report on rcc
TRANSCRIPT
-
7/29/2019 report on rcc
1/46
43
Chapter 3
E X PE R IM E N T A L ST U D Y
3.1 I ntroduction
This chapter describes the design, construction and testing of two interior Corcon rib
beam-column subassemblages tested in the Francis Laboratory at The University of
Melbourne. The second test specimen is the Carbon Fibre Reinforced Polymer (CFRP)
repaired version of the damaged original specimen after the first test.
The first section of this chapter describes the design of prototype model structure and the
test specimen. Details of test specimen, the material properties used and the design
parameters used in designing of prototype structure are presented. The details of test set up
and instrumentation used in the test are presented and discussed.
The approximate dead and live loading of the prototype structure was represented by
adjusting the end reactions. The column axial loading was simulated by prestressing
column ends of the test specimen. The specimens were tested in the reaction frame, with
increasing ratios of quasi-static cyclic drift being applied.
Details of CFRP rectification work of the damaged original test specimen are presented in
section 3.7. The related CFRP design process and the additional instrumentation for the
second test are also presented.
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
2/46
44
3.2 Design
The planning of the experimental program was done considering configuration of the
existing reaction frame at Francis Laboratory at The University of Melbourne. This was
one of the criteria in planning the test procedure and configuration of the test specimen
due to limited funding available for modification or rebuilding a new test set up. This
reaction frame has been designed to investigate seismic performance of reinforced
concrete wide band beam frame interior and exterior connections (Abdouka, 2003; Stehle,
2002). As found in chapter 2, the existing reaction frame is more or less similar to the
reaction frames used by other researchers for testing beam-column subassemblages. Since
one of the main objective was to assess current Australian design practice and to provide
design guidelines for these beam-slab-column systems constructed with the Corcon form
work, it was decided that the first test specimen should be designed in accordance with
Australian code requirements (AS-1170.4, 1993; AS-3600, 2001). However, basic design
guidelines for rib slabs are not available in Australian code (AS-3600, 2001) and therefore,
main design assumptions and procedure were gathered from British and US codes (ACI-
318, 1999; BS-8110, 1995). The Corcon reinforced concrete rib beam section design was
done using Australian standards. Details of design adopted are presented in Appendix A.
A typical four-storey, six bay ordinary moment resisting framed building constructed with
Corcon system as shown in Figure 3-1, was considered as a prototype model structure for
the study. A mainframe spacing of 6.0 m in the transverse direction was assumed. A
column size used of 500 mm square and beams of 894 mm total depth and 2400 mm wide
flange slab were adopted. These sizes are consistent with typical Corcon formwork
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
3/46
45
dimensions. As shown in Figure 3-2, a one way spanning 170 mm thick solid slab was
used between the main flange beams. A half scale of this prototype was used in testing.
The building was designed as an Ordinary Moment Resisting Frame (OMRF), according
to current Australian codes (AS-1170.0, 2002; AS-1170.1, 2002; AS-1170.2, 2002; AS-
1170.4, 1993; AS-3600, 2001), which makes no special detailing requirements mandatory
for these type of frames.
The main frame shown in Figure 3-1 is designed to resist wind and earthquake lateral
loading, while in the transverse direction, lateral loading was assumed to resist by
symmetrically placed shear walls or a perimeter frame. As the prototype structure
considered is symmetrical and no torsional effects. Therefore inelastic analysis can be
limited to simplified two-dimensional analysis.
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
4/46
46
Interior subassemblage
8.4 m 9.6 m9.6 m 8.4 m9.6 m 9.6 m
4.2 m
3.4 m
3.4 m
3.4 m
Transverse mainframe spacing 6.0 m
Beams: 2400 mm wide flange, 894 mm deep rib beam
Columns: 500 mm square
Slab: 170 mm one way spanning solid slab between main beams.
Figure 3-1: Prototype frame dimensions.
2.4 m
6.0 m
894 mm
170 mm
Figure 3-2:Di mensions of mainf rame beam section
In order to determine various loading factors, it was assumed that the frame was a office
building (for imposed live load consideration) situated on a rock site in Newcastle,
Australia. It should be noted that Newcastle has the highest peak ground acceleration
coefficient. Wind and earthquake loading parameters for selected cities are listed in Table
3-1. The design loading parameters adopted for the structure as situated in Newcastle, are
given in Table 3-2. The basic appropriate load combinations for the ultimate limit states
used in checking strength of the prototype frame, as specified in Australian code (AS-
1170.0, 2002), are given in Equation 3-1.
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
5/46
47
QEGe
WGd
QWGc
QGb
Ga
u
u
u
4.00.1)
9.0)
4.02.1)
5.12.1)
35.1)
Equation 3-1
T able 3-1:Acceleration coefficient for major cities in Australia
City U ltimate wind velocity(m/sec)
Peak ground accelerationcoefficient (g)
Melbourne
SydneyAdelaide
Brisbane
Perth
Hobart
Canberra
Newcastle
Alice Spring
Darwin
50
5050
60
50
50
50
50
50
70
0.08
0.080.10
0.06
0.09
0.05
0.08
0.11
0.09
0.08
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
6/46
48
T able 3-2:Design values adopted
Design parameter V alue
Gravity
Superimposed dead load
Live load
Ultimate wind velocity
Region
Terrain category
Topographic multiplier
Shielding multiplier
Importance multiplier (for wind)
Earthquake acceleration coefficient
Site factor
Structural response modification factor
Importance factor (for earthquakes)
9.81 m/s2
1.5 kPa
4.0 kPa
50 m/s
A
2
1.0
1.0
1.0
0.11g
1.0
4.0
1.0
Prototype frame loading was evaluated using actual member self-weights, based on the
sectional dimensions. Earthquake and wind loading was calculated based on the
parameters given in Table 3-2. A limit state design was employed, considering the entire
load combinations specified in Equation 3-1. A structural modification factor of 4.0 was
used, representing a frame of limited ductility. A fundamental period of 0.31 s was
calculated using the Australian code (AS-1170.4, 1993) specified formula (i.e. T=h/46).
As seen from Australian code method, the equivalent static earthquake load, mainly
depends on the accuracy of the fundamental period of the structure. As discussed in
chapter 2, there are different formulae presented in different codes and textbooks. In
general, use of code specified methods to calculate the earthquake force is more
conservative than the calculations based on inelastic dynamic analysis methods. Code
requirements, however, prevent the earthquake force being reduced below 80 % of that
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
7/46
49
determined using the codes formula (AS-1170.4, 1993) for fundamental period. The
calculation of equivalent earthquake force in Australian code is similar to the method used
in UBC (1997). Details of earthquake and wind load calculations are presented in
Appendix A.
The frame was found to have higher earthquake loading than wind loading. It was found
that ultimate gravity load combination governed the design of most members except
columns, for which the ultimate earthquake load combination governed. It should be noted
that the area of reinforcement required for the negative bending moments at supports were
calculated ignoring the area of slab reinforcement. The structure was also designed the
capacity design method to prevent the formation of column sideway mechanism (i.e. beam
hinges were designed to form before the formation of column hinges).
3.3 T est Specimen
The two-dimensional prototype frame analysis revealed that the first interior beam-column
joint in the first floor as shown in Figure 3-1, is more critical in terms of magnitude of the
out of balance moment applied to the joint. Therefore, it was selected to be tested in this
investigation.
3.3.1 Scale
In terms of test subassemblage dimensions, half scale testing was chosen, as this was the
maximum possible scale that could be tested in the reaction frame available, which was
used by Stehle (2002) and Abdouka (2003) for testing of wide band beam-column joints.
There was no adjustment of reinforcement bar spacing of the prototype and the test
specimen as per the Code (AS-3600, 2001) requirements. Table 3-3 shows the
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
8/46
50
reinforcement detailing used in the test specimen. The nominal aggregate size was scaled
down from 20 to 10 mm and the cover provided to reinforcement in beam and column was
scaled down to half. The scaling factors for the respective actions and dimensions are
presented in Table 3-4. It should be noted that a 2:1 scale factor is required for material
density since gravitational acceleration cannot be scaled. This effect was tackled by
including extra weight in the applied dead loading.
T able 3-3: R einforcement details of beam and column (T est specimen)
T est subassembly
Rib beam Top reinforcement over the supportRib beam Bottom reinforcement
Rib beam flange slab reinforcement
Rib beam shear ligatures
2Y201Y20
F 72 (Mesh)
R6-200 Crs
Column main reinforcement
Column shear links
12Y16
R6-175 Crs
Table 3-4: Consistent Scaling relationship -After (Stehle, 2002)
DimensionScale factor
(Modal : Prototype)
Stress, pressure 1:1
Length, displacement 1:2
Area, bar area 1:4
Volume 1:8
Force, shear 1:4
Moment, Torsion 1:8
Density 2:1
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
9/46
51
3.3.2 Specimen details
An isolated half-scale Corcon interior beam-slab-column subassembly, taken from the
prototype model frame structure is shown in Figure 3-3. The test specimen represents a
half scale model of prototype. It was terminated at column mid height and beam mid span,
representing approximate locations of points of contraflexure under lateral loading of the
prototype. The height of column is 1900 mm and the beam length is 4800 mm. The width
of the rib beam is 1200 mm, which is the typical rib beam width of Corcon slab system.
The reinforcement details of rib beam and column are shown in Figure 3-4. Shear ligatures
were provided to entire length of beam at uniform spacing, except in the beam-column
joint area. Similarly, column ligatures were provided to full height except within beam
depth. Figure 3-5 illustrates the reinforcement provided in the flange slab. It should be
noted that main top reinforcement has been curtailed 1000 mm from column centre. This
curtailment point was taken as per the critical bending moment envelope corresponding to
the gravity load case (i.e. 1.25G+1.5Q).
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
10/46
52
1900 mm
1200 mm
4800 mm
447 mm
50 mm thick steel plates.
Figure 3-3: Dimensions of test sub-assemblage.
Figure 3-4: Beam and column cross-section of test subassembly
M ain Top R/FF72 M esh
Figure 3-5: T op view of flange slab wi th r einforcement.
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
11/46
53
3.3.3 M aterial properties
The nominal strength and the measured strength of reinforcement bars used in the test
specimen are given in Table 3-5. Two types of high strength twisted/ribbed reinforcement
types were used, and defined in terms of strength. Those types are specified as: Y bars
and T bars. Y bars have nominal yield strength of 400 MPa and T bars have a
nominal strength of 500 MPa. These reinforcements were used in rib beam and column as
main bars. Other type of reinforcement, specified as R round bars, has a nominal strength
of 250 MPa, used in beam and column, as shear ligatures.
Nominal concrete compression cylinder strengths at 28 days of 40 MPa and 32 MPa were
used for the design of column and rib beam respectively. The measured cylinder
compressive strengths at the time of testing subassemblage are presented in Table 3-6.
T able 3-5: Reinforcement properties
Bar T ype Y 16 Y 20 T 7 R 6
Nominal bar diameter (mm)
Area (mm2)
Nominal yield stress (MPa)
Actual yield stress (MPa)
Actual ultimate stress (MPa)
16
201
400
442
542
20
314
400
448
539
6.75
35
500
510
684
6
28
250
345
502
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
12/46
54
T able 3-6: Uniaxial compr essive str ength of concr ete.
M ember T arget 28 day compr essivestr ength (M Pa)
M easured str ength at thetime of testing (M Pa)1
Rib Beam 32 40.6
Column 40 47.4
3.4 T est configuration
3.4.1 Specimen loading
According to the load combinations given in AS 1170.0 (2002), the gravity loading to be
taken at ultimate limit state, in an event of earthquake is assumed to be 100% dead load
and 40% of live load on the structure (1.0G+0.4Q). The performance of the test specimen
under lateral loading has to be investigated with the scaled portion of gravity loading on
the model, so that conditions present during testing are same as prototype structure.
Since the purpose of the test is to investigate the performance of the specimen during an
earthquake event, only the earthquake load combination was simulated on the test
specimen during testing. Bending moments, shear forces and axial loads in beam and
column are shown in Figure 3-6 to Figure 3-8 for the prototype structure and from Figure
3-9 to Figure 3-11 for half scale test specimen. These diagrams were obtained from a 2-
dimensional analysis conducted using Program Space Gass. The results of the analysis
are presented in Appendix B. Axial force diagram for beam and bending moment and
shear force diagram for the column are not shown since very small values were obtained.
1Concrete strength measured following day of testing. Testing was done one month after casting of beam
and 45 days after casting of upper column.
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
13/46
55
A similar set of diagrams was presented from Figure 3-12 to Figure 3-19 for the static
earthquake loading applied according to AS 1170.4 (1993).
-500
-400
-300
-200
-100
0
100
200
300
-4.8 -4 -3.2 -2.4 -1.6 -0.8 0 0.8 1.6 2.4 3.2 4 4.8
Distance along span (m)
BendingMoment(kNm)
Figure 3-6: Bending moment diagram for beams - full scale gravity loading
-300
-200
-100
0
100
200
300
-4.8 -4 -3.2 -2.4 -1.6 -0.8 0 0.8 1.6 2.4 3.2 4 4.8
Distance along span (m)
Shearforce(kN)
Figure 3-7: Shear force diagram for beams - full scale gravity loading
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
14/46
56
-2.1
-1.8
-1.5
-1.2
-0.9
-0.6
-0.3
00.3
0.6
0.9
1.2
1.5
0 500 1000 1500 2000 2500
Axial force (kN)
Distancealongcolumn
height(m)
Figure 3-8: Axial force diagram for columns full scale gravity loading
-100
-80
-60
-40
-20
0
20
40
-2.4 -2 -1.6 -1.2 -0.8 -0.4 0 0.4 0.8 1.2 1.6 2 2.4
Distance along span (m)
BendingMoment(kNm)
Ms
Figure 3-9: Bending moment diagram for beams - half scale gravity loading
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
15/46
57
-100
-80
-60
-40
-20
0
20
40
60
80
100
-2.4 -2 -1.6 -1.2 -0.8 -0.4 0 0.4 0.8 1.2 1.6 2 2.4
Distance along span (m)
Shearforce(kN)
Figure 3-10: Shear force diagram for beams - half scale gravity loading
-1.05
-0.75
-0.45
-0.15
0.15
0.45
0.75
0 100 200 300 400 500 600
Axial force (kN)
Distancealongcolumnheight(m)
Figure 3-11: Axial force diagram for columns - half scale gravity loading
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
16/46
58
-250
-200
-150
-100
-50
0
50
100
150
200
250
-4.8 -4 -3.2 -2.4 -1.6 -0.8 0 0.8 1.6 2.4 3.2 4 4.8
Distance along span (m)
Bendingmoment
(kNm)
Figure 3-12: Bending moment diagram for beams - full scale earthquake loading
-2.1
-1.8
-1.5
-1.2
-0.9-0.6
-0.3
0
0.3
0.6
0.9
1.2
1.5
-300 -250 -200 -150 -100 -50 0 50 100 150 200 250 300
Bending moment (kNm)
Distancealongcolumnheight(m)
Figure 3-13: Bending moment diagram for columns -full scale earthquake loading
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
17/46
59
-75
-50
-25
0
25
50
75
-4.8 -4 -3.2 -2.4 -1.6 -0.8 0 0.8 1.6 2.4 3.2 4 4.8
Distance along span (m)
Shearforce(kN)
Figure 3-14: Shear force diagram for beams full scale earthquake loading
-2.1
-1.8
-1.5
-1.2
-0.9
-0.6
-0.3
0
0.3
0.6
0.9
1.2
1.5
50 60 70 80 90 100 110 120 130 140 150
Shear force (kN)
Distancealongcolumnheight(m)
Figure 3-15: Shear force diagram for columns -full scale earthquake loading
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
18/46
60
-100
-80
-60
-40
-20
0
20
40
60
80
100
-2.4 -2 -1.6 -1.2 -0.8 -0.4 0 0.4 0.8 1.2 1.6 2 2.4
Distance along span (m)
Bendingmoment
(kNm)
Figure 3-16: Bending moment diagram for beams - half scale earthquake loading
-1.05
-0.75
-0.45
-0.15
0.15
0.45
0.75
-100 -75 -50 -25 0 25 50 75 100
Bending moment (kNm)
Distancealon
gcolumnheight(m)
Figure 3-17: Bending moment diagram for columns - half scale earthquake loading
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
19/46
61
-50
-40
-30
-20
-10
0
10
20
30
40
50
-2.4 -2 -1.6 -1.2 -0.8 -0.4 0 0.4 0.8 1.2 1.6 2 2.4
Distance along span (m)
Shearforce(kN)
Figure 3-18: Shear force diagram for beams - half scale earthquake loading
-1.1
-0.8
-0.5
-0.2
0.1
0.4
0.7
0 10 20 30 40 50 60 70 80 90 100
Shear force (kN)
Distancealongcolumnheight(m)
Figure 3-19: Shear force diagram for columns - half scale earthquake loading
The lateral loading setup is shown in Figure 3-20. This setup demonstrates the boundary
conditions and the loading arrangement to simulate the prototype structure. It can be seen
from bending moment and shear force diagrams for lateral earthquake loading (Figures 3-
12 to 3-19) that mid span bending moment is zero and the shear force is constant along the
span. These bending and shear force diagrams were achieved by using pin connections at
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
20/46
62
ends of beams and column and providing lateral loading at bottom end of the column as
shown in Figure 3-20. In this setup, axial load developed in columns due to earthquake
loading is neglected, as it is small compared with gravity loading.
+ Loading- Loading
Figure 3-20: Setup for lateral loading
The dead and live load effects were approximately modelled by adjusting the beam-end
reactions as shown in Figure 3-21. In this arrangement two roller supports were allowed to
freely deflect under beam self-weight and a further down ward reaction was applied
through the each roller pin connection. The resulting bending moment and shear force
diagrams are shown in Figure 3-22 and Figure 3-23 respectively.
The axial loading on the column was simulated by using external prestressing. The
prestressing loading framework moved with the lateral displacement of the
subassemblage. Therefore, the applied axial load was able to be kept concentric regardless
of the lateral displacement of the specimen. The required axial load on the bottom column
was calculated as 490 kN. The adopted axial load diagram is shown in Figure 3-24. This
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
21/46
63
force was achievable with four 12.7 mm diameter-prestressing strands. The prestress force
was transferred to the column via transfer beams at the top and bottom level of the
column.
Free vertical deflection allowed
under self weight of the beam
before connected to pin roller.
RR R=15.3 kN, reaction force is
applied through pin roller
connection link.
Applied lateral load
Applied axial load
Figure 3-21: A dopted setup for lateral and gravity loading
-100
-80
-60
-40
-20
0
20
40
-2.4 -2 -1.6 -1.2 -0.8 -0.4 0 0.4 0.8 1.2 1.6 2 2.4
Distance along span (m)
BendingMoment(kNm)
Figure 3-22: Bending moment diagram for beams - Adopted half scale gravity loading
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
22/46
64
-50
-40
-30
-20
-10
0
10
20
30
40
50
-2.4 -2 -1.6 -1.2 -0.8 -0.4 0 0.4 0.8 1.2 1.6 2 2.4
Distance along span (m)
Shearforce(kN)
Figure 3-23: Shear force moment diagram for beams - Adopted half scale gravity loading
-1.05
-0.75
-0.45
-0.15
0.15
0.45
0.75
0 100 200 300 400 500 600
Axial force (kN)
Distancealon
gcolumnheight(m)
Figure 3-24: Axial force diagram for columns - Adopted half scale gravity loading
3.4.2 T est setup
The reaction frame has been designed to provide a pin connection to the top column end,
two roller supports which allow vertical deflection under the specimen self weight, a pin
connection at the bottom of the column to which the actuator was attached and a
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
23/46
65
prestressing system to apply the axial load to the column. This setup was originally
designed by Stehle (2002) and Abdouka (2003) for wide band beam testing. It was
modified to suit the specimen tested in this project.
The top and side view of the test setup are shown in Figure 3-25 and Figure 3-26
respectively. The bracings have been provided at top level and on two side faces of the test
rig to provide the lateral stiffness. The pin connection at the top of the column was
provided by using a mild steel pin that was inserted into a hole in the test rig. Once pinned,
the specimen was able to hung freely at the centre of the test rig. At the base of the
column, another mild steel pin was used to connect the actuator arm. The pins at the beam-
ends have been created using vertical links, which hang down from the test rig.
T op-level br acings
Side bracings
Column exter nalpr estressing strands
C ompound cannel at columntop and bottom to tr ansfer axial for ce.
Figure 3-25: T op view of the built t est assembly
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
24/46
66
Pin connections
Actuator
A ctuator hydraulic
controller
comput er based
data logging system
Fi gure 3-26: Side view of the built test assembly
All pin supports has been designed with 50 mm diameter mild steel pins through 52 mm
diameter holes. Hence, a pin slip at the connection was expected and the force-
displacement hysteresis results need to be adjusted. Other researchers using the same test
rig (Siah, 2001; Stehle, 2002) had encountered similar pin slip problems. The correction
procedure to take account of this slip is described later in chapter 4.
The two vertical link pin supports, one at each beam end were also supported by the
reaction frame. These vertical links allow free horizontal movement of the beam, but not
vertical movement. Beam end reactions were applied to simulate gravity loading on the
specimen so that the joint bending moment at the beginning of the test is consistent with
the prototype structure, as mentioned earlier in chapter 3.4.1. The reaction at the beam-
ends was provided by adjusting the length of the threaded bolt by screwing or unscrewing
it. A photo of the vertical link is shown in Figure 3-27. The amount of reaction applied
was measured by four strain gauges, which were installed around the circumference of the
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
25/46
67
threaded rod that connects the top and bottom parts of the vertical link. The calibration of
these strain gauges for each vertical link was done prior to the testing of the specimen and
shown in Figure 3-28 and Figure 3-29.
A djusting Thr eaded r od
50mm pin connections
Figure 3-27: Photo of beam-end vertical link
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
26/46
68
y = 0.2859x + 0.9694
R2
= 0.9999
-80
-60
-40
-20
0
20
40
60
80
-300 -200 -100 0 100 200 300
Average Microstrain
Force(kN)
Figure 3-28: Calibration of North vertical link
y = 0.2874x - 0.8555
R2 = 1
-80
-60
-40
-20
0
20
40
60
80
-300 -200 -100 0 100 200 300
Average Microstrain
Force(kN)
Figure 3-29: C alibr ation of South ver tical link
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
27/46
69
3.4.3 Constr uction of test specimen
The construction details of test specimen were presented in Figure 3-3 to Figure 3-5. The
construction sequence of test specimen followed here is slightly different to the
conventional construction sequence. The followed construction sequence was mainly
determined by the specimen installation procedure to test rig. The steps of construction
were as follows:
Cut and bend column and beam reinforcement as required.
Fabrication of column cage with tie wires.
End bearings plates were welded to top and bottom end of column cage.
Fixing of strain gauges and associated wiring.
Construct formwork around column cage from top bearing plate to beam top level.
Horizontally casting top column and curing.
Remove column formwork and lift column into position in test rig and bolt to transfer
beams.
Place the reinforcement mesh for slab with temporary supports.
Erect Corcon beam and slab sheet metal formwork and formwork for the lower part of
the column.
Place pre-sized and strain gauged beam bars in position with shear links. Figure 3-30
shows the top view of beam ready for next stage concreting.
Concreting lower column and beam.
Curing.
Remove formwork.
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
28/46
70
Upper column after
the completion of 1st
stage concreting
Figure 3-30: Specimen ready for concreting
3.5 I nstr umentation
Three types of instrumentations, i.e. Strain gauges, displacement transducers and load
cells, were used to monitor the behaviour of the specimen during the test. All the data
from the instruments were collected through a computer based data logging system.
3.5.1 Strain gauges
The strain gauges were attached to beam and column reinforcement. The strain gauges
used were Kyowa Type KFG-5-120-C1-11. The locations of strain gauges on beam and
column reinforcement are shown in Figure 3-31 and Figure 3-32 respectively.
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
29/46
71
BTG1 BTG2
BTG3 BTG4
Beam Top view
BBG1 BBG1
Beam Side view
2400 mm 2400 mm
Fi gure 3-31: L ocation of str ain gauges on beam r einforcement
South
North
SWC1
SEC2NWC3
NEC4
N ote : Only column CornerR/F is shown for clarity.
Fi gure 3-32: L ocation of str ain gauges on beam r einforcement
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
30/46
72
3.5.2 D isplacement tr ansducers
Displacement transducers were used to calculate the curvatures of the central portion of
the beam at the beam-column joint. The locations of these transducers are shown in Figure
3-33.
T1 T2
T3 T4
Fi gure 3-33: L ocations of displacement tr ansducers
3.5.3 L oad cells
Load cells were used to determine the load in each column-prestressing strand. Calibration
of the load cells was done before the setup, so that the correct load could be obtained. A
total of four load cells were used for strands. The inbuilt load cell in the actuator was used
to measure the lateral load applied at different displacements.
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
31/46
73
3.6 T esting sequence
As described in section 3.4.2, the reactions to simulate the gravity loading had to be
applied before the testing commenced. The sequence of the loading of the specimen was
as follows:
Apply column axial load of 400 kN using four prestressing stands.
Release the vertical link connection at the end of beam and allow beams to freely
deflect under its self-weight.
Reconnect the beam-ends to vertical links, such that no tension or compression
developed in the vertical links.
Apply a downward force of 15.3kN by turning the threaded bar of the vertical links.
This was done by setting the vertical link strain gauge reading to an equivalent micro-
strain value as per the calibration graphs shown in Figure 3-28 and Figure 3-29.
Finally connect the actuator arm to the bottom end of the column.
At this stage the specimen was ready for the application of cyclic loading. The specimen
cyclic loading sequence was based on specimen drift rather than the ductility index
because of the difficulty in predefining a yield displacement in beam-column
subassemblage. The lateral loading sequence used for the test is shown in Figure 3-34. It
consisted of repeated cyclic loading of increasing drift ratio up to the maximum stroke of
the actuator, which corresponds to a nominal drift of 4%. The test results and observations
are presented in chapter 4.
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
32/46
74
-5
-4
-3
-2
-1
01
2
3
4
5
0 1a 1b 2a 2b 3a 3b 4a 4b 5a 5b 6a 6b 7a 7b 8a 8b 9a 9b 10a
Drift Ratio (%)
Cycle No.
Figure 3-34: Lateral Cyclic loading sequence
3.7 2nd test specimen
3.7.1 General
The second test specimen was a retrofitted version of the damaged first specimen. It was
very clear from the test results and observations that test specimen was experiencing
reinforcement detailing problems. These observations are described in chapter 4. Having
identified the detailing problems in the first test, it was decided to repair the damaged
specimen using a Carbon Fibre Reinforced Polymer (CFRP) system, as a cost-effective
alternative. The repaired version of the specimen would then be re-tested to ascertain its
post-repair performance to loading taken to high drift limits and to observe any
improvements that may have resulted from the proposed repair process. Figure 3-35 shows
the adopted CFRP system.
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
33/46
75
Mortar build-upBolted steel plates
2-layers of CFRP
from A-DAn additional
layers of CFRP
from B-C
2-layers of CFRP
from E-F on each
face
Figure 3-35: Details of CFR P system used for rectification
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
34/46
76
3.7.2 Use of externally bonded FRP for structural repair work
For this repair work, externally bonded carbon fiber in fabric form (CFRP) was selected
after performing a parametric analytical study of the performance of two different types of
FRP systems. The relevant geometrical and mechanical properties of the material chosen,
provided by the supplier, are given in Table 3-7.
T able 3-7: G eometri cal and mechanical proper ties of fi bre
Fibre Type Carbon fibre Glass fibre
Reference CF130 EG-90/10A
W idth/T hickness 300 mm/0.176 mm 670 mm/0.154 mm
E-modulus 240,000 MPa 73,000 MPa
Ultimate tensile strain 1.55 % 4.5 %
T ensile str ength 3800 MPa 3400 MPa
Design tensile force 211 kN/m @ 0.6% strain/m width 264 kN/m @ ult. strain/m width
The moment curvature relation for the (rib beam section at column face) strengthening
system shown in Figure 3-35 was obtained from sectional analysis program Response-
2000 (Bentz and P.Collins, 2000). The positive and negative moment-curvature
relationship for Carbon, Glass fibre and the reinforcement used in the first test specimen
are shown in Figures 3-36 and 3-37 respectively.
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
35/46
77
0
25
50
75
100
125
150
175
200
225
0 25 50 75 100 125
Cu rvature (Rad/km )
M
oment(kNm)
+ve Moment-R/F
+ve Moment-
CF130(200 mm2)
+ve Moment-
Eglass(400 mm2)
Figure 3-36: Positive moment curvature wit h differ ent reinfor cing material s
0
25
50
75
100
125
150
175
200
225
0 25 50 75
C urvature (Rad/km)
M
oment(kNm)
-ve Moment -R/F
-Ve Moment-
CF130(450 mm2)-ve Moment-
Eglass(900 mm2)
Figure 3-37: N egative moment curvature with dif ferent r einfor cing materi als
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
36/46
78
The use of FRP as a means of flexural strengthening will compromise the ductility of the
original reinforcement system. Significant increases in moment capacity with FRP sheets
are afforded at the sake of ductility. However, sections that experience a significant loss in
ductility must be considered. The approach taken by (MBrace, 2002) follows the
philosophy Appendix B of ACI 318, where a section with low ductility must compensate
with a higher strength reserve. The higher reserve of strength is achieved by applying a
strength reduction factor of 0.70 to brittle sections as opposed to 0.90 for ductile sections.
Both concrete crushing and FRP rupture before yielding of the steel are considered as both
brittle failure modes. Steel yielding followed by concrete crushing provides some level of
ductility depending on how far the steel is strained over the yield strain. Steel yielding
followed by FRP rupture is typically ductile because the level of strain needed to rupture
FRP is significantly higher than the strain level needed to yield the steel.
The moment-curvature behaviour of Carbon and Glass fibre was compared with
reinforcement, as shown in Figure 3-36 and Figure 3-37, the Carbon fibre behaviour was
closely matching with reinforcement than that of Glass fibre. It should also be noted that
the area of carbon fibre required to give same moment capacity was approximately half
compared to the glass fibre. In addition the high strength, high modulus and negligible
creep rupture behaviour make carbon fibres ideal for flexural strengthening applications.
Therefore, the carbon fibre was selected for this repair work, as the overall cost of repair
would be drastically reduced due to the less material and labour involvement. Generally,
major portion of total cost is the labour cost, as the preparation and application of FRP
requires highly trained skilled workers.
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
37/46
79
3.7.3 Structural repair work
Since the composite element of an FRP repair system is required to be bonded onto the
concrete substrate, the efficiency of the system depends on the integrity of this bond at the
interface layer. A minimum tensile strength of 1.5 MPa is recommended for the substrate
for this type of CFRP design (MBrace, 2002). Any loose material in areas where the CFRP
system was to be applied was removed and patched with suitable mortars. All cracks
greater than 0.3 mm in width were repaired by epoxy injection. Figure 3-38 illustrates the
prepared specimen for epoxy injection. Wide cracks, similar to those shown in Figure
3-39, were repaired adopting pour techniques using low shrinkage structural grout.
Fi gure 3-38: Specimen before epoxy inj ection
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
38/46
80
Figure 3-39: Fill ing of w ide cracks with low shr ink age str uctural grout.
It was observed that an uneven surface was created near the large cracks, after repair, due
to geometric deformation. Care was taken to flatten these areas using suitable mortars.
Alternatively grinding to flatten out the surface can also prevent possible CFRP peel-off
failure due to unevenness of the substrate.
Other important considerations when applying a CFRP repair system to a damaged
structure, concerns detailing. Material-specific use restrictions for CFRP necessitate
avoidance of sharp corners in structural elements to which they may be applied. Such
corners need to be rounded to decrease the chance of fibre fracture due to stress
concentrations induced by sharp edges. In this specimen, the column and beam dimensions
are different, therefore in order to provide smooth transition for CFRP bottom layer over
the column width, an additional mortar build-up was created near the beam column joint.
In addition to the treatment near the column-beam joint described above, four mild steel
plates were placed over the FRP layer and bolted to the rib beam. The steel plates, as
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
39/46
81
shown in Figure 3-35 provided restraining (clamping) forces to prevent delamination of
the CFRP due to diverting forces created in the fibres from the mortar build-up.
Figure 3-40: M ortar build-up near the beam column joint
3.7.3.1 Surface preparat ion for FR P application
After completing all the structural repair work, the concrete surface needs to be prepared
to receive the FRP application. The concrete surface should be clean, sound and free of
surface moisture, any foreign matter such as dust, laitance, grease, curing compounds and
other bond inhibiting materials from the surface by blast cleaning or equivalent
mechanical means. The surface preparation was done using mechanical wire brush instead
of sand blasting.The general requirement is that the surface must present similar to 60-grit
sandpaper. Figure 3-41 shows the prepared surface at the bottom of the rib beam adjacent
to the beam column joint.
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
40/46
82
Prepared concrete
surface by removing
excess surface grout.
Figure 3-41: Prepared concrete surface to receive FRP application
3.7.3.2 CFR P application to prepared sur face
The first step in the FRP application process was the priming of the concrete surface with
the penetrating primer prior to the application of any subsequent coatings applied using a
roller. The primer was applied uniformly in sufficient quantity to fully penetrate the
concrete and produce a non-porous film in the surface approximately 100-150 microns in
thickness after full penetration. It must be noted that the volume to be applied may vary
depending on the porosity and roughness of the concrete surface.
The next step was to apply an epoxy resin on the primed surface and lay the FRP sheet.
According to the manufactures guidelines, the resin has to be applied to the primed surface
using a medium nap roller (approx. 10 mm) to approximately 500 - 750 microns wet film
thickness (1.3-2 m2
per litre) or sufficient to achieve a wet-out of the FRP Fabric Sheet.
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
41/46
83
This value will vary depending on the weight of the FRP Fabric Sheet as well as the
ambient conditions and wastage. The mixed batch resin has to be used before expiration of
its batch-life, as increased resin viscosity will prevent proper impregnation of the FRP
fabric materials. Figure 3-42 shows the application of epoxy resin over the primer layer.
Epoxy Resin application
Pr evious Pr imer layer
Figure 3-42: A pplication of E poxy r esin
FRP Fabric Sheets must be cut beforehand into required length using appropriate scissors.
The FRP Fabric Sheet was placed with the fibre side placed on the concrete surface and
work in the direction of the fibres and work from the centre of the length of the sheet to
the ends, to remove any entrapped air. The other subsequent layers of FRP were laid
similar to the first layer. Figure 3-43 shows the application of the first CFRP layer. It
should be noted that the application of resin has to be done before and after the laying of
each new FRP fabric layer. A hard roller was used to enhance the impregnation of the
fabric material. The backing polythene paper was then peeled away. The surface of
adhered fabric was squeezed in the longitudinal direction of the fibre using a ribbed roller
in order to impregnate resin into the fabric material and remove any air bubbles (see
Figure 3-44). Figure 3-45 depicts the completely repaired test specimen.
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
42/46
84
Figure 3-43: L aying CFR P on the Epoxy applied surface
Figure 3-44: A r ibbed roller used to impregnate r esin into the fabr ic material
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
43/46
85
Figure 3-45: CFRP repaired test specimen ready for test instrumentation
3.8 I nstr umentation for second test specimen
The instrumentation used for the second test was same as the first test. Additional strain
gauges were installed on the CFRP. The locations of strain gauges on beam top flange and
beam rib are shown in Figure 3-46. All the data from the instruments were collected
through a computer based data logging system similar to the first test.
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
44/46
86
N S
N S
CG1 CG2 CG3 CG4 CG5 CG6 CG7 CG8
CG13 CG14 CG15 CG16
CG9 CG10 CG11 CG12
CG17 CG18 CG19 CG20Beam west side strain gaugenumberingBeam east side strain gauge
numbering
Figure 3-46: Location of strain gauges on CFRP
3.8.1 Photogrammetr y-based measur ement
A photogrammetry-based measurement setup was used to follow the deformations in the
repaired specimen during the test. Approximately 200 highly reflective photosensitive
targets were introduced on one side of the concrete beam as well as on the CFRP surfaces.
Figure 3-47 shows the test specimen with photosensitive target points. Using a purpose-
specific camera, three-dimensional digital measurements were determined from these
target locations from a series of multiple photographs taken at different stages within the
loading cycles. These measurements enabled both global and local deformation of the test
specimen to be followed during the testing.
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
45/46
87
Fi gure 3-47: t est specimen wi th photosensitive tar get points
Created with novaPDF Printer (www.novaPDF.com)
http://www.novapdf.com/http://www.novapdf.com/ -
7/29/2019 report on rcc
46/46
Abdouka, K. (2003). The Seismic Performance of Reinforced Concrete Wide Band Beam
Frames: Exterior Connections. Melbourne, The University of Melbourne, Australia.
ACI-318 (1999). Building Code Requirements for Structural Concrete (ACI-318M-99)
and Commentary (ACI-318RM-99), American Concrete Institute, Farmington Hills, Mich.
AS-1170.0 (2002). Structural design actions, Part 0: General principals, Standard
Association of Australia, Sydney, Australia.
AS-1170.1 (2002). Structural design actions, Part 1: Permanent, Imposed and other
actions, Standard Association of Australia, Sydney, Australia.AS-1170.2 (2002). Structural design actions, Part 2: Wind loads, Standard Association of
Australia, Sydney, Australia.
AS-1170.4 (1993). Minimum Design Loads on Structures, Part 4: Earthquake loads,
Standard Association of Australia, Sydney, Australia.
AS-3600 (2001). Concrete Structures, Standard Association of Australia, Sydney,
Australia.
Bentz, E. C. and M. P.Collins (2000). RESPONSE-2000 Reinforced Concrete Sectional
Analysis Program Manual.BS-8110 (1995). Structural use of concrete, Part 1: Code of practice for design and
construction, British Standard Institute, London.MBrace (2002). Composite strengthening system,Engineering design guidelines, New
York., Watson Bowman Acme Corp.
Siah, W. L. (2001). Seismic Performance of Interior Post-Tensioned Concrete Wide
beams, The University of Melbourne, Australia.
Stehle, J. S. (2002). The Seismic Performance of Reinforced Concrete Wide Band Beam
Frames: Interior Connections, The University of Melbourne, Australia.