riser diagram - sdc security · model : e5rm s/n : 12345678. k3 alarm strike door sensor exit...

2
PROJECT NAME: DISTRIBUTOR: DWG. NO.: 0033 DWN BY: ML DATE: 08-2007 SECURITY DOOR CONTROLS 3580 Willow Lane Westlake Village CA 91361-4921 Tel. 805-494-0622 FAX: 805-494-8861 LOCATION: CONTACT: SO. NO.: © 2009 Security Door Controls Printed in U.S.A EMLock ® EntryCheck™ ExitCheck ® Selectric ® Spacesaver ® HiTower ® SureExit ® PAGE 1 OF 2 RISER DIAGRAM NOTES: (1) ALL LOW VOLTAGE SIGNAL WIRING SHALL BE 20-GAUGE MINIMUM. THE MINIMUM INDUCTIVE LOAD (LOCK) POWER WIRE GAUGE SHALL BE DETERMINED PER THE SDC WIRE GAUGE CHART. ALL WIRING (SINGLE OR MULTI-CONDUCTOR) SHALL BE COLOR CODED WITHOUT SPLICES. A MINIMUM OF TWO SPARE CONDUCTORS IS RECOMMENDED. (2) SPECIFY VOLTAGE WHEN ORDERING PRODUCTS. VOLTAGE IS NOT SPECIFIED ON THIS WIRE DIAGRAM, BE SURE ALL PRODUCTS ARE VOLTAGE COMPATIBLE. (3) ALL WIRING MUST CONFORM TO NATIONAL, STATE AND LOCAL CODES. (4) ALWAYS CONSULT WITH THE AUTHORITY HAVING JURISDICTION (AHJ) BEFORE INSTALLATION. (5) WHERE REQUIRED BY CODE, CONNECT FAILSAFE SYSTEMS TO THE LOCAL FIRE LIFE SAFETY SYSTEM FOR EMERGENCY RELEASE. 602RF POWER SUPPLY TO 120VAC POWER SOURCE TO FIRE ALARM – CLOSED CONTACT CONNECTION 2 COND 4 COND PUSH TO EXIT 422 EXIT BUTTON (INSIDE) Components Qty Description Part Number Manufacturer 1 Magnetic Lock 1511 1571 1581 SDC 1 1 Amp Power Supply 602RF SDC 1 Exit Push Button 422U 412NU SDC 1 Proximity/PIN Card Reader E4KP SDC HID ProxCard II HID-1326 HID Method of Operation Access/Egress: Presenting an authorized card to the reader releases the locking device momentarily for access. Pressing the exit switch button releases the locking device momentarily for egress. Entry and exit momentary unlock time is determined by the card reader programming. Emergency Release: All locks will release automatically (see note 5) upon activation of the fire life safety system. E4KP PROX CARD READER (OUTSIDE) 4 COND EMLOCK ® 1511, 1571 or 1581 AS SPECIFIED BELOW

Upload: lyminh

Post on 21-Apr-2018

220 views

Category:

Documents


5 download

TRANSCRIPT

Page 1: RISER DIAGRAM - SDC Security · model : e5rm s/n : 12345678. k3 alarm strike door sensor exit button input dc12v. on 1 2 3. card reader e4kp – card reader w/ controller relay module

PROJECT NAME: DISTRIBUTOR:

DWG. NO.: 0033

DWN BY: MLDATE: 08-2007

SECURITY DOOR CONTROLS3580 Willow Lane

Westlake Village CA 91361-4921Tel. 805-494-0622 FAX: 805-494-8861

LOCATION:

CONTACT:

SO. NO.:

© 2009 Security Door Controls Printed in U.S.A

EMLock® EntryCheck™ExitCheck® Selectric® Spacesaver® HiTower® SureExit®

PAGE 1 OF 2

RISER DIAGRAM

NOTES: (1) ALL LOW VOLTAGE SIGNAL WIRING SHALL BE 20-GAUGE MINIMUM. THE MINIMUM INDUCTIVE LOAD (LOCK) POWER WIRE GAUGE SHALL BE DETERMINED PER THE SDC WIRE GAUGE CHART. ALL WIRING (SINGLE OR MULTI-CONDUCTOR) SHALL BE COLOR CODED WITHOUT SPLICES. A MINIMUM OF TWO SPARE CONDUCTORS IS RECOMMENDED. (2) SPECIFY VOLTAGE WHEN ORDERING PRODUCTS. VOLTAGE IS NOT SPECIFIED ON THIS WIRE DIAGRAM, BE SURE ALL PRODUCTS ARE VOLTAGE COMPATIBLE. (3) ALL WIRING MUST CONFORM TO NATIONAL, STATE AND LOCAL CODES. (4) ALWAYS CONSULT WITH THE AUTHORITY HAVING JURISDICTION (AHJ) BEFORE INSTALLATION. (5) WHERE REQUIRED BY CODE, CONNECT FAILSAFE SYSTEMS TO THE LOCAL FIRE LIFE SAFETY SYSTEM FOR EMERGENCY RELEASE.

602RF POWER SUPPLY TO 120VAC POWER SOURCE

TO FIRE ALARM – CLOSED CONTACT CONNECTION

2 COND

4 COND

PUSHTO

EXIT

422 EXIT

BUTTON(INSIDE)

Components

Qty Description Part Number Manufacturer 1 Magnetic Lock 1511 1571 1581 SDC 1 1 Amp Power Supply 602RF SDC 1 Exit Push Button 422U 412NU SDC 1 Proximity/PIN Card Reader E4KP SDC

HID ProxCard II HID-1326 HID

Method of Operation

Access/Egress: Presenting an authorized card to the reader releases the locking device momentarily for access. Pressing the exit switch button releases the locking device momentarily for egress. Entry and exit momentary unlock time is determined by the card reader programming. Emergency Release: All locks will release automatically (see note 5) upon activation of the fire life safety system.

E4KPPROX CARD

READER(OUTSIDE)

4 COND

EMLOCK®

1511, 1571 or 1581AS SPECIFIED BELOW

damaso
Select Lock and Switch Switch of choice
damaso
Marked set by damaso
Page 2: RISER DIAGRAM - SDC Security · model : e5rm s/n : 12345678. k3 alarm strike door sensor exit button input dc12v. on 1 2 3. card reader e4kp – card reader w/ controller relay module

PROJECT NAME:

DIST.: DWG. NO.:DRAWN BY: DATE:

SECURITY DOOR CONTROLS3580 Willow LaneWestlake Village CA 91361-4921Tel. 805-494-0622 FAX: 805-494-8861

LOCATION.: CONTACT:

SO NO.:

PAGE 2 OF 2

© 2009 Security Door Controls Printed in U.S.A

REV--

DWG0033

TITLE:

- -- -- 08-2007 ML

--NOTE: ALL WIRING MUST BE REVIEWED AND APPROVED BY THE PROJECT ENGINEER ASSIGNED TO THE LOCATION FOR IT’S CORRECTNESS AND SUITABILITY FOR THE APPLICATION IN THE WHICH THE EQUIPMENT INSTALLED AND OPERATED. ALL WIRING MUST CONFORM TO NATIONAL, STATE, AND LOCAL CODES FOR CLASS 2 FIRE PROTECTION AND CONTROL DEVICES.

--

HiTower®Spacesaver®Exit Check® EMLock® Sure Exit® EntryCheck™SELECTRIC®

POINT TO POINT WIRING DIAGRAM

PUSHTO

EXIT

1511, 1571 OR 1581 SERIES MAGNETIC LOCKS422U OR 422NU

MOMENTARY - SPDT

C

NC

NO

YEL

ORG

WHT

+ - C+ -

G

W

B

CLOSED FIRE ALARMCONTACT

+

-

STANDBYBATTERY

CONNECTION

12VDC OUTPUT

(REMOVE FACTORY JUMPER ONLY IF FIRE ALARM IS USED)

REFER TO POWER SUPPLY INSTRUCTIONS FOR 12VDC

VOLTAGE SELECTION PROCEDURE

TO 120VAC PRIMARY VOLTAGE CONNECTION

602 SERIES POWER SUPPLY

24V 12V

NO

NC

COM

NO

NC

COM

POWER

{DPS

BAS

BAS PLUG IN

15111571

1581

NO

NC

COM

NOT USED

POWER

{DPS

34

56

78

34

56{

REDBLKBRNORG

REDBLKBRNORG

J3REDBLKBRNORGYEL

E5RM CONTROLLER RELAY MODULE

NOT USED

REDBLKBRNORGYELGRNBLU

YELGRNBLUYELGRNBLU

J2

J1

REDBLKBRNORGYELGRNBLU

YELGRNBLUYELGRNBLU

300 ft MAX

+12VGND

CLOCKDATA

+-ACCESSCONTROLLER

K3 FUNCTION SETTINGFUNCTION

DURESS/SHUNTGUARDPATROL

1 2 3ON OFF OFF

ONON

OFFOFFOFF OFF

MODEL : E5RMS/N : 12345678

K3

ALARM

STRIKE

DOOR SENSOREXIT BUTTON

INPUT DC12V

ON

1 2 3

CARD READER

E4KP – CARD READER W/ CONTROLLER RELAY MODULE

RED

RED

LAMP