ROCHESTER PUBLIC UTILITIES ELECTRIC SYSTEM DATA December, 2012 Document Maintained by: Neil Stiller Version Control Version Date Author Change Description 1 February, 1994 G. Woodworth Compiled from numerous sources 2 March, 1995 G. Woodworth Updated to reflect system improvements 3 May, 1999 G. Woodworth Updated to reflect system improvements 4 June, 2002 G. Woodworth Updated to reflect system improvements 5 August, 2002 G. Woodworth Updated to reflect system improvements 6 July, 2009 N. Stiller Updated for completed projects. Conformed to NERC standard FAC-008-1 7 September, 2009 N. Stiller Updated for completed projects. 8 February, 2011 N. Stiller Updated for completed projects. Added plant auxiliary transformers. Updated bus numbers. 9a December, 2012 N. Stiller Revised transformer impedances to show R + jX = Z. Added substation bus equipment Updated Substation Apparatus Limits, corrected misc. error for Westside substation

Upload: trinhhanh

Post on 08-Mar-2018

217 views

Category:

Documents


1 download

TRANSCRIPT

ROCHESTER PUBLIC UTILITIES

ELECTRIC SYSTEM DATA

December, 2012

Document Maintained by: Neil Stiller Version Control

Version Date Author Change Description

1 February, 1994 G. Woodworth Compiled from numerous sources

2 March, 1995 G. Woodworth Updated to reflect system improvements

3 May, 1999 G. Woodworth Updated to reflect system improvements

4 June, 2002 G. Woodworth Updated to reflect system improvements

5 August, 2002 G. Woodworth Updated to reflect system improvements

6 July, 2009 N. Stiller Updated for completed projects. Conformed to NERC standard FAC-008-1

7 September, 2009 N. Stiller Updated for completed projects.

8 February, 2011 N. Stiller Updated for completed projects. Added plant auxiliary transformers. Updated bus numbers.

9a December, 2012 N. Stiller Revised transformer impedances to show R + jX = Z. Added substation bus equipment Updated Substation Apparatus Limits, corrected misc. error for Westside substation

November 2012 System Data Book - 2012 Ver 9a Page 1

TABLE OF CONTENTS

LINE DATA

Legend ....................................................................................................................................... 3 Line K1 ....................................................................................................................................... 5 Line RQ7 .................................................................................................................................... 6 Line RQ11 .................................................................................................................................. 7 Line Q1 ....................................................................................................................................... 8 Line Q2 ....................................................................................................................................... 9 Line Q3 ..................................................................................................................................... 10 Line Q4 ..................................................................................................................................... 11 Line Q5 ..................................................................................................................................... 12 Line Q6 ..................................................................................................................................... 13 Line Q7 ..................................................................................................................................... 14 Line Q8 ..................................................................................................................................... 15 Line Q9 ..................................................................................................................................... 16 Line Q10 ................................................................................................................................... 17 Line Q15 (DPC)........................................................................................................................ 18 Line Q16 (DPC)........................................................................................................................ 19 LineRating vs. Temperature Graphs ................................................................................ 20 – 27 Substation Apparatus Limits .................................................................................................... 28

GENERATION DATA

Legend ..................................................................................................................................... 29 Silver Lake Plant Fact Sheet .................................................................................................... 30 Silver Lake Plant Gen. 1 .......................................................................................................... 31 Silver Lake Plant Gen. 2 .......................................................................................................... 32 Silver Lake Plant Gen. 3 .......................................................................................................... 33 Silver Lake Plant Gen. 4 .......................................................................................................... 34 Cascade Creek Combustion Turbine Gen. 1 ........................................................................... 35 Cascade Creek Combustion Turbine Gen. 2 ........................................................................... 36 Hydro Plant Gen. 1 .................................................................................................................. 37 Hydro Plant Gen. 2 .................................................................................................................. 38 IBM Genset. 1 .......................................................................................................................... 39 IBM Genset 2 .......................................................................................................................... 40 Appendix – Westinghouse Corp. Generator Data ........................................................... 41 – 42

POWER TRANSFORMER DATA

Legend ..................................................................................................................................... 43 Bamber Valley T1..................................................................................................................... 44 Bamber Valley T2..................................................................................................................... 45 Cascade Creek Combustion Turbine Gen. #2 GSU2 .............................................................. 46 Cascade Creek T1 ................................................................................................................... 47 Cascade Creek T2 ................................................................................................................... 48 Crosstown T1 ........................................................................................................................... 49 Crosstown T2 ........................................................................................................................... 50 Hydro Line KU1 ........................................................................................................................ 51 Hydro Plant KL1 ....................................................................................................................... 52 IBM T1 ...................................................................................................................................... 53 IBM T2 ...................................................................................................................................... 54 Northern Hills T1 ...................................................................................................................... 55 Northern Hills T2 ...................................................................................................................... 56 Silver Lake Gen. #4 GSU4 ....................................................................................................... 57 Silver Lake T3 .......................................................................................................................... 58 Silver Lake T4 .......................................................................................................................... 59 Westside T1 ............................................................................................................................. 60 Willow Creek T1 ....................................................................................................................... 61 Willow Creek T2 ....................................................................................................................... 62

November 2012 System Data Book - 2012 Ver 9a Page 2

Zumbro River T1 ...................................................................................................................... 63 Zumbro River T2 ...................................................................................................................... 64

AUXILIARY TRANSFORMER DATA

Legend ..................................................................................................................................... 65 Cascade Creek MA1 ................................................................................................................ 66 Cascade Creek MA2 ................................................................................................................ 67 Silver Lake Plant MA3 .............................................................................................................. 68 Silver Lake Plant MA4 .............................................................................................................. 69 Silver Lake Plant RA1 .............................................................................................................. 70 Silver Lake Plant RA3 .............................................................................................................. 71 Silver Lake Plant RA4 .............................................................................................................. 72 Silver Lake Plant SA1 .............................................................................................................. 73 Silver Lake Plant SA2 .............................................................................................................. 74

GENERATOR REACTOR, RESISTOR, & BUS DUCT DATA

Legend ..................................................................................................................................... 75 Silver Lake Plant Gen. 1 Neutral Reactor ................................................................................ 76 Silver Lake Plant Gen. 2 Neutral Reactor ................................................................................ 77 Silver Lake Plant Gen. 3 Neutral Reactor ................................................................................ 78 Silver Lake Plant Gen. 4 Neutral Grounding Transformer / Secondary Resistor .................... 79 Silver Lake Plant Gen. 4 Iso-Phase Bus Duct ......................................................................... 80 Cascade Creek Combustion Turbine Gen. 1 Phase Reactor .................................................. 81 Cascade Creek Combustion Turbine Gen. 1 Non-Segregate Bus Duct.................................. 82 Cascade Creek Combustion Turbine Gen. 1 Neutral Reactor ................................................ 83 Cascade Creek Combustion Turbine Gen. 2 Neutral Grounding Transformer / Secondary Resistor ................................................................................... 84

TRANSFORMER REACTOR DATA Legend ..................................................................................................................................... 85 Cascade Creek Transformer T1 Neutral Reactor .................................................................... 86 Cascade Creek Transformer T2 Neutral Reactor .................................................................... 87 IBM Transformer T1 Neutral Reactor....................................................................................... 88 IBM Transformer T2 Neutral Reactor....................................................................................... 89 Silver Lake Plant Transformer MA4 Reactor ........................................................................... 90 Silver Lake Plant Transformer RA4 Reactor ............................................................................ 91 Westside Transformer T1 Neutral Reactor .............................................................................. 92

STATION CAPACITOR BANK DATA

Legend ..................................................................................................................................... 93 Silver Lake Plant Capacitor Bank ........................................................................................... 94 Silver Lake Plant Capacitor Bank Reactor 219 ........................................................................ 95 Silver Lake Plant Capacitor Bank Feeder Cable ..................................................................... 96

Zumbro River Capacitor Bank ................................................................................................. 97 Zumbro River Capacitor Bank Reactor 816 ............................................................................. 98 Zumbro River Capacitor Bank Reactor 816C .......................................................................... 99

SUBSTATION BUS DATA Legend ................................................................................................................................... 100 Summary of 161 kV Bus Configurations ............................................................................... 101 Summary of 13.8 kV Bus Switchgear.................................................................................... 102

PHASING Phasing Designations of Companies Interconnected with NSP (XCEL) ............................... 103

November 2012 System Data Book - 2012 Ver 9a Page 3

LINE DATA

LEGEND

1. The voltage listed is the nominal line to line voltage in kilovolts. 2. The positive and zero sequence susceptance given is in per unit for the total three phase line. 3. The charging current given is the charging current in amps of each phase conductor. The line parameter

was calculated by multiplying the positive sequence susceptance by the base current of the line. 4. The loading capacity given is in MVA for the total three phase line. 5. Impedance values are obtained from the Aluminum Association’s Aluminum Electrical Conductor

Handbook, third edition, 1989. Line parameters were calculated using ASPEN Line Constants Program Version 3.1 software or CAPE Line Constants Program (beginning 2009)

6. Pos. Seq. Imp. – Positive sequence impedance of each line section and line total in ohms.

Pos. Seq. Imp. (P.U.) – Positive sequence impedance of each line section and line total in per unit on a 100 MVA base. Zero Seq. Imp. – Zero sequence impedance of each line section and line total in ohms. Zero Seq. Imp. (P.U.) – Zero sequence impedance of each line section and line total in per unit on a 100 MVA base. Zero Seq. Mutual Impedance – Zero sequence mutual impedance of each double circuit line and line total in ohms. Zero Seq. Mutual Impedance (P.U.) – Zero sequence mutual impedance of each double circuit line section and line total in per unit on a 100 MVA base.

7. Ampacity values are obtained from Southwire’s Overhead Conductor Manual, first edition, first printing,

1994 and the associated Thermal Rating Program software. 8. The current carrying capacity of each overhead phase conductor is determined on the basis of:

a. Hot Conductor Design Temperature of the line as follows:

i. 25° C (77 °F) for line K1

ii. 75° C (167 °F) for lines Q2, Q3, Q4, Q5, Q6, Q8, and Q9

iii. 100° C (212 °F) for the parallel 556.5 Osprey conductors on lines Q7 and Q10.

iv. 132° C (270 °F) for the 954 Rail terminal drops in the deadends on lines Q7 and Q10.

v. 100° C (212 °F) for the 795 Drake conductors on line Q1.

vi. 100° C (212 °F) for the 954 Rail conductors on the Westside tap of line Q9

b. Ambient Temperature 80°F (26.7°C) summer normal, 32°F (0°C) winter normal c. Wind speed and other factors are listed above the table on page 26 of this section. d. Emergency ratings are 10% over normal ratings with the exception being Q7 and Q10. The emergency

rating for these lines are base on the more restrictive of a.) 10% greater rating of 556 Osprey or, b.) 5% greater rating of the 954 Rail, since it has a higher normal hot conductor temperature. These exceptions are explained in Note 2 on page 27 of this section.

9. The Q7 and Q10 lines have parallel 556 Osprey conductors per phase except for the last span into the substation

deadends at Crosstown and Silver Lake and the last two spans into the Cascade Creek deadend, which are 954 Rail. The low point of all these spans are located over fenced RPU substation property.

10. Line and terminal capacity curves for varying ambient temperatures for all conductor configurations and

open/closed ring bus configurations are located on pages 20 through 25 of this section. Page 26 of this section

November 2012 System Data Book - 2012 Ver 9a Page 4

contains the base data for the capacity ratings for each line along with the ambient and atmospheric assumptions based on the Southwire Thermal Rating Program. Stated line ratings account for terminal equipment limitations. Line ratings that are restricted by terminal equipment limitations are noted on the respective transmission line data page in this section.

11. Page 27 is a table of line ratings effective July 1, 2002 that are used in the MAPP/MISO operating guides for the

Rochester area. 12. The bracketed number behind the terminal name is the MAPP/MISO bus number. The format of the bus numbers

were revised in 2010.

Station Name Old bus number New bus number

Bamber Valley 63435 625435 Cascade Creek 63430 625430 Chester 63445 625445 Crosstown 63405 625405 IBM 63420 625420 Northern Hills 63415 625415 Silver Lake 63440 625440 West Side 63447 625447 Willow Creek 63410 625410 Zumbro River 63425 625425

13. Line and associated equipment ratings are based on RPU’s Facilities Ratings Methodology for Transmission, Substation, and Generation Equipment, in compliance with NERC FAC-008-3.

November 2012 System Data Book - 2012 Ver 9a Page 5

LINE DATA LINE NO.: K1 VOLTAGE: 34.5 KV TERMINALS: Hydro Plant TO: Hydro Line Substation LINE TOTAL LINE MILES 10.73 MUTUAL MILES PHASE CONDUCTOR 1/0 ACSR 6/1 Raven SHIELD CONDUCTOR 3/8” EHS Steel POS. SEQ. SUSCEPTANCE (P.U.) 0.00073 ZERO SEQ. SUSCEPTANCE (P.U.) 0.00039 CHARGING AMPS 1.2216 LOADING CAPACITY (MVA) SUMMER NORM / EMER 14/15 WINTER NORM / EMER 17/20 LOADING CAPACITY (AMPS/PHASE) SUMMER NORM / EMER 240/260 WINTER NORM / EMER 296/340 EQUIVALENT SPACING (FT.) 5.16 IMPEDANCE DATA POSITIVE SEQUENCE (OHMS)* 9.5280 + j8.4579 ZERO SEQUENCE (OHMS)* 14.6079 + j30.9000 POSITIVE SEQUENCE (P.U.)* 0.8005 + j0.7106 ZERO SEQUENCE (P.U.)* 1.2273 + j2.5961 * This line uses resistance calculated at 25 degrees C.

November 2012 System Data Book - 2012 Ver 9a Page 6

LINE DATA LINE NO.: RQ7 (Owned by SMMPA) VOLTAGE: 161 KV TERMINALS: Cascade Creek Substation [625430] TO: Byron Substation [61948] MUTUAL IMPEDANCE WITH LINE: RQ11 Coupled Segment Uncoupled Segment LINE TOTAL LINE MILES 6.40 3.34 9.74 PHASE CONDUCTOR 954 MCM ACSR 954 MCM ACSR 45/7 Rail 45/7 Rail SHIELD CONDUCTOR 3/8” EHS Steel 3/8” EHS Steel POS. SEQ. SUSCEPTANCE (P.U.) 0.00974 0.00508 0.01482 ZERO SEQ. SUSCEPTANCE (P.U.) CHARGING AMPS 3.49 1.82 5.31 LOADING CAPACITY (MVA) SUMMER NORM / EMER 302/332 * 302/332 * 302/332 * WINTER NORM / EMER 396/435 * 396/435 * 396/435 * LOADING CAPACITY (AMPS/PHASE) SUMMER NORM / EMER 1083/1191 * 1083/1191 * 1083/1191 * WINTER NORM / EMER 1420/1560 * 1420/1560 * 1420/1560 * EQUIVALENT SPACING (FT.) 16.38 16.38 IMPEDANCE DATA POSITIVE SEQUENCE (OHMS) 0.6279 + j4.7017 0.3278 + j2.4545 0.9557 + j7.1562 ZERO SEQUENCE (OHMS) 2.3860 + j16.7418 1.2457 + j8.7403 3.6317 + j25.4821 POSITIVE SEQUENCE (P.U.) 0.0024 + j0.0181 0.0013 + j0.0095 0.0037 + j0.0276 ZERO SEQUENCE (P.U.) 0.0092 + j0.0646 0.0048 + j0.0337 0.0140 + j0.0983 MUTUAL IMPEDANCE DATA ZERO SEQUENCE MUT (OHMS) 1.7626 + j11.3534 ZERO SEQUENCE MUT (P.U.) 0.0068 + j0.0438 * Ratings provided by SMMPA per their ratings’ methodology. ** In 2010, RQ7 was reconfigured to terminate at Byron and Cascade Creek substations after the RQ11 line was constructed to Westside substation. The Maple Leaf tap formerly connected to the RQ7 line was transferred to the RQ11 line.

November 2012 System Data Book - 2012 Ver 9a Page 7

LINE DATA LINE NO.: RQ11 (Owned by SMMPA) VOLTAGE: 161 KV TERMINALS: Westside Substation [625436] TO: Byron Substation [61948] Maple Leaf Substation [61906] MUTUAL IMPEDANCE WITH LINE: RQ7 Byron-ML Segment ML-Westside Segment LINE TOTAL LINE MILES 4.58 2.40 6.98 PHASE CONDUCTOR 954 MCM ACSR 954 MCM ACSR 45/7 Rail 45/7 Rail SHIELD CONDUCTOR 3/8” EHS Steel 3/8” EHS Steel POS. SEQ. SUSCEPTANCE (P.U.) 0.00698 0.00365 0.01063 ZERO SEQ. SUSCEPTANCE (P.U.) CHARGING AMPS 2.50 1.31 3.81 LOADING CAPACITY (MVA) SUMMER NORM / EMER 302/332 302/332 302/332 WINTER NORM / EMER 396/435 396/435 396/435 LOADING CAPACITY (AMPS/PHASE) SUMMER NORM / EMER 1083/1191 1083/1191 1083/1191 WINTER NORM / EMER 1420/1560 1420/1560 1420/1560 EQUIVALENT SPACING (FT.) 16.38 16.38 IMPEDANCE DATA POSITIVE SEQUENCE (OHMS) 0.4919 + j3.3650 0.2578 + j1.7633 0.7497 + j5.1284 ZERO SEQUENCE (OHMS) 1.7502 + j11.9822 0.9172 + j6.2790 2.6673 + j18.2612 POSITIVE SEQUENCE (P.U.) 0.0019 + j0.0130 0.0010 + j0.0068 0.0029 + j0.0198 ZERO SEQUENCE (P.U.) 0.0068 + j0.0462 0.0035 + j0.0242 0.0103 + j0.0705 MUTUAL IMPEDANCE DATA ZERO SEQUENCE MUT (OHMS) 1.7626 + j11.3534 ZERO SEQUENCE MUT (P.U.) 0.0068 + j0.0438 * Ratings provided by SMMPA per their ratings’ methodology. ** In 2010, RQ11 was constructed to terminate at Byron and Westside substations. The Maple Leaf tap formerly connected to the RQ7 line was transferred to the RQ11 line.

November 2012 System Data Book - 2012 Ver 9a Page 8

LINE DATA LINE N O.: Q1 VOLTAGE: 161 KV TERMINALS: Silver Lake Switching Station [625440] TO: Chester Substation (RPU) [625445] MUTUAL IMPEDANCE WITH LINE: Q2 Silver Lake Segment Chester Segment LINE TOTAL LINE MILES 1.64 2.86 4.50 MUTUAL MILES 0 2.86 2.86 PHASE CONDUCTOR 795 MCM ACSR 26/7 795 MCM ACSR 26/7 Drake Drake SHIELD CONDUCTOR OPGW OPGW POS. SEQ. SUSCEPTANCE (P.U.) 0.00253 0.00454 0.00707 ZERO SEQ. SUSCEPTANCE (P.U.) 0.00146 0.00242 0.00388 CHARGING AMPS 0.9073 1.6281 2.5353 LOADING CAPACITY (MVA) SUMMER NORM / EMER 312/335 312/335 312/335 WINTER NORM / EMER 335/335 335/335 335/335 LOADING CAPACITY (AMPS) SUMMER NORM / EMER 1119/1201 1119/1201 1119/1201 WINTER NORM / EMER 1201/1201 1201/1201 1201/1201 EQUIVALENT SPACING (FT.) 11.44 13.12 IMPEDANCE DATA POSITIVE SEQUENCE (OHMS) 0.2074 + j1.1664 0.3629 + j1.9959 0.5703 + j3.1624 ZERO SEQUENCE (OHMS) 0.9850 + j3.4475 1.7108 + j6.2210 2.6958 + j9.6685 POSITIVE SEQUENCE (P.U.) 0.0008 + j0.0045 0.0014 + j0.0077 0.0022 + j.0122 ZERO SEQUENCE (P.U.) 0.0038 + j0.0133 0.0066 + j0.0240 0.0104 + j0.0373 MUTUAL IMPEDANCE DATA ZERO SEQUENCE MUT (OHMS) 1.3093 + j3.8970 1.3093 + j3.8970 ZERO SEQUENCE MUT (P.U.) 0.0051 + j0.0150 0.0051 + j0.0150 The Silver Lake segment is the single circuit portion of the line beginning at Silver Lake sub. The Chester segment is the double circuit portion of the line.

November 2012 System Data Book - 2012 Ver 9a Page 9

LINE DATA LINE NO.: Q2 VOLTAGE: 161 KV TERMINALS: Willow Creek Substation [625410] TO: Chester Substation (RPU) [625445] MUTUAL IMPEDANCE WITH LINE: Q1 Willow Creek Rebuilt LINE Chester Segment Segment Segments* TOTAL LINE MILES 2.86 3.83 0.89 6.69 MUTUAL MILES 2.86 2.86 PHASE CONDUCTOR 556.5 MCM ACSR 556.5 MCM ACSR 556.5 MCM ACSR 18/1 Osprey 18/1 Osprey 18/1 Osprey SHIELD CONDUCTOR OPGW 3/8” EHS Steel 3/8” EHS Steel POS. SEQ. SUSCEPTANCE (P.U.) 0.00436 0.00568 0.0015 0.01004 ZERO SEQ. SUSCEPTANCE (P.U.) 0.00236 0.00333 0.0008 0.00569 CHARGING AMPS 1.5635 0.9216 0.1399 2.7541 LOADING CAPACITY (MVA) SUMMER NORM / EMER 198/221 198/221 198/221 WINTER NORM / EMER 250/275 250/275 250/275 LOADING CAPACITY (AMPS) SUMMER NORM / EMER 710793 710793 710793 WINTER NORM / EMER 897/986 897/986 897/986 EQUIVALENT SPACING (FT.) 11.44 11.72 14.67 IMPEDANCE DATA POSITIVE SEQUENCE (OHMS) 0.5184 + j2.0737 0.5408 + j2.2147 0.1637 + j0.6705 1.2229 + j4.9589 ZERO SEQUENCE (OHMS) 1.7108 + j7.5171 1.5723 + j7.7554 0.4743 + j2.3500 3.7575+ j17.6226 POSITIVE SEQUENCE (P.U.) 0.0020 + j0.0080 0.0021 + j0.0085 0.0006 + j0.0026 0.0047 + j0.0191 ZERO SEQUENCE (P.U.) 0.0066 + j0.0290 0.0061 + j0.0299 0.0018 + j0.0091 0.0145 + j0.0680 MUTUAL IMPEDANCE DATA ZERO SEQUENCE MUT (OHMS) 1.3093 + j3.8970 1.3093 + j3.8970 ZERO SEQUENCE MUT (P.U.) 0.0051 + j0.0150 0.0051 + j0.0150 * The Willow Creek segment is the single circuit portion of the line beginning at Willow Cr. sub. The Chester segment is the double circuit portion of the line. Two other segments of this line totaling 0.89 miles were rebuilt using the present RPU construction standard which has greater phase-phase spacing and taller structures.

November 2012 System Data Book - 2012 Ver 9a Page 10

LINE DATA LINE NO.: Q3 VOLTAGE: 161 KV TERMINALS: Willow Creek Substation [625410] TO: Bamber Valley Substation [625435] Rebuilt LINE Original Constr. Segments* TOTAL LINE MILES 1.13 1.52 2.65 Overhead PHASE CONDUCTOR 556.5 MCM ACSR 556.5 MCM ACSR 18/1 Osprey 18/1 Osprey SHIELD CONDUCTOR 3/8” EHS Steel OPGW POS. SEQ. SUSCEPTANCE (P.U.) 0.00196 0.00224 0.00393 ZERO SEQ. SUSCEPTANCE (P.U.) 0.00099 0.00116 0.00224 CHARGING AMPS 0.355 0.416 1.4093 LOADING CAPACITY (MVA) SUMMER NORM / EMER 198/221 198/221 WINTER NORM / EMER 250/275 250/275 LOADING CAPACITY (AMPS) SUMMER NORM / EMER 710/793 710/793 WINTER NORM / EMER 897/986 897/986 EQUIVALENT SPACING (FT.) 11.72 14.67 IMPEDANCE DATA POSITIVE SEQUENCE (OHMS) 0.2079 + j0.8262 0.2483 + j1.0247 0.4562 + j1.8509 ZERO SEQUENCE (OHMS) 0.6146 + j3.0259 0.7201 + j3.5479 1.3347 + j6.5738 POSITIVE SEQUENCE (P.U.) 0.0008 + j0.0032 0.0010 + j0.0040 0.0018 + j0.0071 ZERO SEQUENCE (P.U.) 0.0024 + j0.0117 0.0028 + j0.0137 0.0052 + j0.0254 * One segment of this line was rebuilt using the present RPU construction standard which has greater phase-phase spacing and taller structures.

November 2012 System Data Book - 2012 Ver 9a Page 11

LINE DATA LINE NO.: Q4 VOLTAGE: 161 KV TERMINALS: Bamber Valley Substation [625435] TO: Cascade Creek Substation [625430] LINE TOTAL LINE MILES 4.33 Overhead PHASE CONDUCTOR 556.5 MCM ACSR 18/1 Osprey SHIELD CONDUCTOR 3/8” EHS Steel POS. SEQ. SUSCEPTANCE (P.U.) 0.00643 ZERO SEQ. SUSCEPTANCE (P.U.) 0.00357 CHARGING AMPS 2.3058 LOADING CAPACITY (MVA) SUMMER NORM / EMER 198/221 WINTER NORM / EMER 250/275 LOADING CAPACITY (AMPS) SUMMER NORM / EMER 710/793 WINTER NORM / EMER 897/986 EQUIVALENT SPACING (FT.) 11.64 IMPEDANCE DATA POSITIVE SEQUENCE (OHMS) 0.7258 + j3.2142 ZERO SEQUENCE (OHMS) 2.5921 + j11.1720 POSITIVE SEQUENCE (P.U.) 0.0028 + j0.0124 ZERO SEQUENCE (P.U.) 0.0100 + j0.0431

November 2012 System Data Book - 2012 Ver 9a Page 12

LINE DATA LINE NO.: Q5 VOLTAGE: 161 KV TERMINALS: Northern Hills Substation [625415] TO: Zumbro River Substation [625425] LINE TOTAL LINE MILES 4.17 Overhead PHASE CONDUCTOR 556 MCM ACSR 18/1 Osprey SHIELD CONDUCTOR 3/8” EHS Steel POS. SEQ. SUSCEPTANCE (P.U.) 0.00601 ZERO SEQ. SUSCEPTANCE (P.U.) 0.00344 CHARGING AMPS 2.1552 LOADING CAPACITY (MVA) SUMMER NORM / EMER 198/221 WINTER NORM / EMER 250/275 LOADING CAPACITY (AMPS) SUMMER NORM / EMER 710/793 WINTER NORM / EMER 897/986 EQUIVALENT SPACING (FT.) 11.64 IMPEDANCE DATA POSITIVE SEQUENCE (OHMS) 0.6999 + j3.1883 ZERO SEQUENCE (OHMS) 2.4366 + j10.6276 POSITIVE SEQUENCE (P.U.) 0.0027 + j0.0123 ZERO SEQUENCE (P.U.) 0.0094 + j0.0410

November 2012 System Data Book - 2012 Ver 9a Page 13

LINE DATA LINE NO.: Q6 VOLTAGE: 161 KV TERMINALS: Zumbro River Substation [625425] TO: Chester Substation (RPU) [625445] LINE TOTAL LINE MILES 10.30 Overhead PHASE CONDUCTOR 556.5 MCM ACSR 18/1 Osprey SHIELD CONDUCTOR 3/8” EHS Steel POS. SEQ. SUSCEPTANCE (P.U.) 0.01529 ZERO SEQ. SUSCEPTANCE (P.U.) 0.00811 CHARGING AMPS 5.4830 LOADING CAPACITY (MVA) SUMMER NORM / EMER 198/221 WINTER NORM / EMER 250/275 LOADING CAPACITY (AMPS) SUMMER NORM / EMER 710/793 WINTER NORM / EMER 897/986 EQUIVALENT SPACING (FT.) 11.64 IMPEDANCE DATA POSITIVE SEQUENCE (OHMS) 1.7367 + j7.6726 ZERO SEQUENCE (OHMS) 6.1692 + j26.5949 POSITIVE SEQUENCE (P.U.) 0.0067 + j0.0296 ZERO SEQUENCE (P.U.) 0.0238 + j0.1026

November 2012 System Data Book - 2012 Ver 9a Page 14

LINE DATA LINE NO.: Q7 VOLTAGE: 161 KV TERMINALS: Cascade Creek Substation [625430] TO: Crosstown Substation [625405] LINE TOTAL LINE MILES 1.215 Overhead PHASE CONDUCTOR 2-556.5 MCM ACSR 18/1* Osprey SHIELD CONDUCTOR OPGW POS. SEQ. SUSCEPTANCE (P.U.) 0.00346 ZERO SEQ. SUSCEPTANCE (P.U.) 0.0019 CHARGING AMPS 0.620 LOADING CAPACITY (MVA)* SUMMER NORM / EMER 396/425* WINTER NORM / EMER 452/474* LOADING CAPACITY (AMPS) SUMMER NORM / EMER 1420/1732 WINTER NORM / EMER 1621/1732 EQUIVALENT SPACING (FT.) 11.4 IMPEDANCE DATA POSITIVE SEQUENCE (OHMS) 0.1037 + j0.4666 ZERO SEQUENCE (OHMS) 0.3629 + j1.5294 POSITIVE SEQUENCE (P.U.) 0.0004 + j0.0018 ZERO SEQUENCE (P.U.) 0.0014 + j0.0059 * See Note 8 & 9 in Legend page 1

November 2012 System Data Book - 2012 Ver 9a Page 15

LINE DATA LINE NO.: Q8 VOLTAGE: 161 KV TERMINALS: Cascade Creek Substation [625430] TO: IBM Substation [625420] LINE TOTAL LINE MILES 2.10 Overhead PHASE CONDUCTOR 556.5 MCM ACSR 18/1 Osprey SHIELD CONDUCTOR 3/8” EHS Steel POS. SEQ. SUSCEPTANCE (P.U.) 0.00312 ZERO SEQ. SUSCEPTANCE (P.U.) 0.00169 CHARGING AMPS 1.1188 LOADING CAPACITY (MVA) SUMMER NORM / EMER 198/221 WINTER NORM / EMER 250/275 LOADING CAPACITY (AMPS) SUMMER NORM / EMER 710/793 WINTER NORM / EMER 897/986 EQUIVALENT SPACING (FT.) 11.64 IMPEDANCE DATA POSITIVE SEQUENCE (OHMS) 0.3629 + j1.5553 ZERO SEQUENCE (OHMS) 1.2183 + j5.4175 POSITIVE SEQUENCE (P.U.) 0.0014 + j0.0060 ZERO SEQUENCE (P.U.) 0.0047 + j0.0209

November 2012 System Data Book - 2012 Ver 9a Page 16

LINE DATA LINE NO.: Q9 VOLTAGE: 161 KV TERMINALS: IBM Substation [625420] TO: Northern Hills Substation [625415] Westside Substation [625436] IBM – Tap NH – Tap Westside – Tap LINE Segment Segment Segment TOTAL LINE MILES 1.27 Overhead 1.57 Overhead 1.83 Overhead 4.67 PHASE CONDUCTOR 954 MCM ACSR 954 MCM ACSR 954 MCM ACSR 45/7 Rail 45/7 Rail 45/7 Rail SHIELD CONDUCTOR OPGW 3/8” EHS Steel OPGW POS. SEQ. SUSCEPTANCE (P.U.) 0.00190 0.00236 0.00274 ZERO SEQ. SUSCEPTANCE (P.U.) 0.00116 0.00143 0.00166 CHARGING AMPS 0.68 0.84 0.98 2.50 LOADING CAPACITY (MVA) SUMMER NORM / EMER 278/305 278/305 342/376 WINTER NORM / EMER 335/335 335/335 399/439 LOADING CAPACITY (AMPS) SUMMER NORM / EMER 997/1094 997/1094 1225/1348 WINTER NORM / EMER 1200/1200 1200/1200 1430/1573 EQUIVALENT SPACING (FT.) 15.45 15.45 14.67 IMPEDANCE DATA POSITIVE SEQUENCE (OHMS) 0.1287 + j0.9247 0.1595 + j1.1456 0.1854 + j1.3319 ZERO SEQUENCE (OHMS) 0.4916 + 3.2892 0.6090 + j4.0747 0.7081 + j4.7375 POSITIVE SEQUENCE (P.U.) 0.0005 + j0.0036 0.0006 + j0.0044 0.0007 + j0.0051 ZERO SEQUENCE (P.U.) 0.0019 + j0.0127 0.0024 + j0.0157 0.0027 + j0.0183 * The Westside tap is constructed at 212 deg. F. NESC sag limit. The Northern Hills to IBM original line is constructed at the 167 degree F. NESC sag limit.

November 2012 System Data Book - 2012 Ver 9a Page 17

LINE DATA LINE NO.: Q10 VOLTAGE: 161 KV TERMINALS: Crosstown Substation [625405] TO: Silver Lake Substation [625440] LINE TOTAL LINE MILES 0.36 Overhead MUTUAL MILES PHASE CONDUCTOR 2-556 MCM ACSR 18/1* Osprey SHIELD CONDUCTOR OPGW POS. SEQ. SUSCEPTANCE (P.U.) 0.00012 ZERO SEQ. SUSCEPTANCE (P.U.) 0.00007 CHARGING AMPS 0.178 LOADING CAPACITY (MVA)* SUMMER NORM / EMER 396/425* WINTER NORM / EMER 452/474* LOADING CAPACITY (AMPS) SUMMER NORM / EMER 1420/1732 WINTER NORM / EMER 1621/1732 EQUIVALENT SPACING (FT.) 15.1 IMPEDANCE DATA POSITIVE SEQUENCE (OHMS) 0.0259 + j0.1555 ZERO SEQUENCE (OHMS) 0.1037 + j0.4666 POSITIVE SEQUENCE (P.U.) 0.0001 + j0.0006 ZERO SEQUENCE (P.U.) 0.0004 + j0.0018 * See Note 8 & 9 in Legend

November 2012 System Data Book - 2012 Ver 9a Page 18

LINE DATA LINE NO.: DPC Q15 VOLTAGE: 161 KV TERMINALS: RPU’s Chester Substation [625445] TO: DPC’s Rochester Substation [69547] LINE TOTAL LINE MILES 0.042 (Approximately 222 feet) MUTUAL MILES PHASE CONDUCTOR 954 MCM ACSR 45/7 Rail SHIELD CONDUCTOR 3/8” EHS Steel POS. SEQ. SUSCEPTANCE (P.U.) 0.00007 ZERO SEQ. SUSCEPTANCE (P.U.) 0.00005 LOADING CAPACITY (MVA) SUMMER NORM / EMER 302/332 WINTER NORM / EMER 335/369 LOADING CAPACITY (AMPS) SUMMER NORM / EMER 1083/1191 WINTER NORM / EMER 1200/1323

a)

EQUIVALENT SPACING (FT.) N/A IMPEDANCE DATA POSITIVE SEQUENCE (OHMS) 0.00473 + J0.03157 ZERO SEQUENCE (OHMS) 0.02653 + J0.10459 POSITIVE SEQUENCE (P.U) 0.00002 + J0.00012 ZERO SEQUENCE (P.U.) 0.00010 + J0.00040 a)

Winter Rating limited by 1200 Amp terminal equipment – Conductor rating is 396 MVA and 1,420 Amps

November 2012 System Data Book - 2012 Ver 9a Page 19

LINE DATA LINE NO.: DPC Q16 VOLTAGE: 161 KV TERMINALS: RPU’s Chester Substation [625445] TO: DPC’s Rochester Substation [69547] LINE TOTAL LINE MILES 0.078 (Approximately 413 feet) PHASE CONDUCTOR 954 MCM ACSR 45/7 Rail SHIELD CONDUCTOR 3/8” EHS Steel POS. SEQ. SUSCEPTANCE (P.U.) 0.00012 ZERO SEQ. SUSCEPTANCE (P.U.) 0.00008 LOADING CAPACITY (MVA) SUMMER NORM / EMER 302/332 WINTER NORM / EMER 335/369 LOADING CAPACITY (AMPS) SUMMER NORM / EMER 1083/1191 WINTER NORM / EMER 1200/1323

a)

EQUIVALENT SPACING (FT.) N/A IMPEDANCE DATA POSITIVE SEQUENCE (OHMS) 0.00861 + J0.05744 ZERO SEQUENCE (OHMS) 0.04828 + J0.19030 POSITIVE SEQUENCE (P.U.) 0.00003 + J0.00022 ZERO SEQUENCE (P.U.) 0.00019 + J0.00073 a)

Winter Rating limited by 1200 Amp terminal equipment – Conductor rating is 396 MVA and 1,420 Amps

November 2012 System Data Book - 2012 Ver 9a Page 20

Line Q1 Rating vs. Temperature graph

November 2012 System Data Book - 2012 Ver 9a Page 21

Lines Q2 – Q6 & Q8 Rating vs. Temperature graph

November 2012 System Data Book - 2012 Ver 9a Page 22

Lines Q7 & Q10 Rating vs. Temperature graph

November 2012 System Data Book - 2012 Ver 9a Page 23

Line Q9 Rating vs. Temperature graph

November 2012 System Data Book - 2012 Ver 9a Page 24

Line Q9 Rating vs. Temperature graph

November 2012 System Data Book - 2012 Ver 9a Page 25

Line Q9 Rating vs. Temperature graph

November 2012 System Data Book - 2012 Ver 9a Page 26

Transmission Line Capacity vs. Ambient Temperature Rating Data

November 2012 System Data Book - 2012 Ver 9a Page 27

RPU Line Rating Summary Guide

November 2012 System Data Book - 2012 Ver 9a Page 28

Substation Apparatus Limits

November 2012 System Data Book - 2012 Ver 9a Page 29

GENERATION DATA

LEGEND

1. For generating units where hydrogen is used as the generator coolant, the manufacturer’s maximum

nameplate MVA rating is given for a hydrogen pressure of 30.0 PSI gauge. The manufacturer’s minimum nameplate MVA rating is given for a hydrogen pressure of 0.5 PSI gauge.

2. Type and rating data for reactors and resistors used as neutral current limiting devices for generating

units can be found in the section marked Miscellaneous Data. Impedances of these devices are not included in the generator impedance data.

3. Impedance data given as % on a machine base is the actual impedance data obtained from the

generator test report. These values are test results with the generator nameplate maximum MVA rating used as an MVA base.

4. The impedance data given as P.U. on 100 MVA base is the actual impedance data obtained from the

generator test report adjusted to a uniform system base of 100 MVA and expressed in per unit. 5. The inertia constant H is expressed in kilowatt-seconds/kilo volt-amperes and is computed as follows: H=0.231 (WK

2) (RPM)

2(10

-6)

KVA Where WK

2 = Moment of inertia in lb.-ft

2

RPM = Turbine speed in revolutions/minute KVA = Generator nameplate rating in kilo volt-amperes 6. The Maximum VAR OUTPUT and Maximum VAR INTAKE are the reactive limits of the machine. (Care

must be taken to not exceed the MVA rating of the machine.)

7. Generator and associated equipment ratings are based on RPU’s Facilities Ratings Methodology for Transmission, Substation, and Generation Equipment, in compliance with NERC FAC-008-3.

November 2012 System Data Book - 2012 Ver 9a Page 30

SILVER LAKE GENERATING PLANT FACT SHEET

UNIT NUMBER 1 2 3 4 ON LINE August 1949 December 1953 November 1962 December 1969 TURBINE-GENERATOR Manufacturer Westinghouse Westinghouse Westinghouse General Electric Generator Nameplate kW 7,500 11,500 25,000 54,400 (Turb 22,000) Maximum Gross Capability kW 10,000 14,000 25,000 60,000 Generator 13,800 volt 13,800 volt 13,800 volt 13,800 volt air cooled air cooled hydrogen cooled hydrogen cooled Turbine Type condensing condensing condensing condensing single flow single flow single flow single flow 3600 PRM 3600 PRM 3600 RPM 3600 RPM BOILER Manufacturer Riley Riley Babcock & Wilcox Babcock & Wilcox Fuel Bituminous coal Bituminous coal Bituminous coal Bituminous coal or natural gas or natural gas or natural gas or natural gas Burners Pulverized coal Pulverized coal Pulverized coal Pulverized coal Maximum Coal Burn Rate 10,000 pounds/hr 15,000 pounds/hr 25,000 pounds/hr 52,000 pounds/hr Steaming Capacity lb/hr 90,000 120,000 220,000 520,000 Steam Conditions 625 PSIG/830-F 625 PSIG/830-F 875 PSIG/905-F 1350 PSIG/955-F COOLING WATER (Maximum Pump Rating in gallons per minute GPM) Once through river water 11,000 14,500 22,000 25,000 Cooling Towers N/A N/A 22,000 41,000 STACK EMISSION EQUIPMENT Type Cyclone Cyclone & Cyclone & Electrostatic Electrostatic Electrostatic Electrostatic Precipitator Precipitator Precipitator Precipitator Manufacturer UOP UOP UOP/Field Service Belco Continuous Emission Monitors S02 & Opacity S02 & Opacity S02 & Opacity S02 & Opacity MISCELLANEOUS - Maximum daily burn 1,000 tons - Unloading capability 1,500 tons per day - Site storage capacity 85,000 tons

November 2012 System Data Book - 2012 Ver 9a Page 31

GENERATION DATA GENERATOR NO.: 1 LOCATION: Silver Lake Plant FUEL SOURCE: Gas and Coal MANUFACTURER: Westinghouse YEAR OF MANUFACTURE: 1948 SERIAL NO.: 1S31P591 PRIME MOVER: Steam Turbine VOLTAGE/CONNECTION: 13,800 / Wye PHASE/FREQ./SPEED: 3 Phase / 60 Cycle / 3,600 RPM MVA RATING: (MAX./MIN.) 9.375 @ 0.80 pf / GROUNDING IMPEDANCE: Neutral Reactor / See Reactor Data (TYPE/RATING) GENERATOR COOLANT: Air IMPEDANCE DATA (P.U. ON MACHINE BASE) (P.U. ON 100 MVA BASE) SYNCHRONOUS REACTANCE (Xd) 1.45 SYNCHRONOUS REACTANCE (Xd) 15.4667 TRANSIENT REACTANCE (X’d) 0.206 TRANSIENT REACTANCE (X’d) 2.1973 SUBTRANSIENT REACTANCE (X”d) 0.116 SUBTRANSIENT REACTANCE (X”d) 1.2373 NEG. SEQUENCE REACTANCE (X2) 0.116 NEG. SEQUENCE REACTANCE (X2) 1.2373 ZERO SEQUENCE REACTANCE (Xo) 0.035 ZERO SEQUENCE REACTANCE (Xo) 0.3733

INERTIA CONSTANT (H) 5.51 KV-Sec/KVA Maximum MW OUTPUT (Pmax) 9.0 Minimum MW OUTPUT (Pmin) 3.0 Maximum MVAR OUTPUT 5.1 Maximum MVAR INTAKE -2.8 NOTE: Comparison of existing RPU generation data (shown here) and data requested from Westinghouse

Corporation show slight discrepancies in the impedance values. The Westinghouse Corporation data is contained in an appendix at the end of this section.

November 2012 System Data Book - 2012 Ver 9a Page 32

GENERATION DATA GENERATOR NO.: 2 LOCATION: Silver Lake Plant FUEL SOURCE: Gas and Coal MANUFACTURER: Westinghouse YEAR OF MANUFACTURE: 1953 SERIAL NO.: 1S47P256 PRIME MOVER: Steam Turbine VOLTAGE/CONNECTION: 13,800 / Wye PHASE/FREQ./SPEED: 3 Phase / 60 Cycle / 3,600 RPM MVA RATING: (MAX./MIN.) 13.529 @ 0.85 pf / GROUNDING IMPEDANCE: Neutral Reactor / See Reactor Data (TYPE/RATING) GENERATOR COOLANT: Air IMPEDANCE DATA (P.U. ON MACHINE BASE) (P.U. ON 100 MVA BASE) SYNCHRONOUS REACTANCE (Xd) 1.33 SYNCHRONOUS REACTANCE (Xd) 9.8307 TRANSIENT REACTANCE (X’d) 0.149 TRANSIENT REACTANCE (X’d) 1.1013 SUBTRANSIENT REACTANCE (X”d) 0.079 SUBTRANSIENT REACTANCE (X”d) 0.5839 NEG. SEQUENCE REACTANCE (X2) 0.079 NEG. SEQUENCE REACTANCE (X2) 0.5839 ZERO SEQUENCE REACTANCE (Xo) 0.052 ZERO SEQUENCE REACTANCE (Xo) 0.3844

INERTIA CONSTANT (H) 6.62 KW-Sec/KVA Maximum MW OUTPUT (Pmax) 13.5 Minimum MW OUTPUT (Pmin) 4.0 Maximum MVAR OUTPUT 7.1 Maximum MVAR INTAKE -3.6 NOTE: Comparison of existing RPU generation data (shown here) and data requested from Westinghouse

Corporation show slight discrepancies in the impedance values. The Westinghouse Corporation data is contained in an appendix at the end of this section.

November 2012 System Data Book - 2012 Ver 9a Page 33

GENERATION DATA GENERATOR NO.: 3 LOCATION: Silver Lake Plant FUEL SOURCE: Gas and Coal MANUFACTURER: Westinghouse YEAR OF MANUFACTURE: 1962 SERIAL NO.: 1S65P979 PRIME MOVER: Steam Turbine VOLTAGE/CONNECTION: 13,800 / Wye PHASE/FREQ./SPEED: 3 Phase / 60 Cycle / 3,600 RPM MVA RATING: (MAX./MIN.) 29.411 @ 0.85 pf / 23.5 @ 0.85 pf GROUNDING IMPEDANCE: Neutral Reactor / See Reactor Data (TYPE/RATING) GENERATOR COOLANT: Hydrogen IMPEDANCE DATA (P.U. ON MACHINE BASE) (P.U. ON 100 MVA BASE) SYNCHRONOUS REACTANCE (Xd) 1.80 SYNCHRONOUS REACTANCE (Xd) 6.1202 TRANSIENT REACTANCE (X’d) 0.263 TRANSIENT REACTANCE (X’d) 0.8942 SUBTRANSIENT REACTANCE (X”d) 0.154 SUBTRANSIENT REACTANCE (X”d) 0.5236 NEG. SEQUENCE REACTANCE (X2) 0.154 NEG. SEQUENCE REACTANCE (X2) 0.5236 ZERO SEQUENCE REACTANCE (Xo) 0.046 ZERO SEQUENCE REACTANCE (Xo) 0.1564

INERTIA CONSTANT (H) 3.61 KW-Sec/KVA

Maximum MW OUTPUT (Pmax) 22.0 Minimum MW OUTPUT (Pmin) 7.0 Maximum MVAR OUTPUT 15.5 Maximum MVAR INTAKE -7.78

NOTE: Comparison of existing RPU generation data (shown here) and data requested from Westinghouse Corporation show slight discrepancies in the impedance values. The Westinghouse Corporation data is

contained in an appendix at the end of this section.

November 2012 System Data Book - 2012 Ver 9a Page 34

GENERATION DATA GENERATOR NO.: 4 LOCATION: Silver Lake Plant FUEL SOURCE: Gas and Coal MANUFACTURER: General Electric YEAR OF MANUFACTURE: 1969 SERIAL NO.: 8357386 PRIME MOVER: Steam Turbine VOLTAGE/CONNECTION: 13,800 / Wye PHASE/FREQ./SPEED: 3 Phase / 60 Cycle / 3,600 RPM MVA RATING: (MAX./MIN.) 64.0 @ 0.85 pf / 44.8 @ 0.85 pf GROUNDING IMPEDANCE: Neutral Resistor / See Resistor data (TYPE/RATING) GENERATOR COOLANT: Hydrogen IMPEDANCE DATA (P.U. ON MACHINE BASE) (P.U. ON 100 MVA BASE) SYNCHRONOUS REACTANCE (Xd) 1.84 SYNCHRONOUS REACTANCE (Xd) 2.875 TRANSIENT REACTANCE (X’d) 0.300 TRANSIENT REACTANCE (X’d) 0.468 SUBTRANSIENT REACTANCE (X”d) 0.190 SUBTRANSIENT REACTANCE (X”d) 0.296 NEG. SEQUENCE REACTANCE (X2) 0.190 NEG. SEQUENCE REACTANCE (X2) 0.296 ZERO SEQUENCE REACTANCE (Xo) 0.095 ZERO SEQUENCE REACTANCE (Xo) 0.148

INERTIA CONSTANT (H) 2.63 KW-Sec/KVA

Maximum MW OUTPUT (Pmax) 60.0 Minimum MW OUTPUT (Pmin) 15.0 Maximum MVAR OUTPUT 33.7 Maximum MVAR INTAKE -16.9

November 2012 System Data Book - 2012 Ver 9a Page 35

GENERATION DATA GENERATOR NO.: 1 LOCATION: Cascade Creek Substation FUEL SOURCE: No. 2 Oil or Natural Gas MANUFACTURER: Westinghouse YEAR OF MANUFACTURE: 1975 SERIAL NO.: 17A2182 PRIME MOVER: Gas Turbine VOLTAGE/CONNECTION: 13,800 / Wye PHASE/FREQ./SPEED: 3 Phase / 60 cycle / 3,600 RPM MVA RATING:(MAX./MIN.) 39.2 @ 0.90 pf / GROUNDING IMPEDANCE: Neutral Reactor / See Reactor Data (TYPE/RATING) GENERATOR COOLANT: Air IMPEDANCE DATA (P.U. ON MACHINE BASE) (P.U. ON 100 MVA BASE) SYNCHRONOUS REACTANCE (Xd) 2.048 SYNCHRONOUS REACTANCE (Xd) 5.2224 TRANSIENT REACTANCE (X’d) 0.314 TRANSIENT REACTANCE (X’d) 0.8007 SUBTRANSIENT REACTANCE (X”d) 0.161 SUBTRANSIENT REACTANCE (X”d) 0.4106 NEG. SEQUENCE REACTANCE (X2) 0.161 NEG. SEQUENCE REACTANCE (X2) 0.4106 ZERO SEQUENCE REACTANCE (Xo) 0.056 ZERO SEQUENCE REACTANCE (Xo) 0.1482

INERTIA CONSTANT (H) 1.92 KW-Sec/KVA Maximum MW OUTPUT (Pmax) 27.0 Sum 40.0 Win Minimum MW OUTPUT (Pmin) 5.0 Maximum MVAR OUTPUT 17.1 Maximum MVAR INTAKE -8.5 NOTE: Comparison of existing RPU generation data (shown here) and data requested from Westinghouse

Corporation show slight discrepancies in the impedance values. The Westinghouse Corporation data is contained in an appendix at the end of this section.

November 2012 System Data Book - 2012 Ver 9a Page 36

GENERATION DATA GENERATOR NO.: 2 LOCATION: Cascade Creek Substation FUEL SOURCE: No. 2 Oil or Natural Gas MANUFACTURER: Pratt & Whitney / Brush YEAR OF MANUFACTURE: 2001 SERIAL NO.: 905043.010 PRIME MOVER: Gas Turbine VOLTAGE/CONNECTION: 13,800 / Wye PHASE/FREQ./SPEED: 3 Phase / 60 cycle / 3,600 RPM MVA RATING:(MAX./MIN.) 71.176 @ 0.85 pf / GROUNDING IMPEDANCE: Neutral Resistor / Dist. Trans. w/secondary resistor (TYPE/RATING) GENERATOR COOLANT: Air IMPEDANCE DATA (P.U. ON MACHINE BASE) (P.U. ON 100 MVA BASE) SYNCHRONOUS REACTANCE (Xd) 2.283 SYNCHRONOUS REACTANCE (Xd) 3.2075 TRANSIENT REACTANCE (X’d) 0.2166 TRANSIENT REACTANCE (X’d) 0.3043 SUBTRANSIENT REACTANCE (X”d) 0.1492 SUBTRANSIENT REACTANCE (X”d) 0.2096 NEG. SEQUENCE REACTANCE (X2) 0.1718 NEG. SEQUENCE REACTANCE (X2) 0.2414 ZERO SEQUENCE REACTANCE (Xo) 0.0913 ZERO SEQUENCE REACTANCE (Xo) 0.1283

INERTIA CONSTANT (H) 1.79 KW-Sec/KVA Maximum MW OUTPUT (Pmax) 49.9 Minimum MW OUTPUT (Pmin) 3.0 Maximum MVAR OUTPUT 37.5 Maximum MVAR INTAKE -18.7

November 2012 System Data Book - 2012 Ver 9a Page 37

GENERATION DATA GENERATOR NO.: 1 LOCATION: Hydro Plant FUEL SOURCE: Water MANUFACTURER: General Electric YEAR OF MANUFACTURE: 1915-1919 Rebuilt 1984 SERIAL NO.: 1352999 PRIME MOVER: Francis Turbine VOLTAGE/CONNECTION: 2300 / Delta PHASE/FREQ./SPEED: 3 Phase / 60 Cycle / 225 RPM MVA RATING:(MAX./MIN.) 1.487 @ 0.95 pf / GROUNDING IMPEDANCE: Ungrounded / (TYPE/RATING) GENERATOR COOLANT: Air IMPEDANCE DATA (P.U. ON MACHINE BASE) (P.U. ON 100 MVA BASE) SYNCHRONOUS REACTANCE (Xd) 1.50 SYNCHRONOUS REACTANCE (Xd) 100.874 TRANSIENT REACTANCE (X’d) 0.40 TRANSIENT REACTANCE (X’d) 26.899 SUBTRANSIENT REACTANCE (X”d) 0.40 SUBTRANSIENT REACTANCE (X”d) 26.899 NEG. SEQUENCE REACTANCE (X2) 0.56 NEG. SEQUENCE REACTANCE (X2) 37.659 ZERO SEQUENCE REACTANCE (Xo) 0.07 ZERO SEQUENCE REACTANCE (Xo) 4.707 Maximum MW OUTPUT (Pmax) 1.2 Minimum MW OUTPUT (Pmin) 0.7 Maximum MVAR OUTPUT 0.46 Maximum MVAR INTAKE -0.23

November 2012 System Data Book - 2012 Ver 9a Page 38

GENERATION DATA GENERATOR NO.: 2 LOCATION: Hydro Plant FUEL SOURCE: Water MANUFACTURER: General Electric YEAR OF MANUFACTURE: 1915-1919 Rebuilt 1984 SERIAL NO.: 1353000 PRIME MOVER: Francis Turbine VOLTAGE/CONNECTION: 2300 / Delta PHASE/FREQ./SPEED: 3 Phase / 60 Cycle / 225 RPM MVA RATING:(MAX./MIN.) 1.487 @ 0.95 pf / GROUNDING IMPEDANCE: Ungrounded / (TYPE/RATING) GENERATOR COOLANT: Air IMPEDANCE DATA (P.U. ON MACHINE BASE) (P.U. ON 100 MVA BASE) SYNCHRONOUS REACTANCE (Xd) 1.50 SYNCHRONOUS REACTANCE (Xd) 100.874 TRANSIENT REACTANCE (X’d) 0.40 TRANSIENT REACTANCE (X’d) 26.899 SUBTRANSIENT REACTANCE (X”d) 0.40 SUBTRANSIENT REACTANCE (X”d) 26.899 NEG. SEQUENCE REACTANCE (X2) 0.56 NEG. SEQUENCE REACTANCE (X2) 37.659 ZERO SEQUENCE REACTANCE (Xo) 0.07 ZERO SEQUENCE REACTANCE (Xo) 4.707 Maximum MW OUTPUT (Pmax) 1.2 Minimum MW OUTPUT (Pmin) 0.7 Maximum MVAR OUTPUT 0.46 Maximum MVAR INTAKE -0.23

November 2012 System Data Book - 2012 Ver 9a Page 39

GENERATION DATA GENERATOR NO.: IBM Genset No. 1 LOCATION: IBM Plant Bldg. 20 FUEL SOURCE: Diesel MANUFACTURER: Caterpillar YEAR OF MANUFACTURE: 2006 SERIAL NO.: GZS00145 PRIME MOVER: Diesel Engine VOLTAGE/CONNECTION: 480/277 / Wye PHASE/FREQ./SPEED: 3 Phase / 60 Cycle / 1800 RPM MVA RATING:(MAX./MIN.) 2.281 @ 0.80 pf / GROUNDING IMPEDANCE: Solidly Grounded / (TYPE/RATING) GENERATOR COOLANT: Air IMPEDANCE DATA (P.U. ON MACHINE BASE) (P.U. ON 100 MVA BASE) SYNCHRONOUS REACTANCE (Xd) 3.1179 SYNCHRONOUS REACTANCE (Xd) 136.690 TRANSIENT REACTANCE (X’d) 0.2188 TRANSIENT REACTANCE (X’d) 9.592 SUBTRANSIENT REACTANCE (X”d) 0.1356 SUBTRANSIENT REACTANCE (X”d) 5.945 NEG. SEQUENCE REACTANCE (X2) 0.1297 NEG. SEQUENCE REACTANCE (X2) 5.686 ZERO SEQUENCE REACTANCE (Xo) 0.0079 ZERO SEQUENCE REACTANCE (Xo) 0.346 Maximum MW OUTPUT (Pmax) 1.825 Minimum MW OUTPUT (Pmin) 0.456 Maximum MVAR OUTPUT 1.368 Maximum MVAR INTAKE 0

November 2012 System Data Book - 2012 Ver 9a Page 40

GENERATION DATA GENERATOR NO.: IBM Genset No. 2 LOCATION: IBM Plant Bldg. 301 FUEL SOURCE: Diesel MANUFACTURER: Caterpillar YEAR OF MANUFACTURE: 2006 SERIAL NO.: GZS00144 PRIME MOVER: Diesel Engine VOLTAGE/CONNECTION: 480/277 / Wye PHASE/FREQ./SPEED: 3 Phase / 60 Cycle / 1800 RPM MVA RATING:(MAX./MIN.) 2.281 @ 0.80 pf / GROUNDING IMPEDANCE: Solidly Grounded / (TYPE/RATING) GENERATOR COOLANT: Air IMPEDANCE DATA (P.U. ON MACHINE BASE) (P.U. ON 100 MVA BASE) SYNCHRONOUS REACTANCE (Xd) 3.1179 SYNCHRONOUS REACTANCE (Xd) 136.690 TRANSIENT REACTANCE (X’d) 0.2188 TRANSIENT REACTANCE (X’d) 9.592 SUBTRANSIENT REACTANCE (X”d) 0.1356 SUBTRANSIENT REACTANCE (X”d) 5.945 NEG. SEQUENCE REACTANCE (X2) 0.1297 NEG. SEQUENCE REACTANCE (X2) 5.686 ZERO SEQUENCE REACTANCE (Xo) 0.0079 ZERO SEQUENCE REACTANCE (Xo) 0.346 Maximum MW OUTPUT (Pmax) 1.825 Minimum MW OUTPUT (Pmin) 0.456 Maximum MVAR OUTPUT 1.368 Maximum MVAR INTAKE 0

November 2012 System Data Book - 2012 Ver 9a Page 41

APPENDIX

November 2012 System Data Book - 2012 Ver 9a Page 42

WESTINGHOUSE CORPORATION

GENERATION DATA

CITY OF ROCHESTER, MINNESOTA

Silver Lake Plant

Unit #1

Silver Lake Plant Unit #2

Silver Lake Plant Unit #3

Cascade Creek Substation Unit #1

Steam Turbine Steam Turbine Steam Turbine Gas Turbine

Gen. S/N 1S31P591 1S47P256 1S65P979 83P350 KVA 9375 13,529 29,411 39,222 % PF 80 85 85 90 KW 7500 11,500 25,000 35,300 % Xd 131 145 178 204.8 % X’d 17.8 20.6 26.0 27.6 % X”d 8.9 11.6 15.0 16.1 % X2 8.9 11.6 15.0 16.1 % Xo 2.8 3.5 4.3 5.6 WK2(lb-ft2) 7500 10,800 12,800 22,600 Coolant Air Air 30# H2 Air Turbine S/N 5A4099 10A4017-1 13A2570 17A2182 WK2(lb-ft2) Turbine

9747

19,103

22,650

76,000

Exciter 755 Gear 7900 Total Unit WK2 (lb-ft2) 17,247 29,903 35,450 107,225 H(KW-Sec/KVA) 5.5076 6.6171 3.6085 8.1860* *NOTE: The Westinghouse Corporation data for the Inertia Constant (H) does not agree at all well with

empirical modeling data. A better approximation was developed in 2002 and is shown on the generator sheet.

November 2012 System Data Book - 2012 Ver 9a Page 43

POWER TRANSFORMER DATA

LEGEND

1. The underlined no load tap setting is a) the setting observed in service in 1979 when the original data was

gathered or b) the setting selected upon commissioning for equipment installed after 1979. 2. The % impedance on transformer base is the actual impedance stamped on the transformer nameplate.

This value is a test result using the transformer OA rating @ 55ºC winding temperature as an MVA base. Impedance data that is shown for R + jX is derived from the manufacturer’s test report for impedance and load losses. Impedance data is generally reported at 75ºC or 85 ºC and base rating. R % = Load Losses/base rating.

3. The PU impedance on 100 MVA base is the actual impedance stamped on the transformer nameplate

adjusted to a uniform system base of 100 MVA and expressed in per unit. 4. In cases where the transformer serves as a generator step-up transformer, for computer modeling

purposes the impedance is also presented on the generator base MVA as required for PSS/E.

5. Transformer ratings are based on RPU’s Facilities Ratings Methodology for Transmission, Substation, and Generation Equipment, in compliance with NERC FAC-008-3.

November 2012 System Data Book - 2012 Ver 9a Page 44

TRANSFORMER DATA TRANSFORMER NO.: T1 LOCATION: Bamber Valley Substation MANUFACTURER: Delta-Star YEAR OF MANUFACTURER: 2001 SERIAL NO.: F68151101 TYPE: Two winding PHASE/CYCLE: 3 Phase/60 Cycle MVA RATING: @55ºC 15.0-OA / 20.0-FA / 25.0-FOA MVA RATING: @65ºC 16.8-OA / 22.4-FA / 28.0-FOA NO LOAD WINDING BUSHING VOLTAGE TAPS AT BIL/(KV CLASS) BIL/(KV CLASS) HIGH VOLTAGE WINDING Delta CONNECTED 161000 None 650kV/(138kV) 650kV/(138kV) LOW VOLTAGE WINDING Grd.Wye CONNECTED 13800Y/7970 110kV/(15kV) 110kV/(15kV) LTC DATA LTC ON LV WINDING, ±15 % RANGE, IN 32 STEPS OF 15/16 % % IMPEDANCE ON P.U. IMPEDANCE ON IMPEDANCE DATA TRANS. BASE 100 MVA BASE HV-LV 0.27 + j9.196 = 9.20 0.018 + j0.6131 = 0.6133

November 2012 System Data Book - 2012 Ver 9a Page 45

TRANSFORMER DATA TRANSFORMER NO.: T2 LOCATION: Bamber Valley Substation MANUFACTURER: GE Prolec YEAR OF MANUFACTURER: 1999 SERIAL NO.: G38101 TYPE: Two winding PHASE/CYCLE: 3 Phase/60 Cycle MVA RATING: @55ºC 15.0 / 20.0-FA / 25.0-FA MVA RATING: @65ºC 16.8 / 22.4 / 28.0-FA NO LOAD WINDING BUSHING VOLTAGE TAPS AT BIL/(KV CLASS) BIL/(KV CLASS) HIGH VOLTAGE WINDING Delta CONNECTED 161000 None 650kV/(161kV) 650kV/(161kV) LOW VOLTAGE WINDING Grd.Wye CONNECTED 13800Y/7970 110kV/(15kV) 110kV/(15kV) LTC DATA LTC ON LV WINDING, ± 10 % RANGE, IN 32 STEPS OF 5/8 % % IMPEDANCE ON P.U. IMPEDANCE ON IMPEDANCE DATA TRANS. BASE 100 MVA BASE HV-LV 0.42 + j 9.758 = 9.767 0.028 + j 0.6505 = 0.6511 NOTE: This unit had been originally installed at Cascade Creek substation in the T1 location. The unit was relocated and commissioned at Bamber Valley in 2009.

November 2012 System Data Book - 2012 Ver 9a Page 46

TRANSFORMER DATA TRANSFORMER NO.: GSU2 LOCATION: Cascade Creek Substation MANUFACTURER: Waukeska YEAR OF MANUFACTURER: 2001 SERIAL NO.: A4332T TYPE: Two winding PHASE/CYCLE: 3 Phase/60 Cycle MVA RATING: @55ºC 37.5-OA / 50.0-FA / 62.5-FA MVA RATING: @65ºC 41.0-OA / 56.0-FA / 70.0-FA NO LOAD WINDING BUSHING VOLTAGE TAPS AT BIL/(KV CLASS) BIL/(KV CLASS) HIGH VOLTAGE 169,050 WINDING 165,025 Delta CONNECTED 161000Y 161,000 650kV/(138kV) 750kV/(161kV) 156,975 152,950 LOW VOLTAGE WINDING Grd.Wye CONNECTED 13800 110kV/(15kV) 110kV/(15kV) LTC DATA LTC ON None WINDING, % RANGE, IN STEPS OF % % IMPEDANCE ON P.U. IMPEDANCE ON IMPEDANCE DATA TRANS. BASE 100 MVA BASE HV-LV 8.99 0.2397 P.U. IMPEDANCE ON 71.176 MVA BASE 0.1706

November 2012 System Data Book - 2012 Ver 9a Page 47

TRANSFORMER DATA TRANSFORMER NO.: T1 LOCATION: Cascade Creek Substation MANUFACTURER: Delta-Star YEAR OF MANUFACTURER: 2008 SERIAL NO.: F7411 TYPE: Two winding PHASE/CYCLE: 3 Phase/60 Cycle MVA RATING: @55ºC 20.0-OA / 26.7-FA / 33.3-FOA MVA RATING: @65ºC 22.5-OA / 29.9-FA / 37.5-FOA NO LOAD WINDING BUSHING VOLTAGE TAPS AT BIL/(KV CLASS) BIL/(KV CLASS) HIGH VOLTAGE WINDING Delta CONNECTED 161000 None 650kV/(138kV) 650kV/(138kV) LOW VOLTAGE WINDING Grd.Wye CONNECTED 13800Y/7970 110kV/(15kV) 110kV/(15kV) LTC DATA LTC ON LV WINDING, ± 15 % RANGE, IN 32 STEPS OF 15/16 % % IMPEDANCE ON P.U. IMPEDANCE ON IMPEDANCE DATA TRANS. BASE 100 MVA BASE HV-LV 0.32 + j9.13 = 9.14 0.0160 + j0.4565 = 0.4570

P.U. IMPEDANCE ON 39.2 MVA BASE 0.1784 NOTE: For dynamics simulation, this transformer serves as a generator step-up transformer for Cascade Creek Combustion Turbine #1.

November 2012 System Data Book - 2012 Ver 9a Page 48

TRANSFORMER DATA TRANSFORMER NO.: T2 LOCATION: Cascade Creek Substation MANUFACTURER: Delta-Star YEAR OF MANUFACTURER: 2001 SERIAL NO.: F68161001 TYPE: Two winding PHASE/CYCLE: 3 Phase/60 Cycle MVA RATING: @55ºC 15.0-OA / 20.0-FA / 25.0-FOA MVA RATING: @65ºC 16.8-OA / 22.4-FA / 28.0-FOA NO LOAD WINDING BUSHING VOLTAGE TAPS AT BIL/(KV CLASS) BIL/(KV CLASS) HIGH VOLTAGE WINDING Delta CONNECTED 161000 None 650kV/(138kV) 650kV/(138kV) LOW VOLTAGE WINDING Grd.Wye CONNECTED 13800Y/7970 110kV/(15kV) 110kV/(15kV) LTC DATA LTC ON LV WINDING, ± 15 % RANGE, IN 32 STEPS OF 15/16 % % IMPEDANCE ON P.U. IMPEDANCE ON IMPEDANCE DATA TRANS. BASE 100 MVA BASE HV-LV 0.28 + j9.296 = 9.30 0.0187 + j0.6197 = 0.6200

November 2012 System Data Book - 2012 Ver 9a Page 49

TRANSFORMER DATA TRANSFORMER NO.: T1 LOCATION: Crosstown Substation MANUFACTURER: ABB YEAR OF MANUFACTURER: 1992 SERIAL NO.: SLL5865 TYPE: Two winding PHASE/CYCLE: 3 Phase/60 Cycle MVA RATING: @55ºC 20.0-OA / 26.667-FA / 33.333-FA MVA RATING: @65ºC 22.4-OA / 29.865-FA / 37.330-FA NO LOAD WINDING BUSHING VOLTAGE TAPS AT BIL/(KV CLASS) BIL/(KV CLASS) HIGH VOLTAGE WINDING Delta CONNECTED 161000 None 650kV/(161kV) 650kV/(161kV) LOW VOLTAGE WINDING Grd.Wye CONNECTED 13800/7967 110kV/(15kV) 110kV/(15kV) LTC DATA LTC ON LV WINDING, ± 15 % RANGE, IN 32 STEPS OF 15/16 % % IMPEDANCE ON P.U. IMPEDANCE ON IMPEDANCE DATA TRANS. BASE 100 MVA BASE HV-LV 0.218 + j9.297 = 9.30 0.0109 + j0.4649 = 0.4650

November 2012 System Data Book - 2012 Ver 9a Page 50

TRANSFORMER DATA TRANSFORMER NO.: T2 LOCATION: Crosstown Substation MANUFACTURER: ABB YEAR OF MANUFACTURER: 1992 SERIAL NO.: SLL5859 TYPE: Two winding PHASE/CYCLE: 3 Phase/60 Cycle MVA RATING: @55ºC 20.0-OA / 26.667-FA / 33.333-FA MVA RATING: @65ºC 22.4-OA / 29.865-FA / 37.330-FA NO LOAD WINDING BUSHING VOLTAGE TAPS AT BIL/(KV CLASS) BIL/(KV CLASS) HIGH VOLTAGE WINDING Delta CONNECTED 161000 None 650kV/(161kV) 650kV/(161kV) LOW VOLTAGE WINDING Grd.Wye CONNECTED 13800/7967 110kV/(15kV) 110kV/(15kV) LTC DATA LTC ON LV WINDING, ± 15 % RANGE, IN 32 STEPS OF 15/16 % % IMPEDANCE ON P.U. IMPEDANCE ON IMPEDANCE DATA TRANS. BASE 100 MVA BASE HV-LV 0.220 + j9.277 = 9.28 0.0110 + j0.4639 = 0.4640

November 2012 System Data Book - 2012 Ver 9a Page 51

TRANSFORMER DATA TRANSFORMER NO.: KU1 LOCATION: Hydro Line Substation MANUFACTURER: Westinghouse YEAR OF MANUFACTURER: 1984 SERIAL NO.: SDT 7191-0101 TYPE: Two winding PHASE/CYCLE: 3 Phase/60 Cycle MVA RATING: @55ºC / / MVA RATING: @65ºC 3.75 / / NO LOAD WINDING BUSHING VOLTAGE TAPS AT BIL/(KV CLASS) BIL/(KV CLASS) HIGH VOLTAGE 36200 WINDING 35300 Wye CONNECTED 34400 34400 220kV/(34.5kV) 200kV/(34.5kV) 33500 32600 LOW VOLTAGE WINDING Delta CONNECTED 13800 110kV/(15kV) 110kV/(15kV) LTC DATA LTC ON None WINDING, % RANGE, IN STEPS OF % % IMPEDANCE ON P.U. IMPEDANCE ON IMPEDANCE DATA TRANS. BASE 100 MVA BASE HV-LV 7.0 1.8667

November 2012 System Data Book - 2012 Ver 9a Page 52

TRANSFORMER DATA TRANSFORMER NO.: KL1 LOCATION: Hydro Plant MANUFACTURER: Westinghouse YEAR OF MANUFACTURER: 1984 SERIAL NO.: SDT 7190-0101 TYPE: Two winding PHASE/CYCLE: 3 Phase/60 Cycle MVA RATING: @55ºC / / MVA RATING: @65ºC 3.75 / / NO LOAD WINDING BUSHING VOLTAGE TAPS AT BIL/(KV CLASS) BIL/(KV CLASS) HIGH VOLTAGE 36200 WINDING 35300 Wye CONNECTED 34400 34400 220kV/(34.5kV) 200kV/(34.5kV) 33500 32600 LOW VOLTAGE WINDING Delta CONNECTED 2300 60kV/(2.4kV) 110kV/(15kV) LTC DATA LTC ON None WINDING, % RANGE, IN STEPS OF % % IMPEDANCE ON P.U. IMPEDANCE ON IMPEDANCE DATA TRANS. BASE 100 MVA BASE HV-LV 7.0 1.8667

November 2012 System Data Book - 2012 Ver 9a Page 53

TRANSFORMER DATA TRANSFORMER NO.: T1 LOCATION: IBM Substation MANUFACTURER: McGraw Edison YEAR OF MANUFACTURER: 1980 SERIAL NO.: C-06225-5-1 TYPE: Two winding PHASE/CYCLE: 3 Phase/60 Cycle MVA RATING: @55ºC 20.0-OA / 26.667-FA / 33.333-FA MVA RATING: @65ºC 22.4-OA / 29.867-FA / 37.333-FA NO LOAD WINDING BUSHING VOLTAGE TAPS AT BIL/(KV CLASS) BIL/(KV CLASS) HIGH VOLTAGE WINDING Delta CONNECTED 161000 x 115000 161000 650kV/(161kV) 650kV/(161kV) 115000 450kV/(115kV) LOW VOLTAGE WINDING Grd.Wye CONNECTED 13800/7970 110kV/(15kV) 110kV/(15kV) LTC DATA LTC ON LV WINDING, ± 15 % RANGE, IN 32 STEPS OF 15/16 % % IMPEDANCE ON P.U. IMPEDANCE ON IMPEDANCE DATA TRANS. BASE 100 MVA BASE HV-LV (161000 Volt Conn) 0.352 + j9.55 = 9.56 0.0176 + j0.4775 = 0.4780

November 2012 System Data Book - 2012 Ver 9a Page 54

TRANSFORMER DATA TRANSFORMER NO.: T2 LOCATION: IBM Substation MANUFACTURER: McGraw Edison YEAR OF MANUFACTURER: 1980 SERIAL NO.: C-06222-5-1 TYPE: Two winding PHASE/CYCLE: 3 Phase/60 Cycle MVA RATING: @55ºC 20.0-OA / 26.667-FA / 33.333-FA MVA RATING: @65ºC 22.4-OA / 29.867-FA / 37.333-FA NO LOAD WINDING BUSHING VOLTAGE TAPS AT BIL/(KV CLASS) BIL/(KV CLASS) HIGH VOLTAGE WINDING Delta CONNECTED 161000 x 115000 161000 650kV/(161kV) 650kV/(161kV) 115000 450/(115kV) LOW VOLTAGE WINDING Grd.Wye CONNECTED 13800/7970 110kV/(15kV) 110kV/(15kV) LTC DATA LTC ON LV WINDING, ± 15 % RANGE, IN 32 STEPS OF 15/16 % % IMPEDANCE ON P.U. IMPEDANCE ON IMPEDANCE DATA TRANS. BASE 100 MVA BASE HV-LV (161000 Volt Conn) 0.352 + j9.55 = 9.56 0.0176 + j0.4775 = 0.4780

November 2012 System Data Book - 2012 Ver 9a Page 55

TRANSFORMER DATA TRANSFORMER NO.: T1 LOCATION: Northern Hills Substation MANUFACTURER: General Electric YEAR OF MANUFACTURER: 1988 SERIAL NO.: M122729 TYPE: Two winding PHASE/CYCLE: 3 Phase/60 Cycle MVA RATING: @55ºC 15.0-OA / 20.0-FA / 25.0-FOA MVA RATING: @65ºC 16.8-OA / 22.4-FA / 28.0-FOA NO LOAD WINDING BUSHING VOLTAGE TAPS AT BIL/(KV CLASS) BIL/(KV CLASS) HIGH VOLTAGE WINDING Delta CONNECTED 161000 None 650kV/(161kV) 650kV/(161kV) LOW VOLTAGE WINDING Grd.Wye CONNECTED 13800Y/7970 110kV/(15kV) 110kV/(15kV) LTC DATA LTC ON LV WINDING, ± 15 % RANGE, IN 32 STEPS OF 15/16 % % IMPEDANCE ON P.U. IMPEDANCE ON IMPEDANCE DATA TRANS. BASE 100 MVA BASE HV-LV 0.327 + j9.945 = 10.47 0.0218 + j0.6630 = 0.6980

November 2012 System Data Book - 2012 Ver 9a Page 56

TRANSFORMER DATA TRANSFORMER NO.: T2 LOCATION: Northern Hills Substation MANUFACTURER: Delta Star YEAR OF MANUFACTURER: 2003 SERIAL NO.: F69610903 TYPE: Two winding PHASE/CYCLE: 3 Phase/60 Cycle MVA RATING: @55ºC 15.0-OA / 20.0-FA / 25.0-FOA MVA RATING: @65ºC 16.8-OA / 22.4-FA / 28.0-FOA NO LOAD WINDING BUSHING VOLTAGE TAPS AT BIL/(KV CLASS) BIL/(KV CLASS) HIGH VOLTAGE WINDING Delta CONNECTED 161000 None 650kV/(161kV) 650kV/(161kV) LOW VOLTAGE WINDING Grd.Wye CONNECTED 13800Y/7970 110kV/(15kV) 110kV/(15kV) LTC DATA LTC ON LV WINDING, ± 15 % RANGE, IN 32 STEPS OF 15/16 % % IMPEDANCE ON P.U. IMPEDANCE ON IMPEDANCE DATA TRANS. BASE 100 MVA BASE HV-LV 0.272 + j10.096 = 10.1 0.0181 + j0.6731 = 0.6733

November 2012 System Data Book - 2012 Ver 9a Page 57

TRANSFORMER DATA TRANSFORMER NO.: Gen. #4 GSU4 LOCATION: Silver Lake Plant MANUFACTURER: Pauwels YEAR OF MANUFACTURER: 1993 SERIAL NO.: 90.4.7204 TYPE: Two winding PHASE/CYCLE: 3 Phase/60 Cycle MVA RATING: @55ºC 37.5-OA / 50.0-FA / 62.5-FA MVA RATING: @65ºC 41.0-OA / 56.0-FA / 70.0-FA NO LOAD WINDING BUSHING VOLTAGE TAPS AT BIL/(KV CLASS) BIL/(KV CLASS) HIGH VOLTAGE 169050 WINDING 165025 Grd.Wye CONNECTED 161000Y 161000 650kV/(161kV) 650kV/(138kV) 156975 152950 LOW VOLTAGE WINDING Delta CONNECTED 13800 110kV/(15kV) 150kV/(25kV) LTC DATA LTC ON None WINDING, % RANGE, IN STEPS OF % % IMPEDANCE ON P.U. IMPEDANCE ON IMPEDANCE DATA TRANS. BASE 100 MVA BASE HV-LV 9.40 0.2507 GSU tie line 0.0001+j0.0003 Total P.U. IMPEDANCE ON 64 MVA BASE* 0.0001+j0.16064 * This impedance includes the generator #4 tie line for computer modeling purposes.

November 2012 System Data Book - 2012 Ver 9a Page 58

TRANSFORMER DATA TRANSFORMER NO.: T3 LOCATION: Silver Lake Substation MANUFACTURER: Pauwels YEAR OF MANUFACTURER: 1992 SERIAL NO.: 90.4.6452 TYPE: Two winding PHASE/CYCLE: 3 Phase/60 Cycle MVA RATING: @55ºC 20.0-OA / 26.660-FA / 33.330-FA MVA RATING: @65ºC 22.5-OA / 29.900-FA / 37.330-FA NO LOAD WINDING BUSHING VOLTAGE TAPS AT BIL/(KV CLASS) BIL/(KV CLASS) HIGH VOLTAGE WINDING Delta CONNECTED 161000 None 650kV/(161kV) 650kV/(161kV) LOW VOLTAGE WINDING Grd.Wye CONNECTED 13800/7970 110kV/(15kV) 110kV/(15kV) LTC DATA LTC ON LV WINDING, ± 15 % RANGE, IN 32 STEPS OF 15/16 % % IMPEDANCE ON P.U. IMPEDANCE ON IMPEDANCE DATA TRANS. BASE 100 MVA BASE HV-LV ** 0.219 + j9.877 = 9.88 0.011 + j0.4939 = 0.4940 ** R and X values estimated based on X/R ratio of 45.

November 2012 System Data Book - 2012 Ver 9a Page 59

TRANSFORMER DATA TRANSFORMER NO.: T4 LOCATION: Silver Lake Substation MANUFACTURER: Pauwels YEAR OF MANUFACTURER: 1991 SERIAL NO.: 90.4.7203 TYPE: Two winding PHASE/CYCLE: 3 Phase/60 Cycle MVA RATING: @55ºC 20.0-OA / 26.660-FA / 33.330-FA MVA RATING: @65ºC 22.5-OA / 29.900-FA / 37.330-FA NO LOAD WINDING BUSHING VOLTAGE TAPS AT BIL/(KV CLASS) BIL/(KV CLASS) HIGH VOLTAGE WINDING Delta CONNECTED 161000 None 650kV/(161kV) 650kV/(161kV) LOW VOLTAGE WINDING Grd.Wye CONNECTED 13800/7970 110kV/(15kV) 110kV/(15kV) LTC DATA LTC ON LV WINDING, ± 15 % RANGE, IN 32 STEPS OF 15/16 % % IMPEDANCE ON P.U. IMPEDANCE ON IMPEDANCE DATA TRANS. BASE 100 MVA BASE HV-LV ** 0.219 + j9.847 = 9.85 0.0109 + j0.4924 = 0.4925 ** R and X values estimated based on X/R ratio of 45.

November 2012 System Data Book - 2012 Ver 9a Page 60

TRANSFORMER DATA TRANSFORMER NO.: T1 LOCATION: Westside Substation MANUFACTURER: Delta-Star YEAR OF MANUFACTURER: 2010 SERIAL NO.: TYPE: Two winding PHASE/CYCLE: 3 Phase/60 Cycle MVA RATING: @55ºC 20.0-OA / 26.7-FA / 33.3-FOA MVA RATING: @65ºC 22.5-OA / 29.9-FA / 37.5-FOA NO LOAD WINDING BUSHING VOLTAGE TAPS AT BIL/(KV CLASS) BIL/(KV CLASS) HIGH VOLTAGE WINDING Delta CONNECTED 161000 None 650kV/(138kV) 650kV/(138kV) LOW VOLTAGE WINDING Grd.Wye CONNECTED 13800Y/7970 110kV/(15kV) 110kV/(15kV) LTC DATA LTC ON LV WINDING, ± 15 % RANGE, IN 32 STEPS OF 15/16 % % IMPEDANCE ON P.U. IMPEDANCE ON IMPEDANCE DATA TRANS. BASE 100 MVA BASE HV-LV 0.340 + j9.914 = 9.92 0.0170 + j0.4957 = 0.4960

November 2012 System Data Book - 2012 Ver 9a Page 61

TRANSFORMER DATA TRANSFORMER NO.: T1 LOCATION: Willow Creek Substation MANUFACTURER: Pauwels YEAR OF MANUFACTURER: 1994 SERIAL NO.: 94.4.3337 TYPE: Two winding PHASE/CYCLE: 3 Phase/60 Cycle MVA RATING: @55ºC 15.0-OA / 20.0-FA / 25.0-FA MVA RATING: @65ºC 16.8-OA / 22.4-FA / 28.0-FOA NO LOAD WINDING BUSHING VOLTAGE TAPS AT BIL/(KV CLASS) BIL/(KV CLASS) HIGH VOLTAGE WINDING Delta CONNECTED 161000 None 650kV/(161kV) 650kV/(161kV) LOW VOLTAGE WINDING Grd.Wye CONNECTED 13800Y/7970 110kV/(15kV) 110kV/(15kV) LTC DATA LTC ON LV WINDING, ± 15 % RANGE, IN 32 STEPS OF 15/16 % % IMPEDANCE ON P.U. IMPEDANCE ON IMPEDANCE DATA TRANS. BASE 100 MVA BASE HV-LV 0.171 + j9.538 = 9.54 0.0114 + j0.6359 = 0.6361

November 2012 System Data Book - 2012 Ver 9a Page 62

TRANSFORMER DATA TRANSFORMER NO.: T2 LOCATION: Willow Creek Substation MANUFACTURER: Delta-Star YEAR OF MANUFACTURER: 2000 SERIAL NO.: F66700101 TYPE: Two winding PHASE/CYCLE: 3 Phase/60 Cycle MVA RATING: @55ºC 15.0-OA / 20.0-FA / 25.0-FA MVA RATING: @65ºC 16.8-OA / 22.4-FA / 28.0-FOA NO LOAD WINDING BUSHING VOLTAGE TAPS AT BIL/(KV CLASS) BIL/(KV CLASS) HIGH VOLTAGE WINDING Delta CONNECTED 161000 None 650kV/(161kV) 650kV/(161kV) LOW VOLTAGE WINDING Grd.Wye CONNECTED 13800Y/7970 110kV/(15kV) 110kV/(15kV) LTC DATA LTC ON LV WINDING, ± 15 % RANGE, IN 32 STEPS OF 15/16 % % IMPEDANCE ON P.U. IMPEDANCE ON IMPEDANCE DATA TRANS. BASE 100 MVA BASE HV-LV 0.285 + j9.296 = 9.30 0.0190 + j0.6197 = 0.6200

November 2012 System Data Book - 2012 Ver 9a Page 63

TRANSFORMER DATA TRANSFORMER NO.: T1 LOCATION: Zumbro River Substation MANUFACTURER: RTE YEAR OF MANUFACTURER: 1982 SERIAL NO.: A6584 TYPE: Two winding PHASE/CYCLE: 3 Phase/60 Cycle MVA RATING: @55ºC 15.0-OA / 20.0-FA / 25.0-FA MVA RATING: @65ºC 16.9-OS / 22.5-FA / 28.0-FA NO LOAD WINDING BUSHING VOLTAGE TAPS AT BIL/(KV CLASS) BIL/(KV CLASS) HIGH VOLTAGE WINDING Delta CONNECTED 161000 x 115000 161000 650kV/(161kV) 650kV/(138kV) 115000 450kV/(115kV) LOW VOLTAGE WINDING Grd.Wye CONNECTED 13800Y/7970 110kV/(15kV) 110kV/(15kV) LTC DATA LTC ON LV WINDING, ± 15 % RANGE, IN 32 STEPS OF 15/16 % % IMPEDANCE ON P.U. IMPEDANCE ON IMPEDANCE DATA TRANS. BASE 100 MVA BASE 161000-13800 0.321 + j9.655 = 9.66 0.0214 + j0.6437 = 0.6440

November 2012 System Data Book - 2012 Ver 9a Page 64

TRANSFORMER DATA TRANSFORMER NO.: T2 LOCATION: Zumbro River Substation MANUFACTURER: RTE YEAR OF MANUFACTURER: 1982 SERIAL NO.: A6585 TYPE: Two winding PHASE/CYCLE: 3 Phase/60 Cycle MVA RATING: @55ºC 15.0-OA / 20.0-FA / 25.0-FA MVA RATING: @65ºC 16.9-OS / 22.5-FA / 28.0-FA NO LOAD WINDING BUSHING VOLTAGE TAPS AT BIL/(KV CLASS) BIL/(KV CLASS) HIGH VOLTAGE WINDING Delta CONNECTED 161000 x 115000 161000 650kV/(161kV) 650kV/(138kV) 115000 450kV/(115kV) LOW VOLTAGE WINDING Grd.Wye CONNECTED 13800Y/7970 110kV/(15kV) 110kV/(15kV) LTC DATA LTC ON LV WINDING, ± 15 % RANGE, IN 32 STEPS OF 15/16 % % IMPEDANCE ON P.U. IMPEDANCE ON IMPEDANCE DATA TRANS. BASE 100 MVA BASE 161000-13800 0.319 + j9.745 = 9.75 0.0213 + j0.6496 = 0.6500

November 2012 System Data Book - 2012 Ver 9a Page 65

AUXILIARY TRANSFORMER DATA

LEGEND

1. The underlined no load tap setting is a) the setting observed in service in 1979 when the original data was

gathered or b) the setting selected upon commissioning for equipment installed after 1979. 2. The % impedance on transformer base is the actual impedance stamped on the transformer nameplate.

This value is a test result using the transformer OA rating @ 55ºC winding temperature as an MVA base. On transformers where the MVA rating is given only on the basis of a 65ºC winding temperature, the % impedance is given for the OA rating at that winding temperature.

3. The PU impedance on 100 MVA base is the actual impedance stamped on the transformer nameplate

adjusted to a uniform system base of 100 MVA and expressed in per unit.

4. Transformer ratings are based on RPU’s Facilities Ratings Methodology for Transmission, Substation, and Generation Equipment, in compliance with NERC FAC-008-3.

November 2012 System Data Book - 2012 Ver 9a Page 66

AUXILIARY TRANSFORMER DATA TRANSFORMER NO.: MA1 LOCATION: Cascade Creek MANUFACTURER: YEAR OF MANUFACTURER: SERIAL NO.: TYPE: Two winding PHASE/CYCLE: 3 Phase/60 Cycle MVA RATING: @80ºC 2.0 -OA / / NO LOAD WINDING BUSHING VOLTAGE TAPS AT BIL/(KV CLASS) BIL/(KV CLASS) HIGH VOLTAGE 14490 WINDING 14145 Delta CONNECTED 13800 13800 (15kV) (15kV) 13455 13110 LOW VOLTAGE WINDING Wye CONNECTED 2400 % IMPEDANCE ON P.U. IMPEDANCE ON IMPEDANCE DATA TRANS. BASE 100 MVA BASE HV-LV (13800 Volt Conn)

November 2012 System Data Book - 2012 Ver 9a Page 67

AUXILIARY TRANSFORMER DATA TRANSFORMER NO.: MA2 LOCATION: Cascade Creek MANUFACTURER: YEAR OF MANUFACTURER: SERIAL NO.: TYPE: Two winding PHASE/CYCLE: 3 Phase/60 Cycle MVA RATING: @80ºC 2.0 -OA / / NO LOAD WINDING BUSHING VOLTAGE TAPS AT BIL/(KV CLASS) BIL/(KV CLASS) HIGH VOLTAGE 14490 WINDING 14145 Delta CONNECTED 13800 13800 (15kV) (15kV) 13455 13110 LOW VOLTAGE WINDING Wye CONNECTED 2400 % IMPEDANCE ON P.U. IMPEDANCE ON IMPEDANCE DATA TRANS. BASE 100 MVA BASE HV-LV (13800 Volt Conn)

November 2012 System Data Book - 2012 Ver 9a Page 68

AUXILIARY TRANSFORMER DATA TRANSFORMER NO.: MA3 LOCATION: Silver Lake Plant MANUFACTURER: Allis Chalmers YEAR OF MANUFACTURER: SERIAL NO.: 3362633 TYPE: Two winding PHASE/CYCLE: 3 Phase/60 Cycle MVA RATING: @80ºC 2.0 -OA / 2.67 -FA / NO LOAD WINDING BUSHING VOLTAGE TAPS AT BIL/(KV CLASS) BIL/(KV CLASS) HIGH VOLTAGE 14490 WINDING 14145 Delta CONNECTED 13800 13800 (15kV) (15kV) 13455 13110 LOW VOLTAGE WINDING Delta CONNECTED 2400 % IMPEDANCE ON P.U. IMPEDANCE ON IMPEDANCE DATA TRANS. BASE 100 MVA BASE HV-LV (13800 Volt Conn) 5.6 2.80

November 2012 System Data Book - 2012 Ver 9a Page 69

AUXILIARY TRANSFORMER DATA TRANSFORMER NO.: MA4 LOCATION: Silver Lake Plant MANUFACTURER: General Electric YEAR OF MANUFACTURER: SERIAL NO.: F964398 TYPE: Two winding PHASE/CYCLE: 3 Phase/60 Cycle MVA RATING: @55ºC 7.5-OA / 8.4-FA / MVA RATING: @65ºC / 10.5-FA / NO LOAD WINDING BUSHING VOLTAGE TAPS AT BIL/(KV CLASS) BIL/(KV CLASS) HIGH VOLTAGE 14400 WINDING 14100 Delta CONNECTED 13800 13800 (15kV) (15kV) 13500 13200 LOW VOLTAGE WINDING Delta CONNECTED 2400 % IMPEDANCE ON P.U. IMPEDANCE ON IMPEDANCE DATA TRANS. BASE 100 MVA BASE HV-LV (13800 Volt Conn) 5.6 0.7467

November 2012 System Data Book - 2012 Ver 9a Page 70

AUXILIARY TRANSFORMER DATA TRANSFORMER NO.: RA1 LOCATION: Silver Lake Plant MANUFACTURER: Westinghouse YEAR OF MANUFACTURER: SERIAL NO.: 4085183 TYPE: Two winding PHASE/CYCLE: 3 Phase/60 Cycle MVA RATING: @55ºC 0.75 -OA / / MVA RATING: @65ºC / / NO LOAD WINDING BUSHING VOLTAGE TAPS AT BIL/(KV CLASS) BIL/(KV CLASS) HIGH VOLTAGE WINDING Grd. Wye CONNECTED 13800/7970 None (15kV) (15kV) LOW VOLTAGE WINDING Delta CONNECTED 480 % IMPEDANCE ON P.U. IMPEDANCE ON IMPEDANCE DATA TRANS. BASE 100 MVA BASE HV-LV (13800 Volt Conn) 8.1 10.80

November 2012 System Data Book - 2012 Ver 9a Page 71

AUXILIARY TRANSFORMER DATA TRANSFORMER NO.: RA3 LOCATION: Silver Lake Plant MANUFACTURER: Allis Chalmers YEAR OF MANUFACTURER: SERIAL NO.: 3362632 TYPE: Two winding PHASE/CYCLE: 3 Phase/60 Cycle MVA RATING: @80ºC 2.0 -OA / 2.67 -FA / NO LOAD WINDING BUSHING VOLTAGE TAPS AT BIL/(KV CLASS) BIL/(KV CLASS) HIGH VOLTAGE 14490 WINDING 14145 Delta CONNECTED 13800 13800 (15kV) (15kV) 13455 13110 LOW VOLTAGE WINDING Delta CONNECTED 2400 % IMPEDANCE ON P.U. IMPEDANCE ON IMPEDANCE DATA TRANS. BASE 100 MVA BASE HV-LV (13800 Volt Conn) 5.6 2.80

November 2012 System Data Book - 2012 Ver 9a Page 72

AUXILIARY TRANSFORMER DATA TRANSFORMER NO.: RA4 LOCATION: Silver Lake Plant MANUFACTURER: General Electric YEAR OF MANUFACTURER: SERIAL NO.: F964397 TYPE: Two winding PHASE/CYCLE: 3 Phase/60 Cycle MVA RATING: @55ºC 7.5-OA / 8.4-FA / MVA RATING: @65ºC / 10.5-FA / NO LOAD WINDING BUSHING VOLTAGE TAPS AT BIL/(KV CLASS) BIL/(KV CLASS) HIGH VOLTAGE 14400 WINDING 14100 Delta CONNECTED 13800 13800 (15kV) (15kV) 13500 13200 LOW VOLTAGE WINDING Delta CONNECTED 2400 % IMPEDANCE ON P.U. IMPEDANCE ON IMPEDANCE DATA TRANS. BASE 100 MVA BASE HV-LV (13800 Volt Conn) 5.6 0.7467

November 2012 System Data Book - 2012 Ver 9a Page 73

AUXILIARY TRANSFORMER DATA TRANSFORMER NO.: SA1 LOCATION: Silver Lake Plant MANUFACTURER: Westinghouse YEAR OF MANUFACTURER: SERIAL NO.: 4085185 TYPE: Two winding PHASE/CYCLE: 3 Phase/60 Cycle MVA RATING: @55ºC 0.75 -OA / / MVA RATING: @65ºC / / NO LOAD WINDING BUSHING VOLTAGE TAPS AT BIL/(KV CLASS) BIL/(KV CLASS) HIGH VOLTAGE WINDING Grd. Wye CONNECTED 13800/7970 None (15kV) (15kV) LOW VOLTAGE WINDING Delta CONNECTED 480 % IMPEDANCE ON P.U. IMPEDANCE ON IMPEDANCE DATA TRANS. BASE 100 MVA BASE HV-LV (13800 Volt Conn) 8.1 10.80

November 2012 System Data Book - 2012 Ver 9a Page 74

AUXILIARY TRANSFORMER DATA TRANSFORMER NO.: SA2 LOCATION: Silver Lake Plant MANUFACTURER: Westinghouse YEAR OF MANUFACTURER: SERIAL NO.: 4085184 TYPE: Two winding PHASE/CYCLE: 3 Phase/60 Cycle MVA RATING: @55ºC 0.75 -OA / / MVA RATING: @65ºC / / NO LOAD WINDING BUSHING VOLTAGE TAPS AT BIL/(KV CLASS) BIL/(KV CLASS) HIGH VOLTAGE WINDING Grd. Wye CONNECTED 13800/7970 None (15kV) (15kV) LOW VOLTAGE WINDING Delta CONNECTED 480 % IMPEDANCE ON P.U. IMPEDANCE ON IMPEDANCE DATA TRANS. BASE 100 MVA BASE HV-LV (13800 Volt Conn) 8.1 10.80

November 2012 System Data Book - 2012 Ver 9a Page 75

GENERATOR REACTOR, RESISTOR, & BUS DUCT DATA

LEGEND

1. The rating information for this section is the actual rating stamped on the equipment nameplate or as

provided on manufacturer’s drawings and documentation. 2. The PU impedance on 100 MVA base is the actual impedance for the equipment adjusted to a uniform

system base of 100 MVA and expressed in per unit.

3. Equipment ratings are based on RPU’s Facilities Ratings Methodology for Transmission, Substation, and Generation Equipment, in compliance with NERC FAC-008-3.

November 2012 System Data Book - 2012 Ver 9a Page 76

REACTOR DATA REACTOR NO.: Gen. No. 1 LOCATION: Silver Lake Plant MANUFACTURER: Westinghouse YEAR OF MANUFACTURE: CAT. NO./ SERIAL NO.: / 6542309 TYPE: Indoor Neutral Reactor, Air Core PHASE / CYCLE: Single Phase / 60 Cycle KVA RATING: 5445 kVA CONTINUOUS CURRENT RATING: SHORT CIRCUIT CURRENT RATING: 5500A (60 Seconds) SYSTEM NOMINAL VOLTAGE: 13.8 kV BIL / (KV CLASS): 95 kV / 8.7 kV OPERATING VOLTAGE DROP: 1010 V IMPEDANCE (ACTUAL OHMS): 0.1836 ohms IMPEDANCE (P.U. ON 100 MVA BASE): 0.0964

November 2012 System Data Book - 2012 Ver 9a Page 77

REACTOR DATA REACTOR NO.: Gen. No. 2 LOCATION: Silver Lake Plant MANUFACTURER: Westinghouse YEAR OF MANUFACTURE: CAT. NO./ SERIAL NO.: / 6542634 TYPE: Indoor Neutral Reactor, Air Core PHASE / CYCLE: Single Phase / 60 Cycle KVA RATING: 11550 kVA CONTINUOUS CURRENT RATING: SHORT CIRCUIT CURRENT RATING: 5500A (60 Seconds) SYSTEM NOMINAL VOLTAGE: 13.8 kV BIL / (KV CLASS): 95 kV / 8.7 kV OPERATING VOLTAGE DROP: 2180 V IMPEDANCE (ACTUAL OHMS): 0.3880 ohms IMPEDANCE (P.U. ON 100 MVA BASE): 0.2037

November 2012 System Data Book - 2012 Ver 9a Page 78

REACTOR DATA REACTOR NO.: Gen. No. 3 LOCATION: Silver Lake Plant MANUFACTURER: Westinghouse YEAR OF MANUFACTURE: CAT. NO./ SERIAL NO.: / TYPE: Indoor Neutral Reactor, Air Core PHASE / CYCLE: Single Phase / 60 Cycle KVA RATING: CONTINUOUS CURRENT RATING: SHORT CIRCUIT CURRENT RATING: 7993A (60 Seconds) SYSTEM NOMINAL VOLTAGE: 13.8 kV BIL / (KV CLASS): 95 kV / 8.7 kV OPERATING VOLTAGE DROP: IMPEDANCE (ACTUAL OHMS): 0.2326 ohms IMPEDANCE (P.U. ON 100 MVA BASE): 0.1221

November 2012 System Data Book - 2012 Ver 9a Page 79

RESISTOR DATA RESISTOR NO.: Gen. No. 4 LOCATION: Silver Lake Plant MANUFACTURER: General Electric YEAR OF MANUFACTURE: 1969 CAT. NO./ SERIAL NO.: 218A8567 / TYPE: Neutral Grounding Transf. / Secondary Resistor PHASE / CYCLE: Single Phase / 60 Cycle TRANSF. KVA RATING: 25 kVA PRIMARY VOLTAGE: 14.4 kV w/ taps at 14.4, 13.8, 13.2, 12.87, 12.54 kV SECONDARY VOLTAGE: 120 / 240 V (resistor connected at 240 V ) BIL / (KV CLASS): 110 kV / 15 kV TRANSF. IMPEDANCE: 2.05% RESISTOR CONTINUOUS CURRENT: 210 Amps OPERATING VOLTAGE DROP: 147 V INSULATION CLASS: 600 V THERMAL RATING: 450 deg. C rise / 10 minutes RESISTOR IMPEDANCE (ACTUAL OHMS): 0.70 TOTAL IMPEDANCE (P.U. ON 100 MVA BASE): 1323.251 + J89.285

November 2012 System Data Book - 2012 Ver 9a Page 80

ISO-PHASE BUS DATA VOLTAGE: 13.8 KV TERMINALS: Silver Lake Plant Gen. #4 TO: Transformer GSU #4 MANUFACTURER: General Electric YEAR OF MANUFACTURE: 1967 PHASE CONDUCTOR 6 ½ “ OD x 0.2” T Alum. tube, 1 per phase SHIELD ENCLOSURE air-insulated metal tube CONFIGURATION 3 phase, Horizontal parallel PRIMARY VOLTAGE 14.4 kV LOADING CAPACITY (MVA) 74.8 LOADING CAPACITY (AMPS PER PHASE CONDUCTOR) 3000 BUS LENGTH 64 ft. DIAM. OF PHASE ENCLOSURE 23 ⅜ inch PHASE SPACING A – B 28 inch PHASE SPACING B – C 28 inch PHASE SPACING A – C 56 inch IMPEDANCE DATA TOTAL POSITIVE SEQUENCE (OHMS) 0.00044+j0.00188 ZERO SEQUENCE (OHMS) 0.00044+j0.00188 POSITIVE SEQUENCE (P.U.) 0.00021+j0.00090 ZERO SEQUENCE (P.U.) 0.00021+j0.00090

November 2012 System Data Book - 2012 Ver 9a Page 81

REACTOR DATA REACTOR NO.: Gen. No. 1 Phase LOCATION: Cascade Creek Substation MANUFACTURER: Areva T & D YEAR OF MANUFACTURE: 2008 CAT. NO./ SERIAL NO.: 3xLCC-3316/2000 / 08.9125-01 TYPE: 3 Single Phase Inrush Current Limiting PHASE / CYCLE: Single Phase / 60 Cycle KVA RATING: 47,800 kVA CONTINUOUS CURRENT RATING: 2000A SHORT CIRCUIT CURRENT RATING: 5.1 kA Thermal 2 sec. / 13 kA Mechanical peak SYSTEM NOMINAL VOLTAGE: 13.8 kV BIL / (KV CLASS): 110 kV / 15 kV OPERATING VOLTAGE DROP: 2750 V TOTAL OPERATING LOSSES: 40.3 kW per phase at 75 deg. C IMPEDANCE (ACTUAL OHMS): R = 0.01 ohms, X = 1.25 ohms, 3.316 mH IMPEDANCE (P.U. ON 100 MVA BASE): 0.0053+j0.6564

November 2012 System Data Book - 2012 Ver 9a Page 82

NON-SEGREGATED PHASE BUS DATA VOLTAGE: 13.8 KV TERMINALS: Cascade Creek Gen. 1 TO: Phase reactor Phase reactor TO: 13.8 kV Bus 1 MANUFACTURER: Westinghouse / Eaton * YEAR OF MANUFACTURE: 1975 / 2008 PHASE CONDUCTOR 6“ x 0.375” T copper bar, 1 per phase SHIELD ENCLOSURE air-insulated aluminum CONFIGURATION 3 phase, Horizontal parallel bar PRIMARY VOLTAGE 15 kV LOADING CAPACITY (MVA) 47.8 LOADING CAPACITY (AMPS PER PHASE CONDUCTOR) 2000 BUS LENGTH 152 ft. + 98 ft = 250 ft. DIM. OF PHASE ENCLOSURE 20” W x 17.38” H PHASE SPACING A – B 5.38 inch PHASE SPACING B – C 5.38 inch PHASE SPACING A – C 10.76 inch IMPEDANCE DATA TOTAL POSITIVE SEQUENCE (OHMS) 0.00118+j0.00925 ZERO SEQUENCE (OHMS) 0.00118+j0.00925 POSITIVE SEQUENCE (P.U.) 0.00062+j0.00486 ZERO SEQUENCE (P.U.) 0.00062+j0.00486 * Approximately 47 ft. original bus duct. Approximately 203 ft. added when phase reactors were installed.

November 2012 System Data Book - 2012 Ver 9a Page 83

REACTOR DATA REACTOR NO.: Gen. No. 1 Neutral LOCATION: Cascade Creek Substation MANUFACTURER: Westinghouse YEAR OF MANUFACTURE: CAT. NO./ SERIAL NO.: / TYPE: Indoor Neutral Reactor PHASE / CYCLE: Single Phase / 60 Cycle KVA RATING: 17,600 – 60 sec. CONTINUOUS CURRENT RATING: SHORT CIRCUIT CURRENT RATING: 10,200 SYSTEM NOMINAL VOLTAGE: 13.8 kV BIL / (KV CLASS): 95 kV / 15 kV OPERATING VOLTAGE DROP: 1725 V IMPEDANCE (ACTUAL OHMS): 0.1690 ohms IMPEDANCE (P.U. ON 100 MVA BASE): 0.0887

November 2012 System Data Book - 2012 Ver 9a Page 84

RESISTOR DATA RESISTOR NO.: Gen. No. 2 LOCATION: Cascade Creek Substation MANUFACTURER: Pratt & Whitney / Brush YEAR OF MANUFACTURE: 2001 CAT. NO./ SERIAL NO.: / TYPE: Neutral Grounding Transf. / Secondary Resistor PHASE / CYCLE: Single Phase / 60 Cycle TRANSF. KVA RATING: 96.6 kVA (30 seconds) PRIMARY VOLTAGE: 13.8 kV SECONDARY VOLTAGE: 120 / 240 V (resistor connected at 240 V ) BIL / (KV CLASS): 110 kV / 15 kV EQUIVALENT TRANSFORMER RESISTANCE (REFERRED TO SECONDARY): 0.104 OHMS @ 75°C. EQUIVALENT TRANSFORMER REACTANCE (REFERRED TO SECONDARY): 0.173 OHMS RESISTOR CONTINUOUS CURRENT: 400 Amps OPERATING VOLTAGE DROP: 100 V INSULATION CLASS: 600 V THERMAL RATING: / 0.5 minutes RESISTOR IMPEDANCE (ACTUAL OHMS): 0.25 TOTAL IMPEDANCE (P.U. ON 100 MVA BASE): 614.584 + J300.347

November 2012 System Data Book - 2012 Ver 9a Page 85

TRANSFORMER REACTOR DATA

LEGEND

1. The rating information for this section is the actual rating stamped on the equipment nameplate or as

provided on manufacturer’s drawings and documentation. 2. The PU impedance on 100 MVA base is the actual impedance for the equipment adjusted to a uniform

system base of 100 MVA and expressed in per unit.

3. Equipment ratings are based on RPU’s Facilities Ratings Methodology for Transmission, Substation, and Generation Equipment, in compliance with NERC FAC-008-3.

November 2012 System Data Book - 2012 Ver 9a Page 86

REACTOR DATA REACTOR NO.: CC T1 Neutral LOCATION: Cascade Creek Sub. MANUFACTURER: Trench Ltd. YEAR OF MANUFACTURE: 2009 CAT. NO./ SERIAL NO.: / C090189-2 TYPE: Outdoor Neutral Reactor PHASE / CYCLE: Single Phase / 60 Cycle KVA RATING: 80 kVA CONTINUOUS CURRENT RATING: 400A SHORT CIRCUIT CURRENT RATING: 20 kA Thermal 2 sec. / 51 kA Mechanical peak SYSTEM NOMINAL VOLTAGE: 13.8 kV BIL / (KV CLASS): 110 kV / 15 kV OPERATING VOLTAGE DROP: IMPEDANCE (ACTUAL OHMS): 0.525 ohms, 1.33 mH IMPEDANCE (P.U. ON 100 MVA BASE): 0.2757

November 2012 System Data Book - 2012 Ver 9a Page 87

REACTOR DATA REACTOR NO.: CC T2 Neutral LOCATION: Cascade Creek Substation MANUFACTURER: Trench Ltd. YEAR OF MANUFACTURE: 2009 CAT. NO./ SERIAL NO.: / C090189-1 TYPE: Outdoor Neutral Reactor PHASE / CYCLE: Single Phase / 60 Cycle KVA RATING: 80 KVA CONTINUOUS CURRENT RATING: 400A SHORT CIRCUIT CURRENT RATING: 20 kA Thermal 2 sec. / 51 kA Mechanical peak SYSTEM NOMINAL VOLTAGE: 13.8 kV BIL / (KV CLASS): 110 kV / 15 kV OPERATING VOLTAGE DROP: IMPEDANCE (ACTUAL OHMS): 0.527 ohms, 1.33 mH IMPEDANCE (P.U. ON 100 MVA BASE): 0.2767

November 2012 System Data Book - 2012 Ver 9a Page 88

REACTOR DATA REACTOR NO.: IBM T1 Neutral LOCATION: IBM Substation MANUFACTURER: General Electric YEAR OF MANUFACTURE: 1981 CAT. NO./ SERIAL NO.: AA-JCL-60 / M103956 TYPE: Outdoor Neutral Reactor PHASE / CYCLE: Single Phase / 60 Cycle KVA RATING: 3075 kVA CONTINUOUS CURRENT RATING: 386A SHORT CIRCUIT CURRENT RATING: 10,000A -10 Sec. SYSTEM NOMINAL VOLTAGE: 13.8 kV BIL / (KV CLASS): 110 kV / 15 kV OPERATING VOLTAGE DROP: 63 IMPEDANCE (ACTUAL OHMS): 0.1632 ohms IMPEDANCE (P.U. ON 100 MVA BASE): 0.0856

November 2012 System Data Book - 2012 Ver 9a Page 89

REACTOR DATA REACTOR NO.: IBM T2 Neutral LOCATION: IBM Substation MANUFACTURER: General Electric YEAR OF MANUFACTURE: 1981 CAT. NO./ SERIAL NO.: AA-JCL-60 / M103957 TYPE: Outdoor Neutral Reactor PHASE / CYCLE: Single Phase / 60 Cycle KVA RATING: 3075 kVA CONTINUOUS CURRENT RATING: 386A SHORT CIRCUIT CURRENT RATING: 10,000A - 10 Sec. SYSTEM NOMINAL VOLTAGE: 13.8 kV BIL / (KV CLASS): 110 kV / 15 kV OPERATING VOLTAGE DROP: 64 IMPEDANCE (ACTUAL OHMS): 0.1658 ohms IMPEDANCE (P.U. ON 100 MVA BASE): 0.08706

November 2012 System Data Book - 2012 Ver 9a Page 90

REACTOR DATA REACTOR NO.: Transformer MA4 Phase LOCATION: Silver Lake Plant MANUFACTURER: Areva T & D YEAR OF MANUFACTURE: 2007 CAT. NO./ SERIAL NO.: 3xLCC-35/2000 / TYPE: 3 Single Phase Current Limiting PHASE / CYCLE: Single Phase / 60 Cycle KVA RATING: 8314 kVA CONTINUOUS CURRENT RATING: 2000A SHORT CIRCUIT CURRENT RATING: 32 kA Thermal 2 sec. / 81.6 kA Mechanical peak SYSTEM NOMINAL VOLTAGE: 2.4 kV BIL / (KV CLASS): 60 kV / 2.4 kV OPERATING VOLTAGE DROP: IMPEDANCE (ACTUAL OHMS): 0.0132 ohms, 0.035 mH IMPEDANCE (P.U. ON 100 MVA BASE): 0.0576

November 2012 System Data Book - 2012 Ver 9a Page 91

REACTOR DATA REACTOR NO.: Transformer RA4 Phase LOCATION: Silver Lake Plant MANUFACTURER: Areva T & D YEAR OF MANUFACTURE: 2007 CAT. NO./ SERIAL NO.: 3xLCC-35/2000 / TYPE: 3 Single Phase Current Limiting PHASE / CYCLE: Single Phase / 60 Cycle KVA RATING: 8314 kVA CONTINUOUS CURRENT RATING: 2000A SHORT CIRCUIT CURRENT RATING: 32 kA Thermal 2 sec. / 81.6 kA Mechanical peak SYSTEM NOMINAL VOLTAGE: 2.4 kV BIL / (KV CLASS): 60 kV / 2.4 kV OPERATING VOLTAGE DROP: IMPEDANCE (ACTUAL OHMS): 0.0132 ohms, 0.035 mH IMPEDANCE (P.U. ON 100 MVA BASE): 0.0576

November 2012 System Data Book - 2012 Ver 9a Page 92

REACTOR DATA REACTOR NO.: Westside T1 Neutral LOCATION: Westside Substation MANUFACTURER: Trench Ltd. YEAR OF MANUFACTURE: 2010 CAT. NO./ SERIAL NO.: / C091013-1 TYPE: Outdoor Neutral Reactor PHASE / CYCLE: Single Phase / 60 Cycle KVA RATING: 80 KVA CONTINUOUS CURRENT RATING: 400A SHORT CIRCUIT CURRENT RATING: 20 kA Thermal 2 sec. / 51 kA Mechanical peak SYSTEM NOMINAL VOLTAGE: 13.8 kV BIL / (KV CLASS): 110 kV / 15 kV OPERATING VOLTAGE DROP: IMPEDANCE (ACTUAL OHMS): 0.53 ohms, 1.33 mH IMPEDANCE (P.U. ON 100 MVA BASE): 0.2783

November 2012 System Data Book - 2012 Ver 9a Page 93

STATION CAPACITOR BANK DATA

LEGEND

1. The rating information for this section is the actual rating stamped on the equipment nameplate or as

provided on manufacturer’s drawings and documentation. 2. The PU impedance on 100 MVA base is the actual impedance for the equipment adjusted to a uniform

system base of 100 MVA and expressed in per unit.

3. Equipment ratings are based on RPU’s Facilities Ratings Methodology for Transmission, Substation, and Generation Equipment, in compliance with NERC FAC-008-3.

November 2012 System Data Book - 2012 Ver 9a Page 94

CAPACITOR DATA CAPACITOR NO.: 209 / 219 LOCATION: Silver Lake Plant MANUFACTURER: McGraw Edison YEAR OF MANUFACTURE: 1981 CAT. NO./ SERIAL NO.: / TYPE: Edisol Fluid-Insulated PHASE / CYCLE: Three Phase / 60 Cycle KVAR RATING STAGE 1: 4800 kVAR KVAR RATING STAGE 2: 4800 kVAR SYSTEM NOMINAL VOLTAGE: 13.8 kV BIL / (KV CLASS): 95 kV / 15 kV IMPEDANCE (P.U. ON 100 MVA BASE):

November 2012 System Data Book - 2012 Ver 9a Page 95

REACTOR DATA REACTOR NO.: 219 LOCATION: Silver Lake Plant Capacitor Bank MANUFACTURER: Joslyn YEAR OF MANUFACTURE: 1981 CAT. NO./SERIAL NO.: 3059X0016G1 / TYPE: 3 Single Phase Inrush Current Limiting PHASE / CYCLE: Single Phase / 60 Cycle KVA RATING: 3187 kVA CONTINUOUS CURRENT RATING: 400A SHORT CIRCUIT CURRENT RATING: 20,000 SYSTEM NOMINAL VOLTAGE: 13.8 kV BIL / (KV CLASS): 110 kV / 15 kV OPERATING VOLTAGE DROP: IMPEDANCE (ACTUAL OHMS): 0.00566 ohms, 0.04 mH IMPEDANCE (P.U. ON 100 MVA BASE): 0.00297

November 2012 System Data Book - 2012 Ver 9a Page 96

CABLE DATA VOLTAGE: 13.8 KV TERMINALS: Silver Lake Plant Bus #2 TO: 13.8 KV Capacitor Bank 209 TOTAL LINE MILES 0.0597 (315 ft.) MUTUAL MILES PHASE CONDUCTOR (UNDERGROUND) 3-1/C #750 MCM CU-P&L

shielded copper SHIELD CONDUCTOR CHARGING KVA 4.695 CHARGING AMPS 0.1964 LOADING CAPACITY (MVA) 16.11 LOADING CAPACITY (AMPS PER PHASE CONDUCTOR) 674.0 EQUIVALENT SPACING (FT.) IMPEDANCE DATA POSITIVE SEQUENCE (OHMS) 0.0097+j0.0224 ZERO SEQUENCE (OHMS) 0.0806+j0.0048 POSITIVE SEQUENCE (P.U.) 0.0051+j0.0118 ZERO SEQUENCE (P.U.) 0.0423+j0.0025

November 2012 System Data Book - 2012 Ver 9a Page 97

CAPACITOR DATA CAPACITOR NO.: 816 / 816C LOCATION: Zumbro River Substation MANUFACTURER: Cooper Power Systems YEAR OF MANUFACTURE: 2007 CAT. NO./ SERIAL NO.: CEB07030E0218D1 / TYPE: Edisol Fluid-Insulated PHASE / CYCLE: Three Phase / 60 Cycle KVAR RATING STAGE 1: 5400 kVAR KVAR RATING STAGE 2: 5400 kVAR SYSTEM NOMINAL VOLTAGE: 14.41 / 8.3 kV BIL / (KV CLASS): 110 kV * / 15 kV IMPEDANCE (P.U. ON 100 MVA BASE): * Individual capacitor units are rated 95 kV BIL.

November 2012 System Data Book - 2012 Ver 9a Page 98

REACTOR DATA REACTOR NO.: 816 LOCATION: Zumbro RIver Capacitor Bank MANUFACTURER: Trench Ltd. YEAR OF MANUFACTURE: 2007 CAT. NO./ SERIAL NO.: / TYPE: 3 Single Phase Inrush Current Limiting PHASE / CYCLE: Single Phase / 60 Cycle KVA RATING: 6.08 kVA CONTINUOUS CURRENT RATING: 400A SHORT CIRCUIT CURRENT RATING: 10 kA Thermal 1 sec. / 25.5 kA Mechanical peak SYSTEM NOMINAL VOLTAGE: 13.8 kV BIL / (KV CLASS): 200 kV / 34.5 kV OPERATING VOLTAGE DROP: IMPEDANCE (ACTUAL OHMS): 0.0380 ohms, 0.10 mH IMPEDANCE (P.U. ON 100 MVA BASE): 0.0200

November 2012 System Data Book - 2012 Ver 9a Page 99

REACTOR DATA REACTOR NO.: 816C LOCATION: Zumbro RIver Capacitor Bank MANUFACTURER: Trench Ltd. YEAR OF MANUFACTURE: 2007 CAT. NO./ SERIAL NO.: / TYPE: 3 Single Phase Inrush Current Limiting PHASE / CYCLE: Single Phase / 60 Cycle KVA RATING: 6.08 kVA CONTINUOUS CURRENT RATING: 400A SHORT CIRCUIT CURRENT RATING: 10 kA Thermal 1 sec. / 25.5 kA Mechanical peak SYSTEM NOMINAL VOLTAGE: 13.8 kV BIL / (KV CLASS): 200 kV / 34.5 kV OPERATING VOLTAGE DROP: IMPEDANCE (ACTUAL OHMS): 0.0380 ohms, 0.10 mH IMPEDANCE (P.U. ON 100 MVA BASE): 0.0200

November 2012 System Data Book - 2012 Ver 9a Page 100

SUBSTATION BUS DATA

LEGEND

1. Aluminum tube bus ratings are based on the NEMA CC1 standard. 2. The current carrying capacity of tubular bus is determined on the basis of:

a. Aluminum allow conductivity: i. 53% conductivity IACS (6063-T6 Alum. alloy) ii. 43% conductivity IACS (6061-T6) = I(53%) x (0.43/0.53)

½

b. Indoor ratings are calculated for a 30 deg. C rise above the ambient temperature of 40 deg. C in still but unconfined air.

c. Outdoor ratings are calculated for a 30 deg. C rise above the ambient temperature of 40 deg. C, wind velocity 2 ft. per second, and emissivity of 0.35.

d. Emergency ratings are 10% over normal ratings.

3. The current carrying capacity of bus jumpers are determined on the basis of: a. Outdoor ratings are calculated for a 35 or 50 deg. C rise above the ambient temperature of 40 deg. C, wind

velocity 2 ft. per second, solar absorbtivity and emissivity of 0.5, Industrial atmosphere, 1100 ft. above sea level, 44 degrees N latitude.

4. The rating information for switchgear is the actual rating stamped on the equipment nameplate or as

provided on manufacturer’s drawings and documentation.

5. Equipment ratings are based on RPU’s Facilities Ratings Methodology for Transmission, Substation, and Generation Equipment, in compliance with NERC FAC-008-3.

November 2012 System Data Book - 2012 Ver 9a Page 101

Summary of 161 kV Bus Configurations

November 2012 System Data Book - 2012 Ver 9a Page 102

Summary of 13.8 kV Bus Switchgear

November 2012 System Data Book - 2012 Ver 9a Page 103

Phasing Designations of Companies Interconnected with NSP (XCEL)