red615_appl_756498_enk

188
 Relion ®  615 series Line Differential Protection and Control RED615  Application Manual

Upload: zinab90

Post on 02-Nov-2015

78 views

Category:

Documents


5 download

DESCRIPTION

DD

TRANSCRIPT

  • Relion 615 series

    Line Differential Protection and ControlRED615Application Manual

  • Document ID: 1MRS756498Issued: 2014-01-24

    Revision: KProduct version: 5.0

    Copyright 2014 ABB. All rights reserved

  • CopyrightThis document and parts thereof must not be reproduced or copied without writtenpermission from ABB, and the contents thereof must not be imparted to a thirdparty, nor used for any unauthorized purpose.The software or hardware described in this document is furnished under a licenseand may be used, copied, or disclosed only in accordance with the terms of suchlicense.TrademarksABB and Relion are registered trademarks of the ABB Group. All other brand orproduct names mentioned in this document may be trademarks or registeredtrademarks of their respective holders.WarrantyPlease inquire about the terms of warranty from your nearest ABB representative.

    http://www.abb.com/substationautomation

  • DisclaimerThe data, examples and diagrams in this manual are included solely for the conceptor product description and are not to be deemed as a statement of guaranteedproperties. All persons responsible for applying the equipment addressed in thismanual must satisfy themselves that each intended application is suitable andacceptable, including that any applicable safety or other operational requirementsare complied with. In particular, any risks in applications where a system failure and/or product failure would create a risk for harm to property or persons (including butnot limited to personal injuries or death) shall be the sole responsibility of theperson or entity applying the equipment, and those so responsible are herebyrequested to ensure that all measures are taken to exclude or mitigate such risks.This product has been designed to be connected and communicate data andinformation via a network interface which should be connected to a securenetwork. It is the sole responsibility of the person or entity responsible for networkadministration to ensure a secure connection to the network and to take thenecessary measures (such as, but not limited to, installation of firewalls, applicationof authentication measures, encryption of data, installation of anti virus programs,etc.) to protect the product and the network, its system and interface included,against any kind of security breaches, unauthorized access, interference, intrusion,leakage and/or theft of data or information. ABB is not liable for any such damagesand/or losses.This document has been carefully checked by ABB but deviations cannot becompletely ruled out. In case any errors are detected, the reader is kindly requestedto notify the manufacturer. Other than under explicit contractual commitments, inno event shall ABB be responsible or liable for any loss or damage resulting fromthe use of this manual or the application of the equipment.

  • ConformityThis product complies with the directive of the Council of the EuropeanCommunities on the approximation of the laws of the Member States relating toelectromagnetic compatibility (EMC Directive 2004/108/EC) and concerningelectrical equipment for use within specified voltage limits (Low-voltage directive2006/95/EC). This conformity is the result of tests conducted by ABB inaccordance with the product standards EN 50263 and EN 60255-26 for the EMCdirective, and with the product standards EN 60255-1 and EN 60255-27 for the lowvoltage directive. The product is designed in accordance with the internationalstandards of the IEC 60255 series.

  • Table of contents

    Section 1 Introduction.......................................................................5This manual........................................................................................5Intended audience..............................................................................5Product documentation.......................................................................6

    Product documentation set............................................................6Document revision history.............................................................6Related documentation..................................................................7

    Symbols and conventions...................................................................7Symbols.........................................................................................7Document conventions..................................................................8Functions, codes and symbols......................................................8

    Section 2 RED615 overview...........................................................13Overview...........................................................................................13

    Product version history................................................................14PCM600 and IED connectivity package version..........................14

    Operation functionality......................................................................15Optional functions........................................................................15

    Physical hardware............................................................................15Local HMI.........................................................................................17

    Display.........................................................................................18LEDs............................................................................................19Keypad........................................................................................19

    Web HMI...........................................................................................20Authorization.....................................................................................21

    Audit trail......................................................................................22Communication.................................................................................24

    Self-healing Ethernet ring............................................................25Secure communication................................................................26

    Section 3 RED615 standard configurations...................................27Standard configurations....................................................................27

    Addition of control functions for primary devices and theuse of binary inputs and outputs..................................................29

    Connection diagrams........................................................................30Standard configuration A..................................................................34

    Applications.................................................................................34Functions.....................................................................................35

    Default I/O connections..........................................................35Default disturbance recorder settings.....................................37

    Table of contents

    RED615 1Application Manual

  • Functional diagrams....................................................................38Functional diagrams for protection ........................................38Functional diagrams for disturbance recorder........................42Functional diagrams for condition monitoring.........................43Functional diagrams for control and interlocking....................45Functional diagrams for measurement functions...................47Functional diagrams for I/O and alarm LEDs.........................49Functional diagrams for other timer logics ............................52Other functions ......................................................................53

    Standard configuration B..................................................................53Applications.................................................................................53Functions.....................................................................................54

    Default I/O connections..........................................................54Default disturbance recorder settings.....................................56

    Functional diagrams....................................................................58Functional diagrams for protection.........................................58Functional diagrams for disturbance recorder........................68Functional diagrams for condition monitoring.........................68Functional diagrams for control and interlocking....................71Functional diagrams for measurement functions...................74Functional diagrams for I/O and alarm LEDs.........................75Functional diagrams for other timer logics.............................78Other functions ......................................................................79

    Standard configuration C..................................................................79Applications.................................................................................79Functions.....................................................................................80

    Default I/O connections..........................................................80Default disturbance recorder settings.....................................82

    Functional diagrams....................................................................83Functional diagrams for protection.........................................84Functional diagrams for disturbance recorder........................90Functional diagrams for condition monitoring.........................91Functional diagrams for control and interlocking....................94Functional diagrams for measurement functions...................97Functional diagrams for I/O and alarm LEDs.........................98Functional diagrams for other timer logics...........................101Other functions ....................................................................102

    Standard configuration D................................................................102Applications...............................................................................102Functions...................................................................................103

    Default I/O connections........................................................103Default disturbance recorder settings...................................105

    Functional diagrams..................................................................108

    Table of contents

    2 RED615Application Manual

  • Functional diagrams for protection ......................................108Functional diagrams for disturbance recorder......................120Functional diagrams for condition monitoring.......................121Functional diagrams for control and interlocking..................124Functional diagrams for measurement functions ................127Functional diagrams for I/O and alarm LEDs.......................129Functional diagrams for other timer logics...........................132Other functions ....................................................................133

    Standard configuration E................................................................134Applications...............................................................................134Functions...................................................................................135

    Default I/O connections........................................................135Default disturbance recorder settings...................................137

    Sensor settings..........................................................................139Functional diagrams..................................................................141

    Functional diagrams for protection.......................................142Functional diagrams for disturbance recorder......................152Functional diagrams for condition monitoring.......................153Functional diagrams for control and interlocking..................156Functional diagrams for measurement functions.................159Functional diagrams for I/O and alarm LEDs ......................161Other functions ....................................................................164

    Section 4 Requirements for measurement transformers..............165Current transformers......................................................................165

    Current transformer requirements for non-directionalovercurrent protection................................................................165

    Current transformer accuracy class and accuracy limitfactor....................................................................................165Non-directional overcurrent protection.................................166Example for non-directional overcurrent protection..............167

    Section 5 IED physical connections.............................................169Inputs..............................................................................................169

    Energizing inputs.......................................................................169Phase currents.....................................................................169Residual current...................................................................169Phase voltages.....................................................................169Residual voltage...................................................................170Sensor inputs.......................................................................170

    Auxiliary supply voltage input....................................................170Binary inputs..............................................................................170RTD/mA inputs..........................................................................172

    Outputs...........................................................................................173

    Table of contents

    RED615 3Application Manual

  • Outputs for tripping and controlling............................................173Outputs for signalling.................................................................173IRF.............................................................................................175

    Protection communication options..................................................175Section 6 Glossary.......................................................................177

    Table of contents

    4 RED615Application Manual

  • Section 1 Introduction

    1.1 This manualThe application manual contains application descriptions and setting guidelinessorted per function. The manual can be used to find out when and for what purposea typical protection function can be used. The manual can also be used whencalculating settings.

    1.2 Intended audienceThis manual addresses the protection and control engineer responsible forplanning, pre-engineering and engineering.The protection and control engineer must be experienced in electrical powerengineering and have knowledge of related technology, such as protection schemesand principles.

    1MRS756498 K Section 1Introduction

    RED615 5Application Manual

  • 1.3 Product documentation1.3.1 Product documentation set

    Pla

    nn

    ing

    &

    pu

    rch

    ase

    En

    gin

    ee

    rin

    g

    Insta

    llatio

    n

    Co

    mm

    issio

    nin

    g

    Op

    era

    tio

    n

    Ma

    inte

    na

    nce

    De

    co

    mm

    issio

    nin

    g,

    de

    insta

    llatio

    n &

    dis

    po

    sa

    l

    Quick start guide

    Quick installation guide

    Brochure

    Product guide

    Operation manual

    Installation manual

    Connection diagram

    Engineering manual

    Technical manual

    Application manual

    Communication protocol manual

    IEC 61850 Engineering guide

    Point list manual

    c

    c

    GUID-12DC16B2-2DC1-48DF-8734-0C8B7116124C V1 EN

    Figure 1: The intended use of documents during the product life cycle

    Product series- and product-specific manuals can be downloadedfrom the ABB Website http://www.abb.com/relion.

    1.3.2 Document revision historyDocument revision/date Product version HistoryA/2008-10-03 1.1 First releaseB/2009-07-03 2.0 Content updated to correspond to the

    product versionC/2010-06-11 3.0 Content updated to correspond to the

    product versionD/2010-06-29 3.0 Terminology updatedE/2010-09-24 3.0 Content updatedF/2012-05-11 4.0 Content updated to correspond to the

    product versionTable continues on next page

    Section 1 1MRS756498 KIntroduction

    6 RED615Application Manual

  • Document revision/date Product version HistoryG/2013-02-21 4.0 FP1 Content updated to correspond to the

    product versionH/2013-12-20 5.0 Content updated to correspond to the

    product versionK/2014-01-24 5.0 Content updated

    Download the latest documents from the ABB Websitehttp://www.abb.com/substationautomation.

    1.3.3 Related documentationName of the document Document IDModbus Communication Protocol Manual 1MRS756468DNP3 Communication Protocol Manual 1MRS756709IEC 60870-5-103 Communication Protocol Manual 1MRS756710IEC 61850 Engineering Guide 1MRS756475Engineering Manual 1MRS757121Installation Manual 1MRS756375Operation Manual 1MRS756708Technical Manual 1MRS756887

    1.4 Symbols and conventions1.4.1 Symbols

    The electrical warning icon indicates the presence of a hazardwhich could result in electrical shock.

    The warning icon indicates the presence of a hazard which couldresult in personal injury.

    The caution icon indicates important information or warning relatedto the concept discussed in the text. It might indicate the presenceof a hazard which could result in corruption of software or damageto equipment or property.

    1MRS756498 K Section 1Introduction

    RED615 7Application Manual

  • The information icon alerts the reader of important facts andconditions.

    The tip icon indicates advice on, for example, how to design yourproject or how to use a certain function.

    Although warning hazards are related to personal injury, it is necessary tounderstand that under certain operational conditions, operation of damagedequipment may result in degraded process performance leading to personal injuryor death. Therefore, comply fully with all warning and caution notices.

    1.4.2 Document conventionsA particular convention may not be used in this manual. Abbreviations and acronyms are spelled out in the glossary. The glossary also

    contains definitions of important terms. Push button navigation in the LHMI menu structure is presented by using the

    push button icons.To navigate between the options, use and .

    Menu paths are presented in bold.Select Main menu/Settings.

    LHMI messages are shown in Courier font.To save the changes in non-volatile memory, select Yes and press .

    Parameter names are shown in italics.The function can be enabled and disabled with the Operation setting.

    Parameter values are indicated with quotation marks.The corresponding parameter values are "On" and "Off".

    IED input/output messages and monitored data names are shown in Courier font.When the function starts, the START output is set to TRUE.

    This document assumes that the parameter setting visibility is "Advanced".

    1.4.3 Functions, codes and symbolsTable 1: Functions included in the IEDFunction IEC 61850 IEC 60617 IEC-ANSIProtectionThree-phase non-directional overcurrentprotection, low stage PHLPTOC1 3I> (1) 51P-1 (1)Three-phase non-directional overcurrentprotection, high stage

    PHHPTOC1 3I>> (1) 51P-2 (1)PHHPTOC2 3I>> (2) 51P-2 (2)

    Three-phase non-directional overcurrentprotection, instantaneous stage PHIPTOC1 3I>>> (1) 50P/51P (1)

    Table continues on next page

    Section 1 1MRS756498 KIntroduction

    8 RED615Application Manual

  • Function IEC 61850 IEC 60617 IEC-ANSIThree-phase directional overcurrent protection,low stage

    DPHLPDOC1 3I> -> (1) 67-1 (1)DPHLPDOC2 3I> -> (2) 67-1 (2)

    Three-phase directional overcurrent protection,high stage DPHHPDOC1 3I>> -> (1) 67-2 (1)Non-directional earth-fault protection, low stage EFLPTOC1 Io> (1) 51N-1 (1)

    EFLPTOC2 Io> (2) 51N-1 (2)Non-directional earth-fault protection, highstage EFHPTOC1 Io>> (1) 51N-2 (1)Non-directional earth-fault protection,instantaneous stage EFIPTOC1 Io>>> (1) 50N/51N (1)Directional earth-fault protection, low stage DEFLPDEF1 Io> -> (1) 67N-1 (1)

    DEFLPDEF2 Io> -> (2) 67N-1 (2)Directional earth-fault protection, high stage DEFHPDEF1 Io>> -> (1) 67N-2 (1)Admittance based earth-fault protection1) EFPADM1 Yo> -> (1) 21YN (1)

    EFPADM2 Yo> -> (2) 21YN (2)EFPADM3 Yo> -> (3) 21YN (3)

    Wattmetric based earth-fault protection1) WPWDE1 Po> -> (1) 32N (1)WPWDE2 Po> -> (2) 32N (2)WPWDE3 Po> -> (3) 32N (3)

    Transient / intermittent earth-fault protection INTRPTEF1 Io> -> IEF (1) 67NIEF (1)Harmonics based earth-fault protection1) HAEFPTOC1 Io>HA (1) 51NHA (1)Non-directional (cross-country) earth-faultprotection, using calculated Io EFHPTOC1 Io>> (1) 51N-2 (1)Negative-sequence overcurrent protection NSPTOC1 I2> (1) 46 (1)

    NSPTOC2 I2> (2) 46 (2)Phase discontinuity protection PDNSPTOC1 I2/I1> (1) 46PD (1)Residual overvoltage protection ROVPTOV1 Uo> (1) 59G (1)

    ROVPTOV2 Uo> (2) 59G (2)ROVPTOV3 Uo> (3) 59G (3)

    Three-phase undervoltage protection PHPTUV1 3U< (1) 27 (1)PHPTUV2 3U< (2) 27 (2)PHPTUV3 3U< (3) 27 (3)

    Three-phase overvoltage protection PHPTOV1 3U> (1) 59 (1)PHPTOV2 3U> (2) 59 (2)PHPTOV3 3U> (3) 59 (3)

    Positive-sequence undervoltage protection PSPTUV1 U1< (1) 47U+ (1)Negative-sequence overvoltage protection NSPTOV1 U2> (1) 47O- (1)Frequency protection FRPFRQ1 f>/f/f/f/f

  • Function IEC 61850 IEC 60617 IEC-ANSIThree-phase thermal protection for feeders,cables and distribution transformers T1PTTR1 3Ith>F (1) 49F (1)Three-phase thermal overload protection forpower transformers, two time constants T2PTTR1 3Ith>T (1) 49T (1)Binary signal transfer BSTGGIO1 BST (1) BST (1)Circuit breaker failure protection CCBRBRF1 3I>/Io>BF (1) 51BF/51NBF(1)Three-phase inrush detector INRPHAR1 3I2f> (1) 68 (1)Master trip TRPPTRC1 Master Trip (1) 94/86 (1)

    TRPPTRC2 Master Trip (2) 94/86 (2)Multi-purpose protection2) MAPGAPC1 MAP (1) MAP (1)

    MAPGAPC2 MAP (2) MAP (2)MAPGAPC3 MAP (3) MAP (3)MAPGAPC4 MAP (4) MAP (4)MAPGAPC5 MAP (5) MAP (5)MAPGAPC6 MAP (6) MAP (6)MAPGAPC7 MAP (7) MAP (7)MAPGAPC8 MAP (8) MAP (8)MAPGAPC9 MAP (9) MAP (9)MAPGAPC10 MAP (10) MAP (10)MAPGAPC11 MAP (11) MAP (11)MAPGAPC12 MAP (12) MAP (12)MAPGAPC13 MAP (13) MAP (13)MAPGAPC14 MAP (14) MAP (14)MAPGAPC15 MAP (15) MAP (15)MAPGAPC16 MAP (16) MAP (16)MAPGAPC17 MAP (17) MAP (17)MAPGAPC18 MAP (18) MAP (18)

    Fault locator SCEFRFLO1 FLOC (1) 21FL (1)Line differential protection with in zone powertransformer LNPLDF1 3Id/I> (1) 87L (1)High impedance fault detection PHIZ1 HIF (1) HIZ (1)Power qualityCurrent total demand distortion CMHAI1 PQM3I (1) PQM3I (1)Voltage total harmonic distortion VMHAI1 PQM3U (1) PQM3V (1)Voltage variation PHQVVR1 PQMU (1) PQMV (1)ControlCircuit-breaker control CBXCBR1 I O CB (1) I O CB (1)Disconnector control DCXSWI1 I O DCC(1) I O DCC (1)

    DCXSWI2 I O DCC(2) I O DCC (2)Table continues on next page

    Section 1 1MRS756498 KIntroduction

    10 RED615Application Manual

  • Function IEC 61850 IEC 60617 IEC-ANSIEarthing switch control ESXSWI1 I O ESC (1) I O ESC (1)Disconnector position indication DCSXSWI1 I O DC (1) I O DC (1)

    DCSXSWI2 I O DC (2) I O DC (2)DCSXSWI3 I O DC (3) I O DC (3)

    Earthing switch indication ESSXSWI1 I O ES (1) I O ES (1)ESSXSWI2 I O ES (2) I O ES (2)

    Auto-reclosing DARREC1 O -> I (1) 79 (1)Condition monitoringCircuit-breaker condition monitoring SSCBR1 CBCM (1) CBCM (1)Trip circuit supervision TCSSCBR1 TCS (1) TCM (1)

    TCSSCBR2 TCS (2) TCM (2)Current circuit supervision CCRDIF1 MCS 3I (1) MCS 3I (1)Fuse failure supervision SEQRFUF1 FUSEF (1) 60 (1)Protection communication supervision PCSRTPC1 PCS (1) PCS (1)Runtime counter for machines and devices MDSOPT1 OPTS (1) OPTM (1)MeasurementDisturbance recorder RDRE1 DR (1) DFR (1)Load profile record LDPMSTA1 LOADPROF(1)

    LOADPROF(1)

    Three-phase current measurement CMMXU1 3I (1) 3I (1)Sequence current measurement CSMSQI1 I1, I2, I0 (1) I1, I2, I0 (1)Residual current measurement RESCMMXU1 Io (1) In (1)Three-phase voltage measurement VMMXU1 3U (1) 3V (1)Residual voltage measurement RESVMMXU1 Uo (1) Vn (1)Sequence voltage measurement VSMSQI1 U1, U2, U0 (1) V1, V2, V0 (1)Three-phase power and energy measurement PEMMXU1 P, E (1) P, E (1)RTD/mA measurement XRGGIO130 X130 (RTD) (1) X130 (RTD) (1)Frequency measurement FMMXU1 f (1) f (1)

    1) One of the following can be ordered as an option: Admittance based E/F, Wattmetric based E/F orHarmonics based E/F. The option is an addition to the existing E/F of the original configuration. Theoptional E/F has also a predefined configuration in the IED. The optional E/F can be set on or off.

    2) For example, used for RTD/mA based protection or analog GOOSE

    1MRS756498 K Section 1Introduction

    RED615 11Application Manual

  • 12

  • Section 2 RED615 overview

    2.1 OverviewRED615 is a phase-segregated two-end line differential protection and control IED(intelligent electronic device) designed for utility and industrial power systems,including radial, looped and meshed distribution networks with or withoutdistributed power generation. RED615 is also designed for the protection of linedifferential applications having a transformer within the protection zone. TheRED615s communicate between substations over a fibre-optic link or a galvanicpilot wire connection. RED615 is a member of ABBs Relion product family andpart of its 615 protection and control product series. The 615 series IEDs arecharacterized by their compactness and withdrawable-unit design. Re-engineeredfrom the ground up, the 615 series has been guided by the IEC 61850 standard forcommunication and interoperability of substation automation equipment.The IED provides unit type main protection for overhead lines and cable feeders indistribution networks. The IED also features current-based protection functions forremote back-up for down-stream protection IEDs and local back-up for the linedifferential main protection. Further, standard configurations B and C also includeearth-fault protection. Standard configuration D includes directional overcurrentand voltage based protection functions.The IED is adapted for the protection of overhead line and cable feeders in isolatedneutral, resistance earthed, compensated (impedance earthed) and solidly earthednetworks. Once the IED has been given the application-specific settings, it candirectly be put into service.The 615 series IEDs support a range of communication protocols including IEC61850 with GOOSE messaging, IEC 61850-9-2 LE (except in RED615), IEC60870-5-103, Modbus and DNP3. Profibus DPV1 communication protocol issupported by using the protocol converter SPA-ZC 302.

    1MRS756498 K Section 2RED615 overview

    RED615 13Application Manual

  • 2.1.1 Product version historyProduct version Product history1.1 Product released2.0 Support for DNP3 serial or TCP/IP

    Support for IEC 60870-5-103 New standard configurations B and C Disturbance recorder upload via WHMI

    3.0 Additions to configuration B Application configurability support Analog GOOSE support Large display with single line diagram Enhanced mechanical design Increased maximum amount of events and fault records Admittance-based earth-fault protection Residual overvoltage protection Low voltage power supply option Pilot wire modem support

    4.0 Additions/changes for configurations A-C Dual fibre optic Ethernet communication option (COM0032) Generic control point (SPCGGIO) function blocks Additional logic blocks Button object for SLD Controllable disconnector and earth switch objects for SLD Wattmetric based E/F Harmonics based E/F Increased maximum amount of events and fault records

    4.0 FP1 Parallel use of IEC 61850 and DNP3 protocols Parallel use of IEC 61850 and IEC 60870-5-103 protocols Two selectable indication colors for LEDs (red or green) Online binary signal monitoring with PCM600

    5.0 New configurations D and E New layout in Application Configuration tool for all configurations In-zone transformer application support Fault locator Load profile recorder Optional RTD/mA inputs Profibus adapter support Support for multiple SLD pages Import/export of settings via WHMI Setting usability improvements HMI event filtering tool

    2.1.2 PCM600 and IED connectivity package version Protection and Control IED Manager PCM600 Ver.2.6 or later RED615 Connectivity Package Ver.5.0 or later

    Parameter Setting Signal Monitoring Event Viewer Disturbance Handling Application Configuration

    Section 2 1MRS756498 KRED615 overview

    14 RED615Application Manual

  • Signal Matrix Graphical Display Editor Communication Management IED User Management IED Compare Firmware Update Fault Record tool Load Record Profile Lifecycle Traceability Configuration Wizard AR Sequence Visualizer Label Printing IEC 61850 Configuration Differential Characteristics Tool

    Download connectivity packages from the ABB Websitehttp://www.abb.com/substationautomation or directly with theUpdate Manager in PCM600.

    2.2 Operation functionality2.2.1 Optional functions

    Autoreclosing (configurations B, C, D and E only) Modbus TCP/IP or RTU/ASCII IEC 60870-5-103 DNP3 TCP/IP or serial Admittance based earth-fault (configurations B, D and E only) Watt-metric based earth-fault (configurations B, D and E only) Harmonics based earth-fault (configurations B, C, D and E only) Power quality functions (configurations D and E only) Fault locator (configurations D and E only) RTD/mA measurement (configuration D only)

    2.3 Physical hardwareThe IED consists of two main parts: plug-in unit and case. The content depends onthe ordered functionality.

    1MRS756498 K Section 2RED615 overview

    RED615 15Application Manual

  • Table 2: Plug-in unit and caseMain Slot ID Content optionsPlug-in

    unit- HMI Small (5 lines, 20 characters)

    Large (10 lines, 20 characters)X100 Auxiliary power/BO

    module48-250 V DC/100-240 V AC; or 24-60 V DC2 normally-open PO contacts1 change-over SO contacts1 normally open SO contact2 double-pole PO contacts with TCS1 dedicated internal fault output contact

    X110 BIO module 8 binary inputs4 SO contacts

    X120 AI/BI module Only with configuration B:3 phase current inputs (1/5 A)1 residual current input (1/5 A or 0.2/1 A)1)1 residual voltage input (60-210 V)3 binary inputs

    Only with configurations A, C and D:3 phase current inputs (1/5 A)1 residual current input (1/5 A or 0.2/1 A)1)4 binary inputs

    Case X130 AI/BI module Only with configuration D:3 phase voltage inputs (60-120 V)1 residual voltage input (60-120 V)4 binary inputs

    AI/RTD/mA module Only with configuration D:3 phase voltage inputs (60-210 V)1 residual voltage input (60-210 V)1 generic mA input2 RTD sensor inputs

    Sensor input module Only with configuration E:3 combi sensor inputs (three-phase current andvoltage)1 residual current input (0.2/1 A)1)

    Optional BIO module Optional for configurations A, B and C:6 binary inputs3 SO contacts

    X000 Communication module See the technical manual for details about differenttypes of communication modules.

    1) The 0.2/1 A input is normally used in applications requiring sensitive earth-fault protection andfeaturing core-balance current transformers.

    Rated values of the current and voltage inputs are basic setting parameters of theIED. The binary input thresholds are selectable within the range 16176 V DC byadjusting the binary input setting parameters.

    See the installation manual for more information about the case andthe plug-in unit.

    The connection diagrams of different hardware modules are presented in this manual.

    Section 2 1MRS756498 KRED615 overview

    16 RED615Application Manual

  • Table 3: Input/output overviewStd.conf.

    Order code digit Analog channels Binary channels 5-6 7-8 CT VT Combi

    sensorBI BO RTD mA

    A ACAD 4 - - 12 4 PO +6 SO

    - -

    AF 4 - - 18 4 PO +9 SO- -

    B AA / ABAC 4 1 - 11 4 PO +6 SO

    - -

    AE 4 1 - 17 4 PO +9 SO- -

    C ACAD 4 - - 12 4 PO +6 SO

    - -

    AF 4 - - 18 4 PO +9 SO- -

    DFE / FF AD 4 5 - 12 4 PO +6 SO

    2 1

    AE / AF AG 4 5 - 16 4 PO +6 SO- -

    E DA AH 1 - 3 8 4 PO +6 SO- -

    2.4 Local HMIThe LHMI is used for setting, monitoring and controlling the IED. The LHMIcomprises the display, buttons, LED indicators and communication port.

    1MRS756498 K Section 2RED615 overview

    RED615 17Application Manual

  • REF615

    Overcurrent

    Dir. earth-fault

    Voltage protection

    Phase unbalance

    Thermal overload

    Breaker failure

    Disturb. rec. Triggered

    CB condition monitoring

    Supervision

    Arc detected

    Autoreclose shot in progr.

    A070704 V4 EN

    Figure 2: Example of the LHMI

    2.4.1 DisplayThe LHMI includes a graphical display that supports two character sizes. Thecharacter size depends on the selected language. The amount of characters androws fitting the view depends on the character size.Table 4: Small displayCharacter size1) Rows in the view Characters per rowSmall, mono-spaced (6x12 pixels) 5 20Large, variable width (13x14 pixels) 4 8 or more

    1) Depending on the selected language

    Table 5: Large displayCharacter size1) Rows in the view Characters per rowSmall, mono-spaced (6x12 pixels) 10 20Large, variable width (13x14 pixels) 8 8 or more

    1) Depending on the selected language

    Section 2 1MRS756498 KRED615 overview

    18 RED615Application Manual

  • The display view is divided into four basic areas.1 2

    3 4A070705 V3 EN

    Figure 3: Display layout1 Header2 Icon3 Content4 Scroll bar (displayed when needed)

    2.4.2 LEDsThe LHMI includes three protection indicators above the display: Ready, Start andTrip.There are 11 matrix programmable LEDs on front of the LHMI. The LEDs can beconfigured with PCM600 and the operation mode can be selected with the LHMI,WHMI or PCM600.

    2.4.3 KeypadThe LHMI keypad contains push-buttons which are used to navigate in differentviews or menus. With the push-buttons you can give open or close commands toobjects in the primary circuit, for example, a circuit breaker, a contactor or adisconnector. The push-buttons are also used to acknowledge alarms, resetindications, provide help and switch between local and remote control mode.

    1MRS756498 K Section 2RED615 overview

    RED615 19Application Manual

  • A071176 V1 EN

    Figure 4: LHMI keypad with object control, navigation and command push-buttons and RJ-45 communication port

    2.5 Web HMIThe WHMI allows secure access to the IED via a Web browser. The supportedWeb browser versions are Internet Explorer 8.0, 9.0 and 10.0. When the SecureCommunication parameter in the IED is activated, the Web server is forced to takea secured (HTTPS) connection to WHMI using TLS encryption.

    WHMI is disabled by default.

    WHMI offers several functions. Programmable LEDs and event lists System supervision Parameter settings Measurement display Disturbance records Phasor diagram Single-line diagram Importing/Exporting parameters

    The menu tree structure on the WHMI is almost identical to the one on the LHMI.

    Section 2 1MRS756498 KRED615 overview

    20 RED615Application Manual

  • A070754 V5 EN

    Figure 5: Example view of the WHMIThe WHMI can be accessed locally and remotely. Locally by connecting the laptop to the IED via the front communication port. Remotely over LAN/WAN.

    2.6 AuthorizationThe user categories have been predefined for the LHMI and the WHMI, each withdifferent rights and default passwords.The default passwords can be changed with Administrator user rights.

    User authorization is disabled by default for LHMI but WHMIalways uses authorization.

    1MRS756498 K Section 2RED615 overview

    RED615 21Application Manual

  • Table 6: Predefined user categoriesUsername User rightsVIEWER Read only accessOPERATOR Selecting remote or local state with (only locally)

    Changing setting groups Controlling Clearing indications

    ENGINEER Changing settings Clearing event list Clearing disturbance records Changing system settings such as IP address, serial baud rate

    or disturbance recorder settings Setting the IED to test mode Selecting language

    ADMINISTRATOR All listed above Changing password Factory default activation

    For user authorization for PCM600, see PCM600 documentation.

    2.6.1 Audit trailThe IED offers a large set of event-logging functions. Normal process-relatedevents can be viewed by the normal user with Event Viewer in PCM600. Criticalsystem and IED security-related events are logged to a separate nonvolatile audittrail for the administrator.Audit trail is a chronological record of system activities that allows thereconstruction and examination of the sequence of events and changes in an event.Past user and process events can be examined and analyzed in a consistent methodwith the help of Event List and Event Viewer in PCM600. The IED stores 2048system events to the nonvolatile audit trail. Additionally, 1024 process events arestored in a nonvolatile event list. Both the audit trail and event list work accordingto the FIFO principle.User audit trail is defined according to the selected set of requirements from IEEE1686. The logging is based on predefined usernames or user categories. The useraudit trail events are accessible with IEC 61850-8-1, PCM600, LHMI and WHMI.Table 7: Audit trail eventsAudit trail event DescriptionConfiguration change Configuration files changedFirmware change Setting group remote User changed setting group remotely

    Table continues on next page

    Section 2 1MRS756498 KRED615 overview

    22 RED615Application Manual

  • Audit trail event DescriptionSetting group local User changed setting group locallyControl remote DPC object control remoteControl local DPC object control localTest on Test mode onTest off Test mode offSetting commit Settings have been changedTime change Time changed directly by the user. Note that this is not used

    when the IED is synchronised properly by the appropriateprotocol (SNTP, IRIG-B, IEEE 1588 v2).

    View audit log Administrator accessed audit trailLogin Successful login from IEC 61850-8-1 (MMS), WHMI, FTP or

    LHMI.Logout Successful logout from IEC 61850-8-1 (MMS), WHMI, FTP

    or LHMI.Firmware reset Reset issued by user or toolAudit overflow Too many audit events in the time periodAttached to retrofit test case Unit has been attached to retrofit caseRemoved from retrofit test case Unit has been removed retrofit caseReset trips Reset latched trips (TRPPTRC*)Violation remote Unsuccessful login attempt from IEC 61850-8-1 (MMS),

    WHMI, FTP or LHMI.Violation local Unsuccessful login attempt from IEC 61850-8-1 (MMS),

    WHMI, FTP or LHMI.

    PCM600 Event Viewer can be used to view the audit trail events together withnormal events. Since only the administrator has the right to read audit trail,authorization must be properly configured in PCM600. The audit trail cannot bereset but PCM600 Event Viewer can filter data. Some of the audit trail events areinteresting also as normal process events.

    To expose the audit trail events also as normal process events,define the level parameter via Configuration/Authorization/Authority logging.

    Table 8: Comparison of authority logging levelsAudit trail event Authority logging level

    NoneConfiguration change

    Settinggroup

    Settinggroup,control

    Settingsedit

    All

    Configuration change Firmware change Firmware change fail

    Table continues on next page

    1MRS756498 K Section 2RED615 overview

    RED615 23Application Manual

  • Audit trail event Authority logging levelAttached to retrofit testcase

    Removed from retrofittest case

    Reset trips Setting group remote Setting group local Control remote Control local Test on Test off Setting commit Time change View audit log Login Logout Firmware reset Audit overflow

    2.7 CommunicationThe IED supports a range of communication protocols including IEC 61850, IEC60870-5-103, Modbus and DNP3. Profibus DPV1 communication protocol issupported by using the protocol converter SPA-ZC 302. Operational informationand controls are available through these protocols. However, some communicationfunctionality, for example, horizontal communication between the IEDs, is onlyenabled by the IEC 61850 communication protocol.The IEC 61850 communication implementation supports all monitoring andcontrol functions. Additionally, parameter settings, disturbance recordings andfault records can be accessed using the IEC 61850 protocol. Disturbance recordingsare available to any Ethernet-based application in the standard COMTRADE fileformat. The IED can send and receive binary signals from other IEDs (so-calledhorizontal communication) using the IEC61850-8-1 GOOSE profile, where thehighest performance class with a total transmission time of 3 ms is supported.Furthermore, the IED supports sending and receiving of analog values usingGOOSE messaging. The IED meets the GOOSE performance requirements fortripping applications in distribution substations, as defined by the IEC 61850standard.The IED can support five simultaneous clients. If PCM600 reserves one clientconnection, only four client connections are left, for example, for IEC 61850 andModbus.

    Section 2 1MRS756498 KRED615 overview

    24 RED615Application Manual

  • All communication connectors, except for the front port connector, are placed onintegrated optional communication modules. The IED can be connected to Ethernet-based communication systems via the RJ-45 connector (100Base-TX). Ifconnection to a RS-485 network is required, a 9-pin screw-terminal connector, anoptional 9-pin D-sub connector or an optional ST-type glass-fibre connector can beused.

    2.7.1 Self-healing Ethernet ringFor the correct operation of self-healing loop topology, it is essential that theexternal switches in the network support the RSTP protocol and that it is enabled inthe switches. Otherwise, connecting the loop topology can cause problems to thenetwork. The IED itself does not support link-down detection or RSTP. The ringrecovery process is based on the aging of the MAC addresses, and the link-up/link-down events can cause temporary breaks in communication. For a betterperformance of the self-healing loop, it is recommended that the external switchfurthest from the IED loop is assigned as the root switch (bridge priority = 0) andthe bridge priority increases towards the IED loop. The end links of the IED loopcan be attached to the same external switch or to two adjacent external switches. Aself-healing Ethernet ring requires a communication module with at least twoEthernet interfaces for all IEDs.

    Managed Ethernet switchwith RSTP support

    Managed Ethernet switchwith RSTP support

    Client BClient A

    Network ANetwork B

    GUID-283597AF-9F38-4FC7-B87A-73BFDA272D0F V3 EN

    Figure 6: Self-healing Ethernet ring solution

    The Ethernet ring solution supports the connection of up to 30IEDs. If more than 30 IEDs are to be connected, it is recommendedthat the network is split into several rings with no more than 30IEDs per ring. Each IED has a 50-s store-and-forward delay, and

    1MRS756498 K Section 2RED615 overview

    RED615 25Application Manual

  • to fullfill the performance requirements for fast horizontalcommunication, the ring size is limited to 30 IEDs.

    2.7.2 Secure communicationThe IED supports secure communication for WHMI and file transfer protocol. Ifthe Secure Communication parameter is activated, protocols require TLS basedencryption method from the client. In this case WHMI must be connected from aWeb browser using the HTTPS protocol and in case of file transfer the client mustuse FTPS.

    Section 2 1MRS756498 KRED615 overview

    26 RED615Application Manual

  • Section 3 RED615 standard configurations

    3.1 Standard configurationsRED615 is available in five alternative standard configurations. The standardsignal configuration can be altered by means of the signal matrix or the graphicalapplication functionality of the Protection and Control IED Manager PCM600.Further, the application configuration functionality of PCM600 supports thecreation of multi-layer logic functions utilizing various logical elements includingtimers and flip-flops. By combining protection functions with logic function blocksthe IED configuration can be adapted to user specific application requirements.The IED is delivered from the factory with default connections described in thefunctional diagrams for binary inputs, binary outputs, function-to-functionconnections and alarm LEDs. The positive measuring direction of directionalprotection functions is towards the outgoing feeder.Table 9: Standard configurationsDescription Std. conf.Line differential protection and CB control ALine differential protection with directional earth-fault protection, CB conditionmonitoring and CB control BLine differential protection with non-directional earth-fault protection, CB conditionmonitoring and CB control CLine differential protection, directional overcurrent and directional earth-faultprotection, phase-voltage and frequency based protection and measurementfunctions, CB condition monitoring, CB control and fault locator (optional)

    D

    Line differential protection with directional overcurrent and directional earth-faultprotection, phase-voltage and frequency based protection and measurementfunctions, CB condition monitoring, CB control, sensor inputs for phase currents andphase voltages and fault locator (optional)

    E

    Table 10: Supported functionsFunction IEC 61850 A B C D EProtection1)Three-phase non-directional overcurrent protection, low stage PHLPTOC 1 1 1 Three-phase non-directional overcurrent protection, high stage PHHPTOC 2 2 2 Three-phase non-directional overcurrent protection,instantaneous stage PHIPTOC 1 1 1 1 1Three-phase directional overcurrent protection, low stage DPHLPDOC 2 2Three-phase directional overcurrent protection, high stage DPHHPDOC 1 1Non-directional earth-fault protection, low stage EFLPTOC 2 2) Non-directional earth-fault protection, high stage EFHPTOC 1 2) Non-directional earth-fault protection, instantaneous stage EFIPTOC 1 2)

    Table continues on next page

    1MRS756498 K Section 3RED615 standard configurations

    RED615 27Application Manual

  • Function IEC 61850 A B C D EDirectional earth-fault protection, low stage DEFLPDEF 2 2)3) 2 2)3) 2 4)5)Directional earth-fault protection, high stage DEFHPDEF 1 2)3) 1 2)3) 1 4)5)Admittance-based earth-fault protection 6) EFPADM (3) 2)3)6) (3) 2)3)6) (3) 2)5)6)Wattmetric-based earth-fault protection 6) WPWDE (3) 2)3)6) (3) 2)3)6) (3) 2)5)6)Transient/intermittent earth-fault protection INTRPTEF 1 7)8) 1 7)8) 1 5)8)Harmonics-based earth-fault protection 6) HAEFPTOC (1) 6)8) (1) 6)8) (1) 6)8) (1) 6)8)Non-directional (cross-country) earth-fault protection, usingcalculated Io EFHPTOC 1 4) 1 4) 1 4)Negative-sequence overcurrent protection NSPTOC 2 2 2 2 2Phase discontinuity protection PDNSPTOC 1 1 1 1Residual overvoltage protection ROVPTOV 3 3) 3 7) 3 5)Three-phase undervoltage protection PHPTUV 3 3Three-phase overvoltage protection PHPTOV 3 3Positive-sequence undervoltage protection PSPTUV 1 1Negative-sequence overvoltage protection NSPTOV 1 1Frequency protection FRPFRQ 4 4Three-phase thermal protection for feeders, cables anddistribution transformers T1PTTR 1 1 1 1Three-phase thermal overload protection for powertransformers, two time constants T2PTTR 1 1 1 1Binary signal transfer BSTGGIO 1 1 1 1 1Circuit breaker failure protection CCBRBRF 1 9) 1 1 1 1Three-phase inrush detector INRPHAR 1 1 1 1 1Master trip TRPPTRC 2 2 2 2 2Multi-purpose protection 10) MAPGAPC 18 18 18 18 18Fault locator SCEFRFLO (1) (1)Line differential protection with in zone power transformer LNPLDF 1 1 1 1 1High impedance fault detection PHIZ 1 1 1 1 Power qualityCurrent total demand distortion CMHAI (1) 11) (1) 11)Voltage total harmonic distortion VMHAI (1) 11) (1) 11)Voltage variation PHQVVR (1) 11) (1) 11)Control Circuit-breaker control CBXCBR 1 1 1 1 1Disconnector control DCXSWI 2 2 2 2 2Earthing switch control ESXSWI 1 1 1 1 1Disconnector position indication DCSXSWI 3 3 3 3 3Earthing switch indication ESSXSWI 2 2 2 2 2Autoreclosing DARREC (1) (1) (1) (1)Condition monitoringCircuit-breaker condition monitoring SSCBR 1 1 1 1Trip circuit supervision TCSSCBR 2 2 2 2 2Current circuit supervision CCRDIF 1 1 1 1 1Fuse failure supervision SEQRFUF 1 1Protection communication supervision PCSRTPC 1 1 1 1 1Runtime counter for machines and devices MDSOPT 1 1 1 1 1MeasurementDisturbance recorder RDRE 1 1 1 1 1Load profile record LDPMSTA 1 1 1 1 1Three-phase current measurement CMMXU 1 1 1 1 1Sequence current measurement CSMSQI 1 1 1 1 1Residual current measurement RESCMMXU 1 1 1 1Three-phase voltage measurement VMMXU 1 1

    Table continues on next page

    Section 3 1MRS756498 KRED615 standard configurations

    28 RED615Application Manual

  • Function IEC 61850 A B C D EResidual voltage measurement RESVMMXU 1 1 Sequence voltage measurement VSMSQI 1 1Three-phase power and energy measurement PEMMXU 1 1RTD/mA measurement XRGGIO130 (1) Frequency measurement FMMXU 1 11, 2, ... = number of included instances() = optional

    1) The instances of a protection function represent the number of identical protection function blocks available in the standard configuration.2) Io selectable by parameter, Io measured as default3) "Uo measured" is always used.4) Io selectable by parameter, "Io calculated" as default5) "Uo calculated" is always used.6) One of the following can be ordered as an option: admittance-based E/F, wattmetric-based E/F or harmonics-based E/F. The option is

    an addition to the existing E/F of the original configuration. The optional E/F has also a predefined configuration in the IED. The optionalE/F can be set on or off.

    7) Uo selectable by parameter, Uo measured as default8) "Io measured" is always used.9) "Io calculated" is always used.10) Multi-purpose protection is used, for example, for RTD/mA-based protection or analog GOOSE.11) Power quality option includes current total demand distortion, voltage total harmonic distortion and voltage variation.

    3.1.1 Addition of control functions for primary devices and theuse of binary inputs and outputsIf extra control functions intended for controllable primary devices are added to theconfiguration, additional binary inputs and/or outputs are needed to complementthe standard configuration.If the number of inputs and/or outputs in a standard configuration is not sufficient,it is possible either to modify the chosen IED standard configuration in order torelease some binary inputs or binary outputs which have originally been configuredfor other purposes, or to integrate an external input/output module, for exampleRIO600, to the IED.The external I/O modules binary inputs and outputs can be used for the less time-critical binary signals of the application. The integration enables releasing someinitially reserved binary inputs and outputs of the IEDs standard configuration.The suitability of the IEDs binary outputs which have been selected for primarydevice control should be carefully verified, for example make and carry andbreaking capacity. If the requirements for the primary device control circuit are notmet, using external auxiliary relays should be considered.

    1MRS756498 K Section 3RED615 standard configurations

    RED615 29Application Manual

  • 3.2 Connection diagrams

    GUID-7A5D7398-4E4E-4B45-A561-01E3AF4C1640 V1 EN

    Figure 7: Connection diagram for the A and C configurations

    Section 3 1MRS756498 KRED615 standard configurations

    30 RED615Application Manual

  • GUID-9A18BC7A-D172-4FD4-9C25-BF39C5879E5D V1 EN

    Figure 8: Connection diagram for the B configuration

    1MRS756498 K Section 3RED615 standard configurations

    RED615 31Application Manual

  • RED615

    16

    17

    1918

    X100

    67

    89

    10

    111213

    15

    14

    2

    1

    3

    45

    22

    212324

    SO2

    TCS2

    PO4

    SO1

    TCS1

    PO3

    PO2

    PO1

    IRF

    +

    -Uaux

    20

    L1L2L3

    S1

    S2

    P1

    P2

    P2

    P1 S1

    S2

    da dn

    X110

    34

    56

    7

    89

    10BI 6

    BI 5

    BI 4

    BI 3

    BI 2

    BI 8

    BI 712

    13

    11

    BI 112

    X110

    16

    14

    15

    19

    17

    18

    22

    20

    21

    SO3

    SO2

    SO1

    23SO4

    24

    a

    nN

    A

    PositiveCurrentDirection

    2)

    X120

    12

    3

    4

    567

    89

    1011

    12

    14Io

    IL1

    IL2

    BI 4

    BI 3

    BI 2

    BI 1

    IL3

    1/5A

    N1/5A

    N1/5A

    N1/5A

    N

    X13012

    34

    56

    BI 4

    BI 3

    BI 2

    BI 1

    87

    9101112

    not in use

    1314

    U1

    1516

    U2

    1718

    U3

    UoN

    N

    N

    N

    60 -

    N

    210V

    60 -210V

    60 -210V

    60 -210V

    60 -210V

    6)

    X1LAN

    X5123456789

    B/-A/+

    / TX

    / RX

    GNDGNDC

    X16Line Differential Protection Communication

    X2LAN

    IRIG-B -IRIG-B +AGND

    1) 3)

    X12RXTX

    1) 3)

    1) 4)

    1) 5)

    B/-A/+

    1) Optional2) The IED features an automatic short-circuit mechanism in the CT connector when plug-in unit is detached3) 100BaseFx / LC or 100BaseTx / RJ-454) RS-485 serial bus5) Fibre Optic (ST) Serial Bus6) AIM0006 (5U+4BI) Alternative Module AIM0003 (5U+2RTD+1mA)

    GUID-28FB3DA2-5BA8-4041-B17D-80C5B5F17D4D V1 EN

    Figure 9: Connection diagram for the D configuration

    Section 3 1MRS756498 KRED615 standard configurations

    32 RED615Application Manual

  • RED615

    16

    17

    1918

    X100

    67

    89

    10

    111213

    15

    14

    2

    1

    3

    45

    22

    212324

    SO2

    TCS2

    PO4

    SO1

    TCS1

    PO3

    PO2

    PO1

    IRF

    +

    -Uaux

    20

    X110

    34

    56

    7

    89

    10BI 6

    BI 5

    BI 4

    BI 3

    BI 2

    BI 8

    BI 712

    13

    11

    BI 112

    X110

    16

    14

    15

    19

    17

    18

    22

    20

    21

    SO3

    SO2

    SO1

    23SO4

    24

    X1LAN

    X5123456789

    B/-A/+

    / TX

    / RX

    GNDGNDC

    X16Line Differential Protection Communication

    X2LAN

    IRIG-B -IRIG-B +AGND

    1) 3)

    X12RXTX

    1) 3)

    1) 4)

    1) 5)

    B/-A/+

    1) Optional3) 100BaseFx / LC or 100BaseTx / RJ-454) RS-485 serial bus5) Fibre Optic (ST) Serial Bus

    X130

    12

    X131

    45

    IL1

    78

    U1

    X132

    45

    IL2

    78

    U2

    X133

    45

    IL3

    78

    U3

    Io0,2/1A

    N

    P2

    P1 S1

    S2

    PositiveCurrentDirection

    L1

    L2

    L3

    GUID-D6DCAA04-E7EA-4926-BEED-D7BD476C9142 V1 EN

    Figure 10: Connection diagram for the E configuration

    1MRS756498 K Section 3RED615 standard configurations

    RED615 33Application Manual

  • 3.3 Standard configuration A3.3.1 Applications

    The standard configuration for line current differential protection is intended forcable feeder applications in the distribution networks. The standard configurationfor line current differential protection includes support for in-zone transformers.The IED with a standard configuration is delivered from the factory with defaultsettings and parameters. The end user flexibility for incoming, outgoing andinternal signal designation within the IED enables this configuration to be furtheradapted to different primary circuit layouts and the related functionality needs bymodifying the internal functionality using PCM600.

    Section 3 1MRS756498 KRED615 standard configurations

    34 RED615Application Manual

  • 3.3.2 Functions

    RED615 AT REMOTE

    END

    CONDITION MONITORING AND SUPERVISION

    COMMUNICATION

    Protocols: IEC 61850-8-1 Modbus

    IEC 60870-5-103 DNP3

    Interfaces: Ethernet: TX (RJ45), FX (LC) Serial: Serial glass ber (ST), RS-485, RS-232/485 D-sub 9, IRIG-B

    1 0 1 0 0 0 1 1 0 0 1 1 0 01 0 1 1 0 0 1 0 1 1 1 0 0 1 01 1 0 0 1 1 1 0 1 1 0 1 01 0 1 1 0 1 1 0 1 1 0 1 0 01 0 1 0 0 0 1 1 0 0 1 1 0 0 1 0 1 0 0 0 1 1 0 0 1 1 0 01 0 1 1 0 0 1 0 1 1 1 0 0 1 01 1 0 0 1 1 1 0 1 1 0 1 01 0 1 1 0 1 1 0 1 1 0 1 0 0

    ALSO AVAILABLE

    - Binary Signal Transfer function (BST)- Disturbance and fault recorder- Event log and recorded data- IED self-supervision - Local/Remote push button on LHMI- User management- Web HMI

    ORAND

    CONTROL AND INDICATION 1) MEASUREMENT

    LINE DIFFERENTIAL PROTECTION AND CONTROL IED

    PROTECTION LOCAL HMI

    Analog interface types 1)

    Current transformer

    Voltage transformer1) Conventional transformer inputs

    Object Ctrl 2) Ind 3)

    CB

    DC

    ES1) Check availability of binary inputs/outputs

    from technical documentation2) Control and indication function for

    primary object3) Status indication function for primary object

    1 -

    2 3

    1 2

    STANDARDCONFIGURATION

    REMARKS

    Optionalfunction

    No. ofinstances

    Alternative function to be dened when ordering

    OR

    Io/Uo

    Calculatedvalue

    3

    RL

    ClearESCI

    O

    Conguration ASystemHMITimeAuthorization

    RL

    ClearESCI

    O

    U12 0. 0 kVP 0.00 kWQ 0.00 kVAr

    IL2 0 A

    A

    With in-zone power transformer supportRED615

    Sum of phase currents

    I

    - I, Io- Limit value supervision- Load prole record- Symmetrical components

    4

    -

    A

    PCSPCS

    OPTSOPTM

    2TCSTCM

    2I2>46

    3I>>>50P/51P

    2Master Trip

    Lockout relay94/86

    3I>/Io>BF51BF/51NBF

    3I2f>68

    3I>51P-1

    23I>>

    51P-23dI>L87L

    MCS 3IMCS 3I

    BSTBST

    PHIZHIZ

    18MAPMAP

    3I

    IoI

    3I

    GUID-78F52211-9D37-4A2F-9527-CD61BDEA68A2 V1 EN

    Figure 11: Functionality overview for standard configuration A

    3.3.2.1 Default I/O connectionsConnector pins for each input and output are presented in the IED physicalconnections section.

    1MRS756498 K Section 3RED615 standard configurations

    RED615 35Application Manual

  • Table 11: Default connections for binary inputsBinary input DescriptionX110-BI2 External start of breaker failure protectionX110-BI3 Setting group changeX110-BI4 Binary signal transfer inputX110-BI5 Disconnector open/truck inX110-BI6 Disconnector open/truck outX110-BI7 Earth-switch closeX110-BI8 Earth-switch openX120-BI1 Blocking input for general useX120-BI2 Circuit breaker closeX120-BI3 Circuit breaker openX120-BI4 Lockout reset

    Table 12: Default connections for binary outputsBinary input DescriptionX100-PO1 Close circuit breakerX100-PO2 Breaker failure backup trip to upstream breakerX100-SO1 Line differential protection trip alarmX100-SO2 Protection communication failure or differential protection not availableX100-PO3 Open circuit breaker/trip 1X100-PO4 Open circuit breaker/trip 2X110- SO1 Upstream overcurrent blockingX110- SO2 Backup protection operatedX110- SO3 Binary transfer signal

    Table 13: Default connections for LEDsLED Description1 Line differential protection biased stage operate2 Line differential protection instantaneous stage operate3 Line differential protection is not available4 Protection communication failure5 Current transformer failure detected6 Phase or negative sequence component over current7 Breaker failure operate8 Disturbance recorder triggered9 Trip circuit supervision alarm10 Binary signal transfer receive11 Binary signal transfer send

    Section 3 1MRS756498 KRED615 standard configurations

    36 RED615Application Manual

  • 3.3.2.2 Default disturbance recorder settings

    Table 14: Default disturbance recorder analog channelsChannel Description1 IL12 IL23 IL34 Io5 -6 -7 -8 -9 -10 -11 -12 -

    Table 15: Default disturbance recorder binary channelsChannel ID text Level trigger mode1 LNPLDF1 - start Positive or Rising2 LNPLDF1 - operate Positive or Rising3 PHIPTOC1 - start Positive or Rising4 PHHPTOC1 - start Positive or Rising5 PHHPTOC2 - start Positive or Rising6 PHLPTOC1 - start Positive or Rising7 NSPTOC1 - start Positive or Rising8 NSPTOC2 - start Positive or Rising9 CCBRBRF1 - trret Level trigger off10 CCBRBRF1 - trbu Level trigger off11 PHIPTOC1 - operate Level trigger off

    PHHPTOC1 - operatePHHPTOC2 - operatePHLPTOC1 - operate

    12 NSPTOC1 - operate Level trigger offNSPTOC2 - operate

    13 INRPHAR1 - blk2h Level trigger off14 PCSRTPC1 - alarm Level trigger off15 LNPLDF1 - rstd2h Level trigger off16 LNPLDF1 - prot not active Level trigger off

    Table continues on next page

    1MRS756498 K Section 3RED615 standard configurations

    RED615 37Application Manual

  • Channel ID text Level trigger mode28 X110BI4 - binary transfer Level trigger off29 X110BI2 - ext ccbrbrf start Level trigger off30 X120BI3 - CB opened Level trigger off31 X120BI2 - CB closed Level trigger off32 X120BI1 - ext OC blocking Level trigger off

    3.3.3 Functional diagramsThe functional diagrams describe the default input, output, alarm LED and function-to-function connections. The default connections can be viewed and changed withPCM600 according to the application requirements.The analog channels have fixed connections to the different function blocks insidethe IEDs standard configuration. However, the 12 analog channels available forthe disturbance recorder function are freely selectable as a part of the disturbancerecorders parameter settings.The phase currents to the IED are fed from a current transformer. The residualcurrent to the IED is fed from either residually connected CTs, an external corebalance CT, neutral CT or internally calculated.The IED offers six different settings group which can be set based on individualneeds. Each group can be activated or deactivated using the setting group settingsavailable in the IED or via binary input.Depending on the communication protocol the required function block needs to beinitiated in the configuration. The Application Configuration tool also includesfixed Boolean signals TRUE and FALSE which can be used as per the applicationneed.

    3.3.3.1 Functional diagrams for protectionThe functional diagrams describe the IED's protection functionality in detail andaccording to the factory set default connections.The line current differential function LNPLDF1 is intended to be the mainprotection offering exclusive unit protection for the power distribution lines orcables. The stabilized low stage can be blocked if the current transformer failure isdetected. The operate value of the instantaneous high stage can be multiplied bypredefined settings, if ENA_MULT_HS input is activated. In this configuration, it isactivated by the open status information of the remote-end circuit breaker and earth-switch, and if the disconnector is not in the intermediate position. The intention ofthis connection is to lower the setting value of the instantaneous high stage bymultiplying with the setting High Op value Mult, in case of internal fault.

    Section 3 1MRS756498 KRED615 standard configurations

    38 RED615Application Manual

  • Alarm LED3 informs when the line differential is not available possibly due to afailure in protection communication, or if the function is set in a test mode.Four non-directional overcurrent stages are offered for overcurrent and short-circuit protection. The non-directional instantaneous stage PHIPTOC1 can beblocked by energizing the binary input X120:BI1. The instantaneous and first highstage are blocked by activation of line differential protection.

    LNPLDF1BLOCKBLOCK_LSENA_MULT_HS

    OPERATESTART

    STR_LS_LOCSTR_LS_REMOPR_LS_LOCOPR_LS_REMOPR_HS_LOCOPR_HS_REMBLKD2H_LOCBLKD2H_REMPRO_ACTIVE

    ORB1B2

    O

    ORB1B2

    O

    ORB1B2

    O

    NOTIN OUT

    ORB1B2

    O

    ORB1B2

    O

    REMOTE_FEEDER_READY

    LNPLDF1_OPERATE

    LNPLDF1_PROT_ACTIVE

    LNPLDF1_PROT_ACTIVE

    CCRDIF1_FAIL

    REMOTE_CB_OPEN

    LNPLDF1_OPR_LS_LOC

    LNPLDF1_OPR_LS_LOC

    LNPLDF1_OPR_LS_REM

    LNPLDF1_OPR_LS_REM

    LNPLDF1_OPR_HS_LOC

    LNPLDF1_OPR_HS_LOC

    LNPLDF1_OPR_HS_REM

    LNPLDF1_OPR_HS_REM

    LNPLDF1_RSTD2H_LOC

    LNPLDF1_RSTD2H_LOC

    LNPLDF1_RSTD2H_REM

    LNPLDF1_RSTD2H_REM

    REMOTE_CCRDIF_FAIL

    LNPLDF_LS_OPERATE

    LNPLDF_HS_OPERATE

    LNPLDF1_PROT_NOT_ACTIVE

    LNPLDF1_START

    LNPLDF_RSTD2H

    GUID-214BD8DC-0A09-4BD2-BF07-0AD63322734C V1 EN

    Figure 12: Line differential protection functions

    1MRS756498 K Section 3RED615 standard configurations

    RED615 39Application Manual

  • PHIPTOC1BLOCKENA_MULT

    OPERATESTART

    PHLPTOC1BLOCKENA_MULT

    OPERATESTART

    PHHPTOC1BLOCKENA_MULT

    OPERATESTART

    PHHPTOC2BLOCKENA_MULT

    OPERATESTART

    ORB1B2

    O

    OR6B1B2B3B4B5B6

    O

    PHIPTOC1_OPERATE

    PHIPTOC1_OPERATE

    PHLPTOC1_OPERATE

    PHLPTOC1_OPERATE

    PHHPTOC1_OPERATE

    PHHPTOC1_OPERATE

    PHHPTOC2_OPERATE

    PHHPTOC2_OPERATE

    X120_BI1_EXT_OC_BLOCKING

    INRPHAR1_BLK2H

    LNPLDF1_PROT_ACTIVE

    LNPLDF1_PROT_ACTIVE

    PHIPTOC1_START

    PHHPTOC1_START

    PHHPTOC2_START

    PHxPTOC_OPERATE

    PHLPTOC1_START

    GUID-1EC75CEC-F8EC-4181-9EA6-B077515E9347 V1 EN

    Figure 13: Overcurrent protection functionsThe upstream blocking both from the start of the instantaneous and the high stageovercurrent protection function is connected to the binary output X110:SO1. Thisoutput can be used to send a blocking signal to the relevant overcurrent protectionstage of the IED at the upstream bay.

    OR6B1B2B3B4B5B6

    O UPSTREAM_OC_BLOCKINGPHIPTOC1_STARTPHHPTOC1_STARTPHHPTOC2_START

    GUID-53A4ACB1-873E-4AA6-A478-536C7BA0E03F V1 EN

    Figure 14: Upstream blocking logicThe inrush detection block's (INRPHAR1) output BLK2H offers the possibility toeither block the function or multiply the active settings for any of the availableovercurrent function blocks.

    INRPHAR1BLOCK BLK2H INRPHAR1_BLK2H

    GUID-76C18EB4-E3EC-427D-B47A-9E1BFD2DBA5E V1 EN

    Figure 15: Inrush detector functionTwo negative sequence overcurrent stages NSPTOC1 and NSPTOC2 are providedfor phase unbalance protection. These functions are used to protect the feederagainst phase unbalance. Both the negative sequence overcurrent protections areblocked in case of detection in failure in secondary circuit of current transformer.

    Section 3 1MRS756498 KRED615 standard configurations

    40 RED615Application Manual

  • NSPTOC1BLOCKENA_MULT

    OPERATESTART

    NSPTOC2BLOCKENA_MULT

    OPERATESTART

    ORB1B2

    O

    NSPTOC1_OPERATE

    NSPTOC1_OPERATE

    NSPTOC2_OPERATE

    NSPTOC2_OPERATE

    CCRDIF1_FAIL

    CCRDIF1_FAIL

    NSPTOC_OPERATE

    NSPTOC1_START

    NSPTOC2_START

    GUID-80E6D94D-4D46-4B79-8383-3C6C3577E763 V1 EN

    Figure 16: Negative sequence overcurrent protection function

    The overcurrent protection and negative sequence overcurrentprotection are used as backup protection against line differentialprotection.

    The backup protection operated information is available at binary outputX110:SO2 which can be used for external alarm purpose.The breaker failure protection CCBRBRF1 is initiated via the START input bynumber of different protection functions available in the IED. The breaker failureprotection function offers different operating modes associated with the circuitbreaker position and the measured phase and residual currents.The breaker failure protection function has two operating outputs: TRRET andTRBU. The TRRET operate output is used for retripping its own breaker throughTRPPTRC2_TRIP. The TRBU output is used to give a backup trip to the breakerfeeding upstream. For this purpose, the TRBU operate output signal is connected tothe binary output X100:PO2.

    CCBRBRF1BLOCKSTARTPOSCLOSECB_FAULT

    CB_FAULT_ALTRBU

    TRRET

    OR6B1B2B3B4B5B6

    O

    OR6B1B2B3B4B5B6

    O CCBRBRF1_TRBU

    X120_BI2_CB_CLOSED

    PHIPTOC1_OPERATE

    PHLPTOC1_OPERATE

    PHHPTOC1_OPERATE

    NSPTOC1_OPERATE

    PHHPTOC2_OPERATE

    NSPTOC2_OPERATE

    LNPLDF1_OPERATE

    CCBRBRF1_TRRET

    X110_BI2_EXT_CCBRBRF_START

    GUID-ED51D248-8DD6-45C2-8B99-8A4885023125 V1 EN

    Figure 17: Circuit breaker failure protection functionThe operate signals from the protection functions are connected to the two triplogics: TRPPTRC1 and TRPPTRC2. The output of these trip logic functions isavailable at binary outputs X100:PO3 and X100:PO4. The trip logic functions are

    1MRS756498 K Section 3RED615 standard configurations

    RED615 41Application Manual

  • provided with a lockout and latching function, event generation and the trip signalduration setting. If the lockout operation mode is selected, binary input X120:BI4can be assigned to RST_LKOUT input of both the trip logic to enable external resetwith a push button.

    TRPPTRC1BLOCKOPERATERST_LKOUT

    TRIPCL_LKOUT

    OR6B1B2B3B4B5B6

    O

    OR6B1B2B3B4B5B6

    OTRPPTRC1_TRIP

    PHIPTOC1_OPERATEPHLPTOC1_OPERATEPHHPTOC1_OPERATE

    NSPTOC1_OPERATEPHHPTOC2_OPERATE

    NSPTOC2_OPERATE

    LNPLDF1_OPERATEX120_BI4_RST_LOCKOUTGUID-8768D080-5A99-4E2D-8E01-FDD152866526 V1 EN

    Figure 18: Trip logic TRPPTRC1

    OR6B1B2B3B4B5B6

    O

    TRPPTRC2BLOCKOPERATERST_LKOUT

    TRIPCL_LKOUT

    OR6B1B2B3B4B5B6

    OTRPPTRC2_TRIP

    PHIPTOC1_OPERATEPHLPTOC1_OPERATEPHHPTOC1_OPERATE

    NSPTOC1_OPERATEPHHPTOC2_OPERATE

    NSPTOC2_OPERATE

    LNPLDF1_OPERATE

    X120_BI4_RST_LOCKOUTCCBRBRF1_TRRET

    GUID-8EC8BF92-8C1B-4315-A462-6A661E013089 V1 EN

    Figure 19: Trip logic TRPPTRC2

    3.3.3.2 Functional diagrams for disturbance recorderThe START and the OPERATE outputs from the protection stages are routed totrigger the disturbance recorder or, alternatively, only to be recorded by thedisturbance recorder depending on the parameter settings. Additionally, theselected signals from different functions and the few binary inputs are alsoconnected to the disturbance recorder.

    Section 3 1MRS756498 KRED615 standard configurations

    42 RED615Application Manual

  • RDRE1

    RDRE

    C1C2C3C4C5C6C7C8C9C10C11C12C13C14C15C16C17C18C19C20C21C22C23C24C25C26C27C28C29C30C31C32C33C34C35C36C37C38C39C40C41C42C43C44C45C46C47C48C49C50C51C52C53C54C55C56C57C58C59C60C61C62C63C64

    TRIGGERED

    OR6B1B2B3B4B5B6

    O

    ORB1B2

    O

    CCBRBRF1_TRBU

    X120_BI3_CB_OPENEDX120_BI2_CB_CLOSED

    PHIPTOC1_OPERATE

    PHLPTOC1_OPERATE

    PHHPTOC1_OPERATE

    NSPTOC1_OPERATE

    PHHPTOC2_OPERATE

    NSPTOC2_OPERATE

    LNPLDF1_OPERATE

    CCBRBRF1_TRRET

    X120_BI1_EXT_OC_BLOCKING

    INRPHAR1_BLK2H

    X110_BI4_BINARY_TRANSFERX110_BI2_EXT_CCBRBRF_START

    LNPLDF1_PROT_NOT_ACTIVE

    PCSRTPC1_ALARM

    PHIPTOC1_STARTPHHPTOC1_STARTPHHPTOC2_START

    LNPLDF1_START

    PHLPTOC1_STARTNSPTOC1_STARTNSPTOC2_START

    LNPLDF_RSTD2H

    DISTURB_RECORD_TRIGGERED

    GUID-7A54A97D-ED30-4EF9-A3CF-F0F21EA72AAB V1 EN

    Figure 20: Disturbance recorder

    3.3.3.3 Functional diagrams for condition monitoringCCRDIF1 detects failures in the current measuring circuits. When a failure isdetected, it can be used to block the current protection functions that measure thecalculated sequence component currents or residual current to avoid unnecessaryoperation.

    CCRDIF1BLOCK FAIL

    ALARMCCRDIF1_FAILCCRDIF1_ALARM

    GUID-3C8B9191-F624-40FF-BE4E-54B68FC6760F V1 EN

    Figure 21: Current circuit supervision functionTwo separate trip circuit supervision functions are included: TCSSCBR1 for poweroutput X100:PO3 and TCSSCBR2 for power output X100:PO4. Both functions areblocked by the Master Trip TRPPTRC1 and TRPPTRC2 and the circuit breakeropen signal.

    1MRS756498 K Section 3RED615 standard configurations

    RED615 43Application Manual

  • It is assumed that there is no external resistor in the circuit breakertripping coil circuit connected in parallel with the circuit breakernormally open auxiliary contact.

    Set the parameters for TCSSCBR1 properly.

    TCSSCBR1BLOCK ALARM

    TCSSCBR2BLOCK ALARM

    ORB1B2

    O

    TCSSCBR1_ALARM

    TCSSCBR1_ALARM

    TCSSCBR2_ALARM

    TCSSCBR2_ALARM

    TCSSCBR_BLOCKING

    TCSSCBR_BLOCKING

    TCSSCBR_ALARM

    GUID-35D08B4E-51FC-4118-AD4C-0C046AA23550 V1 EN

    Figure 22: Trip circuit supervision function

    OR6B1B2B3B4B5B6

    OTRPPTRC2_TRIP

    X120_BI3_CB_OPENED

    TRPPTRC1_TRIP TCSSCBR_BLOCKING

    GUID-5EF1437A-0FC1-43BD-8BCA-4525748A3F10 V1 EN

    Figure 23: Logic for blocking of trip circuit supervisionThe protection communication supervision function PCSRTPC1 is used in theconfiguration to block the operation of the line differential function. This way, themalfunction of the line differential is prevented. The activation of binary signaltransfer outputs during protection communication failure also blocked. These aredone internally without connections in the configurations. The protectioncommunication supervision alarm is connected to alarm LED 4, disturbancerecorder and binary output X100:SO2.

    PCSRTPC1OK

    WARNINGALARMCOMM

    PCSRTPC1_ALARM

    GUID-1C5B59EA-A7A6-4ED4-AA51-392008C46EBA V1 EN

    Figure 24: Protection communication supervision function

    Section 3 1MRS756498 KRED615 standard configurations

    44 RED615Application Manual

  • The binary signal transfer function BSTGGIO1 is used for changing any binaryinformation which can be used for example, in protection schemes, interlockingand alarms. There are eight separate inputs and corresponding outputs available.In this configuration, one physical input X110:BI4 is connected to the binary signaltransfer channel one. Local feeder ready and local circuit breaker open informationare connected to the BSTGGIO input 6 and 7. These are interlocking informationfrom control logic. The information of detected current transformer fault isconnected to input 8.As a consequence of sending interlocking information to remote end, also receivingof same information locally is needed. Therefore, remote feeder ready, remotecircuit breaker open and remote current transformer failure are connected to thebinary signal transfer function outputs. Also the remote binary transfer outputsignal is connected to the binary output X110:SO3.

    BSTGGIO1SEND_SIG_1SEND_SIG_2SEND_SIG_3SEND_SIG_4SEND_SIG_5SEND_SIG_6SEND_SIG_7SEND_SIG_8

    RECV_SIG_1RECV_SIG_2RECV_SIG_3RECV_SIG_4RECV_SIG_5RECV_SIG_6RECV_SIG_7RECV_SIG_8SEND_SIG_ARECV_SIG_A

    REMOTE_BINARY_TRANSFER

    REMOTE_FEEDER_READYLOCAL_FEEDER_READY

    CCRDIF1_FAIL

    X110_BI4_BINARY_TRANSFER

    REMOTE_CB_OPENCBXCBR1_OPENPOSREMOTE_CCRDIF_FAILBSTGGIO1_SEND_SIG_ABSTGGIO1_RECV_SIG_A

    GUID-6E428F3A-5652-4573-BFEC-71E5893CE434 V1 EN

    Figure 25: Binary signal transfer function

    3.3.3.4 Functional diagrams for control and interlockingTwo types of disconnector and earthing switch function blocks are available.DCSXSWI1...3 and ESSXSWI1...2 are status only type, and DCXSWI1...2 andESXSWI1 are controllable type. By default, the status only blocks are connected inthe standard configuration. The disconnector (CB truck) and line side earthingswitch status information is connected to DCSXSWI1 and ESSXSI1.

    DCSXSWI1POSOPENPOSCLOSE

    OPENPOSCLOSEPOS

    OKPOS DCSXSWI1_OKPOS

    X110_BI6_CB_TRUCK_IN_TESTX110_BI5_CB_TRUCK_IN_SERVICE

    GUID-42D1B156-F8DC-47AE-8B49-689E1A4F9930 V1 EN

    Figure 26: Disconnector 1 control logic

    ESSXSWI1POSOPENPOSCLOSE

    OPENPOSCLOSEPOS

    OKPOS

    ESSXSWI1_OPENPOSX110_BI8_ES1_OPENEDX110_BI7_ES1_CLOSED

    GUID-1FCBEC78-041D-49E7-8440-F24B71B0979E V1 EN

    Figure 27: Earth-switch 1 control logic

    1MRS756498 K Section 3RED615 standard configurations

    RED615 45Application Manual

  • The circuit breaker closing is enabled when the ENA_CLOSE input is activated.The input can be activated by the configuration logic, which is a combination ofthe disconnector or circuit breaker truck and earth-switch position status, status ofthe trip logics and remote feeder position indication. Master trip logic, disconnectorand earth-switch statuses are local feeder ready information to be sent for theremote end.The OKPOS output from DCSXSWI defines if the disconnector or circuit breakertruck is either open (in test position) or close (in service position). This output,together with the open earth-switch and non-active trip signals, activates the close-enable signal to the circuit breaker control function block. The open operation forthe circuit breaker is always enabled.

    If REMOTE_FEEDER_READY information is missing, forexample, in case of protection communication not connected, itdisables the circuit breaker closing in the local IED.

    CBXCBR1POSOPENPOSCLOSEENA_OPENENA_CLOSEBLK_OPENBLK_CLOSEAU_OPENAU_CLOSEITL_BYPASS

    SELECTEDEXE_OPEXE_CL

    OPENPOSCLOSEPOS

    OKPOSOPEN_ENAD

    CLOSE_ENAD

    FALSE

    X120_BI3_CB_OPENEDX120_BI2_CB_CLOSED

    CBXCBR1_ENA_CLOSECBXCBR1_EXE_CLCBXCBR1_EXE_OP

    TRUE

    CBXCBR1_AU_CLOSECBXBCR1_AU_OPEN

    CBXCBR1_OPENPOS

    GUID-0644C4E5-EBFA-477B-90B0-7D22E168972A V1 EN

    Figure 28: Circuit breaker 1 control logic

    Any additional signals required by the application can be connectedfor opening and closing of circuit breaker.

    ORB1B2

    O CB_CLOSE_COMMANDCBXCBR1_EXE_CL

    GUID-31AF7051-A62F-4596-B317-36090DEE3235 V1 EN

    Figure 29: Signals for closing coil of circuit breaker 1

    OR6B1B2B3B4B5B6

    O CB_OPEN_COMMANDTRPPTRC1_TRIPCBXCBR1_EXE_OP

    GUID-444B84F9-F5D9-4BA4-9EDC-344CD77F0ED7 V1 EN

    Figure 30: Signals for opening coil of circuit breaker 1

    Section 3 1MRS756498 KRED615 standard configurations

    46 RED615Application Manual

  • ANDB1B2

    O CBXCBR1_ENA_CLOSEREMOTE_FEEDER_READYLOCAL_FEEDER_READY

    NOTIN OUT

    AND6B1B2B3B4B5B6

    O

    NOTIN OUTTRPPTRC2_TRIP

    TRPPTRC1_TRIP

    LOCAL_FEEDER_READYDCSXSWI1_OKPOSESSXSWI1_OPENPOS

    GUID-48415567-5620-4D8C-BEDE-545846CBAB67 V1 EN

    Figure 31: Circuit breaker 1 close enable logicThe configuration includes logic for generating circuit breaker external closing andopening command with the IED in local or remote mode.

    Check the logic for the external circuit breaker closing commandand modify it according to the application.

    Connect the additional signals for closing and opening of the circuitbreaker in local or remote mode, if applicable for the application.

    ANDB1B2

    O

    ANDB1B2

    O

    ORB1B2

    O

    FALSE

    FALSE

    CBXCBR1_AU_CLOSE

    CONTROL_LOCAL

    CONTROL_REMOTE

    GUID-546ECBD3-B766-45AF-9FF5-948DCA545C6F V1 EN

    Figure 32: External closing command for circuit breaker 1AND

    B1B2

    O

    ANDB1B2

    O

    ORB1B2

    O

    FALSE

    FALSE

    CBXBCR1_AU_OPEN

    CONTROL_LOCAL

    CONTROL_REMOTE

    GUID-361E5BC0-42E9-49D8-ABCE-8677BFA017A1 V1 EN

    Figure 33: External opening command for circuit breaker 1

    3.3.3.5 Functional diagrams for measurement functionsThe phase current inputs to the IEDare measured by the three-phase currentmeasurement function CMMXU1. The current input is connected to the X120 cardin the back panel. The sequence current measurement CSMSQI1 measures thesequence current.

    1MRS756498 K Section 3RED615 standard configurations

    RED615 47Application Manual

  • The measurements can be seen in the LHMI and they are available by using themeasurement option in the menu selection. Based on the settings, function blockscan generate low alarm or warning and high alarm or warning signals for themeasured current values.The load profile function LDPMSTA1 is included in the measurements sheet.LDPMSTA1 offers the ability to observe the loading history of the correspondingfeeder.

    CMMXU1BLOCK HIGH_ALARM

    HIGH_WARNLOW_WARN

    LOW_ALARM

    GUID-8B4CEF31-8A1D-40B8-9FCB-E9D2905CA6D5 V1 EN

    Figure 34: Current measurement: Three-phase current measurement

    CSMSQI1

    GUID-60EF9EC2-4E85-4236-A57D-4D663A2B340A V1 EN

    Figure 35: Current measurement: Sequence current measurement

    FLTMSTA1BLOCKCB_CLRD

    GUID-7680B583-F7CC-4C51-B4F4-07071AA72925 V1 EN

    Figure 36: Other measurement: Data monitoring

    LDPMSTA1RSTMEM MEM_WARN

    MEM_ALARM

    GUID-D1F501B2-6430-4E72-A889-3B5838D45918 V1 EN

    Figure 37: Other measurement: Load profile record

    Section 3 1MRS756498 KRED615 standard configurations

    48 RED615Application Manual

  • 3.3.3.6 Functional diagrams for I/O and alarm LEDs

    X110_BI3_SG_CHANGE

    X110_BI6_CB_TRUCK_IN_TEST

    X110_BI5_CB_TRUCK_IN_SERVICE

    X110_BI8_ES1_OPENED

    X110_BI7_ES1_CLOSED

    X110_BI4_BINARY_TRANSFER

    X110_BI2_EXT_CCBRBRF_START

    X110 (BIO).X110-Input 2

    X110 (BIO).X110-Input 3

    X110 (BIO).X110-Input 4

    X110 (BIO).X110-Input 5

    X110 (BIO).X110-Input 6

    X110 (BIO).X110-Input 7

    X110 (BIO).X110-Input 8GUID-5FB90F71-13E8-4A40-8F9E-EB5131350578 V1 EN

    Figure 38: Binary inputs - X110 terminal block

    X120_BI3_CB_OPENED

    X120_BI2_CB_CLOSED

    X120_BI4_RST_LOCKOUT

    X120_BI1_EXT_OC_BLOCKING

    X120 (AIM).X120-Input 1

    X120 (AIM).X120-Input 2

    X120 (AIM).X120-Input 3

    X120 (AIM).X120-Input 4GUID-02B39637-DED0-4D63-A9FE-A4FB30994B9E V1 EN

    Figure 39: Binary inputs - X120 terminal block

    BACKUP_PROT_OPERATE_PULSE

    UPSTREAM_OC_BLOCKING

    REMOTE_BINARY_TRANSFER

    X110 (BIO).X110-SO1

    X110 (BIO).X110-SO2

    X110 (BIO).X110-SO3GUID-65B379D4-FE8D-45EC-8ACF-933E37B249F5 V1 EN

    Figure 40: Binary outputs - X110 terminal block

    1MRS756498 K Section 3RED615 standard configurations

    RED615 49Application Manual

  • CB_CLOSE_COMMAND

    CCBRBRF1_TRBU

    DIFFERENTIAL_OPERATE_PULSE

    LNPLDF_NOT_ACTIVE_OR_PCSRTPC_ALARM

    CB_OPEN_COMMAND

    TRPPTRC2_TRIP

    X100 (PSM).X100-PO1

    X100 (PSM).X100-PO2

    X100 (PSM).X100-SO1

    X100 (PSM).X100-SO2

    X100 (PSM).X100-PO3

    X100 (PSM).X100-PO4GUID-1D17D025-275D-47B2-90D0-F95635D6CEFD V1 EN

    Figure 41: Binary outputs - X100 terminal block

    Section 3 1MRS756498 KRED615 standard configurations

    50 RED615Application Manual

  • LED1OKALARMRESET

    LED2OKALARMRESET

    LED3OKALARMRESET

    LED4OKALARMRESET

    LED5OKALARMRESET

    LNPLDF_LS_OPERATE

    LNPLDF_HS_OPERATE

    LNPLDF1_PROT_NOT_ACTIVE

    PCSRTPC1_ALARM

    CCRDIF1_ALARM

    GUID-DAF8EA20-89B5-48D6-B6E7-5B844BFD7A7B V1 EN

    1MRS756498 K Section 3RED615 standard configurations

    RED615 51Application Manual

  • LED6OKALARMRESET

    LED7OKALARMRESET

    LED8OKALARMRESET

    LED9OKALARMRESET

    LED10OKALARMRESET

    LED11OKALARMRESET

    CCBRBRF1_TRBU

    BACKUP_PROT_OPERATE

    DISTURB_RECORD_TRIGGERED

    BSTGGIO1_SEND_SIG_A

    BSTGGIO1_RECV_SIG_A

    TCSSCBR_ALARM

    GUID-8A7C2989-86B4-40D7-871F-4AFCB28E598D V1 EN

    Figure 42: Default LED connection

    3.3.3.7 Functional diagrams for other timer logicsThe configuration also includes line differential operate, inactive communicationand backup protection operate logic. The operate logics are connected to the pulsetimer TPGAPC1 for setting the minimum pulse length for the outputs. The outputfrom TPGAPC1 is connected to the binary outputs.

    ORB1B2

    O

    ORB1B2

    O

    TPGAPC1IN1IN2

    OUT1OUT2

    DIFFERENTIAL_OPERATE_PULSELNPLDF_NOT_ACTIVE_OR_PCSRTPC_ALARM

    LNPLDF_LS_OPERATELNPLDF_HS_OPERATE

    LNPLDF1_PROT_NOT_ACTIVEPCSRTPC1_ALARM

    GUID-F96BFC4E-C609-4176-901A-5B9EEC2CFAA9 V1 EN

    Figure 43: Timer logic for differential operate and communication not active

    Section 3 1MRS756498 KRED615 standard configurations

    52 RED615Application Manual

  • TPGAPC2IN1IN2

    OUT1OUT2

    ORB1B2

    O

    BACKUP_PROT_OPERATE_PULSE

    PHxPTOC_OPERATENSPTOC_OPERATE

    BACKUP_PROT_OPERATE

    BACKUP_PROT_OPERATE

    GUID-CB98021B-214D-4A49-816D-91CDE2D603C1 V1 EN

    Figure 44: Timer logic for backup protection operate pulse

    3.3.3.8 Other functionsThe configuration includes few instances of multi-purpose protection functionMAPGAPC, high impedance fault detection function PHIZ, runtime counterMDSOPT and few instances of different types of timers and control functions.These functions are not included in application configuration but they can be addedbased on the system requirements.

    3.4 Standard configuration B3.4.1 Applications

    The standard configuration for line current differential protection includingdirectional earth-fault protection and autoreclosing is mainly intended for cablefeeder applications in the distribution networks. The standard configuration for linecurrent differential protection includes support for in-zone transformers. Theconfiguration also includes additional options for selecting earth-fault protectionbased on admittance, wattmetric or harmonic principles.The IED with a standard configuration is delivered from the factory with defaultsettings and parameters. The end user flexibility for incoming, outgoing andinternal signal designation within the IED enables this configuration to be furtheradapted to different primary circuit layouts and the related functionality needs bymodifying the internal functionality using PCM600.

    1MRS756498 K Section 3RED615 standard configurations

    RED615 53Application Manual

  • 3.4.2 Functions

    RED615 AT REMOTE

    END

    CONDITION MONITORING AND SUPERVISION

    COMMUNICATION

    Protocols: IEC 61850-8-1 Modbus

    IEC 60870-5-103 DNP3

    Interfaces: Ethernet: TX (RJ45), FX (LC) Serial: Serial glass ber (ST), RS-485, RS-232/485 D-sub 9, IRIG-B

    1 0 1 0 0 0 1 1 0 0 1 1 0 01 0 1 1 0 0 1 0 1 1 1 0 0 1 01 1 0 0 1 1 1 0 1 1 0 1 01 0 1 1 0 1 1 0 1 1 0 1 0 01 0 1 0 0 0 1 1 0 0 1 1 0 0 1 0 1 0 0 0 1 1 0 0 1 1 0 01 0 1 1 0 0 1 0 1 1 1 0 0 1 01 1 0 0 1 1 1 0 1 1 0 1 01 0 1 1 0 1 1 0 1 1 0 1 0 0

    ALSO AVAILABLE

    - Binary Signal Transfer function (BST)- Disturbance and fault recorder- Event log and recorded data- IED self-supervision - Local/Remote push button on LHMI- User management- Web HMI

    ORAND

    CONTROL AND INDICATION 1) MEASUREMENT

    LINE DIFFERENTIAL PROTECTION AND CONTROL IED

    PROTECTION LOCAL HMI

    Analog interface types 1)

    Current transformer

    Voltage transformer1) Conventional transformer inputs

    Object Ctrl 2) Ind 3)

    CB

    DC

    ES1) Check availability of binary inputs/outputs

    from technical documentation2) Control and indication function for

    primary object3) Status indication function for primary object

    1 -

    2 3

    1 2

    STANDARDCONFIGURATION

    REMARKS

    Optionalfunction

    No. ofinstances

    Alternative function to be dened when ordering