Main Tier Meter Verification Rego Park Page 1 RPS Main Tier On-site Visit Date: 12/29/2014 Meter Verification Report Date Submitted: 12/31/2014 Completed by CDH Energy Corp. Hugh Henderson Applicant Bloom Energy (Main Tier Contract 33393) Facility/Project AT&T, 94-03 Queens Blvd. Rego Park, NY 11374 Facility Description: A Bloom Energy Fuel Cell (FC) Model ES-5700 has been installed at the AT&T data center facility on Queens Blvd in Queens. The FC provides 200 kW of AC power to the facility via the grid paralell circuit from the unit. Metering System The power meter is Veris E51 series, which satisfies the ANSI C12.20 standard and is rated at .5% accuracy. The three CTs used are 6811-400-0.3 V 400A split core with a ±1% accuracy. The PowerDash monitoring system uses a DIGI cellular modem to record the Modbus readings and report them back to their website (www.powerdash.com ). CDH Energy automatically retrieves 15-minute kWh data from the website each night using the PowerDash API. The data retrieved for December 29, 2014 is shown on the graph on the next page. Verification Process We confirmed the settings for the Veris E51 device (CT size=400A, voltages=480, etc). We also compare the readings on the face of the E51 to the readings from the Acuvim power meter in the Bloom Energy Cabinet were consistent (see the table on next page). We also used our Handheld Fluke 39 Power Meter to independently verify the meter readings (current and power). The table on the next page lists the measured current and power. The data from the Veris E51, Acuvium, and Fluke 39 meters were all in good agreement (the difference of 2% for the Fluke 39 is good considering we were only on 1 conductor). The data flowing from the website were also consistent with the E51 power readings.

Upload: ngongoc

Post on 27-Apr-2018

221 views

Category:

Documents


8 download

TRANSCRIPT

Page 1: RPS Main Tier On-site Visit Date: Meter Verification ...dataint.cdhenergy.com/Documentation/Rego_park_main_tier_mtr_rpt.pdf · Meter Verification Report Date Submitted: 12/31/2014

Main Tier Meter Verification – Rego Park Page 1

RPS Main Tier On-site Visit Date: 12/29/2014 Meter Verification Report Date Submitted: 12/31/2014

Completed by CDH Energy Corp. Hugh Henderson

Applicant Bloom Energy (Main Tier Contract 33393)

Facility/Project AT&T, 94-03 Queens Blvd. Rego Park, NY 11374

Facility Description:

A Bloom Energy Fuel Cell (FC) Model ES-5700 has been installed at the AT&T data center

facility on Queens Blvd in Queens. The FC provides 200 kW of AC power to the facility via the

grid paralell circuit from the unit.

Metering System

The power meter is Veris E51 series, which satisfies the ANSI C12.20 standard and is

rated at .5% accuracy. The three CTs used are 6811-400-0.3 V 400A split core with a

±1% accuracy.

The PowerDash monitoring system uses a DIGI cellular modem to record the Modbus

readings and report them back to their website (www.powerdash.com). CDH Energy

automatically retrieves 15-minute kWh data from the website each night using the

PowerDash API. The data retrieved for December 29, 2014 is shown on the graph on the

next page.

Verification Process

We confirmed the settings for the Veris E51 device (CT size=400A, voltages=480, etc).

We also compare the readings on the face of the E51 to the readings from the Acuvim

power meter in the Bloom Energy Cabinet were consistent (see the table on next page).

We also used our Handheld Fluke 39 Power Meter to independently verify the meter

readings (current and power). The table on the next page lists the measured current and

power.

The data from the Veris E51, Acuvium, and Fluke 39 meters were all in good agreement

(the difference of 2% for the Fluke 39 is good considering we were only on 1 conductor).

The data flowing from the website were also consistent with the E51 power readings.

Page 2: RPS Main Tier On-site Visit Date: Meter Verification ...dataint.cdhenergy.com/Documentation/Rego_park_main_tier_mtr_rpt.pdf · Meter Verification Report Date Submitted: 12/31/2014

Main Tier Meter Verification – Rego Park Page 2

On-Site readings on December 29, 2014 at noon.

Measured Current Fluke 39 Power Measurements (on 1 of 3 conductors)

On-Site Power Meters

A - 84 amps A-B = 35 kW Veris E51 = 211 kW B – 89 amps A-C = 34 kW Acuvim = 212 kW (within 0.5%) C – 82 amps Sum = 69 kW x 3 = 207 kW (within 2%)

Graph showing data taken from PowerDash API

200

202

204

206

208

210

212

214

216

218

220

0 5 10 15 20 25

Po

we

r (k

Wh

/h)

Hour of Day

Monday, December 29, 2014

On-site readings

taken at 12 noon

Page 3: RPS Main Tier On-site Visit Date: Meter Verification ...dataint.cdhenergy.com/Documentation/Rego_park_main_tier_mtr_rpt.pdf · Meter Verification Report Date Submitted: 12/31/2014

Main Tier Meter Verification – Rego Park Page 3

SITE PHOTOS:

CT Cabinet PowerDash

Page 4: RPS Main Tier On-site Visit Date: Meter Verification ...dataint.cdhenergy.com/Documentation/Rego_park_main_tier_mtr_rpt.pdf · Meter Verification Report Date Submitted: 12/31/2014

Main Tier Meter Verification – Rego Park Page 4

Acuvium II Meter in Bloom Energy Panel

Veris E51 Power Transducer in Power Dash Panel

Page 5: RPS Main Tier On-site Visit Date: Meter Verification ...dataint.cdhenergy.com/Documentation/Rego_park_main_tier_mtr_rpt.pdf · Meter Verification Report Date Submitted: 12/31/2014

Main Tier Meter Verification – Rego Park Page 5

Namplate Information

Nameplate for Power Module

Nameplate for one of the six fuel cell modules