
rocess_M
ech\03 R
oss-B
ins-B
S\02-R
ossW
TP
\4866-02-d-101.dw
g
DA
TE
: 2017-06-26
, D
esiree P
astorin
DRAWING REVISION
DESCRIPTIONDRAWNDESIGNDATEREV
SHEET
IF
N
OT
5
0 m
m A
DJU
ST
S
CA
LE
S
SC
AL
E(S
) S
HO
WN
A
RE
IN
TE
ND
ED
F
OR
A
NS
I D
(2
2X
34
) S
IZ
E D
RA
WIN
GS
, T
AB
LO
ID
(1
1X
17
) S
IZ
E D
RA
WIN
GS
A
RE
1
/2
O
F S
CA
LE
(S
) S
HO
WN
U
NL
ES
S N
OT
ED
O
TH
ER
WIS
E
SCALE:
50
m
m
www.ae.ca
203 - Five Donald Street, Winnipeg, Manitoba, R3L 2T4
Ph: 204 942 6391 Fax: 204 942 6399
ORIGINAL SEALED BY:
K. ANDERSON, P.ENG.
DATED: JUNE 26, 2017
RUSSELL BINSCARTH
REGIONAL WATER SYSTEM
BINSCARTH & ROSSBURN
RESERVOIR UPGRADES &
NEW BOOSTER STN ON ROAD 117N
M.W.S.B. # 1368 / AE # 20164866-03
AS SHOWN
PROCESS
ROSSBURN RESERVOIR
EXISTING MAIN FLOOR PLAN
4866-02-D-101 0
14
26
0 2017JUN26 K. ANDERSON D. PASTORIN
ISSUED FOR TENDER &
CONSTRUCTION
PLAN
1
-
EXISTING MAIN FLOOR
1:25
NOTE:
1. FOR CLARITY, NOT ALL PIPING AND EQUIPMENT SHOWN.
CONTRACTOR SHALL VISIT SITE TO FAMILIARIZE
THEMSELVES WITH THE FACILITY AND SCOPE OF WORK
PRIOR TO SUBMITTING A BID.
± 2520 ± 750
4
D-301
1
D-301
3
D-301
100Ø SCH80 PVC
RESERVOIR SUPPLY
TIE INTO EXISTING 100Ø
PVC DISTRIBUTION HEADER
STANDBY
PUMP
PRESSURE TANK
RESERVOIR
DISTRIBUTION
PUMPS
BACKWASH
PUMP
SOFTENER
BRINE
TANK
GREENSAND
FILTER
CHLORINE
FEED SYSTEM
OFFICE / LAB / ELECTRICAL
EXISTING
ELECTRICAL PANEL
TO REMAIN
EXISTING
CONTROL PANEL
TO REMAIN
± 500
± 405
± 720
TIE INTO EXISTING 150Ø PVC
PVC SPOOL THROUGH FLOOR
(DISTRIBUTION SUPPLY)
150Ø SCH40 S.S. PIPE SPOOL
THROUGH FLOOR (BY OTHERS)
SUPPLY FROM RUSSELL
100Ø SCH80 PVC
RESERVOIR BYPASS (DIRECT
FEED FROM RUSSELL)
100Ø SCH80 PVC
RESERVOIR SUPPLY
(SUPPLY FROM RUSSELL)
CORE THROUGH EXISTING
RESERVOIR WALL & INSTALL
100Ø SCH40 S.S. PIPE SPOOL
c/w DOUBLE LINK SEAL
RESERVOIR SUPPLY
CHLORINE ANALYZER
DISTRIBUTION SUPPLY
CHLORINE ANALYZER
±535
NEW SCADA PANEL,
BY OTHERS
INSTALL DROP PIPE TO 300 mm
ABOVE RESERVOIR FLOOR &
EXTEND PIPING TO FAR END OF
RESERVOIR c/w SUPPORTS
(APPROX. LENGTH = 15.0 m)
SAMPLE LOCATION
FOR DISTRIBUTION
ANALYZER
P:\20164866\00_M
WS
B_R
ussell_W
TP
\W
orking_D
wgs\400_P
rocess_M
ech\03 R
oss-B
ins-B
S\02-R
ossW
TP
\4866-02-d-102.dw
g
DA
TE
: 2017-06-26
, D
esiree P
astorin
DRAWING REVISION
DESCRIPTIONDRAWNDESIGNDATEREV
SHEET
IF
N
OT
5
0 m
m A
DJU
ST
S
CA
LE
S
SC
AL
E(S
) S
HO
WN
A
RE
IN
TE
ND
ED
F
OR
A
NS
I D
(2
2X
34
) S
IZ
E D
RA
WIN
GS
, T
AB
LO
ID
(1
1X
17
) S
IZ
E D
RA
WIN
GS
A
RE
1
/2
O
F S
CA
LE
(S
) S
HO
WN
U
NL
ES
S N
OT
ED
O
TH
ER
WIS
E
SCALE:
50
m
m
www.ae.ca
203 - Five Donald Street, Winnipeg, Manitoba, R3L 2T4
Ph: 204 942 6391 Fax: 204 942 6399
ORIGINAL SEALED BY:
K. ANDERSON, P.ENG.
DATED: JUNE 26, 2017
RUSSELL BINSCARTH
REGIONAL WATER SYSTEM
BINSCARTH & ROSSBURN
RESERVOIR UPGRADES &
NEW BOOSTER STN ON ROAD 117N
M.W.S.B. # 1368 / AE # 20164866-03
AS SHOWN
PROCESS
ROSSBURN RESERVOIR
PROPOSED MAIN FLOOR PLAN
4866-02-D-102 0
15
26
0 2017JUN26 K. ANDERSON D. PASTORIN
ISSUED FOR TENDER &
CONSTRUCTION
PLAN
1
-
PROPOSED MAIN FLOOR
1:25
NOTE:
1. RESERVOIR LEVELS MAY BE LOWERED TO ALLOW CORE
THROUGH WALL. CONTRACTOR TO COORDINATE WITH
OWNER AND ENGINEER. MINIMUM ONE WEEK ADVANCE
NOTICE IS REQUIRED.
2. OBSOLETE EQUIPMENT AND PIPING TO REMAIN IN PLACE
FOR DEMOLITION AND SALVAGE BY THE OWNER.
± 1500
100Ø SCH80 PVC
RESERVOIR SUPPLY
EXISTING
PVC PIPING
± 900
± 1500
± 900
100Ø MAG METER
EXISTING PVC PIPING
CORE INTO EXISTING RESERVOIR
WALL & INSTALL NEW SCH40 S.S.
SPOOL c/w DBL LINKSEAL & GROUT.
COORDINATE SHUT DOWN w/
OWNER & ENGINEER.
100Ø SCH80 PVC
RESERVOIR BYPASS
(DIRECT TO DISTRIBUTION)
100Ø FLOW
CONTROL VALVE
AIR/VACUUM VALVE
c/w 25Ø PVC DRAIN PIPING
TO NEAREST FLOOR DRAIN,
TYP
100Ø SCH80 PVC
RESERVOIR SUPPLY
INSTALL DROP PIPE TO 300 mm ABOVE
RESERVOIR FLOOR & EXTEND PIPING TO
FAR END OF RESERVOIR c/w SUPPORTS
(APPROX. LENGTH = 15.0 m)
CHLORINE INJECTION
IN REMOVABLE PIPE
SPOOL
± 1500
± 900
EXISTING 150Ø
DISTRIBUTION SUPPLY
TIE INTO EXISTING 150Ø
CAST IRON TEE w/ NEW
100Ø BUTTERFLY VALVE
100Ø SCH80 PVC
RESERVOIR BYPASS
(DIRECT TO DISTRIBUTION)
± 455
± 300
CONNECT TO EXISTING 150Ø
SCH40 S.S. PIPE SPOOL
(SUPPLY FROM RUSSELL)
w/ NEW 150Ø CHECK VALVE
100Ø SCH80 PVC
RESERVOIR SUPPLY
100Ø MAG METER
AIR/VACUUM VALVE
c/w 25Ø PVC DRAIN
PIPING TO NEAREST
FLOOR DRAIN, TYP
100Ø BUTTERFLY
VALVE
EXISTING PVC PIPING
100Ø SCH80 PVC
RESERVOIR BYPASS
(DIRECT TO DISTRIBUTION)
P:\20164866\00_M
WS
B_R
ussell_W
TP
\W
orking_D
wgs\400_P
rocess_M
ech\03 R
oss-B
ins-B
S\02-R
ossW
TP
\4866-02-d-301.dw
g
DA
TE
: 2017-06-26
, D
esiree P
astorin
DRAWING REVISION
DESCRIPTIONDRAWNDESIGNDATEREV
SHEET
IF
N
OT
5
0 m
m A
DJU
ST
S
CA
LE
S
SC
AL
E(S
) S
HO
WN
A
RE
IN
TE
ND
ED
F
OR
A
NS
I D
(2
2X
34
) S
IZ
E D
RA
WIN
GS
, T
AB
LO
ID
(1
1X
17
) S
IZ
E D
RA
WIN
GS
A
RE
1
/2
O
F S
CA
LE
(S
) S
HO
WN
U
NL
ES
S N
OT
ED
O
TH
ER
WIS
E
SCALE:
50
m
m
www.ae.ca
203 - Five Donald Street, Winnipeg, Manitoba, R3L 2T4
Ph: 204 942 6391 Fax: 204 942 6399
ORIGINAL SEALED BY:
K. ANDERSON, P.ENG.
DATED: JUNE 26, 2017
RUSSELL BINSCARTH
REGIONAL WATER SYSTEM
BINSCARTH & ROSSBURN
RESERVOIR UPGRADES &
NEW BOOSTER STN ON ROAD 117N
M.W.S.B. # 1368 / AE # 20164866-03
AS SHOWN
PROCESS
ROSSBURN RESERVOIR
SECTIONS & ISOMETRIC VIEW
4866-02-D-301 0
16
26
0 2017JUN26 K. ANDERSON D. PASTORIN
ISSUED FOR TENDER &
CONSTRUCTION
VIEW
2
-
3D ISOMETRIC
NTS
SECTION
3
D-102
NEW PROCESS PIPING
1:20
SECTION
1
D-102
NEW PROCESS PIPING
1:20
NOTES:
1. 3D VIEWS ARE PROVIDED FOR ILLUSTRATION
PURPOSES ONLY.
2. NOT ALL PIPING, EQUIPMENT AND SUPPORTS ARE
SHOWN OR LABELED.
3. REFER TO PROCESS AND INSTRUMENTATION
DIAGRAMS, PROCESS DRAWINGS AND
SPECIFICATIONS FOR REQUIRED PIPE
CONNECTIONS, MATERIALS AND SIZES.
4. NEW PIPE SUPPORTS NOT SHOWN FOR CLARITY.
SECTION
4
D-102
NEW PROCESS PIPING
1:20
PIT
2160
FIT
2102
RESERVOIR SUPPLY
CHLORINE ANALYZER
DISTRIBUTION SUPPLY
CHLORINE ANALYZER
NEW SCADA PANEL,
BY OTHERS
AIT
2101
2601
AIT
AIT-2101 SAMPLE
LOCATION
AIT-2601 SAMPLE
LOCATION
2188
SV
EXISTING
ELECTRICAL PANEL
EXISTING
CONTROL PANEL
M
CDP-2801
M
CDP-2802
P:\20164866\00_M
WS
B_R
ussell_W
TP
\W
orking_D
wgs\400_P
rocess_M
ech\03 R
oss-B
ins-B
S\02-R
ossW
TP
\4866-02-e-101.dw
g
DA
TE
: 2017-06-26
, D
esiree P
astorin
DRAWING REVISION
DESCRIPTIONDRAWNDESIGNDATEREV
SHEET
IF
N
OT
5
0 m
m A
DJU
ST
S
CA
LE
S
SC
AL
E(S
) S
HO
WN
A
RE
IN
TE
ND
ED
F
OR
A
NS
I D
(2
2X
34
) S
IZ
E D
RA
WIN
GS
, T
AB
LO
ID
(1
1X
17
) S
IZ
E D
RA
WIN
GS
A
RE
1
/2
O
F S
CA
LE
(S
) S
HO
WN
U
NL
ES
S N
OT
ED
O
TH
ER
WIS
E
SCALE:
50
m
m
www.ae.ca
203 - Five Donald Street, Winnipeg, Manitoba, R3L 2T4
Ph: 204 942 6391 Fax: 204 942 6399
ORIGINAL SEALED BY:
S. FRIEL, P.ENG.
DATED: JUNE 26, 2017
RUSSELL BINSCARTH
REGIONAL WATER SYSTEM
BINSCARTH & ROSSBURN
RESERVOIR UPGRADES &
NEW BOOSTER STN ON ROAD 117N
M.W.S.B. # 1368 / AE # 20164866-03
AS SHOWN
ELECTRICAL
ROSSBURN RESERVOIR
MAIN FLOOR PLAN
4866-02-E-101 0
17
26
0 2017JUN26 K. ANDERSON T. DYCHKO
ISSUED FOR TENDER &
CONSTRUCTION
PLAN
1
-
MAIN FLOOR
1:25
UT
UT
UT
UT
UT
UT
UT
UT
UT
UT
UT
UT
UT
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
OP
OP
OP
OP
OP
OP
OP
OP
OP
OP
OP
OP
W
W
W
W
W
W
W
W
W
W
W
FO
X
XX
X
X
X
XX
X
ROAD 117 N
PROPERTY LIMIT
150Ø S.S. RISER PIPE INTO
PROPOSED BUILDING
(BY OTHERS), TYP OF 2
150Ø HDPE DR11 WATER
PIPELINE (BY OTHERS)
NEW
BOOSTER STATION
PROPERTY LIMIT
45.73 m
36.58 m
GRAVEL DRIVEWAY (90 m² APPROX):
- 150 mm A-BASE (100% SPD)
- 400 mm C-BASE (98% SPD) & FULL
DEPTH C-BASE IN EXCAVATED
AREA NON-WOVEN GEOTEXTILE
- 150 mm COMPACTED
UNDISTURBED SUB GRADE
NEW CHAINLINK SECURITY
FENCE c/w 4.0 m WIDE
DOUBLE GATE
12.0
12.0
2.4
0.45
4.0
NOTE:
REFER TO SPECIFICATIONS
FOR FENCE MATERIAL AND
CONSTRUCTION.
3 STRAND BARB WIRE
P:\20164866\00_M
WS
B_R
ussell_W
TP
\W
orking_D
wgs\400_P
rocess_M
ech\03 R
oss-B
ins-B
S\03-B
S\4866-03-c-101.dw
g
DA
TE
: 2017-06-26
, D
esiree P
astorin
DRAWING REVISION
DESCRIPTIONDRAWNDESIGNDATEREV
SHEET
IF
N
OT
5
0 m
m A
DJU
ST
S
CA
LE
S
SC
AL
E(S
) S
HO
WN
A
RE
IN
TE
ND
ED
F
OR
A
NS
I D
(2
2X
34
) S
IZ
E D
RA
WIN
GS
, T
AB
LO
ID
(1
1X
17
) S
IZ
E D
RA
WIN
GS
A
RE
1
/2
O
F S
CA
LE
(S
) S
HO
WN
U
NL
ES
S N
OT
ED
O
TH
ER
WIS
E
SCALE:
50
m
m
www.ae.ca
203 - Five Donald Street, Winnipeg, Manitoba, R3L 2T4
Ph: 204 942 6391 Fax: 204 942 6399
ORIGINAL SEALED BY:
K. ANDERSON, P.ENG.
DATED: JUNE 26, 2017
RUSSELL BINSCARTH
REGIONAL WATER SYSTEM
BINSCARTH & ROSSBURN
RESERVOIR UPGRADES &
NEW BOOSTER STN ON ROAD 117N
M.W.S.B. # 1368 / AE # 20164866-03
AS SHOWN
CIVIL
ROAD 117N BOOSTER STATION
SITE PLAN & DETAILS
4866-03-C-101 0
18
26
0 2017JUN26 K. ANDERSON T. DYCHKO
ISSUED FOR TENDER &
CONSTRUCTION
P
T
H
4
5
ROAD 117 N
WORK AREA
PLAN
1
-
KEY
1:10000
PLAN
2
-
SITE
1:200
P
T
H
4
5
FENCE
RAILWAY
LINETYPES
SANITARY SEWER
BOLLARD
BUSH
SYMBOLS
GAS
UNDERGROUND POWER
OVERHEAD POWER
UNDERGROUND TELEPHONE
FIBRE OPTIC CABLE
WATER MAIN
MANHOLE
METER
FIRE HYDRANT
GATE VALVE
HYDRO / UTILITY POLE
GUY WIRE
TELEPHONE PEDESTAL
FLUSHOUT
LEGEND
EXISTING PROPOSED
EXISTING PROPOSED
NOTES:
1. ALL MATERIALS AND INSTALLATION PRACTICES SHALL CONFORM
TO M.W.S.B. STANDARD CONSTRUCTION SPECIFICATIONS.
2. DECIMALIZED NUMBERS INDICATE METERS AND WHOLE NUMBERS
INDICATE MILLIMETERS.
3. LOCATION OF UNDERGROUND SERVICES AS SHOWN ARE BASED
ON THE BEST INFORMATION AVAILABLE, BUT NO GUARANTEE IS
GIVEN THAT ALL EXISTING SERVICES ARE SHOWN OR THAT THE
GIVEN LOCATIONS ARE EXACT.
4. CONTRACTOR MUST CONFIRM WITH THE INDIVIDUAL UTILITIES
FOR EXISTENCE AND EXACT LOCATIONS OF ALL THE SERVICES
PRIOR TO CONSTRUCTION.
5. ALL SITE LAYDOWN AREAS SHALL BE AS NOTED IN THE
SPECIFICATIONS AND APPROVED BY THE OWNER AND ENGINEER.
6. EXACT BUILDING LOCATION TO BE DETERMINED ONSITE WITH
OWNER AND ENGINEER.
7. REMOVE EXISTING FENCING AT PROPERTY LINE TO SUIT
CONSTRUCTION OF NEW SECURITY FENCE.
PLAN
3
-
SECURITY FENCE
NTS
1 2 3
A
B
C
OUTLINE OF SOFFIT
OVERHANG ABOVE
2
-
320
26751725
320
PROCESS AREA
10
1
DOOR℄
1
1
1
A-201
2
A-201
3
A-201
4
A-201
TYP
4400
320
4400
320
1
1
1000 mm x 1000 mm
REMOVABLE ATTIC
ACCESS PANEL,
w/ RIGID INSULATION
3
-
TYPICAL ROOF CONSTRUCTION
STANDING SEAM METAL ROOF
AIR INFILTRATION BARRIER
19 mm EXTERIOR GRADE PLYWOOD
PRE-ENGINEERED WOOD TRUSSES
R50 BATT INSULATION
6 MIL POLY VAPOUR BARRIER
19 mm PLYWOOD SHEATHING
FIBRE GLASS PANELING
4
1
PREFINISHED METAL FLASHING
EXTEND UP 300 mm MINIMUM
CONCRETE SPLASH PAD
CONTINUOUS SEALANT, TYP
320
16 mm Ø x 300 LONG, HOT DIP
GALVANIZED ANCHOR BOLT
@ 1200 O/C MAX
PROJECT R21.1 RIGID INSULATION
2000 mm MIN AROUND FOUNDATION
PERIMETER
T/O SLAB
EL 100.000
U/S CEILING
EL 102.550
CLOSURE SET IN SEALANT
PREFINISHED GUTTER
c/w GUTTER CLIPS @ 900 O/C MAX
38x140 TRIM BOARD
20x190 FASCIA BOARD
PREFINISHED FLASHING
OVER FASCIA BOARD
PREFINISHED CONTINUOUS
VENTED ALUMINUM SOFFIT
PREFINISHED METAL FLASHING
w/ DRIP EDGE
PREFINISHED METAL DOWNSPOUT
INSULATION STOP
MINIMUM 50 mm AIR SPACE
ENSURE CONTINUATION OF VAPOUR
BARRIER FROM WALL TO CEILING
R50 BATT INSULATION
18 GA. GALV. TRUSS TIE DOWN ANCHORS BOTH
ENDS EACH TRUSS
DOUBLE 38 x 140 TOP PLATE, TYP
PREFINISHED METAL SIDING
50 RIGID INSULATION
FASTENED w/ INSULOC SYSTEM
18 GA. GALVANIZED SKIRT
OVER R21.1 RIGID INSULATION
R21.1 RIGID SLAB INSULATION
12 mm PLYWOOD PROTECTION ON TOP
PRESSURE TREATED 38 x 140 BOTTOM PLATE
MID-HEIGHT BLOCKING BETWEEN STUDS
CONTINUOUS SNOW GUARD, TYP
6 988 6
1000
1028
20 20
2 LAYERS 19 mm PLYWOOD
FIBERGLASS PANEL
P:\20164866\00_M
WS
B_R
ussell_W
TP
\W
orking_D
wgs\400_P
rocess_M
ech\03 R
oss-B
ins-B
S\03-B
S\4866-03-a-101.dw
g
DA
TE
: 2017-06-26
, D
esiree P
astorin
DRAWING REVISION
DESCRIPTIONDRAWNDESIGNDATEREV
SHEET
IF
N
OT
5
0 m
m A
DJU
ST
S
CA
LE
S
SC
AL
E(S
) S
HO
WN
A
RE
IN
TE
ND
ED
F
OR
A
NS
I D
(2
2X
34
) S
IZ
E D
RA
WIN
GS
, T
AB
LO
ID
(1
1X
17
) S
IZ
E D
RA
WIN
GS
A
RE
1
/2
O
F S
CA
LE
(S
) S
HO
WN
U
NL
ES
S N
OT
ED
O
TH
ER
WIS
E
SCALE:
50
m
m
www.ae.ca
203 - Five Donald Street, Winnipeg, Manitoba, R3L 2T4
Ph: 204 942 6391 Fax: 204 942 6399
ORIGINAL SEALED BY:
J. BETKE, P.ENG.
DATED: JUNE 26, 2017
RUSSELL BINSCARTH
REGIONAL WATER SYSTEM
BINSCARTH & ROSSBURN
RESERVOIR UPGRADES &
NEW BOOSTER STN ON ROAD 117N
M.W.S.B. # 1368 / AE # 20164866-03
AS SHOWN
BUILDING
ROAD 117N BOOSTER STATION
MAIN FLOOR PLAN & SECTION
4866-03-A-101 0
19
26
0 2017JUN26 K. ANDERSON T. DYCHKO
ISSUED FOR TENDER &
CONSTRUCTION
PLAN
1
-
MAIN FLOOR
1:25
SECTION
2
-
TYPICAL WALL
NTS
SECTION
3
-
ATTIC ACCESS PANEL
1:10
1 2 3
4
1
3 2 1
A B C C B A
4
1
BOOSTER STATION
T/O SLAB
EL 100.000
U/S CEILING
EL 102.550
T/O SLAB
EL 100.000
U/S CEILING
EL 102.550
T/O SLAB
EL 100.000
U/S CEILING
EL 102.550
T/O SLAB
EL 100.000
U/S CEILING
EL 102.550
1 12
2 3 11311
99
115
7
10
4 4
1
2 3 11311
99
4 4
11
8
19
4
3 3
11 11 112
19
4
3 3
11 11 1111 2
6 6 6 6
6 6
13
MATERIALS LEGEND
1 PRE-FINISHED METAL ROOF CLADDING
COLOUR: TO BE CONFIRMED BY OWNER, FROM STANDARD COLOUR PALETTE
PRE-FINISHED METAL SIDING
COLOUR: TO BE CONFIRMED BY OWNER, FROM STANDARD COLOUR PALETTE
100 mm PRE-FINISHED METAL DOWNSPOUT
COLOUR: TO BE CONFIRMED BY OWNER, FROM STANDARD COLOUR PALETTE
PRE-FINISHED METAL ROOF GUTTER
COLOUR: TO BE CONFIRMED BY OWNER, FROM STANDARD COLOUR PALETTE
INSULATED METAL DOOR AND FRAME
COLOUR: TO BE CONFIRMED BY OWNER, FROM STANDARD COLOUR PALETTE
VENTILATION (SEE MECHANICAL)
OVERFLOW PIPE (SEE PROCESS)
PRESSURE RELIEF PIPE (SEE PROCESS)
CONTINUOUS SNOW GUARD
LIGHT FIXTURE (SEE ELECTRICAL)
PRE-CAST CONCRETE SPLASH PAD
SIGNAGE BY OWNER
PORTABLE GENERATOR RECEPTACLE
2
3
4
5
6
7
8
9
10
11
12
12
P:\20164866\00_M
WS
B_R
ussell_W
TP
\W
orking_D
wgs\400_P
rocess_M
ech\03 R
oss-B
ins-B
S\03-B
S\4866-03-a-201.dw
g
DA
TE
: 2017-06-26
, D
esiree P
astorin
DRAWING REVISION
DESCRIPTIONDRAWNDESIGNDATEREV
SHEET
IF
N
OT
5
0 m
m A
DJU
ST
S
CA
LE
S
SC
AL
E(S
) S
HO
WN
A
RE
IN
TE
ND
ED
F
OR
A
NS
I D
(2
2X
34
) S
IZ
E D
RA
WIN
GS
, T
AB
LO
ID
(1
1X
17
) S
IZ
E D
RA
WIN
GS
A
RE
1
/2
O
F S
CA
LE
(S
) S
HO
WN
U
NL
ES
S N
OT
ED
O
TH
ER
WIS
E
SCALE:
50
m
m
www.ae.ca
203 - Five Donald Street, Winnipeg, Manitoba, R3L 2T4
Ph: 204 942 6391 Fax: 204 942 6399
ORIGINAL SEALED BY:
J. BETKE, P.ENG.
DATED: JUNE 26, 2017
RUSSELL BINSCARTH
REGIONAL WATER SYSTEM
BINSCARTH & ROSSBURN
RESERVOIR UPGRADES &
NEW BOOSTER STN ON ROAD 117N
M.W.S.B. # 1368 / AE # 20164866-03
AS SHOWN
BUILDING
ROAD 117N BOOSTER STATION
ELEVATIONS
4866-03-A-201 0
20
26
0 2017JUN26 K. ANDERSON T. DYCHKO
ISSUED FOR TENDER &
CONSTRUCTION
ELEVATION
1
A-101
SOUTH
1:50 ELEVATION
2
A-101
NORTH
1:50
ELEVATION
3
A-101
WEST
1:50 ELEVATION
4
A-101
EAST
1:50
WALL TYPE
DOOR SCHEDULE
LOCATION DOORS FRAMES HARDWARE
TAG FROM TO SIZE TYPE FRR CORE MATERIAL FINISH TYPE FRR MATERIAL FINISH
FR
R
PA
NIC
KE
YE
D
LO
CK
SE
T
TH
RE
SH
D
CLO
SE
R
WE
AT
HE
R
ST
RIP
KIC
K
PLA
TE
101 PROCESS AREA EXTERIOR 915x2150x45 D1 - INSUL STEEL PT F1 - PS PT ● ● ● ● ● ●
DOOR TYPES FRAME TYPES NOTES:
1. ALL DOORS TO HAVE 2 PAIRS OF BUTT HINGES.
2. ALL HARDWARE TO BE MEDIUM DUTY, COMMERCIAL GRADE.
SEE SPECIFICATIONS.
3. ALL HARDWARE TO BE KEYED TO MASTER KEYING SYSTEM.
4. ALL CLOSERS TO HAVE 90° HOLD OPEN DEVICE.
5. ALL EXTERIOR DOORS TO HAVE STOP CHAINS.
ABBREVIATIONS:
INSUL = INSULATED
PS = PRESSED STEEL
PREF = PREFINISHED
MANUF = MANUFACTURER
FRR = FIRE RESISTANCE RATING
PT = PAINT
ROOM FINISH SCHEDULE
TAG ROOM
FLOOR WALL CEILING
MATERIAL FINISH MATERIAL FINISH HEIGHT MATERIAL FINISH
101 PROCESS AREA CONCRETE HPT1 WOOD SHEATHING FRP1 2550 WOOD SHEATHING FRP1
F1
DOOR FRAME
D1
EXTERIOR WALL
24 GA PREFINISHED METAL SIDING
TYVEK AIR BARRIER
19 mm EXTERIOR GRADE PLYWOOD
38x140 STUDS @ 400 mm O/C
140 (R20) BATT INSULATION
6 MIL POLY VAPOUR BARRIER
19 mm PLYWOOD
FIBER REINFORCED PLASTIC PANEL* FIBER REINFORCED PLASTIC PANEL
SYSTEMS TO BE WATER TIGHT.
INSTALL MID-HEIGHT BLOCKING BETWEEN
STUDS FOR CLADDING ANCHORING.
CODE REVIEW
PROJECT DESCRIPTION :
THE PROJECT CONSISTS OF A NEW ONE-STOREY BOOSTER STATION & SITE WORK
MUNICIPAL ADDRESS :
TBD, ROAD 117N, MANITOBA CANADA
LEGAL DESCRIPTION :
SW-22-20-25-W
LAND USE DESIGNATION:
INDUSTRIAL
MAXIMUM HEIGHT PERMITTED:
PERMITTED: N/A
ACTUAL: N/A
SITE AREA:
TBD
REFERENCE CODE:
MANITOBA BUILDING CODE 2016
MANITOBA FIRE CODE 2016
BUILDING CLASSIFICATION
MAJOR OCCUPANCY
CLASSIFICATION
GROUP F, DIVISION 3, UNOCCUPIED SERVICE BUILDING
SPRINKLER SYSTEM NOT REQUIRED
BUILDING FOOTPRINT
19.36 SQ M ( 208.4 SQ FT )
NUMBER OF STOREYS ONE
BUILDING AREAS
19.36 SQ M ( 208.4 SQ FT )
CONSTRUCTION TYPE
PERMITTED: COMBUSTIBLE OR NON-COMBUSTABLE
ACTUAL: COMBUSTIBLE
FLOOR ASSEMBLY NOT REQUIRED FOR UNOCCUPIED SERVICE BUILDING
LOAD BEARING WALLS
ASSEMBLY
NOT REQUIRED FOR UNOCCUPIED SERVICE BUILDING
ROOF ASSEMBLY NOT REQUIRED FOR UNOCCUPIED SERVICE BUILDING
FIRE ALARM SYSTEM NOT REQUIRED
OCCUPANT LOAD N/A
TRAVEL DISTANCE
8.0 M ( 26.2 FT )
BARRIER FREE REQUIREMENTS
DUE TO THE NATURE OF THE PROJECT, A RELAXATION WILL BE ASSUMED TO ALLOW
THE BUILDING TO BE WAVED FROM THE BARRIER-FREE ACCESS
1
MATERIALS SCHEDULE
COLOURED HARDENER
HPT1 (GENERAL)
FIBERGLASS REINFORCED PLASTIC
FRP1 (GENERAL)
MANUFACTURER:
TYPE:
COLOUR NAME:
TYPE:
COLOUR NAME:
SIKA
DIAMAG 7
NATURAL CONCRETE
GRAY
FLORSEAL WB 18
WATER CLEAR
MANUFACTURER:
CLASS:
COLOUR:
FINISH:
SEE SPEC
SEE SPEC
BRIGHT WHITE
PEBBLE, SEE SPEC FOR
INSTALLATION
INSTRUCTIONS
PT1 (TRIM & DOOR PAINT)
MANUFACTURER:
COLOUR NAME:
COLOUR NUMBER:
FINISH TYPE:
DULUX
OWNER SELECTED
OWNER SELECTED
SEMI-GLOSS
P:\20164866\00_M
WS
B_R
ussell_W
TP
\W
orking_D
wgs\400_P
rocess_M
ech\03 R
oss-B
ins-B
S\03-B
S\4866-03-a-601.dw
g
DA
TE
: 2017-06-26
, D
esiree P
astorin
DRAWING REVISION
DESCRIPTIONDRAWNDESIGNDATEREV
SHEET
IF
N
OT
5
0 m
m A
DJU
ST
S
CA
LE
S
SC
AL
E(S
) S
HO
WN
A
RE
IN
TE
ND
ED
F
OR
A
NS
I D
(2
2X
34
) S
IZ
E D
RA
WIN
GS
, T
AB
LO
ID
(1
1X
17
) S
IZ
E D
RA
WIN
GS
A
RE
1
/2
O
F S
CA
LE
(S
) S
HO
WN
U
NL
ES
S N
OT
ED
O
TH
ER
WIS
E
SCALE:
50
m
m
www.ae.ca
203 - Five Donald Street, Winnipeg, Manitoba, R3L 2T4
Ph: 204 942 6391 Fax: 204 942 6399
ORIGINAL SEALED BY:
J. BETKE, P.ENG.
DATED: JUNE 26, 2017
RUSSELL BINSCARTH
REGIONAL WATER SYSTEM
BINSCARTH & ROSSBURN
RESERVOIR UPGRADES &
NEW BOOSTER STN ON ROAD 117N
M.W.S.B. # 1368 / AE # 20164866-03
NTS
BUILDING
ROAD 117N BOOSTER STATION
SCHEDULES
4866-03-A-601 0
21
26
0 2017JUN26 K. ANDERSON T. DYCHKO
ISSUED FOR TENDER &
CONSTRUCTION
1 2 3
A
B
C
PROCESS AREA
200 4000 200
200
4000
200
1150 1150 R.O.
GC TO CONFIRM
2100
4400
4400
2200 2200
2200
2200
3
-
760
400 400
2
-
TYP
1455 350
400
300 mm THICK CONCRETE PAD
R/W 15M @ 300 O/C TOP & BOT
EACH WAY
1
SUB-GRADE COMPACTED TO
90% STD PROCTOR DENSITY (BY OWNER)
610600 mm THICK GRANULAR A-BASE
COMPACTED TO 98% STD
PROCTOR DENSITY (BY OWNER)
300 mm THICK SUB-BASE (C-BASE)
COMPACTED TO 98% STD
PROCTOR DENSITY (BY OWNER)
1
15M STIRRUPS
@ 300 O/C
1500
200 WIDE x 150 HIGH
CONCRETE EXTERIOR CURB
R/W 10M STIRRUPS @ 150 O/C
2-15M HORZ TOP CONTINUOUS
T/O SLAB
EL 100.000
1
1
1
1
3 - 15M EXTRA TYPICAL AT
THICKENED EDGE
600
450
1
1
75
MIN
C
OV
ER
75
MIN
C
OV
ER
75
MIN COVER
4400
1000 mm AROUND DISCHARGE
100 - 150 mm FREE DRAINING STONE
1000
3000
75Ø FLOOR DRAIN
C/W LOW PROFILE P-TRAP
3-15M CONT.
TOP & BOTTOM
15M STIRRUPS @ 300 O/C
DRILL & EPOXY GROUT
MIN. 150 mm INTO EXISTING
15M @ 300 O.C
w/ STD. HOOK
25 CHAMFER, TYP
FLOOR SLABT/O FLR SLAB
EL 100.000
400
250
P:\20164866\00_M
WS
B_R
ussell_W
TP
\W
orking_D
wgs\400_P
rocess_M
ech\03 R
oss-B
ins-B
S\03-B
S\4866-03-s-101.dw
g
DA
TE
: 2017-06-26
, D
esiree P
astorin
DRAWING REVISION
DESCRIPTIONDRAWNDESIGNDATEREV
SHEET
IF
N
OT
5
0 m
m A
DJU
ST
S
CA
LE
S
SC
AL
E(S
) S
HO
WN
A
RE
IN
TE
ND
ED
F
OR
A
NS
I D
(2
2X
34
) S
IZ
E D
RA
WIN
GS
, T
AB
LO
ID
(1
1X
17
) S
IZ
E D
RA
WIN
GS
A
RE
1
/2
O
F S
CA
LE
(S
) S
HO
WN
U
NL
ES
S N
OT
ED
O
TH
ER
WIS
E
SCALE:
50
m
m
www.ae.ca
203 - Five Donald Street, Winnipeg, Manitoba, R3L 2T4
Ph: 204 942 6391 Fax: 204 942 6399
ORIGINAL SEALED BY:
J. BETKE, P.ENG.
DATED: JUNE 26, 2017
RUSSELL BINSCARTH
REGIONAL WATER SYSTEM
BINSCARTH & ROSSBURN
RESERVOIR UPGRADES &
NEW BOOSTER STN ON ROAD 117N
M.W.S.B. # 1368 / AE # 20164866-03
AS SHOWN
STRUCTURAL
ROAD 117N BOOSTER STATION
MAIN FLOOR PLAN & SECTIONS
4866-03-S-101 0
22
26
0 2017JUN26 J. BETKE T. DYCHKO
ISSUED FOR TENDER &
CONSTRUCTION
PLAN
1
-
MAIN FLOOR
EL 100.000
1:25
SECTION
3
-
CONCRETE SLAB
1:25DETAIL
2
-
CONCRETE PUMP BASE
NTS
NOTES:
A. COORDINATION:
A.1. SEE MANITOBA WATER SERVICES BOARD STANDARD CONSTRUCTION
SPECIFICATIONS FOR SUBMISSION REQUIREMENTS.
B. CONCRETE REINFORCEMENTS STEEL:
B.1. ALL REINFORCEMENT SHALL BE IN ACCORDANCE WITH CSA G30.18.
B.2. REINFORCING STEEL - GRADE 400 R DEFORMED BLACK STEEL.
B.3. CONCRETE COVER TO BE 50 mm CLEAR, UNLESS NOTED OTHERWISE.
C. CAST-IN PLACE CONCRETE:
C.1. ALL CONCRETE SHALL BE IN ACCORDANCE WITH CSA A23.1/A23.2.
C.2. CONCRETE TYPE HS, CLASS OF EXPOSURE S-2.
C.3. REQUIRED CONCRETE STRENGTH AT 28 DAYS IS 30 MPA.
C.4. NOT WITHSTANDING MANITOBA WATER SERVICES BOARD STANDARD
CONSTRUCTION SPECIFICATIONS, SECTION 033000 - CAST-IN PLACE
CONCRETE:
SUPERPLASTICIZER IS NOT REQUIRED.
SLUMP SHALL BE 100 mm ± 30 mm
C.5. FINISHING CONCRETE SURFACES:
C.5.1. MAIN FLOOR SURFACE HARDENER: APPLY DRY-SHAKE FLOOR
HARDENER ON ALL CONCRETE MAIN FLOOR SURFACES IN
ACCORDANCE WITH MANUFACTURER'S RECOMMENDATION.
PRODUCT: DIAMAG 7 BY SIKA OR APPROVED EQUIVALENT.
C.5.2. MAIN FLOOR SURFACE SEALER: APPLY WATER-BASED CURING
COMPOUND ON ALL CONCRETE MAIN FLOOR SURFACES IN
ACCORDANCE WITH MANUFACTURER'S RECOMMENDATION.
PRODUCT: FLORSEAL WB BY SIKA OR APPROVED EQUIVALENT.
NOTE:
STAINLESS STEEL STANDS ARE
AN ACCEPTABLE ALTERNATIVE.
. .
PW
REGIONAL WTP
BUV-3202
CAV-3211
FE
3102
PI
3201
.
PIT
3200
.
INCOMING
PRESSURE
M M
. .
PW
TO ROSSBURN
BUV-3261 PRV-3662
BUV-3240 BUV-3244
PI
3210
.
PIT
3211
.
PI
3220
.
PIT
3221
.
VFD
3220
VFD
3210
BAV-3290
PIT
3200
FI
3102
FQI
3102
XA
3102
XA
3102A
XS
3102
FLOW
INDICATE
FLOW
TOTALIZER
ALARM
EMPTY PIPE
ALARM
FAULT
RESET
PRESSURE
INDICATION
XI
3210
SI
3210
XA
3210
RUN
STATUS
SPEED
INDICATION
GENERAL
ALARM
PI
3210A
PRESSURE
INDICATION
XI
3220
SI
3220
XA
3220
RUN
STATUS
SPEED
INDICATION
GENERAL
ALARM
PI
3220A
PRESSURE
INDICATION
XI
3299
DOOR
CONTACT
DOOR
CONTACT
BP-3002
BOOSTER PUMP
.
..
BP-3001
BOOSTER PUMP
.
..
100-PW-H1
50-PW-H1
100-PW-H1
80-SRL-H1
FIT
3102
.
BOOSTER PUMP
7.5 HP
6.0 L/SEC @ 60 PSI BOOST
BOOSTER PUMP
7.5 HP
6.0 L/SEC @ 60 PSI BOOST
P:\20164866\00_M
WS
B_R
ussell_W
TP
\W
orking_D
wgs\400_P
rocess_M
ech\03 R
oss-B
ins-B
S\03-B
S\4866-03-d-001.dw
g
DA
TE
: 2017-06-26
, D
esiree P
astorin
DRAWING REVISION
DESCRIPTIONDRAWNDESIGNDATEREV
SHEET
IF
N
OT
5
0 m
m A
DJU
ST
S
CA
LE
S
SC
AL
E(S
) S
HO
WN
A
RE
IN
TE
ND
ED
F
OR
A
NS
I D
(2
2X
34
) S
IZ
E D
RA
WIN
GS
, T
AB
LO
ID
(1
1X
17
) S
IZ
E D
RA
WIN
GS
A
RE
1
/2
O
F S
CA
LE
(S
) S
HO
WN
U
NL
ES
S N
OT
ED
O
TH
ER
WIS
E
SCALE:
50
m
m
www.ae.ca
203 - Five Donald Street, Winnipeg, Manitoba, R3L 2T4
Ph: 204 942 6391 Fax: 204 942 6399
ORIGINAL SEALED BY:
K. ANDERSON, P.ENG.
DATED: JUNE 26, 2017
RUSSELL BINSCARTH
REGIONAL WATER SYSTEM
BINSCARTH & ROSSBURN
RESERVOIR UPGRADES &
NEW BOOSTER STN ON ROAD 117N
M.W.S.B. # 1368 / AE # 20164866-03
AS SHOWN
PROCESS
ROAD 117N BOOSTER STATION
PROCESS & INSTRUMENTATION DIAGRAM
4866-03-D-001 0
23
26
0 2017JUN26 D. PASTORIN D. PASTORIN
ISSUED FOR TENDER &
CONSTRUCTION
1 2 3
A
B
C
BP-3001 BP-3002
25Ø AIR RELEASE
100Ø BUTTERFLY VALVE
100Ø MAG METER
PRESSURE GAUGE
OUTLINE OF ROOF
OVERHANG ABOVE
PRESSURE GAUGE
& INDICATING
TRANSMITTER, TYP
EACH PUMP
PRESSURE GAUGE
100Ø BUTTERFLY
VALVE (N.C.)
50Ø
50Ø
100Ø
INCOMING 150Ø SCH40 S.S.
RURAL WATER SUPPLY
(BY OTHERS)
OUTGOING 150Ø SCH40 S.S.
RURAL WATER SUPPLY
(BY OTHERS)
100Ø
75Ø PRESSURE RELIEF &
SURGE ANTICIPATOR VALVE
c/w 75Ø DISCHARGE PIPING
THROUGH WALL TO OUTSIDE
± 500
± 500
150Ø S.S. OVERFLOW PIPE
w/ 6 mm THICK FLAP VALVE
c/w INSECT SCREEN, INSTALLED 290 AFF
100Ø
100Ø
50Ø B'FLY VALVE,
TYP EACH PUMP
75Ø
50Ø CHECK VALVE,
TYP EACH PUMP
DISCHARGE
PRESSURE GAUGE &
INDICATING TRANSMITTER
75Ø
75Ø
MANUAL AIR RELEASE
PRESSURE GAUGE,
TYP OF 2
75Ø BUTTERFLY
VALVE, TYP OF 2
150x75 REDUCING TEE
45
0
100Ø
75Ø
OUTGOING 150Ø
SCH40 S.S. PIPE
SPOOL THROUGH
FLOOR (BY OTHERS)
CUT PIPE & WELD
NEW 300# FLANGE TO
CORRECT ELEVATION
750
75Ø
50Ø
150Ø
100Ø BUTTERFLY VALVE
(N.C.)
BLIND FLANGE
(SWAB LAUNCH)
150x100 REDUCING TEE
600 55
0
50Ø
50Ø BUTTERFLY
VALVE, TYP OF 3
MANUAL AIR RELEASE
25Ø AIR RELEASE VALVE
c/w ISOLATION BALL
VALVE & S.S. SUPPORT
ANGLE OR UNISTRUT
BOLTED TO FLANGE
100Ø BUTTERFLY VALVE
(N.O.)
100Ø CHECK VALVE
150x100 REDUCER
100Ø MAG METER
100Ø
PRESSURE GAUGE
& INDICATING
TRANSMITTER, TYP
EACH PUMP
75Ø
50Ø CHECK
VALVE, TYP
400x400x250 HIGH
CONCRETE PUMP BASE
SEE 2/S-101
75Ø BUTTERFLY
VALVE, TYP (N.O.)
SAMPLE TAP
INCOMING 150Ø SCH40 S.S.
PIPE SPOOL THROUGH FLOOR
(BY OTHERS)
CUT PIPE & WELD NEW
300# FLANGE TO
CORRECT ELEVATION
50Ø
PRESSURE GAUGE &
INDICATING TRANSMITTER
75x50
ECCENTRIC
REDUCER, TYP
75Ø SCH10 S.S. PRESSURE
RELIEF DISCHARGE
c/w INSECT SCREEN
BETWEEN FLANGES
CONCRETE SPLASH PAD
500
350
BP-3001
BP-3002
75Ø PRESSURE RELIEF &
SURGE ANTICIPATOR VALVE
OUTGOING 150Ø
RURAL WATER SUPPLY
INCOMING 150Ø
RURAL WATER SUPPLY
150Ø BUTTERFLY VALVE
(NORMALLY OPEN)
100Ø MAGNETIC
FLOW METER
50Ø BUTTERFLY VALVE
(NORMALLY OPEN)
100Ø BUTTERFLY VALVE
(NORMALLY CLOSED)
100Ø BUTTERFLY VALVE
(NORMALLY OPEN)
25Ø AIR RELEASE VALVE
MANUAL AIR RELEASE
P:\20164866\00_M
WS
B_R
ussell_W
TP
\W
orking_D
wgs\400_P
rocess_M
ech\03 R
oss-B
ins-B
S\03-B
S\4866-03-d-101.dw
g
DA
TE
: 2017-06-26
, D
esiree P
astorin
DRAWING REVISION
DESCRIPTIONDRAWNDESIGNDATEREV
SHEET
IF
N
OT
5
0 m
m A
DJU
ST
S
CA
LE
S
SC
AL
E(S
) S
HO
WN
A
RE
IN
TE
ND
ED
F
OR
A
NS
I D
(2
2X
34
) S
IZ
E D
RA
WIN
GS
, T
AB
LO
ID
(1
1X
17
) S
IZ
E D
RA
WIN
GS
A
RE
1
/2
O
F S
CA
LE
(S
) S
HO
WN
U
NL
ES
S N
OT
ED
O
TH
ER
WIS
E
SCALE:
50
m
m
www.ae.ca
203 - Five Donald Street, Winnipeg, Manitoba, R3L 2T4
Ph: 204 942 6391 Fax: 204 942 6399
ORIGINAL SEALED BY:
K. ANDERSON, P.ENG.
DATED: JUNE 26, 2017
RUSSELL BINSCARTH
REGIONAL WATER SYSTEM
BINSCARTH & ROSSBURN
RESERVOIR UPGRADES &
NEW BOOSTER STN ON ROAD 117N
M.W.S.B. # 1368 / AE # 20164866-03
AS SHOWN
PROCESS
ROAD 117N BOOSTER STATION
MAIN FLOOR PLAN & SECTIONS
4866-03-D-101 0
24
26
0 2017JUN26 D. PASTORIN D. PASTORIN
ISSUED FOR TENDER &
CONSTRUCTION
PLAN
1
-
MAIN FLOOR
1:25
SECTION
3
-
PROCESS PIPING
1:25 SECTION
4
-
PROCESS PIPING
1:25SECTION
2
-
PRESSURE RELIEF PIPING
1:25
NOTE:
ALL PIPING SHALL BE SCH10
STAINLESS STEEL, UNLESS
NOTED OTHERWISE.
NOTES:
1. OPERATING PRESSURE OF FACILITY SHALL BE 125-200 PSI
(860-1380 kPa). EQUIPMENT, PIPING AND FLANGES TO SUIT.
2. ALL PIPING SHALL BE SCH10 S.S. c/w 300# FLANGES.
VIEW
2
-
3D ISOMETRIC
NTS
T
DM-101
EF-101
M
M
O/A 190 L/SEC
UH
EUH-102
UH
EUH-101
DM-102
T
T
H
ELECTRIC
UNIT HEATER
INTAKE LOUVER
EXHAUST FAN
THERMOSTAT, TYP
WEATHER HOOD
WALL MOUNTED
THERMOSTAT
CONTROLS UNIT
HEATER FAN
AND HEAT
TS
O/A
INTAKE
EXHAUST
FAN
H
ROOM THERMOSTAT
& HUMIDISTAT
EXHAUST DAMPER
OPERATOR
INTAKE DAMPER
OPERATOR
T
38x38x3 ANGLE FRAME
SUPPORT AROUND HOOD
OPENING
SEAL TIGHT AROUND LOUVER
FRAME & WALL OPENING
16 GA. 25 SQ. FRAMED
ALUMINUM BIRD SCREEN w/
INSECT SCREEN ON EXTERIOR
1.6 THICK GALVANIZED
METAL WEATHER HOOD
ACCESSIBLE
MOTORIZED DAMPER
50 INSULATION
WITH CANVAS
SUPPORT TO STRUCTURE
w/ 38x38x3 ANGLE
ACCESSIBLE, SLIDE
OUT INSECT SCREEN
NOTE:
MOUNT AND SECURE FAN IN ACCORDANCE WITH
MANUFACTURER'S INSTALLATION PROCEDURES.
ACCESSIBLE
MOTORIZED DAMPER
EXHAUST FAN
ANCHORED TO WALL w/
WEATHERPROOF SEAL
P:\20164866\00_M
WS
B_R
ussell_W
TP
\W
orking_D
wgs\400_P
rocess_M
ech\03 R
oss-B
ins-B
S\03-B
S\4866-03-m
-101.dw
g
DA
TE
: 2017-06-26
, D
esiree P
astorin
DRAWING REVISION
DESCRIPTIONDRAWNDESIGNDATEREV
SHEET
IF
N
OT
5
0 m
m A
DJU
ST
S
CA
LE
S
SC
AL
E(S
) S
HO
WN
A
RE
IN
TE
ND
ED
F
OR
A
NS
I D
(2
2X
34
) S
IZ
E D
RA
WIN
GS
, T
AB
LO
ID
(1
1X
17
) S
IZ
E D
RA
WIN
GS
A
RE
1
/2
O
F S
CA
LE
(S
) S
HO
WN
U
NL
ES
S N
OT
ED
O
TH
ER
WIS
E
SCALE:
50
m
m
www.ae.ca
203 - Five Donald Street, Winnipeg, Manitoba, R3L 2T4
Ph: 204 942 6391 Fax: 204 942 6399
ORIGINAL SEALED BY:
K. ANDERSON, P.ENG.
DATED: JUNE 26, 2017
RUSSELL BINSCARTH
REGIONAL WATER SYSTEM
BINSCARTH & ROSSBURN
RESERVOIR UPGRADES &
NEW BOOSTER STN ON ROAD 117N
M.W.S.B. # 1368 / AE # 20164866-03
AS SHOWN
MECHANICAL
ROAD 117N BOOSTER STATION
MAIN FLOOR PLAN
4866-03-M-101 0
25
26
0 2017JUN26 K. ANDERSON T. DYCHKO
ISSUED FOR TENDER &
CONSTRUCTION
PLAN
1
-
MAIN FLOOR
EL 100.000
1:25
DAMPER, LOUVER & FAN SCHEDULE
TAG MANUFACTURER MODEL LOCATION SERVICE OPERATION BLADE ORIENTATION
FLOW AREA (mm²) AIR FLOW (L/s)
DIMENSIONS (mm x
mm)
V/Ph/Hz NOTES
DM-101 TAMCO 9000-MR PROCESS AREA SUPPLY AIR OPPOSED - SEE PLAN SEE PLAN 120/1/601,2
DM-101 TAMCO 9000-MR PROCESS AREA EXHAUST OPPOSED - SEE PLAN SEE PLAN 120/1/601,2
EF-101 GREENHECK SE1-10-428-P-1 PROCESS AREA EXHAUST AIR DEPOSED - SEE PLAN SEE PLAN 120/1/60
NOTES:
1. C/W BELIMO LF120 US SPRING RETURN ACTUATOR.
2. C/W TAMCO 6000 INSECT SCREEN IN DUCT. SLIDE OUT SIDE.
3. EF-101 TO BE LOCATED MINIMUM 3050 FROM DM-101
ELECTRIC UNIT HEATER SCHEDULE
TAG MANUFACTURER MODEL LOCATION
INPUT / OUTPUT
CAPACITY (kW)
HP V/Ph/Hz NOTES
EUH-101 OUELLETT OAS PROCESS AREA 10.0 FRAC 600/3/601, 2, 3
EUH-102 OUELLETT OAS PROCESS AREA 10.0 FRAC 600/3/601, 2, 3
NOTES:
1. C/W ADJUSTABLE LOUVER DIFFUSER
2. C/W WALL-MOUNTED THERMOSTAT WITH GUARD AND LOCKABLE COVER
3. C/W CONTROL TRANSFORMER.
DETAIL
4
-
INTAKE HOOD IN WALL
NTS
SCHEMATIC
2
-
DAMPER CONTROL
NTS SCHEMATIC
3
-
UNIT HEATER CONTROL
NTS
HVAC NOTES
1. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL
LABOR REQUIRED TO INSTALL COMPLETE AND OPERABLE
MECHANICAL SYSTEMS AS INDICATED ON THE DRAWINGS, AS
SPECIFIED AND AS REQUIRED BY CODE.
2. INSTALL ALL MECHANICAL EQUIPMENT AND APPURTENANCES IN
ACCORDANCE WITH MANUFACTURERS' RECOMMENDATIONS,
CONTRACT DOCUMENTS, AND APPLICABLE CODES AND
REGULATIONS.
3. COORDINATE ALL LOUVRE AND EXHAUST FAN OPENINGS WITH
PROCESS AND ELECTRICAL EQUIPMENT LOCATIONS.
4. ALL GRAVITY DRAIN PIPING SHALL BE INSTALLED AT A MINIMUM
1% GRADE.
5. UNLESS OTHERWISE INDICATED, LOCATE ALL ROOM
THERMOSTATS AND HUMIDISTATS 1320MM ABOVE FINISHED
FLOOR.
6. MATCH DAMPER MOTOR ELECTRICAL REQUIREMENTS TO FAN
MOTOR STARTER OR ELECTRIC MOTOR CHARACTERISTICS.
PROVIDE ELECTRIC TRANSFORMERS AND/OR DAMPER MOTORS
TO SUIT WIRING ARRANGEMENT.
7. FOR EVERY THERMOSTAT TO BE MOUNTED ON AN OUTSIDE
WALL, PROVIDE A 20MM MIN. THERMAL ISOLATION BLOCK
BETWEEN THE THERMOSTAT AND WALL.
8. ALL ACTUATORS FOR MOTORIZED DAMPERS ARE TO BE
INSTALLED OUTSIDE OF THE AIRSTREAM.
VENTILATION SEQUENCE OF OPERATIONS:
BOOSTER STATION (EF-101):
ON A SPACE TEMPERATURE RISE GREATER THAN THE COOLING
SET-POINT, OR SPACE HUMIDITY RISE GREATER THAN THE HUMIDITY
SET-POINT, THE OUTDOOR AIR DAMPER (DM-501) AND EF-101 FAN
DAMPER SHALL OPEN AND EF-101 SHALL START. WHEN THE SPACE
TEMPERATURE DROPS BELOW THE COOLING SET-POINT AND THE
SPACE HUMIDITY DROPS BELOW THE HUMIDITY SET-POINT, EF-101
SHALL STOP AND ALL DAMPERS SHALL CLOSE.
TEMPERATURE CONTROLLER INITIAL ADJUSTABLE COOLING
SET-POINT: 24C.
HUMIDITY CONTROLLER INITIAL ADJUSTABLE SET-POINT: 65% RH.
ELECTRIC UNIT HEATERS:
HEATING DEVICE SHALL CYCLE ON AND OFF TO MAINTAIN
TEMPERATURE AT SET-POINT.
TEMPERATURE CONTROLLER INITIAL ADJUSTABLE HEATING
SET-POINT: 18C
UNIT HEATERS ARE TO BE ADJUSTED TO DIRECT AIRFLOW TO THE
FLOOR.
DETAIL
5
-
SIDEWALL MOUNTED EXHAUST FAN
NTS
1 2 3
A
B
C
A
C
A
AA
B
XX
XX
XX
XX
XX
XX
XX
DXX
1 2 3
A
B
C
BP
3001
M M
BP
3002
PIT
3200
PIT
3221
FIT
3102
EUH-102
EUH-101
PIT
3211
EF-101
GROUND
ELECTRODE
MCC, 600A, 600V, 3Ø, 4W
SPD
PANEL A, 100A,
42 CCT
M
PAD MOUNTED
CTSE ENCLOSURE
600V, 3Ø, 4W SERVICE DIP
BY MANITOBA HYDRO
100A MANUAL
TRANSFER SWITCH
3 POLE, SOLID
NEUTRAL
100A SPLITTER
3-#3/0 &
GROUND
4-#2 &
GROUND
100 AMP
100% RATED
SERVICE RATED
BREAKER
15 KVA
600V:208V
3 PHASE
4 WIRE
XFMR-601
7.5
HP
BP
1001
HZ
7.5
HP
BP
1002
HZ HZ
3-#8 &
GND
3-#8 &
GND
P:\20164866\00_M
WS
B_R
ussell_W
TP
\W
orking_D
wgs\400_P
rocess_M
ech\03 R
oss-B
ins-B
S\03-B
S\4866-03-e-101.dw
g
DA
TE
: 2017-06-26
, D
esiree P
astorin
DRAWING REVISION
DESCRIPTIONDRAWNDESIGNDATEREV
SHEET
IF
N
OT
5
0 m
m A
DJU
ST
S
CA
LE
S
SC
AL
E(S
) S
HO
WN
A
RE
IN
TE
ND
ED
F
OR
A
NS
I D
(2
2X
34
) S
IZ
E D
RA
WIN
GS
, T
AB
LO
ID
(1
1X
17
) S
IZ
E D
RA
WIN
GS
A
RE
1
/2
O
F S
CA
LE
(S
) S
HO
WN
U
NL
ES
S N
OT
ED
O
TH
ER
WIS
E
SCALE:
50
m
m
www.ae.ca
203 - Five Donald Street, Winnipeg, Manitoba, R3L 2T4
Ph: 204 942 6391 Fax: 204 942 6399
ORIGINAL SEALED BY:
S. FRIEL, P.ENG.
DATED: JUNE 26, 2017
RUSSELL BINSCARTH
REGIONAL WATER SYSTEM
BINSCARTH & ROSSBURN
RESERVOIR UPGRADES &
NEW BOOSTER STN ON ROAD 117N
M.W.S.B. # 1368 / AE # 20164866-03
AS SHOWN
ELECTRICAL
ROAD 117N BOOSTER STATION
MAIN FLOOR PLAN & SCHEDULES
4866-03-E-101 0
26
26
0 2017JUN26 S. FRIEL T. DYCHKO
ISSUED FOR TENDER &
CONSTRUCTION
* - "kW" COLUMN FOR INDUCTIVE LOADS MEANS POWER OUTPUT AND FOR RESISTIVE LOADS MEANS POWER INPUT.
NOTES:
1. REFER TO DELCO WIRING SCHEDULES AND INFORMATION.
2. REFER TO MANUFACTURER'S RECOMMENDATIONS
3. CONFIRM RATINGS FROM EQUIPMENT SHOP DRAWINGS.
4. WIRE AND CONNECT TSTATS, HSTATS, HVAC EQUIP, ETC. TO MAIN PANELBOARDS.
PROVIDE MOTOR CIRCUIT PROTECTORS AND OVERLOAD PROTECTION FOR ALL MOTOR LOADS.
FINAL CONNECTIONS TO MOTOR LOADS OR LOADS WITH VIBRATION OR MOVEMENT SHALL BE BY TECK CABLE.
STARTER TYPES:
FVR - FULL VOLTAGE REVERSING
MAN - MANUAL
FVNR - FULL VOLTAGE NON-REVERSING
RVNR - REDUCED VOLTAGE NON-REVERSING
SSRV - SOFT START REDUCED VOLTAGE
VFD - VARIABLE FREQUENCY DRIVE
VSC - VARIABLE SPEED CONTROLLER
REMOTE CONTROL TYPES:
FS - FLOW SWITCH
HOA - HAND-OFF-AUTO SWITCH
HSTAT - HUMIDSTAT
LMS - LIMIT SWITCH
LVS - LEVEL SWITCH
PS - PRESSURE SWITCH
PB - PUSH BUTTON
S/C - SPEED CONTROL
TS - TEMPERATURE SWITCH
TSTAT - THERMOSTAT
FR - FWD/REV SWITCH
S/S - START/STOP SWITCH
REMOTE CONTROL TYPES:
VS - VARIABLE SPEED SWITCH
DCS - DeltaV PROCESS CONTROL SYSTEM
DDC - HVAC DIRECT DIGITAL CONTROL SYSTEM
DISCONNECT TYPES:
DSF - FUSED DISCONNECT SWITCH
DSU - UNFUSED DISCONNECT SWITCH
PLAN
1
-
MAIN FLOOR
LIGHTING
1:25
MOTOR & EQUIPMENT SCHEDULE
EQUIPMENT INFORMATION STARTER
REMOTE
CONTROL
DISC
TYPE
NOTES REMARKS
TAG DESCRIPTION LOCATION HP kW* VOLTS Ø
POWER CONDUIT
AND/OR FEEDER SIZE
CONNECTED TO SUPPLIED BY TYPE HOA
S/S
PB
IND
LITE
MAN
S/C
CONTROL
Y/N Y/N Y/N Y/N
BP-1001 RAW WATER BOOSTER PUMP PROCESS AREA 7.5 600 3 3C#8 TECK90 MCC-1001 GC VFD Y N Y Y2,3
C/W PRESSURE TRANSDUCER
BP-1002 RAW WATER BOOSTER PUMP PROCESS AREA 7.5 600 3 3C#8 TECK90 MCC-1001 GC VFD Y N Y Y2,3
C/W PRESSURE TRANSDUCER
EF-101 EXHAUST FAN PROCESS AREA 1.50 120 1 2C#12 TECK90 PANEL A GC FVNR HSTAT2,3,4 PROVIDE STARTER, CONNECT W/ CONTROLS
DM-101 MOTORISED DAMPNER PROCESS AREA 0.10 120 1 2C#12 TECK90 PANEL A GC HSTAT2,3,4
DM-102 MOTORISED DAMPNER PROCESS AREA 0.10 120 1 2C#12 TECK90 PANEL A GC HSTAT2,3,4
EUH-101 ELECTRIC UNIT HEATER PROCESS AREA 10.0 600 3 3C#12 TECK90 MCC-1001 GC TSTAT2,3,4
EUH-102 ELECTRIC UNIT HEATER PROCESS AREA 10.0 600 3 3C#12 TECK90 MCC-1001 GC TSTAT2,3,4
LIGHTING FIXTURE SCHEDULE
FIXTURE
TAG
No.
EQUIPMENT INFORMATION
REMARKS
DESCRIPTION MANUFACTURER & CATALOGUE No.
MOUNTING
TYPE
MOUNTING
HEIGHT
VOLTS
FIXTURE
SIZE
WATTS
LAMPS
No. TYPE K-VALUE
A VAPOUR TIGHT SURFACE MOUNT
METALUX:
4VT2-LD4-4-DR-UNV-L840-WL-U-VT2
SURFACE - 120V 178X1265 81W 1 LED 4000
B REMOTE EMERGENCY LIGHT LUMACELL: MQM2HZ-LD9-6V10W-SG WALL 2300 AFF 120V - 10W 2 LED - -
C EXIT SIGN COMBO LUMACELL: 3LERHZN-2-LD9-GG-AT WALL 2300 AFF 120V - 10W 2 LED - -
D EXTERIOR WALL PACK LUMARK: XTOR2B-N-PC1 SURFACE 2300 AFF 120V 250X150 18W 1 LED 3500 PHOTOCELL
PLAN
2
-
MAIN FLOOR
POWER AND INSTRUMENTS
1:25
SCADA PANEL
(BY OTHERS)
TRANSFORMER
MANUAL TRANSFER SWITCH w/
RECEPTACLE ON SOUTH
EXTERIOR WALL FOR PORTABLE
GENERATOR
MCC
DIAGRAM
3
-
SINGLE LINE
NTS
PANEL A