ROOM AIR CONDITIONER For Split AC Domestic Models TYPE : WALL MOUNTED P/No. MFL39754865_V3 MFL39754865 Regd. Office: LG Electronics India Pvt. Ltd., A Wing (3rd Floor), D-3, District Center, Saket, New Delhi - 110017 Please read this manual carefully before operating your set and retain it for future reference.

Upload: others

Post on 25-Jun-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

ROOM AIR CONDITIONER

For Split AC Domestic Models

TYPE : WALL MOUNTED

P/No. MFL39754865_V3MFL39754865

Regd. Office: LG Electronics India Pvt. Ltd., A Wing (3rd Floor), D-3, District Center, Saket, New Delhi - 110017

Please read this manual carefully before operatingyour set and retain it for future reference.

Page 2: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

BEFORE

– Prior to operation– Components– Electrical Safety– Using the remote control

Inserting BatteriesInstalling the remote control holderWireless Remote Control

BASIC FUNCTIONS

Cooling your roomHeating your roomRemoving humidityAiring your roomAdjusting the fan speedAdjusting the air flow directionSetting the timer– Setting the current time– Turning ON the air conditioner automatically at a set time– Turning OFF the air conditioner automatically at a set time– Cancelling the timer setting- Setting sleep mode

ADVANCED FUNCTIONSChanging room temperature quicklyIndoor air purification– Auto Clean operationEnergy saving cooling modeAuto operationDimmerAuto ChangeoverMosquito away operationOperating the air conditioner without theremote controlRestarting the air conditioner automatically

MAINTENANCE

– Cleaning the air filter– Cleaning the anti-allergy filter– Cleaning the plasma filter

TROUBLESHOOTING

– Self-diagnosis function– Before requesting service

• Contact the authorized service technician for repair ormaintenance of this unit.

• Please install your air-conditioner by companyauthorized service franchisee / authorized serviceand sales dealer.

• The air conditioner is not intended for use by youngchildren or invalids without supervision.

• Young children should be supervised to ensure thatthey do not play with the air conditioner.

• When the power cord is to be replaced, replacementwork shall be performed by authorized personnel only,using only genuine replacement parts.

We recommend usage of voltage stabilizer with

high / low voltage cut off in areas having voltage

fluctuations.

AC TONNAGE STABILIZER KVA(3-STEP STABILIZER)

1.0

1.5

2.0

3

4

5

CAUTION

Cleaning the Micro Protection filter.Outdoor Unit

2

SAFETY INSTRUCTION

3

4

8

12

15

18

21

Page 3: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

3

reduce the cooling / dehumidification functions.

Avoid excessive cooling

(Refer page no. 19 and 20 details of owner's manual).

Page 4: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

4SAFETY INSTRUCTIONS

Page 5: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

5

Be sure to use only those parts which are listed in the service parts list. Never attempt to modify the equipment. It may result in death, serious injury, effect on product performance or product failure.

Only use the refrigerant specified on the air conditioner label. Failure to do so may result in explosionor fire.

SAFETY INSTRUCTIONS

Dos and Don’ts

Do not install the air conditioner on an unstable surface or where there may be a danger of unit falling

It may result in death, serious injury, or product failure.

Only use components that are approved by the manufacturer and do not repair or modify them.Failure to do so may result in electric shock, effect on product performance or product failure.

enter

Page 6: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

For inner cleaning, contact an Authorized Service Center or a dealer. Do not use harsh detergent thatcauses corrosion or damage on the unit. Harsh detergent that causes failure or product, fire or electronic shock

6 SAFETY INSTRUCTIONS

Dos & Don'ts

ON OFF

When there is a gas leak, before using air conditioner again contact authorized service person for verification and repair. Failure to do so may result in explosion or fire.

Do not block the inlet or outlet of air flow. It may effect product performance.

or serious injury.

or health complications.

effect product performance.

water leakage or product failure.

tonot cause

,

neighbours. neighbours.

It may effect product performance.

Page 7: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

Disposal of your old appliance (as per e-waste Rules)1. When this crossed out wheeled bin symbol is depicted on

the product and its operator’s manual, it means the product is covered by the e-waste Management and Handling Rules, 2011 and are meant to be recycled, dismantled, refurbished or disposed off.

2. Dos

a. The product is required to be handed over only to the authorized recycler for disposal.

b. Keep the product in isolated area, after it becomes non-functional/un-repairable so as to prevent its accidental breakage.

Don’t

a. The product should not be opened by the user himself/herself, but only by authorized service p e rsonnel.

b. The product is not meant for re-sale to any unauthorized agencies/scrap dealer/ kabariwalah.

c. The product is not meant for mixing into household waste stream.

d. Do not keep any replaced spare part(s) from the product in exposed area.

3. Any disposal through unauthorized agencies/person will attract action under Environment (Protection) Act 1986 .

4. Hazards of improper handling or accidental breakage

a. If batteries are disposed incorrectly, it can greatly harm the environment. The chemical by-products are hazardous.T he metals and chemicals

found in batteries can mix into soil which may be hazardous to humans, plants and animals. If thrown in fire, they can cause blast and release toxic gases which may be harmful for health.

b. The refrigerant (R-22) used can be combustible at low pressure. The potential health effects of over exposure is dizziness, headache and

heart irregularities.

5. To locate a nearest collection centre or call for pick-up (limited area only) for disposal of this appliance, please contact Toll Free No.1800-180-9999 for details. All collection centre and pick up facilities are done by third parties with LG Electronics India Pvt. Ltd. merely as a facilitator.

For more detailed information , please visit : http://www.lg.com

vius iqjkus midj.k dk fuiVku ¼bZ&vif’k"V fu;e ds vuqlkj½1- tc bl dkVs x;s ifg;s okys fcu dk fpº+u fdlh midj.k vkSj

blds vksisjVj dh iqfLrdk ds lkFk layXu gksrk gSa rks bldk eryc gS fd bls "bZ&vif'k"V" ¼izca/ku vkSj gFkkyu½ fu;e 2011 ds vUrxZr lfEefyr fd;k x;k gS] vkSj bls uohuhdj.k] fo?kVu vkSj fuiVku ds fy, cuk;k x;k gSA

2- djsa& d& midj.k dks flQZ vf/kd`r iqu% uohuhdj.kdrkZ dks gh fuiVkj.k

djus gsrq gLrkarfjr djsaA [k& tc midj.k dk;Zjr u gks bls vyx {ks= esa j[kas rkfd midj.k ls gksus okyh

nq?kZVukvks ls cpk tk ldsA uk djsa& d& bl midj.k dks Lo;a/[kqn ugha [kksyuk pkfg, midj.k dks dsoy vf/kd`r !

vf/kdkjh ds }kjk gh [kksyk tkuk pkfg,A [k&bl midj.k dks iqu% fcØh ds fy, fdlh Hkh dckM+hokyk@Hkaxkj okyk@vukf/kd`r

laLFkk dks u nsaA x& bl midj.k dks fdlh ?kjsyw vif'k"V lkeku ds lkFk feykdj u j[ksaA ?k& midj.k ds cnys gq, ;k vkrafjd iqjtks dks [kqys {ks= esa u j[ksaA3- ;fn fdlh vukf/kd`r foHkkx ;k O;fDr ds }kjk fuiVkj.k fd;k tkrk gS rks ;g i;kZoj.k

¼lqj{kk½ /kkjk 1986 ds vUrxZr vkrk gSA4- nq?kZVukxzLr VwV@QwV rFkk vO;ofLFkr j[k&j[kko ls cps A d& ;fn cSVfj;ksa dk fuiVkj.k v'kq) :i ls dj jgs gaS] rks ;g okrkoj.k dks cgqr

uqdlku igqqWpk ldrk gSaA jklk;fud midj.k [krjukd gksrs gaSA tks jlk;u vkSj /kkrq cSVfj;ksa esa ik, tkrs gaS] bls feV~Vh esa feykus ij ;g euq";ksa] ikS/kksa vkSj i'kqvksa ds fy, [krjukd gks ldrh gaSA ;fn bls vkx esa Qsadrs gaS rks ;s foLQksV dj ldrh gaS vkSj ;s tgjhyh xSlsa ns ldrk gS tks LokLF; ds fy, gkfudkjd gaSA

[k& jsÝhtjsaV ¼R-22½ de ncko ij ngu'khy gks ldrh gaS rFkk blls LokLF; ij nqLizHkko iM+ ldrk gS tSls pDdj vkuk] flj nnZ vkSj g`n; xfr :dukA

5- mijksDr inkFkksZ ds fuiVkju ds fy, utnhdh fuiVkju laLFkku ¼ladh.kZ {ks=½ esa dkWy djsaA vf/kd tkudkjh ds fy, gekjs Vksy Ýh uEcj 1800-180-9999 ij dkWy djsaA lHkh laxzg.k dsUnz o fid&vi dh lqfo/kk,a FkMZ&ikVhZ ls tks "LG Electronics India Pvt. Ltd" dks viuh lsok,a iznku dj jgh gksa] ls djok,aA

vf/kd tkudkjh ds fy, ns[ksa osclkbV % http://www.lg.com

7SAFETY INSTRUCTIONS

remote

may effect product performance or

electric shock or serious injury.

Page 8: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

Prior to Operation

Preparing for Operation

1. Contact an installation specialist for installation.

2. Plug in the power plug properly.3. Use a dedicated circuit breaker.4. Do not use an extension cord.5. Do not start/stop operation by plugging/

unplugging the power cord.6. If the cord/plug is damaged, replace it with

only an authorized replacement part.

Usage

1. Being exposed to direct airflow for a long time may be hazardous to your health. Do not expose occupants, pets, or plants to direct airflow for a long time.

2. Due to the possibility of oxygen deficiency, ventilate the room when using the appliance together with stoves or other heating devices.

3. Do not use this air conditioner for non-specified special purpose (e.g. preserving precision devices, food, pets, plants, or art objects). Such use may damage your properties.

Cleaning and Maintenance

1. Do not touch the metal parts of the unit when removing the filter. Injury can occur.

2. Do not use water to clean inside the air conditioner. Exposure to water can destroy the insulation, leading to electric shock or effect product performance.

3. When cleaning the unit, first make sure that the power and breaker are turned off. The fan rotates at a very high speed during operation. There is a possibility of injury if the unit’s power is triggered while cleaning inner parts of the unit.

Service

For repair and maintenance, contact your authorized service dealer.

Page 9: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

Components

Symbols used in this Manual

This symbol alerts you to the risk of electric shock.

This symbol alerts you to hazards that may cause harm to the

air conditioner.

This symbol indicates special notes.

Air Intake Vents

Air Outlet Vents

ConnectingWires

Piping

Drain HoseBase Plate

Indoor unit

Outdoor unit

This appliance should be installed in accordance with national wiring regulations. This guide acts as aguide to help to explain product features.

Front PanelAir Filter

Air Inlet

Signal Receiver

WARNING

Features

Page 10: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

Electrical Safety

• This appliance must be properly grounded. To minimize the risk of electric shock, you must always plug into a grounded outlet.

• Do not cut or remove the grounding.

• Attaching the adapter ground terminal to the wall receptacle cover screw does not ground the appliance unless the cover screw is metal and not insulated, and the wall receptacle is grounded through the house wiring.

• If you have any doubt whether the air conditioner is properly grounded, check the wall receptacle and circuit checked by a qualified electrician.

WARNING

Using the remote control

Page 11: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

Using the remote control

You can operate the air conditioner more conveniently with the remote control.

Wireless remote control

Used to circu-Air Circulation buttonlate the room air without cooling orheating.

Sets thesleep mode auto operation.

Ad-justs the desired temperature when cool-ing and heating.

fan speed.

air flow direction.

-

-

Use to remove excess moisture.M’SOON

H’COOL button : Cools down the indoor temperature within a short period of time

the start / end time

display ON or OFF.

AM ON

OFF

A/CLEAN

Turn indoor unit

controller settings.remote

LIGHT

H’COOL

Used tostart or stop Mosquito Away operationMosquito Away operation button

DisplayScreen

ControlPanel

M’SOONFAN

2

H’COOL

M

M

LIGHT

DisplayScreen

ControlPanel

2

H’COOL

M’SOON

M

LIGHT

Symbol is for indoor unit display ON/OFF not remote controller.

Signal Transmitter

Signal Transmitter

Turns the air conditioner ON/OFFON/OFF button :

and set current time.

Page 12: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

12

BASIC FUNCTIONSCooling your room(Cooling operation)1 Press to turn on the power.

2 Press repeatedly to select the cooling

operation.- is displayed on the display screen.

3 Press or to set the desired

- The temperature range is 18°C - 30°C

Heating your room(Heating operation)

1 Press to turn on the power.

2 Press repeatedly to select the heating

operation.

- is displayed on the display screen.

3 Press or to set the desired tempera-ture.

- The temperature range is 16°C - 30°C

Removing humidity (Cooling Mode Only)(Monsoon operation)This mode removes excess moisture from environment with high humidity or in the rainyseason, in order to prevent mold from settingin. This mode adjusts the room temperatureand the fan speed automatically to maintainthe optimal level of humidity.

1 Press to turn on the power.

2 Press to select the monsoon operation.

- is displayed on the display screen.

NOTE!Cooling-only models do not support thisfunction.

M’SOON

NOTE!• In this mode you cannot adjust the room

temperature, as it is adjusted automati-cally. Also, the room temperature is notdisplayed on the display screen.

• In this mode indoor unit fan and outdoor unit will be OFF intermittently.• To Exit from Monsoon mode press

key or key or key

BASIC FUNCTIONS

temperature.

H’COOL

M

M

Page 13: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

13

Adjusting the air flow direc-tion1 To adjust the direction of the flow verti-

cally, press change the air flow direc-

tion automatically.

- This function is apply for only turn SWING On/Off.

2 To adjust the direction of the flow horizon-tally, press change the air flow direc-

tion automatically.

- This function is apply for only turn SWING On/Off.

Setting the timerYou can use the timer function to save energyand to use the air conditioner more efficiently.

Setting the current time1 Press and hold it for longer than 3 sec-

onds.

- The AM/PM icon flickers at the bottom ofthe display screen.

NOTE!• Adjusting the air flow direction horizon-

tally may not be supported, dependingon the model.

• Adjusting the air deflector arbitrarily maycause product failure.

• If you restart the air conditioner, it startsto operate with the previously set direc-tion of air flow, so the air deflector maynot match the icon displayed on the re-mote control. When this occurs, press

or to adjust the direction of

the air flow again.

Airing your room(Air Circulation operation)This mode only circulates the indoor air

without changing the room temperature.

3 Press to adjust the fan speed.

Adjusting the fan speed1 Press repeatedly to adjust the fan

speed.

- Select if you want natural air. The fan speed adjusts automatically.

Natural wind (CHAOS Logic)For fresher feeling, press the INDOOR FANSPEED SELECTION BUTTON and set toNatural wind mode ( ).In this mode, the wind blows like a naturalbreeze by automatically changing fan speed.

is displayed on the display screen.

1 Press to turn on the power.

2 Fan button : Press turn on the air

circulation operation.

-

FAN

Page 14: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

14

2 Press or to select .

3 Press to finish.

Turning ON the air conditioner auto-matically at a set time1 Press

- The icon below flickers at the bottom ofthe display screen.

2 Press or to select

3 Press to finish.

4 When setting the timer, current time and

times.

ON icon are displayed on the displayscreen indicating that the ON TIMER isset.

Turning OFF the air conditioner auto-matically at a set time1 Press

- The icon below flickers at the bottom ofthe display screen.

2 Press or to select

3 Press to finish.

4 When setting the timer, current time and

the times.

OFF icon are displayed on the displayscreen indicating that the OFF TIMER isset.

Canceling the timer setting1 Press or to select the timer setting

to cancel.

2 Press

- To cancel all timer settings, press

Setting sleep modeUse the sleep mode to turn OFF the air condi-tioner automatically when you go to sleep.

1 Press to turn on the power.

2 Press

3 Press or to select the hour

(up to 7 hours).

4 Press to finish.

- is displayed on the display screen insleep mode.

desired time.

desired time.

desired time.

This mode does not have auto restartfeature.

(The timer lamp on the air conditioner andthe display will go off.)

The sleep mode will operate indoor fan atsuper low speed in cooling mode and at lowspeed in heating mode for pleasant sleep

In cooling mode or Monsoon mode:

The setting temperature will rise automaticallytwo times by 1°C over next consecutive 30minutes (Maximum 2°C) for a comfortablesleep.This will be the final setting temperature aslong as sleep mode is functioning.After completion of set time unit will switchOFF automatically.

Page 15: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

15

ADVANCED FUNCTIONSThe air conditioner offers some additional ad-vanced functions.

Changing room temperaturequicklyH’COOL(Himalaya)ModeThis mode allows you to cool indoor air quickly

Press

-In H’COOL(Himalaya)mode,30 minutes strong focused air blows out for faster cooling.

Indoor air purificationAuto Clean operationIn the cooling and monsoon operations,moisture is generated inside the indoor unit.Use the auto cleaning function to removesuch moisture.

2 Press - is displayed on the display screen.

1 Press to turn on the power.

- If you turn off the power, the fan oper-ates for 30 minutes and cleans the insideof the indoor unit.

NOTE!Some buttons cannot be used while theauto cleaning function is in operation.

During Auto Clean function, “Co” willbe displayed on the unit.

Power saving lamp blink dependingon the model.

Energy saving cooling modeThis mode minimizes power consumption dur-ing cooling and increases the set temperatureto the optimal level for a more comfortable en-vironment.

The temperature automatically sets at22°C if ambient temperature is below 22°C.

The temperature maintains if ambient temper-ature is above 22°C

1 Press to turn the power on.

2 Press repeatedly to select the cooling

operation.

3 Press

- is displayed on the display screen.

!This function may not be supported, depending on the model. In Energy SavingCooling Mode, temperature on the displayof the remote controller and air condi-tioner can be different.

NOTE

This mode does not have auto restartfeature.

ADVANCED FUNCTIONS

H’COOL

This mode does not have auto restartfeature.

During & after H'COOL mode swing function will be ON by default.

To OFF swing function Press respectiveswing key.

Page 16: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

AI

AI

AI

16 ADVANCED FUNCTIONS

Auto operation (Optional)(Artificial inelligence)

1 Press to turn on the power.

2 Press repeatedly to select auto operation.

3 Press or to select the desired oper-

ation code if the temperature is higher orlower than the desired temperature.

Code Description

2 Cool1 Cool slightly 0 Maintain

room temperature

-1 Heat slightly -2 Heat

NOTE!• In this mode, you cannot adjust the fan

speed, but you can set the air deflectorto rotate automatically.

• This function may not be supported, de-pending on the model.

In this mode, the fan speed and thetemperature adjust automatically,based on the room temperature.

Dimmer (Optional)

1. 2.

Make sure that remote & Air conditioner are ON.

In Dimmer Mode Unit Display will be turned OFFcompletely but system will be in running state.

Dimmer Mode will be cancelled if any key except is pressed

(Power Keywill turn OFF the Unit).

This function may not be supported by Auto Restart feature (depending onselected models).

Press to activate/deactivate dimmer

function.

Auto Changeover (Optional)

1 Press to turn on the power.

2 Press repeatedly to select auto operation.

This operation is basically heating or cooling function of the air conditioner. But during this operation the controller change the operation mode automatically to keep the temperature within ±2°C with respect to the setting temperature.

Cooling-only models Heat pump models

NOTE!• This function may not be supported, de-

pending on the model.

LIGHT

3 Press or to set the desired

30°C - The temperature range is 18°C - temperature.

4 Press repeatedly to select the fan speed.

- is displayed on the display screen.

Mosquito Away* Operation (Optional)Mosquito Away is a device to radiate frequency which mosquitoes don’t like.

1 Press - To start Mosquito Away function.

2 Press again to finish

NOTE!• You can use this function by pressing without

turning the air conditioner ON. (In this case, Fan speed can not be changed).

At this time horizontal vane will be at default position & the fan speed will be low.

• This function can be used with other function like timer, monsoon.

• This function may not be supported depending on the model.

• The Mosquito Away performance can be different depending on the customer’s environment.

* For detail refer Disclaimer.

Page 17: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

17ADVANCED FUNCTIONS

Open the frontpanel upward

ON/OFFbutton

(Forced Operation)

Heat pump Model*Cooling Model

Room Temp. ³ 24°C 21°C ³ Room Temp. < 24°C Room Temp. < 21°C

Operating mode Cooling Cooling Healthy Dehumidification Heating

Indoor FAN Speed High High High High

Setting Temperature 22°C 22°C 23°C 24°C

If you want to stop the unit, re-press the power button.

8

Open the frontpanel upward

ON/OFFbutton

restart (Optional)

ON/OFF

NOTE!• This function may not be supported, de-

pending on the model.

Page 18: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

consumption.

Micro protection filter*

MAINTENANCE18

Micro Protection filter* Micro Protection filter.1

Use soap solution to clean the heat exchanger coils and the panel vents (consult with technician).

*

OFF

Page 19: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

MAINTENANCE 19

Do not press the mesh

Caution :

Remove the plasma filter after 10 seconds.

Page 20: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

MAINTENANCE20

Cleaning the Micro Protection Filter(Optional)

Micro Protection Filter.

We suggest changing the Micro ProtectionFilter every 6 months.

- Do not wash the Micro Protection Filter with water because the filter can be damaged.

,

For more filters, Please contact theLG service center.(Refer to the warranty card.)

The location of the filters may differ,depending on the model.

The feature can be changed according to type of model.

(Side)

(Rear)

Air intakevents

Air outletvents

Piping

Drain Hose

Dirty or clogged coils will reduce the operating efficiency of the system and cause higher operating costs.

Outdoor UnitThe heat exchanger coils and panel vents of the outdoor unit should be checked regularly. If clogged with dirt or soot, the heat exchanger and panel vents may be professionally steam cleaned.

Page 21: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

TROUBLESHOOTING 21

call

call call

call

There is a burning smell andan abrupt sound comingfrom the unit.

Page 22: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

TROUBLESHOOTING22

Operate the air conditioner on Air circulationmode (Refer to page 13) for 2 to 3 hours.

• This will dry out the internal mechanisms.

When air conditioner is not going to be used for a long time.

When the air conditioner is to be used again.

Turn off the circuit breaker, and disconnectthe plug.

Remove the batteries from the remotecontrol.

Turn off the circuit breaker when the air conditioneris not going to be used for a long time.

Dirt may collect and may cause a fire.

Clean the air filter and install it in the indoorunit.

(Refer to page 19 for cleaning filters.)

Check that the air inlet and outlet of theindoor/outdoor unit are not blocked.

CAUTION

When the air conditioner is not going to be used for a long time.

Tak-tak noise from indoor unit

Contraction or expa-nsion of plastic com-ponents due to chan-ge in temperature

It is a natural phenomenon, and can only be reduced but not overcome completely

Operation rangesFor Heat & Cool model, heating operation range follows the below table.

Heating Operation range

Outdoor temperature

0~24°C

* When the outdoor temperature drops below 0°C, heating capacity may drop slightly depending on the operation condition.

In summer, it may take some time to coolindoor air. In this case, select the H’COOLoperation to cool indoor air quickly.

The auto operation,H’COOL operation or dehumidifying operation is selcted.

The air circulation op-eration or H’COOL oper-ation is selected.

In some operation modes, such as the H’COOL or dehumidifying operation modes, you cannot adjust the fan speed. Select an operation mode in which you can adjust the fan speed.In some operation modes, such as the aircirculation or H’COOL mode, you cannot adjust the temperature. Select an operation mode in which you can adjust the temperature.

Page 23: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

DISCLAIMER 23

IMPORTANT: Long term effect not tested and mosquitoes may become resistant. Mosquito species used in the test below may differ from the mosquito species of your region. This product is one of the ways to manage mosquitoes and not intended to replace other protective devices against mosquitoes.

DISCLAIMER

Test Details: A: Tested by International Institute of Biotechnology and Toxicology (IIBAT), India, According to LG internal

testing method.

Test conducted, three times at temperature of 27±2°C and humidity of 60±10%

Test used two chambers size 3.5m x 2.6m x 2.2m, the chamber with the LG air conditioner assumed to be inside (“inside chamber”) and the chamber without the LG conditioner assumed to be outside (“outside chamber”).

3Cages (25cm ) are placed inside each chamber, connected using netted sleeves to enable the movement of the mosquitoes from one cage to another.

One person is placed inside the chamber to attract mosquitoes

For each test, 50 lab cultured 3-5 days old mosquitoes were placed in the cage in outside chamber; number of mosquitoes coming into the cage in inside chamber was counted every 10 minutes for 90 minutes under 2 settings:

Control setting (low fan ON + mosquito repelling ultrasonic OFF)Treatment setting (low fan ON + mosquito repelling ultrasonic ON)

Test Result:Found to repel on average 81.1% of Aedes aegypti mosquitoes. Repel rate shows percentage of mosquitoes prevented from entering the inside chamber after 90 minutes of Treatment setting compared to Control setting. Represented average of 81.1% derived from 76.9%, 84.6%, 81.8%.

B: Tested by Intertek, Korea, According to LG internal testing method.

Test conducted, three times at temperature of 27±2°C and humidity of 60±10%3 3Test used two chambers size 33m and 19m connected by a channel made of white sheet, small

chamber assumed to be outside (“outside chamber”) and the large chamber to be inside with the LG air conditioner (“inside chamber”)

One person is placed inside the inside chamber to attract mosquitoes

For each test, 50 lab cultured 3-5 days old mosquitoes were released into outside chamber; number of mosquitoes coming into the inside chamber was counted every 10 minutes for 90 minutes under 2 settings:

Control setting (low fan ON + mosquito repelling ultrasonic OFF)

Treatment setting (low fan ON + mosquito repelling ultrasonic ON)

Found to repel on average 72.5% of Aedes aegypti mosquitoes. Repel rate shows percentage of mosquitoes prevented from entering the inside chamber after 90 minutes of Treatment setting compared to Control setting. Represented average of 72.5% derived from 73.1%, 64.3%, 80.0%.

Test Result:

Results may vary in other settings, including but not limited to temperature, humidity, location, space, mosquito species, number of mosquitoes, number of persons, and operation time.

Page 24: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

21 INSTALLATION

- Do not use sea water for this purpose.

windbreak so that outdoor unit

Page 25: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

TEST RUNNING

Bolt

Tubing connection

Check that all tubing and wiring have beenproperly connected.Check that the gas and liquid side service valvesare fully open.

1.

2.

Ensure the difference between the intaketemperature and the discharge is more than 8°C(Cooling) or reversely (Heating).

3.

APrepare remote controlRemove the battery coverby pulling it according to thearrow direction.

Insert new batteries makingsure that the (+) and (–) ofbattery are installed correctly.

Reattach the cover bypushing it back into position.

Use 2 AAA(1.5volt) batteries. Do not use

rechargeable batteries.

Remove the batteries from the remote control if

the system is not going to be used for a long

time.

BSettlement of outdoor unit

Anchor the outdoor unit with a bolt and nut ø10mm)tightly and horizontally on a concrete or rigid mount.

When installing on the wall, roof or rooftop, anchorthe mounting base securely with a nail or wireassuming the influence of wind and earthquake.

In the case when the vibration of the unit isconveyed to the hose, secure the unit with ananti-vibration rubber.

CEvaluation of the performanceOperate unit for 15~20 minutes, then check thesystem refrigerant charge:

Measure the pressure of the gas side servicevalve.

Measure the temperature of the intake anddischarge of air.

1.

2.

Dischargetemperature

Discharge air

Intake temperature

1.

2.

3.

INSTALLATION 20

For reference; the gas side pressure of optimumcondition is as below (Cooling).

4.

If the actual pressure is higher than shown, thesystem is most likely over-charged, and chargeshould be removed. If the actual pressure islower than shown, the system is most likelyundercharged, and charge should be added.

The air conditioner is now ready for use.

2kgf/cm

2kgf/cm

PUMP DOWNThis is performed when the unit is to berelocated or the refrigerant circuit is serviced.Pump Down means collecting all refrigerant in theoutdoor unit without loss in refrigerant gas.

CAUTION:Be sure to perform Pump Down procedure with theunit cooling mode.

Pump Down ProcedureConnect a low-pressure gauge manifold hose to thecharge port on the gas side service valve.

Open the gas side service valve halfway and purgethe air from the manifold hose using the refrigerantgas.

Close the liquid side service valve(all the way in).

Turn on the unit's operating switch and start thecooling operation.

When the low-pressure gauge reading becomes 12

to 0.5kg/cmG(14.2 to 7.1 P.S.I.G.), fully close thegas side valve stem and then quickly turn off theunit. At that time, Pump Down has been completedand all refrigerant gas will have been collected inthe outdoor unit.

1.

2.

3.

4.

5.

Page 26: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

Gas side

Liquid side

Cap

Hexagonal wrench

2-way valve(Open)

3-way valve(Close)

CEvacuation

Soap water methodRemove the caps from the 2-way and 3-wayvalves.

Remove the service-port cap from the 3-wayvalves.

To open the 2-way valve turn the valve stemcounterclockwise approximately 90°, wait forabout 2~3 sec, and close it.

Apply a soap water or a liquid neutral detergenton the indoor unit connection or outdoor unitconnections by a soft brush to check forleakage of the connecting points of the piping.

If bubbles come out, the pipes have leakage.

(1)

(2)

(3)

(4)

(5)

Connect the charge hose end described in thepreceding steps to the vacuum pump toevacuate the tubing and indoor unit.Confirm the "Lo" knob of the manifold valve isopen. Then, run the vacuum pump.The operation time for evacuation varies withtubing length and capacity of the pump. Thefollowing table shows the time required forevacuation.

Required time for evacuation when 30 gal/hvacuum pump is used

If tubing length is lessthan 10m (33 ft)

10 min. or more15 min. or more

If tubing length is longerthan 10m (33 ft)

When the desired vacuum is reached, close the"Lo" knob of the manifold valve and stop thevacuum pump.

DFinishing the jobWith a service valve wrench, turn the valve stemof liquid side valve counter-clockwise to fullyopen the valve.

Turn the valve stem of gas side valvecounter-clockwise to fully open the valve.

Loosen the charge hose connected to the gas sideservice port slightly to release the pressure, thenremove the hose.

Replace the flare nut and its bonnet on the gas sideservice port and fasten the flare nut securely with anadjustable wrench. This process is very important toprevent leakage from the system.

Replace the valve caps at both gas and liquid sideservice valves and fasten them tight.

This completes air purging with a vacuum pump.The air conditioner is now ready to test run.

Indoor unit

Outdoor unit

LoHi

Manifold valve

Vacuum pump

Pressuregauge

OpenClose

AIR PURGING

INSTALLATION19

Page 27: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

LoHi

Indoor unit

Outdoor unit

Manifold valve

Charge hose

Nitrogen gascylinder(in verticalstanding position)

Pressuregauge

Air purging

Pressure in the system rises.

Air and moisture remaining in the refrigerantsystem have undesirable effects as indicatedbelow.

Operating current rises.

Cooling(or heating) efficiency drops.Moisture in the refrigerant circuit mayfreeze and block capillary tubing.

Water may lead to corrosion of parts in therefrigeration system.

Therefore, the indoor unit and tubing betweenthe indoor and outdoor unit must be leak testedand evacuated to remove any non condensablegas and moisture from the system.

Air purging with vacuumpump

ACheck that each tube(both liquid and gasside tubes) between the indoor andoutdoor units have been properlyconnected and all wiring for the test runhas been completed. Remove the servicevalve caps from both the gas and the liquidside on the outdoor unit. Note that both theliquid and the gas side service valves onthe outdoor unit are kept closed at thisstage.

BLeak testConnect the manifold valve(with pressuregauges) and dry nitrogen gas cylinder tothis service port with charge hoses.

Do a leak test of all joints of the tubing(bothindoor and outdoor) and both gas and liquid sideservice valves.

Bubbles indicate a leak. Be sure to wipe off thesoap with a clean cloth.

After the system is found to be free of leaks,relieve the nitrogen pressure by loosening thecharge hose connector at the nitrogen cylinder. When the system pressure is reduced to normal,disconnect the hose from the cylinder.

AIR PURGING

Preparation

INSTALLATION

To avoid nitrogen entering the refrigerant system in aliquid state, the top of the cylinder must be higher than itsbottom when you pressurize the system. Usually, thecylinder is used in a vertical standing position.

CAUTION

18

Be sure to use a manifold valve for airpurging. If it is not available, use a stop valvefor this purpose. The 3-way valve must always be kept close.

CAUTION

Pressurize the system to maximum 250 P.S.I.G.(R-22 model) or 400 P.S.I.G. (R-410A model) with dry nitrogen gas and close the cylinder valve when the gauge reading reached 250 P.S.I.G. (R-22 model) or 400 P.S.I.G. (R-410A model). Next, stepis leak test with liquid soap.

There is a risk of fire and explosion. - Inert gas (nitrogen) should be used when you check plumbing leaks, cleaning or repairs of pipes etc. If you are using combustible gases including oxygen, product may have the risk of fires and explosions.

CAUTION

Page 28: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

Tip of drain hose dipped in water

WaterleakageDitch

Less than 50mm gap

Checking the drainage

Do not make drain piping.

Form the piping

Do not raise

Waterleakage

Accumulateddrain water

Air

WavingWaterleakage

Taping

Drainhose

Pipings

Connectingcable

AForm the piping by wrapping theconnecting portion of the indoor unit withinsulation material and secure it with twokinds of vinyl tapes.

If you want to connect an additional drainhose, the end of the drain outlet should be

routed above the ground. Secure the drainhose appropriately.

BIn cases where the outdoor unit isinstalled below the indoor unit performthe following.

Tape the piping, drain hose andconnecting cable from down to up.

Secure the tapped piping along the exteriorwall using saddle or equivalent.

CIn cases where the Outdoor unit isinstalled above the Indoor unit performthe following.

Tape the piping, and connecting cable fromdown to up.

Secure the taped piping along the exteriorwall. Form a trap to prevent water enteringthe room.

Fix the piping onto the wall by saddle orequivalent.

Seal small openingsaround pipings with agum type sealant.

Trap is required to prevent waterfrom entering into electrical parts.

Seal a small openingaround the pipingswith gum type sealant.

Trap

Trap

Downward slope

ATo remove the front panel from the indoorunit cabinet.

Set the air direction of louvers up-and-down tothe position(horizontally) by hand.

Remove the securing screws that retain thefront panel. Pull the lower left and rightsides of the grille toward you and lift it off.(1TR, 1.5TR, 2TR)

BTo check the drainage.Pour a glass of water on the evaporator.

Ensure the water flows through the drainhose of the indoor unit without any leakageand goes out the drain exit.

CDrain piping

The drain hose should point downward foreasy drain flow.

Screw

Pull the right andthe left side.

CHECKING THE DRAINAGE AND FORMING THE PIPING

INSTALLATION17

Page 29: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

CONNECTING THE CABLEBETWEEN INDOOR & OUTDOOR UNIT

Connect the cable to theoutdoor unit

ARemove the control cover from the unit byloosening the screw.Connect the wires to the terminals on thecontrol board individually.

BSecure the cable onto the control board withthe cord clamp.

CRefix the control cover to the originalposition with the screw.

DUse a recognized circuit breaker 20A (12K,18K),25A (24K) between the power sourceand the unit. A disconnecting device toadequately disconnect all supply lines mustbe fitted.

After the confirmation of the above conditions, prepare the wiring as follows:

Never fail to have an individual power circuit specifically for the air conditioner. As forthe method of wiring, be guided by the circuit diagram posted on the inside of controlcover.The screw which fasten the wiring in the casing of electrical fittings are liable to comeloose from vibrations to which the unit is subjected during the course oftransportation. Check them and make sure that they are all tightly fastened. (If theyare loose, it may cause burn-out of the wires.)Specification of power source.Confirm that electrical capability is sufficient.The starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate.Confirm that the cable thickness is as specified in the power source specification.(Particularly note the relation between cable length and thickness. (Refer to page 15))Always install an earth leakage circuit breaker in a wet or moist area.The following would be caused by voltage drop.

The means for disconnection from a power supply shall be incorporated in the fixedwiring and have an air gap contact separation of at least 3mm in each active(phase)conductors.

Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of thenormal function of the overload.

1)

2)

3)4)5)

6)

7)8)

9)

Outdoor Unit

Terminal block

Over 5mm

Cover controlConnecting cable 1

Connecting cable 2

Cover Control

CAUTION

INSTALLATION 16

Connecting Cable 1 each (Cooling only)Connecting cable 2 each (Heat pump only)

Page 30: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

CONNECTING THE CABLEBETWEEN INDOOR & OUTDOOR UNITConnect the cable fromIndoor to outdoor unit.

If a power plug is not to be used, provide a circuit breaker between power source and the unit as shown below.

Main power source

Circuit BreakerUse a circuitbreaker or timedelay fuse.

AirConditioner

The power cord connected to the indoor unit shouldbe compiled with the following specifications

The power connecting cable connected to theindoor and outdoor unit should be compiled with thefollowing specifications

The connecting signal cable connected to theindoor and outdoor unit should be compiled with the following specifications

Capacity(Btu/h)

NORMAL CROSS-SECTIONAL AREA

18K

24K

21.0mm

21.5mm

22.5mm

Capacity(Btu/h)

NORMAL CROSS-SECTIONAL AREA

9K, 12K

18K,(4,5 Star)

21.0mm

21.5mm

NORMALCROSS-SECTIONAL

2AREA 0.75mm

9K, 12K

INSTALLATION15

(Optional)Cooling model (9K,12K)Cooling model (9K,12K,18K,24K)

Heat pump model(12K,18K,24K)

CAUTION

CAUTION

--

connecting the indoor and outdoor housing connector (male - female housing matching). Outdoor Unit connection.

no

18K,(2,3 Star) 24K

22.5mm

Page 31: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

FLARING WORK AND CONNECTION OF PIPINGBundle the piping and drain hose together bywrapping them with cloth tape over the rangewithin which they fit into the rear piping housingsection.

Drain hose

Pipe

Vinyl tape(narrow)

HReroute the pipings and the drain hose acrossthe back of the chassis.

Wrap withvinyl tape(wide)

ISet the pipings and the drain hose to the back ofthe chassis with the tubing holder.

Hook the edge of tubing holder to tap on chassisand push the bottom of tubing holder to beengaged at the bottom of chassis.

JIndoor unit installationRemove the spacer.Ensure that the hooks are properly seated on theinstallation plate by moving it left and right.

Press the lower left and right sides of the unit againstthe installation plate until the hooks engage into theirslots(clicking sound).

Connection of thepiping-Outdoor

When tightening the flare nut with torquewrench, ensure the direction for tighteningfollows the arrow on the wrench.

AAlign the center of the pipings andsufficiently tighten the flare nut by hand.

BFinally, tighten the flare nut with torquewrench until the wrench clicks.

Tubing holderHook

Push

Drain hose

Connectingcable

Outdoor unit Gas side piping(Bigger diameter)

Liquid sidepiping(Smallerdiameter)

Torque wrench

2

1

Piping forpassage throughpiping hole

INSTALLATION 14

N.m17.6~24.533.3~41.253.9~64.761.7~80.497~118.6

kgf.cm180~250340~420550~660630~820

990~1210

Page 32: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

Vinyl tape(narrow)

Connecting cable

Pipe

Connectionpipe

Vinyl tape(wide)

Wrap with vinyl tape

Indoor unit pipe

Vinyl tape(narrow)Adhesive

Drain pipe

Indoor unit drain hose

Installation plate

Spacer

Indoor unit

8cm

CInsert the connecting cable into the indoor unit.

Don't connect the cable to the indoor unit.Make a small loop with the cable for easyconnection later.

DTape the drain hose and the connecting cable.

Connecting cable

EIndoor unit installation

Hang the indoor unit from the hooks at the top ofthe installation plate.

Insert the spacer etc. between the indoor unit andthe installation plate and separate the bottom ofthe indoor unit from the wall.

FConnecting the pipings to the indoor unit andthe drain hose to drain pipe.

Align the center of the pipings and sufficientlytighten the flare nut by hand.

When extending the drain hose at the indoor unit.install the drain pipe.

GWrap the insulation material around theconnecting portion.

Overlap the connection pipe heat insulation and theindoor unit pipe heat insulation material. Bind themtogether with vinyl tape so that there is no gap.

Wrap the area which accommodates the rearpiping housing section with vinyl tape.

Spanner (fixed)

Flare nut

Connection pipeTorque wrench

Indoor unit tubing

Indoor unit tubingFlare nutPipings

Tighten the flare nut with a wrench.

FLARING WORK AND CONNECTION OF PIPING

INSTALLATION13

N.m17.6~24.533.3~41.253.9~64.761.7~80.497~118.6

kgf.cm180~250340~420550~660630~820

990~1210

Page 33: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

Vinyl tape(narrow)

Connecting cable

Pipe

Connectionpipe

Vinyl tape(wide)

Wrap with vinyl tape

Indoor unit pipe

Drain pipe

Connecting cable

Wrap with vinyl tape

Drain hose

Pipe

Vinyl tape(wide)

Tighten the flare nut with a wrench.Wrap the area which accommodates the rearpiping housing section with vinyl tape.

Bundle the piping and drain hose together bywrapping them with vinyl tape over the rangewithin which they fit into the rear pipinghousing section.

Vinyl tape(narrow)Adhesive

Drain pipe

Indoor unit drain hose

BInsert the piping, drain hose and the connectingcable into the piping hole.

FWrap the insulation material around theconnecting portion.

ARoute the indoor tubing and the drain hose tothe required piping hole position.

For right rear piping

When extending the drain hose at the indoor unit,install the drain pipe.

Overlap the connection pipe insulation material andthe indoor unit pipe insulation material. Bind themtogether with vinyl tape so that there is no gap.

Spanner (fixed)

Flare nut

Connection pipeTorque wrench

Indoor unit tubing

FLARING WORK AND CONNECTION OF PIPING

INSTALLATION 12

N.m17.6~24.533.3~41.253.9~64.761.7~80.497~118.6

kgf.cm180~250340~420550~660630~820

990~1210

Page 34: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

FLARING WORK AND CONNECTION OF PIPINGConnection of piping-Indoor

Preparing the indoor unit's piping and drainhose for installation through the wall.

Remove the plastic tubing retainer (seeillustration below) and pull the tubing anddrain hose away from chassis.

Replace the plastic tubing holder in theoriginal position.

CTape the tubing, drain hose and the connectingcable. Be sure that the drain hose is located atthe lowest side of the bundle. Locating at theupper side can cause drain pan to overflowinside the unit.

*Foamed polyethylene or equivalent is recommended.

Loop

Connectingcable

Drain hose

Gas sidepiping

Liquid sidepiping Tubing holder

To remove the holder,press the bottom ofchassis near the holderupward and pull the tabout of its hole.

DIndoor unit installation

Hook the indoor unit onto the upper portion ofthe installation plate.(Engage the two hooks ofthe rear top of the indoor unit with the upperedge of the installation plate.) Ensure that thehooks are properly seated on the installationplate by moving it left and right

ARoute the indoor tubing and the drain hosein the direction of rear left.

Drain hose

BInsert the connecting cable into the indoorunit from the outdoor unit through thepiping hole.

Do not connect the cable to the indoor unit.Make a small loop with the cable for easyconnection later.

For left rear piping

CAUTIONWhen install, make surethat the remaining partsmust be removed clearlyso as not to damage thepiping and drain hose,especially power cordand connecting cable.

Press the lower left and right sides of theunit against the installation plate until thehooks engage into their slots (clicking-sound).

EConnecting the pipings to the indoor unit anddrain hose to drain pipe.

Align the center of the pipings and sufficientlytighten the flare nut by hand.

Indoor unit tubingFlare nutPipings

Drain hose

Connectingcable

INSTALLATION11

If the drain hose is routed inside the room,insulate the hose with an insulation material* sothat dripping from "sweating"(condensation) willnot damage furniture or floors.

Page 35: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

Outside diametermm

ø6.35

ø9.52

ø12.7

ø15.88

ø19.05

inch

1/4"

3/8"

1/2"

5/8"

3/4"

mmmm

1.1~1.30.7

1.5~1.70.8

1.6~1.80.8

1.6~1.8

1.9~2.1

1.0

1.0

AThickness

FLARING WORK AND CONNECTION OF PIPING

AUse the piping kit accessory or the pipespurchased locally.

Measure the distance between the indoorand the outdoor unit.

Cut the pipes a little longer than measureddistance.

Cut the cable 1500mm longer than the pipelength.

DCarry out flaring work using flaring tool as shownbelow.

Firmly hold copper pipe in a die in thedimension shown in the table above.

BCompletely remove all burrs from the cutcross section of pipe/tube.

Put the end of the copper tube/pipe in adownward direction as you remove burrs inorder to avoid dropping burrs into the tubing.

ECompare the flared work with figure below.If flare is noted to be defective, cut off the flaredsection and do flaring work again.

CRemove flare nuts attached to indoor andoutdoor unit, then put them on pipe/tubehaving completed burr removal.(not possible to put them on after flaringwork)

Copperpipe90°Slanted Uneven Rough

Pipe

Reamer

Point down

Flare nut

Copper tube

Bar

Copper pipe

Clamp handleRed arrow mark

Cone

Yoke

Handle

Bar "A"

Inclined

Inside is shiny without scratches.

Smooth all round

Even lengthall round

Surfacedamaged

CrackedUneventhickness

= Improper flaring =

Main cause for gas leakage is due to defectin flaring work. Carry out correct flaring workin the following procedure.

Flaring workFlaring work

Burrs removalCheck

Cut the pipes and the cable

Putting nut on

INSTALLATION 10

Page 36: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

Mount the installation plate horizontally by

aligning the centerline using a level.

AMount the installation plate on the wall withfour type “A” screws. If mounting the unit on aconcrete wall, use anchor bolts.

The wall you select should be strong and solidenough to prevent vibration.

BMeasure the wall and mark the centerline. Itis also important to use caution concerningthe location of the installation plate-routing ofthe wiring to power outlets is through thewalls typically. Drilling the hole through thewall for piping connections must be donesafely.

Drill the piping hole with a ø70mm hole core

drill. Drill the piping hole at either the right or

the left with the hole slightly slanted to the

outdoor side.

Indoor

WALL

Outdoor

5-7

mm

(0.2

~0.3

")

CAUTIONMake sure that the drilled hole in the wall is properly sealed (using a proper sealant, for example cement, plaster of paris etc.) after passing the installation pipe, drainage pipe and the inter connecting cable.

INSTALLATION OF INDOOR & OUTDOOR UNITHow to fix installation plateDrill a hole in the wall

Outdoor Unit

Drain Pipe

Drain Pan

Drain pan along with drain pipe (asshown below) can be used to drainthe water accumulated in the outdoorduring the Heat Mode.

Left rear pipingRight rear piping

Hole centerø70mm

"D""C"

Usage of Drain Pan(Heat Pump)

INSTALLATION9

Type “A” Screw

Page 37: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

INSTALLATION OF INDOOR & OUTDOOR UNITRead completely, then follow step by step.

Capacity is based on standard length and maximumallowance length is on the basis of reliability.Oil trap should be installed every 5~7 meters.

In case more than 5m

A

Indoor unit

Oil trap

Outdoor unit

A

Indoor unit

Outdoor unit

ADo not have any heat or steam near theunit.Select a place where there are noobstacles in front of the unit.Make sure that condensation drainagecan be conveniently routed away.Do not install near a doorway.Ensure that the space around the left andright of the unit is more than 100mm. Theunit should be installed as high on thewall as possible, allowing a minimum of200mm from ceiling.Use a stud finder to locate studs toprevent unnecessary damage to the wall.

More than 100mmMore than 200mm

More than 2300mmMore than 100mm

Install the indoor unit on the wall where the heightfrom the floors more than 2300 mm.

BIf an awning is built over the unit to

prevent direct sunlight or rain exposure,make sure that heat radiation from the

condenser is not restricted.Ensure that the space around the backand sides is more than 300mm. The front ofthe unit should have more than 700mm of

space.Do not place animals and plants in thepath of the warm air.

Take the air conditioner weight intoaccount and select a place where noiseand vibration are minimum.Select a place so that the warm air andnoise from the air conditioner do not

disturb neighbors.

Select the best locationIndoor Unit

CAUTION

Outdoor Unit

If the outdoor unit is installed on a roof structure, be

sure to level the unit. Ensure the roof structure and

anchoring method are adequate for the unit location.

Consult local codes regarding rooftop mounting.

Rooftop Installation

Piping length and elevation

CAUTION

INSTALLATION 8

B

Capacity(Btu/h)

18K (5 star)24K Cooling

24K Cooling & Heat Pump5/8"3/8"3 to 5

Pipe Size

GASLIQUID

StandardLength

(m)

1/2"1/4"

1/4"

3 to 5

3 to 5

20

20

20

20

5/8"1/4"3 to 52030

2030

Max.length

(m) A

AdditionalRefrigerant

(g/m)

9K3/8"

9K, 12K,18K (2,3 star)

18K Heat Pump

Page 38: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

1

2

3

4

5

6

7

8

9

10

11

12

Installation Tools

S.No.Required Tools

Level Gauge

Screw Driver

Electric Drill

Hole Core Drill (Dia-70mm)

Flaring Tool Set

Specified torque wrenches 1.8kg.m, 4.2kg.m, 5.5kg.m, 6.6kg.m(Different depending on model no.)

Spanner (Half Union)

Hexagonal Wrench

Gas-Leak Detector

Vacuum Pump

Gauge Manifold

Thermometer

INSTALLATION PARTS7

Page 39: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

INSTALLATION PARTSInstallation parts provided with the unit

NameShapeOthers

Installation parts you must purchase

Owner’sManualInstallationManual

Sleeve

Bushing Sleeve

Putty (Gum type sealant)

Vinyl tape (Wide)

Gas side piping

Liquid side piping

Additional drain pipe

Vinyl tape

Saddle

INSTALLATION PARTS 6

Installation�parts�youmust�purchaseInstallation plateSleeveBushing-SleevePutty(Gum Type Sealant)

Bend the pipe as closelyon the wall as possible,but be careful that itdoesn't break.

Vinyl tape (Wide)Apply after carrying out adrainage test.

To carry out the drainagetest, remove the air filtersand pour water into the heatexchanger.

Gas side piping

Liquid side piping

Additional drain pipe

Vinyl tape

Connecting cable: Cooling & Heat pump: 2EA

Cooling only: 1EA

Saddle

Air filter

(Left and rightare identical)

Type ‘A’ Screw

NameQuantityShapeOthers

5

Installation Plate

Type ‘B’ Screw

Holder Remote Control

1

2

1

Owner’s ManualInstallation Manual

••

The actural part can be changed according to the type of model.

Page 40: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

5 SAFETY INSTRUCTIONS

Always check for gas (refrigerant) leakage after installation or repair of product.- Low refrigerant levels may cause failure of product or may effect product performance.

tonot cause

neighbours.neighbours.

Page 41: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

4SAFETY INSTRUCTIONS

Page 42: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

3

reduce the cooling/ dehumidification functions.

Avoid excessive cooling

(Refer page no. 19 and 20 details of owner's manual).

Page 43: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

6 Installation Parts provided with the Unit6 Installation Parts you must purchase7 Installation Tools

INSTALLATION PARTS 6

8-910-14

1011111214

15-16

17

182021

Connecting the cable between indoorand outdoor unitChecking the drainage and forming thepipingAir purgingTest runningInstallation guide at the seaside

Installation of Indoor & Outdoor UnitFlaring Work and Connection of Piping

INSTALLATION 8

Flaring WorkConnection of piping-IndoorFor left rear pipingFor right rear pipingConnection of piping-Outdoor

IMPORTANT SAFETY INSTRUCTIONS 4

TIPS FOR SAVING ENERGY 3

Page 44: ROOM AIR CONDITIONERgscs-b2c.lge.com › downloadFile?fileId=KROWM000606296.pdf · Do not install the air conditioner on an unstable surface or where there may be a danger of unit

ROOM AIR CONDITIONER

For Split AC Domestic Models

TYPE : WALL MOUNTED

P/No. MFL39754865_V3MFL39754865

INSTALLATION MANUAL

Regd. Office: LG Electronics India Pvt. Ltd., A Wing (3rd Floor), D-3, District Center, Saket, New Delhi - 110017

Please read this installation manual completely before installing the product and retain it for future reference.