removable inspection cover general notesremovable inspection cover with cast-in-place handle...

2
1'- 0" GENERAL NOTES: FALL THROUGH THE HYDRO-KINETIC PLANT FROM INLET INVERT TO OUTLET INVERT IS FIVE INCHES. INLET INVERT IS TWELVE INCHES BELOW TANK TOP. ON DEEPER INSTALLATIONS, PRECAST RISERS MUST BE USED TO EXTEND CASTINGS TO GRADE. INSPECTION COVERS MUST BE DEVELOPED TO WITHIN TWELVE INCHES OF GRADE. TANK REINFORCED PER ACI STD. 318. REMOVABLE COVERS ON RISERS WEIGH IN EXCESS OF SEVENTY-FIVE POUNDS EACH TO PREVENT UNAUTHORIZED ACCESS. CONTACT THE LOCAL, LICENSED HYDRO-KINETIC DISTRIBUTOR FOR ELECTRICAL REQUIREMENTS. CRITICAL DIMENSIONS 1 A B C D E F H G I J K L M N O P Q R S U T V W X Y Z CONTRACTOR'S CERTIFICATION: I (WE) HEREBY CERTIFY THAT THIS DRAWING HAS BEEN CHECKED AND IS APPROVED FOR USE IN CONFORMITY WITH THE CONTRACT DOCUMENTS. DATE: NAME: PROJECT ENGINEER'S APPROVAL: I (WE) HEREBY CERTIFY THAT THIS DRAWING HAS BEEN CHECKED AND IS APPROVED FOR USE IN CONFORMITY WITH THE CONTRACT DOCUMENTS. DATE: NAME: U.S. AND FOREIGN PATENTS PENDING MMXV THIS DRAWING IS THE PROPERTY OF NORWALK WASTEWATER EQUIPMENT COMPANY AND MAY NOT BE COPIED OR REPRODUCED IN WHOLE OR IN PART WITHOUT WRITTEN PERMISSION FROM NORWECO. DRAWN BY APPROVED BY REVISION DATE DATE SCALE DRAWING NO. REVISION MT JMM 09-03-2015 NTS PC-5-1077 2 3 4 5 MODEL 600 FEU HYDRO-KINETIC WASTEWATER TREATMENT SYSTEM WITH EXTERNAL PRETREATMENT CHAMBER, UV DISINFECTION SYSTEM AND PUMP TANK 2'- 9" 2'- 8" 3'- 7" 2'- 3" 9'- 3" 1'- 0" 0'- 1" 1'- 1" 0'- 3" 0'- 3" 0'- 2" 0'- 3" 0'- 2 1/2" 1'- 4" 4'- 8" 6'- 0" 5'- 6" 1'- 5" 4'- 7" 3'- 7 1/2" A W C D E F Z J K L M N R S U REMOVABLE INSPECTION COVER WITH CAST-IN-PLACE HANDLE APPROVED SEALANT OR SEALING DEVICE X A A PLAN VIEW OUTLET END VIEW NOTE: TOTAL SYSTEM CAPACITY: 2,420 GALLONS RATED CAPACITY: 500/600 GALLONS PER DAY APPROVED SEALANT OR SEALING DEVICE ANOXIC CHAMBER RISER CASTING WITH LID MODEL A100 AIR PUMP AERATION CHAMBER RISER CASTING WITH VENTED LID NORWECO FRESH AIR VENT ASSEMBLY OREGON APPROVED 1000 GALLON SEPTIC TANK SUBMERGED TRANSFER PORT ANOXIC CHAMBER MIXING BAR DIFFUSER BAR AERATION CHAMBER SECTION A-A MEDIA CHAMBER CHAMBER TRANSFER PORT CAST-IN AERATION INFLUENT CHAMBER CLARIFICATION CHAMBER MODEL SD103 RECIRCULATION PUMP REACTOR ELEMENT HIGH WATER ALARM FLOAT CLARIFICATION CHAMBER RISER CASTING WITH LID FLOW EQUALIZATION DEVICE (SEE DETAIL) 4" DIAMETER TRANSFER PIPE (TYP) SOLVENT WELD CONNECTION ANOXIC CHAMBER REMOVABLE INSPECTION COVER WITH CAST-IN-PLACE HANDLE AERATION CHAMBER 4" DIAMETER EFFLUENT LINE HYDRO-KINETIC BIO-FILM REACTOR RISER CASTING WITH LID REMOVABLE INSPECTION COVER WITH CAST-IN-PLACE HANDLE OUTLET TEE GROUT OR SYNTHETIC SEAL OPTIONAL PRETREATMENT CHAMBER RISER CASTING WITH LID TRANSFER TEE NOTE: PRETREATMENT CHAMBER MINIMUM REQUIREMENTS SHALL BE: 1000 GALLONS CAPACITY, 7 GALLONS PER INCH OF LIQUID LEVEL AND 9 INCHES OF FREEBOARD V PRETREATMENT CHAMBER I H Y 1'- 1" GASKETED DISCHARGE FLANGE ASSEMBLY OUTLET COUPLING TO 4" DIAMETER EFFLUENT LINE FLOW EQUALIZATION DEVICE DETAIL CLARIFICATION CHAMBER B O P 60ー 60ー EFFLUENT PUMP SIMPLEX SUBMERSIBLE ACCESS COVER TO CONTROL PANEL ELECTRICAL CONDUIT ACCESS RISER OVERRIDE FLOAT ALARM FLOAT ON/OFF FLOAT NOTE: TYPICAL PUMP TANK SHOWN. ACTUAL CONFIGURATION MAY VARY. NOTE: SOME CRITICAL DIMENSIONS ARE INTENTIONALLY LEFT BLANK TO BE FILLED IN PER INDIVIDUAL JOB SITE SPECIFICATIONS. OREGON APPROVED PUMP TANK Q FORCE MAIN G T UV DISINFECTION SYSTEM NOTE: FAILSAFE CONTROLS WILL SHUT DOWN EFFLUENT PUMP IF THERE IS A MALFUNCTION IN THE AIR PUMP. FAILSAFE CONTROLS WILL ALARM AND NOTIFY THE SERVICE PROVIDER IN THE EVENT OF A MALFUNCTION. FAILSAFE CONTROLS WILL ALARM IF EFFLUENT LEVEL REACHES THE ALARM FLOAT. 11-24-2015 A

Upload: others

Post on 15-Jul-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: REMOVABLE INSPECTION COVER GENERAL NOTESremovable inspection cover with cast-in-place handle approved sealant or sealing device x a plan view outlet end view note: total system capacity:

1'- 0"

GENERAL NOTES:

FALL THROUGH THE HYDRO-KINETICPLANT FROM INLET INVERT TO OUTLETINVERT IS FIVE INCHES. INLET INVERT ISTWELVE INCHES BELOW TANK TOP.

ON DEEPER INSTALLATIONS, PRECASTRISERS MUST BE USED TO EXTENDCASTINGS TO GRADE. INSPECTIONCOVERS MUST BE DEVELOPED TOWITHIN TWELVE INCHES OF GRADE.

TANK REINFORCED PER ACI STD. 318.

REMOVABLE COVERS ON RISERS WEIGHIN EXCESS OF SEVENTY-FIVE POUNDSEACH TO PREVENT UNAUTHORIZEDACCESS.

CONTACT THE LOCAL, LICENSEDHYDRO-KINETIC DISTRIBUTOR FORELECTRICAL REQUIREMENTS.

CRITICAL DIMENSIONS

1

ABCDEF

HG

IJKLM

NOPQRS

UT

VWXYZ

CONTRACTOR'S CERTIFICATION:I (WE) HEREBY CERTIFY THAT THISDRAWING HAS BEEN CHECKED AND ISAPPROVED FOR USE IN CONFORMITYWITH THE CONTRACT DOCUMENTS.

DATE:

NAME:

PROJECT ENGINEER'S APPROVAL:I (WE) HEREBY CERTIFY THAT THISDRAWING HAS BEEN CHECKED AND ISAPPROVED FOR USE IN CONFORMITYWITH THE CONTRACT DOCUMENTS.

DATE:

NAME:

U.S.AND

FOREIGNPATENTSPENDING

©MMXV

THIS DRAWING IS THE PROPERTY OF NORWALKWASTEWATER EQUIPMENT COMPANY AND MAY NOTBE COPIED OR REPRODUCED IN WHOLE OR IN PARTWITHOUT WRITTEN PERMISSION FROM NORWECO.

DRAWN BY

APPROVED BY

REVISION DATE

DATE

SCALE

DRAWING NO.

REVISION

MT

JMM

09-03-2015

NTS

PC-5-1077

2

3

4

5

MODEL 600 FEUHYDRO-KINETIC

WASTEWATER TREATMENT SYSTEMWITH EXTERNAL

PRETREATMENT CHAMBER, UVDISINFECTION SYSTEM AND PUMP

TANK

2'- 9"2'- 8"3'- 7"2'- 3"9'- 3"1'- 0"0'- 1"1'- 1"0'- 3"0'- 3"0'- 2"0'- 3"

0'- 2 1/2"1'- 4"4'- 8"6'- 0"5'- 6"1'- 5"4'- 7"3'- 7 1/2"

A

W C D E

F

Z

J

K

L

M

N

R

S

U

REMOVABLE INSPECTION COVERWITH CAST-IN-PLACE HANDLE

APPROVED SEALANTOR SEALING DEVICE

X

A A

PLAN VIEW

OUTLET END VIEW

NOTE: TOTAL SYSTEM CAPACITY: 2,420 GALLONS RATED CAPACITY: 500/600 GALLONS PER DAY

APPROVED SEALANTOR SEALING DEVICE

ANOXIC CHAMBER RISERCASTING WITH LID

MODEL A100 AIR PUMP

AERATION CHAMBER RISERCASTING WITH VENTED LID

NORWECO FRESH AIR VENT ASSEMBLY

OREGON APPROVED 1000GALLON SEPTIC TANK

SUBMERGED TRANSFER PORT

ANOXIC CHAMBER

MIXING BAR

DIFFUSER BAR

AERATION CHAMBER

SECTION A-A

MEDIA CHAMBER

CHAMBER TRANSFER PORTCAST-IN AERATION

INFLUENT CHAMBER

CLARIFICATION CHAMBER

MODEL SD103 RECIRCULATION PUMP

REACTOR ELEMENT

HIGH WATER ALARM FLOAT

CLARIFICATION CHAMBER RISERCASTING WITH LID

FLOW EQUALIZATION DEVICE(SEE DETAIL)

4" DIAMETER TRANSFER PIPE (TYP)

SOLVENT WELD CONNECTION

ANOXIC CHAMBER

REMOVABLE INSPECTION COVERWITH CAST-IN-PLACE HANDLE

AERATION CHAMBER

4" DIAMETER EFFLUENT LINE

HYDRO-KINETIC BIO-FILM REACTORRISER CASTING WITH LID

REMOVABLE INSPECTION COVERWITH CAST-IN-PLACE HANDLE

OUTLET TEE

GROUT OR SYNTHETIC SEAL

OPTIONAL PRETREATMENT CHAMBERRISER CASTING WITH LID

®

®

TRANSFER TEE

NOTE: PRETREATMENT CHAMBER MINIMUM REQUIREMENTS SHALL BE: 1000 GALLONS CAPACITY, 7 GALLONS PER INCH OF LIQUID LEVEL AND 9 INCHES OF FREEBOARD

V

PRETREATMENT CHAMBER

I

H

Y

1'- 1"

®

GASKETED DISCHARGEFLANGE ASSEMBLY

OUTLET COUPLING TO4" DIAMETER EFFLUENT LINE

FLOW EQUALIZATION DEVICE DETAIL

CLARIFICATION CHAMBER

B

O

P

60°60°

EFFLUENT PUMPSIMPLEX SUBMERSIBLE

ACCESS COVER

TO CONTROL PANELELECTRICAL CONDUIT

ACCESS RISER

OVERRIDE FLOAT

ALARM FLOAT

ON/OFF FLOAT

NOTE: TYPICAL PUMP TANK SHOWN. ACTUAL CONFIGURATION MAY VARY.

NOTE: SOME CRITICAL DIMENSIONS ARE INTENTIONALLY LEFT BLANK TO BE FILLED IN PER INDIVIDUAL JOB SITE SPECIFICATIONS.

OREGON APPROVED PUMP TANK

Q

FORCE MAIN

G

T

UV DISINFECTION SYSTEM

NOTE: FAILSAFE CONTROLS WILL SHUT DOWN EFFLUENT PUMP IF THERE IS A MALFUNCTION IN THE AIR PUMP.

FAILSAFE CONTROLS WILL ALARM AND NOTIFY THE SERVICE PROVIDER IN THE EVENT OF A MALFUNCTION.

FAILSAFE CONTROLS WILL ALARM IF EFFLUENT LEVEL REACHES THE ALARM FLOAT.

11-24-2015 A

RTROX
Approved
Page 2: REMOVABLE INSPECTION COVER GENERAL NOTESremovable inspection cover with cast-in-place handle approved sealant or sealing device x a plan view outlet end view note: total system capacity:

BK

2000SYSTEM

1'- 0"

GENERAL NOTES:

FALL THROUGH THE HYDRO-KINETICPLANT FROM INLET INVERT TO OUTLETINVERT IS FIVE INCHES. INLET INVERT ISTWELVE INCHES BELOW TANK TOP.

ON DEEPER INSTALLATIONS, PRECASTRISERS MUST BE USED TO EXTENDCASTINGS TO GRADE. INSPECTIONCOVERS MUST BE DEVELOPED TOWITHIN TWELVE INCHES OF GRADE.

TANK REINFORCED PER ACI STD. 318.

REMOVABLE COVERS ON RISERS WEIGHIN EXCESS OF SEVENTY-FIVE POUNDSEACH TO PREVENT UNAUTHORIZEDACCESS.

CONTACT THE LOCAL, LICENSEDHYDRO-KINETIC DISTRIBUTOR FORELECTRICAL REQUIREMENTS.

CRITICAL DIMENSIONS

1

ABCDEF

HG

IJKLM

NOPQRS

UT

VWXYZ

CONTRACTOR'S CERTIFICATION:I (WE) HEREBY CERTIFY THAT THISDRAWING HAS BEEN CHECKED AND ISAPPROVED FOR USE IN CONFORMITYWITH THE CONTRACT DOCUMENTS.

DATE:

NAME:

PROJECT ENGINEER'S APPROVAL:I (WE) HEREBY CERTIFY THAT THISDRAWING HAS BEEN CHECKED AND ISAPPROVED FOR USE IN CONFORMITYWITH THE CONTRACT DOCUMENTS.

DATE:

NAME:

U.S.AND

FOREIGNPATENTSPENDING

©MMXV

THIS DRAWING IS THE PROPERTY OF NORWALKWASTEWATER EQUIPMENT COMPANY AND MAY NOTBE COPIED OR REPRODUCED IN WHOLE OR IN PARTWITHOUT WRITTEN PERMISSION FROM NORWECO.

DRAWN BY

APPROVED BY

REVISION DATE

DATE

SCALE

DRAWING NO.

REVISION

MT

JMM

09-03-2015

NTS

PC-5-1078

2

3

4

5

MODEL 600 FEUHYDRO-KINETIC

WASTEWATER TREATMENT SYSTEMWITH EXTERNAL

PRETREATMENT CHAMBER, UVDISINFECTION SYSTEM AND PLASTIC

PUMP TANK

2'- 9"2'- 8"3'- 7"2'- 3"9'- 3"1'- 0"0'- 1"1'- 1"0'- 3"0'- 3"0'- 2"0'- 3"

0'- 2 1/2"1'- 4"4'- 8"6'- 0"5'- 6"1'- 5"4'- 7"3'- 7 1/2"

A

C D E

F

Z

J

K

L

M

N

R

S

U

REMOVABLE INSPECTION COVERWITH CAST-IN-PLACE HANDLE

APPROVED SEALANTOR SEALING DEVICE

A A

PLAN VIEW

OUTLET END VIEW

NOTE: TOTAL SYSTEM CAPACITY: 2,420 GALLONS RATED CAPACITY: 500/600 GALLONS PER DAY

APPROVED SEALANTOR SEALING DEVICE

ANOXIC CHAMBER RISERCASTING WITH LID

MODEL A100 AIR PUMP

AERATION CHAMBER RISERCASTING WITH VENTED LID

NORWECO FRESH AIR VENT ASSEMBLY

OREGON APPROVED 1000GALLON SEPTIC TANK

SUBMERGED TRANSFER PORT

ANOXIC CHAMBER

MIXING BAR

DIFFUSER BAR

AERATION CHAMBER

SECTION A-A

MEDIA CHAMBER

CHAMBER TRANSFER PORTCAST-IN AERATION

INFLUENT CHAMBER

CLARIFICATION CHAMBER

MODEL SD103 RECIRCULATION PUMP

REACTOR ELEMENT

HIGH WATER ALARM FLOAT

CLARIFICATION CHAMBER RISERCASTING WITH LID

FLOW EQUALIZATION DEVICE(SEE DETAIL)

4" DIAMETER TRANSFER PIPE (TYP)

SOLVENT WELD CONNECTION

ANOXIC CHAMBER

REMOVABLE INSPECTION COVERWITH CAST-IN-PLACE HANDLE

AERATION CHAMBER

4" DIAMETER EFFLUENT LINE

HYDRO-KINETIC BIO-FILM REACTORRISER CASTING WITH LID

REMOVABLE INSPECTION COVERWITH CAST-IN-PLACE HANDLE

OUTLET TEE

GROUT OR SYNTHETIC SEAL

OPTIONAL PRETREATMENT CHAMBERRISER CASTING WITH LID

®

®

TRANSFER TEE

NOTE: PRETREATMENT CHAMBER MINIMUM REQUIREMENTS SHALL BE: 1000 GALLONS CAPACITY, 7 GALLONS PER INCH OF LIQUID LEVEL AND 9 INCHES OF FREEBOARD

PRETREATMENT CHAMBER

I

H

Y

1'- 1"

®

GASKETED DISCHARGEFLANGE ASSEMBLY

OUTLET COUPLING TO4" DIAMETER EFFLUENT LINE

FLOW EQUALIZATION DEVICE DETAIL

CLARIFICATION CHAMBER

B

O

P

60° 60°

EFFLUENT PUMPSIMPLEX SUBMERSIBLE

ACCESS COVER

TO CONTROL PANELELECTRICAL CONDUIT

OVERRIDE FLOAT

ALARM FLOAT

ON/OFF FLOAT

NOTE: TYPICAL PUMP TANK SHOWN. ACTUAL CONFIGURATION MAY VARY.

NOTE: SOME CRITICAL DIMENSIONS ARE INTENTIONALLY LEFT BLANK TO BE FILLED IN PER INDIVIDUAL JOB SITE SPECIFICATIONS.

OREGON APPROVED PUMP TANK

Q

FORCE MAIN

G

T

UV DISINFECTION SYSTEM

W

V

6'- 7 1/4"

NOTE: FAILSAFE CONTROLS WILL SHUT DOWN EFFLUENT PUMP IF THERE IS A MALFUNCTION IN THE AIR PUMP.

FAILSAFE CONTROLS WILL ALARM AND NOTIFY THE SERVICE PROVIDER IN THE EVENT OF A MALFUNCTION.

FAILSAFE CONTROLS WILL ALARM IF EFFLUENT LEVEL REACHES THE ALARM FLOAT.

11-24-2015 A

RTROX
Approved