retrofit guidelines for dupont mo79 refrigerant - chemours · pdf filereservoirs on the low...
TRANSCRIPT
DuPont™ ISCEON® 9 SeriesREFRIGERANTS
Technical Information
ART- 44 (MO79-EU)
Retrofit Guidelines forDuPont™ ISCEON® MO79 (R-422A)
Refrigerant
Retrofit Guidelines for
DuPont™ ISCEON® MO79 Refrigerant
Table of Contents
Page
Introduction 1
Summary - Steps to Retrofit 1
Important Safety Information 1
Flammability 2
General Retrofit Information 2
Lubricant 2
Filter Drier 2
Elastomeric Seals/ Gaskets etc. 2
System Modifications 3
System Superheat 3
System Oil Management 3
Systems with Capillary Tube expansion devices 3
Refrigerant Recovery Information 3
Expected Performance After Retrofit 4
Detailed Retrofit Procedure for R22 Systems to ISCEON® MO79 4
Pressure-Temperature Charts 7
How to Read the Pressure/Temperature Tables 7
How to Determine Suction Pressure, Superheat, and Subcool 7
Retrofit Checklist for conversion of R22, R502, R402A, R408A (and other refrigerant) toISCEON® MO79 8
System Data Sheet 10
Physical property comparison 11
Composition of ISCEON® MO79 11
Appendix
(PT Charts ) 12
3
Introduction
DuPont™ ISCEON® MO79 (R-422A) is a non-ozone-
depleting HFC Refrigerant designed to replace R22
containing refrigerants used in R502 technology equipment
(e.g. R402A, R408A and others) in existing direct expansion
(DX) medium- and low-temperature refrigeration systems. It
is also recommended as a replacement for R22 in low
temperature DX refrigeration systems where either additional
system cooling capacity is required or in close-coupled
systems where compressor discharge temperature control is
not used. (In these cases check that system design
pressures will be adequate for ISCEON® MO79)
Field experience has shown that ISCEON® MO79 provides
performance that meets customer requirements in most
properly retrofitted systems. ISCEON® MO79 provides
similar cooling capacity and energy efficiency to R502 in
most systems. Actual performance depends on system
design and operating conditions.
ISCEON® MO79 is compatible with traditional and new
lubricants; in most cases no change of lubricant type
during retrofit is required. Oil return is determined by a
number of operating and design conditions – in some
systems with complex piping configurations or liquid
reservoirs on the low pressure side, POE may need to be
added. Minor equipment modifications (e.g., seal
replacement) or expansion device adjustments may be
required in some applications. Systems using ISCEON®
MO79 are easy to service. For most systems, should a
refrigerant loss occur, the charge can be completed
without the need to remove any residual refrigerant, and
the system will then operate normally. The cause of the
refrigerant loss should be investigated and corrected as
soon as is possible.
Note: When servicing critically charged systems, all of the
refrigerant charge should be removed. This is the same
practice recommended for all other refrigerants in critically
charged systems.
General Considerations
The use of ISCEON® MO79 in the EU and EEA member
countries is regulated under the terms of the Regulation
842/2006 (known as the “F Gas Regulation”), which
requires regular leakage testing for systems using the
designated substances. ISCEON® MO79 (R422A) is
listed in the European Standard EN 378:2008
(Refrigerating and Heat Pump Systems – Safety and
Environmental Requirements). Part 4 of this standard
relates to retrofit activities.
Summary - Steps to RetrofitThe following provides a summary of the basic retrofit steps
for ISCEON® MO79.
(Detailed discussion of each step is provided in this bulletin.)
1. Establish baseline performance with existing refrigerant.
(See retrofit checklist (attached))
2. Remove all the old (R22 containing) refrigerant from the
system into a recovery cylinder. Weigh the amount
removed.
3. Replace the filter drier and critical elastomeric
seals/gaskets.
4. Evacuate system and check for leaks.
5. Charge with ISCEON® MO79.
• Remove liquid only from charging cylinder.
• The initial charge amount should be lower than the
standard amount of old refrigerant. (For the expected
charge sizes for the principal R502 technology, R-22
containing refrigerants see Table 2)
6. Start up system, adjust charge size (unless liquid
receiver or TXV present) to achieve optimum
superheat.
7. Monitor oil levels in compressor. Add oil as required to
maintain proper levels
8. Label system showing the refrigerant (and any
replacement lubricant) used. Update system log-book.
Retrofit Complete
Important Safety Information
Like CFCs and HCFCs, ISCEON® 9 Series refrigerants are
safe to use when handled properly. However, any refrigerant
can cause injury or even death when mishandled. Please
review the following guidelines before using any refrigerant.
• Do not work in high concentrations of refrigerant vapors.
Always maintain adequate ventilation in the work area. Do
not breathe vapors. Do not breathe lubricant mists from
leaking systems. Ventilate the area well after any leak
before attempting to repair equipment.
4
• Do not use handheld leak detectors to check for
breathable air in enclosed working spaces. These
detectors are not designed to determine if the air is safe to
breathe. Use oxygen monitors to ensure adequate oxygen
is available to sustain life.
• Do not use flames or halide torches to search for leaks.
Open flames (eg. Halide detection torches, or brazing
torches) can release large quantities of acidic compounds
in the presence of all refrigerants, and these compounds
can be hazardous. Halide torches are not effective as leak
detectors for HFC refrigerants; they detect the presence of
Chlorine, which is not present in ISCEON® MO79, and
consequently, these detectors will not detect the presence
of this refrigerant. Use an electronic leak detector
designed to find the refrigerants you are using.
If you detect a visible change in the size or color of a flame
when using brazing torches to repair equipment, stop work
immediately and leave the area. Ventilate the work area
well and stop any refrigerant leaks before resuming work.
These flame effects may be an indication of very high
refrigerant concentrations, and continuing to work without
adequate ventilation may result in injury or death.
Note: Any refrigerant can be hazardous if used improperly.
Hazards include liquid or vapor under pressure, and frostbite
from the escaping liquid.
Overexposure to high concentrations of refrigerant vapor can
cause asphyxiation and cardiac arrest. Please read all safety
information before handling any refrigerant.
Refer to the ISCEON® MO79 Material Safety Data Sheet
(MSDS) for more specific safety information. .DuPont Safety
Bulletin AS-1 also gives additional information for safe
handling of refrigerants.
Flammability
ISCEON® MO79 is non-flammable in air under normal
conditions. However, this product when mixed with high
concentrations of air or oxygen under elevated pressure can
become combustible in the presence of an ignition source.
This product should not be mixed with air to check for
system leaks.
General Retrofit Information
Lubricants
Lubricant selection is based on many factors, including
compressor wear characteristics, material compatibility, and
lubricant/refrigerant solubility (which can affect oil return to
the compressor). ISCEON® MO79 is compatible with
traditional and new lubricants – in most retrofit situations with
direct expansion systems no change of oil type is required.
Field experience has shown that ISCEON® MO79 will
work successfully with the existing mineral (or alkyl-
benzene) oil in most DX systems. In systems where oil
return is a potential concern, such as systems where the
suction line accumulator acts as a low pressure receiver,
replacement of all, or part (~30%) of the compressor oil
charge with an OEM approved polyol ester oil is
recommended.
Filter Drier
Change the filter drier during the retrofit. This is a routine
system maintenance practice. There are two types of filter
driers commonly used, solid core and loose filled. Replace
the drier with the same type currently in use in the system.
The drier label will show which refrigerants can be used with
that drier. Select a drier specified to work with HFC
refrigerants. (Many driers sold today are “universal” – they
will work with most fluorocarbon refrigerants.)
Elastomeric Seals/ Gaskets etc.
R22 containing refrigerant blends (and to a greater extent
R22), interact relatively strongly with many elastomers
causing significant swelling and often, over time, a
measurable increase in hardness, etc. ISCEON® MO79
does not have such a strong effect on those elastomers
commonly used in seals in refrigeration systems. A
consequence of this is that, when replacing R22 containing
blends (and, to a greater extent, R22) with ISCEON® MO79
in a system retrofit, it is possible for leaks to occur at
Elastomeric seals that are exposed to the refrigerant. (This is
not a problem attributable to the use of ISCEON® MO79.
Such seal leaks have been reported when replacing R22
based refrigerants with other HFC refrigerants such as
R407C or R404A.) Leaks do not occur in every system
retrofitted and, in practice, it is difficult to predict whether
such leaks will occur. (As a rule of thumb the older the
system, the higher the probability that leaks will be observed
after a retrofit.)
5
As a consequence it is recommended to change any
system-critical seals (those which would require removal of
the refrigerant charge to allow seal replacement e.g., liquid
receiver, liquid sight glasses, etc.) as a matter of course
during the retrofit and to have spare seals for other
components available during restart of the system. A
rigorous leak check regime pre- and post- retrofit will
minimize any refrigerant losses. All seals should be checked
including manual valves, schrader valves, solenoid valves,
sight glasses, electrical cable sealing grommets (on
compressors), mechanical seals on open drive compressors,
etc. Obviously any seals found to be leaking before the
retrofit takes place should be replaced during the retrofit.
System Modifications
The compositions of the ISCEON® MO79 refrigerant has
been selected to provide performance comparable R502 in
terms of both capacity and energy efficiency. As a result,
minimal system modifications are anticipated when
retrofitting.
ISCEON® MO79 is a near-azeotrope. The vapor
composition in the refrigerant cylinder is different from the
liquid composition. For this reason, ISCEON® MO79 should
be transferred from the container from the liquid phase
during system charging (or when transferring from one
container to another).
In general, ISCEON® MO79 refrigerant is not recommended
for use in centrifugal compressor systems or for chillers with
flooded evaporators. Direct expansion systems with low
pressure receivers may be retrofitted using ISCEON® MO79
but a single oil change to a POE oil of the same viscosity as
the original oil type is required to ensure adequate oil
management for this system configuration.
Note: ISCEON® MO79 should not be mixed with other
refrigerants or additives that have not been clearly specified
by DuPont or the system equipment manufacturer. Mixing
this refrigerant with CFC or HCFC refrigerants, or mixing two
different alternative refrigerants, may have an adverse effect
on system performance. “Topping off” a CFC or HCFC
refrigerant with any Suva® or ISCEON® 9 Series refrigerant
is strictly not recommended.
System Superheat
Desired system performance after a retrofit with DuPont™
ISCEON® MO79 requires correct setting of the system
superheat. This is discussed in the detailed retrofit
procedures given below.
System Oil Management
In many situations, systems retrofitted with ISCEON® MO79
have operated routinely using the mineral oil or Alkyl
benzene that was used with the original HCFC refrigerant.
With complex systems, in a small number of cases, the oil
may not return consistently to the compressor.
It is important that oil levels in the compressors be monitored
during initial operation with the ISCEON® MO79. If the oil
level falls below the minimum allowed, top up the oil to the
minimum level with the existing oil type. Do not fill to
maximum as the level may rise again.
Should the oil level fall continuously, or suffer large
oscillations during an operating cycle, addition of POE
lubricant has proven effective in restoring adequate oil return
rates. POE lubricant should be progressively added to the
system. An initial addition of 10-30% (of the total oil charge)
should be made. This should be followed by further small
increments until the oil level returns to normal.
It is important to ensure that, when adding POE oil to the
system, the oil level (immediately after addition) is kept
below the system mid-point (e.g. mid-sight glass) oil level.
It is also important to keep accurate records of how much oil
is added to avoid over-filling.
Systems with Capillary Tube expansiondevice
In general it is not necessary to change the capillary tube in
the refrigerant circuit. Experience has shown that capillary
tubes used in R502 and similar systems give good
performance when the system is retrofitted to use ISCEON®
MO79. In these systems setting of the compressor
suction superheat is made by adjusting the refrigerant
charge quantity in the system.
Refrigerant Recovery Information
Most recovery or recycle equipment used for R502, R22 or
R22 containing blends, can be used for ISCEON® MO79.
Use standard procedures to avoid cross contamination when
switching from one refrigerant to another. Most recovery or
recycle machines can use the same compressor oil that was
used for the HCFC refrigerant. However, some modifications
may be necessary, such as a different kind of drier or a
different moisture indicator. Consult the equipment
manufacturer for specific recommendations.
6
Expected Performance After Retrofit
Table 1 shows approximate system performance changes
following a retrofit and are general guidelines for system
behavior. These values are based on thermodynamic
property data; and assume equal compressor efficiency.
Cooling capacity and energy efficiency depend greatly on
system design, operating conditions and the actual condition
of the equipment. ISCEON® MO79 provides similar cooling
capacity and energy efficiency to R22 containing blends in
most systems while operating at significantly lower
compressor discharge temperature. Actual performance
depends on system design and operating conditions.
Table 1ISCEON
®MO79 Performance Compared to R22, R502, Suva
®HP80 and Suva
®408 in Low Temperature refrigeration
systems
Performance with subcooling based on thermocycle calculations and do not include heat tr ansfer effects
RefrigerationLow Temperature
–35°C evaporator, 40°C condenser, 8K evaporator superheat, 18°C return gas, 5K subcooling
Difference vsR502
Difference vsSuva HP80
(R402A)
Difference vsR408A
Difference vsR22
Difference vsR407A
Discharge Temperature (with demand cooling) -8 K -8 K -8 K -8 K -8 K
Discharge Temperature (without demand cooling) -17 K -18 K -31 K -64 K -34 K
Discharge Pressure (bar) 1.7 -1.0 1.4 3.0 0.9
Cooling Capacity (with demand cooling) -2% -9% 5% 28% 18%
C.O.P. (with demand cooling) -3% 1% 5% 16% 9%
“+” represents an increase and “–“ represents a decrease for ISCEON®
MO79 vs. the other refrigerants.R22 assumes demand cooling with discharge temperature controlled at 125ºC
Table 2
Refrigerant Charge Amount Recommendations for Retrofit to ISCEON® MO79
Approximate ApproximateInitial Charge Final Charge
R22 85% 95%R502 85% 95%
R402A (HP80) 90% 100%R408A 90% 105%
Note: These values apply provided no changes to mechanical components of the system (which could significantly affect the
system’s internal volumetric capacity) will be made during the retrofit.
7
Detailed Retrofit Procedure for R22 inDirect Expansion Medium and LowTemperature Refrigeration Systems,Residential and Commercial Air-Conditioning
(Refer to the retrofit checklists on p. 8 and 9of this bulletin)
1. Establish baseline performance before the retrofit.
Collect system performance data while the previous
refrigerant is in the system. Check for correct refrigerant
charge and operating conditions. The baseline data of
temperatures and pressures at various points in the system
(evaporator, condenser, compressor suction and discharge
and calculation of superheat and subcool.) at normal
operating conditions will be useful when optimizing operation
of the system with the ISCEON®
MO79. A System Data
Sheet is included at the back of this bulletin to record
baseline data.
2. Remove the existing refrigerant from the system
into a recovery cylinder. The existing charge should be
removed from the system and collected in a recovery
cylinder using a recovery device capable of pulling 10–15 in
Hg vacuum (50–65) kPa absolute). If the recommended
charge size for the system is not known, weigh the amount
of refrigerant removed. The initial quantity of ISCEON®
MO79 to charge to the system can be estimated from this
amount. (See step 5). Ensure that any residual refrigerant
dissolved in the compressor oil is removed by holding the
system under vacuum. Break the vacuum with dry nitrogen.
3. Replace the filter drier and critical elastomeric
seals/gaskets etc
It is routine practice to replace the filter drier during system
maintenance. Replacement filter driers are available that are
compatible with ISCEON® MO79.
While the system is empty, check and replace any
elastomeric seals that may be near the end of their
serviceable life. Even if they were not previously leaking, the
change of swell characteristics when changing to any new
refrigerant (e.g., R22 containing refrigerant to any HFC
refrigerant) and the general disturbance to the system may
cause worn seals to leak after retrofit. Although, in general,
the same seal materials can be used with ISCEON® MO79
(refer to Compatibility Tables in the DuPont PUSH bulletin
#K-10927) it has been observed as with other HFC based
refrigerants that shrinkage of the original seal may occur
after conversion causing refrigerant leakage (refer to the
DuPont bulletin on HFC Compatibility with Elastomeric Seals
#K-17335). Critical components commonly affected are
Schrader core seals, liquid level receiver gaskets, solenoid
valves, ball valves and flange seals but all external seals in
contact with the refrigerant should be viewed as a potential
leak source post retrofit. Field experience has shown that the
older the system, the greater the likelihood of seal and
gasket leaks. It is recommended to change any system
critical seals (e.g., those which require removal of the
refrigerant charge to allow seal replacement e.g., liquid
receiver, condenser system) as a matter of course and to
have spare seals for other components available during the
retrofit should any seal failure occur Schrader valves can
generally be changed in-situ, under pressure, using a special
tool, and thus are not considered to be system critical. A
rigorous leak check regime pre and post retrofit will minimize
any refrigerant losses.
4. Evacuate system and check for leaks. Use normal
service practices. To remove air or other non-
condensables and any residual moisture from the system,
evacuate the system to near full vacuum (29.9 in Hg vacuum
[500 microns] or less than 0.1 kPa absolute), isolate the
vacuum pump from the system and observe the vacuum
reading. If the system does not maintain vacuum it is an
indication that there might be a leak. Pressurise the system
with nitrogen taking care not to exceed the system design
maximum pressure and check for leaks. Do not use mixtures
of air and refrigerant under pressure to check for leaks;
these mixtures can be combustible. After leak checking with
Nitrogen remove residual Nitrogen using a vacuum pump.
5 Charge with ISCEON® MO79. Remove liquid only
from charging cylinder. (If the cylinder does not have a valve
with a dip-tube invert the cylinder so that the valve is
underneath the cylinder). The proper cylinder position for
liquid removal is often indicated by arrows on the cylinder
and cylinder box. Once Liquid is removed from the cylinder,
the refrigerant can be allowed to enter the refrigeration
system as liquid or vapor as desired. Use the manifold
gauges or a throttling valve to flash the liquid to vapor if
required.
WARNING: Do not charge liquid refrigerant into the
compressor. This will cause serious irreversible
damage!
In general, the refrigeration system will require less weight of
the ISCEON® MO79 than of the original R22 charge,
8
although some will require slightly more (See table 2). The
optimum charge will vary depending on the system design
and operating conditions.
Note: For systems with a liquid refrigerant receiver charge
the system to the normal refrigerant level in the receiver. The
values given in table 2 apply provided no changes to
mechanical components of the system (which could
significantly affect the system’s internal volumetric capacity)
will be made during the retrofit.
6. Start up system, adjust charge size (for systems
without a liquid receiver).
Start the system and let conditions stabilize. If the system is
undercharged (as indicated by the level of superheat at the
evaporator exit, or by the amount of sub-cool at the
condenser exit) add more ISCEON® MO79 in small amounts
(still by transferring as liquid from the charging cylinder) until
the system conditions reach the desired level. See the
pressure-temperature charts in this bulletin to compare
pressures and temperatures in order to calculate superheat
or sub-cooling for the refrigerant you are using. Sight
glasses in the liquid line can be used in most cases as a
guide to system charge, but correct system charge must be
determined by measuring system operating conditions
(discharge and suction pressures, suction line temperature,
compressor motor amps, superheat, etc.). Attempting to
charge until the sight glass is “free of bubbles” may result in
overcharging the refrigerant. Please read “How to Determine
Suction Pressure, Superheat and Subcool.”
Ensuring that the correct compressor suction superheat
is set is very important for reliable system operation with
ISCEON® MO79. Experience has shown that superheat (at
the compressor inlet) for ISCEON® MO79 should be the
same as for the refrigerant being replaced.
WARNING: Liquid refrigerant entering the compressor at
any time during system operation can lead to
compressor oil level problems and rapid compressor
failure.
7. Monitor oil levels.
During initial operation of the system it is very important
to monitor the level of oil in the compressor (or
compressor oil management system) to verify that oil is
returning to the compressor in an adequate manner.
• If the oil level falls below the minimum allowed level,
top up to the minimum level with the existing oil type.
Do not fill to the maximum level as the level may rise
again.
• Should the oil return appear to be erratic as
evidenced by large swings in oil level during the
refrigeration system cycle it is recommended that
some of the oil be removed from the system and
replaced with POE oil. Replacement of up to 30% of
the oil with POE will help to restore oil return stability.
The exact amount of oil to be changed will depend
on the system itself (evaporating temperatures,
physical geometry, etc.)
• POE lubricant should be progressively added to the
system. An initial addition of 10 – 20% (of the total oil
charge) should be made. This should be followed by
small increments until the oil level returns to normal
consistently throughout the refrigeration system
operating cycle.
• It is important to ensure that, when adding POE oil to
the system, the oil level (immediately after addition)
is kept below the system mid-point (e.g. mid-sight
glass) oil level.
8. Label the system to clearly and permanently show the
refrigerant in the system and any oil(s) present in the
system. It is most important that the change in
refrigerant and any other component (including
lubricating oil) changes be registered in the system
documentation (log book).
IMPORTANT: Thoroughly leak check the system. As
mentioned in step 3 it is possible that refrigerant
leakage can occur during or immediately after a
retrofit. Experience has shown that some leaks will
not appear until after the new refrigerant has been
charged to the system. Pay particular attention to
Schrader valve core seals, solenoid valves and ball
valve stems on the liquid high-pressure side.
9
Pressure/Temperature Charts
How to Read the Pressure/Temperature Chart
The following pages contain pressure/temperature charts for
the refrigerants discussed in this bulletin. Three
temperatures are shown at a given pressure:
• Saturated Liquid Temperature (Bubble Point)—In the
condenser, this is the temperature at which the last bit of
vapor has condensed. Below this temperature, the
refrigerant will be subcooled liquid. This temperature
should also be used when determining the
pressure/temperature value of product stored in a
refrigerant cylinder.
• Saturated Vapor Temperature (Dew Point)—In the
evaporator, this is the temperature at which the last drop
of liquid has just boiled. Above this temperature, the
refrigerant will be superheated vapor.
• Average Coil Temperature (for ISCEON® MO79)—The
evaporator and condenser will perform as if it is operating
at this constant temperature. It is an average of the bubble
and dew point temperatures determined from either the
suction or condenser pressure. Use this average
temperature to compare coil temperatures with the
refrigerant you are replacing. Note: this is an
approximation of the average temperature for low glide
refrigerants.
How to Determine Suction Pressure,Superheat, and Subcool
Suction Pressure
Determine the expected evaporator temperature using the
R22 containing refrigerant (from the baseline data you
collected prior to the retrofit). Find the same expected
evaporator temperature in the Average Coil Temperature
column for ISCEON® MO79. Note the corresponding
pressure for this temperature. This is the approximate
suction pressure at which the system should operate.
Superheat
Using the saturated vapor pressure tables for ISCEON®
MO79, determine the saturated vapor temperature (dew
point) for the measured suction pressure. Measure the
temperature at the compressor inlet (suction) and subtract
the previously determined dew point temperature for
ISCEON MO79 to give the amount of vapor superheat.
Subcool
Using the saturated liquid pressure tables for ISCEON®
MO79, determine the saturated liquid temperature (bubble
point) for the measured condensing pressure (usually the
high-side pressure). Measure the refrigerant liquid line
temperature and subtract it from the previously determined
bubble point temperature for ISCEON® MO79 to give the
amount of liquid subcool.
10
Retrofit Checklists for Converting CFC or HCFC Systems to DuPont™ ISCEON® MO79
Retrofit Guidelines forDuPont™ ISCEON® MO79 Refrigerant
Retrofit Check List: 1) Pre- and Post- Retrofit Checks
Pre-Retrofit
Advance Preparation for Retrofit
1 Ensure the Retrofit Procedure has been read
Clarify any doubts with DuPont Technical Services
2 Check Service History log-book
Recent refrigerant additions might signify system leaks
Is current system design in agreement with log-book?
3 Leak check system
If leaks found schedule repair
4 Check compressor oil management system design
If no oil separator present oil level observation needed after retrofit
5 System performance check: complete data sheet
See Retrofit procedure p.10
If obvious performance problem: Correct before retrofit (or plan to do it during retrofit)
6 Identify system critical elastomeric seals
See Retrofit Guidelines p.2
7 Check Compressor oil condition
If doubtful schedule change
8 Ensure all needed materials will be available
Seals, filter cores, etc.
Recovery cylinder(s) Recovery machine, vacuum pump, Nitrogen
Technical data: Retrofit Guidelines, PT data (Slide rules, etc.)
Post-Retrofit
Verification of system performance and integrity
24 hrs 48 hrs 72hrs 1 week
1 Observe compressor oil level
Correct if needed (see Guidelines p 6)
2 Measure Performance Data
Use Data Sheet
3 Carry out Leak check
Correct any leaks found
Complete
CheckComplete
Check
11
Retrofit Guidelines forDuPont™ ISCEON® MO79 Refrigerant
Retrofit Check List: 2) Retrofit Progress Checks
Retrofit Steps
1 Recover old refrigerant using good refrigeration practice
Use dedicated recovery cylinder(s)
Weigh the recovered refrigerant
De-gas the compressor oil using a vacuum pump
2 Break the vacuum using dry nitrogen
Minimise ingress of moist air into the system
4 Change necessary mechanical components
Filter/dryer
Identified system critical elastomeric seals
Replace oil if needed
5 Evacuate system. Hold under vacuum.
To remove moisture.
Early indication of leaks (if vacuum does not hold)
6 If indication of leak pressurise with Nitrogen.
Locate leak(s). De-pressurise and correct
Evacuate system. Hold under vacuum
7 Charge with ISCEON®MO79 from liquid phase
a) If system receiver - to normal level
b) If no receiver - initial 90% of R22 charge (See text for values for other refrigerants)
8 Start system, measure performance data (See data sheet)
Adjust refrigerant charge if needed
Adjust superheat setting if needed
10 Check Compressor oil levels
Adjust if necessary
11 Re-check system for refrigerant leaks
12 Label System
Refrigerant (and any added/changed oil)
Update log-book
CheckComplete
12
System Data Sheet
Type of System/Location: _________________________________________________________________________Equipment Mfg.:_______________________________________ Compressor Mfg.:______________________________Model No.:_______________________________________ Model No.:____________________________________Serial No.:_______________________________________ Serial No.:____________________________________Date of Manufacture_______________________________ Date of manufacture____________________________Original Refrigerant Charge Size:__________________________ Lubricant Type:____________________________Lubricant Charge Size:__________________________________ Drier Mfg.:____________________________________
Drier Type (check one): Model No.:_________________________ Loose Fill:________Solid Core:___________________
Condenser Cooling Medium (air/water): _________________________________________________________________
Expansion Device (check one): Capillary Tube: _________Expansion Valve: _______
If Expansion valve: Manufacturer: _____________________________ Model No:_______________________________
Control/Set Point: ________________ Location of Sensor: __________________________________________________
Other System Controls (ex.: head press control),
Describe:_____________________________________________________________________
(circle units used where applicable)
Date/Time
Refrigerant
Charge Size (kg)
Ambient Temp. (°C)
Compressor:
Suction T (°C)
Suction P (kPa)
Discharge T (°C)
Discharge P (kPa/)
Evaporator:
Coil Air/H2O In T (°C)
Coil Air/H2O Out T (°C)
Operating Service Temperature) (°C)
Condenser:
Coil Air/H2O In T (°C)
Coil Air/H2O Out T (°C)
Superheat and Sub-Cool (derived values)
Refrigerant T at Superheat Ctl. Pt (°C)
Calculated Superheat (K)
Exp. Device Inlet T (°C)
Calculated sub-cool (K)
Motor Amps (if pack: total)
13
Table 3
Physical Properties of DuPont™ ISCEON® MO79
Physical Property Unit ISCEON®
MO79 R-22 R-502
Boiling Point (1 atm.) °C –47 –41 –45
Pressure at 25°C (77°F) kPa abs 1274 1041 1162
Density at 25°C (77°F) kg/m3
1136 1193 1217
Satd. Vapor at 25°C (77°F) kg/m3
74.3 44.9 67.3
Ozone Depletion Potential CFC11 = 1.0 0 0.05 0.23Global Warming Potential CO2 = 1 2530 1700 5494
Table 4
Composition of ISCEON® MO79 (Wt. %)
HFC125 HFC134a isobutane
ISCEON MO79 85.1 11.5 3.4
14
Appendix
Table 5
Pressure – Temperature Chart (SI Units): R22, R502 and ISCEON® MO79
Pressure Temperature (ºC)(bar(g)) R22 ISCEON®MO79 R502
Sat Liq Sat Vap. Ave. Coil
–0.7 –64 –69 –66 –67 –68–0.6 –59 –64 –61 –63 –63–0.5 –55 –60 –57 –59 –59–0.4 –51 –57 –54 –55 –56–0.3 –48 –54 –51 –53 –53
–0.2 –46 –51 –49 –50 –50–0.1 –43 –49 –46 –48 –48
0 –41 –47 –44 –46 –45
0.1 –39 –45 –42 –44 –430.2 –37 –43 –41 –42 –41
0.3 –35 –41 –39 –40 –400.4 –34 –40 –37 –38 –380.5 –32 –38 –36 –37 –360.6 –31 –37 –34 –35 –350.7 –29 –35 –33 –34 –33
0.8 –28 –34 –32 –33 –32
0.9 –26 –33 –30 –31 –311 –25 –31 –29 –30 –29
1.1 –24 –30 –28 –29 –28
1.2 –23 –29 –27 –28 –27
1.3 –22 –28 –26 –27 –261.4 –21 –27 –25 –26 –251.5 –20 –26 –24 –25 –24
1.6 –18 –25 –23 –24 –231.7 –17 –24 –22 –23 –22
1.8 –17 –23 –21 –22 –211.9 –16 –22 –20 –21 –20
2 –15 –21 –19 –20 –192.1 –14 –20 –18 –19 –182.2 –13 –19 –17 –18 –17
2.3 –12 –18 –17 –18 –16
2.4 –11 –18 –16 –17 –152.5 –10 –17 –15 –16 –142.6 –10 –16 –14 –15 –14
2.7 –9 –15 –13 –14 –13
2.8 –8 –15 –13 –14 –122.9 –7 –14 –12 –13 –11
3 –7 –13 –11 –12 –113.1 –6 –12 –11 –12 –103.2 –5 –12 –10 –11 –9
3.3 –4 –11 –9 –10 –83.4 –4 –10 –9 –9 –8
Pressure Temperature (ºC)(bar(g)) R22 ISCEON®MO79 R502
Sat Liq Sat Vap. Ave. Coil
3.5 –3 –10 –8 –9 –7
3.6 –2 –9 –7 –8 –63.7 –2 –8 –7 –8 –6
3.8 –1 –8 –6 –7 –53.9 0 –7 –5 –6 –4
4 0 –7 –5 –6 –44.2 1 –5 –4 –5 –34.4 3 –4 –3 –3 –1
4.6 4 –3 –1 –2 0
4.8 5 –2 0 –1 15 6 –1 1 0 2
5.2 7 0 2 1 3
5.4 8 1 3 2 4
5.6 9 2 4 3 55.8 10 3 5 4 6
6 11 4 6 5 76.2 12 5 6 6 86.4 13 6 7 7 9
6.6 14 7 8 7 106.8 15 7 9 8 11
7 15 8 10 9 127.2 16 9 11 10 137.4 17 10 12 11 13
7.6 18 11 12 12 14
7.8 19 12 13 12 158 20 12 14 13 16
8.2 20 13 15 14 17
8.4 21 14 15 15 18
8.6 22 15 16 15 188.8 23 15 17 16 19
9 23 16 18 17 20
9.5 25 18 19 19 2210 27 19 21 20 23
10.5 29 21 23 22 2511 30 23 24 23 27
11.5 32 24 26 25 2812 33 26 27 26 30
12.5 35 27 28 28 31
13 36 29 30 29 3313.5 38 30 31 31 34
14 39 31 33 32 3614.5 40 33 34 33 37
15 42 34 35 34 38
15
Pressure Temperature (ºC)(bar(g)) R22 ISCEON®MO79 R502
Sat Liq Sat Vap. Ave. Coil
15.5 43 35 36 36 4016 44 36 37 37 41
16.5 46 37 39 38 4217 47 39 40 39 43
17.5 48 40 41 40 45
18 49 41 42 41 4618.5 50 42 43 43 47
19 51 43 44 44 4819.5 52 44 45 45 49
20 53 45 46 46 50
20.5 54 46 47 47 5121 56 47 48 48 52
21.5 57 48 49 49 53
22 58 49 50 50 5422.5 59 50 51 51 55
23 59 51 52 51 5623.5 60 52 53 52 57
24 61 53 54 53 5824.5 62 54 55 54 59
25 63 55 55 55 60
25.5 64 55 56 56 61
26 65 56 57 57 6226.5 66 57 58 58 63
27 67 58 59 58 6427.5 68 59 60 59 64
28 68 60 60 60 6528.5 69 60 61 61 66
29 70 61 62 61 67
29.5 71 62 63 62 6830 72 63 63 63 68
30.5 72 63 64 64 6931 73 64 65 64 70
31.5 74 65 65 65 7132 75 66 66 66 72
32.5 75 67 67 67 72
33 76 73
33.5 77 7434 78 74
34.5 78 75
Note: Saturated Liquid Temperature = Bubble Point
Saturated Vapor Temperature = Dew Point
16
Table 6
Pressure – Temperature Charts (SI Units): Suva®HP80 (R402A) and ISCEON®
MO79
Pressure Temperature (ºC)bar (g) ISCEON®ISCEON®ISCEON®Suva® Suva® Suva®
MO79 MO79 MO79 HP80 HP80 HP80Sat.Liq. Sat.Vap. Ave.Coil Sat.Liq. Sat. Vap. Ave.Coil
–0.7 –69 –66 –67 –72 –69 –70–0.6 –64 –61 –63 –67 –64 –66–0.5 –60 –57 –59 –63 –61 –62–0.4 –57 –54 –55 –59 –57 –58–0.3 –54 –51 –53 –56 –54 –55
–0.2 –51 –49 –50 –54 –52 –53–0.1 –49 –46 –48 –51 –49 –50
0 –47 –44 –46 –49 –47 –480.1 –45 –42 –44 –47 –45 –460.2 –43 –41 –42 –45 –43 –44
0.3 –41 –39 –40 –44 –42 –430.4 –40 –37 –38 –42 –40 –410.5 –38 –36 –37 –40 –39 –390.6 –37 –34 –35 –39 –37 –380.7 –35 –33 –34 –37 –36 –37
0.8 –34 –32 –33 –36 –34 –350.9 –33 –30 –31 –35 –33 –341 –31 –29 –30 –34 –32 –33
1.1 –30 –28 –29 –32 –31 –311.2 –29 –27 –28 –31 –30 –30
1.3 –28 –26 –27 –30 –28 –291.4 –27 –25 –26 –29 –27 –281.5 –26 –24 –25 –28 –26 –271.6 –25 –23 –24 –27 –25 –261.7 –24 –22 –23 –26 –24 –25
1.8 –23 –21 –22 –25 –23 –241.9 –22 –20 –21 –24 –23 –232 –21 –19 –20 –23 –22 –22
2.1 –20 –18 –19 –22 –21 –222.2 –19 –17 –18 –21 –20 –21
2.3 –18 –17 –18 –21 –19 –202.4 –18 –16 –17 –20 –18 –192.5 –17 –15 –16 –19 –18 –182.6 –16 –14 –15 –18 –17 –172.7 –15 –13 –14 –17 –16 –17
2.8 –15 –13 –14 –17 –15 –162.9 –14 –12 –13 –16 –15 –153 –13 –11 –12 –15 –14 –15
3.1 –12 –11 –12 –15 –13 –143.2 –12 –10 –11 –14 –12 –13
3.3 –11 –9 –10 –13 –12 –123.4 –10 –9 –9 –12 –11 –123.5 –10 –8 –9 –12 –10 –113.6 –9 –7 –8 –11 –10 –103.7 –8 –7 –8 –11 –9 –10
3.8 –8 –6 –7 –10 –9 –93.9 –7 –5 –6 –9 –8 –94 –7 –5 –6 –9 –7 –8
4.2 –5 –4 –5 –7 –6 –74.4 –4 –3 –3 –6 –5 –6
Pressure Temperature (ºC)bar (g)
ISCEON®ISCEON®ISCEON® Suva® Suva® Suva®
MO79 MO79 MO79 HP80 HP80 HP80Sat.Liq. Sat.Vap. Ave.Coil Sat.Liq. Sat. Vap. Ave.Coil
4.6 –3 –1 –2 –5 –4 –54.8 –2 0 –1 –4 –3 –45 –1 1 0 3 –2 1
5.2 0 2 1 –2 –1 –25.4 1 3 2 –1 0 –1
5.6 2 4 3 0 1 15.8 3 5 4 1 2 26 4 6 5 2 3 3
6.2 5 6 6 3 4 46.4 6 7 7 4 5 5
6.6 7 8 7 5 6 66.8 7 9 8 6 7 77 8 10 9 6 8 7
7.2 9 11 10 7 8 87.4 10 12 11 8 9 9
7.6 11 12 12 9 10 107.8 12 13 12 10 11 118 12 14 13 11 12 12
8.2 13 15 14 11 12 128.4 14 15 15 12 13 13
8.6 15 16 15 13 14 148.8 15 17 16 14 15 159 16 18 17 14 15 15
9.5 18 19 19 16 17 1710 19 21 20 19 20 20
10.5 21 23 22 21 22 2111 23 24 23 22 23 23
11.5 24 26 25 24 25 2412 26 27 26 25 26 26
12.5 27 28 28 27 28 27
13 29 30 29 28 29 2913.5 30 31 31 30 30 3014 31 33 32 31 32 31
14.5 33 34 33 32 33 3315 34 35 34 33 34 34
15.5 35 36 36 35 35 3516 36 37 37 36 37 36
16.5 37 39 38 37 38 3717 39 40 39 38 39 38
17.5 40 41 40 39 40 40
18 41 42 41 40 41 4118.5 42 43 43 41 42 4219 43 44 44 42 43 43
19.5 44 45 45 43 44 4420 45 46 46 44 45 45
20.5 46 47 47 45 46 4621 47 48 48 46 47 47
21.5 48 49 49 47 48 4822 49 50 50 48 49 49
22.5 50 51 51 49 50 50
17
Pressure Temperature (ºC)bar (g)
ISCEON®ISCEON®ISCEON® Suva® Suva® Suva®
MO79 MO79 MO79 HP80 HP80 HP80Sat.Liq. Sat.Vap. Ave.Coil Sat.Liq. Sat. Vap. Ave.Coil
23 51 52 51 50 51 5123.5 52 53 52 51 52 5124 53 54 53 52 53 5224.5 54 55 54 53 54 5325 55 55 55 54 54 54
25.5 55 56 56 55 55 5526 56 57 57 56 56 56
26.5 57 58 58 56 57 5727 58 59 58 57 58 57
27.5 59 60 59 58 59 58
28 60 60 60 59 59 5928.5 60 61 61 60 60 6029 61 62 61 60 61 61
29.5 62 63 62 61 62 6130 63 63 63 62 62 62
30.5 63 64 64 63 63 6331 64 65 64 63 64 64
31.5 65 65 65 64 65 6432 66 66 66 65 65 65
32.5 67 67 67 66 66 66
Note: Saturated Liquid Temperature = Bubble PointSaturated Vapor Temperature = Dew Point
18
Table 7
Pressure – Temperature Charts (SI Units): Suva®408 (R408A) and ISCEON®
MO79
Pressure Temperature ( C)
bar (g)
ISCEON®ISCEON®ISCEON® Suva® Suva® Suva®
MO79 MO79 MO79 408A 408A 408A
Sat. Liq. Sat. Vap. Av. Coil Sat. Liq. Sat. Vap Av. Coil
–0.7 –69 –66 –67 –67 –67 –67–0.6 –64 –61 –63 –62 –62 –62–0.5 –60 –57 –59 –58 –58 –58–0.4 –57 –54 –55 –55 –54 –55–0.3 –54 –51 –53 –52 –51 –52
–0.2 –51 –49 –50 –49 –49 –49–0.1 –49 –46 –48 –47 –46 –47
0 –47 –44 –46 –45 –44 –440.1 –45 –42 –44 –43 –42 –420.2 –43 –41 –42 –41 –40 –40
0.3 –41 –39 –40 –39 –38 –390.4 –40 –37 –38 –37 –37 –370.5 –38 –36 –37 –36 –35 –350.6 –37 –34 –35 –34 –34 –340.7 –35 –33 –34 –33 –32 –32
0.8 –34 –32 –33 –31 –31 –310.9 –33 –30 –31 –30 –30 –301 –31 –29 –30 –29 –28 –29
1.1 –30 –28 –29 –28 –27 –271.2 –29 –27 –28 –26 –26 –26
1.3 –28 –26 –27 –25 –25 –251.4 –27 –25 –26 –24 –24 –241.5 –26 –24 –25 –23 –23 –231.6 –25 –23 –24 –22 –22 –221.7 –24 –22 –23 –21 –21 –21
1.8 –23 –21 –22 –20 –20 –201.9 –22 –20 –21 –19 –19 –192 –21 –19 –20 –18 –18 –18
2.1 –20 –18 –19 –17 –17 –172.2 –19 –17 –18 –16 –16 –16
2.3 –18 –17 –18 –16 –15 –152.4 –18 –16 –17 –15 –14 –152.5 –17 –15 –16 –14 –14 –142.6 –16 –14 –15 –13 –13 –132.7 –15 –13 –14 –12 –12 –12
2.8 –15 –13 –14 –12 –11 –112.9 –14 –12 –13 –11 –11 –113 –13 –11 –12 –10 –10 –10
3.1 –12 –11 –12 –9 –9 –93.2 –12 –10 –11 –9 –8 –9
3.3 –11 –9 –10 –8 –8 –83.4 –10 –9 –9 –7 –7 –73.5 –10 –8 –9 –7 –6 –73.6 –9 –7 –8 –6 –6 –63.7 –8 –7 –8 –5 –5 –5
3.8 –8 –6 –7 –5 –4 –53.9 –7 –5 –6 –4 –4 –44 –7 –5 –6 –4 –3 –3
4.2 –5 –4 –5 –2 –2 –2
Pressure Temperature ( C)
bar (g)ISCEON®ISCEON®ISCEON® Suva® Suva® Suva®
MO79 MO79 MO79 408A 408A 408ASat. Liq. Sat. Vap. Av. Coil Sat. Liq. Sat. Vap Av. Coil
4.4 –4 –3 –3 –1 –1 –1
4.6 –3 –1 –2 0 0 04.8 –2 0 –1 1 2 25 –1 1 0 2 3 3
5.2 0 2 1 3 4 45.4 1 3 2 4 5 5
5.6 2 4 3 5 6 65.8 3 5 4 6 7 76 4 6 5 7 8 8
6.2 5 6 6 8 9 96.4 6 7 7 9 9 9
6.6 7 8 7 10 10 106.8 7 9 8 11 11 117 8 10 9 12 12 12
7.2 9 11 10 13 13 137.4 10 12 11 14 14 14
7.6 11 12 12 14 15 157.8 12 13 12 15 15 158 12 14 13 16 16 16
8.2 13 15 14 17 17 178.4 14 15 15 18 18 18
8.6 15 16 15 18 18 188.8 15 17 16 19 19 199 16 18 17 20 20 20
9.5 18 19 19 22 22 2210 19 21 20 23 24 23
10.5 21 23 22 25 25 2511 23 24 23 27 27 27
11.5 24 26 25 28 28 2812 26 27 26 30 30 30
12.5 27 28 28 31 31 31
13 29 30 29 33 33 3313.5 30 31 31 34 34 3414 31 33 32 35 36 35
14.5 33 34 33 37 37 3715 34 35 34 38 38 38
15.5 35 36 36 39 39 3916 36 37 37 40 41 41
16.5 37 39 38 42 42 4217 39 40 39 43 43 43
17.5 40 41 40 44 44 44
18 41 42 41 45 45 4518.5 42 43 43 46 47 4619 43 44 44 47 48 48
19.5 44 45 45 49 49 4920 45 46 46 50 50 50
20.5 46 47 47 51 51 5121 47 48 48 52 52 52
19
Pressure Temperature ( C)
bar (g)ISCEON®ISCEON®ISCEON® Suva® Suva® Suva®
MO79 MO79 MO79 408A 408A 408ASat. Liq. Sat. Vap. Av. Coil Sat. Liq. Sat. Vap Av. Coil
21.5 48 49 49 53 53 5322 49 50 50 54 54 54
22.5 50 51 51 55 55 55
23 51 52 51 56 56 5623.5 52 53 52 56 57 5724 53 54 53 57 58 58
24.5 54 55 54 58 59 5825 55 55 55 59 59 59
25.5 55 56 56 60 60 6026 56 57 57 61 61 61
26.5 57 58 58 62 62 6227 58 59 58 63 63 63
27.5 59 60 59 64 64 64
28 60 60 60 64 65 6428.5 60 61 61 65 65 6529 61 62 61 66 66 66
29.5 62 63 62 67 67 6730 63 63 63 68 68 68
30.5 63 64 64 68 68 6831 64 65 64 69 69 69
31.5 65 65 65 70 70 7032 66 66 66 71 71 71
32.5 67 67 67 71 71 71
33 72 72 7233.5 73 73 7334 73 74 74
Note: Saturated Liquid Temperature = Bubble PointSaturated Vapor Temperature = Dew Point
20
For more information and to find the location of
your nearest DuPont ISCEON® refrigerants
supplier please contact: www.isceon.com/uk
Europe, Middle East, Africa Regional OfficeDu Pont de Nemours International S.A.2 Chemin du PavillonP.O. Box 50CH-1218 Le Grand-SaconnexGeneva, SwitzerlandPhone: (+41) 22 717 5111Fax: (+41) 22 717 6169
Czech RepublicDu Pont CZ s.r.o.Pekarska 628/14155 00 Praha 5 JinonicePhone: (+420) 257 414 111Fax: (+420) 257 414 150
GermanyDu Pont de Nemours (Deutschland) GmbHHugenottenallee 173-175D- 63263 Neu-IsenburgPhone: (+49) 6102 18 1312Fax: (+49) 6012 18 1318
HungaryDu Pont Hungary Ltd.Neumann Janos street nr.l.II. floorH-2040 BudaorsPhone: (+36) 23 509 400Fax: (+36) 23 509 432
PolandDu Pont Poland Sp z.o.o.UI Powzakowska 44cPL-01-797 WarszawaPhone: (+48) 22 320 0900Fax: (+48) 22 320 0901
RussiaDu Pont Russia LLCUl. Krylatskaya, 17/3121614 MoscowPhone: +7 (495) 797 22 00/06Fax: +7 (495) 797 22 01
SpainDu Pont Iberica SAAv. Diagonal 56108029 BarcelonaPhone: (+34) 93 227 6171Fax: (+34) 93 227 6215
TurkeyDu Pont Products SABuyukdere Caddesi, Ozsezen Is MerkeziNo: 122, Kat: 1-3Esentepe 80280IstanbulPhone: (+90) 212 340 0 400Fax: (+90) 212 340 0 4
UkraineDu Pont de Nemours International S.A.Representative office – UkraineBusiness center “Podil Plaza“30/A, Spaska St. – Kyiv, 04070Phone: (+38) 044 495 26 70Fax: (+38) 044 495 26 71
United KingdomDu Pont (UK) LimitedWedgwood WayStevenageHertfordshire. SG1 4QNPhone: (+44) 438 734000Fax: (+44) 1438 734065
21
Reorder N°: K-10921 (MO79-EU) Revised 11/08Printed in Switzerland
This information corresponds to our current knowledge on the subject. It is offered solely to providepossible suggestions for your own experimentations. It is not intended, however, to substitute for anytesting you may need to conduct to determine for yourself the suitability of our products for your particularpurposes. This information may be subject to revision as new knowledge and experience becomesavailable. Since we cannot anticipate all variations in actual end-use conditions, DuPont makes nowarranties and assumes no liability in connection with any use of this information. Nothing in this publicationis to be considered as a license to operate under or a recommendation to infringe any patent right.The DuPont Oval, DuPont™, The miracles of science™, ISCEON® are registered trademarks or trademarksof DuPont or its affiliates