Page 1: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

ROTH TerraStar Heat Pumps W-SeriesWATER-TO-WATERTwo-Stage, R-410aPackaged VerticalUnit Specification CatalogP/N 2300100911

...Your environment is our business...

Call 888-266-7684 US or 800-969-7684 CAN or visit our website at www.roth-america.com

Page 2: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

1RWT Series Catalog - August 2010 Roth

Table of Contents:

Product Introduction & Unit Features .............................................................................................................2-3

Performance Data: ISO 13256-2 ......................................................................................................................4-5

Unit Nomenclature: ............................................................................................................................................6

Unit Nomenclature: Air Handlers .......................................................................................................................7

Unit Nomenclature: ”A” Coils ..............................................................................................................................8

Glossary, Application Notes, Calculations, & Water Flow Selection .................................................................9

Performance Considerations .............................................................................................................................10

Buffer Tank Sizing ..............................................................................................................................................11

Performance Data: RWT026 - Part Load Heating & Cooling ...........................................................................12

Performance Data: RWT026 - Full Load Heating & Cooling ...........................................................................13

Performance Data: RWT034 - Part Load Heating & Cooling ...........................................................................14

Performance Data: RWT034 - Full Load Heating & Cooling ...........................................................................15

Performance Data: RWT046 - Part Load Heating & Cooling ...........................................................................16

Performance Data: RWT046 - Full Load Heating & Cooling ...........................................................................17

Performance Data: RWT058 - Part Load Heating & Cooling ...........................................................................18

Performance Data: RWT058 - Full Load Heating & Cooling ...........................................................................19

Performance Data: RWT070 - Part Load Heating & Cooling ...........................................................................20

Performance Data: RWT070 - Full Load Heating & Cooling ...........................................................................21

Performance Data: RWT092 - Part Load Heating & Cooling ...........................................................................22

Performance Data: RWT092 - Full Load Heating & Cooling ...........................................................................23

Performance Data: RWT120 - Part Load Heating & Cooling ...........................................................................24

Performance Data: RWT120 - Full Load Heating & Cooling ...........................................................................25

Performance Data: RWT144 - Part Load Heating & Cooling ...........................................................................26

Performance Data: RWT144 - Full Load Heating & Cooling ...........................................................................28

Air Handler & “A” Coil Capacities ......................................................................................................................28

Dimensional Data ..............................................................................................................................................29

Dimensional Data: MPH Air Handlers & AC “A” Coils ............................................................................. 30 - 31

Electrical Data ............................................................................................................................................ 32 - 34

Controls ...................................................................................................................................................... 35 - 38

Wiring Diagrams .......................................................................................................................................39 & 40

Engineering Specifications ................................................................................................................................41

Accessories..........................................................................................................................................................42

Warranty .............................................................................................................................................................43

Revision Table ....................................................................................................................................................45

Page 3: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

2Roth RWT Series Catalog - August 2010

Product Introduction & Unit Features

The RWT Series Product Line is highly efficient, reliable and quiet operating, year-round comfort solution for your home or business.

The RWT Series Line provides exceptional operating efficiency throughout a wide range of entering water temperatures between 25°F to 110°F.

The RWT Series is manufactured in the heart of America. Pride in workmanship has been deeply embedded in the culture of our company. Every department places a high value on integrity and complete customer satisfaction. “World Class Service – Hometown Values” is far more than a slogan, it’s a way of life.

The RWT Series comes standard with powder coated steel cabinet designed for long life and extraordinary beauty. The cabinet is bolted together, rather than using screws for unmatched integral strength. The cabinet is also insulated with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature is rubber mounted Scroll compressors. These features work in concert to reduce vibration, which reduces noise.

All Coaxial Heat Exchangers are insulated to reduce corrosion, but also avoids condensation problems at low temperatures. The Bidirectional Expansion Valve delivers optimum refrigerant flow over a wide range of conditions and provides bidirectional operation without troublesome check valves. Highly advanced Copeland UltraTech® Scroll Compressor Technology deliver high efficiencies, two-stage operation, and comfort for any application.

Unit Features at a Glance• Two-StageOperationonAllModels• Non-Ozone Depleting R-410A Refrigerant• RuggedPowderCoatedSteelCabinet

Construction with Two-Tone Accent Panel• AllPanelsRemovableforEasyService• BidirectionalExpansionValve• ETLCertifiedtoUL&CSAStandards• RatedinaccordancewithISOStandards• CopperCoaxialWaterHeatExchanger• FlowSwitchProtected• FaultRetryToEliminateNuisance

Service Calls• HighEfficiencyCopelandUltraTech®

Scroll Compressor• 10YearLimitedResidentialWarranty

Optionalfeatures• Cupro-nickelheatexchanger• HotWaterGenerator(Desuperheater)

Page 4: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

3RWT Series Catalog - August 2010 Roth

Features (Hydronic air handlers):

• Multi-positionairpattern• Shipsinupflowandhorizontal

left configuration• Fieldconvertibletodownflowandhorizontal

right configuration (downflow kit required for downflow operation)

• VariablespeedG.E.ECMfanmotorwithmultiple speed taps

• Singlecoilforbothchilledwaterand hot water

• Designedfor100°Fto120°Fwaterin heating operation

• OptimizedforusewithRothwater-to-waterheat pumps

• Corrosion-proof plastic drain pan with primary and secondary drain connections

• Oversizedcoppertube/aluminumfine“A”coilfor maximum efficiency

• Coppersweatwaterconnections• Narrowwidth(22”maximum)forsmall

closet installations• Slide-outblowerassembly• Standard5-yearparts/10-yearcoilwarranty

and 5-year labor allowance*• Optionaldownflowkit• Optionalfilterrackwithstandardsize1”filters

Features(Hydronic“A”coils):

• Singlecoilforbothchilledwaterand hot water

• Designedfor100°Fto120°Fwaterin heating operation

• OptimizedforusewithRothwater-to-waterheat pumps

• Corrosion-proofplasticdrainpanwithprimaryand secondary drain connections

• Coppersweatwaterconnections• Standard10-yearcoilwarrantyand5-year

labor allowance*

*Dealer covers labor for year one.

MPSeriesMulti-PositionAirHandlers&ACSeriesUncased“A”Coils

Page 5: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

4Roth RWT Series Catalog - August 2010

Unit Performance:ISO13256-2Data-Single&DualCompressorUnitsGround Loop Heat Pump

Water-to-Water Models Single Compressor

Model Capacity

Ground Loop Heat Pump

Cooling Heating

BtuH EEr BtuH CoP

rWt026Part Load 18,200 17.7 16,200 3.1

Full Load 23,100 14.3 26,400 3.1

rWt034Part Load 26,400 17.9 25,500 3.0

Full Load 36,200 14.6 33,100 3.0

rWt046Part Load 36,700 17.4 37,300 3.1

Full Load 47,900 14.2 46,400 3.0

rWt058Part Load 40,500 19.7 37,200 3.1

Full Load 52,700 15.4 45,700 3.4

rWt070Part Load 49,900 18.4 44,800 3.0

Full Load 64,500 15.0 55,900 3.0

Water-to-Water Models Dual Compressor

rWt092Part Load 73,400 17.4 73,600 3.1

Full Load 95,800 14.2 90,200 2.9

rWt120 Nominal 108,200 17.0 100,000 3.0

rWt144 Nominal 128,000 14.7 122,800 2.6

Notes:rated in accordance with ISo Standard 13256-2 which includes Pump Penalties.Heating capacities based on 32°F ESt & 104°F ELt.Cooling capacities based on 77°F ESt & 53.6°F ELt.Entering load temperature over 120°F heating and under 45°F Cooling is not permissible.Floor heating is most generally designed for 85°F entering load temperature.

Notice:Model 144 does not meet Energy Star requirements.

Page 6: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

5RWT Series Catalog - August 2010 Roth

Unit Performance:ISO13256-2Data-Single&DualCompressorUnitsGround Water Heat Pump

Water-to-Water Models Single Compressor

Model Capacity

Ground Water Heat Pump

Cooling Heating

BtuH EEr BtuH CoP

rWt026Part Load 18,100 19.5 17,200 3.7

Full Load 25,200 18.0 29,300 3.4

rWt034Part Load 25,900 19.1 27,300 3.4

Full Load 40,200 18.6 36,300 3.2

rWt046Part Load 37,000 19.7 38,900 3.4

Full Load 51,500 17.8 50,500 3.2

rWt058Part Load 40,400 21.7 39,600 3.7

Full Load 57,600 19.4 50,700 3.4

rWt070Part Load 46,800 18.8 47,300 3.6

Full Load 70,500 16.5 61,900 3.3

Water-to-Water Models Dual Compressor

rWt092Part Load 74,100 19.7 77,800 3.4

Full Load 102,900 17.8 101,000 3.2

rWt120 Nominal 122,600 20.0 108,800 3.4

rWt144 Nominal 131,600 16.5 133,300 3.0

Notes:rated in accordance with ISo Standard 13256-2 which includes Pump Penalties.Heating capacities based on 50°F ESt & 104°F ELt.Cooling capacities based on 59°F ESt & 53.6°F ELt.Entering load temperature over 120°F heating and under 45°F Cooling is not permissible.Floor heating is most generally designed for 85°F entering load temperature.

Notice:only Models 058 & 120 meet Energy Star GWHP requirements.Model 144 does not meet Energy Star requirements.

Page 7: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

6Roth RWT Series Catalog - August 2010

Unit Nomenclature:Two-StageUnits

Roth Geothermal Heat Pumps2010 Models - Water-to-Water Two-Stage

Rev. 08JUL2010

R W T 046 A 1 1 A A A C SS

BrandR = Roth

TypeW = Water-to-Water

StagesT = Two-stage

Unit CapacityNominal MBTUH026,034,046,058,070,092,120,144

SeriesA = Current Revision

Voltage1 = 208/230 Volts, 60 Hz, 1ph RESIDENTIAL

Other OptionsSS = Stock Standard

Heat Exchanger Options (Source)C = Copper coaxN = CuNi coax

Option 3A = N/A

Option 2A = N/A

Option 1A = N/A

Hot Water Options0 = No Desuperheater1 = With Desuperheater & int. pump

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Page 8: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

7RWT Series Catalog - August 2010 Roth

Unit Nomenclature:MPHSeriesAirHandlers

MP H 048 A 1 M M 1 S R

Product SeriesMP = Multi-position air handler

TypeH = Hydronic

Unit CapacityNominal MBTUH Hydronic = 024,036,048,060

SeriesA = Current Revision

Voltage1 = 208/230 Volts, 60 Hz, 1 Ph9 = 115 Volts 60 Hz, 1 Ph

BrandR = Roth

OptionsS = Standard

Blower Options1 = ECM

Discharge Air ConfigurationM = Multi-position

Return OptionsM = Multi-position

Roth Geothermal Heat Pumps2010 Models - Hydronic Air Handler

Rev. 08JUL2010

Page 9: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

8Roth RWT Series Catalog - August 2010

Unit Nomenclature:ACSeries“A”Coils

AC H 048 A S R

Product SeriesAC = Uncased “A” Coil

TypeH = Hydronic

Unit CapacityNominal MBTUHHydronic = 024, 036, 048, 060

BrandR = Roth

OptionsS = Standard

SeriesA = Current Revision

Roth Geothermal Heat Pumps2010 Models - Hydronic A-Coil

Rev. 08JUL2010

Page 10: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

9RWT Series Catalog - August 2010 Roth

Calculations,&WaterFlowSelection

Source Water Flow SelectionProper flow rate is crucial for reliable operation of geothermal heat pumps. the performance data shows three flow rates for each entering water temperature (ESt column). the general “rule of thumb” when selecting flow rates is the following:

top flow rate: open loop systems (1.5 to 2.0 gpm per ton)Middle flow rate: Minimum closed loop system flow rate (2.25 to 2.50 gpm/ton)Bottom flow rate: Nominal (optimum) closed loop system flow rate (3.0 gpm/ton)

Although the “rule of thumb” is adequate in most areas of North America, it is important to consider the application type before applying this “rule of thumb.” Antifreeze is generally required for all closed loop (geothermal) applications. Extreme Southern u.S. locations are the only exception. open loop (well water) systems cannot use antifreeze, and must have enough flow rate in order to avoid freezing conditions at the Leaving Source Water temperature (LWt) connection.

Calculations must be made for all systems without antifreeze to deter-mine if the top flow rate is adequate to prevent LWt at or near freezing conditions. the following steps should taken in making this calculation:

Determine minimum ESt based upon your geographical area.Go to the performance data table for the heat pump model selected and look up the the Heat of Extraction (HE) at the “rule of thumb” water flow rate (GPM) and at the design Entering Load temperature (ELt).

Calculate the temperature difference (tD) based upon the HE and GPM of the model.tD = HE / (GPM x 500).Calculate the LWt.LWt = ESt - tD.

If the LWt is below 35-38°F, there is potential for freezing conditions if the flow rate or water temperature is less than ideal conditions, and the flow rate must be increased.

Example 1:ESt = 50°F, ELt = 95°F.Model rWt034, heating. Flow rate = 5 GPM. HE = 30,100 Btuh.tD = 30,100 / (5 x 500) = 12.0°FLWt = 50 - 12.0 = 38.0°FWater flow rate should be adequate under these conditions.

Example 2:ESt = 40°F, ELt = 95°F.Model rWt036, heating. Flow rate = 5 GPM. HE = 25,700 Btuh.tD = 25,700 / (5 x 500) = 10.3°FLWt = 40 - 10.3 = 29.7°FWater flow rate must be increased.

Heating Cooling

LWt = ESt - HE GPM x 500*

LWt = ESt + Hr GPM x 500*

HE = 500* x GPM x (EWt - LWt) Hr = 500* x GPM x (LWt - EWt)

*500 = Constant factor for pure water. Brine should be 485.

Heating & Cooling Calculations

CoP = Coefficient of Performance = Btu output / Btu Input Hr = total Heat of rejection, Btu/hr

DH = Desuperheater Capacity, Btu/hr KW = total Power unit Input, Kilowatts

EEr = Energy Efficiency ratio = Btu output/Watts input LWt = Leaving Source Water temperature, Fahrenheit

ESt = Entering Source Water temperature, Fahrenheit LLt = Leaving Load Water temperature, Fahrenheit

ELt = Entering Load Water temperature, Fahrenheit tC = total Cooling Capacity, Btu/hr

GPM = Water Flow, Gallons Per Minute HC = Heating Capacity, Btu/hr

HE = total Heat of Extraction, Btu/hr WPD = Water Pressure Drop, PSI & Feet of Water

Glossary

Notes:1. Desuperheater Capacity is based upon 0.4 GPM Flow per nominal ton at 90°F entering hot water temperature.2. Extrapolation data down to 25°F for heating and interpolation between ESt & GPM data is permissible.3. EWt (Entering Water temperature) is also called ESt (Entering Source temperature).4. Load flow rate is the same as the source flow rate at each of the three flow selections.

Application Notes for Performance Data

Page 11: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

10Roth RWT Series Catalog - August 2010

Performance Considerations

Guidelines For Heating Mode Operation For Water-To-Water Units Using Scroll Compressors

• • • • • • •

Acceptable Operating Conditions

45°F40°F35°F30°F25°F20°F15°F10°F

100°F

110°F

115°F

120°F

125°F

130°F

SCROLL COMPRESSOR OPERATING CONDITIONS (WATER TO WATER)HEATING MODE OPERATION

Source Entering Water Temperature

• • • • •70°F65°F60°F55°F50°F

FAILURE ZONE

Acceptable Operating Conditions

Outside Safe Operating Range

Outside Safe O

perating Range

• •

•75°F

•80°F

FAILURE ZONE

Load

Lea

ving

Wat

er Te

mpe

ratu

re

SafetyFactor

SafetyFactor

Because the water-to-water machines have become so popular for providing heated water for a multitude of uses, we’ve provided the above chart for reference.

The obvious correlation is that the warmer the Source Entering Water Temperature, the hotter the Load Leaving Water Temperature can be, to a point. R410A can only handle up to about 125°F Load Leaving Water Temperature before putting the compressor at risk.

Actual usage, and choices of heat distribution devices need to follow the acceptable operating conditions presented in the chart. If a question arises, please consult the Technical Services Department.

Page 12: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

11RWT Series Catalog - August 2010 Roth

Buffer Tanks

Virtually all water-to-water heat pumps used for hydronic applications require a buffer tank to prevent equipment short cycling, and to allow different flow rates through the water-to-water unit than through the hydronic delivery system. The following are considerations for buffer tank sizing.

• The size of the buffer tank should be determined based upon the predominant use of the water-to-water equipment (heating or cooling.

• The size of the buffer tank is based upon the lowest operating stage of the equipment. For example, a water-to-water heat pump with a two-stage compressor or two compressors may be sized for first stage capacity, reducing the size of the tank (as long as a two-stage aquastat is used).

• Pressurized buffer tanks are sized differently than non-pressurized tanks (see guidelines listed below).

Pressurized buffer tanks for predominately heating applications should be sized at one (1) U.S. gallon per 1,000 Btuh of heating capacity (10 gallons per ton may also be used) at the maximum entering source water temperature (EST) and the minimum entering load water temperature (ELT), the point at chich the water-to-water unit has the highest heating capacity, usually 50-70°F EST and 80-90°F ELT.

For predominately cooling applications, pressurized buffer tanks should be sized at one (1) U.S. gallon per 1,000 Btuh of cooling capacity (10 U.S. gallons per ton may also be used) at the minimum EST and the maximum ELT, the point at which the water-to-water unit has the highest cooling capacity, usually 50-70°F ESt and 50-60°F ELT.

Select the size of the tank based upon the larger on the calculations (heating or cooling).

Non-pressurized buffer tanks must also be sized based upon predominate use (heating or cooling) and based upon the lowest capacity stage. Requirements for storage are less according to the manufacturer of the HSS series non-pressurized buffer tank. Using the same conditions for maximum heating and cooling capacity mentioned above, on-pressurized buffer tanks require 6 U.S. gallons per ton.

Page 13: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

12Roth RWT Series Catalog - August 2010

RWT026PerformanceData:2.0Ton,PartLoadCapacity

ESt GPM PSI FtHeating Cooling

ELt HC HE KW LLt CoP DH ELt tC Hr KW LLt EEr DH

30

2.2 0.3 0.8

85 17.4 13.7 1.07 100.8 4.76 1.7

operation Not recommended

95 16.8 12.9 1.13 110.3 4.36 1.7

110 16.2 12.1 1.19 124.7 3.99 1.8

3.2 0.8 1.8

85 18.2 14.5 1.10 96.4 4.85 1.7

95 17.6 13.7 1.16 106.0 4.45 1.8

110 17.0 12.9 1.22 120.6 4.08 1.9

4.0 1.2 2.7

85 18.6 14.8 1.11 94.3 4.91 1.7

95 18.0 14.0 1.17 104.0 4.51 1.8

110 17.4 13.2 1.23 118.7 4.14 1.9

50

2.2 0.3 0.7

85 22.9 19.1 1.14 105.8 5.89 2.1 40 16.8 19.7 0.75 24.7 22.4 1.2

95 22.1 18.0 1.20 115.1 5.40 2.2 45 18.3 21.0 0.76 28.4 24.1 1.3

110 21.4 16.9 1.26 129.5 4.98 2.3 50 19.8 22.3 0.78 32.0 25.4 1.3

3.2 0.7 1.7

85 24.0 20.1 1.17 100.0 6.01 2.3 40 17.1 19.8 0.71 29.3 24.1 1.2

95 23.2 19.0 1.23 109.5 5.53 2.3 45 18.6 21.1 0.72 33.4 25.8 1.2

110 22.4 17.9 1.29 124.0 5.09 2.4 50 20.1 22.4 0.74 37.4 27.2 1.3

4.0 1.1 2.5

85 24.5 20.7 1.18 97.3 6.08 2.3 40 17.3 19.9 0.69 31.4 25.1 1.1

95 23.7 19.5 1.24 106.9 5.60 2.3 45 18.8 21.2 0.70 35.6 26.9 1.2

110 22.9 18.3 1.30 121.5 5.16 2.4 50 20.3 22.5 0.72 39.9 28.2 1.2

70

2.2 0.3 0.7

85 28.2 24.0 1.23 110.6 6.72 2.6 40 16.0 19.2 0.85 25.5 18.8 1.8

95 27.2 22.6 1.30 119.7 6.13 2.7 45 17.4 20.4 0.87 29.2 20.0 1.9

110 26.3 21.2 1.36 133.9 5.67 2.8 50 18.8 21.6 0.89 32.9 21.1 1.9

3.2 0.7 1.6

85 29.5 25.3 1.26 103.4 6.86 2.7 40 16.3 19.3 0.81 29.8 20.1 1.8

95 28.5 24.0 1.33 112.8 6.28 2.8 45 17.7 20.5 0.83 33.9 21.3 1.8

110 27.5 22.5 1.40 127.2 5.76 2.9 50 19.1 21.7 0.85 38.1 22.5 1.8

4.0 1.0 2.4

85 30.1 26.0 1.27 100.1 6.94 2.9 40 16.5 19.4 0.79 31.8 20.9 1.7

95 29.1 24.6 1.34 109.6 6.36 2.9 45 17.9 20.6 0.80 36.1 22.4 1.7

110 28.1 23.0 1.41 124.1 5.84 3.0 50 19.3 21.8 0.82 40.4 23.5 1.8

90

2.2 0.3 0.7

85 32.7 28.3 1.30 114.7 7.37 3.1 40 14.9 18.7 1.07 26.5 13.9 2.4

95 31.6 26.8 1.37 123.7 6.76 3.1 45 16.2 19.9 1.09 30.3 14.9 2.5

110 30.5 25.1 1.44 137.7 6.21 3.2 50 17.5 21.1 1.11 34.1 15.8 2.6

3.2 0.6 1.5

85 34.3 30.0 1.34 106.4 7.50 3.2 40 15.2 18.8 1.01 30.5 15.1 2.4

95 33.1 28.4 1.41 115.7 6.88 3.3 45 16.5 20.0 1.03 34.7 16.0 2.4

110 32.0 26.6 1.48 130.0 6.34 3.3 50 17.8 21.2 1.05 38.9 17.0 2.4

4.0 1.0 2.2

85 35.0 30.8 1.35 102.5 7.60 3.3 40 15.4 18.9 0.98 32.3 15.7 2.2

95 33.8 29.1 1.42 111.9 6.97 3.4 45 16.7 20.1 1.00 36.7 16.7 2.3

110 32.7 27.3 1.49 126.4 6.43 3.5 50 18.0 21.3 1.02 41.0 17.7 2.4

110

2.2 0.3 0.7

operation Not recommended

40 13.7 18.1 1.29 27.5 10.6 3.1

45 14.9 19.2 1.31 31.5 11.4 3.2

50 16.1 20.4 1.34 35.4 12.0 3.3

3.2 0.6 1.5

40 13.9 18.1 1.22 31.3 11.4 3.0

45 15.1 19.3 1.24 35.6 12.2 3.1

50 16.3 20.5 1.27 39.8 12.8 3.2

4.0 0.9 2.2

40 14.1 18.2 1.18 33.0 12.0 2.9

45 15.3 19.4 1.20 37.4 12.8 3.0

50 16.5 20.6 1.23 41.8 13.4 3.1

* See Page 9 for Application Notes

Page 14: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

13RWT Series Catalog - August 2010 Roth

RWT026PerformanceData:2.0Ton,FullLoadCapacity

EST GPM PSI FTHeating Cooling

ELT HC HE KW LLT COP DH ELT TC HR KW LLT EER DH

30

3.3 1.4 3.1

85 26.2 19.2 2.02 100.9 3.80 2.5

operation Not recommended

95 25.3 18.1 2.13 110.3 3.48 2.6

110 24.4 17.0 2.23 124.8 3.21 2.7

4.7 2.5 5.8

85 27.4 20.3 2.07 96.7 3.88 2.6

95 26.5 19.1 2.18 106.3 3.56 2.7

110 25.6 18.0 2.29 120.9 3.28 2.8

6.0 4.1 9.4

85 28.1 20.8 2.09 94.4 3.94 2.6

95 27.1 19.6 2.20 104.0 3.61 2.7

110 26.2 18.4 2.31 118.7 3.32 2.8

50

3.3 1.3 2.9

85 34.3 26.8 2.15 105.8 4.67 3.2 40 24.2 29.3 1.39 25.3 17.4 1.8

95 33.1 25.4 2.26 115.1 4.29 3.3 45 26.3 31.2 1.42 29.1 18.5 1.8

110 32.0 23.8 2.37 129.4 3.96 3.4 50 28.4 33.1 1.45 32.8 19.6 1.9

4.7 2.3 5.4

85 35.8 28.3 2.19 100.2 4.79 3.4 40 24.6 29.5 1.33 29.5 18.5 1.7

95 34.6 26.8 2.31 109.7 4.39 3.5 45 26.8 31.4 1.35 33.6 19.9 1.7

110 33.4 25.1 2.42 124.2 4.04 3.6 50 28.9 33.3 1.38 37.7 20.9 1.8

6.0 3.8 8.7

85 36.7 29.1 2.21 97.2 4.87 3.5 40 24.9 29.6 1.28 31.7 19.5 1.6

95 35.4 27.5 2.33 106.8 4.45 3.5 45 27.1 31.5 1.30 36.0 20.9 1.7

110 34.2 25.8 2.44 121.4 4.11 3.6 50 29.3 33.4 1.33 40.2 22.0 1.7

70

3.3 1.3 2.9

85 42.1 34.1 2.31 110.5 5.34 3.9 40 22.8 28.9 1.72 26.2 13.3 2.6

95 40.7 32.3 2.43 119.7 4.91 4.0 45 24.8 30.7 1.75 30.0 14.2 2.7

110 39.2 30.3 2.55 133.8 4.50 4.1 50 26.8 32.6 1.79 33.8 15.0 2.7

4.7 2.3 5.2

85 44.0 36.1 2.36 103.7 5.46 4.1 40 23.2 29.1 1.63 30.1 14.2 2.5

95 42.6 34.1 2.49 113.1 5.01 4.2 45 25.2 30.9 1.66 34.3 15.2 2.6

110 41.1 32.0 2.61 127.5 4.61 4.3 50 27.2 32.8 1.70 38.4 16.0 2.6

6.0 3.6 8.3

85 45.1 37.0 2.38 100.0 5.55 4.3 40 23.5 29.2 1.57 32.2 15.0 2.4

95 43.6 35.0 2.51 109.5 5.09 4.4 45 25.5 31.0 1.60 36.5 15.9 2.4

110 42.0 32.8 2.63 124.0 4.68 4.5 50 27.5 32.9 1.64 40.8 16.8 2.5

90

3.3 1.2 2.7

85 49.0 40.7 2.46 114.7 5.84 4.6 40 20.8 28.0 2.14 27.4 9.7 3.4

95 47.4 38.5 2.59 123.7 5.36 4.7 45 22.6 29.8 2.18 31.3 10.4 3.5

110 45.7 36.1 2.72 137.7 4.92 4.8 50 24.4 31.6 2.23 35.2 10.9 3.6

4.7 2.1 4.8

85 51.3 42.9 2.52 106.8 5.96 4.8 40 21.2 28.2 2.03 31.0 10.4 3.3

95 49.6 40.6 2.65 116.1 5.48 4.9 45 23.0 30.0 2.07 35.2 11.1 3.4

110 47.8 38.1 2.78 130.3 5.04 5.0 50 24.8 31.8 2.12 39.4 11.7 3.4

6.0 3.3 7.7

85 52.5 44.1 2.53 102.5 6.08 5.0 40 21.4 28.3 1.96 32.9 10.9 3.1

95 50.8 41.7 2.67 111.9 5.57 5.1 45 23.3 30.1 2.00 37.2 11.7 3.2

110 49.0 39.1 2.80 126.3 5.13 5.2 50 25.2 31.9 2.04 41.6 12.4 3.3

110

3.3 1.1 2.6

operation Not recommended

40 18.3 26.7 2.57 28.9 7.1 4.2

45 19.9 28.4 2.62 32.9 7.6 4.3

50 21.5 30.1 2.68 37.0 8.0 4.4

4.7 2.1 4.8

40 18.7 26.9 2.43 32.0 7.7 4.1

45 20.3 28.6 2.48 36.4 8.2 4.2

50 21.9 30.3 2.53 40.7 8.7 4.3

6.0 3.3 7.6

40 18.9 27.0 2.36 33.7 8.0 3.9

45 20.5 28.7 2.40 38.2 8.5 4.0

50 22.1 30.4 2.45 42.6 9.0 4.1

* See Page 9 for Application Notes

Page 15: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

14Roth RWT Series Catalog - August 2010

RWT034PerformanceData:3.0Ton,PartLoadCapacity

ESt GPM PSI FtHeating Cooling

ELt HC HE KW LLt CoP DH ELt tC Hr KW LLt EEr DH

30

3.4 0.5 1.1

85 21.6 16.4 1.51 97.7 4.19 2.5

operation Not recommended

95 20.9 15.5 1.59 107.3 3.85 2.6

110 20.2 14.6 1.67 121.9 3.54 2.7

4.7 0.9 2.0

85 22.6 17.3 1.55 94.6 4.27 2.6

95 21.8 16.3 1.63 104.3 3.92 2.7

110 21.1 15.3 1.71 119.0 3.62 2.7

6.0 1.4 3.3

85 23.1 17.7 1.56 92.7 4.34 2.6

95 22.3 16.7 1.64 102.4 3.98 2.7

110 21.5 15.7 1.72 117.2 3.66 2.8

50

3.4 0.4 1.0

85 28.4 22.8 1.61 101.7 5.17 3.3 40 24.6 28.5 0.96 25.5 25.6 1.8

95 27.4 21.5 1.70 111.1 4.72 3.3 45 26.7 30.3 0.98 29.3 27.2 1.8

110 26.5 20.2 1.78 125.6 4.36 2.8 50 28.8 32.1 1.00 33.1 28.8 1.9

4.7 0.8 1.9

85 29.5 24.0 1.65 97.6 5.24 3.4 40 25.0 28.7 0.91 29.4 27.5 1.7

95 28.5 22.6 1.74 107.1 4.80 3.5 45 27.2 30.5 0.93 33.4 29.3 1.7

110 27.5 21.2 1.83 121.7 4.40 3.6 50 29.4 32.3 0.95 37.5 31.0 1.8

6.0 1.3 3.1

85 30.2 24.6 1.66 95.1 5.33 3.5 40 25.3 28.8 0.88 31.6 28.8 1.6

95 29.2 23.2 1.75 104.7 4.89 3.5 45 27.5 30.6 0.90 35.8 30.6 1.7

110 28.2 21.8 1.84 119.4 4.49 3.7 50 29.7 32.4 0.92 40.1 32.3 1.7

70

3.4 0.4 1.0

85 34.8 28.8 1.73 105.5 5.89 4.0 40 23.2 27.6 1.18 26.4 19.7 2.6

95 33.6 27.3 1.82 114.8 5.41 4.1 45 25.2 29.4 1.20 30.2 21.0 2.7

110 32.5 25.6 1.91 129.1 4.99 4.2 50 27.2 31.2 1.23 34.0 22.1 2.7

4.7 0.8 1.8

85 36.3 30.3 1.77 100.4 6.01 4.2 40 23.5 27.8 1.12 30.0 21.0 2.5

95 35.0 28.7 1.86 109.9 5.51 4.3 45 25.6 29.6 1.14 34.1 22.5 2.6

110 33.8 26.9 1.95 124.4 5.08 4.4 50 27.6 31.4 1.16 38.3 23.8 2.6

6.0 1.3 2.9

85 37.1 31.2 1.78 97.4 6.11 4.3 40 23.8 27.9 1.08 32.1 22.0 2.3

95 35.8 29.5 1.88 106.9 5.58 4.3 45 25.9 29.7 1.10 36.4 23.6 2.5

110 34.6 27.6 1.97 121.5 5.15 4.5 50 28.0 31.5 1.12 40.7 25.0 2.5

90

3.4 0.4 1.0

85 40.7 34.5 1.84 108.9 6.48 4.6 40 21.2 26.3 1.38 27.5 15.4 3.4

95 39.4 32.6 1.94 118.2 5.95 4.7 45 23.1 28.0 1.41 31.4 16.4 3.5

110 38.0 30.6 2.04 132.4 5.46 4.8 50 24.9 29.7 1.44 35.4 17.3 3.6

4.7 0.7 1.7

85 42.4 36.3 1.88 103.0 6.61 4.8 40 21.6 26.4 1.33 30.8 16.2 3.3

95 41.0 34.3 1.98 112.4 6.07 5.0 45 23.5 28.1 1.35 35.0 17.4 3.3

110 39.5 32.2 2.08 126.8 5.56 5.0 50 25.4 29.8 1.38 39.2 18.4 3.5

6.0 1.2 2.7

85 43.4 37.2 1.90 99.5 6.69 5.0 40 21.9 26.5 1.28 32.7 17.1 3.2

95 42.0 35.2 2.00 109.0 6.15 5.1 45 23.8 28.2 1.30 37.1 18.3 3.2

110 40.5 33.0 2.10 123.5 5.65 5.2 50 25.7 29.9 1.33 41.4 19.3 3.4

110

3.4 0.4 0.9

operation Not recommended

40 18.9 24.9 1.71 28.9 11.1 4.3

45 20.6 26.5 1.74 32.9 11.8 4.4

50 22.2 28.1 1.78 36.9 12.5 4.5

4.7 0.7 1.7

40 19.3 25.0 1.63 31.8 11.8 4.2

45 21.0 26.6 1.66 36.1 12.7 4.3

50 22.7 28.2 1.70 40.3 13.4 4.4

6.0 1.2 2.7

40 19.5 25.1 1.57 33.5 12.4 3.9

45 21.2 26.7 1.60 37.9 13.3 4.1

50 22.9 28.3 1.64 42.4 14.0 4.2

* See Page 9 for Application Notes

Page 16: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

15RWT Series Catalog - August 2010 Roth

RWT034PerformanceData:3.0Ton,FullLoadCapacity

ESt GPM PSI FtHeating Cooling

ELt HC HE KW LLt CoP DH ELt tC Hr KW LLt EEr DH

30

5.0 1.0 2.3

85 32.3 22.5 2.83 97.9 3.34 3.8

operation Not recommended

95 31.2 21.2 2.97 107.5 3.08 3.9

110 30.1 19.9 3.13 122.0 2.82 4.0

7.0 1.9 4.5

85 33.8 23.6 2.90 94.7 3.41 3.9

95 32.6 22.3 3.04 104.3 3.14 4.0

110 31.5 21.0 3.20 119.0 2.88 4.1

9.0 3.2 7.4

85 34.6 24.3 2.92 92.7 3.47 3.9

95 33.4 22.9 3.07 102.4 3.19 4.1

110 32.3 21.5 3.23 117.2 2.93 4.2

50

5.0 0.9 2.2

85 42.4 31.8 3.03 102.0 4.10 4.9 40 36.8 44.1 1.92 25.3 19.2 2.7

95 41.0 30.1 3.18 111.4 3.78 5.0 45 40.0 46.9 1.96 29.0 20.4 2.7

110 39.5 28.2 3.35 125.8 3.45 4.1 50 43.2 49.7 2.00 32.7 21.6 2.8

7.0 1.8 4.2

85 44.1 33.5 3.10 97.6 4.17 5.1 40 37.4 44.3 1.84 29.3 20.3 2.5

95 42.7 31.7 3.25 107.2 3.85 5.2 45 40.7 47.1 1.87 33.4 21.8 2.6

110 41.2 29.7 3.42 121.8 3.53 5.4 50 43.9 49.9 1.91 37.5 23.0 2.7

9.0 3.0 6.8

85 45.3 34.5 3.12 95.1 4.25 5.2 40 37.9 44.5 1.77 31.6 21.4 2.4

95 43.8 32.6 3.28 104.7 3.91 5.3 45 41.2 47.3 1.80 35.8 22.9 2.5

110 42.2 30.6 3.45 119.4 3.58 5.5 50 44.5 50.2 1.84 40.1 24.2 2.5

70

5.0 0.9 2.2

85 51.9 40.7 3.25 105.8 4.68 5.9 40 34.7 43.2 2.36 26.1 14.7 3.9

95 50.2 38.5 3.41 115.1 4.31 6.1 45 37.7 45.9 2.40 29.9 15.7 4.0

110 48.4 36.1 3.59 129.4 3.95 6.2 50 40.7 48.7 2.45 33.7 16.6 4.1

7.0 1.7 4.0

85 54.2 42.8 3.32 100.5 4.78 6.2 40 35.3 43.4 2.24 29.9 15.8 3.7

95 52.4 40.5 3.49 110.0 4.40 6.4 45 38.4 46.1 2.28 34.0 16.8 3.9

110 50.5 38.0 3.67 124.4 4.03 6.5 50 41.5 48.9 2.33 38.1 17.8 3.9

9.0 2.8 6.5

85 55.5 44.1 3.35 97.3 4.85 6.4 40 35.7 43.5 2.16 32.1 16.5 3.5

95 53.7 41.7 3.52 106.9 4.47 6.5 45 38.8 46.3 2.20 36.4 17.6 3.7

110 51.8 39.1 3.70 121.5 4.10 6.7 50 41.9 49.1 2.25 40.7 18.6 3.8

90

5.0 0.9 2.0

85 60.6 48.8 3.46 109.2 5.13 6.8 40 31.7 41.7 2.90 27.3 10.9 5.1

95 58.6 46.1 3.63 118.4 4.73 7.0 45 34.5 44.3 2.95 31.2 11.7 5.2

110 56.5 43.3 3.82 132.6 4.33 7.1 50 37.2 47.0 3.01 35.1 12.4 5.4

7.0 1.6 3.7

85 63.3 51.3 3.54 103.1 5.24 7.2 40 32.3 41.8 2.75 30.8 11.8 4.9

95 61.2 48.5 3.72 112.5 4.82 7.4 45 35.1 44.5 2.80 35.0 12.5 5.0

110 59.0 45.5 3.91 126.9 4.42 7.5 50 37.9 47.2 2.86 39.2 13.3 5.2

9.0 2.6 6.1

85 64.8 52.8 3.57 99.4 5.32 7.5 40 32.6 42.0 2.65 32.8 12.3 4.7

95 62.7 49.9 3.75 108.9 4.90 7.6 45 35.5 44.7 2.70 37.1 13.2 4.8

110 60.5 46.8 3.95 123.4 4.49 7.8 50 38.3 47.4 2.76 41.5 13.9 5.0

110

5.0 0.8 1.9

operation Not recommended

40 27.9 39.6 3.53 28.8 7.9 6.3

45 30.3 42.1 3.60 32.9 8.4 6.5

50 32.7 44.6 3.68 36.9 8.9 6.7

7.0 1.6 3.7

40 28.3 39.8 3.36 31.9 8.4 6.1

45 30.8 42.3 3.42 36.2 9.0 6.3

50 33.3 44.9 3.49 40.5 9.5 6.4

9.0 2.6 6.0

40 28.7 40.0 3.24 33.6 8.9 5.8

45 31.2 42.5 3.30 38.1 9.5 6.0

50 33.7 45.1 3.37 42.5 10.0 6.2

* See Page 9 for Application Notes

Page 17: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

16Roth RWT Series Catalog - August 2010

RWT046PerformanceData:4.0Ton,PartLoadCapacity

ESt GPM PSI FtHeating Cooling

ELt HC HE KW LLt CoP DH ELt tC Hr KW LLt EEr DH

30

4.8 0.6 1.4

85 29.0 22.1 2.02 97.1 4.21 3.5

operation Not recommended

95 28.0 20.8 2.13 106.7 3.85 3.7

110 27.1 19.6 2.23 121.3 3.56 3.8

6.8 1.2 2.8

85 30.3 23.2 2.07 93.9 4.29 3.7

95 29.3 21.9 2.18 103.6 3.94 3.8

110 28.3 20.6 2.29 118.3 3.62 3.9

8.7 2.0 4.6

85 31.1 23.9 2.09 92.1 4.36 3.7

95 30.0 22.5 2.20 101.9 4.00 3.9

110 29.0 21.2 2.31 116.7 3.68 3.9

50

4.8 0.6 1.3

85 38.1 30.8 2.16 100.9 5.17 4.6 40 34.8 40.3 1.39 27.6 25.0 2.5

95 36.9 29.1 2.27 110.4 4.76 4.8 45 37.8 42.9 1.42 31.5 26.6 2.6

110 35.6 27.3 2.38 124.8 4.38 4.9 50 40.8 45.5 1.45 35.4 28.1 2.7

6.8 1.1 2.6

85 39.9 32.3 2.20 96.7 5.31 4.8 40 35.3 40.5 1.33 30.9 26.5 2.4

95 38.6 30.6 2.32 106.4 4.87 5.0 45 38.4 43.1 1.35 35.2 28.4 2.5

110 37.2 28.7 2.43 120.9 4.49 5.1 50 41.5 45.7 1.38 39.4 30.1 2.5

8.7 1.8 4.3

85 40.8 33.3 2.22 94.4 5.38 4.9 40 35.8 40.7 1.28 32.9 28.0 2.3

95 39.5 31.5 2.34 104.1 4.95 5.0 45 38.9 43.3 1.30 37.3 29.9 2.3

110 38.1 29.5 2.46 118.8 4.54 5.2 50 42.0 45.9 1.33 41.7 31.6 2.4

70

4.8 0.6 1.3

85 47.2 39.3 2.32 104.7 5.96 5.7 40 32.7 39.2 1.72 28.3 19.0 3.7

95 45.7 37.2 2.44 114.0 5.49 5.8 45 35.6 41.7 1.75 32.3 20.3 3.7

110 44.1 34.9 2.56 128.4 5.05 6.0 50 38.4 44.2 1.79 36.3 21.5 3.9

6.8 1.1 2.5

85 49.4 41.5 2.37 99.5 6.11 6.0 40 33.3 39.4 1.63 31.5 20.4 3.5

95 47.8 39.2 2.50 109.1 5.60 6.1 45 36.2 41.9 1.66 35.7 21.8 3.7

110 46.1 36.8 2.62 123.6 5.16 6.2 50 39.1 44.4 1.70 40.0 23.0 3.7

8.7 1.8 4.1

85 50.5 42.6 2.39 96.6 6.19 6.1 40 33.7 39.6 1.57 33.3 21.5 3.3

95 48.9 40.3 2.52 106.2 5.69 6.3 45 36.6 42.1 1.60 37.8 22.9 3.5

110 47.2 37.8 2.64 120.9 5.24 6.4 50 39.5 44.6 1.64 42.2 24.1 3.6

90

4.8 0.5 1.2

85 56.1 47.8 2.47 108.4 6.65 6.7 40 29.8 37.1 2.03 29.4 14.7 4.8

95 54.3 45.2 2.60 117.6 6.12 6.8 45 32.4 39.5 2.07 33.4 15.7 5.0

110 52.4 42.4 2.73 131.8 5.62 7.0 50 35.0 41.9 2.12 37.5 16.5 5.1

6.8 1.0 2.3

85 58.6 50.5 2.53 102.2 6.79 7.0 40 30.3 37.3 1.93 32.2 15.7 4.6

95 56.7 47.7 2.66 111.7 6.25 7.2 45 33.0 39.7 1.97 36.5 16.8 4.8

110 54.7 44.8 2.79 126.1 5.74 7.4 50 35.6 42.1 2.01 40.9 17.7 4.9

8.7 1.6 3.8

85 60.1 51.9 2.54 98.8 6.93 7.3 40 30.7 37.5 1.87 33.9 16.4 4.5

95 58.1 49.0 2.68 108.4 6.35 7.4 45 33.4 39.9 1.90 38.4 17.6 4.6

110 56.0 46.0 2.81 122.9 5.84 7.6 50 36.1 42.3 1.94 42.9 18.6 4.7

110

4.8 0.5 1.2

operation Not recommended

40 26.2 35.0 2.57 30.6 10.2 5.9

45 28.5 37.2 2.62 34.8 10.9 6.1

50 30.8 39.4 2.68 39.0 11.5 6.3

6.8 1.0 2.3

40 26.7 35.1 2.44 33.2 10.9 5.7

45 29.0 37.3 2.49 37.6 11.7 5.9

50 31.3 39.5 2.54 42.0 12.3 6.1

8.7 1.6 3.7

40 26.9 35.3 2.36 34.7 11.4 5.5

45 29.3 37.5 2.40 39.2 12.2 5.7

50 31.6 39.8 2.45 43.7 12.9 5.9

* See Page 9 for Application Notes

Page 18: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

17RWT Series Catalog - August 2010 Roth

RWT046PerformanceData:4.0Ton,FullLoadCapacity

ESt GPM PSI FtHeating Cooling

ELt HC HE KW LLt CoP DH ELt tC Hr KW LLt EEr DH

30

7.2 1.3 3.1

85 43.5 30.1 3.79 97.1 3.36 5.3

operation Not recommended

95 42.1 28.5 3.98 106.7 3.10 5.5

110 40.6 26.7 4.19 121.3 2.84 5.7

10.1 2.7 6.2

85 45.4 31.7 3.87 94.0 3.44 5.5

95 43.9 30.0 4.07 103.7 3.16 5.7

110 42.3 28.1 4.28 118.4 2.90 5.9

13.0 4.4 10.2

85 46.5 32.7 3.91 92.2 3.48 5.6

95 45.0 30.9 4.11 101.9 3.21 5.8

110 43.4 29.0 4.32 116.7 2.94 5.9

50

7.2 1.3 2.9

85 57.0 42.9 4.04 100.8 4.13 6.9 40 51.7 62.3 2.79 27.5 18.5 3.8

95 55.1 40.6 4.24 110.3 3.81 7.1 45 56.2 66.2 2.84 31.5 19.8 3.9

110 53.1 38.1 4.46 124.8 3.49 7.3 50 60.7 70.2 2.90 35.4 20.9 4.0

10.1 2.5 5.8

85 59.6 45.3 4.13 96.8 4.23 7.2 40 52.6 62.5 2.64 31.0 19.9 3.6

95 57.6 42.8 4.34 106.4 3.89 7.4 45 57.2 66.5 2.69 35.2 21.3 3.7

110 55.6 40.1 4.56 121.0 3.57 7.6 50 61.8 70.5 2.75 39.4 22.5 3.8

13.0 4.1 9.4

85 61.0 46.5 4.17 94.4 4.29 7.3 40 53.2 62.8 2.55 32.9 20.9 3.4

95 59.0 44.0 4.38 104.1 3.95 7.5 45 57.9 66.8 2.60 37.3 22.3 3.5

110 56.9 41.3 4.61 118.8 3.62 7.7 50 62.5 70.8 2.66 41.7 23.5 3.6

70

7.2 1.3 2.9

85 69.9 54.9 4.34 104.4 4.72 8.4 40 48.7 61.0 3.43 28.3 14.2 5.5

95 67.6 51.9 4.56 113.8 4.34 8.6 45 53.0 64.9 3.49 32.2 15.2 5.6

110 65.2 48.7 4.80 128.1 3.98 8.8 50 57.2 68.8 3.57 36.2 16.0 5.8

10.1 2.4 5.6

85 73.0 57.8 4.44 99.5 4.82 8.8 40 49.7 61.3 3.25 31.5 15.3 5.3

95 70.6 54.6 4.67 109.0 4.43 9.0 45 54.0 65.2 3.31 35.8 16.3 5.5

110 68.1 51.2 4.91 123.5 4.06 9.2 50 58.3 69.1 3.38 40.0 17.3 5.6

13.0 3.9 9.0

85 74.8 59.5 4.48 96.5 4.89 9.0 40 50.2 61.6 3.14 33.3 16.0 5.0

95 72.3 56.2 4.71 106.1 4.50 9.3 45 54.6 65.5 3.20 37.7 17.1 5.2

110 69.8 52.7 4.95 120.7 4.13 9.5 50 58.9 69.4 3.27 42.1 18.0 5.4

90

7.2 1.2 2.7

85 81.6 65.7 4.61 107.7 5.19 9.7 40 44.6 58.9 4.18 29.3 10.7 7.2

95 78.9 62.1 4.85 116.9 4.77 9.9 45 48.5 62.6 4.26 33.3 11.4 7.4

110 76.1 58.3 5.10 131.1 4.37 10.1 50 52.4 66.4 4.35 37.4 12.1 7.6

10.1 2.2 5.1

85 85.2 69.2 4.73 101.9 5.28 10.2 40 45.3 59.1 3.97 32.3 11.4 6.9

95 82.4 65.4 4.97 111.3 4.86 10.5 45 49.3 62.9 4.04 36.6 12.2 7.1

110 79.5 61.4 5.23 125.7 4.45 10.7 50 53.2 66.7 4.13 40.9 12.9 7.3

13.0 3.6 8.4

85 87.3 71.3 4.77 98.4 5.36 10.6 40 45.9 59.4 3.83 33.9 12.0 6.7

95 84.4 67.3 5.01 108.0 4.94 10.8 45 49.9 63.2 3.90 38.3 12.8 6.8

110 81.5 63.2 5.27 122.5 4.53 11.0 50 53.9 67.0 3.99 42.8 13.5 7.0

110

7.2 1.1 2.6

operation Not recommended

40 39.1 56.0 5.14 30.6 7.6 8.9

45 42.5 59.6 5.24 34.8 8.1 9.2

50 45.9 63.2 5.35 38.9 8.6 9.4

10.1 2.2 5.1

40 39.8 56.4 4.88 33.2 8.2 8.6

45 43.3 60.0 4.97 37.6 8.7 8.9

50 46.7 63.6 5.08 42.0 9.2 9.1

13.0 3.6 8.2

40 40.3 56.6 4.71 34.6 8.6 8.2

45 43.8 60.2 4.80 39.2 9.1 8.5

50 47.3 63.8 4.91 43.7 9.6 8.8

* See Page 9 for Application Notes

Page 19: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

18Roth RWT Series Catalog - August 2010

RWT058PerformanceData:5.0Ton,PartLoadCapacity

ESt GPM PSI FtHeating Cooling

ELt HC HE KW LLt CoP DH ELt tC Hr KW LLt EEr DH

30

5.6 0.8 1.9

85 31.7 23.9 2.22 96.3 4.18 4.0

operation Not recommended

95 30.6 22.5 2.34 105.9 3.83 4.1

110 29.6 21.2 2.46 120.6 3.53 4.2

7.8 1.6 3.7

85 33.0 25.1 2.28 93.5 4.24 4.1

95 31.9 23.7 2.40 103.2 3.89 4.2

110 30.8 22.3 2.52 117.9 3.58 4.3

10.1 2.8 6.4

85 33.9 25.9 2.30 91.7 4.32 4.1

95 32.7 24.5 2.42 101.5 3.96 4.3

110 31.6 22.9 2.54 116.3 3.65 4.4

50

5.6 0.8 1.8

85 41.8 33.7 2.36 99.9 5.19 5.2 40 37.9 43.6 1.39 24.2 27.3 2.8

95 40.5 31.9 2.49 109.5 4.77 5.3 45 41.2 46.4 1.42 27.8 29.0 2.9

110 39.0 29.9 2.61 123.9 4.38 5.4 50 44.5 49.2 1.45 31.5 30.7 3.0

7.8 1.5 3.4

85 43.6 35.4 2.42 96.2 5.28 5.4 40 38.5 43.8 1.33 28.7 29.0 2.7

95 42.2 33.5 2.55 105.8 4.85 5.5 45 41.9 46.6 1.35 32.7 31.0 2.8

110 40.7 31.4 2.68 120.4 4.45 5.7 50 45.2 49.4 1.38 36.7 32.8 2.8

10.1 2.6 5.9

85 44.7 36.5 2.44 93.9 5.37 5.5 40 39.0 44.0 1.28 31.0 30.5 2.6

95 43.3 34.5 2.57 103.6 4.94 5.6 45 42.4 46.8 1.30 35.3 32.6 2.6

110 41.7 32.3 2.70 118.3 4.53 5.8 50 45.8 49.6 1.33 39.5 34.4 2.7

70

5.6 0.8 1.8

85 52.3 43.6 2.54 103.7 6.03 6.4 40 33.1 39.3 1.61 26.2 20.6 4.1

95 50.6 41.2 2.68 113.1 5.53 6.6 45 36.0 41.8 1.64 30.0 22.0 4.2

110 48.8 38.6 2.81 127.4 5.09 6.7 50 38.9 44.3 1.68 33.8 23.2 4.4

7.8 1.4 3.3

85 54.6 45.8 2.61 99.0 6.13 6.7 40 33.7 39.5 1.52 30.1 22.2 4.0

95 52.8 43.3 2.75 108.5 5.63 6.9 45 36.7 42.0 1.55 34.2 23.7 4.1

110 50.9 40.6 2.89 123.1 5.16 7.0 50 39.6 44.5 1.58 38.4 25.1 4.2

10.1 2.4 5.7

85 55.9 47.2 2.63 96.1 6.23 6.9 40 34.1 39.7 1.47 32.2 23.2 3.8

95 54.1 44.6 2.76 105.7 5.74 7.1 45 37.1 42.2 1.50 36.5 24.7 3.9

110 52.2 41.8 2.91 120.3 5.26 7.3 50 40.1 44.7 1.53 40.8 26.2 4.0

90

5.6 0.7 1.7

85 62.7 53.5 2.71 107.4 6.78 7.6 40 32.0 39.4 2.03 26.7 15.8 5.4

95 60.6 50.6 2.84 116.6 6.25 7.8 45 34.8 41.9 2.07 30.5 16.8 5.5

110 58.5 47.5 2.99 130.9 5.73 7.9 50 37.6 44.4 2.12 34.3 17.7 5.7

7.8 1.3 3.1

85 65.4 56.3 2.76 101.8 6.94 8.0 40 32.6 39.6 1.93 30.4 16.9 5.2

95 63.2 53.2 2.90 111.2 6.39 8.2 45 35.4 42.1 1.97 34.6 18.0 5.4

110 61.0 49.9 3.05 125.6 5.86 8.4 50 38.2 44.6 2.01 38.8 19.0 5.5

10.1 2.3 5.2

85 67.0 58.0 2.79 98.3 7.04 8.3 40 32.9 39.8 1.87 32.4 17.6 4.9

95 64.8 54.8 2.93 107.8 6.48 8.5 45 35.8 42.3 1.90 36.8 18.8 5.2

110 62.5 51.4 3.08 122.4 5.95 8.6 50 38.7 44.9 1.94 41.1 20.0 5.3

110

5.6 0.7 1.6

operation Not recommended

40 28.3 37.1 2.57 28.2 11.0 6.6

45 30.8 39.5 2.62 32.2 11.8 6.8

50 33.3 41.9 2.68 36.1 12.4 7.1

7.8 1.3 3.1

40 28.8 37.3 2.43 31.5 11.9 6.4

45 31.3 39.7 2.48 35.8 12.6 6.6

50 33.8 42.1 2.53 40.1 13.4 6.8

10.1 2.2 5.2

40 29.2 37.5 2.36 33.3 12.4 6.1

45 31.7 39.9 2.40 37.7 13.2 6.4

50 34.2 42.3 2.45 42.1 14.0 6.5

* See Page 9 for Application Notes

Page 20: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

19RWT Series Catalog - August 2010 Roth

RWT058PerformanceData:5.0Ton,FullLoadCapacity

ESt GPM PSI FtHeating Cooling

ELt HC HE KW LLt CoP DH ELt tC Hr KW LLt EEr DH

30

8.3 1.8 4.2

85 47.5 32.9 4.18 96.4 3.33 6.0

operation Not recommended

95 46.0 31.1 4.39 106.1 3.07 6.1

110 44.4 29.1 4.62 120.7 2.82 6.3

11.7 3.6 8.4

85 49.6 34.7 4.27 93.5 3.40 6.1

95 48.0 32.8 4.49 103.2 3.13 6.3

110 46.3 30.7 4.72 117.9 2.87 6.5

15.0 6.0 13.8

85 50.9 35.6 4.31 91.8 3.46 6.2

95 49.2 33.7 4.53 101.6 3.18 6.4

110 47.4 31.6 4.76 116.3 2.92 6.6

50

8.3 1.7 3.9

85 62.3 46.8 4.44 100.0 4.11 7.7 40 56.6 67.2 2.79 24.3 20.3 4.2

95 60.2 44.2 4.67 109.5 3.78 7.9 45 61.5 71.5 2.84 27.9 21.7 4.3

110 58.1 41.5 4.91 124.0 3.47 8.1 50 66.4 75.8 2.90 31.6 22.9 4.4

11.7 3.4 7.8

85 65.0 49.3 4.55 96.1 4.19 8.0 40 57.6 67.6 2.64 28.6 21.8 4.0

95 62.9 46.6 4.78 105.8 3.86 8.2 45 62.6 71.9 2.69 32.6 23.3 4.1

110 60.7 43.7 5.03 120.4 3.54 8.5 50 67.6 76.2 2.75 36.6 24.6 4.2

15.0 5.5 12.8

85 66.6 50.7 4.59 93.9 4.25 8.2 40 58.2 67.9 2.55 31.0 22.8 3.8

95 64.4 47.9 4.82 103.6 3.91 8.4 45 63.3 72.2 2.60 35.3 24.4 3.9

110 62.1 44.9 5.07 118.3 3.59 8.6 50 68.3 76.6 2.66 39.5 25.7 4.0

70

8.3 1.7 3.9

85 76.3 59.9 4.78 103.4 4.68 9.4 40 49.6 61.6 3.32 26.2 14.9 6.1

95 73.8 56.6 5.02 112.8 4.31 9.6 45 53.9 65.5 3.38 30.0 16.0 6.3

110 71.2 53.1 5.28 127.2 3.95 9.8 50 58.2 69.4 3.45 33.8 16.9 6.5

11.7 3.3 7.5

85 79.8 63.1 4.89 98.6 4.78 9.8 40 50.5 61.9 3.15 30.0 16.0 5.9

95 77.1 59.6 5.14 108.2 4.39 10.1 45 54.9 65.8 3.21 34.1 17.1 6.1

110 74.4 55.9 5.40 122.7 4.04 10.3 50 59.3 69.8 3.28 38.3 18.1 6.2

15.0 5.3 12.2

85 81.7 64.9 4.93 95.9 4.86 10.1 40 51.0 62.2 3.04 32.2 16.8 5.6

95 79.0 61.3 5.18 105.5 4.47 10.3 45 55.5 66.1 3.10 36.5 17.9 5.8

110 76.2 57.5 5.45 120.2 4.10 10.6 50 59.9 70.1 3.17 40.8 18.9 6.0

90

8.3 1.6 3.7

85 89.2 71.8 5.08 106.5 5.14 10.8 40 47.8 62.0 4.07 26.7 11.7 8.1

95 86.2 67.8 5.34 115.8 4.73 11.1 45 52.0 65.9 4.15 30.6 12.5 8.3

110 83.2 63.7 5.61 130.0 4.35 11.3 50 56.1 69.9 4.24 34.4 13.2 8.5

11.7 3.0 7.0

85 93.1 75.6 5.19 100.9 5.26 11.4 40 48.6 62.3 3.87 30.4 12.6 7.8

95 90.0 71.4 5.46 110.4 4.83 11.7 45 52.9 66.2 3.94 34.5 13.4 8.0

110 86.9 67.0 5.74 124.9 4.44 11.9 50 57.1 70.2 4.03 38.7 14.2 8.2

15.0 4.9 11.3

85 95.4 77.7 5.24 97.7 5.33 11.8 40 49.2 62.5 3.73 32.4 13.2 7.4

95 92.2 73.5 5.51 107.3 4.90 12.1 45 53.5 66.5 3.80 36.8 14.1 7.7

110 89.0 68.9 5.79 121.9 4.50 12.3 50 57.8 70.5 3.88 41.1 14.9 7.9

110

8.3 1.5 3.5

operation Not recommended

40 42.4 59.1 5.04 28.2 8.4 9.9

45 46.1 62.9 5.13 32.2 9.0 10.2

50 49.8 66.7 5.24 36.2 9.5 10.6

11.7 3.0 7.0

40 43.1 59.4 4.78 31.5 9.0 9.6

45 46.9 63.2 4.87 35.7 9.6 9.9

50 50.6 67.0 4.98 40.0 10.2 10.1

15.0 4.8 11.2

40 43.7 59.7 4.61 33.3 9.5 9.2

45 47.5 63.5 4.70 37.7 10.1 9.5

50 51.3 67.3 4.80 42.1 10.7 9.8

* See Page 9 for Application Notes

Page 21: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

20Roth RWT Series Catalog - August 2010

RWT070PerformanceData:6.0Ton,PartLoadCapacity

ESt GPM PSI FtHeating Cooling

ELt HC HE KW LLt CoP DH ELt tC Hr KW LLt EEr DH

30

6.7 1.2 2.8

85 40.1 30.5 2.75 97.0 4.27 4.9

operation Not recommended

95 38.8 28.9 2.89 106.6 3.93 5.0

110 37.4 27.1 3.04 121.2 3.60 5.2

9.4 2.3 5.4

85 41.8 32.1 2.81 93.9 4.36 5.0

95 40.5 30.4 2.95 103.6 4.02 5.2

110 39.0 28.5 3.11 118.3 3.67 5.3

12.1 3.9 9

85 42.9 33.1 2.84 92.1 4.43 5.1

95 41.5 31.3 2.98 101.9 4.08 5.3

110 40.0 29.3 3.14 116.6 3.73 5.5

50

6.7 1.1 2.6

85 53.7 43.6 2.93 101.0 5.37 6.5 40 43.8 50.8 1.72 26.9 25.5 3.5

95 51.9 41.2 3.08 110.5 4.94 6.6 45 47.6 54.0 1.75 30.8 27.2 3.5

110 50.1 38.6 3.24 125.0 4.53 6.8 50 51.4 57.3 1.79 34.7 28.7 3.7

9.4 2.2 5.0

85 56.0 45.9 3.00 96.9 5.47 6.8 40 44.5 51.1 1.63 30.5 27.3 3.3

95 54.2 43.4 3.15 106.5 5.04 6.9 45 48.4 54.3 1.66 34.7 29.2 3.4

110 52.3 40.7 3.32 121.1 4.62 7.1 50 52.3 57.6 1.70 38.9 30.8 3.5

12.1 3.6 8.3

85 57.4 47.2 3.03 94.5 5.55 6.9 40 45.1 51.3 1.57 32.5 28.7 3.1

95 55.5 44.6 3.18 104.2 5.11 7.0 45 49.0 54.5 1.60 36.9 30.6 3.2

110 53.5 41.8 3.35 118.8 4.68 7.2 50 52.9 57.8 1.64 41.3 32.3 3.3

70

6.7 1.1 2.6

85 68.6 57.9 3.15 105.5 6.38 8.2 40 41.5 49.3 2.03 27.6 20.4 5.0

95 66.3 54.7 3.31 114.8 5.87 8.4 45 45.1 52.4 2.07 31.5 21.8 5.2

110 64.0 51.3 3.48 129.1 5.39 8.6 50 48.7 55.6 2.12 35.5 23.0 5.4

9.4 2.1 4.8

85 71.6 60.9 3.23 100.2 6.49 8.6 40 42.2 49.6 1.93 31.0 21.9 4.8

95 69.2 57.5 3.39 109.7 5.98 8.8 45 45.9 52.7 1.97 35.2 23.3 5.0

110 66.8 54.0 3.57 124.2 5.48 9.1 50 49.6 55.9 2.01 39.4 24.7 5.1

12.1 3.4 7.9

85 73.3 62.7 3.26 97.1 6.59 8.8 40 42.7 49.7 1.87 32.9 22.8 4.6

95 70.9 59.2 3.42 106.7 6.07 9.0 45 46.4 52.9 1.90 37.3 24.4 4.8

110 68.4 55.6 3.60 121.3 5.57 9.3 50 50.1 56.1 1.94 41.7 25.8 5.0

90

6.7 1.1 2.4

85 84.2 73.0 3.36 110.1 7.34 10.0 40 38.1 46.9 2.46 28.6 15.5 6.7

95 81.4 68.9 3.53 119.3 6.76 10.2 45 41.4 49.9 2.51 32.6 16.5 6.9

110 78.6 64.7 3.71 133.5 6.21 10.4 50 44.7 52.9 2.57 36.7 17.4 7.0

9.4 1.9 4.5

85 87.9 76.8 3.44 103.7 7.49 10.5 40 38.7 47.2 2.34 31.8 16.5 6.4

95 85.0 72.6 3.61 113.1 6.90 10.8 45 42.1 50.2 2.38 36.0 17.7 6.6

110 82.0 68.1 3.80 127.4 6.32 10.9 50 45.5 53.2 2.43 40.3 18.7 6.7

12.1 3.2 7.4

85 90.1 79.0 3.47 99.9 7.61 10.9 40 39.2 47.4 2.26 33.5 17.4 6.1

95 87.1 74.7 3.64 109.4 7.01 11.1 45 42.6 50.4 2.30 38.0 18.5 6.3

110 84.1 70.0 3.83 123.9 6.43 11.3 50 46.0 53.4 2.35 42.4 19.6 6.5

110

6.7 1.0 2.3

operation Not recommended

40 33.4 44.1 3.10 30.0 10.8 8.2

45 36.3 46.9 3.16 34.2 11.5 8.5

50 39.2 49.7 3.23 38.3 12.1 8.7

9.4 1.9 4.5

40 34.0 44.3 2.95 32.8 11.5 7.9

45 37.0 47.1 3.01 37.1 12.3 8.2

50 39.9 49.9 3.08 41.5 13.0 8.3

12.1 3.2 7.3

40 34.4 44.5 2.85 34.3 12.1 7.6

45 37.4 47.3 2.90 38.8 12.9 7.9

50 40.4 50.2 2.96 43.3 13.7 8.1

* See Page 9 for Application Notes

Page 22: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

21RWT Series Catalog - August 2010 Roth

RWT070PerformanceData:6.0Ton,FullLoadCapacity

ESt GPM PSI FtHeating Cooling

ELt HC HE KW LLt CoP DH ELt tC Hr KW LLt EEr DH

30

10.0 2.3 5.4

85 60.0 41.8 5.17 97.0 3.40 7.3

operation Not recommended

95 58.0 39.5 5.44 106.6 3.12 7.5

110 55.9 37.0 5.72 121.2 2.86 7.8

14.0 4.4 10.1

85 62.6 44.0 5.29 93.9 3.47 7.5

95 60.5 41.6 5.56 103.6 3.19 7.8

110 58.4 39.0 5.84 118.3 2.93 8.0

18.0 7.0 16.2

85 64.1 45.3 5.34 92.1 3.52 7.6

95 62.0 42.8 5.61 101.9 3.24 7.9

110 59.8 40.1 5.90 116.6 2.97 8.2

50

10.0 2.2 5.0

85 78.5 59.5 5.50 100.7 4.18 9.5 40 65.8 78.7 3.43 26.8 19.2 5.2

95 75.9 56.2 5.78 110.2 3.85 9.7 45 71.5 83.7 3.49 30.7 20.5 5.3

110 73.2 52.7 6.08 124.6 3.53 10.0 50 77.2 88.7 3.57 34.6 21.6 5.5

14.0 4.1 9.4

85 82.0 62.6 5.63 96.7 4.27 9.9 40 66.9 79.2 3.26 30.4 20.5 5.0

95 79.3 59.1 5.92 106.3 3.92 10.1 45 72.8 84.2 3.32 34.6 21.9 5.1

110 76.5 55.5 6.22 120.9 3.60 10.4 50 78.6 89.3 3.39 38.8 23.2 5.2

18.0 6.6 15.1

85 84.0 64.4 5.68 94.3 4.33 10.1 40 67.7 79.5 3.14 32.5 21.6 4.7

95 81.2 60.8 5.97 104.0 3.99 10.3 45 73.6 84.5 3.20 36.8 23.0 4.8

110 78.4 57.1 6.27 118.7 3.66 10.6 50 79.5 89.6 3.27 41.2 24.3 5.0

70

10.0 2.2 5.0

85 96.2 75.8 5.92 104.2 4.76 11.5 40 61.9 76.6 4.06 27.6 15.3 7.5

95 93.0 71.6 6.23 113.6 4.37 11.8 45 67.3 81.5 4.14 31.5 16.3 7.7

110 89.8 67.2 6.55 128.0 4.02 12.1 50 72.7 86.4 4.23 35.5 17.2 8.0

14.0 3.9 9.0

85 100.5 79.7 6.06 99.4 4.86 12.1 40 63.0 77.1 3.87 31.0 16.3 7.2

95 97.1 75.4 6.37 108.9 4.47 12.4 45 68.5 82.0 3.94 35.2 17.4 7.5

110 93.7 70.7 6.69 123.4 4.10 12.7 50 74.0 86.9 4.03 39.4 18.4 7.6

18.0 6.2 14.4

85 103.0 82.1 6.11 96.4 4.94 12.4 40 63.7 77.4 3.73 32.9 17.1 6.9

95 99.5 77.6 6.43 106.1 4.53 12.7 45 69.3 82.3 3.80 37.3 18.2 7.1

110 96.1 72.8 6.76 120.7 4.17 13.0 50 74.8 87.3 3.88 41.7 19.3 7.4

90

10.0 2.0 4.7

85 112.5 90.9 6.29 107.5 5.24 13.3 40 56.6 74.0 5.04 28.7 11.2 9.9

95 108.7 85.9 6.62 116.7 4.81 13.6 45 61.6 78.7 5.13 32.7 12.0 10.2

110 104.9 80.6 6.96 131.0 4.42 13.9 50 66.5 83.4 5.24 36.7 12.7 10.4

14.0 3.6 8.3

85 117.4 95.6 6.44 101.8 5.34 14.0 40 57.7 74.4 4.78 31.8 12.1 9.5

95 113.5 90.4 6.77 111.2 4.91 14.4 45 62.7 79.1 4.87 36.0 12.9 9.8

110 109.5 84.8 7.11 125.6 4.51 14.6 50 67.7 83.9 4.98 40.3 13.6 10.0

18.0 5.8 13.3

85 120.3 98.4 6.49 98.4 5.43 14.5 40 58.3 74.7 4.61 33.5 12.7 9.1

95 116.3 93.0 6.83 107.9 4.99 14.8 45 63.4 79.4 4.70 38.0 13.5 9.4

110 112.2 87.3 7.18 122.5 4.58 15.1 50 68.4 84.2 4.80 42.4 14.3 9.7

110

10.0 2.0 4.5

operation Not recommended

40 49.8 70.3 6.21 30.0 8.0 12.2

45 54.1 74.8 6.33 34.2 8.6 12.6

50 58.4 79.3 6.47 38.3 9.0 13.0

14.0 3.6 8.3

40 50.7 70.7 5.90 32.8 8.6 11.8

45 55.1 75.2 6.01 37.1 9.2 12.2

50 59.5 79.7 6.14 41.5 9.7 12.4

18.0 5.7 13.2

40 51.2 71.0 5.69 34.3 9.0 11.3

45 55.7 75.5 5.80 38.8 9.6 11.7

50 60.1 80.1 5.93 43.3 10.1 12.1

* See Page 9 for Application Notes

Page 23: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

22Roth RWT Series Catalog - August 2010

RWT092PerformanceData:8.0Ton,PartLoadCapacity

ESt GPM PSI FtHeating Cooling

ELt HC HE KW LLt CoP DH ELt tC Hr KW LLt EEr DH

30

9.7 0.6 1.4

85 58.0 44.2 4.04 97.1 4.21 7.0

operation Not recommended

95 56.0 41.6 4.26 106.7 3.85 7.4

110 54.2 39.2 4.46 121.3 3.56 7.6

13.5 1.2 2.8

85 60.6 46.4 4.14 93.9 4.29 7.4

95 58.6 43.8 4.36 103.6 3.94 7.6

110 56.6 41.2 4.58 118.3 3.62 7.8

17.4 2.0 4.6

85 62.2 47.8 4.18 92.1 4.36 7.4

95 60.0 45.0 4.40 101.9 4.00 7.8

110 58.0 42.4 4.62 116.7 3.68 7.8

50

9.7 0.6 1.3

85 76.2 61.6 4.32 100.9 5.17 9.2 40 69.5 79.1 2.80 26.8 24.8 5.0

95 73.8 58.2 4.54 110.4 4.76 9.6 45 75.5 85.3 2.86 30.6 26.4 5.2

110 71.2 54.6 4.76 124.8 4.38 9.8 50 81.5 91.5 2.92 34.5 27.9 5.4

13.5 1.1 2.6

85 79.8 64.6 4.40 96.7 5.31 9.6 40 70.5 79.6 2.68 30.3 26.3 4.8

95 77.2 61.2 4.64 106.4 4.87 10.0 45 76.7 86.0 2.72 34.5 28.2 5.0

110 74.4 57.4 4.86 120.9 4.49 10.2 50 82.9 92.4 2.78 38.6 29.8 5.0

17.4 1.8 4.3

85 81.6 66.6 4.44 94.4 5.38 9.8 40 71.5 80.3 2.58 32.4 27.7 4.6

95 79.0 63.0 4.68 104.1 4.95 10.0 45 77.7 86.6 2.62 36.7 29.7 4.6

110 76.2 59.0 4.92 118.8 4.54 10.4 50 83.9 93.1 2.69 41.1 31.2 4.8

70

9.7 0.6 1.3

85 94.4 78.6 4.64 104.7 5.96 11.4 40 65.3 77.1 3.47 27.6 18.8 7.4

95 91.4 74.4 4.88 114.0 5.49 11.6 45 71.1 83.1 3.53 31.5 20.1 7.4

110 88.2 69.8 5.12 128.4 5.05 12.0 50 76.7 89.0 3.61 35.4 21.3 7.8

13.5 1.1 2.5

85 98.8 83.0 4.74 99.5 6.11 12.0 40 66.5 77.7 3.29 30.9 20.2 7.0

95 95.6 78.4 5.00 109.1 5.60 12.2 45 72.3 83.7 3.35 35.1 21.6 7.4

110 92.2 73.6 5.24 123.6 5.16 12.4 50 78.1 89.8 3.43 39.3 22.8 7.4

17.4 1.8 4.1

85 101.0 85.2 4.78 96.6 6.19 12.2 40 67.3 78.1 3.17 32.8 21.2 6.6

95 97.8 80.6 5.04 106.2 5.69 12.6 45 73.1 84.1 3.23 37.2 22.6 7.0

110 94.4 75.6 5.28 120.9 5.24 12.8 50 78.9 90.2 3.31 41.6 23.8 7.2

90

9.7 0.5 1.2

85 112.2 95.6 4.94 108.4 6.65 13.4 40 59.5 73.5 4.09 28.7 14.6 9.6

95 108.6 90.4 5.20 117.6 6.12 13.6 45 64.7 79.0 4.18 32.7 15.5 10.0

110 104.8 84.8 5.46 131.8 5.62 14.0 50 69.9 84.5 4.28 36.7 16.3 10.2

13.5 1.0 2.3

85 117.2 101.0 5.06 102.2 6.79 14.0 40 60.5 73.8 3.89 31.7 15.6 9.2

95 113.4 95.4 5.32 111.7 6.25 14.4 45 65.9 79.4 3.97 36.0 16.6 9.6

110 109.4 89.6 5.58 126.1 5.74 14.8 50 71.1 84.9 4.05 40.3 17.6 9.8

17.4 1.6 3.8

85 120.2 103.8 5.08 98.8 6.93 14.6 40 61.3 74.2 3.78 33.5 16.2 9.0

95 116.2 98.0 5.36 108.4 6.35 14.8 45 66.7 79.8 3.84 37.9 17.4 9.2

110 112.0 92.0 5.62 122.9 5.84 15.2 50 72.1 85.5 3.92 42.3 18.4 9.4

110

9.7 0.5 1.2

operation Not recommended

40 52.3 70.0 5.18 30.0 10.1 11.8

45 56.9 74.9 5.28 34.2 10.8 12.2

50 61.5 80.0 5.41 38.3 11.4 12.6

13.5 1.0 2.3

40 53.3 70.1 4.92 32.7 10.8 11.4

45 57.9 75.0 5.02 37.1 11.5 11.8

50 62.5 80.0 5.12 41.4 12.2 12.2

17.4 1.6 3.7

40 53.7 69.9 4.76 34.3 11.3 11.0

45 58.5 75.1 4.85 38.8 12.1 11.4

50 63.1 80.0 4.95 43.3 12.8 11.8

* See Page 9 for Application Notes

Page 24: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

23RWT Series Catalog - August 2010 Roth

RWT092PerformanceData:8.0Ton,FullLoadCapacity

ESt GPM PSI FtHeating Cooling

ELt HC HE KW LLt CoP DH ELt tC Hr KW LLt EEr DH

30

14.5 1.4 3.3

85 87.0 60.2 7.58 97.1 3.36 10.6

operation Not recommended

95 84.2 57.0 7.96 106.7 3.10 11.0

110 81.2 53.4 8.38 121.3 2.84 11.4

20.2 2.7 6.2

85 90.8 63.4 7.74 94.0 3.44 11.0

95 87.8 60.0 8.14 103.7 3.16 11.4

110 84.6 56.2 8.56 118.4 2.90 11.8

26.0 4.4 10.2

85 93.0 65.4 7.82 92.2 3.48 11.2

95 90.0 61.8 8.22 101.9 3.21 11.6

110 86.8 58.0 8.64 116.7 2.94 11.8

50

14.5 1.3 3.1

85 114.0 85.8 8.08 100.8 4.13 13.8 40 103.3 122.5 5.63 26.8 18.4 7.6

95 110.2 81.2 8.48 110.3 3.81 14.2 45 112.3 131.9 5.73 30.6 19.6 7.8

110 106.2 76.2 8.92 124.8 3.49 14.6 50 121.3 141.3 5.85 34.4 20.7 8.0

20.2 2.5 5.8

85 119.2 90.6 8.26 96.8 4.23 14.4 40 105.1 123.3 5.33 30.4 19.7 7.2

95 115.2 85.6 8.68 106.4 3.89 14.8 45 114.3 132.8 5.43 34.5 21.1 7.4

110 111.2 80.2 9.12 121.0 3.57 15.2 50 123.5 142.4 5.55 38.7 22.3 7.6

26.0 4.1 9.4

85 122.0 93.0 8.34 94.4 4.29 14.6 40 106.3 123.9 5.15 32.4 20.6 6.8

95 118.0 88.0 8.76 104.1 3.95 15.0 45 115.7 133.6 5.25 36.7 22.0 7.0

110 113.8 82.6 9.22 118.8 3.62 15.4 50 124.9 143.2 5.37 41.1 23.3 7.2

70

14.5 1.3 3.1

85 139.8 109.8 8.68 104.4 4.72 16.8 40 97.3 120.9 6.92 27.5 14.1 11.0

95 135.2 103.8 9.12 113.8 4.34 17.2 45 105.9 129.9 7.04 31.4 15.0 11.2

110 130.4 97.4 9.60 128.1 3.98 17.6 50 114.3 138.9 7.20 35.3 15.9 11.6

20.2 2.4 5.6

85 146.0 115.6 8.88 99.5 4.82 17.6 40 99.3 121.7 6.56 30.9 15.1 10.6

95 141.2 109.2 9.34 109.0 4.43 18.0 45 107.9 130.7 6.68 35.1 16.2 11.0

110 136.2 102.4 9.82 123.5 4.06 18.4 50 116.5 139.8 6.82 39.3 17.1 11.2

26.0 3.9 9.0

85 149.6 119.0 8.96 96.5 4.89 18.0 40 100.3 121.9 6.34 32.8 15.8 10.0

95 144.6 112.4 9.42 106.1 4.50 18.6 45 109.1 131.1 6.46 37.2 16.9 10.4

110 139.6 105.4 9.90 120.7 4.13 19.0 50 117.7 140.2 6.60 41.6 17.8 10.8

90

14.5 1.2 2.9

85 163.2 131.4 9.22 107.7 5.19 19.4 40 89.1 117.9 8.43 28.6 10.6 14.4

95 157.8 124.2 9.70 116.9 4.77 19.8 45 96.9 126.2 8.59 32.6 11.3 14.8

110 152.2 116.6 10.20 131.1 4.37 20.2 50 104.7 134.6 8.77 36.6 11.9 15.2

20.2 2.2 5.1

85 170.4 138.4 9.46 101.9 5.28 20.4 40 90.5 117.8 8.01 31.7 11.3 13.8

95 164.8 130.8 9.94 111.3 4.86 21.0 45 98.5 126.4 8.16 36.0 12.1 14.2

110 159.0 122.8 10.46 125.7 4.45 21.4 50 106.3 134.8 8.34 40.2 12.8 14.6

26.0 3.6 8.4

85 174.6 142.6 9.54 98.4 5.36 21.2 40 91.7 118.1 7.73 33.5 11.9 13.4

95 168.8 134.6 10.02 108.0 4.94 21.6 45 99.7 126.6 7.87 37.9 12.7 13.6

110 163.0 126.4 10.54 122.5 4.53 22.0 50 107.7 135.2 8.05 42.3 13.4 14.0

110

14.5 1.2 2.8

operation Not recommended

40 78.1 113.5 10.36 30.0 7.5 17.8

45 84.9 121.0 10.57 34.1 8.0 18.4

50 91.7 128.5 10.79 38.2 8.5 18.8

20.2 2.2 5.1

40 79.5 113.1 9.85 32.7 8.1 17.2

45 86.5 120.7 10.03 37.1 8.6 17.8

50 93.3 128.3 10.25 41.4 9.1 18.2

26.0 3.6 8.2

40 80.5 113.0 9.51 34.3 8.5 16.4

45 87.5 120.6 9.69 38.8 9.0 17.0

50 94.5 128.3 9.91 43.3 9.5 17.6

* See Page 9 for Application Notes

Page 25: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

24Roth RWT Series Catalog - August 2010

RWT120PerformanceData:10.0Ton,PartLoadCapacity

ESt GPM PSI FtHeating Cooling

ELt HC HE KW LLt CoP DH ELt tC Hr KW LLt EEr DH

30

8.3 2.2 5.0

85 47.8 34.3 4.05 96.5 3.46 6.0

operation Not recommended

95 46.5 32.3 4.27 106.1 3.19 6.1

110 45.0 30.5 4.48 120.8 2.95 6.3

11.7 4.0 9.3

85 49.3 35.8 4.10 93.5 3.53 6.1

95 47.9 33.7 4.31 103.2 3.26 6.3

110 46.6 31.7 4.53 118.0 3.02 6.5

15.0 6.5 15.0

85 49.9 36.5 4.09 91.7 3.58 6.2

95 48.6 34.5 4.31 101.5 3.31 6.4

110 47.3 32.3 4.53 116.3 3.06 6.6

50

8.3 2.0 4.7

85 61.9 48.0 4.25 99.8 4.27 7.7 40 50.4 59.3 2.74 27.9 18.4 4.2

95 60.0 45.2 4.47 109.4 3.93 7.9 45 54.7 63.1 2.80 31.9 19.6 4.3

110 58.0 42.5 4.69 123.9 3.62 8.1 50 59.1 66.9 2.85 35.8 20.7 4.4

11.7 3.7 8.6

85 64.5 50.2 4.33 96.1 4.37 8.0 40 50.9 59.5 2.61 31.3 19.5 4.0

95 62.4 47.4 4.56 105.7 4.01 8.2 45 55.3 63.3 2.67 35.5 20.7 4.1

110 60.4 44.5 4.79 120.4 3.69 8.5 50 59.7 67.1 2.72 39.8 21.9 4.2

15.0 6.0 14.0

85 65.8 51.6 4.35 93.8 4.44 8.5 40 51.4 59.8 2.54 33.1 20.3 3.8

95 63.7 48.6 4.58 103.5 4.08 8.4 45 55.9 63.7 2.59 37.5 21.6 3.9

110 61.6 45.7 4.81 118.2 3.75 8.6 50 60.3 67.4 2.65 42.0 22.8 4.0

70

8.3 2.0 4.7

85 75.3 60.5 4.51 103.1 4.89 9.4 40 47.3 57.7 3.29 28.7 14.4 6.1

95 72.6 57.0 4.75 112.4 4.48 9.6 45 51.3 61.4 3.37 32.7 15.2 6.3

110 70.0 53.6 4.98 126.8 4.12 9.8 50 55.5 65.1 3.42 36.7 16.2 6.5

11.7 3.6 8.3

85 79.1 63.7 4.65 98.6 4.99 9.8 40 48.0 58.0 3.13 31.8 51.3 5.9

95 76.3 60.1 4.89 108.1 4.57 10.1 45 52.1 61.7 3.20 36.1 16.3 6.1

110 73.5 56.5 5.15 122.6 4.19 10.3 50 56.3 65.4 3.26 40.3 17.3 6.2

15.0 5.8 13.3

85 81.2 65.7 4.70 95.8 5.06 10.1 40 48.4 58.3 3.04 33.5 15.9 5.6

95 78.3 62.0 4.95 105.4 4.64 10.3 45 52.7 62.0 3.10 38.0 17.0 5.8

110 75.3 56.5 5.19 120.0 4.25 10.6 50 56.8 65.6 3.16 42.4 18.0 6.0

90

8.3 1.9 4.3

85 86.8 71.3 4.48 105.8 5.68 10.8 40 43.0 55.6 4.07 29.7 10.6 8.1

95 83.6 67.2 5.06 115.1 4.84 11.1 45 46.7 59.1 4.15 33.8 11.3 8.3

110 80.4 63.2 5.21 129.3 4.52 11.3 50 50.5 62.7 4.21 37.9 12.0 8.5

11.7 3.3 7.7

85 91.8 75.6 4.92 100.7 5.47 11.4 40 43.8 55.9 3.83 32.5 11.5 7.8

95 88.4 71.3 5.18 110.2 5.01 11.7 45 47.7 59.4 3.92 36.8 12.2 8.0

110 85.0 67.1 5.44 124.6 4.58 11.9 50 51.5 62.9 3.98 41.2 12.9 8.2

15.0 5.3 12.3

85 94.8 78.3 4.99 97.6 5.57 11.8 40 44.3 56.0 3.73 34.1 11.9 7.4

95 91.2 73.9 5.25 107.2 5.09 12.1 45 48.2 59.5 3.80 38.6 12.7 7.7

110 87.6 69.5 5.51 121.7 4.66 12.3 50 52.0 63.1 3.89 43.1 13.4 7.9

110

8.3 1.8 4.2

operation Not recommended

40 37.5 52.9 5.07 31.0 7.4 9.9

45 40.7 56.3 5.14 35.2 7.9 10.2

50 44.0 59.6 5.26 39.4 8.4 10.6

11.7 3.3 7.7

40 38.4 53.1 4.74 33.4 8.1 9.6

45 41.9 56.4 4.85 37.8 8.6 9.9

50 45.2 59.8 4.98 42.2 9.1 10.1

15.0 5.3 12.1

40 38.8 53.1 4.64 34.8 8.4 9.2

45 42.3 56.4 4.70 39.4 9.0 9.5

50 45.6 59.8 4.79 43.9 9.5 9.8

* See Page 9 for Application Notes

Page 26: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

25RWT Series Catalog - August 2010 Roth

RWT120PerformanceData:10.0Ton,FullLoadCapacity

ESt GPM PSI FtHeating Cooling

ELt HC HE KW LLt CoP DH ELt tC Hr KW LLt EEr DH

30

15.6 2.3 5.3

85 95.7 68.7 8.10 97.3 3.46 11.9

operation Not recommended

95 93.0 64.7 8.54 106.9 3.19 12.3

110 90.0 60.9 8.95 121.6 2.95 12.6

21.8 4.3 9.8

85 98.6 71.6 8.19 94.1 3.53 12.3

95 95.9 67.3 8.63 103.8 3.26 12.7

110 93.3 63.3 9.06 118.6 3.02 13.1

28.0 6.8 15.8

85 99.9 72.9 8.18 92.1 3.58 12.4

95 97.2 68.9 8.62 101.9 3.31 12.9

110 94.6 64.7 9.05 116.8 3.06 13.3

50

15.6 2.1 4.9

85 123.8 95.9 8.49 100.9 4.27 15.4 40 100.7 118.6 5.47 27.1 18.4 8.5

95 120.1 90.3 8.95 110.4 3.93 15.9 45 109.5 126.3 5.60 30.9 19.6 8.7

110 116.0 85.0 9.38 124.9 3.62 16.3 50 118.2 133.8 5.71 34.8 20.7 8.9

21.8 4.0 9.1

85 129.0 100.5 8.66 96.9 4.37 16.1 40 101.8 119.0 5.23 30.6 19.5 8.1

95 124.8 94.8 9.12 106.5 4.01 16.5 45 110.5 126.5 5.34 34.8 20.7 8.3

110 120.8 89.0 9.59 121.1 3.69 17.0 50 119.4 134.2 5.45 39.0 21.9 8.5

28.0 6.4 14.7

85 131.7 103.1 8.70 94.4 4.44 16.4 40 102.8 119.6 5.08 32.7 20.3 7.7

95 127.4 97.3 9.16 104.1 4.08 16.8 45 111.8 127.3 5.18 37.0 21.6 7.9

110 123.1 91.4 9.62 118.8 3.75 17.3 50 120.7 134.8 5.29 41.4 22.8 8.1

70

15.6 2.1 4.9

85 150.6 121.0 9.03 104.4 4.89 18.8 40 94.5 115.5 6.58 27.9 14.4 12.2

95 145.3 114.1 9.49 113.7 4.48 19.2 45 102.6 122.8 6.73 31.8 15.2 12.6

110 139.9 107.1 9.96 128.0 4.12 19.6 50 110.9 130.2 6.84 35.8 16.2 13.0

21.8 3.8 8.8

85 158.2 127.4 9.29 99.5 4.99 19.7 40 96.0 115.9 6.26 31.2 15.3 11.8

95 152.6 120.2 9.78 109.0 4.57 20.2 45 104.3 123.4 6.40 35.4 16.3 12.2

110 146.9 112.9 10.29 123.5 4.19 20.6 50 112.6 130.9 6.52 39.7 17.3 12.4

28.0 6.1 14.0

85 162.4 131.4 9.40 96.6 5.06 20.2 40 96.8 116.5 6.07 33.1 15.9 11.2

95 156.6 124.0 9.89 106.2 4.64 20.7 45 105.3 124.0 6.19 37.5 17.0 11.6

110 150.7 116.5 10.38 120.8 4.25 21.2 50 113.6 131.3 6.32 41.9 18.0 12.0

90

15.6 2.0 4.6

85 173.7 142.7 8.96 107.3 5.68 21.6 40 86.0 111.1 8.14 29.0 10.6 16.1

95 167.2 134.4 10.13 116.5 4.84 22.1 45 93.5 118.2 8.29 33.0 11.3 16.6

110 160.8 126.4 10.42 130.7 4.52 22.6 50 101.0 125.5 8.43 37.0 12.0 17.0

21.8 3.5 8.1

85 183.5 151.2 9.83 101.9 5.47 22.9 40 87.7 111.8 7.66 31.9 11.5 15.5

95 176.9 142.7 10.35 111.3 5.01 23.4 45 95.3 118.8 7.84 36.2 12.2 15.9

110 169.9 134.1 10.87 125.6 4.58 23.9 50 103.0 125.9 7.96 40.5 12.9 16.3

28.0 5.6 13.0

85 189.7 156.6 9.99 98.5 5.57 23.6 40 88.7 112.0 7.46 33.7 11.9 14.9

95 182.5 147.7 10.50 108.0 5.09 24.1 45 96.4 119.0 7.60 38.1 12.7 15.3

110 175.3 138.9 11.03 122.5 4.66 24.6 50 104.1 126.3 7.77 42.6 13.4 15.7

110

15.6 1.9 4.4

operation Not recommended

40 75.0 105.7 10.13 30.4 7.4 19.9

45 81.4 112.6 10.27 34.5 7.9 20.5

50 88.1 119.2 10.53 38.7 8.4 21.1

21.8 3.5 8.1

40 76.9 106.1 9.48 32.9 8.1 19.2

45 83.7 112.8 9.70 37.3 8.6 19.9

50 90.4 119.6 9.96 41.7 9.1 20.3

28.0 5.5 12.8

40 77.7 106.1 9.28 34.5 8.4 18.4

45 84.5 112.8 9.41 39.0 9.0 19.0

50 91.2 119.6 9.59 43.5 9.5 19.7

* See Page 9 for Application Notes

Page 27: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

26Roth RWT Series Catalog - August 2010

RWT144PerformanceData:12.0Ton,PartLoadCapacity

ESt GPM PSI FtHeating Cooling

ELt HC HE KW LLt CoP DH ELt tC Hr KW LLt EEr DH

30

10.0 2.2 5.0

85 58.8 42.2 5.13 96.7 3.36 7.3

operation Not recommended

95 57.1 39.7 5.40 106.4 3.10 7.5

110 55.3 37.4 5.66 121.0 2.86 7.8

14.0 4.0 9.3

85 60.5 44.0 5.18 93.7 3.42 7.5

95 58.9 41.3 5.46 103.4 3.16 7.8

110 57.3 38.9 5.73 118.2 2.93 8.0

18.0 6.5 15.0

85 61.3 44.8 5.18 91.8 3.47 7.6

95 59.7 42.3 5.45 101.6 3.21 7.9

110 58.1 39.7 5.73 116.5 2.97 8.2

50

10.0 2.0 4.7

85 76.0 58.9 5.37 100.2 4.15 9.5 40 61.9 72.8 3.57 27.6 17.3 5.2

95 73.7 55.4 5.66 109.7 3.82 9.7 45 67.2 77.5 3.65 31.6 18.4 5.3

110 71.2 52.2 5.93 124.2 3.52 10.0 50 72.6 82.1 3.73 35.5 19.5 5.5

14.0 3.7 8.6

85 79.2 61.7 5.48 96.3 4.24 9.9 40 62.5 73.1 3.41 31.1 18.3 5.0

95 76.6 58.2 5.77 106.0 3.89 10.1 45 67.9 77.7 3.48 35.3 19.5 5.1

110 74.2 54.6 6.06 120.6 3.58 10.4 50 73.3 82.4 3.55 39.5 20.6 5.2

18.0 6.0 14.0

85 80.8 63.3 5.50 94.0 4.31 10.1 40 63.1 73.5 3.31 33.0 19.1 4.7

95 78.2 59.7 5.79 103.7 3.96 10.3 45 68.6 78.2 3.38 37.4 20.3 4.8

110 75.6 56.1 6.09 118.4 3.64 10.6 50 74.1 82.8 3.45 41.8 21.5 5.0

70

10.0 2.0 4.7

85 92.5 74.3 5.71 103.5 4.75 11.5 40 58.0 70.9 4.29 28.4 13.5 7.5

95 89.2 70.1 6.01 112.8 4.35 11.8 45 63.0 75.4 4.39 32.4 14.3 7.7

110 85.9 65.8 6.30 127.2 4.00 12.1 50 68.1 80.0 4.47 36.4 15.3 8.0

14.0 3.6 8.3

85 97.1 78.3 5.88 98.9 4.84 12.1 40 58.9 71.2 4.09 31.6 14.4 7.2

95 93.7 73.8 6.19 108.4 4.44 12.4 45 64.0 75.8 4.17 35.8 15.3 7.5

110 90.2 69.4 6.51 122.9 4.06 12.7 50 69.1 80.4 4.25 40.1 16.2 7.6

18.0 5.8 13.3

85 99.7 80.7 5.95 96.1 4.92 12.4 40 59.4 71.6 3.96 33.4 15.0 6.9

95 96.1 76.1 6.26 105.7 4.50 12.7 45 64.7 76.2 4.04 37.8 16.0 7.1

110 92.5 71.5 6.57 120.3 4.13 13.0 50 69.8 80.6 4.13 42.2 16.9 7.4

90

10.0 1.9 4.3

85 106.6 87.6 5.67 106.3 5.52 13.3 40 52.8 68.2 5.31 29.4 9.9 9.9

95 102.7 82.5 6.41 115.5 4.70 13.6 45 57.4 72.6 5.41 33.5 10.6 10.2

110 98.8 77.6 6.59 129.7 4.39 13.9 50 62.0 77.0 5.50 37.6 11.3 10.4

14.0 3.3 7.7

85 112.7 92.9 6.22 101.1 5.31 14.0 40 53.8 68.6 4.99 32.3 10.8 9.5

95 108.6 87.6 6.55 110.5 4.86 14.4 45 58.5 73.0 5.12 36.6 11.4 9.8

110 104.3 82.4 6.88 124.9 4.45 14.6 50 63.3 77.3 5.19 41.0 12.2 10.0

18.0 5.3 12.3

85 116.5 96.1 6.32 97.9 5.40 14.5 40 54.5 68.7 4.87 33.9 11.2 9.1

95 112.0 90.7 6.64 107.4 4.94 14.8 45 59.2 73.1 4.96 38.4 11.9 9.4

110 107.6 85.3 6.98 122.0 4.52 15.1 50 63.9 77.5 5.07 42.9 12.6 9.7

110

10.0 1.8 4.2

operation Not recommended

40 46.0 64.9 6.61 30.8 7.0 12.2

45 50.0 69.1 6.70 35.0 7.5 12.6

50 54.1 73.2 6.87 39.2 7.9 13.0

14.0 3.3 7.7

40 47.2 65.2 6.19 33.3 7.6 11.8

45 51.4 69.3 6.33 37.6 8.1 12.2

50 55.5 73.5 6.50 42.1 8.5 12.4

18.0 5.3 12.1

40 47.7 65.2 6.06 34.7 7.9 11.3

45 51.9 69.3 6.14 39.2 8.5 11.7

50 56.0 73.5 6.25 43.8 9.0 12.1

* See Page 9 for Application Notes

Page 28: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

27RWT Series Catalog - August 2010 Roth

RWT144PerformanceData:12.0Ton,FullLoadCapacity

ESt GPM PSI FtHeating Cooling

ELt HC HE KW LLt CoP DH ELt tC Hr KW LLt EEr DH

30

17.8 2.3 5.4

85 117.5 84.3 10.26 98.2 3.36 14.6

operation Not recommended

95 114.2 79.4 10.81 107.8 3.10 15.1

110 110.6 74.8 11.33 122.4 2.86 15.5

24.9 4.4 10.1

85 121.1 87.9 10.37 94.7 3.42 15.1

95 117.7 82.7 10.92 104.5 3.16 15.6

110 114.5 77.8 11.47 119.2 2.93 16.1

32.0 7.0 16.2

85 122.6 89.6 10.36 92.7 3.47 15.3

95 119.4 84.7 10.91 102.5 3.21 15.8

110 116.2 79.4 11.45 117.3 2.97 16.3

50

17.8 2.2 5.0

85 152.0 117.8 10.75 102.1 4.15 18.9 40 123.7 145.7 7.14 26.1 17.3 10.4

95 147.5 110.9 11.32 111.6 3.82 19.5 45 134.4 155.1 7.30 29.9 18.4 10.7

110 142.5 104.3 11.87 126.0 3.52 20.0 50 145.1 164.3 7.45 33.7 19.5 10.9

24.9 4.1 9.4

85 158.5 123.4 10.95 97.7 4.24 19.7 40 125.0 146.2 6.82 29.9 18.3 9.9

95 153.2 116.5 11.54 107.3 3.89 20.3 45 135.7 155.4 6.97 34.1 19.5 10.2

110 148.3 109.3 12.13 121.9 3.58 20.8 50 146.7 164.8 7.11 38.2 20.6 10.4

32.0 6.6 15.1

85 161.7 126.6 11.01 95.1 4.31 20.1 40 126.3 146.9 6.62 32.1 19.1 9.4

95 156.5 119.4 11.59 104.8 3.96 20.7 45 137.2 156.4 6.76 36.4 20.3 9.7

110 151.2 112.2 12.17 119.4 3.64 21.2 50 148.2 165.6 6.90 40.7 21.5 9.9

70

17.8 2.2 5.0

85 185.0 148.6 11.42 105.8 4.75 23.0 40 116.1 141.8 8.59 27.0 13.5 15.0

95 178.4 140.1 12.01 115.1 4.35 23.6 45 126.0 150.8 8.79 30.8 14.3 15.5

110 171.8 131.6 12.60 129.3 4.00 24.1 50 136.2 159.9 8.93 34.7 15.3 16.0

24.9 3.9 9.0

85 194.2 156.5 11.76 100.6 4.84 24.2 40 117.9 142.3 8.17 30.5 14.4 14.5

95 187.3 147.6 12.37 110.1 4.44 24.8 45 128.1 151.5 8.35 34.7 15.3 15.0

110 180.5 138.7 13.02 124.5 4.06 25.3 50 138.3 160.7 8.51 38.9 16.2 15.2

32.0 6.2 14.4

85 199.5 161.4 11.89 97.5 4.92 24.8 40 118.9 143.1 7.92 32.6 15.0 13.7

95 192.3 152.2 12.51 107.0 4.50 25.4 45 129.3 152.3 8.08 36.9 16.0 14.2

110 185.1 143.1 13.14 121.6 4.13 26.0 50 139.5 161.2 8.25 41.3 16.9 14.7

90

17.8 2.0 4.7

85 213.3 175.2 11.33 109.0 5.52 26.6 40 105.6 136.5 10.62 28.1 9.9 19.8

95 205.4 165.0 12.82 118.1 4.70 27.2 45 114.8 145.1 10.82 32.1 10.6 20.3

110 197.5 155.2 13.19 132.2 4.39 27.7 50 124.0 154.1 11.00 36.1 11.3 20.8

24.9 3.6 8.3

85 225.4 185.7 12.44 103.1 5.31 28.1 40 107.6 137.2 9.99 31.3 10.8 19.1

95 217.2 175.2 13.10 112.5 4.86 28.7 45 117.1 145.9 10.23 35.6 11.4 19.6

110 208.7 164.7 13.75 126.8 4.45 29.3 50 126.5 154.6 10.38 39.8 12.2 20.1

32.0 5.8 13.3

85 233.0 192.3 12.64 99.6 5.40 29.0 40 108.9 137.5 9.73 33.2 11.2 18.3

95 224.1 181.4 13.29 109.0 4.94 29.6 45 118.4 146.2 9.91 37.6 11.9 18.8

110 215.2 170.6 13.95 123.5 4.52 30.2 50 127.8 155.1 10.14 42.0 12.6 19.3

110

17.8 2.0 4.5

operation Not recommended

40 92.1 129.8 13.22 29.6 7.0 24.4

45 100.0 138.3 13.40 33.8 7.5 25.2

50 108.2 146.4 13.73 37.8 7.9 25.9

24.9 3.6 8.3

40 94.4 130.4 12.38 32.4 7.6 23.6

45 102.8 138.5 12.65 36.7 8.1 24.4

50 111.0 146.9 13.00 41.1 8.5 24.9

32.0 5.7 13.2

40 95.4 130.4 12.11 34.0 7.9 22.6

45 103.8 138.5 12.28 38.5 8.5 23.4

50 112.0 146.9 12.51 43.0 9.0 24.1

* See Page 9 for Application Notes

Page 29: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

28Roth RWT Series Catalog - August 2010

PerformanceData:AirHandlers&“A”CoilCapacities

Hot Water Heating Capacity -- 68°F EAT (DB)

Model CFM EWT°F GPM WPD

Ft HdHtg Cap

BtuhLAT°F

MPH024 789

100

3.0

1.9 13,526 83.9105 1.9 17,677 88.7110 1.9 21,829 93.6115 1.8 25,980 98.5120 1.8 30,131 103.4

MPH036 1058

100

4.5

1.9 17,808 83.6105 1.9 23,527 88.6110 1.9 29,246 93.6

115 1.8 34,965 98.6120 1.8 40,684 103.6

MPH048 1564

100

6.0

2.5 25,339 83.0105 2.4 33,373 87.8110 2.4 41,407 92.5115 2.4 49,441 97.3120 2.3 57,474 102.0

MPH060 1952

100

7.5

4.0 34,801 84.5105 3.9 44,796 89.2110 3.9 54,791 94.0115 3.8 64,785 98.7120 3.7 74,779 103.5

Chilled Water Cooling Capacity -- 80/67°F EAT (DB/WB)

Model CFM EWT°F GPM WPD

Ft HdTC

BtuhSC

BtuhMPH024 800 45 3.5 2.1 32,350 22,190MPH036 1200 45 4.0 3.3 41,540 30,430MPH048 1600 45 5.5 5.5 51,940 38,600MPH060 2000 45 7.0 8.4 63,750 47,340

Air Handler / “A” Coil Capacities

Entering Air Correction FactorsHeating Cooling

EAT°F (DB)

HeatingCapacity

EAT°F (WB)

TotalCapacity

Sensible CapacityEAT °F (DB)

60 65 70 75 80 85

50 1.038 50 0.743 0.911 ** ** ** ** **

55 1.028 55 0.820 0.771 0.882 1.019 ** ** **

60 1.018 60 0.896 0.670 0.854 1.047 ** **

65 1.007 65 0.971 0.649 0.866 1.081 **

68 1.000 67 1.000 0.556 0.780 1.000 1.216

70 0.995 70 1.044 0.638 0.865 1.08575 0.984 75 1.116 0.601 0.832

**At this condition, Total Capacity = Sensible Capacity.Gray shaded area includes conditions not typical for cooling operation.

Airflow Correction Factors

Model CFM HeatingCapacity

Tot CoolingCapacity

SensibleCapacity

MPH024

880 1.047 1.046 1.074789 1.000 1.000 1.000690 0.949 0.950 0.920584 0.895 0.897 0.833

MPH036

1058 1.000 1.000 1.0001023 0.987 0.987 0.979831 0.913 0.915 0.862657 0.846 0.850 0.757

MPH048

1952 1.101 1.098 1.1591761 1.051 1.050 1.0811564 1.000 1.000 1.0001385 0.954 0.955 0.927

MPH060

1952 1.000 1.000 1.0001761 0.960 0.961 0.9371564 0.919 0.921 0.8731385 0.882 0.885 0.814

Air Handler / “A” Coil Corrections

Air Handler / “A” Coil Corrections

Page 30: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

29RWT Series Catalog - August 2010 Roth

Single Compressor units

ModelDimensional Data Ground Loop Load Loop

WeightA B C IN OUT IN OUT

RWT026 20 22 32 0.75” 0.75” 0.75” 0.75” 200

RWT034 24 26 34 1” 1” 1” 1” 280

RWT046 24 26 34 1” 1” 1” 1” 300

RWT058 24 26 36 1” 1” 1” 1” 350

RWT070 24 26 36 1” 1” 1” 1” 350

Dual Compressor units

ModelDimensional Data Ground Loop Load Loop

WeightA B C IN* OUT IN* OUT

RWT092 24 30 48 1” 1.25” 1” 1.25” 550

RWT120 24 30 48 1” 1.5” 1” 1.5” 670

RWT144 24 30 48 1” 1.5” 1” 1.5” 670

DimensionalData

B

In (Load Loop #1)

Out (Load Loop)Out (Ground Loop)In (Ground Loop #2)In (Ground Loop #1)In (Load Loop #2)

C

A

Desuperheater OutDesuperheater In Hydron Module

B

In (Ground Loop)

Out (Ground Loop)

Out (Load Loop)

Desuperheater Out

Desuperheater In

In (Load Loop)

C

A

Hydron Module

B

In (Ground Loop)

Out (Ground Loop)

Out (Load Loop)

Desuperheater Out

Desuperheater In

In (Load Loop)

C

A

Hydron Module

W024, 36, 48, 60 & 72 W122

Optional Configuration

Single Compressor

* there are two “IN” connections, but only one “out” connection

B

In (Load Loop #1)

Out (Load Loop)Out (Ground Loop)In (Ground Loop #2)In (Ground Loop #1)In (Load Loop #2)

C

A

Desuperheater OutDesuperheater In Hydron Module

B

In (Ground Loop)

Out (Ground Loop)

Out (Load Loop)

Desuperheater Out

Desuperheater In

In (Load Loop)

C

A

Hydron Module

B

In (Ground Loop)

Out (Ground Loop)

Out (Load Loop)

Desuperheater Out

Desuperheater In

In (Load Loop)

C

A

Hydron Module

W024, 36, 48, 60 & 72 W122

Optional Configuration

Dual Compressor

Page 31: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

30Roth RWT Series Catalog - August 2010

PhysicalData:AirHandlers

ModelSize

(tons)All Dimensions in Inches

A B C D E F G024 2 17 5/8 21 16 1/3 20 1/4 15 1/2 12 1/2 43036 3 21 1/8 21 19 3/4 20 1/4 19 12 1/2 48 1/4

048-060 4 - 5 25 22 23 3/8 20 1/2 19 5/8 16 1/8 58 3/4

A

B

C

D

G

F

E

TOP VIEW BOTTOM VIEW

FRONT VIEW

Model Size(tons) A B C D E F G

48-60 4 - 5 25 22 23 3/8 20 1/2 19 5/8 16 1/8 58 3/4

24 2 17 5/8 21 16 1/3 20 1/4 15 1/2 12 1/2 4336 3 21 1/8 21 19 3/4 20 1/4 19 12 1/2 48 1/4

DIMENSIONAL DATAAll Dimensions in Inches

Alternate DrainConnection(Horizontal)

Alternate DrainConnection

(Vertical)

Water Connections, Hydronic (Sweat)Line Set Connection, DX units

Primary DrainConnection

(Vertical)

Primary DrainConnection(Horizontal)

A

B

C

D

G

F

E

TOP VIEW BOTTOM VIEW

FRONT VIEW

Model Size(tons) A B C D E F G

48-60 4 - 5 25 22 23 3/8 20 1/2 19 5/8 16 1/8 58 3/4

24 2 17 5/8 21 16 1/3 20 1/4 15 1/2 12 1/2 4336 3 21 1/8 21 19 3/4 20 1/4 19 12 1/2 48 1/4

DIMENSIONAL DATAAll Dimensions in Inches

Alternate DrainConnection(Horizontal)

Alternate DrainConnection

(Vertical)

Water Connections, Hydronic (Sweat)Line Set Connection, DX units

Primary DrainConnection

(Vertical)

Primary DrainConnection(Horizontal)

Page 32: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

31RWT Series Catalog - August 2010 Roth

PhysicalData:“A”Coils

PAN REMOVED FOR CLARITYB A

BackSideFront

Drain Pan Drain Pan

I

D

E

FG

H

C

NotES:1. the AC series coils are designed as high efficiency “A” coils to be installed on new and existing indoor

furnaces. these coils may be used in upflow and downflow applications.2. Coils are EtL and CSA approved.3. Primary and secondary drain connections are available on the LH or rH side of the drain pan, and are

3/4” FPt. Center line of drains located from pan corner, 1 1/2” for primary and 3 1/2” for secondary.4. Drain pan is injection molded high temperature uL approved plastic.

ModelSize

(tons)All Dimensions In Inches

B A I D E F G H C024 2 19.00 16.63 16.00 16.00 4.00 8.67 8.67 3.27 18.5036 3 19.00 19.63 16.00 20.00 6.76 6.77 6.77 6.04 21.0

048-060 4 - 5 20.50 23.92 17.50 28.58 9.38 9.38 9.38 8.66 28.0

Page 33: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

32Roth RWT Series Catalog - August 2010

ElectricalData:SingleCompressorUnits

Notes:1. All line and low voltage wiring must adhere to the National Electrical Code and Local Codes, whichever is the most stringent. 2. Wire length based on a one way measurement with a 2% voltage drop. 3. Wire size based on 60°C copper conductor and minimum circuit ampacity. 3. All fuses class rK-54. Min/Max Voltage: 208-230/60/1 = 197/243* the external loop pump FLA is based on a maximum of three uP26-116F-230V pumps (1/2hp) for 046 - 070 and two pumps for 026 - 034

Model VoltageCode

60 Hz Power CompressorHWGPump

FLA

Ext Loop PumpFLA*

total unitFLA

MinCircuitAMPS

Max Fuse

HACr

Min AWG

Max FtVoltage Min/Max Phase QtY LrA rLA

026 1 208-230 197 - 254 1 1 70 14.1 0.5 4.0 18.6 22.1 35 12 53

034 1 208-230 197 - 254 1 1 96 16.7 0.5 4.0 21.2 25.4 40 10 78

046 1 208-230 197 - 254 1 1 118 25.6 0.5 5.5 31.6 38.0 60 8 81

058 1 208-230 197 - 254 1 1 150 27.2 0.5 5.5 33.2 40.0 60 8 77

070 1 208-230 197 - 254 1 1 150 27.2 0.5 5.5 33.2 40.0 60 8 77

Page 34: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

33RWT Series Catalog - August 2010 Roth

ElectricalData:DualCompressorUnits

Model VoltageCode

60 Hz Power Compressor HWGPump

FLA

Ext Loop PumpFLA*

total unitFLA

MinCircuitAMPS

Max Fuse

HACr

Min AWG

Max FtVoltage Min/Max Phase QtY LrA rLA

092 1 208-230 197 - 254 1 2 118 EA.

25.6 EA. N/A N/A 51.2 57.6 80 4 126

120 1 208-230 197 - 254 1 2 158.0Each

30.1Each N/A N/A 60.2 67.7 90 4 107

144 1 208-230 197 - 254 1 2 148.0Each

32.1Each N/A N/A 64.2 72.2 100 3 129

Notes:1. All line and low voltage wiring must adhere to the National Electrical Code and Local Codes, whichever is the most stringent. 2. Wire length based on a one way measurement with a 2% voltage drop. 3. Wire size based on 60°C copper conductor and minimum circuit ampacity. 3. All fuses class rK-54. Min/Max Voltage: 208-230/60/1 = 197/243

Page 35: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

34Roth RWT Series Catalog - August 2010

ElectricalData:AirHandlers

Model

60 HZ PowerSinglePhaseVolts

Motor Amps /

HP

Electric Heater Data Minimum Circuit Ampacity Maximum overcurrent Protection

# of Circuits kW

Amps115V

Amps208V

Amps208V

Amps240V

Amps240V

MCA115V

MCA208V

MCA208V

MCA240V

MCA240V

MoCP115V

MoCP208V

MoCP208V

MoCP240V

MoCP240V

Cr 1 Cr 1 Cr 2 Cr 1 Cr 2 Cr 1 Cr 1 Cr 2 Cr 1 Cr 2 Cr 1 Cr 1 Cr 2 Cr 1 Cr 2

024

208/240 2.8 / 0.33 0 0 - - - - - - 3.5 - 3.5 - - 10.0 - 10.0 -

208/240 2.8 / 0.33 1 5 - 18.0 - 20.8 - - 25.3 - 28.8 - - 35.0 - 35.0 -

208/240 2.8 / 0.33 1 10 - 36.1 - 41.7 - - 47.9 - 54.9 - - 60.0 - 60.0 -

115 5.0 / 0.33 0 0 5.0 - - - - 6.3 - - - - 10.0 - - - -

036

208/240 4.3 / 0.50 0 0 - - - - - - 5.4 - 5.4 - - 10.0 - 10.0 -

208/240 4.3 / 0.50 1 5 - 18.0 - 20.8 - - 26.8 - 30.3 - - 35.0 - 40.0 -

208/240 4.3 / 0.50 1 10 - 36.1 - 41.7 - - 49.4 - 56.4 - - 60.0 - 60.0 -

208/240 4.3 / 0.50 2 15 18.0 36.1 20.8 41.7 26.8 49.4 30.3 56.4 35.0 60.0 40.0 60.0

115 7.7 / 0.50 0 0 7.7 - - - - 9.6 - - - - 15.0 - - - -

048-060

208/240 6.8 / 0.75 0 0 - - - - - - 8.5 - 8.5 - - 15.0 - 15.0 -

208/240 6.8 / 0.75 1 5 - 18.0 - 20.8 - - 29.3 - 32.8 - - 35.0 - 40.0 -

208/240 6.8 / 0.75 1 10 - 36.1 - 41.7 - - 51.9 - 58.9 - - 60.0 - 70.0 -

208/240 6.8 / 0.75 2 15 - 18.0 36.1 20.8 41.7 - 29.3 51.9 32.8 58.9 - 35.0 60.0 40.0 70.0

208/240 6.8 / 0.75 2 20 - 36.1 36.1 41.7 41.7 - 51.9 51.9 58.9 58.9 - 60.0 60.0 70.0 70.0

115 12.8 / 1.0 0 0 12.8 - - - - 16.0 - - - - 20.0 - - - -

Notes:1. Always refer to unit nameplate data prior to installation2. Maximum overcurrent device, overcurrent protection installed on breaker are sized per MCA

Page 36: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

35RWT Series Catalog - August 2010 Roth

Controls

MiCrOPrOCeSSOr FeATUreS AND OPerATiON Roth’s geothermal heat pump controls provide a unique modular approach for controlling heat pump operation. The control system uses one, two, or three printed circuit boards, depending upon the features of a particular unit. This approach simplifies installation and troubleshooting, and also eliminates features that are not applicable for some units.

A microprocessor-based printed circuit board controls the inputs to the unit as well as outputs for status mode, faults, and diagnostics. A status LED and an LED for each fault is provided for diagnostics.

Removable low voltage terminal strips provide all necessary terminals for field connections. Not only are the thermostat inputs included, but there are also removable terminal strips for all of the accessory wiring for ease of installation and troubleshooting. Startup/random StartThe unit will not operate until all the inputs and safety controls are checked for normal conditions. At first power-up, the compressor is energized after a five minute delay. In addition, a zero to sixty second random start delay is added at first power-up to avoid multiple units from being energized at the same time.

Short Cycle Protection A built-in five minute anti-short cycle timer provides short cycle protection of the compressor.

Component Sequencing DelaysComponents are sequenced and delayed for optimum space conditioning performance and to make any startup noise less noticeable.

Test Mode The microprocessor control allows the technician to shorten most timing delays for faster diagnostics by changing the position of a jumper located on the lockout board.

Water Solenoid Valve Connections Two accessory relay outputs at the terminal strip provide a field connection for two types of water solenoid valves, a standard 24VAC solenoid valve, or a 24VAC solenoid valve with an end switch. Additional field wiring is no longer required for operation of the end switch.

Loop Pump Circuit Breakers (Single Compressor Units)The loop pump(s) and desuperheater pump are protected by control box mounted circuit breakers for easy wiring of pumps during installation. Circuit breakers eliminate the need to replace fuses.

Safety Controls The control receives separate signals for high pressure, low pressure, low water flow, and condensate overflow faults. Upon a continuous 30-second measurement of the fault (immediate for high pressure), compressor operation is suspended (see Fault Retry below), and the appropriate LED flashes. Once the unit is locked out (see Fault Retry below), an output (terminal “L”) is made available to a fault LED at the thermostat (water-to-water unit has fault LED on the corner post).

Low Pressure: If the low pressure switch is open for 30 continuous seconds, the compressor operation will be interrupted, and the control will go into fault retry mode. At startup, the low pressure switch is not monitored for 90 seconds to avoid nuisance faults.

High Pressure: If the high pressure switch opens, the compressor operation will be interrupted, and the control will go into fault retry mode. There is no delay from the time the switch opens and the board goes into fault retry mode. There is also no delay of switch monitoring at startup.

Flow Switch: If the flow switch is open for 30 continuous seconds, the compressor operation will be interrupted, and the control will go into fault retry mode. At startup, the flow switch is not monitored for 30 seconds to avoid nuisance faults.

Page 37: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

36Roth RWT Series Catalog - August 2010

Controls

FAULT reTry All faults are retried twice before finally locking the unit out. The fault retry feature is designed to prevent nuisance service calls. There is an anti-short cycle period between fault retries. On the third fault, the board will go into lockout mode.

Over/Under Voltage Shutdown The lockout board protects the compressor from operating when an over/under voltage condition exists. The control monitors secondary voltage (24VAC) to determine if an over/under voltage condition is occurring on the primary side of the transformer. For example, if the secondary voltage is 19 VAC, the primary voltage for a 240V unit would be approximately 190V, which is below the minimum voltage (197V) recommended by the compressor manufacturer. This feature is self-resetting. If the voltage comes back within range, normal operation is restored. Therefore, over/under voltage is not a lockout.

Under voltage (18 VAC) causes the compressor to disengage and restart when the voltage

returns to 20 VAC. Over voltage (31 VAC) causes the compressor to disengage and restart when the voltage returns to 29 VAC. During an over or under voltage condition, all five fault LEDs will blink (HP + LP + FS + CO + Status). When voltage returns to normal operation, the four fault LED’s will stop blinking, but the status LED will continue to flash. While the board LEDs are flashing, the thermostat fault light will be illuminated.

intelligent reset If the thermostat is powered off and back on (soft reset), the board will reset, but the last fault will be stored in memory for ease of troubleshooting. If power is interrupted to the board, the fault memory will be cleared.

Diagnostics The lockout board includes five LEDs (status, high pressure, low pressure, low water flow, condensate overflow) for fast and simple control board diagnosis. Below is a table showing LED function.

LED Color Location1 Function Normal operation Fault retry2 Lockout2

Green top High Pressure oFF Flashing3 oN3

orange 2nd Low Pressure oFF Flashing3 oN3

red 3rd Water Flow oFF Flashing3 oN3

Yellow Not applicable on water-to-water units

Green Bottom Status Flashing4 Flashing5 Flashing4

Notes:1. Looking at the board when the LEDs are on the right hand side2. If all five lights are flashing, the fault is over/under voltage3. only the light associated with the particular fault/lockout will be on or flashing.

For example, if a high pressure lockout has occurred, the top green light will be on. the orange, red, and yellow lights will be off

4. Status lights will be off when in test mode5. Flashes alternately with the fault LED

LED Identification

Page 38: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

37RWT Series Catalog - August 2010 Roth

Controls

Hot Water Pump Control Controls for high water temperature and low compressor discharge line temperature prevent the hot water (desuperheater) pump from operating when the leaving water temperature is above 130°F, or when the compressor discharge line is too cool to provide adequate water heating.

Lockout Board Jumper SelectionThe lockout board includes three jumpers for field selection of various board features.

Water Solenoid Valve Delay (WSD): When the WSD jumper is installed, the “A” terminal is energized when the compressor is energized. When the jumper is removed, the “A” terminal is energized 10 seconds after the compressor. If using the Taco water solenoid valve (or a valve with an end switch), the unit terminal strip includes a means for connecting a valve of this type. The WSD jumper should be installed. If using a slow opening valve that does not have an end switch, the jumper should be removed.

Test Mode (TEST): When the TEST jumper is installed, the board operates in the normal mode. When the jumper is removed, the board operates in test mode, which speeds up all delays for easier troubleshooting. When service is complete, the jumper must be re-installed in order to make sure that the unit operates with normal sequencing delays.

Over/Under Voltage Disable (O/V): When the O/V jumper is installed, the over/under voltage feature is active. When the jumper is removed, the over/under voltage feature is disabled. On rare occasions, variations in voltage will be outside the range of the over/under voltage feature, which may require removal of the jumper. However, removal of the jumper could cause the unit to run under adverse conditions, and therefore should not be removed without contacting technical services. An over/under voltage condition could cause premature component failure or damage to the unit controls. Any condition that would cause

this fault must be thoroughly investigated before taking any action regarding the jumper removal. Likely causes of an over/under voltage condition include power company transformer selection, insufficient entrance wire sizing, defective breaker panel, incorrect transformer tap (unit control box), or other power-related issues.

Lockout Board Layout

ACRYLO

CCG

CC HPHPLPLPFSFSCOCO

LockoutBoard

Status

R2 R1 C2 C1

WSDTESTO/V

SeqUeNCe OF OPerATiON:Water-to-Water Units, Single Compressor

Heating first stage (Y1)The compressor (first stage) and loop/desuperheater pump(s) are energized 10 seconds after the “Y1” input is received.

Heating second stage (Y1, Y2)The compressor solenoid is energized immediately upon receiving a “Y2” input, switching the compressor to full load.

Cooling OperationThe reversing valve is energized for cooling operation. Terminal “O” is connected to the reversing valve solenoid.

Cooling first stage (Y1, O)The compressor (first stage) and loop/desuperheater pump(s) are energized 10 seconds after the “Y1” input is received.

Page 39: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

38Roth RWT Series Catalog - August 2010

Controls

Cooling second stage (Y1, Y2, O)The compressor solenoid is energized immediately upon receiving a “Y2” input, switching the compressor to full load.

SeqUeNCe OF OPerATiON:Water-to-Water Units, Dual Compressors

Heating first stage (Y1)Both compressors are energized in first stage 10 seconds after the “Y1” input is received.

Heating second stage (Y1, Y2)Both compressor solenoids are energized immediately upon receiving a “Y2” input, switching the compressors to full load.

Cooling OperationThe reversing valve is energized for cooling operation. Terminal “O” is connected to the reversing valve solenoid.

Cooling first stage (Y1, O)Both compressors are energized in first stage 10 seconds after the “Y1” input is received.

Cooling second stage (Y1, Y2, O)Both compressor solenoids are energized immediately upon receiving a “Y2” input, switching the compressors to full load.

HyDrONiC Air HANDLer:ECM fan/hydronic chilled water/hot water coil

Thermostat Wiring / Fan Speed Notes For two-stage thermostats, use both Y1 and Y2. For single stage thermostats, jumper Y1 and Y2, and use the “CFM Y2” column in table 6b for determining jumper location. The ECM control board in the air handler is the thermostat connection point. Wire nut the thermostat wiring to the “pigtails” connected to the 1/4” spades on the ECM board.

For dehumidification in cooling, cut the resistor at the “DEHUMIDIFY” LED. Use either the HUM terminal (reverse logic -- designed to be used with a humidistat) to lower the fan speed when

ModelCool/Heat

Jumpers

High Spd Cfm Y2

Low Spd Cfm Y1 Fan G

MPH024

A 880 490 440

B 789 440 395

C 690 390 345

D 584 330 300

MPH036

A 1058 730 530

B 1023 710 510

C 831 575 415

D 657 455 330

MPH048

A 1952 1235 975

B 1761 1115 880

C 1564 990 780

D 1385 875 695

MPH060

A 1952 1235 975

B 1761 1115 880

C 1564 990 780

D 1385 875 695

MPH Air Handler Fan Speeds

NotES:1. the CooL and HEAt jumpers should both be set at the

same position. 2. the ADJuSt jumper provides for a +/- 15% adjustment.

eCM Board (Air Handler Board)

GY1Y2O

W1EMC1R

HUM

ECM Control Board (MPD series)

CFM

COOL HEAT ADJUST

DEHUMIDIFY

Low VoltageConnection

to ECM Motor

DCBA

DCBA

TEST(-)(+)NORM

CUT TO ENABLE

MPH Series

dehumidification is needed, or if the HUM terminal is not connected (and the resistor is cut), the air handler will operate at a lower fan speed in cooling and normal fan speed in heating.

Page 40: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

39RWT Series Catalog - August 2010 Roth

WiringDiagrams:SingleCompressorUnits

2 STAGE AquASTAT

R1 Y1 Y2

Page 41: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

40Roth RWT Series Catalog - August 2010

WiringDiagrams:DualCompressorUnits

Page 42: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

41RWT Series Catalog - August 2010 Roth

EngineeringSpecifications

Generalthe Geothermal Heat Pump system and the earth loop system shall be one system and include all interconnecting piping and controls to provide an efficient, harmoniously balanced package. All units shall be tested and rated by EtL in accordance with uL and CSA test laboratory safety and performance standards. Each unit shall be mounted on a pallet and shrinkwrapped. units shall be designed to operate with entering liquid temperature between 25°F and 110°F.

refrigerant CircuitCompressor(s) shall be hermetically sealed high efficient scroll, mounted on vibration isolators. the coaxial water heat exchanger shall be designed for low water pressure drop and constructed of a cupro-nickel inner tube and a steel outer tube with enhanced heat exchanger surface. An optional domestic water desuperheater coil of vented double wall copper construction for potable water with high limit control shall be employed. the thermostatic expansion device shall be a bi-directional mechanical controlled and shall provide proper superheat over the entire liquid temperature range with minimal hunting. the reversing valve shall be of copper construction with a 24V solenoid valve with fail-to-heating position.

Cabinetthe cabinet shall be of heavy gauge steel. It shall be bolted together, and be installed with high-density insulation, with smoke and flame spread of class 1 type and acoustic value of NrC .45. It shall be oriented to allow complete component service access from all sides. Electrical box shall be of heavy gauge steel located on the access panel side of the cabinet.

Controlsunits shall incorporate a microprocessor based control board. Equipment shall incorporate both high and low pressure switches and freeze protection with total refrigerant circuit lockout with manual reset. the board shall provide detachable terminal block, LED status, fault indicators, fault memory and accessory output.

Piping & ConnectionsLoop water connections (supply/return) shall be ¾” or 1-inch FPt brass swivel connection, which provide a union for easy connection. Larger units (092) fitting shall be female copper (1 to 1½) connection. All water piping shall be insulated.

Note: Copper is the only acceptable material for pipingthe desuperheater.

Page 43: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

42Roth RWT Series Catalog - August 2010

Options&Accessories

Desuperheateroptional desuperheater package of vented double wall copper constructed heat exchanger coil suitable for potable water shall be provided. the heat exchanger and hot water circulating pump shall be factory installed inside the cabinet. For 3-phase units, the hot water circulating pump(s) shall be field furnished, and field installed in the hot water piping outside the unit cabinet.

Field Installed Hydronic Pump Module (Flow Center)Pump module shall be self contained and provide all liquid flow, liquid fill and connection required for earth loop system. the pumps shall be wired to the pump terminal strip inside unit electric box.

Page 44: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

43RWT Series Catalog - August 2010 Roth

STANDARD RESIDENTIAL WARRANTY Roth Industries, Inc. for brand: “TerraStar” Residential Single Family 10 YEAR LIMITED WARRANTY (10/5/5) Roth Industries, Inc. warrants the refrigerant system components, to include the compressor, air coil, coaxial heat exchanger(s), expansion valve and reversing valve, to be free from defects in material and workmanship for a period of ten (10) years from the date of delivery to the original purchaser-user, transferable to new owner. Roth Industries, Inc. warrants it’s geothermal unit against defect in materials and workmanship for five (5) years from the date of delivery to the original purchaser-user, excluding damage due to rough handling, abuse, accident or casualty loss, exposure to outdoor elements/outdoor installation, including but not limited to: salt air exposure, damage caused by exposure to the following (whether indoors or outdoors): chlorine, airborne contaminants, other corrosive elements in the atmosphere, swimming pools, or hot tubs, transferable to new owner. NOTE: Accessories included in the original installation (thermostat, flow center, auxiliary heater) are covered by this five (5) year warranty but are not included in owner transfer. Roth Industries, Inc. warrants the service labor allowances for five (5) years (second through the fifth years with the dealer/installer warranting the first year) from date of delivery to the original purchaser/user, transferable to new owner, for the servicing, removing or reinstalling parts for the refrigerant system, or for any defect in materials and workmanship inside the unit as set forth above. NOTE: Labor allowances may not cover the full amount of labor charged, depending on the servicing contractor. CONDITIONS AND EXCLUSIONS: The Limited Warranty only applies if the following conditions are met. A) This Limited Warranty will not apply and shall be null and void if the Roth Industries, Inc. serial number has been altered, defaced or removed. B) This Limited Warranty shall be null and void if the Roth Industries, Inc. unit has been disconnected or removed from the location of original installation, or if the dealer/installer has not been paid in full. C) This Limited Warranty shall not apply to unit failure or defunct caused by improper installation, field modification, improper supply voltage, improper maintenance or misuse including operation during building construction, corrosion caused by airborne contaminants, chlorine or salt air exposure, corrosive liquids or water, abuse, neglect, Act of God, outdoor installation or storage prior to installation, damage from abuse, accident, fire, flood, and the like, or to defects or damage caused by the use of any attachment, accessory or component not authorized by Roth Industries, Inc. D) Replacement or repaired parts and components are warranted only for the remainder of the original warranty period, as stated above. E) This Limited Warranty applies only to Roth Industries, Inc. units installed by a factory trained, independent , Dealer of Roth Industries, Inc. in the United States or Canada, and subjected to normal usage as described and rated on the applicable specification sheet for each unit. This warranty shall not be valid if equipment is not installed in accordance with methods prescribed on our technical data and manuals and in compliance with local codes. Dealer must complete the warranty registration card supplied with the Roth Industries, Inc. unit which must then be endorsed by the original purchaser-user and mailed within ten (10) days after initial installation. If warranty registration card is not returned, warranty shall commence at date unit was shipped from Roth Industries, Inc. manufacturing facility. F) The obligation for Roth Industries, Inc. under this Limited Warranty is expressly limited to replacement of any parts or components as specified and found within the cabinet. Roth Industries, Inc. reserves the right to replace defective components under warranty with new or reconditioned parts. Except as set forth above, this warranty does not cover any labor expenses for service, nor for removing or reinstalling parts. Accessory, peripheral and ancillary parts and equipment are not covered by this warranty. G) Roth Industries, Inc. does not warrant equipment which has been custom built or modified to purchaser-user specifications. Likewise, any field modification of any equipment shall also void this, and any and all warranties. Notice: Outdoor or unconditioned space installation or storage prior to installation of any equipment shall cause this and all warranties to be deemed void. SHIPPING COSTS: The purchaser-user will be responsible for the cost of shipping warranty replacement parts from the Roth Industries, Inc. manufacturing location to the distributor of the parts. Purchaser-user is also responsible for any shipping cost of returning the failed part to the distributor. THE FOREGOING LIMITIED WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES (AND IMPIED CONDITIONS IN CANADA), EXPRESSED, IMPLIED, AND STATUTORY, INCLUDING WITHOUT LIMITATAION, THE IMPLIED WARRANTIES OF MERCHANTABILITY, AND FITNESS FOR A PARTICULAR PURPOSE, AND ALL SUCH WARRANTIES EXPRESSED OR IMPLIED, ARE EXCLUDED AND SHALL NOT APPLY TO THE GOODS SOLD. IN NO EVENT SHALL WARRANTOR BE LIABLE FOR DIRECT, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES RESULTING FROM ANY DEFECT IN THE GOODS EXCEPT TO THE EXTENT SET FORTH HEREIN. (Some states do not allow exclusion or limitation of implied warranties or liability for incidental or consequential damage). For additional information or assistance, contact the WARRANTOR, which is: Roth Industries, Inc., 268 Bellew Ave. S., Watertown, NY 13601

Page 45: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

44Roth RWT Series Catalog - August 2010

Page 46: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

45RWT Series Catalog - August 2010 Roth

Revision Table

Date: By: Page: Description:

August 2010 Kt All First Published

Page 47: ROTH TerraStar Heat Pumps W-Series WATER-TO-WATER · with 3/8” recycled blue-jean insulation (foil faced) for quiet operation and easy clean up. Another noise reduction feature

Roth Industries, Inc.P.O. Box 245

Syracuse, NY 13211

888-266-7684 US800-969-7684 CAN866-462-2914 FAX

[email protected]

* AHRI certification is shown as the Roth brand under the Enertech Manufacturing certification reference number**Roth Industries geothermal heat pumps are shown as a multiple listing of Enertech Manufacturing’s ETL certification*** Roth geothermal heat pumps are listed as a brand under Enertech Manufacturing’s Energy Star ratings

** * ***