regtronic operating instructions - metal … manule regtro… · it is advisable to enter low ......
TRANSCRIPT
2
1. FEATURES
• Electricalconnection:M128-pinconnector.• Presetpressurerange0.05-10barwithpossiblefullscaleandminimumpressureregulation.• 10–100mbaradjustabledeadband.• Supplypressure:FS+atleast1bar,max11bar.• 24Vdcpowersupply.• IP65indexofprotection.• LEDindicatingpressureachievedanddigitaloutputactive.• Graphicaldisplayandkeypadtodisplaythepressure,unitofmeasurementandparametersetting.• 0-10Vanalogoutputsignal.
2. SETTINGS
PressOKandESCtogethertoaccessthesettingmenu.Selecttheparameterusingthearrowkeys.PressESCtoreturntothepreviouspage.
m During setting, pressure regulation is NOT active.
2.1 DISPLAY
2.1.1 LANGUAGE
Italiano English Deutsch Español Français
•SelectLANGUAGEusingthearrowkeys,thenpressOK. •Selectthedesiredlanguageusingthearrowkeys,thenpressOK. 2.1.2 UNIT OF MEAS
bar psi MPa
•SelectUNIT OF MEAS.usingthearrowkeys,thenpressOK. •Selectthedesiredunitofmeasurementusingthearrowkeys,thenpressOK. 2.1.3 CONTRAST
• Manualdisplaycontrastadjustment •SelectCONTRASTusingthearrowkeys,thenpressOK. •Selectthevalueusingthearrowkeys,thenpressOK. •Compensationasafunctionoftemperatureisautomatic.
2.2 SET UP
2.2.1 INPUT
0/10V 0/5V 4/20mA RS232 Keypad
•SelectINPUTusingthearrowkeys,thenpressOK. •SelectthetypeofinputusingthearrowkeysandthenpressOK. •Forthetypeofanaloginput(0/10V-0/5V-4/20mA),useanappropriateanalogsignal. •ForthetypeofRS232input,usethecommunicationprotocoldescribedinchapter12. •Forthetypeofkeypadinput,setthepressurevalueusingthearrowkeys.Whenyoupressthedisplaybuttons,thesetpressureappears; whenyoureleasethem,thepresetpressureisdisplayed.
3
2.2.2 DEADBAND
Thisindicatesthepressurerangeinproximitytothesetpressure,withinwhichregulationisactive.Thedeadbandis+and-thesetvalue. Itisadvisabletoenterlowvalues,10or15mbar,onlyifhighregulationaccuracyisrequired.Highaccuracyinvolvesmoreworkforthesolenoid valves.
•SelectDEADBusingthearrowkeys,thenpressOK. •Enterthevalueusingthearrowkeys,thenpressOK.
2.2.3 FULL SCALE
Thisindicatesthemaximumpresetpressure.TheanalogcommandisdividedovertheFullScale.Theanalogoutputsignalindicatesthatthepreset pressureis0-10Vfor0-10bar.
Exampleswithmaximumpresetpressure3,5and10bar
For optimal regulation, the feed pressure must be FS + 1 bar.
2.2.4 MINIMUM PRESSURE
Indicatestheminimumregulatedpressurewithset0V(4mA).Thevaluecanbesetbetween0and50%oftheFullScaleset.Thereferencesetis dividedbetweentheMinimumPressurevalueandtheFullScalevalue.
The minimum value which can be set with Keyboard Set is the Minimum Pressure value. 2.2.5 RS232
Enablesserialtransmission,irrespectiveofthetypeofinput.
Regolation ON
Regolation ON
- BM
+ BM
SET Regolation OFF
Set10
100% [FS]
[V]0[V]50[mA]204
[V][V][mA]
10 [V]0[V]50[mA]204
[V][V][mA]
set
50% [FS]set
[FS]set
Full Scale
Fondo Scala
Set10
10
0
3
5
[bar]
[V]0[V]50[mA]204
[bar]
[bar]
[bar][V][V][mA]
10
10
0
5
[bar]
[V]0[V]50[mA]204
[bar]
[bar][V][V][mA]
Out analogico
10
10
0
3
5
[bar]
[volt]0
[bar]
[bar]
[bar][volt] 3 [volt] 5 [volt]
FullScale AnalogOut
4
2.2.6 REGULATION SPEED
Itallowstomodifytheresponsespeedoftheregulator
V=5fastregulation V=1slowregulation
2.3 DIGITAL OUTPUT
Twodigitaloutputsareavailable,onePNPandoneNPN.Theycanbeconfiguredindependentlyasnormallyopenornormallyclosed.ThePON(P+) andPOFF(P-)activation/deactivationthresholdsareunique.
2.3.1 PRESSURE SWITCH CONFIGURATION (P)
•SelectOUTPUTusingthearrowkeys,thenpressOK. •SelectCONFIGUR.toselecttheoperatingmode,thenpressOK. •SelectPRESSURE SWITCH,thenpressOK.PRESSURE SWITCHmode, shownwithCONFIGUR. P.hasbeenselected. •UsethearrowkeystoselectPRESSURE SWITCHandpressOK. •SelectP ONandpressOK.Enterthedesiredactivationpressureand pressOK. •SelectP OFFandpressOK.Enterthedesireddeactivationpressure andpressOK. •PressESCtoexitthemenu.
2.3.2 SET (S) REFERENCE
Thisfunctioncanbeusedtomakea“variable”settingforthepressureswitch. Outisactivatedwhenthepresetpressureisreached,withatolerancedefinedbyP+andP-.
•SelectOUTPUTusingthearrowkeys,thenpressOK. •SelectCONFIGUR.toselecttheoperatingmode,thenpressOK. •SelectSET. REFandpressOK.SETREFERENCEmode,shownwith CONFIGUR. S.hasbeenselected. •UsethearrowkeystoselectPRESSURE SWITCHandpressOK. •SelectSET.REFandpressOK. •SelectP+ andpressOK. •EntertheuppertolerancepressureandpressOK. •SelectP-andpressOK.Enterthelowertolerancepressureandpress OK. •PressESCtoexitthemenu. 2.3.3 TYPE OF CONTACT
Thisfunctionisusedtoidentifywhetherthedigitaloutputisnormallyopenornormallyclosed. •SelectTYPE OF CONTACTandclickOK. •SelectTYPE PNPorTYPE NPN,clickOKandenterthetypeofcontact. •ClickESCtoexit.
2.4 DATABASE
Serialnumber Softwareversion Hourcounter:indicatestheoperatingtimeinhours.
SET SET
P ON
OFF
P OFF
ON
SETOUT ON
OUT OFF
P+
P-
OUT OFF
PRESSURE
5
2.5 DEBUG
Utilityusedforcheckingcorrectoperationofthetwosolenoidvalves.
•SelectDEBUGandpressOK. •SelectPINandpressOK.Theinsolenoidvalveactivatesandthepressure increases. •PressOK.Theinsolenoidvalvedeactivatesandpressurestabilizes. •SelectPOUTandpressOK.Theoutsolenoidvalveactivatesandpressure decreases. •PressOK,theoutsolenoidvalvedeactivatesandpressurestabilizes.
2.6 PASSWORD
Thisisathree-digitcodeusedtoprotectthesetconfiguration.• SelectSET PASSWORDwiththearrowkeysandclickOK.Onthesettingpage,usethearrowkeystoenterthedesiredvalueandclickOKto confirm.Thesystemthendisplaystheconfirmationmessage“PASSWORD SAVED”.• SelectPASSWORDandclickOKtoenable/disablethefunction.IfthepasswordsettoON,itpreventsaccesstotheconfigurationmenu. WhenyoupressOK+ESCtogethertoaccesstheconfigurationmenu,youarepromptedtoenterthepassword. Enterthesavedpassword.YoucanusethearrowkeystochangethevalueorclickOKtochangethefield. IfthepasswordissettoOFF,itisnotenabled.
Ifyouforgetthepassword,contactthemanufacturertoobtainapasswordresetcode.
•PressOKtodisplaythesetparameters.•PressOKandESCtogethertoaccesstheparametersettingmenu.•Usetheupanddownarrowstoscrollthroughthemenuandmodifytheparameters.
P IN
P OUT
bar
P
3. ACCESS TO THE MENU
ITALIANOGERMAN
ENGLISH
SPANISHFRENCH
ESC OK
PRESSURE OUT
SET UP
7.00bar
DISPLAY
SET UPOUTPUTDATABASEDEBUGPASSWORD OFFSET PASSWORD
LANGUAGE ENG
UNIT MEAS. BARCONTRAST 40
CONTRAST40
bar
MPaPSI
+ESC OK
ESC
OK
OK
ESC
ESC
OK
OK
OK
OK
DISPLAY SETPARAMETERS
INPUT 0/10 VUNIT MEAS. BAROUTPUT PDEAD BAND 0.050F SCALE 7.5MIN. PRESS. 0.000LANGUAGE ITAT= 40.5°CPC ONSERIAL NO 00100SW VERS 03.01
ESC
ESC
6
3. ACCESS TO THE MENU
INPUT 0/10 VDEAD BAND 0.050F. SCALE 10.0MIN. PRESS. 0.000PC ONSPEED ADJ 4
OK
ESC
DISPLAYSET UPOUTPUTDATABASEDEBUGPASSWORD OFFSET PASSWORD
0/10V0 / 5 V4 / 20 mARS232KEYPAD
DEAD BAND0.050 bar
F.SCALE10.0 bar
OK
OK
OK
ESC
OK
OK
OK
INPUT 0/10 VDEAD BAND 0.050F. SCALE 10.0PC OFFOK
OK
MIN. PRESS. 0.000OKOK
OK OKSPEED ADJ
4
CONFIGUR. PPRESS.SWITCHRIF. SETCONTACT TYPE
PRESS.SWITCHRIF. SET
TYPE PNP NCTYPE NPN NO
TYPE PNP NOTYPE NPN NO
PON 7.0POFF 5.0
PON
7.0 bar
P+ 2.0P- 1.0
P-
1.0 bar
P+
2.0 bar
POFF
5.0 bar
DISPLAYSET UPOUTPUTDATABASEDEBUGPASSWORD OFFSET PASSWORD
OK
ESC
OK
OK
ESC
OK
OK
OK
OK
ESC
OK
OK ESC
OK
OK
7
DISPLAYSET UPOUTPUTDATABASEDEBUGPASSWORD OFFSET PASSWORD
SERIAL NO 00010SW VERS. 03.01H.-METER 00001
DISPLAYSET UPOUTPUTDATABASEDEBUGPASSWORD OFFSET PASSWORD
PIN 0
POUT 0
PIN 1
POUT 0
PIN 0
POUT 0
OK
ESC
OK
ESC
OK OK
PIN 0
POUT 0
PIN 0
POUT 1
PIN 0
POUT 0OK OK
DISPLAYSET UPOUTPUTDATABASEDEBUGPASSWORD OFFSET PASSWORD
DISPLAYSET UPOUTPUTDATABASEDEBUGPASSWORD OFFSET PASSWORD
DISPLAYSET UPOUTPUTDATABASEDEBUGPASSWORD ONSET PASSWORD
10.00 bar
PASSWORD
- - -
PASSWORD
12 -
PASSWORD
1 - -
PASSWORD
123
PASSWORD
123 SALVATA
OK
ESC
OK
OK OK OK
OK
OK
8
5.1 PNEUMATIC CONNECTION
Pneumaticconnectionisviathethreadedholesinthebody. Itisimportantfortheregulatorpressurenottoexceed11barandthecompressedairtobefilteredat10µmanddried,topreventimpuritiesor excessivecondensatefromcausingamalfunction. Thesupplypressuremustalwaysbehigherthanthepresetpressure. Theregulatorpressuremustbeatleast1barhigherthanthefullscalevalue. Ifasilencerismountedontheoutlet,theflowratesandresponsetimesmayvary.Checkthesilencerperiodicallyforcloggingandreplaceifnecessary.
5.2 ELECTRICAL CONNECTION
ThisisbymeansofM12femalecircular8-pinconnector(to be ordered separately). Refertothewiringdiagrambelow. Wrong connections may permantenly damage the regulator.
5.2.1 CONNECTOR PIN CONFIGURATION
1=TX(RS232) (WHITE) 2=RX(RS232) (BROWN) 3=set0-10V/0-5V/4-20mA (GREEN) 4=digitalout0-24VNPN (YELLOW) 5=analogout0-10V (GREY) 6=digitalout0-24VPNP (PINK) 7=0V(GND) (BLUE) 8=powersupply+24V (RED)
colours’sequenceincompliancewithMetalWorkprewiredconnectors.
4. TECHNICAL DATAThreadedportFluid
MINinletpressure barMAXinletpressure barTemperaturerange °CPressureregulationrange barFlowrateat6.3bar∆P0.5 Nl/minFlowrateat6.3bar∆P0.1 Nl/minExhaustflowrateat6.3barwith0.1baroverpressure Nl/minExhaustflowrateat6.3barwith0.5baroverpressure Nl/minWeight KgClassofprotectionPowersupplyInputsignal(inputimpedence) Voltage Current Serialports ManualOutputsignal Analog Digital
LinearityHysteresisRepeatabilitySensitivity/Dead-bandOutputpressuredisplay Accuracy Unitofmeasurement MinimumresolutionAnalogoutputaccuracyTemperaturecharacteristicsResponsetimewith∆P=1barfrom6to7bar sfrom7to6bar sInstallationpositionNotes
REGTRONIC REGTRONIC REGTRONIC REGTRONIC NEW DEAL 300 400 1/8’’ 1/4’’ 3/4’’ 1’’ 1/2’’ 3/4’’ 1’’ 1’’ 1’’1/4’’1’’1/2’’ 2’’
Filtered,unlubricatedair.Theairmustbefilteredatatleast10µm
Regulationpressure+1bar11
0÷500.05÷10(settablefullscaleandminimumpressure)
770 1490 10000 4500 18000 20000 1050 1700 13000 7000 - - 320 500 1800 250 400 400 650 1200 2000 500 850 850 0.38 0.38 1.3 1.5 5 5.8
IP6524Vcc+10%-5%Imax110mA
0÷5Vcc,0÷10Vcc(approx.168KΩ)4÷20mA(approx.100KΩ)
RS232Keypad
0÷10Vcc(1V=1bar)-1mAmaxPNPopencollectoroutput:max24V60mANPNopencollectoroutput:max24V60mA
≤±0,5%(Fullscale)≤±0,2%(Fullscale)≤±0,2%(Fullscale)
settingrange10÷100mbar≤±0,3%(Fullscale)
bar,Mpa,psi0.01bar-0.001MPa-0.01psi
≤±0,4%(Fullscale)max2mbar/°C
volume100cc volume1000cc volume1000cc volume1000cc 0.2 0.3 0.45 0.35 0.3 0.3 0.45 0.7
InanypositionThefeaturesshownrefertothestaticconditiononly.Withairconsumptionontheoutputside,thepressuremayvary
5. INSTALLATION AND OPERATION
Regulatorconnectorviewedfromabove
78
45
3
2 1
6
9
5.2.2 DIGITAL OUT CONNECTION
Utilityperverificareilcorrettofunzionamentodelledueelettrovalvole
5.3 OPERATING PRINCIPLE
Usingasoftwarealgorythm,thecontrolcircuitcomparestheinputsignalwiththeoutputpressuremeasuredbythepressuresensor.Whenthereisachange,itactivatestheinletandoutletsolenoidvalvestore-establishanequilibrium.Thisgivesanoutputpressurethatisproportionaltotheinputsignal.
N.B.: removing the power supply, the outlet pressure doesn’t get discharged
5.3.1 FUNCTION DIAGRAM
NPN Digital OUT
LOAD
Pin 4
+24 V
PNP Digital OUT
LOAD
Pin 6
0 V
P
DISPLAY
CONTROLCIRCUIT
INLETSOLENOIDVALVE
FEED
INPUTSIGNAL
OUTPUTSIGNAL
OUTLETSOLENOIDVALVE
PRESSURESENSOR
IN OUT
6. TROUBLESHOOTING
PROBLEMThe display does not come on
The unit does not respond or responds wrongly to the setpoint
The unit does not reach the desired pressure
The display shows an unreal valueThe display is difficult to readThe unit adjusts continually
Other problems
POSSIBLE CAUSES SOLUTION No24Vpowersupply Checkthepowersupply,makesureitis enoughandcheckthewiringisinaccordance withthewiringdiagram Wronginputsignalconfiguration Configuretheappropriatetypeofinputfromthemenu Checkthesignalwireisconnectedtotheright pin Setpointtoolow Provideasuitablesetpoint
Thefull-scalesettingisatalowerpressure Setthefullscalecorrectly thandesired Thesupplypressureistoolow Increasethesupplypressure Wrongunitofmeasurement Checktheunitofmeasurement Poorcontrast Adjustthecontrast Airleakinthecircuitaftertheunit Eliminatetheleak Continuousvariationinvolume Normalbehaviour;theunithastokeep adjustingthemaintainthepresetpressure
Deadbandtoosmall Increasethedeadband Contactthemanufacturer
10
CommunicationprotocolcanbeusedtoconfigureandcontroltheregulatorviaanPCserialport.Toactivateserialcommunication,settheRS232toONontheset-uppage.Thecommunicationprotocolis24008N1(8bits,noparity,1stopbit)andthecommandsareinASCIIformat.Allcommandsarethefollowingtype:
ESCcnnnnn
Where ESC (Escape)preparestheunittoreceivecommands,cisthecommandandnnnnnistheassociatedparameter,thelengthofwhichdependsontheactualcommand.
Theavailablecontrolsareshownherewithbelow.
•Set Unit of measurementSetstheunitofmeasurement.Thecommandisthefollowingtype:
ESCcn
Wheren=0=pressureinbar1=pressureinMPA2=pressureinpsi
Ifnisnotoneofthesevalues,theunitdoesnotchange.
•Set type of inputSetsthetypeofcontrol.Thecommandisthefollowingtype:
ESCdn
Wheren=0=0-10Vinput1=0-5Vinput2=4-20mAinput3=keypadinput4=serialinput
Ifnisnotoneofthesevalues,thetypeofcontroldoesnotchange
7. SERIAL COMMUNICATION PROTOCOL
6.1 LIST OF ALLARMS
ALARM+V NPN DOUT SHORT-CIRCUIT ALARM
0V PNP DOUT SHORT-CIRCUIT ALARM
LOW VDC ALARM0V P. INP SHORT-CIRCUIT ALARM0V P. OUT SHORT-CIRCUIT ALARMP. INP DISCONNECTED ALARMP. OUT DISCONNECTED ALARMANALOG SET ALARM
PRESSURE OUT OF RANGE ALARM
POSSIBLE CAUSES SOLUTION NPNoutputtopowersupplyunithas Eliminatethecauseoftheshortcircuit.Switch shortcircuited theunitoffandbackonagaintoresetthealarm. PNPoutputtoearthhasshortcircuited Eliminatethecauseoftheshortcircuit.Switch theunitoffandbackonagaintoresetthealarm. Supplyvoltagebelow18V Increasetoasufficientvoltage Supplysolenoidvalvehasshortcircuited Drainsolenoidvalvehasshortcircuited Switchtheunitoffandbackonagain.Ifthe Fillsolenoidvalvedisconnected alarmpersists,contactthemanufacturer. Drainsolenoidvalvedisconnected Occurswith4/20mAinputwhenthecurrent Sendtheunitacorrectinputsignal.Switch exceeds23mA theunitoffandbackonagaintheresetthealarm. Downstreampressureexceeds10200mbar Checktoseeifthedrainisblocked.Thealarmresets automaticallywhenthepressuredropsbelowthe threshold.
11
•Set DeadbandSetsthedeadband.Thecommandisthefollowingtype:
ESCbnnn
Parameternnnmustalwaysbe3digits.Thevaluemustbeexpressedinmbar.
•Set Full ScaleSetsthefullscale.Thecommandisthefollowingtype:
ESCEnnnnn
Parameternnnnnmustalwaysbe5digits.Thevaluemustbeexpressedinmbar(e.g.ESCE7000,thesetfullscaleis7000mbar)
•Minimum pressure setSettheminimumregulatedpressurewithset0.Themaximumvaluewhichcanbesetisthe50%oftheFS.Thecontrolistype:
ESCennnnn
Theparameternnnnnmustbealwaysdefinedon5figures.Thevaluemustbeexpressedinmbar(Forexample,ESCe01000,theminimumpressureissetat1000mbar)
•Digital output configurationSetsthetypeofdigitaloutputandtheactivation/deactivationvalues.Thecommandisthefollowingtype:
ESCO1sssssxxxxx
Where:1=typeofoutput(0=pressureswitch1=reference)sssss=outputactivationthresholdxxxxx=outputdeactivationthresholdParameterssandxmustalwaysbe5digits.Thevaluemustbeexpressedinmbar.
•Set PressureSetsthepressuretoreach.Thecommandisthefollowingtype:
ESCPnnnnn
Parameternnnnnmustalwaysbe5digits.Thevaluemustbeexpressedinmbar(e.g.ESCP01001,thesetpressureis1001mbar)
•Read preset pressureDisplaysthepresetpressurevalue.Thiscommandrequiresnoparameters.Itisthefollowingtype:
ESCp
Theresponseis:
ESCpnnnnn
Parameternnnnnrepresentsthepressureinmbar(e.g.ESCp05600,thepresetpressureis5.60bar)
12
• Read configurationDisplaysastringwithcompletemoduleconfiguration.Thiscommandrequiresnoparameters.Itisthefollowingtype:
ESCi
Theexpectedresponseis:
ESCi05322b050c0d2E10000O10500002000e01000
Where:05322=thepressurereading050=thedeadband(b=thesetdeadbandcode)0=theunitofmeasurement(c=thesetunitofmeasurementcode)2=typeofcontrol(d=thesettypeofcontrolcode)10000=thefullscale(E=thecode)1=typeofoutput(0=pressureswitch1=reference)(O=thecode)05000=outputactivationthreshold02000=outputdeactivationthreshold01000=minimumpressure
Thetypeofparameterisindicatedbeforethevalue,exceptforpressure.
7.1 SERIAL CABLE CONNECTION DIAGRAM
M12 connector 9-pin D-Sub connector
PIN1(TX)
PIN2(RX)
OV
PIN2
PIN3
PIN5