Page 1: Rpt (af 2-741-in-1-0698)

RPT

B E T T E R A I R I S O U R B U S I N E S S ®

Safe Change Housing

● Compact, modular design

● Fully enclosing bag systemfor safe filter change

● Suitable for both verticaldownflow and horizontalairflow

● Adjustable clampingmechanism for positiveairtight sealing

Application The RPT Safe Change Housing is areliable duct housing for the removalof Radioactive, Pathogenic and Toxiccontaminants. It can be suppliedwith a single or double stagefiltration system, consisting of asingle HEPA filter or a HEPA filterwith a prefilter. Typical areas ofapplication include the healthcare,pharmaceutical, microelectronic andnuclear industries as well asbiochemical laboratories. The unitcan be used for vertical downflow orhorizontal airflow.

SafetyThe RPT Housing is designed tofacilitate safe removal of contamina-ted filters and to minimize the risk ofhazardous particulate escaping intothe immediate environment. To thisend the housing is equipped with afully enclosed bag system into whichthe filter is placed for safe disposal.

Filter InstallationTo guarantee a truly leaktight systemthe HEPA filter is clamped against asealing frame with a maintenance-free positive locking mechanism,operated with a single lever; theprefilter is installed by pushing thesupport frame upwards.

Filter ReplacementFilter removal is done by opening theservice hatch, extending thepolyethylene bag and removing thecontaminated filter from the housinginto the bag, which is secured to thebag flange at the opening.

Space Saving DesignThe RPT housing is compact andmodular in design. To cater for highair volumes, modules may beinstalled side by side up to amaximum of 5 units in single ordouble row formation or,alternatively, one on top of the other.

Sturdy, Reliable Construction The standard unit is made of mildreinforced steel coated with epoxywhite paint. It can be operated at anoverpressure of up to 2500 Papositive and 3000 Pa negative. Theupper operating temperature limit is60˚C. Differential pressure measuringpoints are located in both theprefilter and mainfilter sections.

Options a) A flange with test groove for leak

testing of the gasket seal between main filter and housing

b) Coupling set consisting of frames and bolts for the installation of several adjacent units

c) Integrated prefilter sectiond) Stainless steel executione) Other (contact local AAF sales

office)

Page 2: Rpt (af 2-741-in-1-0698)

RPT

AF-2-741-IN-1-0698 © 1998 AAF International

AAF has a policy of continuous product research and improvement and reserves the right to change design and specifications without notice

AAF-International B.V .P.O. Box 79281008 AC Amster damThe NetherlandsTel.: + 31 20 549 44 11 Fax: + 31 20 644 43 98

International AAF Offices:Vienna (A), Montreal (CDN), Dortmund (D),Vitoria (E), Paris (F), Cramlington (GB),Athens (GR), Milan (I), Riyadh (KSA), Mexico (Mex), Amsterdam (NL), Singapore,Istanbul (TR), Louisville, Ky (USA)

AAF Ag ents:Copenhagen (DK), Bangalore (IND)Oslo (N), Lisbon (P), Johannesburg (RSA), Dalsjöfors (S), Malmö (S), Helsinki (SF)

850

580

57.5 57.5

72 724X146 = 584

613

728

Ø 1

0

REC

OM

MEN

DED

FOR

SER

VIC

E57

.5

724X

146

= 58

4

613

728

72

57.5

135

1000

Total air flow capacity m3/s Filters

Size BioCel I / BioPak AstroCel I / AstroPak AstroCel I High Capacity 610 x 610 mm

at 125 Pa at 250 Pa at 125 Pa at 250 Pa at 125 Pa at 250 Pa Number

11 0.56 1.11 0.28 0.56 0.36 0.72 121 1.11 2.22 0.56 1.11 0.72 1.44 231 1.67 3.33 0.83 1.67 1.08 2.17 341 2.22 4.44 1.11 2.22 1.44 2.89 451 2.78 5.56 1.39 2.78 1.81 3.61 512 1.11 2.22 0.56 1.11 0.72 1.44 222 2.22 4.44 1.11 2.22 1.44 2.89 432 3.33 6.67 1.67 3.33 2.17 4.33 642 4.44 8.89 2.22 4.44 2.89 5.78 852 5.56 11.11 2.78 5.56 3.61 7.22 10

Style Code:

RPT-XX-X-X-X-X

Size: (see tabel)XX First digit: number adjecent filterhousings

Second digit: single(1) or double (2) rowX Prefilter / No prefilter (P or N)X Number of mainfilters in air flow directionX DIN test flange / No DIN test flange (D or N)*X Coupling set / No coupling set (C or N)

Example:

RPT-32-N-2-D-C

Size: 32 Three adjecent filterhousings

Double rowN No prefilter2 Two mainfilters in air flow directionD DIN test flange includedC Coupling set included

* In case two or more mainfilter sections are installed in the air flow direction, only the last section will be suppliedwith a test flange