refrigerant dryers - energía neumática del pacífico ... · 4 boge air. the air to work....

8
Refrigerant Dryers RA Series BOGE AIR. THE AIR TO WORK.

Upload: leque

Post on 02-Nov-2018

215 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Refrigerant Dryers - Energía neumática del pacífico ... · 4 BOGE AIR. THE AIR TO WORK. ENVIRONMENTALLY FRIENDLY The R134A refrigerant does not have any ozone depleting characteristics

Refrigerant Dryers RA Series

BOGE AIR. THE AIR TO WORK.

Page 2: Refrigerant Dryers - Energía neumática del pacífico ... · 4 BOGE AIR. THE AIR TO WORK. ENVIRONMENTALLY FRIENDLY The R134A refrigerant does not have any ozone depleting characteristics

BOGE AIR. THE AIR TO WORK.

Over 100,000 compressed air users expect more when it comes to their compressed air supply.

If it is BOGE AIR then you can be assured that it is quality air “Made in Germany.” This not only applies to the first class energy efficient compressed air systems manufactured by BOGE but also to the top quality compressed air treatment products.

BOGE compressed air treatment products have been designed to work in perfect harmony with the compressor range to provide the optimal, most effective and efficient compressed air quality with options available to meet the highest air quality requirements.

BOGE air provides them with the air to work.

Page 3: Refrigerant Dryers - Energía neumática del pacífico ... · 4 BOGE AIR. THE AIR TO WORK. ENVIRONMENTALLY FRIENDLY The R134A refrigerant does not have any ozone depleting characteristics

Moist compressed air

Dry compressed air

Cooling

Condensate

FUNCTION Warm, moisture saturated compressed air is cooled down to a temperature of +37˚F. The

generous dimensions of the heat exchanger promote especially effective cooling, while flow

resistance is reduced to an absolute minimum.

Contrary to conventional systems the air follows a downward path through the heat exchanger.

The force of gravity results in a particularly high droplet separation of almost 99%. Within the

oversized condensate collection area, the flow velocity is greatly reduced, so the carryover of

previously separated droplets is reliably prevented.

The dried, cold compressed air is re-heated in an air-to-air heat exchanger before being expelled

downstream from the dryer. During this process, the relative humidity of the air is lowered

considerably and up to 60% of the cooling energy is recovered.

Any resulting condensate from the cooling process is discharged from the BOGE RA unit through

the electronic level-controlled condensate drain in order to maximize energy savings. The condensate

can then be safely treated with an appropriate treatment system, such as the QWIK-PURE® oil/water

separation system.

The comprehensive BOGE RA range makes it possible to select a treatment system that is ideally suited to the actual operating conditions.

1

2

3

4

Compressed Air Treatment | Dryers

3

Efficiency in every detail: The RA series refrigerant dryers.

The BOGE efficiency edge: a total cost comparison shows that reduced pressure losses and low energy consumption ensure a rapid pay back period on the RA series dryers – a clear advantage for both the environment and your investment.

TRADITIONAL DRYER

Costs due to energy consumption

Costs due to energy consumption

Costs due to pressure losses

Costs due to pressure losses

Capital costs

Capital costs

Page 4: Refrigerant Dryers - Energía neumática del pacífico ... · 4 BOGE AIR. THE AIR TO WORK. ENVIRONMENTALLY FRIENDLY The R134A refrigerant does not have any ozone depleting characteristics

4 BOGE AIR. THE AIR TO WORK.

ENVIRONMENTALLY FRIENDLYThe R134A refrigerant does not have any ozone

depleting characteristics. It is safe for normal

handling as it is non-toxic, non-flammable and

non-corrosive. The BOGE RA dryer has a direct

effect on reducing energy consumption (for

every 2-psi drop saved across the dryer, the

customer saves 1% in energy costs) and

displays maximum respect for the environment

because nearly every component can be

recycled.

LOWEST POSSIBLE PRESSURE LOSS All dryers are characterized by their extremely

low pressure differential due to the downward

path through the aluminum heat exchanger.

This means that the generation pressure

upstream of the compressor can be optimized

and all aspects of the customer’s processes will

run smoother and much more efficiently.

INTELLIGENT DESIGNThe specially-designed aluminum heat

exchanger represents an innovative vertical

profile concept that allows the force of gravity

to result in high droplet separation and

self-cleaning. The BOGE RA series dryer has

a large cross section of flow channels for low

velocities and reduced power input. All

components are time proven and field tested.

RELIABLE PRESSURE DEWPOINTThe all new BOGE RA series dryers are built with

a Varioflow hot gas bypass valve, which utilizes a

special, gas charged capsule that operates

independently of power or electronic support.

This provides users with a 100% stable dew

point, no maintenance, and zero freeze-ups.

Installation instructions To install the standard designed dryers,

the room and/or ambient temperature

may not exceed 122°F and not fall below

40°F. Sufficient clearance must be

provided on all sides of the dryer

to ensure good cooling air circulation.

A suitably dimensioned drainage pipe

must be installed to remove condensate.

Design conditions The flow capacity rate is determined

in relation to the air intake condition

of the compressor (70°F and 14.7 psi):

Compressed air temperature 100°F

(max. 160°F possible), operating

pressure 100 psi, ambient temperature

100°F (max. 122°F possible), pressure

dew point 37°F (higher dew points

possible).

Features: • Varioflow hot gas bypass valve

• Zero loss condensate drain

• Vertical aluminum heat exchanger

Options: • Standard bypass line

• Special voltages

• High pressure

Flow capacity: 10 – 5000 cfm

Refrigerant Dryers RA 10 – RA 5000 Series

Page 5: Refrigerant Dryers - Energía neumática del pacífico ... · 4 BOGE AIR. THE AIR TO WORK. ENVIRONMENTALLY FRIENDLY The R134A refrigerant does not have any ozone depleting characteristics

5 Compressed Air Treatment | Dryers

The most efficient method of drying compressed air: when compressed air is cooled near to freezing point, water and oil vapors create condensate. This method of drying is expensive for the end user as it uses energy and creates pressure losses. Because of its energy saving components, RA series is capable of substantially reducing such costs over the entire lifetime of the compressed air system by combining savings potentials with maximum reliability.

BOGEModel

Flow Capacity

Max.OperatingPressure

PressureDifferentialAt full load

Electr.Power

ConsumptionInstalledPower

CompressedAir

ConnectionCooling Air

RequirementDimensions H x W x D Weight

m3/min cfm psig bar pisd kW hp kW hp m3/h cfm in. lbs.

RA-10 0.28 10 200 0.10 1.5 0.19 0.25 0.19 0.26 3/8" 306 180 12 x 14 x 17 52

RA-15 0.43 15 200 0.14 2.0 0.19 0.25 0.19 0.26 1/2" 306 180 15 x 22 x 19 58

RA-20 0.57 20 200 0.04 0.6 0.19 0.25 0.21 0.28 1/2" 306 180 15 x 22 x 19 62

RA-35 0.99 35 200 0.09 1.3 0.28 0.375 0.29 0.39 1/2" 306 180 15 x 22 x 19 66

RA-50 1.42 50 200 0.15 2.2 0.28 0.375 0.30 0.40 1" 408 240 15 x 22 x 19 70

RA-75 2.12 75 200 0.18 2.6 0.28 0.375 0.45 0.60 1" 408 240 14 x 17 x 29 90

RA-100 2.83 100 200 0.15 2.2 0.37 0.50 0.70 0.94 1 1/4" 510 300 14 x 17 x 29 98

RA-125 3.54 125 200 0.20 2.9 0.37 0.50 1.10 1.48 1 1/4" 595 350 19 x 17 x 33 105

RA-150 4.25 150 200 0.23 3.4 0.37 0.50 1.20 1.61 1 1/2" 595 350 19 x 17 x 33 110

RA-200 5.66 200 200 0.16 2.3 0.47 0.625 1.38 1.85 1 1/2" 900 530 20 x 21 x 35 125

RA-250 7.08 250 200 0.24 3.5 0.84 1.125 1.62 2.17 2" 2549 1500 20 x 21 x 35 140

RA-300 8.50 300 200 0.12 1.8 0.84 1.125 2.24 3.00 2" 2549 1500 21 x 22 x 36 240

RA-350 9.91 350 200 0.14 2.1 0.93 1.25 2.33 3.12 2 1/2" 2718 1600 21 x 22 x 36 250

RA-400 11.33 400 200 0.10 1.5 1.12 1.50 2.39 3.19 2 1/2" 3738 2200 22 x 24 x 37 265

RA-500 14.16 500 200 0.18 2.6 1.30 1.75 2.93 3.93 2 1/2" 3738 2200 22 x 24 x 37 300

RA-600 17.00 600 200 0.15 2.2 1.30 1.75 3.20 4.29 3" FLG 5437 3200 31 x 38 x 59 405

RA-800 22.65 800 200 0.23 3.4 2.24 3 5.00 6.71 3" FLG 6626 3900 31 x 38 x 59 420

RA-1000 28.32 1000 200 0.19 2.7 2.80 3.75 5.80 7.78 3" FLG 6626 3900 31 x 41 x 59 600

RA-1250 35.40 1250 200 0.19 2.8 3.17 4.25 6.50 8.72 3" FLG 6626 3900 31 x 41 x 59 620

RA-1500 42.48 1500 200 0.22 3.2 3.17 4.75 8.72 11.7 4" FLG 19029 11200 53 x 61 x 73 1200

RA-1750 49.55 1750 200 0.15 2.2 4.47 6 10.5 14.1 4" FLG 19029 11200 53 x 61 x 73 1300

RA-2000 56.63 2000 200 0.19 2.7 5.03 6.75 11.6 15.6 4" FLG 19029 11200 53 x 61 x 73 1350

RA-2500 70.79 2500 200 0.19 2.8 6.15 8.25 12.2 16.4 4" FLG 19029 11200 53 x 61 x 73 1450

RA-3000 84.95 3000 200 0.15 2.2 7.46 10 14.6 19.6 6" FLG 38058 22400 55 x 89 x 73 1750

RA-4000 113.3 4000 200 0.17 2.5 11.2 15 21.3 28.6 6" FLG 38058 22400 55 x 89 x 73 1850

RA-5000 141.6 5000 200 0.28 4.1 15.7 21 29.2 39.2 8" FLG 38058 22400 104 x 61 x 68 2040

Reference conditions in accordance with CAGI standard N˚ ADF100

Inlet Air Pressure psig 60 80 100 120 140 160 180 200

Factor f1 0.79 0.91 1.00 1.07 1.13 1.18 1.23 1.27

Inlet Air Temperature ˚F 90 100 110 120 130 140 150 160

Factor f2 1.16 1.00 0.85 0.73 0.63 0.54 0.47 0.4

Ambient Air Temperature ˚F 80 90 100 105 110 115 122

Factor f3 1.22 1.11 1.00 0.94 0.89 0.83 0.78

Pressure Dew Point ˚F 37 41 45 50

Factor f4 1.00 1.09 1.22 1.4

Capacity Correction Factors

Example (for 100 SCFM dryer)

Volume Flow (cfm) cfm 100 Factor

=SCFM

=100

= 85.50 = RA 100f1 x f2 x f3 x f4 1.07 x 0.88 x 0.94 x 1.00

Inlet Pressure f1 120 = 1.07

Inlet Temperature f2 110 = 0.85

Ambient Temperature f3 105 = 0.94

Pressure Dew Point f4 37 = 1.00

Page 6: Refrigerant Dryers - Energía neumática del pacífico ... · 4 BOGE AIR. THE AIR TO WORK. ENVIRONMENTALLY FRIENDLY The R134A refrigerant does not have any ozone depleting characteristics

Max. Pressure725 psig

Outlet temperaturemax. 7.8˚Fbelow inlet temperature(rel. humidity approx.30% DTP / PDP +3˚C)

Stainless steelheat exchanger

Inlet temperature max 125˚F

Inlet temperature max 160˚F

Inlet temperature max 212˚F

RS HPmax. 1750 scfm

RSmax. 800 scfm

RAmax. 5000 scfm

RA HTmax. 350 scfm

Aluminum heatexchanger

Max. Pressure232 psig

6 BOGE AIR. THE AIR TO WORK.

A Full Range of Refrigerant Drying

BOGE RSBOGE RS compressed air refrigeration dryers are designed specifically for corrosive environments. The

smooth surfaces and durability of the stainless steel plates do not need any maintenance and are well

suited to the most strenuous operating conditions.

BOGE RS HPBOGE RS HP compressed air refrigeration dryers are designed specifically for high pressure applications.

They are certified for operating pressures up to 725 psig. Among the technical highlights of this series are

the specially developed plate heat exchangers made of stainless steel and a condensate separation

system based on the demister principle.

BOGE RA HTBOGE RA HT compressed air refrigeration dryers are designed for application in environments with high

ambient temperatures and for inlet temperatures up to 212˚F . Included in the package are two additional

components: an aftercooler equipped with copper tubing and aluminum fins and prefiltering with a zero

loss condensate drain.

Page 7: Refrigerant Dryers - Energía neumática del pacífico ... · 4 BOGE AIR. THE AIR TO WORK. ENVIRONMENTALLY FRIENDLY The R134A refrigerant does not have any ozone depleting characteristics

BOGEModel

Flow Capacity

Max.Operating

Temperature

PressureDifferentialAt full load

Electr.Power

ConsumptionInstalledPower

CompressedAir

ConnectionCooling Air

RequirementDimensions H x W x D Weight

m3/min cfm OF bar psid kW hp kW hp m3/h cfm in. lbs.

RA HT 20 0.57 20 212 0.10 1.5 0.07 0.10 0.21 0.28 ½” 493 290 25 x 17 x 16 82

RA HT 30 0.85 30 212 0.19 2.8 0.09 .125 0.28 0.38 ½” 493 290 25 x 17 x 16 88

RA HT 50 1.42 50 212 0.28 4.1 0.15 0.20 0.46 0.62 ½” 493 290 25 x 17 x 16 93

RA HT 75 2.12 75 212 0.26 3.8 0.25 0.33 0.77 1.03 1” 900 530 45 x 16 x 18 112

RA HT 100 2.83 100 212 0.21 3.0 0.25 0.33 0.89 1.18 1” 1003 590 52 x 20 x 20 134

RA HT 150 4.25 150 212 0.35 5.0 0.37 0.50 1.10 1.48 1¼” 1495 880 52 x 20 x 20 146

RA HT 200 5.66 200 212 0.23 3.3 0.47 .625 1.55 2.08 1¼” 3500 2060 55 x 22 x 23 165

RA HT 250 7.08 250 212 0.35 5.1 0.84 1.125 1.82 2.44 1½” 4927 2900 55 x 22 x 23 185

RA HT 300 8.50 300 212 0.28 4.1 0.93 1.25 2.60 3.49 1½” 6116 3600 59 x 28 x 31 291

RA HT 350 9.91 350 212 0.31 4.5 0.93 1.25 2.70 3.62 2” 6286 3700 59 x 28 x 31 304

7 Compressed Air Treatment | Dryers

High Temperature and High Pressure conditions: when compressedair entering the dryer is not ideal, BOGE has the perfect solution. For every 20˚F raise in temperature, you double the moisture in the system. The BOGE RA HT is specifically designed to remove this excess moisture with inlets as high as 212˚F. The BOGE RS HP has specially developed stainless steel heat exchangers and condensate systems to deal with pressures up to 725 psig.

BOGEModel

Flow Capacity

Max.OperatingPressure

PressureDifferentialAt full load

Electr.Power

ConsumptionInstalledPower

CompressedAir

ConnectionCooling Air

RequirementDimensions H x W x D Weight

m3/min cfm psig bar psid kW hp kW hp m3/h cfm in. lbs.

RS HP 15 0.43 15 725 0.25 3.6 0.09 .125 0.19 0.25 3/8” 306 180 18 x 15 x 18 62

RS HP 30 0.85 30 725 0.24 3.5 0.13 0.17 0.22 0.30 1/2” 408 240 18 x 15 x 18 64

RS HP 40 1.13 40 725 0.25 3.6 0.13 0.17 0.26 0.35 1/2” 408 240 18 x 15 x 18 71

RS HP 50 1.42 50 725 0.23 3.3 0.19 0.25 0.35 0.47 1/2” 408 240 24 x 14 x 19 79

RS HP 80 2.27 80 725 0.23 3.3 0.25 0.33 0.54 0.72 1/2” 408 240 24 x 14 x 19 82

RS HP 100 2.83 100 725 0.24 3.5 0.25 0.33 0.58 0.78 1” 595 350 33 x 20 x 25 119

RS HP 140 3.96 140 725 0.24 3.5 0.37 0.50 1.10 1.48 1 1/4” 595 350 33 x 20 x 25 130

RS HP 180 5.10 180 725 0.20 2.9 0.37 0.50 1.20 1.61 1 1/4" 900 530 33 x 20 x 25 135

RS HP 260 7.36 260 725 0.22 3.2 0.47 .625 1.38 1.85 1 1/4” 2379 1400 34 x 22 x 29 192

RS HP 350 9.91 350 725 0.22 3.2 0.93 1.25 1.62 2.17 1 1/2” 2718 1600 34 x 22 x 29 240

RS HP 450 12.74 450 725 0.23 3.3 0.93 1.25 2.24 3.00 1 1/2” 3738 2200 49 x 23 x 26 262

RS HP 550 15.57 550 725 0.22 3.2 1.31 1.75 2.80 3.75 2” 3738 2200 49 x 23 x 26 291

RS HP 700 19.82 700 725 0.22 3.2 2.05 2.75 4.30 5.77 2” 7646 4500 67 x 24 x 46 512

RS HP 800 22.65 800 725 0.23 3.3 2.42 3.25 5.30 7.11 2 1/2” 7646 4500 67 x 24 x 46 525

RS HP 1100 31.15 1100 725 0.22 3.2 2.80 3.75 5.60 7.51 2 1/2” 7646 4500 67 x 24 x 46 573

RS HP 1400 39.64 1400 725 0.25 3.6 3.91 5.25 9.47 12.7 3” FLG 19029 11200 63 x 54 x 55 948

RS HP 1750 49.55 1750 725 0.25 3.6 4.74 6.00 10.3 13.8 3” FLG 19029 11200 63 x 54 x 55 992

Page 8: Refrigerant Dryers - Energía neumática del pacífico ... · 4 BOGE AIR. THE AIR TO WORK. ENVIRONMENTALLY FRIENDLY The R134A refrigerant does not have any ozone depleting characteristics

322-

GB-4

-12.

2009

/T ·

Tec

hnic

al c

hang

es a

nd e

rrors

rese

rved

.

BOGE AIR. THE AIR TO WORK.

Our ranges of services include the following: • Energy efficient systems development

• Plant design and engineering

• System control and visualizing

• Oil-free piston compressors

• Oil injected screw compressors

and oil lubricated piston compressors

• Compressed air treatment

• Compressed air distribution and storage

• Compressed air accessories

• Compressed air service

For four generations, customers from mechanical engineering, industry and trade have relied on BOGE know-how when it comes to planning, developing and manufacturing compressed air systems. They are fully aware of the fact that BOGE AIR is more than just ordinary compressed air: utmost safety, outstanding efficiency, excellent quality, maximized flexibility along with dependable service are the ingredients to transform BOGE AIR into air to work with – in Germany, in Europe and in more than 80 countries around the world.

BOGE America, Inc.3414 Florence Circle · Suite 100

Powder Springs · GA 30127

Tel: 770-874-1570 · Fax: 770-874-1571

www.boge.com

BOG0104_12/2010_500