Residential Gas – Honeywell Valve - Thermopile Powered
Series 300/301
![Page 2: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301](https://reader036.vdocuments.us/reader036/viewer/2022062618/5513fb12550346dd488b461e/html5/thumbnails/2.jpg)
Atmospheric Vented
Category IStatus LED
Wrap-around Filter
![Page 3: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301](https://reader036.vdocuments.us/reader036/viewer/2022062618/5513fb12550346dd488b461e/html5/thumbnails/3.jpg)
• Introduction
• Installation
• Operation
• Service
![Page 4: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301](https://reader036.vdocuments.us/reader036/viewer/2022062618/5513fb12550346dd488b461e/html5/thumbnails/4.jpg)
Gas Valve/Thermostat
Spark Igniter Button
LED StatusLight
Status Codes
Thermopile
Powered
![Page 5: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301](https://reader036.vdocuments.us/reader036/viewer/2022062618/5513fb12550346dd488b461e/html5/thumbnails/5.jpg)
Gas Valve/Thermostat
Propane Gas Valve/Thermostat Color Coding
![Page 6: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301](https://reader036.vdocuments.us/reader036/viewer/2022062618/5513fb12550346dd488b461e/html5/thumbnails/6.jpg)
Installation
![Page 7: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301](https://reader036.vdocuments.us/reader036/viewer/2022062618/5513fb12550346dd488b461e/html5/thumbnails/7.jpg)
Installation – Gas Supply
Gas Maximum Supply Press.
Manifold Gas Press.
Natural 10.5 In WC 5.0 In WC
Propane 13.0 In WC 10.0 In WC
![Page 8: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301](https://reader036.vdocuments.us/reader036/viewer/2022062618/5513fb12550346dd488b461e/html5/thumbnails/8.jpg)
Installation - Piping
![Page 9: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301](https://reader036.vdocuments.us/reader036/viewer/2022062618/5513fb12550346dd488b461e/html5/thumbnails/9.jpg)
Installation – Combustion Air
• 12.5 Cubic Feet of Air Per 1000 Btu
1,000BTU1,000BTU +
10 CU.FT.
COMB.AIR
10 CU.FT.
COMB.AIR
2.5 CU.FT.
EXCESSAIR
2.5 CU.FT.
EXCESSAIR
![Page 10: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301](https://reader036.vdocuments.us/reader036/viewer/2022062618/5513fb12550346dd488b461e/html5/thumbnails/10.jpg)
• Operation
![Page 11: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301](https://reader036.vdocuments.us/reader036/viewer/2022062618/5513fb12550346dd488b461e/html5/thumbnails/11.jpg)
Operation - Thermopile Powered
A grouping of thermocouples into one housing results in a “Thermopile” or “Generator”
• Heat on the thermopile, generates 750 to 850 milli- volts (.750VDC) – open circuit.
• When heated and connected to the gas valve, ours generates 350 or more mV - closed circuit.
![Page 12: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301](https://reader036.vdocuments.us/reader036/viewer/2022062618/5513fb12550346dd488b461e/html5/thumbnails/12.jpg)
Operation - Lighting the Pilot
Note This Comment
![Page 13: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301](https://reader036.vdocuments.us/reader036/viewer/2022062618/5513fb12550346dd488b461e/html5/thumbnails/13.jpg)
Note this
comment
Operation – Lighting the Pilot
The pilot cannot be relit if this steady LED light is still ON. The thermopile must cool to automatically reset the control.
![Page 14: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301](https://reader036.vdocuments.us/reader036/viewer/2022062618/5513fb12550346dd488b461e/html5/thumbnails/14.jpg)
Operation – Lighting the Pilot
• Status Indicator– Blinking once every 3 seconds = pilot knob
may be released and normal operation in HEAT mode.
– Solid On – control has been turned Off – thermopile cooling
– 2 to 8 flashes every 3 seconds – error codes
![Page 15: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301](https://reader036.vdocuments.us/reader036/viewer/2022062618/5513fb12550346dd488b461e/html5/thumbnails/15.jpg)
Operation - Temperature Adjustment
Dial Approx. Temp ° F
VAC 55
HOT 120
VERY HOT
155
120°F is the recommended setting
![Page 16: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301](https://reader036.vdocuments.us/reader036/viewer/2022062618/5513fb12550346dd488b461e/html5/thumbnails/16.jpg)
Review Questions
1. Natural Gas – maximum gas supply pressure?
10.5 Inches WC
![Page 17: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301](https://reader036.vdocuments.us/reader036/viewer/2022062618/5513fb12550346dd488b461e/html5/thumbnails/17.jpg)
Review Questions
2. Since these products get combustion air directly from outdoors, indoor air supply does not matter?
They do NOT use air directly from outdoors. They use room air for combustion and therefore room air quality and quantity is very important.
![Page 18: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301](https://reader036.vdocuments.us/reader036/viewer/2022062618/5513fb12550346dd488b461e/html5/thumbnails/18.jpg)
Review Questions
3. Thermopile – This is a misspelling of thermocouple?
No – a thermopile is like a grouping of thermocouples into one housing. This results in a much stronger DC milli-voltage output from the heated end of the thermopile to the gas valve.
![Page 19: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301](https://reader036.vdocuments.us/reader036/viewer/2022062618/5513fb12550346dd488b461e/html5/thumbnails/19.jpg)
Review Questions
4.Thermopiles receive electrical power from a transformer?
No – pilot heat on the end of the thermopile generates electricity – millivolts. A maximum of 750 MV Vs a thermocouple which normally has a maximum output of 30MV.
![Page 20: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301](https://reader036.vdocuments.us/reader036/viewer/2022062618/5513fb12550346dd488b461e/html5/thumbnails/20.jpg)
Review Questions
5. Millivolts are AC or DC?
Direct Current
![Page 21: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301](https://reader036.vdocuments.us/reader036/viewer/2022062618/5513fb12550346dd488b461e/html5/thumbnails/21.jpg)
Review Questions
6. When I see the pilot light through the sight glass, I can release the pilot knob?No, you must wait for the LED to flash indicating the milli-voltage from the thermopile circuit has reached an adequate level to power the gas valve/thermostat control functions.
![Page 22: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301](https://reader036.vdocuments.us/reader036/viewer/2022062618/5513fb12550346dd488b461e/html5/thumbnails/22.jpg)
Service
![Page 23: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301](https://reader036.vdocuments.us/reader036/viewer/2022062618/5513fb12550346dd488b461e/html5/thumbnails/23.jpg)
Service - Combustion Chamber
![Page 24: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301](https://reader036.vdocuments.us/reader036/viewer/2022062618/5513fb12550346dd488b461e/html5/thumbnails/24.jpg)
Service - Burner Assembly
![Page 25: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301](https://reader036.vdocuments.us/reader036/viewer/2022062618/5513fb12550346dd488b461e/html5/thumbnails/25.jpg)
Service - Supply Gas Pressure Test
Burner Off – Static Pressure
9.85 In W.C.
Burner On – Dynamic Pressure
8.90 In W.C.
(Natural Gas)
![Page 26: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301](https://reader036.vdocuments.us/reader036/viewer/2022062618/5513fb12550346dd488b461e/html5/thumbnails/26.jpg)
Service – Manifold Gas Pressure
See Gas Valve Label Or Model and Rating Plate For Proper
Reading
Pressure Test Fittings
![Page 27: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301](https://reader036.vdocuments.us/reader036/viewer/2022062618/5513fb12550346dd488b461e/html5/thumbnails/27.jpg)
Service - LED Diagnostic Codes
If you have to reset the thermal switch (TCO), always check for flammable vapors or clean the filter and flame trap before
relighting.
![Page 28: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301](https://reader036.vdocuments.us/reader036/viewer/2022062618/5513fb12550346dd488b461e/html5/thumbnails/28.jpg)
Service
![Page 29: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301](https://reader036.vdocuments.us/reader036/viewer/2022062618/5513fb12550346dd488b461e/html5/thumbnails/29.jpg)
Service – Connections Check
Igniter Wire
From Thermopi
le(White)
From Thermal Switch (Red)
Manifold Press. Tap
Igniter Button
![Page 30: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301](https://reader036.vdocuments.us/reader036/viewer/2022062618/5513fb12550346dd488b461e/html5/thumbnails/30.jpg)
Service - Wrap Around Air Filter
Wrap Around Air Filter Must Be Kept Clean
![Page 31: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301](https://reader036.vdocuments.us/reader036/viewer/2022062618/5513fb12550346dd488b461e/html5/thumbnails/31.jpg)
Service - Thermopile Powered
A grouping of thermocouples into one housing results in a “Thermopile” or “Generator”
• Heat on the thermopile, generates 750 to 850 milli- volts (.750VDC) – open circuit.
• When heated and connected to gas valve, ours generates 350 or more mV - closed circuit.
![Page 32: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301](https://reader036.vdocuments.us/reader036/viewer/2022062618/5513fb12550346dd488b461e/html5/thumbnails/32.jpg)
Disconnecting Thermopile
Disconnect wires from gas valve/thermostat
![Page 33: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301](https://reader036.vdocuments.us/reader036/viewer/2022062618/5513fb12550346dd488b461e/html5/thumbnails/33.jpg)
Service - Thermopile Check –Open Circuit
Knob held in to
sustain gas to pilot
Multimeter testing of
thermopile leads
Generating .797VDC or
797 millivolt
From thermopile
From thermal switch
![Page 34: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301](https://reader036.vdocuments.us/reader036/viewer/2022062618/5513fb12550346dd488b461e/html5/thumbnails/34.jpg)
Service - Thermopile Check –Closed Circuit
Generating .353VDC or 353.4 millivolt
Thermopile circuit
leads are connected
to gas valve
Pilot is lit
Multi-meter leads
inserted into
thermopile circuit
connections
![Page 35: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301](https://reader036.vdocuments.us/reader036/viewer/2022062618/5513fb12550346dd488b461e/html5/thumbnails/35.jpg)
Service - Thermopile Check –Closed Circuit
.658VDC or 658 mV- well in excess of
the minimum 350mV
Multi-meter test lead to
thermostat connection
(white) and 2nd lead to thermal
switch.
Pilot is lit
2nd closed circuit test method
Red – from
thermal
switch
![Page 36: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301](https://reader036.vdocuments.us/reader036/viewer/2022062618/5513fb12550346dd488b461e/html5/thumbnails/36.jpg)
Review Questions
9. I can not relight the pilot! Most likely reasons?
• Thermopile still hot – wait for LED to go out,
• open thermal switch (TCO),
• plugged filter,
• plugged flame-trap.
![Page 37: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301](https://reader036.vdocuments.us/reader036/viewer/2022062618/5513fb12550346dd488b461e/html5/thumbnails/37.jpg)
Review Questions
10. My multimeter says that the thermopile is generating nearly 30 milli-volts DC. Why won’t my pilot light.
30mv is a thermocouple reading value.
• Check multimeter setting,
• poor flame impingement on thermopile,
• faulty thermopile.
![Page 38: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301](https://reader036.vdocuments.us/reader036/viewer/2022062618/5513fb12550346dd488b461e/html5/thumbnails/38.jpg)
Review Questions
11. My shower time has decreased significantly. Why?
A 40 gallon model set at 140°F was removed and a 40 gallon model set at 120° was installed.
![Page 39: Residential Gas – Honeywell Valve - Thermopile Powered Series 300/301](https://reader036.vdocuments.us/reader036/viewer/2022062618/5513fb12550346dd488b461e/html5/thumbnails/39.jpg)
Atmospheric Vented, Residential Gas – Honeywell Valve -
Thermopile PoweredSeries 300/301