Ready to install Distribution boards, DIN rail mounted equipment,enclosures and connection systems
Contents
Isobar 4 distribution boardsand protective devices
Section one 7
Modular control products Section two 31
Unit mounted residual current devices
Section three 73
Unit mounted circuit breakers Section four 79
Connection systems Section five 113
Enclosures Section six 121
Technical data Section seven 133
Dimensions Section eight 163
Schneider Electric overview Section nine 197
Comprehensive quick reference index
Section ten 203
Isobar 4 Type A distribution board features
Fully type tested conditional short circuit rating of 16kA to BS EN 60439
High performance MCB 10kA BS 60898 15kA BS 60947-2 in B, C or D curve single and double pole
125A busbar rating
Isobar disconnection system ensuring unused outgoing ways are isolated
Option of switching outgoing neutral on all boards using distributed neutral kit
Terminal block for feeding up to 100A
Range of incomers: switch disconnectors, residual current devices, terminal blocks
Single pole RCBO for new or retrofit maintaining device density
Full range of device accessories and auxiliaries
Knockouts for cable gland and conduit
Isobar 4Type B distribution board with 125A incomer features
High performance MCB 10kA BS 60898 15kA BS 60947-2 in B, C or D curve 1, 2, 3 and 4 pole
Fully type tested conditional short circuit rating of 25kA to BS EN 60439 when fed by MCCB
250A busbar rating
Isobar disconnection system ensuring unused outgoing ways are isolated
Option of switching outgoing neutral using distributed neutral kit
Range of incomers
Removable insulated pan assembly
Fully shrouded neutral
Split neutral bars
Removable gland plates
Isobar 4Type B distribution board with 250A incomer features
High performance MCB 10kA BS 60898 15kA BS 60947-2 in B, C or D curve 1, 2, 3 or 4 pole
Fully type tested conditional short circuit rating of 25kA to BS EN 60439 when fed by MCCB
250A busbar rating
Isobar disconnection system ensuring unused outgoing ways are isolated
Option of switching outgoing neutral using distributed neutral kit
Range of incomers up to 250A
Removable insulated pan assembly
Fully shrouded neutral
Split neutral bars
Removable gland plates
Isobar 4 distribution boards and protective devices
Section one
Replacement items
Pan assemblies Type A and Type B 20Doors and covers Type A and Type B 20
Type A single phase
Distribution boards 8 - 9Incoming devices 10Outgoing devices 21 - 22Loose enclosures and accessories 11
Type B three phase
Distribution boards 12Incoming devices 14 - 15Outgoing devices 21 - 22Loose enclosures and accessories 16
7
Isobar 4SP&N type A distribution boards*
8
125A Standard A boards (incomers not included)
Part No. No. of outgoing Dimensions (mm)
ways Height Width Depth
MGAN6 6 264 260 127
MGAN9 9 264 315 127
MGAN12 12 264 370 127
MGAN15 15 264 450 127
*MGAN23 23 494 370 127
* 2 row unit.
125A Split load A boards (incomers not included)
Part No. Unprotected Protected Dimensions (mm)
outgoing ways outgoing ways Height Width Depth
MGAN46SL 4 6 264 450 127
MGAN48SL 4 8 264 450 127
MGAN66SL 6 6 264 450 127
Incomers:Switch disconnector see page 10Residual current device see page 10Terminal block see page 10
Outgoers:MCBs see page 21RCBOs see page 222 pole Vigi see page 23Auxiliaries see page 26
Distribution board accessories see page 11
Specification: Designed, manufactured and tested to
BS EN 60439-3 Unique Isobar outgoing phase connection link Busbar rating 125A Voltage rating 230/240Vac Distributed neutral allowing 2 pole switching at
any outgoing way using distributed neutral kit Ingress protection IP31 to BS EN 60529 Cable capacity neutral and earth bar 25mm2
DIN rail mounting with fully shrouded busbars Surface or flush mounting using flush
mounting kit, see page 11 5 single pole blanking plates Colour RAL 9001 epoxy powder coated IP2X with covers removed
Note: All devices are sold separately
MGAN6
MGAN66SL
* for use only with C60H range
Incomers:Switch disconnector see page 10Residual current device see page 10Terminal block see page 10
Outgoers:MCBs see page 21RCBOs see page 222 pole Vigi see page 23Auxiliaries see page 26Control and command devices see page 31
Distribution board accessories see page 11
Isobar 4SP&N type A distribution boards*
9
125A Dual incomer A boards (incomers not included)
Part No. No. of No. of Dimensions (mm)
outgoing ways outgoing ways
Circuit A Circuit B Height Width Depth
MGAN46DS 4 6 264 370 127
MGAN66DS 6 6 264 450 127
MGAN76DS 7 6 264 450 127
Loads should be evenly distributed across primary and secondary supplies.
125A Multi service A boards (incomers not included)
Part No. No. of Useable Dimensions (mm)
outgoing ways DIN rail
SP way Height Width Depth
MGAN416MS 4 8 264 370 127
MGAN520MS 5 10 264 450 127
MGAN716MS 7 8 264 450 127
MGAN96MS 9 3 264 370 127
MGAN912MS 9 6 264 450 127
MGAN1010MS 10 5 264 450 127
MGAN126MS 12 3 264 450 127
MGAN1228MS 12 14 494 370 127
2 row unit.
Specification: Designed, manufactured and tested to
BS EN 60439-3 Unique Isobar outgoing phase connection link Busbar rating 125A Voltage rating 230/240Vac Distributed neutral allowing 2 pole switching at
any outgoing way using distributed neutral kit Ingress protection IP31 to BS EN 60529 Cable capacity neutral and earth bar 25mm2
DIN rail mounting with fully shrouded busbars Surface or flush mounting using flush mounting
kit, see page 11 5 single pole blanking plates Colour RAL 9001 epoxy powder coated IP2X with covers removed
Note: All devices are sold separately
MGAN66DS
MGAN716MS
* for use only with C60H range
Isobar 4SP&N type A distribution boards - incomers
10
Part No. Rating Voltage No. of poles
MGTB1252 125A 230/240V 2
Part No. Rating Voltage Sensitivity
RMG630302 63A 230/240V 30mA
RMG631002 63A 230/240V 100mA
RMG633002 63A 230/240V 300mA
RMG800302 80A 230/240V 30mA
RMG801002 80A 230/240V 100mA
RMG803002 80A 230/240V 300mA
23111 80A 230/240V 100mA Time delayed
RMG1000302 100A 230/240V 30mA
RMG1001002 100A 230/240V 100mA
RMG1001002S 100A 230/240V 100mA Time delayed
RMG1003002 100A 230/240V 300mA
23116 100A 230/240V 300mA Time delayed
Part No. Rating Voltage No. of poles
MGI1252 125A 230/240V 2
Specification: BS EN 61008. Positive contact indication in accordance with BS 7671 Cable capacity 63A, 80A = up to 35mm2
100A = up to 50mm2
Terminal tightening torque 2Nm (35mm2), 3.5Nm (50mm2)
Specification: Direct connection incoming lug unit, two pole
suitable for use in any Isobar 4 A type board Cable capacity 50mm2
Terminal tightening torque 3.5Nm
BS EN 60947-3 AC22A Cable capacity 50mm2
Red toggle and PCI in accordance with BS 7671 Wiring Regulations
Tightening torque 3.5Nm
MGI1252
RMG630302
MGTB1252
Isobar 4MGA loose enclosures and
board accessories
11
Part Useable No. of Dimensions (mm)No. DIN rail rows
SP ways Height Width DepthMGN16DE 8 1 264 260 127MGN22DE 11 1 264 315 127MGN28DE 14 1 264 370 127MGN34DE 17 1 264 450 127*MGN56DE 28 2 494 370 127* 2 row unit.
ApplicationA range of steel enclosures using the Isobar 4 A board design suitable formounting DIN devices including MCBs, RCBOs and control and commandproducts.
Flush mounting kitPart No. For use with
MGAN6FK MGAN6, MGN16DE
MGAN9FK MGAN9
MGAN12FK MGAN12, MGAN46DS, MGAN416MS
MGAN15FK MGAN15, MGAN46SL, MGAN48SL, MGAN66SL, MGAN76DS, MGAN912MS,
MGAN1010MS, MGAN1228MS
MGAN24FK MGAN23, MGAN1228MS
Part No. SP circuits Description
MGANWL 15 A board spare outgoing way
self adhesive labels
Part No. Description
MGACE Clean earth facility for A type boards (6 hole).
Or can be used to comply with BS 7671 607-02
where the protective conductor ring shall be
separately connected at the distribution board.
Part No. Description
MGTB1001 100A terminal block for installation in Isobar boards as an
outgoing way. Supplied with identification labels.
Note: cable must be provided with local protection to
comply with BS 7671. Cable capacity 50mm2.
MGN56DE
MGANWL
MGTB1001
MGACE
Part No. Description
MGNA4 Distributed neutral kit for 4 way SP+N
MGNA6 Distributed neutral kit for 6 way SP+N
MGNA7 Distributed neutral kit for 7 way SP+N
MGNA9 Distributed neutral kit for 9 way SP+N
MGNA12 Distributed neutral kit for 12 way SP+N
MGNA15 Distributed neutral kit for 15 way SP+N
MGNA24 Distributed neutral kit for 24 way SP+N
NKIT Phase to neutral conversion kit (pack 4)Note: One pack included in a distributed neutral kit
Accessories:Part No. DescriptionMGBL Key lockBP Blanking plates 5 off
light grey
Specification: Folded sheet steel enclosure Ingress protection IP31 to
BS EN 60529 DIN rail Colour RAL 9001 epoxy
powder coated Surface or flush mounting using
flush mounting kit Earth bar 5 single pole blanking plates
Isobar 4TP&N type B distribution boards*
12
Standard B boardsPart No. No. of TP Dimensions (mm)
outgoing ways Height Width Depth
MGBN4 4 484 470 158
MGBN6 6 484 470 158
MGBN8 8 538 470 158
MGBN12 12 700 470 158
MGBN16 16 808 470 158
MGBN18 18 808 470 158
MGBN24 24 970 470 158
Split load B boardsThese are achieved by selecting any 2 Isobar B boards and joining with either
MGBNTJKN and feeding the top board via a outgoing 100 amp terminal block MGTB1001 for each phase
or use
MGBN63SPL split load kit which is supplied with a 63 amp C curve mcb
Incomers: see page 14
Outgoers: see page 21
Specification: Designed, manufactured and tested to
BS EN 60439-3 Unique Isobar outgoing phase connection link Busbar rating 250A Voltage rating 400/415Vac Distributed neutral allowing 2 or 4 pole switching
at any outgoing way using distributed neutral kit Ingress protection IP31 to BS EN 60529 Cable capacity neutral and earth bar 25mm2
100% rated DIN rail mounting with fully shrouded busbars Surface mounting Flush mounting available 5 single pole blanking plates supplied Colour RAL 9001 epoxy powder coated IP2X with covers removed
Note: All devices are sold separately
MGBN12
* for use only with C60H range
Multi service B boardsControl products can be added to any B type distribution board using a modular extension box
MGBNEX034N which will accept 17 single pole wide control products
MGBN12+MGBN8
MGBN8 + Multi service
Isobar 4TP&N type B distribution boards*
13
Heavy duty IP55 (125A) Part No. No. of outgoing Height Width Depth
ways TP
MGBN6HDGK 6 650 600 330
MGBN8HDGK 8 650 600 330
MGBN12HDGK 12 850 600 330
MGBN16HDGK 16 850 600 330
Specification: Designed, manufactured and tested to
BS EN 60439-3 Unique Isobar outgoing phase connection link Busbar ratings 125A Voltage rating 400/415Vac Distributed neutral allowing 2 or 4 pole switching
at any outgoing way using distributed neutral kit Ingress protection IP55 to BS EN 60529 Cable capacity neutral and earth bar 25mm2
DIN rail mounting with fully shrouded busbars Additional earth stud provided 5 single pole blanking plates Colour RAL 9001 epoxy powder coated Door can be left or right handed Key lockable enclosure as standard
Incomers:Switch disconnector see page 15Residual current devices see page 15Terminal blocks see page 15(Maximum 125A DIN rail mounted)
Outgoers:MCBs see page 21RCBOs see page 23
MGBN12HDGK
Note: All devices are sold separately
* for use only with C60H range
14
Isobar 4TP&N type B distribution boards - incomers
Residual current circuit breakers (RCCBS 63 - 160A)Part No. Rating Voltage Sensitivity No.
of poles
RMG630304 63A 415V 30mA 4
RMG631004 63A 415V 100mA 4
RMG633004 63A 415V 300mA 4
23146 63A 415V 300mA TD** 4
16261 80A 415V 30mA 4
23213 100A 415V 300mA 4
23227 100A 415V 300mA TD** 4
MGNI160RCCB* 160A 415V Adjustable 4
* Item is supplied with 270mm extension box, MCCB and Vigi.
** Time delay as an element of discrimination.
Switch disconnectors (160 - 250A)Part No. Rating Voltage No. of poles
MGNI1603 160A 415V 3+N
MGNI2003 200A 415V 3+N
MGNI2503 250A 415V 3+N
MGNI1604 160A 415V 4
MGNI2004 200A 415V 4
MGNI2254 225A 415V 4
MGNI2504 250A 415V 4
29243 Bare cable connector set 95mm2 160A set of 4
29260 Bare cable connector set 185mm2 250A set of 4
MGALK Allen key kit for fitting devices >160A
Devices fit directly into distribution board and are supplied with 270mm extension box.
Switch disconnectors Part No. Rating Voltage No. of poles
MGI1253N 125A 415V 3 + N
MGI1254 125A 415V 4
Specification: BS EN 60947-3 Copper pad for M8 lugs, tightening torque 15Nm Lockable in “ON” or “OFF” position Category of duty AC22 Positive contact indication in accordance with BS 7671
Specification: BS EN 61008 Positive contact indication in accordance with
BS 7671 Lockable in “ON” or “OFF” position Trip free mechanism Cable capacity 63A/80A - 35mm2, 100A - 50mm2
Terminal tightening torque 2Nm (63/80A), 3.5Nm (100A), 15Nm (160A)
Specification: BS EN 60947-3 Category of duty AC22 Positive contact indication in accordance with
BS 7671 Cable capacity 50mm2
Terminal tightening torque 3.5Nm Lockable in “ON” or “OFF” position
using ref: MGLAMGI1254
MGNI2504
MGBNI160RCCB
15
Isobar 4TP&N type B distribution boards - incomers
Terminal blocks (125/250A)Part No. Rating Voltage Notes
MGTB1254 125A 415V
MGNTB2504 250A 415V With extension box
MGNPBN250TB 250A 415V Without extension box
Dual source incomerPart No. Rating Voltage No. of poles
MGNDSI ≤125A 415V 4
Moulded case circuit breakers (MCCBs 100 - 250A)Part No. Rating Voltage No. of poles
MGNCB1004 100A 415V 4
MGNCB1604 160A 415V 4
MGNCB2004 200A 415V 4
MGNCB2504 250A 415V 4
MGALK Allen key kit for fitting devices >160A
Specification: Cable capacity: 125A - 50mm2
250A - M8 copper pad Terminal tightening torque: 125A - 3.5Nm
250A - 15Nm
To be used in dual source applications, with standby being a portable/fixedgenerator set or second transformer. Mechanically interlocks any combination ofthe following incoming 4P devices:
MGI1254 C120 C60
A padlocking facility enables either one or both to be locked in the OFF position orusing MGLA for locking ON. Front cover is lockable using MGBL.Cable capacity 50mm2.Supplied complete with board connection.
MGTB1254
MGNCB2004
MGNDSI
Devices fit directly into distribution board and aresupplied with 270mm extension box and terminalshield
Can be fitted with shunt trip, UVR and auxiliaryswitch. Refer to Compact NS Catalogue
Distribution boards fitted with a MCCB are suitable for installations with fault levels up to25kA
Specification: BS EN 60947-2 Category of duty AC22 Positive contact indication in accordance with
BS 7671 Cable capacity 50mm2 - 185mm2
Terminal tightening torque 100A - 10Nm, 160, 200 and 250A - 15Nm
To be ordered separately.
Surge arrestor kitPart No. Description
MGNPRD Supplied with extension box and protection device
16
Supplied with DIN rail, door and plain front cover
Part No. No. of No. of Dimensions (mm)
18mm rows
SP ways Height Width Depth
MGBN4SXP 34 2 484 470 158
MGBN8SXP 34 2 538 470 158
MGBN12SXP 51 3 700 470 158
MGBN16SXP 68 4 808 470 158
MGBN24SXP 85 5 970 470 158
Isobar 4MGB loose enclosures
Supplied with DIN rail, door and slotted front cover
Part No. No. of No. of Dimensions (mm)
18mm rows
SP ways Height Width Depth
MGBN4SXS 34 2 484 470 158
MGBN8SXS 34 2 538 470 158
MGBN12SXS 51 3 700 470 158
MGBN16SXS 68 4 808 470 158
MGBN24SXS 85 5 970 470 158
Specification: Ingress protection IP31 to BS EN 60529 Earth bar capacity 25mm2
Surface or flush mounting using flush mounting kit,see page 28
Colour RAL 9001 epoxy powder coated For enclosure accessories see page 18
For alternative enclosures see Section six, page 121.
ApplicationMGB loose enclosures are designed to accommodate DIN rail mounted products,primarily for control and metering. They may be mounted individually or attached tothe side of an MGB board of equivalent height using the side joining kitMGBNSJK.Alternatively they may be attached to the top or bottom of an MGB board using thetop/bottom joining kit MGBNTJKN.
MGBN8SXS
Type Part No.For panel mounting12 holes MG12EE18 holes MG18EE24 holes MG24EE36 holes MG36EE48 holes MG48EE56 holes MG56EE72 holes MG72EE
Extra terminal bar for earth For inside enclosure mounting Including support Current rating 200A 25mm2 holes
MGBN8SXP
17
Isobar 4B board extension boxes and metering
MGBNEXN
MGBNEX034N
MGBNEXA15N
ApplicationThe range of B boards are manufactured in a 270mm modular height thereof, toallow the user greater flexibility, so enabling the inclusion of single phasedistribution boards, multi service units, larger cabling arrangements etc.
Part No. DescriptionMGBNEXN Extension box with plain
front cover. Provides additional wiring space or a housing for control or metering equipment.
Part No. DescriptionMGBNEX034N Extension box with DIN
rail, slotted front cover and door. Provides space for up to 17 SPDIN mounted products.Includes gland plate andjoining kit.
Part No. DescriptionMGBNEXA15N A 15 way Isobar 4c
A type distribution boarddesigned for fixing directon to any Isobar 4cB type board.
Part No. DescriptionMGBN100CCI Provides contactor
control and isolation of Isobar 4cB type boards
Kit includes 100A contactor 240Vac coil (Part No. 15978,
see page 46 for details) Switch disconnector Extension box 270mm Interconnections 100A terminal block
MGBNKWH
Contactor incomer 100A
Part No. DescriptionMGBNKWH Extension box with
multi-function meter, CT’s, wiring loom and MCB to pick up voltage.
Meter provides Phase voltage kVArh Current Power factor kWh, kW per phase Pulsed output per kWh
Note: Voltage connection takes up 4 SP outgoing ways at bottom of stack
3 phase kWh metering
MGBN100CCI
18
Isobar 4TP&N type B distribution board accessories
Part No. Description SP circuitsMGBNWL B board front
cover way labels 72
Part No. DescriptionMGTB1001 100A terminal block for installation in Isobar boards as
an outgoing way. Supplied with identification labels. Note: cable must be provided with local protection tocomply with BS 7671. Cable capacity 50mm2.
Part No. DescriptionMGBL Door lock for A and B boards
new style square sliding catch MGK33 2 off spare keys for MGBL
Spare door catch
Part No. DescriptionBP 5 pole blanking plates (light grey).
Note: 1 off BP supplied with each distribution board.
Part No. DescriptionMGBNGPN Gland plate plain for B type distribution boardMGBNGPEXN Gland plate for Isobar extension box
Gland plate for B board with knock out
MGBNWL
100A outgoing terminal block
MGBL
BP
19
Isobar 4TP&N type B distribution board accessories
Part No. Description
MGNBCE7 for type B boards provides 7 clean earth or extra
neutral/earth holes.
MGNBCE25 25 hole
Clean earth facility
MGNB6
Part No. Description
MGBNTJKN Joining kit for two type B distribution boards mounted
above or below each other.
MGBNSJK Joining kit for two type B distribution boards mounted
side by side.
MGBN63SPL 63amp split load kit kit.
Single phasing kit (125/250A)Part No. Rating Voltage DescriptionMG125SPEV 125A 415V For 4P incomers up to 125AMG250SPEV 250A 415V For 4P incomers up to 250AConverts a TP&N B board incomer into single phase applications when used inconjunction with the above terminal blocks and switch disconnectors.
MG125SPEV MG250SPEV
MGBNSJK
Part No. Description
MGNB4 Distributed neutral kit for 4 way TP+N
MGNB6 Distributed neutral kit for 6 way TP+N
MGNB8 Distributed neutral kit for 8 way TP+N
MGNB12 Distributed neutral kit for 12 way TP+N
MGNB16 Distributed neutral kit for 16 way TP+N
MGNB18 Distributed neutral kit for 18 way TP+N
MGNB24 Distributed neutral kit for 24 way TP+N
NKIT Phase to neutral conversion kit (pack 4)Note: One pack included in a distributed neutral kit
20
Isobar 4Replacement pan assemblies, doors and covers
B board pan assemblyPart No. DescriptionMGBN4P 4 way TP&N pan assemblyMGBN6P 6 way TP&N pan assemblyMGBN8P 8 way TP&N pan assemblyMGBN12P 12 way TP&N pan assemblyMGBN16P 16 way TP&N pan assemblyMGBN418P 18 way TP&N pan assemblyMGBN24P 24 way TP&N pan assembly
B board door and coverPart No. DescriptionMGBN4C Suitable for MGBN4MGBN6C Suitable for MGBN6MGBN8C Suitable for MGBN8MGBN12C Suitable for MGBN12MGBN16C Suitable for MGBN16MGBN18C Suitable for MGBN18MGBN24C Suitable for MGBN24
A board pan assembly*Part No. DescriptionMGAN6P 6 way SP&N pan assemblyMGAN9P 9 way SP&N pan assemblyMGAN12P 12 way SP&N pan assemblyMGAN15P 15 way SP&N pan assembly
A board door and coverPart No. DescriptionMGAN6C Suitable for MGAN6MGAN9C Suitable for MGAN9MGAN12C Suitable for MGAN12MGAN15C Suitable for MGAN15MGAN23C Suitable for MGAN23
MGAN9P
MGBN8P
MGAN6C
MGBN8C * for use only with C60H range
21
C60HIsobar 4 outgoers miniature circuit breakers 1 - 63A
Installation In Merlin Gerin Isobar 4 distribution boards Symmetrical DIN rail Direct panel mounting Isobar 4 pan assemblies
Technical data Current ratings: 1 - 63A at 300C to
BS EN 60898 Voltage ratings: 240 - 440Vac Breaking capacity: BS EN 60898: 10kA,
BS EN 60947-2: 15kASee page 140 for further information on breakingcapacities and dc ratings. Operating cycles (O-C): on load 20,000 Operating temperature: -300C to +700C Positive contact indication: in accordance
with BS 7671 Current limitation: Class 3 Width:Pole 18mm SP ways mm1 1 182 2 363 3 544 4 72
Dimensions: see page 172
Weight:Pole Grams1 1102 2203 3404 450
Accessories: see page 26Add on earth leakage: see page 23Technical data: see page 133
Note: 2 and 4 pole C60H MCBs are suitable forinstallation in Isobar 4 distribution boards and panassemblies with NKIT.
For current ratings greater than 63A, see Section four.Note: Not suitable as outgoing way in Isobar 4c.
See page 135 for grouping factor
1, 2, 3 and 4 pole Type B Miniature circuit breakers
1, 2, 3 and 4 pole Type C Miniature circuit breakers
1, 2 and 3 pole Type D Miniature circuit breakers
22
C60HIsobar 4 outgoers miniature circuit breakers 1 - 63A
C60HB type B (3 - 5In)ApplicationsProtection and control of circuits against overloadsand short circuits. In applications with general load characteristics Tripping characteristics: BS EN 60898 type B:
magnetic setting between 3 and 5 In Cable capacity:
1 - 25A = 25mm2
32 - 63A = 35mm2
Tightening torque:≤ 25A = 2.5Nm32 - 63A = 3.5Nm
Ratings 1P 2P 3P 4P(A) 1 C60HB 101 C60HB 201 C60HB 301 C60HB 4012 C60HB 102 C60HB 202 C60HB 302 C60HB 4024 C60HB 104 C60HB 204 C60HB 304 C60HB 4046 C60HB 106 C60HB 206 C60HB 306 C60HB 406
10 C60HB 110 C60HB 210 C60HB 310 C60HB 41016 C60HB 116 C60HB 216 C60HB 316 C60HB 41620 C60HB 120 C60HB 220 C60HB 320 C60HB 42025 C60HB 125 C60HB 225 C60HB 325 C60HB 42532 C60HB 132 C60HB 232 C60HB 332 C60HB 43240 C60HB 140 C60HB 240 C60HB 340 C60HB 44050 C60HB 150 C60HB 250 C60HB 350 C60HB 45063 C60HB 163 C60HB 263 C60HB 363 C60HB 463
C60HD miniature circuit breakers Part No’sC60HD type D (10 - 14In)ApplicationsProtection and control of circuits against overloadsand short circuits. In applications with high inrush currents, such as
transformers, motors, certain lighting systems etc Tripping characteristics: BS EN 60898 type D:
magnetic setting between 10 and 14 In Cable capacity:
1 - 25A = 25mm2
32 - 63A = 35mm2
Tightening torque:≤ 25A = 2.5Nm32 - 63A = 3.5Nm
Ratings 1P 2P 3P 4P (A)1 C60HD 101 C60HD 201 C60HD 301 25211 2 C60HD 102 C60HD 202 C60HD 302 252124 C60HD 104 C60HD 204 C60HD 304 25214 6 C60HD 106 C60HD 206 C60HD 306 2521510 C60HD 110 C60HD 210 C60HD 310 2521616 C60HD 116 C60HD 216 C60HD 316 2521720 C60HD 120 C60HD 220 C60HD 320 2521825 C60HD 125 C60HD 225 C60HD 325 2521932 C60HD 132 C60HD 232 C60HD 332 2522040 C60HD 140 C60HD 240 C60HD 340 2522150 C60HD 150 C60HD 250 C60HD 350 2522263 C60HD 163 C60HD 263 C60HD 363 25223
Ratings 1P 2P 3P 4P(A)1 C60HC 101 C60HC 201 C60HC 301 248722 C60HC 102 C60HC 202 C60HC 302 248734 C60HC 104 C60HC 204 C60HC 304 248756 C60HC 106 C60HC 206 C60HC 306 24876
10 C60HC 110 C60HC 210 C60HC 310 2487716 C60HC 116 C60HC 216 C60HC 316 2487820 C60HC 120 C60HC 220 C60HC 320 2487925 C60HC 125 C60HC 225 C60HC 325 2488032 C60HC 132 C60HC 232 C60HC 332 2488140 C60HC 140 C60HC 240 C60HC 340 2488250 C60HC 150 C60HC 250 C60HC 350 2488363 C60HC 163 C60HC 263 C60HC 363 24884
C60HC miniature circuit breaker Part No’s
C60HB miniature circuit breaker Part No’s
C60HC type C (5 - 10In)ApplicationsProtection and control of circuits against overloadsand short circuits. In applications with moderate inrush currents,
such as certain lighting systems Tripping characteristics: BS EN 60898 type C:
magnetic setting between 5 and 10 In Cable capacity:
1 - 25A = 25mm2
32 - 63A = 35mm2
Tightening torque:≤ 25A = 2.5Nm32 - 63A = 3.5Nm
23
Vigi C60Add on residual current device for use with C60 MCBs only
ApplicationsClipped onto the side of any C60 MCB, add on Vigisprovide a high level of protection against earth fault inaddition to overload and short circuit protection provided by the MCB alone.
Effectively creating an RCBO to BS EN 61009, C60MCBs with add on Vigis can be used with any Isobar 4 distribution board, pan assemblies as well asa wide range of DIN enclosures.
+ =
Specification: Standards Approval: BS EN 61008 (BS EN 61009 when fitted to MCB) Operating voltage: 2 pole = 110/240V, 50/60Hz,
4 pole = 240/415V, 50/60Hz Cable capacity: 2 pole = 25mm2,
4 pole = 35mm2
Tightening torque: 2.5Nm = 25mm2,3.5Nm = 35mm2
Class AC Integral self test button Indication of earth fault tripNote: Must not be used as the sole means of protection against direct contactwith live parts (BS 7671).
Vigi modules - 2 pole for assembly with 1 or 2 pole MCBsPart No. Ratings Sensitivity Width in
(A) (mA) 18mm SP ways
MGV 25 010 2 25 10 2
MGV 63 030 2 63 30 2
MGV 63 100 2 63 100 2
MGV 63 300 2 63 300 2
Vigi modules - 4 pole for assembly with 3 or 4 pole MCBsPart No. Ratings Sensitivity Width in
(A) (mA) 18mm SP ways
MGV 63 030 4 63 30 3
MGV 63 300 4 63 300 3
Terminal screw shields available for Vigi RCDs.
See C60 accessories on page 26.
MCB 2P Vigi RCBO
Dimensions: see page 172
T
T
2 4
1 3
1 3 5 7
2 4 6 8
24
C60H RCBO (18mm)Combined MCB/RCD
Applications
Protection against overloads, short circuits and earth leakage faults.
Part No. Ratings Curve Class(A) type
C60HC6R30 6A 30mA C AC
C60HC10R30 10A 30mA C AC
C60HC16R30 16A 30mA C AC
C60HC20R30 20A 30mA C AC
C60HC32R30 32A 30mA C AC
C60HC45R30 45A 30mA C AC
C60HC6R100 6A 100mA C AC
C60HC10R100 10A 100mA C AC
C60HC16R100 16A 100mA C AC
C60HC20R100 20A 100mA C AC
C60HC32R100 32A 100mA C AC
C60HC45R100 45A 100mA C AC
C60HC6RA10 6A 10mA C A
C60HC10RA10 10A 10mA C A
C60HC16RA10 16A 10mA C A
C60HC20RA10 20A 10mA C A
C60HC32RA10 32A 10mA C A
C60HC45RA10 45A 10mA C A
C60HC6RA30 6A 30mA C A
C60HC10RA30 10A 30mA C A
C60HC16RA30 16A 30mA C A
C60HC20RA30 20A 30mA C A
C60HC32RA30 32A 30mA C A
C60HC45RA30 45A 30mA C A
The C60H RCBO provides: Protection against indirect contact Supplementary protection against direct contact
(BS 7671) Protection against insulation faults Finger safe terminals Reverse polarity protection Loss of neutral and earth protection Operating voltage: 200Vac - 230Vac Current ratings: 6A - 45A Tripping characteristics: BS EN 61009 (type C)
magnetic setting between 5 - 10 In Breaking capacity: BS EN 60898 10,000A,
BS EN 60947 15kA Class 3 current limiting overcurrent protection Positive contact indication in accordance with
BS 7671 Lockable in “ON” or “OFF” position using MGLA Trip free mechanism Compatible with C60 auxiliaries and accessories
e.g. alarm contact, shunt trip Load terminals cable capacity 16mm2
Dimensions: see page 172
Installation Isobar 4 distribution boards, pan assemblies and
standard enclosures on symmetrical DIN rail
C60HC32R30
Trip sensitivityAC classTripped by sinusoidal AC currents independent ofrate of rise.
A classTripped by sinusoidal AC pulsed DC and thosecontaining DC component.
25
Electrical auxiliariesC60 MCBs and RCBOs
ApplicationsFor the remote control and status indication of C60 MCBs.
Auxiliary combination
They are mounted to the left of the circuit breakerwithin a maximum width of 54mm
Fixed using clips (no tools) onto the left side of the circuit breaker
Compatible with Vigi modules (fitted to the right side) A maximum of 3 indication auxiliaries on the same
circuit breaker A maximum of 2 changeover auxiliaries (OF+SD/OF)
on the same circuit breaker A maximum of 2 tripping auxiliaries (MX + OF or MN)
on the same circuit breaker A maximum of 1 tripping auxiliary (MN s or MNx or
MSU) on the same circuit breaker
++++
OF+SD/OFauxiliarycontact
OFauxiliarycontact
SDfault indication
switch
Mx + OF, MN, MN s MNx orMSU auxiliary
Circuitbreaker
26
U>
C1C2
Electrical auxiliariesC60 MCBs and RCBOs
MX + OF (shunt release and auxiliary contact)Control Part No. Width involtage 18mm SP (Vac) (Vdc) ways110 - 415 110 - 130 26946 148 48 26947 112/24 12/24 26948 1Disconnects the MCB when a voltage is applied. Indication of tripping and fitted with changeover contact for indication. Self breaks control circuit allowing it to remain energised.
MSU (voltage threshold release)1P + N Control Part No. Width in
voltage 18mm SP (Vac) ways220 - 240 tripping at 255V 26979 2220 - 240 tripping at 275V 26479 2
MN (under voltage release)Instantaneous Control Part No. Width in
voltage 18mm SP (Vac) (Vdc) ways220 - 240 26960 148 48 26961 1115 (400Hz) 26959 1220 - 240 Delayed s 26963 2Disconnects the MCB when a voltage is removed.
MNx emergency stopControl Part No. Width involtage 18mm SP (Vac) ways230 26969 2230 26977 2*400 26991 2*400 26971 2* For use with C60 only.Disconnects the MCB when the normally closed push button contact is opened. Does not trip in the event of power supply failure.
MX shunt releaseControl Part No. Width involtage 18mm SP (Vac) (Vdc) ways110 - 415 110 - 130 26476 148 48 26477 112/24 12/24 26478 1
U>
14 12 C2 C1
U>
E1 E2 N L
U>>
N L
U<
D1 D2
26946
26476
26979
26963
26969
27
Electrical auxiliariesC60 MCBs and RCBOs
SD fault indicating switchPart No. Width in
18mm SP ways
26927 0.5
Contact rating (V) (A)240Vac 6A415Vac 3A24Vdc 6A48Vdc 2A125Vdc 1A
OF auxiliary contactPart No. Width in
18mm SP ways
26924 0.5
Contact rating (V) (A)240Vac 6A415Vac 3A24Vdc 6A48Vdc 2A125Vdc 1A
OF + SD/OF selector switchPart No. Width in
18mm SP ways
26929 0.5
94 92 91
24 22 2192 94 91
14 12 11
26927
26924
26929
Auxiliary contactchanges when devicetrips with front faceindication, red fortripped.
Auxiliary contactchanges with maincontacts (on/off) withtest button on frontface.
Auxiliary contact andselectable auxiliary orfault contact withfront face indication.Note: Does not fitonto Isobar 4distribution board.
28
AccessoriesFor C60
Padlocking facilityBreaker Quantity Part No.C60 Pack of 5 MGLA
Screw shieldBreaker Quantity Part No.C60 Sealable and dividable
2 x strips of 4 26981
Screw shieldBreaker Quantity Part No.C60 Vigi Sealable
1P shields 20 off 26982
Terminal shieldBreaker Pole Part No.C60 pair 1 26975
2 269763 26975 + 269764 26978
Insulated sub distribution terminalFor 3 x cables up to 16mm2 each Breaker Quantity Part No.
C60>25A Pack of 4 19091
*Aluminium cable terminalFor cables of 16 - 50mm2 Breaker Quantity Part No.
C60>25A Pack of 1 27060
MGLA
26981
26975/26976
19091
27060
Note: MGLA is suitable for use with C60MCBs/RCBOs mounted in Isobar 4 distributionboards.
Description Part No.Padlock 4mm hasp for MGLA MGLAPFor MCBs/RCDs (pack of 2) 26970
* not for use in Isobar 4 distribution boards
29
AccessoriesFor C60
*Rear connection terminal For cables up to 50mm2. Breaker Quantity Part No.
C60 Pack of 2 18528
Inter-pole barrierBreaker Quantity Part No.C60 Pack of 10 27001
18528
27001
* not for use in Isobar 4 distribution boards
30
AccessoriesFor C60
SpacerBreaker Width Part No.C60 9mm 27062
Replacement cover for vigiblocBreaker Pole Part No.C60 2 26483Pack of 5 3 26484replacements 4 26485
27062
26483
Modular control products Section two
Local control 32 - 44
Remote control 45 - 54
Time management 55 - 58
Lighting management 59 - 60
Metering and measurement 61 - 70
Heating management 71
31
32
ApplicationThe I switches perform the operations of control anddisconnection.
Technical details Compliance with standards: I 20, 32 and 40A: BS EN 60669-1, IEC 669-1 I 63, 100 and 125A, IEC 947-3
- Degree of pollution 3- Isolating voltage 500Vac- Impulse voltage 6kV- Degree of protection IP4X on the front panel- Frequency 50 - 60Hz
Isolation with positive contact indication DC application: 48V (110V with 2 series
connected poles) Mechanical endurance: I 20, 32 and 40A: 200,000 operating cycles I 63, 100A and 125A: 50,000 operating cycles Electrical endurance: AC22, p.f. = 0.6: I = 20 and 32A:30,000 operating cycles I = 40 and 63A: 20,000 operating cycles I = 100A: 10,000 operating cycles I = 125A: 2,500 operating cycles
I switch disconnectors20 - 125A
Short circuit withstand: 20 x In: 1s Tropicalisation: treatment 2 (relative humidity
95% at 55°C) Connection by tunnel terminals for: 10mm_ flexible/rigid cables for I 20 - 40A 50mm_ rigid cables or comb busbars, 35mm2
supple cables for I 63, 100 and 125A Tightening torque: 20A = 1.4Nm 32 - 40A = 2Nm 63 - 125A = 3.5Nm AuxiliaryO.C auxiliary switch Contact breaking capacity: 3A at 400Vac 6A at 230Vac Fixing by clipping onto symmetrical rail, on the left
side of the switch Connection by tunnel terminals for 2 x 2.5mm
cables
Type Rating Voltage Width Part No.(A) (Vac) in 18mm
SP waysI switches 20 250 1 150051P 32 250 1 15009
40 250 1 1502463 250 1 15013100 250 1 15090125 250 1 15057
I switches 20 250 1 150631P + indicator 32 250 1 15100
1 x1
2 x2
15013
1
2
33
I switch disconnectors20 - 125A
15014
Type Rating Voltage Width Part No.(A) (Vac) in 18mm
SP waysI switches 20 415 1 150062P 32 415 1 15010
40 415 2 1502063 415 2 15014100 415 2 15091125 415 2 15058
I switches 20 415 2 150642P + indicator 32 415 2 15101
1 3
2 4
x1
x2
1 3
2 4
Type Rating Voltage Width Part No.(A) (Vac) in 18mm
SP waysI switches 20 415 2 150073P 32 415 2 15011
40 415 3 1502363 415 3 15015100 415 3 15092125 415 3 15059
Type Rating Voltage Width Part No.(A) (Vac) in 18mm
SP waysI switches 20 415 2 150084P 32 415 2 15012
40 415 4 1501963 415 4 15016100 415 4 15093125 415 4 15060
Type Rating Voltage Width Part No.(A) (Vac) in 18mm
SP waysAccessoriesNO auxiliary 3 (6) 415 (230) 1 15096Terminal shields 15094
1 3
2 4
5
6
1 3
2 4
5
6
7
8
15015
15096
15212
34
TR transformers4 - 63VA
ApplicationSafety and bell transformers allow for a very low voltage to be obtained from a230Vac supply.
Technical details Primary voltage: 230Vac ± 10% Secondary voltage on load: 8 - 12 - 24Vac ± 15% for bell transformers 12 - 24Vac ± 5% for safety transformers Frequency: 50Hz - 60Hz Compliance with standards: EN 61558-1,
IEC 61558-1 Connection tunnel terminals for cables up to
4mm2
Type Power Secondary Width Part No.(VA) voltage in 18mm
(Vac) SP waysBell transformer 4 8 2 15214
4 8 - 12 2 152138 8 - 12 2 1521616 8 - 12 2 1521225 12 - 24 3 15215
Safety transformer 16 12 - 24 5 1521815 12 - 24 5 1521920 12 - 24 5 1522063 12 - 24 5 15222
15218
12V
230V1 11
8V4 8
230V1 11
12V
4 86 8V
230V1 11
24V
4 86 12V
230V1 11
24V
4 810
230V1 11
24V
8 128 13
230V1 11
12V
6 128 10
15214 15212, 15213,15216
15215 15218, 15219
15218, 15219 15220, 15222
35
RO buzzer and SO bellAudible signalling
Type Secondary Sound Width Part No.voltage level in 18mm(V) (dB) SP ways
Bell 240 80 1 1532012 80 1 15321
Buzzer 240 70 1 1532212 70 1 15323
ApplicationAudible indication of signals.
Technical details Sound level (at distance of 60 cm): RO buzzer: 70dB SO bell: 80dB Frequency: 50 - 60Hz Consumption: 3.6VA:8 - 12A 5VA: 220 - 240V Connection: tunnel terminals for cables up to
4mm2
15320
15322
SO bell RO buzzer
STI fuse carriersWithdrawable gl or gG fuse links
36
Type Voltage Width Part No.(Vac) in 18mm
ways1P 500 1 156361P+N 500 1 156462P 500 2 156513P 500 3 156563P+N 500 3 15658
Type Rating Dimensions Part No.(A) (mm)
gG (gl) fuse links 2 10.3 x 38 157754 10.3 x 38 157766 10.3 x 38 1577710 10.3 x 38 15779
Blown fuse indicator 15668
Dimensions Rating Operating Breaking(Ø x L) (A) voltage capacity(mm) (Vac) (kA) gG (gL - gl)10 x 38 32 500 80
15636
15775
ApplicationSTI fuse carriers provide overload and short circuit protection.
Technical detailsCarrier Isolation of all poles is guaranteed for the 2P and
3P versions during factory assemble Positive contact indication To be equipped with gG (gL - gl) type fuse links,
with or without fuse blowing indicator Fuse carrier: Captive Additional housing is provided for a spare fuse Optional indication: by indicator lights (see
accessories) Connection: by tunnel terminals for rigid cables
up to 10mm2 and flexible cables up to 6mm2
Complies with standard: IEC 947-3
Fuse link gG (gL - gl) types. Fuse link without striker pin Breaking capacity: as standard IEC 269-1/2 Vertitas and Lloyd’s approved
PRD surge arrestersDraw out
37
16562
PRD 1P+N
PRD 3P+N
ApplicationPRD removable surge arresters enable the rapid replacement of damagedcartridges without any cable disconnection.
Technical details*Each surge arrester in the range has a specific use: Incomer and protection: PRD 40r/PRD 40 are recommended for a high
risk level The PRD 15 is recommended for a low risk level Secondary protection: The PRD 8 ensures secondary protection of
loads to be protected and is placed in acascading configuration with surge arresters atthe incomer end
Common technical data Operation indication by means of a
mechanical indicator: White: normal operation Disconnection of the short circuited surge arrester
to be conducted with a circuit breaker Recommended breaker: Single phase + N: C60HC220 Three phase + N: 24879
Standards IEC 61643-11 class 2 test
PRD 40r/PRD 40 Imax (8/20µs): 40kA In (8/20µs): 15kA The PRD 4 0r includes: Operating indicator on front panel
PRD 15 Imax (8/20µs): 40kA
In (8/20µs): 15kA
PRD 8 Imax (8/20µs): 40kA In (8/20µs): 15kA
Spare cartridges 40, 15, 8 kA and neutral cartridges The C40r and C neutral r cartridges have
operating indicator
Type Un Uc (V) Up Width Part No.(V) MC MD (kV) in 18mm
SP waysPRD65r 1P+N 230 440 275 1.2 2 16557PRD65r 3P 440 440 2 3 16558PRD65r 3P+N 440 440 275 1.2 4 16559PRD40r 1P+N 230 440 275 1.2 2 16562PRD40r 3P 440 440 1.8 3 16563PRD40r 3P+N 440 440 275 1.2 4 16564PRD40 1P+N 230 440 275 1.2 2 16567PRD40 3P 440 440 275 1.8 3 16568PRD40 3P+N 440 440 275 1.2 4 16569PRD15 1P+N 230 440 275 1.2 2 16572PRD15 3P 440 440 1.8 3 16573PRD15 3P+N 440 440 275 1.2 4 16574PRD8 1P+N 230 440 275 1.2 2 16577PRD8 3P 440 440 1.8 3 16578PRD8 3P+N 440 440 275 1.2 4 16579
Replacement cartridgesC65r - 440 16581C65r - 275 16581C40r - 440 16583C40r - 275 16583C40 - 440 16585C40 - 275 16585C15 - 440 16587C15 - 275 16587C8 - 440 16589C8 - 275 16589C neutral r 16590C neutral 16591
Isobar installation kit MGNPRD
NL
NL1
L3L2
* Further details of surge arrester selection can be found on pages 147 - 149 at the rear of the document. Or in publication Ref: MGD 5082
PF surge arrestersFixed
38
15689
ApplicationThe PF all contained, multiple pole surge arrester range is especially adapted to TTand TN-s earthing systems.
Technical details*Each surge arrester in the range has a specific use: Incomer and protection: PF30r/PF30 are recommended for a high risk
level The PF 15 is recommended for a low risk level Secondary protection: The PF 8 ensures secondary protection of loads
to be protected and is placed in a cascadingconfiguration with surge arresters at the incomerend
Common technical data Operation indication by means of a
mechanical indicator: Not illuminated: OK Flashing: surge arrester must be immediately
replaced Disconnection upon thermal overload built into the
surge arrester Disconnection of the short circuited surge
arrester to be conducted with a circuitbreaker:
Single phase + N: C60HC220 Three phase + N: 24879
PF 30r and PF 30Common mode protection Imax (8/20µs): 30kA In (8/20µs): 10kA Up: 1.8kV Test button for front panel indicator. The PF30r has a built-in remote indication
contact: Normally closed
PF 15Common mode protection Imax (8/20µs): 15kA In (8/20µs): 5kA Up: 1.8kVDifferential mode protection Imax (8/20µs): 8kA In (8/20µs): 2kA
Up: 1kV
PF 8Common mode protection Imax (8/20µs): 8kA In (8/20µs): 2kA Up: 1.5kVDifferential mode protection Imax (8/20µs): 8kA In (8/20µs): 2kA Up: 1kV
PF 1P+N PF 3P+N
N L1
L1
N
N L1
L1
N
L2 L3
L2
L3
Type Un Uc (V) Up Width Part No.(V) MC MD (kV) in 18mm
SP waysPRD65r 1P+N 230 440 2 7 15684PRD65r 3P+N 440 440 2 7 15685PRD30r 1P+N 230 440 1.8 3 15689PRD30r 3P+N 440 440 1.8 4 15690PRD30 1P+N 230 440 1.8 3 15687PRD30 3P+N 440 440 1.8 4 15688PRD15 1P+N 230 440 250 1.8 2 15692PRD15 3P+N 440 440 250 1.8 4 15693PRD8 1P+N 230 440 250 1.5 2 15695PRD8 3P+N 440 440 250 1.5 4 15696
* Further details of surge arrester selection can be found on pages 147 - 149 at the rear of the document. Or in publication Ref: MGD 5082
CM selector switchesLocal control
39
18074
ApplicationCM selector switches allow the manual switching of circuits.
Technical details Voltage rating: 250Vac Current rating: 20A Electrical durability: 30,000 cycles AC22 Complies with standard: IEC 60669-1 and
IEC 60947-5-1 Operating temperature: -20°C to +50°C Storage temperature: -40°C to +80°C Tropicalisation: treatment 2 (relative humidity
95% at 55°C) Connection by rigid or flexible cable with or
without cable end: Tunnel terminals up to 2 x 2.5mm2, +/- recess
screw, Pozidrive n°1 Staggered terminals simplifying cable connection
1 changeover switch
2 changeover switches
2 changeover switches 1NO + NC
1 changeover switch
Type Circuit Width Part No.in 18mmways
2 position1 changeover 1 180702 changeover 2 180711NO+1NC 1 18072
3 position1 changeover 1 180732 changeover 2 18074
2 position selector switches
3 position selector switches
0 I4 2
1
0 I4 2
1
8 6
5
0 I2
1
4
3
I 0 II2
1
4I 0 II
2
1
4 6
5
8
BP pushbuttonsLocal control
40
18035
ApplicationThe BP pushbuttons are used to give manual impulse signals.
Technical details Voltage rating: 250Vac Current rating: 20A Electrical durability: 30 000 switching operations
AC22 (cosØ = 0.8) Complies with standard: IEC 60669-1 and
IEC 60947-5-1 Indicator light with LED technology: Consumption: 0.3 W Service life: 100,000 hours with constant luminous
efficiency Indicator light requires no maintenance
(non-interchangeable LEDs) Operating temperature: -20°C to +50°C Storage temperature: -40°C to +80°C Tropicalisation: treatment 2 (relative humidity:
95% at 55°C) Connection by rigid or flexible cable with or
without cable end: Tunnel terminals up to 2 x 2.5mm2 +/- recess
screw, Pozidrive n°1 Staggered terminals simplifying cable connection
1 NC 1 NO 1 NO+1 NC 1 NO/1 NC 1 NO/1 NC
Type Indicator Pushbutton Indicator Circuit Width Part No.colour colour voltage in 18mm
waysSingle Grey 1NC 1 18030
Red 1NC 1 18031Grey 1NO 1 18032
Double Grey 1NO+1NC 1 18033Grey/Red 1NO+1NC 1 18034Grey/Grey 1NO+1NC 1 18035
Pushbutton with Green Grey 110 - 230Vac 1NO 1 18036indicator Red Grey 110 - 230Vac 1NC 1 18037
Green Grey 12 - 48Vac/dc 1NO 1 18038Red Grey 12 - 48Vac/dc 1NC 1 18039
BP
1 NO 1 NC
BP with indicator light
3
4
1
2
1
2
3
4
1
2
3
4
1
2
3
4
1
2
x1
x2
3
4
x1
x2
V indicator lightsLocal control
41
18326
ApplicationThe V indicator lights provide visual indication and signalling.
Technical details Complies with standard IEC 60947-5-1 (except
part number 18327 complies with standard IEC 73and IEC 1000-4)
Operating frequency: 50 - 60Hz Indicator light with LED technology Consumption: 0.3 W (0.5 W for Part No. 18327) Service life: 100,000 hours with constant luminous
efficiency Indicator light requires no maintenance
(non-interchangeable LEDs) Flashing frequency: 2Hz (18326) Degree of protection: IP4X for the part outside the enclosure IP2X at the terminals Divisible partition to accommodate a comb busbar Operating temperature: -20°C to +50°C Storage temperature: -40°C to +100°C Tropicalisation: treatment 2 (relative humidity
95% at 55°C) Connection by rigid or flexible cable with or
without cable end: Tunnel terminals up to 2 x 2.5mm2, +/- recess
screw, Pozidrive n°1 Staggered terminals simplifying cable connection
Type Colour Voltage Width Part No.in 18mmways
Single indicator Red 110 - 230Vac 1 18320light Green 110 - 230Vac 1 18321
White 110 - 230Vac 1 18322Blue 110 - 230Vac 1 18323Yellow 110 - 230Vac 1 18324Red 12 - 48Vac/dc 1 18330Green 12 - 48Vac/dc 1 18331White 12 - 48Vac/dc 1 18332Blue 12 - 48Vac/dc 1 18333Yellow 12 - 48Vac/dc 1 18334
Double indicator Green/Red 110 - 230Vac 1 18335lightFlashing indicator Red 110 - 230Vac 1 18326lightThree phase indicator Red/Red/Red 230 - 400Vac 1 18327light
Single indicatorlight
Double indicatorlight
Flashing Three phaseindicator light
x1-
x2+
x1
x2
x3
x4
x1
x2
==
x1
XC (N)*
x2 x3 230Vac=
XB device holderLocal control
42
15151
ApplicationThe device holders can be mounted on 35mm rail to facilitate mounting ofpushbuttons, indicators or other devices*.
Technical detailsButton holder For buttons, switches and indicators with metal or
plastic flange Ø 22 of the Telemecanique XB4 /XB5 type*
Depth under rail 60mm (same as products in themulti 9 range)
Drilling diameter: Ø 22.3 Self-extinguishing insulating material Colour: light grey RAL 7035
Universal holder For buttons, indicators, light emitting diodes
(LED), potentiometers Easy drilling, to be adapted depending on use Depth under rail 60 mm (same as products in the
multi 9 range) Self extinguishing insulating material Colour: light grey RAL 7035
15152
Type Width Part No.in 18mmways
22mm button holder 3 15151Universal holder 3 15152
* Further details of Telemecanique pushbuttons can be found in publication Ref: ICC 1854
PowerLogic:Power meter series PM700
43
Applications Panel instrumentation
Submetering and cost allocation
Remote monitoring of an electrical installation
Harmonic monitoring (THD)
Contract optimisation and load profiling
CharacteristicsLarge, easy-to-read display Multiple values displayed at the same time on an anti-glare display featuring a
green back-light
Easy to operate Intuitive navigation with context-sensitive menus for easy use
Only 50mm deep Measures 96 x 96 x 50 mm including connectors and Modbus communications
Energy class 1 as defined by IEC 61036 Sufficient accuracy for submetering and cost allocation
Power, current demand, THD, min/max Expanded metering data for the cost of analog metering
Description Part numberPM700/700P/710Power Meter with THD, min/max PM700MGPower Meter with THD, min/max, 2 pulse outputs PM700PMGPower Meter with THD, min/max, RS 485 communications PM710MG
Selection guide PM700 PM710 PM700PGeneralUse on LV and HV systems Current and voltage accuracy 0.5% 0.5% 0.5%Energy and power accuracy 1.0% 1.0% 1.0%
Instantaneous rms valuesCurrent, voltage, frequency Active, reactive, Total and per phase apparent powerPower factor Total
Energy valuesActive, reactive, apparent energy
Demand valuesCurrent Present and max. Active, reactive, Present and max. apparent powerSetting of calculation mode Block, sliding block, rolling block
Data recordingMin/max of instantaneous values
Display and I/OBacklit LCD Display Pulse output - - 2
CommunicationRS 485 port - 2 wire -Modbus protocol - -
1 Mounting slots
2 RS485 communications (450C) or 2 pulse outputs (450P)
3 Heartbeat LED
4 Control power
5 Voltage inputs
6 Current inputs
PowerLogic:Power meter series PM700
44
PM700 series back view
Electrical characteristicsType of measurement True rms up to the 15th harmonic
On three-phase AC system (3P 3P + N)32 samples per cycle
Measurement Current and voltage 0.5 %accuracy Power 1 %
Frequency ± 0.01 Hz from 45 to 65 HzReal Energy IEC 61036 Class 1Reactive Energy IEC 61036 Class 2
Data update rate 1 sInput-voltage Measured voltage 10 to 480 V AC (direct L-L)characteristics 10 to 277 V AC (direct L-N)
0 to 3.2 MV AC (with external VT)Metering over-range 1.2 UnImpedance 2 MΩ (L-L) / 1 MΩ (L-N)Frequency range 45 to 65 Hz
Input-current CT ratings Primary Adjustable from 5A to 65534 Acharacteristics Secondary 5 A starting at 10 mA
Measurement input range 0 to 6 APermissible overload 15 A continuous
50 A for 10 seconds per hour120 A for 1 second per hour
Impedance < 0.1 ΩLoad < 0.15 VA
Control Power AC 110 to 415 ±10 % V AC, 5 VADC 125 to 250 ±20 % V DC, 3 WRide-through time 100 ms at 120 V AC
Output Pulse output PM700P Static output (240 ±10 % V AC or 300 ±10% V DC, 100 mA max. @ 25 °C, derate 0.56 mAper °C above 25°C) 2.41 kV rms isolation
Mechanical characteristicsWeight 0.37 kg
IP degree of protection (IEC 60529) IP52 front display, IP30 meter bodyDimensions 96 x 96 x 88 mm (meter with display)
96 x 96 x 50 mm (behind mounting surface)Environmental conditionsOperating Meter -0 °C to +60 °Ctemperature Display -10 °C to +50 °CStorage temp. Meter + display -40 °C to +85 °CHumidity rating 5 to 95 % RH at 50 °C (non-condensing)Pollution degree 2Metering category III, for distribution systems up to 277 V L-N /
480 V AC L-LDielectric withstand As per EN61010, UL508Electromagnetic compatibilityElectrostatic discharge Level III (IEC 61000-4-2)Immunity to radiated fields Level III (IEC 61000-4-3)Immunity to fast transients Level III (IEC 61000-4-4)Immunity to impulse waves Level III (IEC 61000-4-5)Conducted immunity Level III (IEC 61000-4-6)Immunity to magnetic fields Level III (IEC 61000-4-8)Immunity to voltage dips Level III (IEC 61000-4-11)Conducted and radiated emissions CE commercial environment/FCC part 15 class B
EN55011Harmonics emissions IEC 61000-3-2Flicker emissions IEC 61000-3-3SafetyEurope CE, as per IEC 61010-1U.S. and Canada UL508CommunicationRS 485 port 2-wire, up to 19200 bauds, Modbus RTUFirmware characteristicsMin./max. Worst min. and max. with phase indication for
voltages, currents, voltage unbalance, and THD. Min. and max. values for power factor (True and Displacement), power (P, Q, S) and frequency
Firmware update Update via the communication portsDisplay characteristicsDimensions 73 x 69mm Back-lit green LCD (6 lines total, 4 concurrent values)
45
CT contactors16 - 100A
Type of Control Powercable circuit circuit
16 and 25A 40 - 63A 100AFlexible 2x2.5mm2 2x2.5mm2 2x10mm2 2x35mm2
Rigid 2x1.5mm2 6mm2 25mm2 50mm2
ApplicationCT Contactors can be used for remote switching of heating, lighting, or powercircuits. Full guidance on selection can be found on pages 160 - 161.
Technical details Power circuit: CT ratings: 16 - 100A (AC7a category) Manually operated CT ratings: 16 - 63A (AC7a
category) Characterisation based on load types: see pages
160 - 161 in the technical section Voltage rating: 250Vac (1P and 2P): 400Vac (3P
and 4P) Frequency: 50Hz or 60Hz Control circuit: Voltage: 24Vac (± 10%), 230 - 240Vac
(-15% - +6%) Coil frequency: 50Hz or 60Hz Operating temperature: -5°C to +60°C Tropicalisation: treatment 2 (relative humidity:
95% at 55°C) Complying with standards: EN 61095, IEC
1095, NF, IMQ, NEMKO, SEMKO, VDE Connection via tunnel terminals:
Marking: contactors can be equipped with clip-onmarkers, see page 39 for details
Manually operated contactors have a 3 position selector switch on the front face: Automatic mode Temporary or permanent override operation Off
1 3 5
2 4 63NO
1 3 5 7
2 4 6 84NO
1 3
2 42NO
1
21NO
R1
R21NC
R1 R3
R2 R42NC
R1 R3 R5
R2 R4 R63NC
R1 R3 R5 R7
R2 R4 R6 R84NC
1 R1
2 R21NO+1NC
1 3 R1
2 4 R22NO+1NC
1 3 R1 R2
2 4 R2 R42NO+2NC
CT contactor Manually operated CT contactor
A1
A2
A1
A2
PI
O
Auto
Con
tact
num
ber
43
21
Type of contactsNO NC Mixed NO + NC
46
CT contactors16 - 100A
15959
15967
27062
15981
Type Rating Contacts Control Width in Part No.(A) voltage (Vac) 18mm
ways1P 16 1NC 24 1 16111
16 1NO 230 - 240 1 1611325 1NO 230 - 240 1 15958
2P 16 2NC 24 1 1611516 1NO+1NC 230 - 240 1 1585616 1NO+1NC 24 1 1612616 2NO 230 - 240 1 1595725 2NO 230 - 240 1 1595925 2NO 24 1 1602025 2NC 230 - 240 1 1596040 2NO 230 - 240 2 1596663 2NO 230 - 240 2 1597163 2NO 24 2 16024100 2NO 230 - 240 3 15977
3P 16 3NC 24 2 1611816 3NO 230 - 240 2 1612025 3NO 230 - 240 2 1596140 3NO 230 - 240 3 1596763 2NO+1NC 230 - 240 3 1531963 3NO 230 - 240 3 15972
4P 16 4NC 24 2 1612216 4NO 230 - 240 2 1612416 2NO+2NC 24 2 1612916 2NO+2NC 230 - 240 2 1613025 4NO 230 - 240 2 1596225 4NO 24 2 1602225 4NC 230 - 240 2 1596325 4NC 24 2 1602325 2NO+2NC 230 - 240 2 1596440 4NO 230 - 240 3 1596840 4NC 230 - 240 3 1596963 4NO 230 - 240 3 1597363 4NO 24 3 1602563 4NC 230 - 240 3 1597463 4NC 24 3 1602663 2NO+2NC 230 - 240 3 15975100 4NO 230 - 240 6 15978
Manually Operated2P 16 2NO 230 - 240 1 16116
16 1N0+1NC 230 - 240 1 1612725 2NO 230 - 240 1 1598140 2NO 230 - 240 2 1598463 2NO 230 - 240 2 15987
3P 25 3NO 230 - 240 2 159824P 25 4NO 230 - 240 2 15983
40 4NO 230 - 240 3 1598663 4NO 230 - 240 3 15988
AccessoriesTerminal shield 2P 16/40/63 2 15922Terminal shield 3/4P 16/25 2 15921Terminal shield 3/4P 40/63 3 15923Spacer for use every 2 contactors 0.5 27062
47
ACT contactor auxiliariesRemote control
ACTt
ACTp
ApplicationThe ACT range of auxiliaries connect to CT contactors to provide indication(ACTo+f), disturbance suppression (ACTp), impulsed or latched control and timedelays (ACTt).
Technical detailsACTo+ƒ Contact: 1NO + 1NC: 10 mA min. at 24Vac/dc - cos Ø = 1 10 mA min. at 24Vac/dc - cos Ø = 1
ACTc Min. impulse duration: 250ms Mains failure: < 1s: keeps its initial status > 5s: reset Restarted via manual operation on X or T
ACTt 4 types of time delay. See page 162 for details
ACTo+f ACTp ACTc ACTtCombined with CTRight hand side
Left hand side
Via clips (1)
Power SupplyVoltage 230V 24V 230V 24 - 48V 24 - 240VFrequency 50/60Hz 50/60Hz 50/60Hz 0 - 50/60Hz 50Hz
ConsumptionOff load 3VA 3VA 3VA 3VA 5VAInrush (2) 2A 2A 3AHolding (2) 0.5A 0.5A 0.2A
ConnectionTunnel terminals
Flexible cable (mm2) 2x2.5 2x2.5 2x2.5 2x2.5 2x2.5 2x2.5Rigid cable (mm2) 2x1.5 2x1.5 2x1.5 2x1.5 2x1.5 2x1.5(1): Electrical and mechanical link(2): Maximum consumption of all controlled contactors
ACTp ACTo+f ACTc ACTt
1 1
CTACTp
2 2
L
N
S
CT
1
L
N
A1
A2
2
23
24
ACTo+f CTACTt
A1
A2
1
2
S
L
N
CTACTc
L
N
L
N
T
X
1
2
S BP
Type Control Width Part No.voltage in 18mm
waysACTo+f 0.5 15914ACTc 230 - 240Vac 1 18308ACTc 24 - 48Vac/dc 1 18309ACTp 230 - 240Vac 1 15920ACTp 24Vac 1 15919ACTt 24 - 240Vac 1 15917
48
RLI, RBN interface relaysRemote control
ApplicationThe RLI, RBN and RTBT interface with automated systems to enable switching ofpower circuits from low voltage supplies. The ERL is an extension for the RLI relay.
Common technical data Frequency: 50 - 60Hz Electrical durability: 100,000 switching
operations Connection: tunnel terminals for 0.5 - 6mm2
cables
Specific technical dataRLI and ERL Direct control on the front face: Power by pushbutton Coil: by selector switch (disconnection) Position indicator: built into the pushbutton Identification: clip-on markers on the front face,
ERL It is mounted without tools or additional wiring by
means of a yellow clip This clip is used for mechanical assemble and
electrical connection between coils
RBN and RTBT Green pilot light on the control circuit Enhance isolation between ELV/LV circuits:
4kV
15393
RLI ERL RBN RTBT
A1
A2
1 5
4 62
1 5
4 62
11
1412
A1
A2
11
1412
A1
A2
Type Coil Consumption Output 10A Width in Part No.voltage inrush @ 230V 18mm(Vac) (holding) VA (cos Ø = 1) ways
RLI 230 - 240 4 (4) 10 1 1553548 4 (4) 10 1 1553624 4 (4) 10 1 1553712 4 (4) 10 1 15538
ERL 230 - 240 4 (4) 10 1 1553948 4 (4) 10 1 1554024 4 (4) 10 1 1554112 4 (4) 10 1 15542
RBN 230 - 240 5 (2.5) 2 1 15393RTBT 12 - 24 0.22 2 1 15416
(ac or dc) (0.11)
49
RC control relaysEnergy management
RCP RCI
L1
1 3 5 7
2 4 6 8
L2L3
F=60Hz
L
1 3 5 7
2 4 6 8
1A ≤ Ir ≤ 10A
N
Circuit to control0.15A ≤ Ir ≤ 1.5A
21180
21181
ApplicationThe RCP relay monitors phase order and asymmetry on all phases of a 3 phasecircuit and reports loss or reversal. The RCI relay monitors the current flowing in acircuit and reports when a preset threshold is reached.
Technical details Operating frequency: 50 - 60Hz Operating temperature: -5 to +55°C Consumption: 3VA Indication: Green LED for power ON Red LED for fault Output by 8 A changeover switch under 250Vac
(cos Ø = 1) Connection: tunnel terminals for rigid cables from
1.5 - 6mm2
RCP Operating voltage: 400Vac ± 15% Phase asymmetry threshold setting: 5 - 25% Hysteresis: fixed, 5% of asymmetry threshold Phase rotation direction monitoring 3 phase presence monitoring Time delay on tripping: 0.3s
RCI Measurement: Range: 0.15 - 10A Automatic recognition of ac and dc current 1 measurement ranges selected by wiring
- 0.15 - 1.5A- 1 - 10A
Overcurrent and undercurrent monitoring Threshold adjustable from 5 - 50% Failsafe contact Time delay on threshold reached: 0.1 - 10s Power supply: 230Vac Optional fault memorisation with rest Compatible with TI current transformers with an
X/5 ratio. See page 69
Type Width Part No.in 18mmways
RCP 2 21180RCI 2 21181
50
RT time relayTime management
ApplicationThe RT range of time relays provide various delays for enhanced control.
RTA offers delay on energisation of the load.
RTB causes an off delay after energisation via the closing of an auxiliary contact.
RTC causes an off delay after energisation via the closing and opening of anauxiliary contact.
RTH causes a time delay before energisation of a load.
RTL enables cyclic control with on and off timing.
RTMF is a multifunction time relay with the functionality of RTA, RTB, RTC or RTH.
Technical data Time delay range: 0.1s - 100h Control circuit: Control and supply voltage:
- 24Vdc ± 10%- 24 - 240Vac ± 10%- RTMF: 12 - 240Vac/dc ± 10%
Frequency: 50 - 60Hz Operating temperature: -5 to +55°C Power circuit: Changeover switch (without cadmium)
- minimum rating: 10 mA/5Vdc- maximum rating: 8 A/250Vdc and 8 A/250Vac
Mechanical durability: > 5x106 operations Electrical durability: > 105 operations (utilisation
category AC1) Accuracy: ± 10% full scale Minimum control impulse duration: 100mS Maximum resetting time by voltage break:
100mS Repetition accuracy: ± 0.5% with constant
parameters Visualisation of contact status by green indicator
light (flashing during the time delay) Unaffected by brownouts < 20mS Case protection: IP40 Connection by tunnel terminals: 2 x 2.5mm2 single strand cable without end 2 x 1.5mm2 multi-strand cable with end
16066
Specific technical dataRTA The single time delay cycle starts on energisation
of the supply of the RTA relay The load is energised at the end of the time
delay T
RTB The single time delay cycle starts on closing of an
auxiliary contact (pushbutton) At the end of time delay T, the load is
de-energised
RTC The single time delay cycle only starts when an
auxiliary contact is released (pushbutton) At the end of the time delay T, the load is
de-energised
RTH The single time delay cycle starts on energisation
of the supply of the RTH relay The load is de-energised at the end of time
delay T
RTL The time delay cycle starts on energisation The load is energised for an adjustable time T,
then de-energised for an adjustable time R.This cycle is repeated until the RTL relay supply isde-energised
RTMF As applicable, the RTMF generated the time delay
cycles of the RTA, RTB, RTC or RTH relays
51
RT time relayTime management
16065
16069
Type Width Part No.in 18mmways
RTA 1 16065RTB 1 16066RTC 1 16067RTH 1 16068RTL 1 16069RTMF 1 16070
RTA RTB
RTC RTH
RTL RTMF
52
TL impulse relays and auxiliariesRemote control
ApplicationTL and TLI impulse relays allow remote control from impulse commands(mechanically latched) or from several control points. They can be used for controlof resistive circuits (incandescent lamps, lv halogen lamps, convectors)and inductive circuits (fluorescent tubes, discharge lamps). TLc, TLm and TLs havebuilt in auxiliaries that allow centralised control, latched order control and/or remote indication.
15516
Technical data Environment: Operating temperature: -20 to +50°C Tropicalisation: treatment 2 (relative humidity 95%
at +55°C) Identification by clip-on markers on the front face Switching noise level < 60dBA (at 1M) Compliance with standard: EN 669-1,
EN 669-2-2 Approved by NF USE, CEBEC, SEMKO, DEMKO,
SETI
Specific to TL 16A, TLI, TLc, TLm and TLs Power circuit: Electrical endurance:
- 200 000 cycles AC21- 100 000 cycles AC22
Control circuit Control voltage (Uc):
- tolerance at 50Hz: Uc + 6% - 15%- tolerance at 60Hz: Uc ± 6%- tolerance in dc: + 6% - 10%
Inrush power:- 1P and 2P: 19VA- 3P and 4P (TL + ETL): 38VA
Impulse duration: 50mS (recommended value forautomatic control: 200mS
Maximum switching frequency: 5operations/minute
Connection: (+/- screw, Pozidrive) tunnelterminals for cable 0.5 - 6mm2
Specific to TL 32A Power circuit: Electrical endurance:
- 50 0000 cycles AC21- 20 0000 cycles AC22
Control circuit: Control voltage (Uc):
- tolerance at 50Hz: Uc + 6% -15%- tolerance at 60Hz : Uc ± 6%- tolerance in dc: Uc + 6% - 10%
Inrush power:- 1P: 19VA, 2P: 38VA- 3P: 57VA 4P: 76VA
Impulse duration: 50mS (recommended value forautomatic control: 200mS)
Maximum switching frequency: 5operations/minute
Connection (+/- screw, Pozidrive): Power circuit:
- tunnel terminals for cables up to 10mm2
Control circuit:- tunnel terminals for cables 0.5 - 6mm2
TLc impulse relayCentralised control of a set of impulse relays.Keeps local impulse control. Electrical control: Impulse duration 50ms (recommended value for
automatic control: 200ms max) Centralised control: (recommended value for
automatic control: 500ms max) Possible combinations: ETL for TL 16A (reference 15530), ATLt, ATLz,
ATLc+c ATLc+s (only uses its indication function)
TLm impulse relay Operates by latched order from a changeover switch (selector, time switch, thermostat) of one ormore TLm. The manual control is not operational. Electrical control: Impulse duration 50ms (recommended value for
automatic control: 200ms max) Possible combinations: ETL for TL 16A (reference 15530) ATLc+s (only uses its indication function)
TLs impulse relay Remote indication of its electrical state Auxiliary switch: 6A, 24 - 250Vac, cos Ø = 1 Electrical control: Impulse duration 50ms (recommended value for
automatic control: 200ms max) Possible combinations: ETL for TL 16A (reference 15530), ATLt, ATLz,
ATLc+s Indication: clip-on markers on the front face
53
5
6
TL impulse relaysRemote control
15500+15530
15510+15530
15518
TL 1P TL 2P TL1 1P
A1
A2
1
2
A1
A2
1 3
2 4
A1
A2
1 3
2 4
ETL 16A ETL 32A
5 9
8 106
TLc 1P TLm 1P TLs 1P
1
Off 2On
A1
A2
1
Off 2On
A1
A2
1
14 212
A1
A2
11
Type Rating Control Width in Part No.voltage 18mm(Vac) (Vdc) ways
TL 1P 16A 230 - 240 110 1 1551016A 130 48 1 1551116A 48 24 1 1551216A 24 12 1 1551316A 12 6 1 1551432A 230 - 240 110 1 15515
TL 2P 16A 230 - 240 110 1 1552016A 130 48 1 1552116A 48 24 1 1552216A 24 12 1 1552316A 12 6 1 15524
ETL+1P 16A 230 - 240 110 1 1553016A 130 48 1 1553116A 48 24 1 1553216A 24 12 1 1553316A 12 6 1 1553432A 230 - 240 110 1 15505
TLI 16A 230 - 240 110 1 1550016A 48 24 1 1550216A 24 12 1 15503
TLc 16A 230 - 240 110 1 1551816A 48 24 1 1552616A 24 12 1 15525
TLm 16A 230 - 240 110 1 15516TLs 16A 230 - 240 110 1 15517
16A 48 24 1 1552816A 24 12 1 15527
54
ATL impulse relays auxiliariesRemote control
ApplicationThe ATL auxiliaries connect onto TL impulse relays to provide time delayed control,centralised control with indication and multi level centralised control.
Technical dataATLt time delay auxiliary Automatically returns the impulse relay to its initialstate after a time delay that may be set from 1 secondto 10 hours. The time delay cycle starts when the device
closes. A new impulse order opens the impulserelay and interrupts the cycle
Added to the left of TL, TLI, TLs, TLc
ATLc+s centralised control + indication auxiliaryAllows centralised control thanks to a ‘ pilot line’, of aset of impulse relays controlling separate networks,while keeping the possibility of local individual controlof each impulse relay. Also enables remote indicationof the mechanical state of each relay. Added to the right of TL, TLI, ETL, TLs, TLc and
TLm Auxiliary switch: 6A: 240V cos Ø = 1
ATLc+c centralised control + indication auxiliaryAllows centralised control of several sets of impulserelays while conserving the possibility of localindividual control and multilevel centralised control. Each set, made up of TLc or (TL or TLI or TLs) +
ATLc+s, must contain a single ATLc +c Mounting: without mechanical connection to the
impulse relays and auxiliaries
ALTt ALTc+s ALTc+c
11
14 11
Off 14On 12 OnOnOff Off
Type Rating Control Width in Part No.voltage 18mm(Vac) (Vdc) ways
ATLt 16A 24 - 240 24 - 110 1 15411ATLc+s 16A 130 - 240 1 15409ATLc+c 16A 130 - 240 1 15410
55
IH mechanical time switches60 minute - 7 days
153351533615338163641536515367
15337 15366
24h 7 days
15335
15365
ApplicationControlling and switching of one or more separate circuits according to the positionof programming jumpers by the user.
Technical detailsElectrical data Voltage: 230Vac ± 10% Frequency: 50 - 60Hz (50Hz for Part No. 15338) Consumption: 2.5VA (1VA for Part No. 15338) Time accuracy: ± 2 second per day at 20°C Contact rating:
Under 250Vac Under 250Vac(cos Ø = 1) (cos Ø = 0.6)16A 4A
Degree of protection: Front face: IP40 Terminals: IP20 Operating temperature: -10°C to +50°C Storage temperature: -40°C to +85°C
Type No. of No. of Power Interval Width in Part No.switching channels reserve between 18mmoperations 2 jumpers ways
IH 1c 24hr 18mm 48on - 48off 1 None 15min 1 15335IH 1c 24hr 18mm 48on - 48off 1 100h 15min 1 15336IH 1c 60min 24on - 24off 1 None 15min 15s 3 15338IH 1c 24hr 24on - 24off 1 None 15min 3 16364IH 1c 24hr 24on - 24off 1 150hr 30min 3 15365IH 1c 24hr 24on - 24off 2 150hr 30min 3 15337IH 1c 7day 21on - 21off 1 150hr 4hr 3 15367IH 1c 24hr + 7day 16on - 16off 1 + 1 150hr 45min 3 15366
+ 7on - 7off + 12hrSpare riders 15341
56
IHP digital time switches24 hours - 7 days
ApplicationControlling and switching of one or more separate circuits for the purpose ofheating, ventilation, lighting or any other application requiring time control.
Technical dataElectrical data Voltage: 230Vac +/- 10% Frequency: 50 - 60Hz Consumption: 3 - 8.5VA Saving of program and time by lithium battery Time accuracy: ± 1 second per day at 20°C Contact rating:
Mechanical data Degree of protection: Front face: IP40 Terminals: IP20 Operating temperature: - 10°C to +50°C Storage temperature: -25°C to +70°C
Under 250Vac Under 250Vac(cos Ø = 1) (cos Ø = 0.6)16A 4A
15720 1572215721 15723
16 (10)A 250V ~
1 3 5
C2
L1
N1
16 (10)A 250V ~
2 4 6N
Load230V
C1
Auto
Off03 9910
10.30
12 15 18 21 24
1 2 3 4 5 6 7
9
6
3
0
L1
N1
16 (10)A 250V ~
2 4 6N
Load230V
C1
Auto
Off03 9910
10.30
12 15 18 21 24
1 2 3 4 5 6 7
9
6
3
0
15854
15722
15351
menu
Res
ok
10:54
n 02Prog
On04
L N
Load
Type No. of No. of Width in Part No.switching channels 18mmoperations ways
IHP 18mm 1c 28 1 1 15854IHP 1c 28 1 2.5 15720IHP+ 1c 42 1 2.5 15721IHP 2c 42 2 2.5 15722IHP+ 2c 42 2 2.5 15723
57
ITM multifunction time switch60 minute - 7 days plus specified days
ApplicationWeekly or annual programming distributed over 4 output channels from a maximumof 6 conditional inputs. Create a flexible time managed operation or control anumber of applications from one device.
Technical dataElectrical data Voltage: 230Vac ± 10% Frequency: 50Hz Consumption: 45VA Saving program and time by lithium battery: Lifetime: 10 years Back-up time: 5 years Time accuracy: ± 1 second per day at 20°C Contact rating: 10A under 250Vac (cos Ø = 1) 6A under 250Aac (cos Ø = 0.6)
Mechanical data Overall dimensions: 10 modules of 9mm Weight: 290g Degree of Protection: Front face: IP40 Terminals: IP20 Operating temperature: -5°C to + 50°C Storage temperature: -25°C to +70°C Accessory: Removable memory cartridge
15270
Type No. of No. of Width in Part No.switching channels 18mmoperations ways
ITM 4c 6i 40 45 weekly 15 annual 12 pulse 4 5 15270
AccessoriesMemory cartridge 15280
L N
L N L N L N L N
230V~ 50Hz 1...6 =EntrÈes / Inputs 230V~
C1......C4Canaux / Channels 10A / 230V~
C 1 C 2 C 3 C 4
menu OK
+-
L N 1 2 3 4 5 6
(switch, pushbutton,
light sensitve switch, thermostat,
motion control switch, etc..)
6 x 230Vac inputs
Removable memory cartridge 15280 optional
4 x 230Vac 10A output channels
C1-C2 C3-C4
On
Off
Load(lamp, small motor,
bell, luminous sign
etc)
! Preferably relay your
load with a contactor.
58
PRE only Only to be used with the following timers: 15363 50% reduction in brightness during warning time Time adjustable from 20 - 60 seconds Maximum power: 2000W for incandescent
lighting only Not compatible with fluorescent tubes,
fluocompact lamps and very low voltage halogenlamps
15233
Type Voltage Output Width in Part No.(A @ cos Ø = 1) 18mm
waysMIN 230 16 1 15363PRE 230 1 15233
AccessoryTerminal Shield 15359
MIN timers and PRE switch off warningLighting management with time
ApplicationMIN, MINe and MINs opens a contact after a predetermined time.
PRE Is used with MIN on incandescent lighting circuits to reduce provide advancewarning of switch off by reducing the brightness.
Technical data* Consumption: < 5VA Ingress Protection: IP40 Connection: Tunnel terminals for cables up to 6mm
MIN only Two operating modes triggered by switch on
front face: Automatic mode:
- operation in timing mode- time delay adjustable from 1 - 7 minutes- setting in steps of 15 and using thumb knob- pressing a pushbutton renews the time delay
Manual override mode Maximum power required:
- incandescent or low voltage 230V halogen lighting: 2000W
15363
* Timing diagrams can be found on page 152 in the technical Section.
59
IC light sensitive switches2 - 2000 lux
Type Voltage Width in Part No.(Vac) 18mm
waysIC200 220 - 240 2.5 15284*IC2000 220 - 240 3.5 15368*IC2000P 220 - 240 5 15286*
AccessoriesPhotocell (IP65) for IC2000 Flush mount 15281Photocell (IP54) for IC2000/P Wall mount 15268
ApplicationThe IC switches open or close a contact when the photo cell detects that a lightinglevel has been reached.
The IC/P switch has the additional function of time dependency.
Technical data Photo-cell: “panel front face” type (IP54) supplied Time delay before switch ON and switch OFF 40S Luminosity monitoring: light goes on when
threshold is reached Connection: tunnel terminals for cables up to
6mm2
Contact ratings: 10A: cos Ø = 1 6A: cos Ø = 0.6 Consumption: 3VA Operating temperature: -10 to +50°C
Specific technical dataIC200 Brightness threshold: adjustable from
2 - 200 lux
IC2000/IC2000P Brightness threshold: 2 adjustable thresholds: 2 - 35 lux or
35 - 2000 lux
IC2000P Autonomy: 6 years Continuous liquid crystal display of: Time (hours and minutes) Day of the week, week Switching status Minimum programming interval: 1 minute Memory: 42 settings Program: 24 hours and 7 days Summer-winter time changes: a single
operation without modifying the program Easy program control: Forced “on” or “off” overrides Advanced switching Setting deletion to modify or remove a sequence Holiday override: 1 - 45 days Operating temperature: -10 to +50°C
IC200
N 2 4 6
L 3 5
220 - 240V
2 35
M
Utilisation
IC2000
N 2 4 6
L 3 5
235 2000
2 35
220 - 240V
M
Utilisation
IC2000P
d h m
prog
N 2 4 6
L 3 5
235 2000
2 35
220 - 240V Utilisation
15284
15286
15281
15268
*supplied with a 15268 photocell
60
C movement detection4 - 30 meters
ApplicationAutomatic control of lighting or heating systems by the detection of movement orpresence in a monitored area.
Technical data* Power supply: 230Vac ± 10%, 50Hz
Specific technical dataCE30 Output contacts: 10A cos Ø = 1 5A cos Ø = 0.5 Incandescent lights: relays compulsory Degree of protection: IP43 Connection: 1.5mm2 spring tunnel type terminals Consumption: < 1W Operating temperature: - 25 to +55°C
CDM Lighting power: Incandescent lights: 1000W max Halogen lamps: 500W max Fluorescent and fluocompact lights: relays
compulsory Degree of protection: IP54 Connection: screw terminals up to 2.5mm2
Consumption: 1.1VA Operating temperature: -25 to +50°C
57655
16990
16992
16994
CDP/CPDt Degree of protection: IP20 Operating temperature: -15°C to +55°C Storage temperature: -25°C to +70°C Weight: 144g Dimensions: Diameter: 120mm Height: 70mm Fixing centre distance: 81mm
CDP Lighting power: Incandescent lights: 2000W max LV halogen lights (230V) and ELV (12V): 1000W
max Fluorescent lights with conventional ballast:
1000W max (cos Ø = 0.5) Fluorescent lights with parallel corrected ballast:
500W max (cos Ø = 0.5)
CDPt Lighting power (max number of 1 - 10V
ballasts): 16 x (1 x 36W) 12 x (1 x 58W) 12 x (2 x 36W) 8 x (2 x 58W)
Type Detection Range Brightness Time Movement Presence Part No.angle (m) threshold delay
(Lux)CE30 20 30 5 - 300 40 sec x 57655
- 8 minCDM 0 - 180 0 - 12 3 - 80 4 sec x 16990
- 15 minCDP 180 - 360 4 - 24 20 - 1300 4 - 15 min x x 16992CDPt 180 - 360 4 - 24 100 - 1300 4 - 15 min x x 16994
AccessoriesAdditional Remote control for CDPt 16995
* Refer to Section seven page 155 for further information.
61
AMP/VLT analogue ammeters and voltmetersMetering and measurement
Type Scale Connection Width in Part No.(A or V) with CT 18mm
ways
Amp with direct connection0 - 30 Direct 4 16029
AMP with connection via CTBasic device xxx/5 4 16030Dials 0 - 5 (See TI range on pages 77-78) 16031
0 - 50 160320 - 75 160330 - 100 160340 - 150 160350 - 200 160360 - 250 160370 - 300 160380 - 400 160390 - 500 160400 - 600 160410 - 800 160420 - 1000 160430 - 1500 160440 - 2000 16045
VLT Scale0 - 300 4 160600 - 500 4 16061
AMP: 16029
VLT: 16060
ApplicationThe meters facilitate the real-time monitoring of current and voltage.
Technical details Ferromagnetic device Connection: Tunnel terminals for 1.5 - 6mm2 rigid cable Pseudo-linear scale over 90° Overall dimensions: h = 79 : w = 72 : d = 66mm Weight (g): 170 Complied with standards: IEC 51 - IEC 414 Degree of protection: Terminal block IP40 Terminals IP20 Installation temperature: -25°C to +55°C Storage temperature: -40°C to +80°C Reference temperature: 23°C Effect of temperature on accuracy ± 0.03%/°C Overload AMP ONLY Maximum for 5 seconds: 10 In Permanence: 1.2 In Consumption: 1.1VA Accuracy class: 1.5
Analogue AMP Analogue VLT
Load
3 4
A
Load
3 4
V
62
AMP/VLT/FRE digital metersMetering and measurement
15201
ApplicationThe meters facilitate the real time monitoring of current, voltage and frequency.
Technical details Supply voltage: 230Vac Operating frequency: 50 - 60Hz Display by red LED: 3 digits Accuracy at full scale: 0.5% ± 1 digital Consumption: 0.3VA Connection: tunnel terminals for 2.5mm2 cables EMC electromagnetic compatibility:
IEC EN 50081-1 and IEC EN 50082-2 Safety: IEC EN 61010-1
AMP 10A Minimum value measured: 4% of rating Measurement input consumption: 1VA
AMP Multirange Ratings: In direct reading: 5A By CT (not supplied) configurable on the front
face of the ammeter: 10, 15, 20, 25, 40, 50, 60,100, 150, 200, 250, 400, 500, 600, 800, 1000,1500, 2000, 2500, 4000, 5000A
Minimum value measured: 4% of rating Measurement input consumption: 0.55VA
VLT Direct measurement: 0 - 600Vac Input impedance: 2 MΩ Minimum value measured: 4% of rating
FRE Minimum value measured: 20Hz Maximum value measured: 100Hz Full scale display: 99.9Hz
Type Scale Connection Width in Part No.with CT 18mm
ways
Amp with direct connection0 - 10A Direct 2 15202
AMP with multirating0 - 5000A As per rating 2 15209
VLT0 - 600V As per rating 2 15201
FRE20 - 100Hz As per rating 2 15208
Digital AMP + TI Digital VLT Digital FRE
1 2 3 4
LN NL
230V
1 2 3 4
LN 0-800V
230V
1 2 3 4
LN 20-600V
230V
63
PM9 multimeterMetering and measurement
15196
ApplicationThe PM9 digital multimeter displays the values of a three phase network. It providesinformation for the whole installation including voltage, current, active, reactive andapparent power, power factor, phase shifts, active and reactive energy andfrequency.
Technical details Supply voltage: 230Vac ± 10% Maximum measurement voltage without
voltage transformer: 3 x 400Vac (rms) Operating frequency: 50 - 60Hz Back-lit LCD display with: 3 groups each with 3 digits The type of measurement in progress The phase measured The unit: V, A, kW, kWh, VAr, Hz, pf Range of current transformers (CT): Primary: 1 - 9999A Fixed secondary: 230A
Type Supply Width Part No.voltage in 18mm
waysPM9 230 4 15196
1 2 3 4 5 6 7 8 9
10 11 12 13 14 15 16 17 18
S1
S2
P1
P2 S1
S2
P1
P2 S1
S2
P1
P2
N L1 L2 L3
Range of voltage transformers (VT): Primary: 1 - 9999V Fixed secondary: 230V Accuracy class: Voltage: 0.5% of full scale Current: 0.5% of full scale Active energy: class 2 as per IEC EN 61036 Reactive energy: class 3 as per IEC-EN 61268 Maximum consumption of each measurement
input: 0.55VA Operating temperature: -5°C to +55°C Storage temperature: -40°C to +85°C Connection by tunnel terminals: 2 x 2.5mm2
Three phase and neutral network: 3 x 230/400V
1 2 3 4 5 6 7 8 9
10 11 12 13 14 15 16 17 18
S1
S2
P1
P2 S1
S2
P1
P2 S1
S2
P1
P2
L1 L2 L3
230V
L3
Three phase network: 3 x 400V
1 2 3 4 5 6 7 8 9
10 11 12 13 14 15 16 17 18
L1
L2
L3
L2
L1
N
L3
Three phase and neutral network with or withoutneutral greater than 400V
1 2 3 4 5 6 7 8 9
10 11 12 13 14 15 16 17 18
S1
S2
P1
P2 S1
S2
P1
P2 S1
S2
P1
P2
L1 L2 L3
Three phase network: 3 x 230V
Note: Do not earth thesecondary of the CT’s(2)
S1
S2
P1
P2
P1
P2
64
CM selector switchesMetering and measurement
15125
ApplicationThe CM selector switches provide selection of phases when used in conjunctionwith AMP or VLT meters.
Technical details Rotary handle Maximum operating voltage: 440V, 50/60Hz Nominal thermal current: 10A Operating temperature: -20°C to +55°C Storage temperature: -25°C to +80°C Mechanical durability (AC21A-3 x 440V):
2000,000 operations Electrical durability: 1000,000 operations Connection: jumper terminals with captive
screws, for cables up to 1.5mm2
Complies with standards: IEC 60947-3 (EN 60947-3) VDE 0660 - 107 UL
N 1 2 3S1
S2S1
S2S1
S24 10 2
3 2
A
CMA1 3
V
CMA
N 1 2 3
12 10 6 2
Type Voltage Rating Width Part No.(Vac) (A) in 18mm
waysCMA 415 10 2 15126CMV 415 10 2 15125
65
CE/ME watt hour metersMetering and measurement
ApplicationClass 2 watt hour meters are designed for sub metering. They meter the electricalpower consumed per hour by a single or three phased electrical load. There are twodistinct families: Meters with electro-mechanical displays: CE range Meters with digital displays: ME range
Technical detailsCE, Cer Operating temperature: -25 to +55°C Power consumption: 5VA Utilisation for all types of load up to 10% of third
current harmonics Connection via tunnel terminals: 2.5mm2 and
up to 50mm2
ME Accuracy class: 2 Frequency: 50/60Hz Consumption: 2.5VA Total meter: On a phase (single phase network), on the 3 phases
(three phase network) Capacity
- ME1, ME1z, ME1zr, ME3, ME3zr, ME4, and ME4zr:999.99 MWh
- ME4zrt associated with a CT rating < 150A999.99 MWh
- ME4zrt associated with a CT rating > 150A: 9999.99 MWh
Display: in kWh or MWh with 5 significant digits Partial meter: On a phase (single phase network), on the 3 phases
(three phase network) With RESET Capacity:
- ME1z, ME1zr, ME3zr and ME4zr: 99.99 MWh- ME4zrt associated with a CT rating < 150A:
99.99 MWh- ME4zrt associated with a CT rating > 150A:
999.99 MWh Display: in kWh or MWh with 4 significant digits Flashing meter indicator (yellow) on front panel Operating temperature: -25°C to +55°C Connection using tunnel terminals: Primary connection: 6mm2
Secondary connection: 16mm2
Conform to IEC 1036 standard (with a sealableenclosure)
3P+N network SP networkuse of 3 TI use of 2 TI
Ph-N voltage Ph-Ph voltage230V 400V
Maximum current Maximum power Maximum power(A) (kW) (kV)
50 34.5 40100 69 80200 138 160400 276 320
17067
15464
66
CE/ME watt hour metersMetering and measurement
ME1zr ME3ME3zr
ME4zrt
N N L L
N L
N L
17067
MERLIN GERIN
ME1zr
10(63)A Cl. 2230Va50/60Hz
1000 imp. / kWh
1 imp. / kWh
kWh
To impulsemeter (ME1zr)
L1 L2 L3
L1 L2 L3
17076
L2 L3 L3L1 L1 L2
MERLIN GERIN
ME3zr
0.1 imp. / kWh
100 imp. / kWh
kWh
10(63)A Cl. 23x400V - 3x230V - 50/60Hz
To impulsemeter (ME3zr)
L1 L2 L3
P1
P2 S2
S1
P1
P2 S2
S1
P1
P2 S2
S1
17072
MERLIN GERIN
ME4zrt
10/x imp. / kWh
S1S1 S2 S2S1 S2
L2 L3N L1
(L1) (L2) (L3)
10000/x imp./kWh
kWh
To impulsemeter
ME4ME4zr
ME4zrt CE 1P
N L1
N L2 L3 L3L1 L1 L2
L2 L3
N
N L1 L2 L3
17071
MERLIN GERIN
ME4zr
10(63)A Cl. 23x230/400Va 50/60Hz
0.1 imp. / kWh
100 imp. / kWh
kWh
To impulsemeter (ME4zr)
N L1 L2 L3
P1
P2 S2
S1
P1
P2 S2
S1
P1
P2 S2
S1
17072
MERLIN GERIN
ME4zrt
10/x imp. / kWh
S1S1 S2 S2S1 S2
L2 L3N L1
(L1) (L2) (L3)
10000/x imp./kWh
kWh
To impulsemeter
3 5 7 9 11 13 15 2523
N L
N L
In = 25 A In = 90 A
U
IIN
17 19 211
4 6 8 10 12 14 16 262418 20 222
262420 22 262420 22
CE 3P CEr 1P
3 5 7 9 11 13 15 2523
L1
L2
L3
N
U
IL1
IL2
IL3
IN
S1
P1
S2
S1
P1
S2
S1
P1
S2
17 19 211
18 20 22 24 26
50 A100 A200 A400 A
3 5 7 9 11 13 15 2523
L
L
In = 25 A In = 90 A
U
IIN
17 19 211
4 6 8 10 12 14 16 262418 20 222
262420 22 262420 22
67
CE/ME watt hour metersMetering and measurement
Operation CE CE CE ME1 ME3 ME4 ME4zrtCEr CEr CEr ME1z ME3zr ME4zr(1P) 3P 230V 3P 400V ME1zr
Single phase
Three phase
Three phase + neutral
Rated voltage230V (1P+N)
230V (3P)
400V (3P)
127/230V (3P+N)
230/400V (3P+N)
Frequency (50/60Hz)
Direct measurement current (A)For single phase 25 or 90 63For three phase 63 63Current measurement 50 - 400 50 - 400 40 - 6000via CT (A)Total meter
Total meter capacity 999.99 MWh 999.99 MWh 999.99 MWh 999.99 MWh 999.99 MWh 999.99 MWh With CT ≤150A999.99 MWhWith CT ≥ 150A999.99 MWh
Partial meter ME1z/ME1zr ME3zr ME4zr(with RESET)
DisplayElectro-mechanical
(6 significant digitsin kWh)Digital (5 significant
digits in kWh or MWhRemote transfer CEr CEr ME1zr ME3zr ME4zr
Type Rating Voltage Width Part No.(A) rating in 18mm
(Vac) ways
Single phaseCE 25 or 90 230 6 15464Cer 25 or 90 230 6 15466ME1 63 230 2 17065ME1z 63 230 2 17066ME1zr 63 230 2 17067
Three phase three wireME3 63 3x400 4 17075ME3zr 63 3x400 4 17076
Three phase four wireCE 50 - 400(via CT) 3x230/400 6 15465Cer 50 - 400(via CT) 3x230/400 6 15467ME4 63 3x230/400 4 17070ME4zr 63 3x230/400 4 17071ME4zrt 40 - 6000(via CT) 3x230/400 4 17072
17067
15464
For more information refer to publication Ref’s: MGD 5171 and MGD 5195
68
CH/CI countersMetering and measurement
15440
15443
ApplicationThe CH counters measure the total operating time of any load. The CI counterscount 230Vac pulses from devices such as utility meters or people counters.
Technical detailsCH Electromechanical display Maximum display: 99999.99 hours Display accuracy: 0.01% Without reset Storage temperature: -25°C to +85°C Connection: tunnel terminals for 2.5mm2 cable Consumption: 0.15VA Operating temperature: -10°C to +70°C Mounting on symmetrical rail
CI Supply and metering voltage: 230Vac,
50/60 Hz Consumption: 0.15VA Maximum display: 9 999 999 impulses Without reset Metering data Minimum impulse time: 50ms Minimum time between 2 impulses: 50ms Storage temperature: -25°C to +85°C Operating temperature: -10°C to +70°C Connection: tunnel terminals for 2.5mm2 cable
CH CI
Load
CH2 3
Load
CI2 3
Kwh
Type Control Width Part No.voltage in 18mm
waysCH 230Vac 2 15440CI 230Vac 2 15443
69
TI current transformersMetering and measurement
ApplicationTI are a range of current transformers with a ratio of x/5 for use with measurementdevices (AMP, ME) and control devices.
Technical details Suited to all types of modular electrical
switchboards and enclosures Easy installation on symmetrical rail Easy, reliable connection using tunnel terminals,
terminals for lugs or screw terminals Compliance with standards: IEC 44-1,
NEF 42502, VDE 0414, BS 7626 and IEC 38-1 Degree of protection: IP20 Ambient installation temperature: Standard range: -5°C to +55°C, humidity < 95%, Tropicalised range: -25°C to +60°C
humidity > 95% Storage temperature: -40°C to +80°C
TI electrical data Maximum voltage rating Ue: 720V Secondary current: 5A Frequency: 50 - 60Hz
TI mechanical data Maximum dimensions of primary circuit opening
and weight:
Specific technical dataRing type current transformers Secondary connection using terminals for crimped
lugs, tunnel terminals or using studs (dependingon Part No.)
Delivered with:
Part No. Opening Diameter Weight(mm) (mm) (g)
16500 - 16506 and 16451 - 16456 20x5 21 20016509 - 16515 and 16459 - 16465 30x10 22 27016518 - 16521 and 16468 - 16471 40x10 35 43016523 - 16524 and 16473 - 16474 64x11 and 51x31 50016526 - 16535 and 16476 - 16483 65x32 32 60016537 - 16538 34x84 70016540 - 16544 38x127 150016545 - 16547 52x127 150016548 - 16549 55x165 5000
Part No. Adaptor Adaptor Insulated Sealablefor fixing for fixing binding coveron a on a screwsymmetrical platerail
16500 - 16506 and 16451 - 16456
16509 - 16515 and 16459 - 16465 Optional16518 - 16521 and 16468 - 16471 Optional16523 - 16524 and 16473 - 16474
16526 - 16535 and 16476 - 16483
16537 - 16538
16540 - 16544
16545 - 16547
16548 - 16549
For further details on selecting a current transformer, see page 161.
16503
70
TI current transformersMetering and measurement
16503
16512
Rating Part No. Part No. Part No.standard tropicalised cylinderTI TI
40/5A 16500 1655050/5A 16501 16451 1655075/5A 16502 16452 16550100/5A 16503 16453 16550125/5A 16504 16454 16550150/5A 16505 16455 16550
16509 16459200/5A 16506 16456 16550
16510 1646016526 16476
250/5A 16511 16461 1655116518 1646816627 16477
300/5A 16512 16462 1655116519 1646916528 16478
400/5A 16520 1647016529 1647916513* 16463 16551
500/5A 16521 1647116523 1647316530 1648016514* 16464 16551
600/5A 16524 1647416531 1648116515* 16465 16551
800/5A 16532 164821000/5A 16533 164831250/5A 16534
1653716540
1500/5A 165351653816541
2000/5A 165422500/5A 16543
16545300/5A 165444000/5A 165475000/5A 165486000/5A 16549* Only for use with cylinder
Power (VA) Accuracy class0.5 1 3
22.531.544
62.517.541.58510.51028124814.512.5152012822.5151015204025606070
1.251.252.5445.56729541186127.515124101861021.515202515123020152025503080120120
11.53456.56.578.55118613.512715101815612228122620253020
3525
60
100
Accessories Part No.Sealable cover for 16509 - 16515 and 16459 - 16465 16552Sealable cover for 16518 - 16521 and 16468 - 16471 16553
71
TH modular thermostatsEnergy management
ApplicationThe TH3 and TH6 modular thermostats offer close tolerance temperature control fora variety of applications.
Technical data Output contact rating: 5 A at 250Vac cos Ø =1 1 A at 250Vac cos Ø = 0.6 Electronic thermostat: Consumption: 2VA Temperature difference between tripping and
activation: ± 0.2°C Degree of protection: IP20
Specific technical dataTH3 Three indicator lights visualise: Above freezing operation (green) Reduced operation (yellow) The make position of the output contacts (red) Connection: 6mm2 tunnel terminals Delivered with ambient temperature probe
TH6 Indicator light: a (red) light emitting diode
visualises the make position of the outputcontacts
Connection: 2 x 2.5mm2 tunnel terminals Delivered without probe
15840
15841
Type Temperature Width in Part No.range 18mm(0C) ways
TH3 (c/w probe 15846) +8 to +26 4.5 15841TH6 -30 to +90 4.5 15840
AccessoriesGround probe 15845Ambient probe 15846Outdoor probe 15847Collar probe 15848
TH3 TH6
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16
NL
220/240V
NOLAmbienttemperaturecontrol
External contacts
Abovefreezing
Reducedsetpoint
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16
NL
220/240V
NOLAmbienttemperaturecontrol
72
Unit mounted residual current devices
RMG residual current devices 74
RMG auxiliaries 75
RMG accessories 76
RMG enclosures 77
Section three
The devices featured in Section three are not suitable formounting in the Isobar 4 outgoing connection system
73
RMG residual current devicesRatings: 16 - 100ASensitivities: 10 - 300mA, time delayed
74
3 phase 3 wire 415V applicationsIn applications where no neutral is available an auxiliarytest resistor is required for test button operation.Note: Device operation is independent of voltage or typeof connection.30mA 2700Ω 4 watt100mA 820Ω 4 watt300 mA 270Ω 4 wattNote: Resistors are not available from Merlin Gerin.
FEED
LOAD
N R Y B
or
FEED
LOAD
N R Y B
Type RMG RCD - two pole 240V Class ACRating Sensitivity Part No.(A) (mA)16 10 RMG 16 010 225 10 RMG 25 010 225 30 RMG 25 030 240 30 RMG 40 030 240 300 RMG 40 300 263 30 RMG 63 030 263 100 RMG 63 100 263 300 RMG 63 300 280 30 RMG 80 030 280 100 RMG 80 100 280 300 RMG 80 300 2100 30 RMG 100 030 2100 100 RMG 100 100 2100 300 RMG 100 300 280 100time delayed 50 - 70ms 23111100 300time delayed 50 - 70ms 23116100 100time delayed 50 - 70ms RMG 1001002S
Type RMG RCD - four pole 415V Class ACRating Sensitivity Part No.(A) (mA)25 30 RMG 25 030 425 300 RMG 25 300 440 30 RMG 40 030 440 300 RMG 40 300 463 30 RMG 63 030 463 100 RMG 63 100 463 300 RMG 63 300 463 300time delayed 50 - 70ms 2314680 30 16261100 300 23213100 300time delayed 50 - 70ms 23227
Type RMG RCD Class ARating No. of Part No.(A) poles25A 30mA 2 2324940A 30mA 2 2325363A 30mA 2 23258
40A 30mA 4 2330363A 30mA 4 23308
ApplicationType RMG residual current devices provide the functions of isolation, switching andearth leakage protection of electrical circuits. They have a residual current operatedelectro-mechanical release which operates without any auxiliary source of supply toopen a circuit automatically in the case of an earth leakage fault between phase andearth greater than or equal to a threshold of 10, 30, 100, or 300mA.
Specifications RCD: BS EN 61008
Technical data Positive contact indication in accordance with
BS 7671Unwanted trippingAll RMG rcd's incorporate a filtering device preventingthe risks of unwanted tripping due to transient voltages(lightning, line disturbances on other equipment...) andtransient currents (from high capacitive circuits.)
Electrical data Current ratings: 16A - 100A Voltage ratings: 2 pole: 110/240Vac,
4 pole: 240/415Vac Cable capacities
16A - 80A: tunnel terminals for cables up to 35mm2
100A: clamp terminals for cables up to 50mm2
Number of operating cycles: (on load) 20,000 cycles (O-C)
Operating temperature: -5 to +40°C Identification system: All RMG RCDs can accept
up to a total of 4 marking accessories on each of their poles.
Width in 18mm SP ways:2P RMG all ratings: 24P RMG all ratings: 4
Installation On symmetrical DIN rail Panel mountingNote: RMG residual current devices must be used withcircuit breakers to provide circuit protection of overloadand short circuit faults. Dimensions: see page 170
RMG 80 030 2
75
Electrical auxiliaries for 2 and 4 pole RMGs
Shunt trip release (MX) Enables remote tripping Is equipped with a cut off switch in series with the
coil allowing control circuit to remain energised Includes one auxiliary changeover switch (OF) Red flag trip indicator Mounted on the LHS of the OFS Cable capacity 2.5mm2
Arrangement of auxiliaries
Note: both 2P and 4P RMG type residual currentdevices can be fitted with the above combinations of electrical auxiliaries. Note: OFS required for all combinations.
Auxiliaryswitch OF
Shunt tripmodule MX
Undervoltagetrip module MN
Auxiliaryswitch OF.S
RCD
OF
OF
OF
MXor
MN
MXor
MN
R
M
G
R
M
G
R
M
G
OFS
OFS
OFS
MXor
MN+
+ + + +
+
+ + + +
Width Coil Consumption Partin 18mm volt pickup W or VA No.SP ways1 130Vdc 10 269461 240Vac 50 269461 415Vac 120 269461 48 - 60Vdc 22 269471 48 - 130Vac 200 269471 24Vac/dc 120 26948Also requires OFS 26923
Undervoltage release (MN) Enables the RCD to be tripped either when the
auxiliary supply voltage drops or by the opening operation of a normally closed remote pushbutton
Prevents the RCD from being switched 'ON' again if the undervoltage release supply is not present
Red flag trip indicator Mounted on the LHS of the OFS Cable capacity 2.5mm2
Width Coil Consumption Partin 18mm volt pickup W or VA No.SP ways1 220/240Vac 4.1 269601 48Vac/dc 4.3 26961Also requires OFS 26923
Auxiliary switch (OFS) A changeover switch which acts as an indicating
or control device to monitor the ON or OFF positions of an RCD
The OFS also acts as an adaptor mounted on the LHS of RCD, between the RCD and any other auxiliaries (additional OF, MX, MN, mounted on LHS of OFS). Indicates type of RCD
Cable capacity 2.5mm2
Auxiliary switch (OF) Changes main contacts to ON/OFF Test button on front face Cable capacity 2.5mm2
Width Partin 18mm No.SP ways0.5 OFS 26923Contact ratings (A): 3A at 415Vac 1A at 125Vdc 6A at 24Vdc 6A at 240Vac 2A at 48Vdc
Width Partin 18mm No.SP ways0.5 OF 26924Also requires OFS 26923
26946
26960
26923
26924
Description Part No.Padlocking bag of 2 26970Padlock + 2 keys MGPLSpare key for MGPL MGPLSK
76
AccessoriesRMG type residual current devices
Description Part No.Two piece unit for use with 2PRMG RCDs (except 100A unit) 26976Two piece unit for use with 4PRMG RCDs 26978
Description Part No.For use with 2P and 4PRMG RCDs (2 strips of 4) 26981
26978
26981
Terminal shields Two piece: completely covers terminals
(cannot be fitted to 100A 2 pole unit)
Sealable terminal screw shield Enables total isolation of the terminal screws 2P and 4P RMG RCDs only
Padlocking facility
77
EnclosuresRMG type residual current devices
Metal All insulated
Capacity in Part No.18mm SP ways3 995604 145995 14603
Capacity in Part No.18mm SP ways2 133924 133946 133968 13398 Dimensions: see page 189 For 2P RMG RCDs use 13392 For 4P RMG RCDs use 13394
Capacity in Part No.18mm SP ways4 134416 134428 1344312 13444
Lock & key 13948Sealing kit 13947Bag of membrane glands 14190 Dimensions: see page 190
14599
13394
13441
Dimensions: see page 189 For 2P RMG RCDs use 99560 For 4P RMG RCDs use 14599.
G9 enclosure IP30For a more comprehensive range of enclosures please refer to Section seven. Made from folded steel, epoxy powder coated Degree of protection: IP30 It consists of: A back plate with DIN rail A cover screwed to the back plate having 25mm knockouts top and bottom
Mini opale IP30Impact resistant, all insulated enclosure self extinguishing to 650°C. Degree of protection: IP30 It consists of: An insulated back plate with integral DlN rail A cover clipped to the back plate Four hole terminal bar (also available separately -
(1 X 16mm2 + 3 X 10mm2) Part No. 14901)
Kaedra weatherproof IP65 Degree of protection: IP65 Protection against mechanical damage IK09 Self extinguishing insulating material Flame and abnormal heat resistance 6500C,
IEC 60695-2-1 Class 2: total insulation They are supplied complete with: Built in dividable blanking plate Screwed cover with hinged transparent window 13441 - 13443 two terminal blocks 4 holes each 13444 - two terminal blocks 8 holes each Accessories: see page 131
78
Circuit breakers Section four
DPN MCBs, 1 - 40A 80
DPN RCBOs, 6 - 40A 81
C120 MCBs, 10 - 125A 82 - 83
C120 Vigi’s, 10 - 125A 84 - 85
DPN/C60/C120 auxiliaries 86 - 89
DPN/C60/C120 accessories 90 - 91
NG125 MCBs, 10 - 125A 92 - 98
NG125 Vigi’s, 10 - 125A 99 - 103
NG125 auxiliaries 104 - 107
NG125 accessories 108 - 109
P25M, 0.16 - 25A 110 - 111
The devices featured in Section four are not suitable formounting in the Isobar 4 Connection System
79
DPNMiniature circuit breakers 1P + switched neutralRatings 4 - 40A, breaking capacity 6kA
80
ApplicationsProtection and control of circuits against overloads and short circuits where switching of the neutral is required.
DPN type B For use in applications with general load
characteristics 2 pole switching in single pole width. Phase only
protected Tripping characteristics: BS EN 60898 type B
magnetic setting between 3 and 5 In
Installation Panel mounting on symmetrical DIN rail in
multi-service type boards and standardenclosures
Technical data Current rating: 1 to 40A at 300C Voltage rating: 240Vac Breaking capacity: BS EN 60898, 6kA Operating cycles: Mechanical: 20,000
Electrical: 20A, 20,00025A, 15,00032A, 10,00040A, 6,000
Positive contact indication: in accordance withBS 7671
Width: 18mm Weight: 120g Cable capacity: 16mm2
Tightening torque: 2.5Nm
Accessories: see page 96Dimensions: see page172
Rating Part Width in 18mm(A) No. SP ways4 19249 16 19250 110 19252 116 19254 120 19255 125 19256 132 19257 140 19258 1
DPN type C For use in applications with moderate inrush
currents 2 pole switching in single pole width. Phase only
protected Tripping characteristics: BS EN 60898 type C
magnetic setting between 3 and 10 In
Rating Part Width in 18mm(A) No. SP ways1 19260 12 19261 14 19263 16 19264 110 19266 116 19268 120 19269 125 19270 132 19271 140 19272 1
19271
DPN RCBOCombined MCB/RCD
1P + switched neutral
81
19668
DPN comb busbar 100A/240V IEC664
2 pole switching of phase & neutral. Phase protected against overloads and short circuits
Commercial, industrial and domestic electrical distribution systems
Note: must not be used as the sole means of providing protection against direct contact (BS7671).
Technical data Nominal voltage: 110/240V Breaking capacity: 6000A Ics to BS EN 60898,
and earth leakage tested to BS EN 61009 Tripping characteristics: C curve: the magnetic
release operates between 5 and 10 In Positive contact indication of the phase
conductor: in accordance with the IEE WiringRegulations BS7671
Sensitivity: (non-adjustable) 30mA: unwanted tripping: The DPN rcbo incorporates afiltering device, preventing the risks of unwantedtripping due to transient voltages (lightning, line disturbances on other equipment and transientcurrents from high capacitive circuits)
Visual indication of trip due to earth faults AC Class Cable capacities: Tunnel terminals up to 16mm2
Weight: 190g Installation: Panel mounting on symmetrical DIN
rail in multi-service type boards and standardenclosures
Padlocking in the ON/OFF position by using Part No. MGLA or 26970
Type Width Sens. Rat. Part No.in (mA) (A)18mmSP ways
N + 1P 2 30 6 1966110 1966316 1966520 1966625 1966732 1966840 19669
N 1P
R
N 2
Comb busbarsComb busbars enable several circuit breakers to besupplied with power. The supply to the comb busbar can be connected: Directly across the circuit breaker terminals by a
16mm2 cableOR
Via 25mm2 connectors. Suitable for use with DPNMCBs and DPN vigi or combinations of both
Characteristics Current rating at 400C: 100A with a central connector 125A with two supply points
Clip-on markers Markers can be installed: On the front face (max. 6 markers) Or above the downstream terminals (max. 4
markers).
Type No. of MCBs Part no.Comb busbar1P+N 13 148801P+N 24 14890(bag of 2)25mm2 insulated 14885connector (bag of 4)
235max.13 MCBs
27
10
15
432max.24 MCBs
ApplicationProtection against the effects of earth leakage, overload and short circuit currents.
1 protected pole + switched neutral
C120H circuit breakersB, C and D curvesRatings 10 - 125A, breaking capacity 15kA
82
ApplicationsC120 MCBs provide high levels of current capacity,while maintaining a breaking capacity of 15kA.Available with a wide range of add on earth leakageand control accessories, C120H provides a physicalreplacement for the previous NC100 range of deviceswith B, C, and D type characteristics and 1 - 4 poles. Protection of cables against overloads and short
circuits in final distribution Manual control and isolation Earth leakage protection when combined with a
Vigi to BS EN 61009 Remote tripping, indication, by adding auxiliaries
common to the entire C60/C120 rangeSee page 88
Technical data Current rating: 10 - 125A Maximum voltage rating Ue: 440Vac Insulation voltage Ui: 500V Impulse withstand voltage Uimp: 6kV Complies with: BS EN 60898 and
BS EN 60947-2 Breaking capacity: BS EN 60898Type Voltage Breaking
(V) capacity Icn (A)1, 2, 3, and 4P 230 - 400 15000
Breaking capacity: BS EN 60947-2Type Voltage Breaking
(V) capacity Icu (A)1P 130 30000
230 - 240 15000400 - 415 4500 (1)
2, 3 and 4P 230 - 240 30000400 - 415 15000440 10000
(1) Breaking capacity under 1 pole with IT isolatedneutral system (case of double fault).
Service breaking capacity: Ics = 50% Icu Positive contact indication Fast closing ensures simultaneous closing of
poles Electrical durability: ≤63A: 10,000 cycles (O-C) 80 - 125A: 5,000 cycles (O-C) Limitation class: 3 Mechanical durability: 20,000 cycles (O-C) Weight:Pole Grams1 2052 4103 6154 820
Connection: Flexible cables: 1.5 - 35mm2
Rigid cables: 1 - 50mm2
Tightening torque: 3.5Nm Terminals ensure: Degree of protection IP2X Clamping of wide cross section cables Automatic guiding of cable into the correct
position Markers: 4 marker clips next to the upstream terminal Label holder on handle (2, 3 and 4 pole) Degree of pollution: 3
1, 2, 3 and 4 pole Type B C120H miniature circuit breakers
1, 2, 3 and 4 pole Type C C120H miniature circuit breakers
1, 2, 3 and 4 pole Type D C120H miniature circuit breakers
C120H circuit breakersB, C and D curves
Ratings 10 - 125A, breaking capacity 15kA
83
B curve Applications:
Protection andcontrol of circuitsagainst overloadsand short circuits inapplications withgeneral loadcharacteristics
Trippingcharacteristics:BS EN 60898 Type B. Magneticsetting between 3and 5 In
Note: These products are not suitable for use with Isobar 4 connection system.
Note: These products are not suitable for use with Isobar 4 connection system.
Note: These products are not suitable for use with Isobar 4 connection system.
Ratings 1P Width in 2P Width in 3P Width in 4P Width in(A) 18mm 18mm 18mm 18mm
SP ways SP ways SP ways SP ways101620253240506380100125
C120H Type B curve miniature circuit breaker Part No’s
1839418395183961839718398183991840018401184021840318404
1.51.51.51.51.51.51.51.51.51.51.5
1842718428184291843018431184321843318434184351843618437
66666666666
1840518406184071840818409184101841118412184131841418415
33333333333
1841618417184181841918420184211842218423184241842518426
4.54.54.54.54.54.54.54.54.54.54.5
C curve Applications:
Protection andcontrol of circuitsagainst overloadsand short circuits inapplications withmoderate inrushcurrents
Trippingcharacteristics:BS EN 60898 Type C. Magneticsetting between 5and 10 In
Ratings 1P Width in 2P Width in 3P Width in 4P Width in(A) 18mm 18mm 18mm 18mm
SP ways SP ways SP ways SP ways101620253240506380100125
C120H Type C curve miniature circuit breaker Part No’s
1843818439184401844118442184431844418445184461844718448
1.51.51.51.51.51.51.51.51.51.51.5
1847118472184731847418475184761847718478184791848018481
66666666666
1844918450184511845218453184541845518456184571845818459
33333333333
1846018461184621846318464184651846618467184681846918470
4.54.54.54.54.54.54.54.54.54.54.5
D curve Applications:
Protection andcontrol of circuitsagainst overloadsand short circuits inapplications withhigh inrush currents
Trippingcharacteristics:BS EN 60898 Type D. Magneticsetting between 10and 14 In
Ratings 1P Width in 2P Width in 3P Width in 4P Width in(A) 18mm 18mm 18mm 18mm
SP ways SP ways SP ways SP ways101620253240506380100125
C120H Type D curve miniature circuit breaker Part No’s
1848218483184841848518486184871848818489184901849118492
1.51.51.51.51.51.51.51.51.51.51.5
1851518516185171851818519185201852118522185231852418525
66666666666
1849318494184951849618497184981849918500185011850218503
33333333333
1850418505185061850718508185091851018511185121851318514
4.54.54.54.54.54.54.54.54.54.54.5
1
2
1
2
3
4
1
2
3
4
5
6
1
2
3
4
5
6
7
8
Vigi C120 modulesAdd on residual current devices for use with C120 MCBsStandard and si type, BS EN 61009-IEC 60497.2 appendix B
84
Common technical data The Vigi C120 module incorporates the residual
current relay and toroid in a case. Its earth leakage module is electro-mechanical. It functionswithout an auxiliary power supply source and thushas a very wide operating range
Protected against nuisance tripping due to transient overvoltages (lightning strike, switchgearswitching on the network, etc.)
Breaking and making capacity upon short circuitis equal to the breaking capacity of the circuitbreaker
Instantaneous or selective s trip units Reinforced electromagnetic compatibility
Technical data for standard type AC class: standard, 50 - 60Hz 8/20ms impulse withstand: Instantaneous: 250A peak Selective: 3kA peak Impulse withstand: Instantaneous: 3kA peak Selective: 5kA peak Remote tripping: possible using an MX or MN
release on circuit breaker Connection: Identical to C120 circuit breakers: Flexible cables: 1.5 - 35mm2
Rigid cables: 1 - 50mm22
Tightening torque: 3.5Nm Width of C120 residual current device + Vigi
module: (in number of 18mm SP ways)
2P 3P 4P6.5 (3+3.5) 9.5 (4.5+5) 11 (6+5)
Weight (g):
2P 3P 4P325 500 580
Fault indication by means of a red strip on theresetting handle
Resetting the Vigi module, at user's convenience:
Either using the circuit breaker handle Or independently of the circuit breaker Test button on front face for local operation check
Common function
The protection of electrical installations against earth faults
The protection of persons against indirect contact:medium sensitivities (300, 500, 1000mA)
Supplementary protection of persons against accidental direct contact: high sensitivity (30mA)
The C120 residual current device complies with BS EN 61009. It is equipped with a locating devicethat ensures the correct rating and number of poles.
The technical data of C120 circuit breakers whencombined with Vigi modules remain unchanged andthe circuit breakers remain compatible with indicationor control auxiliaries.
Trip sensitivity AC class
Tripped by sinusoidal AC currents whether they are quickly applied or rise slowly
A classA class: ensures tripping with a DC component current. Tripped by sinusoidal AC currents as well as by pulsed DC currents whether they are quickly applied or rise slowly
Trip typeInstantaneousProvides a trip upon reaching threshold (no intentionaltime delay).
Selective sProvides discrimination with down stream device byintroducing an intentional time delay. Down streamdevice must be instantaneous with a sensitivity of 1/2the upstream device.
siProvides continuity of supply on circuits with a disturbed supply network. Used where there is a highrisk of nuisance tripping due to: Lightning strikes IT earthing systems Switched electronic ballastsDesensitised by: Harmonics or high frequencies DC components
Combination of earth leakage moduleswith circuit breakers
C120 circuit breaker Vigi C120 module C120 residual current device
+ =
T
Vigi C120 modulesAdd on residual current devices for use with C120 MCBs
AC, A, si class, BS EN 61009
85
1 3
2 4
T1 3 5
2 4 6
T1 3 5 7
2 4 6 8
18563 18546 18549
Sens. 2P Width in 3P Width in 4P Width in(mA) 18mm 18mm 18mm
SP ways SP ways SP ways30300300 s5001000 s
Class AC, C120 Vigi module. 230 - 415V
1856318564185441856518545
3.53.53.53.53.5
1856618567185461856818547
55555
1856918570185481857118549
55555
18572
2 pole devices 3 pole devices 4 pole devices
18584 18589
Sens. 2P Width in 3P Width in 4P Width in(mA) 18mm 18mm 18mm
SP ways SP ways SP ways30300300 s500500 s1000 s
Class A, C120 Vigi module. 230 - 415V
185721857318581185741858218583
3.53.53.53.53.53.5
185751857618584185771858518586
555555
185781857918587185801858818589
555555
18591 18558 18561
Sens. 2P Width in 3P Width in 4P Width in(mA) 18mm 18mm 18mm
SP ways SP ways SP ways30300300 s5001000 s
Class si, C120 Vigi module. 230 - 415V
1859118592185561859318557
3.53.53.53.53.5
1859418595185581859618559
55555
1859718598185601859918561
55555
Electrical auxiliariesFor DPN, C60 and C120
86
ApplicationsThe TM unit provides remote control of C60 and C120 circuit breakers via an electrical signal. For security or energy management, TM can be used to controllighting motors or heating.
For the remote control and status indication of DPN, C60 or C120 MCBs.
They are mounted to the left of the circuit breakerwithin a maximum width of 54mm
Fixed using clips (no tools) onto the left side of the circuit breaker Compatible with Vigi modules (fitted to the right side) A maximum of 3 indication auxiliaries on the same circuit breaker A maximum of 2 changeover auxiliaries (OF+SD/OF) on the same
circuit breaker A maximum of 2 tripping auxiliaries (MX + OF or MN) on the same
circuit breaker A maximum of 1 tripping auxiliary (MN s or MNx or MSU) on the same
circuit breaker
++++++
OF+SD/OFauxiliarycontact
OFauxiliarycontact
SDfault
indicationswitch
MN s , MNx or MSUauxiliary
MX + OF or MNauxiliary
TMremote control
Circuitbreaker
TM remote controlsFor C60 and C120
87
Tm modules allow: Remote control of C60/C120 circuit breakers (with
or without a Vigi module)via a latched order Circuit breaker resetting after tripping, while
respecting safety rules and regulations in force A disconnection selector switch placed on the
front panel is used to: Disconnect the remote control Lock the remote controlled circuit breaker in the
"open" position (7 mm Ø padlock not supplied) A mechanical indicator shows the "open" or
"closed"status of the Tm remote control Reclosing after a fault: Must be carried out in manual mode,locally after
search and clearance of the fault To enable manual and local resetting, an SD
auxiliary switch (cat.no.26927),cabled in series inthe control line of the Tm to module, prevent automatic remote reclosing
Remote reclosing is possible provided regulationsare complied with:resetting takes place by opening the control circuit for more than 1.5s
Technical data Control voltage (Uc): 230Vac (-15% +10%) Frequency: 50 - 60Hz Consumption: Inrush: -Tm C60:28VA, -Tm C120:35VA Holding: 2VA Insensitive to brownouts: 0.45s Undervoltage behaviour: >0.45s,mechanical opening of poles Reclosing 2s after power is restored Number of cycles (O-C)at 40°C: Tm +C60:20 000 Tm +C120 (63A):10 000 Tm +C120 (80 - 125A): 5 000 Opening time by Tm: 0.5s Closing time by Tm: 2s
Connection Using tunnel terminals: 1 x 6mm2 cable 2 x 1.5mm2 or 2.5mm2 cables
Weight 1 - 2P: 300g 3 - 4P: 310g
Possible Voltage Part No. Width incombinations (V) 18mm SP
waysC60 1 - 2P 230 18310 3.5C120 1 - 2P 230 18312 3.5
Possible Voltage Part No. Width incombinations (V) 18mm SP
waysC60 3 - 4P 230 18311 3.5
MX
MN
SD
OF
auto
230V ~
A2
A1
MX
MN
SD
OF
auto
230V ~
A2
A1
18310
18311
U>
Electrical auxiliariesFor DPN, C60 and C120
88
MN (under voltage release)Instantaneous Control Part No. Width in
voltage 18mm SP(Vac) (Vdc) ways220 - 240 26960 148 48 26961 1115 (400Hz) 26959 1220 - 240 Delayed s 26963 2Disconnects the MCB when a voltage is removed.
MNx emergency stopPh + N Control Part No. Width in
voltage 18mm SP(Vac) ways230 26969 2230 26977 2*400 26991 2*400 26971 2
MX shunt releaseControl Part No. Width involtage 18mm SP (Vac) (Vdc) ways110 - 415 110 - 130 26476 148 48 26477 112/24 12/24 26478 1
U>
14 12 C2 C1
U<
E1 E2 N L
U>>
N L
U<
D1 D2
26946
26476
26979
26963
26969
* For use with C60 only.Disconnects the MCB when the normally closed pushbutton contact is opened. Does not trip in the event ofpower supply failure.
MX + OF (shunt release and auxiliary contact)Control Part No. Width involtage 18mm SP(Vac) (Vdc) ways110 - 415 110 - 130 26946 148 48 26947 112/24 12/24 26948 1Disconnects the MCB when a voltage is applied. Indication of tripping and fitted with changeover contact for indication and self breaks control circuit allowing it to remain energised.
MSU (voltage threshold release)1P + N Control Part No. Width in
voltage 18mm SP(Vac) ways220 - 240 tripping at 255V 26979 2*220 - 240 tripping at 275V 26479 2*
C1C2
Electrical auxiliariesFor DPN, C60 and C120
89
SD fault indicating switchPart No. Width in
18mm SPways
26927 0.5
Contact rating (V) (A)240Vac 6A415Vac 3A24Vdc 6A48Vdc 2A125Vdc 1A
OF auxiliary contactPart No. Width in
18mm SPways
26924 0.5
Contact rating (V) (A)240Vac 6A415Vac 3A24Vdc 6A48Vdc 2A125Vdc 1A
OF + SD/OF selector switchPart No. Width involtage 18mm SP
ways26929 0.5
94 92 91
24 22 2192 94 91
14 12 11
26927
26924
26929
Auxiliary contactchanges when devicetrips, with front faceindication.
Auxiliary contactchanges with maincontacts (ON/OFF)with test button onfront face.
Auxiliary contact andselectable auxiliary orfault contact with frontface indication.
AccessoriesFor C60 and C120
90
Padlocking facilityBreaker Quantity Part No.C60 Pack of 5 MGLAC120 Pack of 2 27145
Screw shieldBreaker Quantity Part No.C60 Sealable and dividable
2 strips of 4 26981C60 vigi 1P shields pack of 20 26982C120 Sealable and dividable
2 strips of 4 18527
Terminal shieldBreaker Pole Part No.C60 1 26975
2 269763 269754 26976 + 26978
C120 1 185262 2 x 185263 3 x 185264 4 x 18526
Insulated sub distribution terminalBreaker Quantity Part No.C60/C120 Pack of 4 19091For 3 x cables up to 16mm2 each.
Aluminium cable terminalBreaker Quantity Part No.C60/C120 Pack of 1 27060For cables 16 - 50mm2.
26970
18527
18526
27060
19091
AccessoriesFor C60 and C120
91
Screw connectionBreaker Quantity Part No.C60/C120 Pack of 8 27053
Rear connection terminal with interpole barrierBreaker Quantity Part No.C60/C120 Pack of 2 18528
Inter-pole barrierBreaker Quantity Part No.C60/C120 Pack of 10 27001
SpacerBreaker Width Part No.C60/C120 9mm 27062
Label holderBreaker Quantity Part No.C120 Pack of 10
replacements 27150
Replacement wire cover for vigiblocBreaker Pole Part No.C60 2 26483Pack of 5 3 26484replacements 4 26485
18528
27062
27001
26483
Marking accessoriesThese clip-on markers allow identification of MCBs and RCDs
27017
Circuit breakersStandard Number Rating Type Curves Magnetic Breaking capacity at 415V
of poles (A) threshold (kA)In 16 25 36 50
BS EN 60947-2 1, 2 10 - 80 NG125N C 8
3, 4 10 - 125 NG125N C 8
3, 4 80 - 125 NG125N B 4
3, 4 80 - 125 NG125N D 12
1, 2, 3, 4 10 - 80 NG125H C 8
2, 3 1.6 - 80 NG125LMA MA 12
NG125 circuit breakersSelection
92
Earth leakage modules for trip free circuit breakers and switch disconnectorsStandard Number Rating Vigi Sensitivity Instantaneous
of poles In at 400C type (mA) Instantaneous or selective s(A) Instantaneous Selective s or selective or delayed 150ms
BS EN 60947-2 2, 3, 4 63 Vigi NG125 30 300-500-1000-3000300 300 with fault threshold
1000 indication (1)3 125 Vigi NG125 30 300-500-1000 300-500-1000-3000
with fault threshold indication
4 125 Vigi NG125 30 300-500-1000 300-500-1000-3000300 with fault threshold
indication
Trip free switch disconnectorStandard Number Rating Type
of polesBS EN 60947-3 3, 4 80, 100, 125 NG125NA
(1) Only in 3P and 4P.
Note: This product is not suitable for use with Isobar 4 connection systems.
NG125 circuit breakersSelection
93
Choice of circuit breakersType NG125N NG125H NG125LMA
Impulse voltage Uimp (kV) 8 8 8
Insulation voltage Ui (V) 690 690 690
Maximum voltage rating Ue (V) 500 500 500
Number of poles 1 2, 3, 4 1 2, 3, 4 – 2, 3
Breaking Icu AC 110 - 130V 50 – 70 – – –
capacity 220 - 240V 25 50 36 70 – 100
(kA) 380 - 415V 6 25 9 36 – 50
IEC 947.2 440V – 20 30 – 40
500V – 10 – 12 – 15
DC 60V 25 – 36 – – –
125V – 25 (2P) – 36 (2P) – –
250V – 25 (4P) – 36 (4P) – –
500V – – – – – –
Ics AC 75% Icu 75% Icu 75% Icu
DC 100% Icu 100% Icu 100% Icu
Tripping B curve 40°C 80 - 125 –
curves C curve 40°C 10 - 80 10 - 125 10 - 80 10 - 80
/ratings (A) D curve 40°C 80 - 125 –
MA curve 40°C – – 1.6 - 80
Fast closing
Positive break indication
Auxiliaries
Degree of pollution 3
18668
NG125 switch disconnectorsBS EN 60947-3
94
ApplicationsThe NG125NA is a trip free switch disconnector for on load opening and closing.
This modular device has the same auxiliary functions and accessories asthe NG125 circuit breaker. Vigi NG125 module for earth leakage protection OF + SD auxiliary contact MX or MN releases Various connection types (80, 100 and 125A
ratings) Rotary handle.This modular device has the same
auxiliary
Common technical data Ratings: 63 - 125A Maximum voltage rating Ue: 500Vac Performance as in BS EN 60947.3 Short time withstand current (50ms) Icw:
1.5kA Maximum making capacity: see co-ordination
tables Maximum insulation voltage Ui: 690V Impulse voltage Uimp: 8kV Electrical durability:Voltage Category 63/80A 100/125A500Vac AC22B 1500 1000440Vac AC22B 1500 1000415Vac AC22A-AC23B 1500 1000125Vdc DC22A 1500 1000(2P series)250Vdc DC22A 1500 1000(4P series)
Isolation with positive contact indication Built-in padlocking facility Weight (g):Type 3P 4P
720 960
Compatible with Pragma or Prisma G or Pmodular enclosures
Connection: tunnel terminals for flexible and rigidcopper cables up to 70 mm2
3PMaximum Part No. Width inrating 18mm SP(A) ways63 18889 4.580 18890 4.5100 18891 4.5125 18892 4.5
4PMaximum Part No. Width inrating 18mm SP(A) ways63 18893 680 18894 6100 18895 6125 18896 6
1 3 5
2 4 6
1 3 5
2 4 6
7
8
18891
Note: This product is not suitable for use with Isobar 4 connection systems.
NG125N circuit breakersB, C and D curves
BS EN 60947-2: 25kA
95
ApplicationsThis circuit breaker is specially designed for functions requiring a high breakingcapacity (up to 25kA): modular enclosure incomer, main incomer in sub-distributionswitchboards, outgoer, protection of loads directly supplied by a power switchboard.
Common technical data Rating: 10 - 125A Reference temperature: 40°C Uimp: 8kV Ui: 690V Maximum voltage rating: 500Vac Breaking capacity: as in BS EN 60947-2:Type Voltage Breaking capacity
(Vac) (A)1P 220 - 240 250001P 380 - 415 6000 (1)2, 3, 4P 380 - 415 25000(1) 1 pole breaking capacity in the IT isolated neutralsystem (double fault).
Isolation with positive contact indication 3 position toggle: open-tripped-closed Built-in padlocking facility on 3P and 4P Fault display on front face by: Fault indicator Position of toggle: tripped Test button to check proper operation of the
tripping mechanism Fast closing Electrical durability: 10,000 cycles at In Tropicalisation as in IEC 68.1: treatment 2
(relative humidity: 95% at 55°C) Weight (g):Type 1P 2P 3P 4P
240 480 720 960
Compatible with loose enclosures, refer to Section 6
Degree of protection: IP20B (IP40D for the partoutside the enclosure)
Connection: ≤ 63A ratings: tunnel terminals for 1.5 - 50mm2
copper cables 80 - 125A ratings: tunnel terminals for
16 - 70mm2 copper cables Aluminium cables, copper cables with lug or
busbar (see connection accessories) On 3P and 4P: upstream voltage connection on
each pole, by 6.35mm Fast on lugs, for auxiliarycircuit supply
B curve The magnetic trip units operate at 4 In ± 20%
C curve The magnetic trip units operate at 8 In ± 20%
D curve The magnetic trip units operate at 12 In ± 20%
NG125N circuit breakersB, C and D curves BS EN 60947-2: 25kARatings 10 - 125A
96
18664
Rating 3P Width in 4P Width in(A) 18mm 18mm
SP ways SP ways80100125
B curve NG125N
186631866418665
4.54.54.5
186661866718668
666
18669
Rating 3P Width in 4P Width in(A) 18mm 18mm
SP ways SP ways80100125
D curve NG125N
186691867018671
4.54.54.5
186721867318674
666
18610
Rating 1P Width in 2P Width in 3P Width in 4P Width in(A) 18mm 18mm 18mm 18mm
SP ways SP ways SP ways SP ways101620253240506380100125
C curve NG125N
186101861118612186131861418615186161861718618
1.51.51.51.51.51.51.51.51.5
186211862218623186241862518626186271862818629
333333333
4.54.54.54.54.54.54.54.54.54.54.5
1864918650186511865218653186541865518656186581866018662
66666666666
1863218633186341863518636186371863818639186401864218644
1 pole devices 2 pole devices 3 pole devices 4 pole devices
1
2
1 3
2 4
1 3 5
2 4 6
1 3 5
2 4 6
7
8
Note: This product is not suitable for use with Isobar 4 connection systems.
NG125H circuit breakersC curve BS EN 60947-2: 36kA
Ratings 10 - 125A
97
ApplicationsThis circuit breaker is specially designed for functions requiring a high breakingcapacity (up to 36kA): main incomer in sub-distribution switchboards; outgoer, protection of loads directly supplied by a power switchboard.
Common technical data Rating: 10 - 80A Reference temperature: 40°C Uimp: 8kV Ui: 690V Maximum voltage rating: 500Vac Breaking capacity: as in BS EN 60947-2:Type Voltage Breaking capacity
(Vac) (A)1P 220 - 240 360001P 380 - 415 9000 (1)2, 3, 4P 380 - 415 36000(1) 1 pole breaking capacity in IT isolated neutral systems (double fault).
Isolation with positive break indication 3 position toggle: open-tripped-closed Built-in padlocking facility on 3P and 4P Fault display on front face by: Fault indicator Position of toggle: tripped Test button to check proper operation of the
tripping mechanism Fast closing Electrical durability: 10,000 cycles at In Tropicalisation as in IEC 68.1: treatment 2
(relative humidity: 95% at 55°C)
Weight (g):Type 1P 2P 3P 4P
240 480 720 960
Compatible with loose enclosures, refer to Section 6
Degree of protection: IP20B (IP40D for the partoutside the enclosure)
Connection: ≤ 63A ratings: tunnel terminals for 1.5 - 50mm2
copper cables 80A rating: tunnel terminals for 16 - 70mm2
copper cables Connection of aluminium cables, copper cables
with lug or busbar for 3P and 4P (see connectionaccessories)
Upstream voltage connection on each pole, by6.35mm Fast on lugs, for auxiliary circuit supply
C curve The magnetic trip units operate at 8 In ± 20%
18705
187051870618707187081870918710187111871218713
1.51.51.51.51.51.51.51.51.5
187141871518716187171871818719187201872118722
333333333
Rating 1P Width in 2P Width in 3P Width in 4P Width in(A) 18mm 18mm 18mm 18mm
SP ways SP ways SP ways SP ways101620253240506380
C curve NG125H
4.54.54.54.54.54.54.54.54.5
187321873318734187351873618737187381873918740
666666666
187231872418725187261872718728187291873018731
1 pole devices 2 pole devices 3 pole devices 4 pole devices
1
2
1 3
2 4
1 3 5
2 4 6
1 3 5
2 4 6
7
8
Note: This product is not suitable for use with Isobar 4 connection systems.
NG125 circuit breakersMA curve (magnetic trip)BS EN 60947-2: 50kA
98
ApplicationsThe NG125LMA circuit breakers are designed to protect motor supply circuits(cables and starters) against short circuit current. These devices can be used inconjunction with Telemecanique overload relays to achieve total motor protection.
Common technical data Trip units: 1.4 - 80A Reference temperature: 40°C Uimp: 8kV Ui: 690V Maximum voltage rating: 500Vac Breaking capacity: as in BS EN 60947-2:Type Voltage Breaking capacity
(V) (A)2, 3P 380 - 415 50000
Isolation with positive contact indication 3 position toggle: open-tripped-closed Built-in padlocking facility on 3P Fault display on front face by: Fault indicator Position of toggle: tripped Test button to check proper operation of the
tripping mechanism Fast closing
Electrical durability: 10,000 cycles at In Tropicalisation as in IEC 68.1: treatment 2
(relative humidity: 95% at 55°C) Weight (g):Type 2P 3P
480 720
Compatible with loose enclosures, refer to Section 6
Degree of protection: IP20B (IP40D for the partoutside the enclosure)
Connection: Trip units up to MA63: tunnel terminals for
1.5 - 50mm2 copper cables MA80 trip units: tunnel terminals for 16 - 70mm2
copper cables On 3P, upstream voltage connection on each
pole, by 6.35mm Fast on lugs, for auxiliary circuitsupply
MA curve The magnetic trip units operate at 12 In ± 20%
18868
Rating In Trip unit Magn. Im 2P Width in 3P Width in(A) (A) 18mm 18mm
SP ways SP ways4 MA4 506.3 MA6.3 7510 MA10 12012.5 MA12.5 15016 MA16 19025 MA25 30040 MA40 48063 MA63 75080 MA80 960
MA curve NG125N
188681886918870188711887218873188741887518876
333333333
188791888018881188821888318884188851888618887
4.54.54.54.54.54.54.54.54.5
2 pole devices 3 pole devices
1 3
2 4
1 3 5
2 4 6
Note: This product is not suitable for use with Isobar 4 connection systems.
NG125 VigiSelection
99
Vigi module A class 10 - 63A 80 - 125APole Page Pole Page
Adjustable 300, 500, 1000mA 3P, 4P 111
instantaneous, selective s
300, 500, 1000, 3000mA 3P, 4P 111 3P, 4P 111
instantaneous, selective, delayed
Non adjustable 30mA 2P, 3P, 4P 109 3P, 4P 109
300mA 2P, 3P, 4P 111 4P 111
300mA selective s 2P, 3P, 4P 111
1000mA selective s 2P, 3P, 4P 111
Vigi module AC class 10 - 63APole Page
Non adjustable 30mA 2P, 3P, 4P 108
300mA 2P, 3P, 4P 110
Vigi module si class 80 - 125APole Page
Adjustable 300, 500, 1000, 3000mA 3P, 4P 111
instantaneous, selective, delayed
Non adjustable 30mA 3P, 4P 109
1904918668
NG125 high sensitivity Vigi30mA instantaneous, BS EN 61008AC class
100
ApplicationsCombined with an NG125 MCB, vigi units provide protection against indirect andsupplementary protection against contact with live parts.
Technical data Class AC: Sensitive to sinusoidal AC currents
whether instantaneous or slowly rising fault Class A: Sensitive to DC component sinusoidal
AC or pulsed DC current whether instantaneousor slowly rising fault
Incorporates in a single case: The residual current relay The toroid Connection to the circuit breaker by rigid links
(compact size) insulated by a shield (supplied) (degree of protection IP40D)
Earth fault display on the front face of the Vigimodule by reset handle
Voltage rating: 230 - 415Vac Frequency: 50/60Hz Uimp: 8kV Ui: 690V Protection against nuisance tripping due to
transient overvoltages (lightning, switchgearswitching on the network, etc.)
Tripping by direct mechanical action on the circuitbreaker
Rated current: 63A or 125A with locatingdevice:
63A for < 63A circuit breakers 125A for 80, 100 and 125A circuit breakers Auxiliaries that can be plugged onto Vigi
125A: Remote tripping by MXV shunt trip Remote indication of earth fault trip by SDV
auxiliary switch Weight (g) of Vigi only:Type 2P 3P 4P5 mod. 250 — —9 mod. — 410 45011 mod. — 750 800
Connection: ≤ 63A ratings: tunnel terminals for 1.5 - 50mm2
copper cables 80 - 125A ratings: tunnel terminals for 16 - 70mm2
copper cables Aluminium cables, copper cables with lug (see
connection accessories)
Class AC ~2P Sensitivity I Max. Part No. Width in
(mA) (A) 18mm SPways
30 63 19000 2.5
T1 3
2 4
4P Sensitivity I Max. Part No. Width in(mA) (A) 18mm SP
ways30 63 19004 4.5
3P Sensitivity I Max. Part No. Width in(mA) (A) 18mm SP
ways30 63 19002 4.5
T1 3 5
2 4 6
T1 3 5 7
2 4 6 8
NG125 high sensitivity Vigi30mA instantaneous, BS EN 61008
A class
101
Class A2P I Max. Sensitivity Part No. Width in
(A) (mA) 18mm SPways
63 30 19008 (1) 2.5(1) Voltage rating: 110 - 220Vac.
T1 3
2 4
4P I Max. Sensitivity Part No. Width in(A) (mA) 18mm SP
ways63 30 19015 4.5125 30 19041 5.5
3P I Max. Sensitivity Part No. Width in(A) (mA) 18mm SP
ways63 30 19013 4.5125 30 19039 5.5
T1 3 5
2 4 6
T1 3 5 7
2 4 6 8
Class A si type3P I Max. Sensitivity Part No. Width in
(A) (mA) 18mm SPways
125 30 19100 5.5T
1 3 5
2 4 6
4P I Max. Sensitivity Part No. Width in(A) (mA) 18mm SP
ways125 30 19101 5.5
T1 3 5 6
2 4 6 8
19010
NG125 sensitivity VigiInstantaneous, selective, time delayed (300 - 300mA)BS EN 61008 AC class
102
Specific technical data of the adjustablevigi I∆n sensitivity adjustable by index: 300, 500,
1000, 3000mA Adjustable tripping time: Instantaneous Selective: 60ms Delayed: 150ms Leakage current indication on 3P and 4P 300 -
3000 I/S/D : On the front face by LED Remotely, by 250V - 1A (low level) volt free NO
contact, connected by 2 x 1.5 mm2 plateterminal
Threshold setting by potentiometer from 10 - 50%of I∆n
Disconnection essential for dielectric testing bybuilt-in pushbutton
Auxiliaries plugged onto 125A and 63A Vigi I/S/D Remote tripping by MXV shunt trip Remote indication of earth fault trip by SDV
auxiliary switch Weight (g) of Vigi only:Type 2P 3P 4P5 mod. 250 — —9 mod. — 410 45011 mod. — 750 800
Class AC ~2P I Max. Sensitivity Part No. Width in
(A) (mA) 18mm SPways
63 300 19001 2.5
T1 3
2 4
3P I Max. Sensitivity Part No. Width in(A) (mA) 18mm SP
ways63 300 19003 4.5
T1 3 5
2 4 6
4P I Max. Sensitivity Part No. Width in(A) (mA) 18mm SP
ways63 300 19005 4.5
T1 3 5 7
2 4 6 8
Class AC: Sensitive to sinusoidal AC currentswhether instantaneous or slowly rising fault
Class A: Sensitive to DC component sinusoidalAC or pulsed DC current whether instantaneousor slowly rising fault
Selective s : Provides discrimination with downstream device by introducing an intentional timedelay. Down stream device must beinstantaneous and 1/2 ∆In sensitivity
Si: Provides continuity of supply on circuits withdisturbed supply network i.e. areas with high riskof nuisance tripping
Incorporates in a single case: The residual current relay The toroid Connection to the circuit breaker by rigid links
(compact size) insulated by a shield (supplied) Earth fault display: On the front face of the Vigi by reset handle Protection against nuisance tripping due to
transient overvoltages (lightning, switchgearswitching on the network, etc.)
Rated current: 63 or 125A with locating device: 63A: for 63A circuit breakers 125A: for 80 - 100 - 125A circuit breakers Frequency: 50/60Hz
NG125 medium sensitivity VigiInstantaneous, selective, time delayed (300 - 300mA)
BS EN 61008 A class
103
4P I Max. Sensitivity Part No. Width in(A) (mA) 18mm SP
ways63 300 19016 4.5
300 s 19034 4.51000 s 19035 4.5300 - 3000 I/S/D 19037 5.5300 - 3000 I/S/D 19054 (2) 5.5
125 300 19042 5.5300 - 1000 I/S 19046 5.5300 - 3000 I/S/D 19049 5.5300 - 3000 I/S/D 19056 (2) 5.5
(2) Voltage rating: 440/415Vac, without early warning function.
T1 3 5 7
2 4 6 8
Class A2P I Max. Sensitivity Part No. Width in
(A) (mA) 18mm SPways
63 300 19012 2.5300 19009 (1) 2.5300 s 19030 2.51000 s 19031 2.5
(1) Voltage rating: 110 - 220Vac.
T1 3
2 4
3P I Max. Sensitivity Part No. Width in(A) (mA) 18mm SP
ways63 300 19014 4.5
300 s 19032 4.51000 s 19033 4.5300 - 3000 I/S/D 19036 5.5300 - 3000 I/S/D 19053 (2) 5.5
125 300 - 1000 I/S 19044 5.5300 - 3000 I/S/D 19047 5.5300 - 3000 I/S/D 19055 (2) 5.5
(2) Voltage rating: 440/415Vac, without early warning function.
T1 3 5
2 4 6
4P I Max. Sensitivity Part No. Width in(A) (mA) 18mm SP
ways125 300 - 3000 I/S/R 19107 5.5T
1 3 5 7
2 4 6 8
Class A si type
3P I Max. Sensitivity Part No. Width in(A) (mA) 18mm SP
ways125 300 - 3000 I/S/R 19106 5.5
T1 3 5
2 4 6
19049
NG125 and NG125 VigiElectrical auxiliaries
104
Applications
MX+OF, MXV shunt tripTrips the circuit breaker or Vigi (MXV) when a voltageis applied.
MN, MN undervoltage releaseTrips the circuit breaker when the voltage is disconnected.
Delayed MN s undervoltage releaseProvides delayed tripping of the circuit breaker towhich it is attached.
OF+SD, OF+OF, SDV auxiliary contactsRemotely indicates: The "open" or "closed" position (OF) A fault on the circuit breaker (SD) or Vigi module
(SDV)
Early warning This function is performed by light indication and
fault free contact Built in adjustable Vigi modules, 300 - 3000mA, of
the I/S/R/ type from 230 - 415Vac
Common technical data Complies with standard: BS EN 60947-5-1 (MX + OF, OF + SD, OF + OF
and SDV) BS EN 6094712 (MN, MN s , MX and MXV) Electrical durability: 10,000 cycles (AC 15): Ui: class 2 insulation : 690V Uimp: 8kV Degree of pollution: 3
Technical data for circuit breaker auxiliaries
OF+OF Auxiliary contact changes with main contacts
(ON/OFF)
OF+SD Fault indicating switch changes when main
contacts trip
MX+OF Shunt releases Tripping: on energisation Equipped with a contact allowing self breaking
MN Undervoltage release Tripping and opening of the associated circuit
breaker: if supply voltage drops between 70 and35%
Reclosing: forbidden if supply voltage is notrestored (e.g.: emergency stop by pushbutton)
MN s delayed undervoltage release Allows a 0.25 second time delay on brownout or
voltage drop
Technical data for Vigi module auxiliaries Can be added to: All types of 125A Vigi module 63A 300 - 3000 I/S/D Vigi module SDV Fault indicating switch
MXV Shunt releases Tripping: on energisation Equipped with a contact allowing self breaking Impulse withstand: 6kV High impedance input: use an ACTp if leakage
current is greater than 1mA see page 55
MNx Undervoltage release unaffected by power cuts
Connection: plate terminal for: 1 or 2 flexible or rigid 2.5mm2 cables 2 x 2.5mm2 uninsulated cable ends 2 x 1.5mm2 insulated cable ends 2 x 1.5mm2 fork lugs
NG125 with residual current circuit breaker or device
NG125 and NG125 VigiElectrical auxiliaries
105
Auxiliaries for circuit breakerOF + OF Voltage Part No. Width in
(Vac) 18mm SPways
220 - 240 (6A) 190710.5
Fault indicating switchOF + SD Voltage Part No. Width in
(Vac) 18mm SPways
220 - 240 (6A) 190720.5
OF+OF or OF+SD Voltage Part No. Width in(Vac) 18mm SP
ways240 (6A) 19073 0.5
Shunt tripMX + OF Voltage Part No. Width in
(Vac) (Vdc) 18mm SPways
230 - 415 110 - 130 19064 148 - 130 48 19065 124 24 19066 1
U>
21 22 24
11 12 14
95 98 96
11 12 14
21 22 2495 98 96
11
1412 C2 C1
12 14
19071
19072
19073
19064
NG125 and NG125 VigiElectrical auxiliaries
106
Undervoltage releaseMN Voltage Part No. Width in
(Vac) (Vdc) 18mm SPways
220 - 240 19067 148 19069 1
48 19070 1
Undervoltage release with 0.5s time delayMN s Voltage Part No. Width in
(Vac) 18mm SPways
230 - 240 19068 2
U>
U>
D1 D2
D1 D2
Auxiliary contacts for Vigi moduleSDV Voltage Part No. Width in
(Vac) 18mm SPways
NO 250 (0.1 - 2A) 19058 -NC 250 (0.1 - 2A) 19059 -
Shunt trip for Vigi moduleMXV Voltage Part No. Width in
(Vac) 18mm SPways
110 - 240 19060 -
Note: High impedance output (use an ACTP Cat. No. 15919, if the leakage current of the control device is greater than 1mA).
U>
11 12 13 14
M1 M2
19067
19068
19058
19060
Distribloc125A splitters
107
ApplicationsDistribloc is a fully insulated four pole modular splitters.Connection by screw terminals or spring terminals.
Technical data Rated insulation voltage: 690V Permissible peak current: Ipk = 20kA Complies with the low voltage switchgear
standard: BS EN 60947-7-1 Rated current at 40°C: 125A Installation: Clipped onto a symmetrical rail Fits onto a row next to other modular device:
- 45mm nose- 12 mod. of 9mm
Can be screwed onto a plain or mounting grid
Connection Incomer: Tunnel terminal for 35mm2 flexible or rigid cables Optional factory built link for NG125
(Part No.07054) Outgoer in spring terminals: Minimum cross section: 1mm2
Simplifies rebalancing of phases and extensions Unaffected by temperature variations Spring contact pressure automatically adapted to
conductor cross section A single cable without metal end per spring:
- by flexible cables: 2 x 10mm2 + 3 x 6mm2 +7 x 4 mm2
- by rigid cables: 2 x 16mm2 + 3 x 6mm2 +7 x 4mm2
Outgoer in screw terminals: 1x16mm2 or 25mm2
flexible or rigid cables
DistriblocType Part No. Width in
18mm SPways
Distribloc 125A 07105 6Set of 4 125Aflexible links 07054 -
Distribloc 125
NG125 and NG125 VigiAccessories
108
ApplicationsThe following NG125 accessories can be used to increase flexibility and simplifyinstallation.
Screw shield Prevents contact with device terminal screws Protection against direct contact: IP40D: on the front face IP20B: at connection level Optional sealing terminal shield for circuit breaker
Terminal shield Installation: mounted upstream and downstream
of the circuit breaker/vigi Phase-to-phase insulation voltage Ui = 1000V Protection against direct contact: IP40D Class II in metal or plastic enclosures (up to
440V) Optional sealing terminal shield for residual
current device
Tunnel terminals for copper cables Cable cross section: For 63A ratings:
- flexible cable: 1 - 35mm2
- rigid cable: 1.5 - 50mm2
For 80-100-125A ratings:- flexible cable: 10 - 50mm2
- rigid cable: 16 - 70mm2
Tightening torque and tool type: For ≤ 63A ratings: 3.5Nm with 6.5mm flat
screwdriver or PZ N°. 2 (Pozidrive recessed headscrew)
For 80-100-125A ratings: 6Nm with 4mm Allenwrench (hexagon socket screw)
Degree of protection: IP20B
Extended rotary handle Installation: front 3 & 4 pole devices Utilisation: circuit breaker control from outside
the enclosure Retains isolation/padlocking in the O position (3
padlocks) IP55 3 positions Door interlocking: opening possible in O position
only direct rotary handle
Padlocking accessory Enables padlocking (in l or O position) of 1P
or 2P NG125 circuit breakers: In l position of 3P or 4P NG125 circuit breakers
Note: the 3P/4P NG125 circuit breakers arefactory designed for padlocking in the O position(isolated)
Padlock: Ø 5 - 8mm (not supplied)
Insulated sub-distribution terminal Holes for 3 cables: 16mm2 rigid cables 10mm2 flexible cables
Copper cable sub-distribution terminals Cable cross section for all ratings (circuit
breaker only): Flexible cable: 1 - 10mm2
Rigid cable: 1.5 - 16mm2
With ends: up to 4mm2 inclusive Tightening torque and tool type: 2Nm with
5.5mm flat screwdriver or PZ N°. 1 (Pozidriverecessed head screw)
Phase-to-phase insulation voltage: Ui = 1000V
Matching terminals for 70mm2
aluminium cables Cable cross section for 80,100 and 125A ratings:
25 - 70mm2
Tightening torque and tool type: 6Nm with 4mmAllen wrench (hexagon socket screw)
Screws and nutsfor lug and bar connection Installation: upstream or downstream Connection of 80, 100 and 125A ratings: copper lug:
- flexible cable up to 35mm2
- rigid cable up to 50mm2
Bars: 16x3mm, 15x4mm Lugs with small eyelet hole Tightening torque and tool type: 6Nm with Allen
4mm wrench (M6 screw) Phase-to-phase insulation voltage: Ui = 1000V
Cable lugs Connection of 80, 100 and 125A ratings: Flexible copper cable: 50mm2
Rigid copper cable: 70mm2
Comb busbar Utilisation: for NG125 circuit breaker up to 63A direct supply by circuit breaker terminal (50mm2
max. rigid cable) Tooth shield available for unused teeth Length (dividable): 16 modules of 27mm,
i.e. 48 modules of 9mm 125A max. upstream Insulation voltage: 690V Uimp: 8kV Degree of protection when used with
tooth-shield ends: IPXXB
Rotary handle
NG125 and NG125 VigiAccessories
109
Screw shield for circuit breakerPack of 10 Type Part No.
1P 190842P 190853P 190864P 19087
Terminal shield for circuit breakerPair Type Part No.
1P 190802P 190813P 190824P 19083
Insulated sub-distribution terminalType Part No.Pack of 4 19091
Screws and nuts for lug or bar connectionPart No.
Pack of 4 19093
Cable lugsType Part No.Pack of 4 19094
Matching terminal for aluminium cablePack of 4 19095
Comb busbar for NG125 and C120Type Part No.1P 148112P 148123P 148134P 14814Tooth shield end (set of 20) 14818
Terminal shield for residual current device (Set of)63A Type Part No.
2P 190743P 190753P adjustable 190774P 190764P adjustable 19078
125A 3P 190774P 19078
Rotary handleType Part No.Direct standard 19092Extended standard, black 19088Red handle 19089yellow backgroundNote: Not suitable for 1 & 2 pole devices
Padlocking accessoryType Part No.Pack of 4 19090
19087
19080
19076
19088
19090
19091
19093
19094
14813
P25M motor protection circuit breakerRatings: 0.1 - 25ABS EN 60947-2
110
IcuinkA
5050
Icsin%
100100
IcuinkA
15151515
Icsin%
50504040
IcuinkA
50158866
Icsin%
10010050505050
IcuinkA
50106644
Icsin%
10010075757575
IcuinkA
33333333
Icsin%
7575757575757575
Installation Symmetrical DIN rail
Technical data Phase failure sensitive Temperature compensation: -200C to +400C in
enclosure Current ratings (In): 0.1 - 25A Voltage ratings (Ue): 690Vac Breaking capacity: BS EN 60947-2
Operating cycles: 100,000 AC3 Positive contact indication in accordance with
BS7671 Width: 2.5 SP ways (45mm) Cable capacity: min 2 x 1mm2 rigid,
max. 2 x 6mm2 flexible Approvals: CEBEC, DEMKO, NEMKO,
SEMKO, F1 Accessories: see page 112 Technical data: see page 144
Limiter blockIncreases the breaking capacity to 100kA up to 415V.Individual mounting (upstream) or on the terminalblock part no. 21144 .
Connection: tunnel terminal for flexible cable up to 25mm2
Dimensions: see page 175
Rating Settings Part No.In (A)0.16 0.1 - 0.16 211000.25 0.16 - 0.25 211010.40 0.25 - 0.40 211020.63 0.40 - 0.63 211031.0 0.63 - 1.0 211041.6 1.0 - 1.6 211052.5 1.6 - 2.5 211064.0 2.5 - 4.0 211076.3 4.0 - 6.3 2110810 6.0 - 10 2110914 9.0 - 14 2111018 13 - 18 2111123 17 - 23 2111225 20 - 25 21113
Width in Rating Part18mm (A) No.SP ways2.5 63 21115
Rating(A)0.16to1.62.546.31014182325
230,240 400,415 440 500 690Voltage (V)
self protected
P25M circuit breaker
21115
P25M motor protection circuit breakerAuxiliaries
111
P25M
P25M
Auxiliary combination
O+F/
F+F
F+F/
O+F
O+F/
F+F
MX/
MNSD
Width in 18mm Part No.SP ways0.5 Contact position O+F 211170.5 Contact position F+F 21116
43 31
44
21117 21116
32
43 33
44 34
Width in 18mm Part No.SP ways0.5 Position+alarm
contact F+SD.F 211180.5 Position+alarm
contact O+SD.F 211190.5 Position+alarm
contact F+SD.O 211200.5 Position+alarm
contact O+SD.O 21121
21120 21121
95 53
96 54
95 51
96 52
21118 21119
97 53
98 54
97 51
98 52
Remote indication: Position: O+F contact indicates ON or OFF position of the
P25M F+F contact double contact for ON position Position + alarm indicator: with red flag trip
indicator: F+SD.O - ON position + OFF fault indication O+SD.O - OFF position + OFF fault indication F+SD.F - ON position + ON fault indication O+SD.F - OFF position + ON fault indication
Technical dataVoltage Position (OF) Fault (SD)Ue
Vac (A) (A)24 1.548 6 1130 4.5 0.5240 3.3 0.3415 2.2440 1.5Vdc DC 13 DC 1324 6 148 5 0.360 3 0.15110 1.3220 0.5
Width Voltage Frequency Part No.18mm (V) (Hz)SP waysMX shunt trip release1 220.240 50 21127
380.415 50 21128
Width Voltage Frequency Part No.18mm (V) (Hz)SP waysMN under voltage release1 220.240 50 21129
380.415 50 21130
Remote tripping MX shunt trip release: trips the P25M when
energised MN undervoltage release: trips the P25M when
the voltage supply drops (between 35% and 75%)and prevents reclosing until the supply voltage isrestored
Power consumption of releases:AC DC(VA) (W)
MXPick up 14 10Hold 5 1.6MNHold 3.5 1.1 Connection by terminal clamp
Min.: rigid cables 2 x 1mm2
Max.: flexible cables up to 2 x 2.5mm2
Flexible cable with cable end 2 x 1.5mm2
Connection by terminal clamp:Min.: rigid cables 2 x 1mm2
Max.: flexible cables 2 x 2.5mm2
Flexible cable with cable end 2 x 1.5mm2
21118
21127
P25M motor protection circuit breakerAccessories
112
Part No.Enclosure 21133
Neon indicator light 220 - 240V green 21140red 21142
Neon indicator light 380 - 440V green 21141red 21143
P25M insulated enclosure(Surface mounting). Can incorporate 1 x P25M with 1 xauxiliary contact and 1 x shunt or UVR release withearth and neutral terminals. Degree of protection: IP55 Double insulation Sealable cover Indicator lamp can be installed on the front to
indicate the ON or OFF position 4 knock outs for cable gland Ø 16mm
Dimensions: see page 175
Comb busbars P25M3 Poles 63APower supply for several P25M up to 63A. Comb busbarversions 2 or 4 outlets and the possibility of combiningcomb busbar. Auxiliary contacts can be installedbetween the P25Ms.
Comb busbar Part No.For 2 P25M units 21145For 4 P25M units 21146
Part No.End cover (pack of 5) 21148Terminal block 21144
Part No.Insulated connector 21147
Terminal blockFor supply of busbars with cables up to 25mm2 (canbe installed with limiter block).
Insulated connectorTo supply comb busbars or P25M directly with cablesup to 25mm2.
21133
21146 21145
21144
21147
Connection systems
Isobar 4 MCB pan assemblies 114
Mulitclip busbar and Polybloc 116
Comb busbars 117
Terminals and installation accessories 118 - 119
Section five
113
Isobar 4 MCB pan assembliesPS type single phasePS type three phase
114
Application for PS type single phase and neutral (No neutral switching facility)
All pan assemblies incorporate the unique Isobar MCB way disconnector feature,which offers the user the highest levels of safety through electrical isolation ofunused ways. The SN range of pan assemblies is designed to suit single poleapplications, where switching and protection of the neutral is unnecessary.
Each pan assembly is comprised of a flat steel base incorporating DIN rail,incoming and outgoing busbar assembly with neutral and earth terminal bars. Theycan be easily incorporated into custom built enclosure systems.
MGAN6PS
MGBN8PS
Technical data for PS pan assemblies Standards: BS EN 60439 - 1 and 3 Busbar rating: 125A Operating Voltage: 230/240V also suitable for 110Vac operation Frequency: 50Hz Incomers: As A type distribution boards, see page 00Note: All Merlin Gerin 2 pole RCDs are available for use as incomers to PS pan assemblies. Outgoers: SP C60H MCBs, SP C60H RCBO, C60H MCB & vigi combination
Application for PS pan assemblies (No neutral switching facility)
The PS range of three phase pan assemblies is designed to suit applications whereswitching and protection of the neutral is deemed unnecessary. Each pan assemblyis fully insulated incorporating DIN rail, incoming and outgoing busbar assembly.They can be easily and quickly incorporated into custom built enclosure systems.PS pan assemblies are designed for use with SP and TP C60H MCB, and are alsosuitable for two pole two phase equipment.
Technical data Standards: BS EN 60439 - 1 and 3 Busbar rating: 250A Operating Voltage: 400/415V Frequency: 50Hz Incomers: MGI1253, MGNPB250TB, PS pan assemblies can utilise
Multi 9, 3 or 4 pole devices as incomers - additional shroud must be used - ref. 80011
Outgoers: SP C60H MCB, SP C60H RCBOTP C60H MCBSP C60H MCB and Vigi combinationTP C60H MCB and Vigi combination
SP ways Part No.6 MGAN6PS9 MGAN9PS12 MGAN12PS15 MGAN15PS
TP ways Part No.4 MGBN4PS6 MGBN6PS8 MGBN8PS12 MGBN12PS16 MGBN16PS18 MGBN18PS24 MGBN24PS
115
Isobar 4 MCB pan assembliesType E
ApplicationThis range of pan assemblies is designed for use with Merlin Gerin’s high qualityPrisma range of enclosures or custom built steelwork. Each pan assembly includesall components necessary for final distribution and protection of circuits, i.e. steelfixing plate, DIN rail busbar assembly, incoming connections, neutral and earth barsdistributed neutral busbar for switched neutral applications. The Prisma functionalsystem enables the construction of a full range of distribution equipment productsfrom wall mounted enclosures to IP55 floor mounted switch boards having busbarsystems up to 3200A. Functional system Prisma G, GX for wall mountedenclosures and functional system Prisma P for floor standing enclosures publication ref. MGD 5064
MGBN8E
MGBN8EV
MGI1254
NKIT
Technical data Standards: BS EN 60439 - 1 and 3 Busbar rating: 250A Operating Voltage: 400/415V Frequency: 50Hz Incomers: Switch disconnectors: 3 pole 125A MGI1253N
4 pole 125A MGI1254 Terminal block: 125A MGTB1254
250A MGNPB250TB RCDs: 16261, 23213, 23227 for details see page 74 For MCCBs and switch disconnectors up to 250A use connection kit MSIS95AN Outgoers: 1, 2, 3 or 4P C60H MCBs, C60H RCBO, C60 MCB and Vigi
combinationsNote: All 4 pole RMG RCDs can be used as incomers. Other incoming devicesmay be used by separately mounting them into the Prisma cubicle.To install in prisma G use sp or kit MGBNSPA
TP ways Front cover Part No. Part No.coloured blacksliders sliders
4 - MGBN4E MGBN4EV6 07795P MGBN6E MGBN6EV8 07796P MGBN8E MGBN8EV12 07797P MGBN12E MGBN12EV16 07798P MGBN16E MGBN16EV18 - MGBN18E MGBN18EV24 07799P MGBN24E MGBN24EV
Mulitclip busbar and Polybloc
116
ApplicationA fast , reliable and maintenance free method of connecting outgoing circuits. Each connection is made in a spring front accessed connection rated at 40A.Contact pressure of the spring is automatically adjusted to suit the cross sections ofthe conductor.
Technical details Voltage rating: 440V Current rating: 200A at 40°C Incoming connection: direct by cable lugs,
connectors or flexible bars Outgoing connection: Provides reliable, maintenance free electrical
connecting independent of heat variations Rapid connection and reconnection after
modification Automatic spring connections 12 connection points for each phase and 18/or
neutral Cable capacity 10mm2 max (supplied with 24
connections), 52A max. current rating per connection Fixing: On Multifix rails (fixing brackets included) By screws on all standard supports
Multifix DIN rail (Merlin Gerin patent).Multifix (length 470mm) Rail only, drilled on each end 03004 With two fixed height mounting brackets 03001 With two adjustable height mounting
brackets 03002
PD390661
Polybloc 250AA distribution block patented by Merlin Gerin for ‘wire to wire’ connections, it consists of:
Short circuit withstand currentThis table indicates the short circuit withstand current (in kA rms) for variouscombinations of upstream and downstream devices on a 380/415V installation.
PD390549
Type Part No.2P Phase and Neutral 040123P 040134P 3 Phase and Neutral 04014
Symmetrical DIN rail L = 2000 Part No. th = 2.3; h = 15 06603
Asymetrical rail L = 2000 Part No. th = 1.5; h = 15 06602
Part No.Polybloc 3P 04033Polybloc 4P 04034
Outgoing 6 x 10mm2 and 3 x 16mm2 cables per phase
Downstream device Short circuit withstand current (in kA rms), depending on upstream device
--
(1)
N2525(1)
H3625(1)
N2525(1)
H3040(1)
L3040(1)
N25-
(1)
H30-
(1)
L30-
(1)
N25-
(1)
H30-
(1)
L30-
(1)
C120 NS100NG125 NS160 NS250
C60H (10kA)C120 (15kA)Other devices
(1) Check that the peak short circuit current, limited by the downstream device, is lower than 12kA. Check that the thermal stress delivered by the downstreamdevice does not exceed the permissible thermal stress of the 6mm cable (4.76 x 105 A2s).
Comb busbars, connectors and assembled terminals
117
Application for Comb busbar C60HWhen fed by a single cable per phase the busbar is rated 100A at 40°C. If two connections (i.e. two cables) are used per phase the rating is increased to120A. Short circuit rating compatible with the breaking capacity of the MCBs fitted. Short time ratings: 10kA for 30ms, 1800A for 1 second. Suitable for use with allMerlin Gerin MCBs with 18mm width poles (C60HB/HC/HD).
Technical dataRated operational voltage 500V. Complies with BS EN 60439-1 Fully insulated for protection against direct
contact Supplied with insulated end covers Main connection: 16mm2 direct 25mm2 via
connectors part no. 14885
Type suitable for C60H and STI Part No.1P 1 row of 12 - 1P MCBs (12) 14881
1 row of 54 - 1P MCBs (54) 148012 row of 24 - 1P MCBs (24) 14891
2P 1 row of 6 - 2P MCBs (6) 148821 row of 27 - 2P MCBs (27) 148022 row of 12 - 2P MCBs (24) 14892
3P 1 row of 4 - 3P MCBs (4) 148831 row of 18 - 3P MCBs (18) 148032 row of 8 - 3P MCBs (16) 14893
4P 1 row of 3 - 4P MCBs (3) 148841 row of 13 - 4P MCBs (13) 148042 row of 6 - 4P MCBs (12) 14894
Cable connectors - pack of 4 14885
Type suitable for DPN Part No.1P+N 1 row of 13 MCBs 14880
2 row of 12 - 24 MCBs 14890
Type suitable for C120 NG125 Part No.1P 16 MCBs 148112P 8 MCBs 148123P 5 MCBs 148134P 4 MCBs 14814Set of 20 boots for unused teeth 14818
Accessories Part No.Set of 40 ends caps
for 1P and 2P combs 14886for 3P and 4P combs 14887
Set of 40 boots for unused teeth 14888
14881
Stepped terminals 125/140A (40°C)Installation
Clipping on to Multifix or symmetrical rails Screwing on to plain or slotted plates, Multifix rails
or asymmetrical rails
13514
07105
Distribloc 125 and 160A4 pole distribution block comprising: A fully insulated, one piece distribution system
complying with IPXXB (protection against direct contact)
A modular cover designed for a 45mm panel slotfor integration in a row of DIN rail mounted modular products
Technical data Ui = 690V, Icw = 4.5kA/1s to IEC947-7-1 Peak withstand current: Ipk = 20kA to IEC439-1 Rated impulse withstand voltage: Uimp = 8kV
Terminals with holes 125AIsc (kA rms)415V Part No.
4 x 10 holes 3.5kA/1s 13512(5 x 10 mm2) + (4 x 16 mm2) + (1 x 35 mm2)4 x 17holes 3.5kA/1s 13514(8 x 10 mm2) +(8 x 16 mm2) + (1 x 35 mm2)Terminals with clamps 10kA/1s 14949140A 4 x 12 holes (12 clamps 6 mm2)
Type Part No.Distribloc 125 07105Distribloc 160 0710635mm2 x 210 07054 4 flexible connections
Cable capacityDistribloc 125 Incoming 6 - 35mm2 flexible
or 10 - 35mm2
rigid cablesDistribloc 160 Incoming Flexible cable
links fitted to device
Distribloc 125 & 160 Outgoing Per pole:2 x 10mm2
3 x 6mm2
7 x 4mm2
1 x 25mm2
(16mm2 multicore)
Terminals and installation accessories
118
Technical data Current rating: 80A
Terminal blocksFor fixing to symmetrical DIN rails. 1P and 2P blockscan be fitted together to form 3P and 4P blocks.
Connection strips 80 - 125A (40°C)Cross section for stranded cables.Each strip has one M4 threaded hole for screwattachment to any support.
Terminal block supportsTerminal block support made of self extinguishinginsulating material: 960°C/5s. Beige in colour.
Type Part No.1P (2 x 25mm2 + 4 x 16mm2) 149361P (2 x 35mm2 + 4 x 25mm2) 149382P (2 x 25mm2 + 4 x 16mm2) 149372P (2 x 35mm2 + 4 x 25mm2) 14939
80A connection strip Part No.4 holes 14962(2 x 10mm2 + 2 x 16mm2)length 32mm6 holes 14963(3 x 10mm2 + 2 x 16mm2 + 1 x 35mm2 )length 50mm10 holes 14964(5 x 10mm2 + 4 x 16mm2 + 1 x 35mm2 )length 74mm
125A connection strip14 holes 14965(7 x 10mm2 + 6 x 16 mm2 + 1 x 35mm2)length 98mm
Cross section for stranded cables Part No.80A terminal block4 holes 14975(2 x 10mm2 + 2 x 16mm2)length 68mm6 holes 14976 (3 x 10mm2 + 2 x 16mm2 + 1 x 35mm2)length 68mm10 holes 14977 (5 x 10mm2 + 4 x 16mm2 + 1 x 35mm2)length 115mm
125A terminal block14 holes 14979(7 x 10mm2 + 6 x 16mm2 + 1 x 35 mm2)length 115mm
Each support can be individually identified using clip-on markers (optional): Blue for neutral Yellow/green for earthFixing: Clipped on to: 12 x 2 flat bar Multifix or symmetrical rail Screwed on to any support (plain or slotted plate)
using 2 ears
Terminal blocks
Connection strips
Terminal block supports
Type Part No.For panel mounting1 x 20 holes, length 183mm(19 x 162+ 1 x 1202) 992171 x 25 holes, length 222mm(24 x 162+ 1 x 1202) 992191 x 38 holes, length 332mm(37 x 162 + 1 x 1202) 992211 x 49 holes, length 419mm(48 x 162 + 1 x 1202) 992231 x 73 holes, length 624mm(72 x 16+1 x 1202 ) 99225
Type Part No.2 x 50 identification card 14989(50 blue mark, 50 yellow/green mark) Flat bar 12 x 2 07046
Identification cardThe markers can be used to identify terminal blocks:neutral or earth.
Terminal bar for earth/neutral connections For panel mounting Including support Current rating 200A
14989
Terminal bars
Terminals and installation accessories
119
End stop For symmetrical/asymmetrical DIN rail.
14915
Type Part No.End stop (pack of 10) 14915
Universal terminal support This unit can be installed on: Symmetrical DIN rail Slotted mounting plate Asymmetrical DIN raiI width: 3 modules of 9mm
Type Part No.Universal terminal support 6619(pack of 5)
06619
Flush mounting clampAllows the installation of all DlN standard devices onan enclosure door. The depth is adjustable by turning the bracket round.DIN rail not included.
Type Part No.Flush mounting clamp (pack of 4) 20267
20267
Transparent hinged weatherproof coversfor enclosure doors - IP55Allows the installation of DlN standard devices up to 10SP ways (twenty 9mm modules) on an enclosure door. Degree of protection IP55. External dimensions (mm):
w 235 x h 126 x d 33 Dimensions of the hole on the door (mm):
w 186 x h 96Supplied with a blanking plate (to cover up to ten 9mmmodules) and fixing and drilling template.
Type Part No.Transparent hinged cover (10 x 18mm ways) 14210DIN rail support 14211(and fixing)Transparent hinged cover (4 x 18mm ways) 99246ATransparent hinged cover complete with DIN support bracket (4 x 18mm ways) 99246B
99246B
Card strip holderSelf adhesive plastic holder for card label strip. 430mm/479mm modules wide, 20mm high. Suppliedwith card strip and transparent cover strip.
Type Part No.Card strip holder 07360Pack of 10 holders and 10 card strips
07360
EnclosuresFeatures and benefits
120
Merlin Gerin’s range of enclosures has been designed tocater for a wide range of applications, suitable for themounting of DIN rail components such as timers, relays,contactors, MCBs etc.
Whether the enclosure is for indoors or outdoors use, in a clean or dirty
environment, in metal or insulated material, with a plain or transparent door, Merlin
Gerin has an enclosure to suit.
Page 132 - 133 features a quick selection table, designed to guide you through theproduct range to select the most suitable enclosure.
Tamperproof facility via a lockable option (where applicable)
Transparent door option (where applicable) enables quickidentification of status and settings, useful for MCBs andtimers etc
High levelsof safety
Ingress protection ratings available from IP30 through toIP66
Insulated or metal enclosures suitable for the mounting ofDIN rail devices, ranging from 2 up to 240 SP ways
Enclosures supplied complete with accessories (seerelevant product information for further details)
Performanceand quality
Design flexibility of modular or custom chassis enablesthe user to tailor internal fittings to the application
Aesthetically pleasing
Productinnovation
Enclosures
Mini Opale IP30 124
G9 IP30 124
A-series IP30 124
B-series IP31 125
Pragma C IP40 126
Pragma metal IP41 127
UT weatherproof IP54 128
Prisma GK IP55 129
Pragma C weatherproof IP55 130
Kaedra weatherproof IP65 131
UP weatherproof IP66 132
Section six
121
EnclosuresSelection guide
122
Mini OpaleIP30
Insulated Page 2 3 4 5 6 8 11 12 14
124
Pragma CIP40
126
WeatherproofPragma CIP55
130
Weatherproof KaedraIP65
131
Weatherproof UP (GRP)IP66
132
G9IP30
Metal Page
124
A-Series enclosureIP30
124
B-Series enclosureIP31
125
PragmaIP30/41
127
Weatherproof UTIP54
128
Prisma GKIP55
129
Step 1: Select the number of SP ways required Step 2: Select either insulated or metal,
2 3 4 5 6 8 11 12 14
1Row
1Row
1Row
1Row
1Row
1Row
1Row
1Row
1Row
1Row
1Row
1Row
1Row
1Row
1Row
1Row
1Row
Enclosure capacity in 18mm SP ways
Enclosure capacity in 18mm SP ways
123
EnclosuresSelection guide
17 24 28 34 36 48 51 68 72 85 88 96 112 120 144 240
Step 3: Select IP rating required, Step 4: Refer to the product page for more details.
17 24 28 34 36 48 51 68 72 85 88 96 112 120 144 240
2Rows
3Rows
4Rows
1Row
2Row
2Row
3Row
4Row
5Row
1Row
2Row
2Row
3Row
4Row
4Row
4Row
6Row
5Row
6Row
3Row
2Row
3Row
4Row
5Row
6Row
2Rows
2 Rows3
Rows4
Rows4
Rows6
Rows
3Rows
4Rows
EnclosuresIP30
124
Mini Opale enclosures (IP30) Mini Opale enclosures are all insulated and made of an impact resistant materialwhich is self extinguishing to 6500C.Degree of protection: IP30
They consist of: An insulated back plate incorporating a DlN rail A cover clipped to the back plate Two 4 hole terminal bars built in, 13396 and 13398
only. (1 X 16mm2 + 3 X 10mm2)
Installation Wall mounting, 2 or 4 screws supplied. Dimensions: see page 189
SP Size (mm) Part No.18mm H - W - Dways2 130 x 44 x 57 133924 130 x 80 x 57 133946 160 x 119 x 65 133968 160 x 155 x 65 13398
Suitable for most DlN standard devices
G9 enclosures (IP30)These enclosures are made from pressed sheet steel, epoxy powder coated. Colour: moonstone beige.Degree of protection: IP30.
They consist of: A back plate with DlN raiI A cover, screwed to the back plate, having 25mm
knockouts top and bottom
Installation Wall mounting Dimensions: see page 189
SP Size (mm) Part No.18mm H - W - Dways3 200 x 101 x 63 995604 250 x 122.5 x 63 145995 250 x 122.5 x 63 14603
Suitable for most DlN standard devices
A-series enclosures (IP30)These enclosures are made from folded steel sheet, epoxy powder coated. Colour: RAL 9001.Degree of protection: IP30.
SP No. of Size (mm) Part No.18mm holes H - W - Dways8 9 264 x 260 x 127 MGN16DE11 12 264 x 315 x 127 MGN22DE14 18 264 x 370 x 127 MGN28DE17 24 264 x 450 x 127 MGN34DE28 36 494 x 370 x 127 MGN56DE*
Suitable for most DlN standard devices* Two tier
AccessoriesKey lock MGBL
They consist of: An enclosure having a back plate with DlN rail
25mm knockouts in top, bottom, sides and rear of enclosure built-in earth terminal bar:
A cover having a drop down door with plastic latch.To lock enclosure use easily fitted key lock MGBL
Installation Wall mounting Dimensions: see page 164
13396
MGN16DE
EnclosuresB-series IP31
125
ApplicationThese enclosures are designed to accommodate DIN rail mounted products, primarily for control and metering. They may be mounted individually or attached tothe side of an MGB board of equivalent height using the side joining kit MGBNSJK.For mounting above and below a standard B board use ref MGBNTJKN.
Specification Ingress protection: IP31 to BS EN 60529 Earth bar capacity: 25mm2
Surface mounting Colour: RAL 9001 epoxy powder coated
Supplied with DIN rail, door and slotted front coverPart No. Capacity No. of Dimensions in mm
in 18mm rows Height Width DepthSP ways
MGBN4SXS 34 2 484 470 158MGBN8SXS 34 2 538 470 158MGBN12SXS 51 3 700 470 158MGBN16SXS 68 4 808 470 158MGBN24SXS 85 5 970 470 158
Supplied with DIN rail, door and plain front coverPart No. Capacity No. of Dimensions in mm
in 18mm rows Height Width DepthSP ways
MGBN4SXP 34 2 484 470 158MGBN8SXP 34 2 538 470 158MGBN12SXP 51 3 700 470 158MGBN16SXP 68 4 808 470 158MGBN24SXP 85 5 970 470 158Suitable for most DIN standard devices
Installation Wall mounting Dimensions: see page 169
MGBN8SXP
MGBN8SXS
MGBN8SXP
EnclosuresPragma C IP40
126
ApplicationThese enclosures are designed to accommodate DIN rail mounted products,primarily for control and metering. Colour: ivory (RAL9001)
Supplied with plain doorPart No. Capacity No. of Dimensions in mm
in 18mm rows Height Width DepthSP ways
10901 12 1 250 275 11510902 24 2 375 275 11510903 36 3 500 275 11510904 48 4 752 275 115
Supplied with transparent doorPart No. Capacity No. of Dimensions in mm
in 18mm rows Height Width DepthSP ways
10911 12 1 250 275 11510912 24 2 375 275 11510913 36 3 500 275 11510914 48 4 752 275 115Suitable for most DIN standard devices
Additional accessoriesDescription Part No.80A terminal block, 4 holes 1357580A terminal block, 8 holes 1357680A terminal block, 16 holes 1357780A terminal block, 22 holes 1357880A terminal block, 32 holes 13579
IP2X protective cover terminal block, green-yellow, 4 & 8 hole 13582IP2X protective cover terminal block, green-yellow, 16, 22 & 32 hole 13583IP2X protective cover terminal block, red, 4 & 8 hole 13584IP2X protective cover terminal block, red, 16, 22 & 32 hole 13585IP2X protective cover terminal block, blue, 4 & 8 hole 13586IP2X protective cover terminal block, blue, 16, 22 & 32 hole 13587
Angled terminal block support 13600Key lock 13665Set of 4 wall mounting hooks 14181
Installation Wall mounting Dimensions: for more detailed dimensions, see page 191
Available with either a plain or transparent door, theseenclosures are supplied complete with the following:
2 angled terminal block supports 1 earth terminal block without cover: 12 way enclosure supplied with 16 hole terminal
bar (8 x 10mm2 + 8 x 16mm2) 24 and 36 way enclosure supplied with 22 hole
terminal bar (11 x 10mm2 + 11 x 16mm2) 48 way enclosure supplied with 32 hole terminal
bar (16 x 10mm2 + 16 x 16mm2) 1 neutral terminal block with blue cover: 12 way enclosure supplied with 16 hole terminal
bar (8 x 10mm2 + 8 x 16mm2) 24 and 36 way enclosure supplied with 22 hole
terminal bar (11 x 10mm2 + 11 x 16mm2) 48 way enclosure supplied with 32 hole terminal
bar (16 x 10mm2 + 16 x 16mm2) Identification labels and pictograms 5 module dividable blanking plates: 12 way enclosure supplied with 1 24 way enclosure supplied with 2 36 and 48 way enclosure supplied with 3
10901
10912
10903
10914
EnclosuresPragma metal IP41
127
A back plate which supports a removable DlN railchassis which is also insulated from the backplate
Removable top and bottom insulated gland plates(metal plates are an option)
Metal side panels which are insulated from theback plate
Insulated front plates, one for each row of DlN rail Earth and neutral terminal bars, each 30 holes Way label for each row, with blanking plates
(8 poles for 1, 2, 3 rows - 16 poles for 4, 5, 6rows)
Optional plain door or glazed door which may behinged left or right
EnclosureNo. of Capacity Part No. Part No. doorrows in 18mm enclosure plain glazed
SP ways1 24 13811 13841 138512 48 13812 13842 138523 72 13813 13843 138534 96 13814 13844 138545 120 13815 13845 138556 144 13816 13846 13856Suitable for most DlN standard devices
ApplicationThese enclosures are manufactured from sheet metal 8/10 epoxy/polyester powder coated. They are supplied complete with DIN mounting rails and insulatedfront plates. Degree of protection is IP30 with front plates, IP41 with overall door. They consist of:
Dimensions All Pragma enclosures are 550mm wide,
depth 170mm, with front plates 182mm withoverall door
Height mm1 row 3002 row 4503 row 6004 row 7505 row 9006 row 1050
Installation Wall mounted with internal fixing and location
brackets
Compact NS/Interpact incomers Purpose designed mounting plates and front
plates to accept Compact NS or Interpact up to160A
Each Interpact front plate occupies the space of 2MCB front plates
Each Compact NS occupies the space of 1 MCBfront plate
Terminals A range of terminals and connections to ease
installation
Accessories A range of accessories to extend the applications
for Pragma enclosures
Description Part No.Interpact IN125T - IN160Tmounting plate and front plate 13861Compact NS / VIGI NS 100 / 160 mounting plate and front plate 13863160A connection blocks (fits onto incoming units) 13875Earth/neutral terminal blocks (2 x 30 hole)* 13876Connections to install POLYBLOC on incoming unit 13866Plain front plate (1 row) 13871Slotted mounting plate (H 150mm) 13864Blanking plate 24 pole 13430Label strip 24 pole 13879Door lock key No. 405 13877Touch up paint RAL 9001 13880Pack of blanking strip 5 pole 13429Metal gland plate PRGPM* 13876 complete with insulated holders, insulated cover eachbar has 1 x 35mm, 15 x 16mm, 14 x 10mm holes.
13811 + 13841
EnclosuresUT weatherproof IP54
128
EnclosuresEnclosure size (mm) UT range
Internal fittingsMounting plates
Height Width Depth Plain Perforated
3004005006007008001000
250300400400500600800
150200200200200250250
04583045840458504586045870458804590
09231092340923809239092400924409248
09211092140921809219092200922409228
2 x 123 x 163 x 164 x 224 x 286 x 36
025240252502526025270252802530
092630926409264092650926609268
092510925209253092540925509257
Withplaindoor
4 Multifixrails
Verticaluprights
Rows of18mmSP ways
Chassiscomplete
Custom chassis Modular chassis
Accessories
Set of wall fixing lugs (external) 04629
Handle with barrel + 2 keys 405 05196
Earth connection 6mm2 for door 07081
RAL7032 aerosol paint spray 02499
Blanking plate for Multi 9 front plate 13730
Set of 4 - M8 x 50 spacers for
custom chassis and mounting plates 05224
Set of 4 - M6 x 12 screws and
nuts to fix DIN rails in custom chassis 09917
20 cage nuts for M4 05114
perforated mounting plate M5 05115
M6 05116
Dimensions: see page 192
UT weatherproof enclosures: All welded construction, manufactured from 1.2mm sheetsteel, epoxy/polyester powder coated
Colour: RAL 7032 grey Degree of protection: IP54 to IEC 529. Wall fixing
by internal or external fixings. The door is removable and is sealed using a mouldedpolyurethane gasket. A bottom gland plate is fitted,fully gasketed and removable from the outside
ApplicationThere are 4 - M8 x 20 bolts at the back of the enclosure to fix mounting plates orchassis. Both plain and perforated mounting plates are available. Custom chassisallow rapid fixing of symmetrical DIN rail mounted devices. It comprises of 2 verticalrails fitted to the back of the enclosure, the DIN rails are fitted at the required positions.Modular chassis (common to the UT and UP enclosures) comprise a supportingstructure, symmetrical DIN rails with adjustable depth, plastic front plates with built inidentification.Weatherproof enclosure
EnclosuresPrisma GK IP55
129
ApplicationHeavy Duty enclosure suitable for use in harsh environments. Ideal for use inIndustrial & Commercial buildings these enclosures offer the following: Functionality (ease & simplicity of product selection) Sealed from the effects of water and dust to IP55 Extendible (enclosures can be joined or extended by the use of joining kits) Robust (high resistance to impacts & mechanical damage)
These enclosures are wall mountable, up to 23x50mm Prisma modules, or floorstanding for 27 and 33x50mm Prisma modules using a plinth. They are availablewith either a plain or transparent door and can be used to house devices up to630A with standard connections.
Colour: RAL 9001. For other colours consult Merlin Gerin. Degree of protection: IP55
Part No’s.Enclosure Plain door Transparent door
Enclosure (7 mod.), H450 x W600 05502 05532 05542Enclosure (11 mod.), H650 x W600 05503 05533 05543Enclosure (15 mod.), H850 x W600 05504 05534 05544Enclosure (19 mod.), H1050 x W600 05505 05535 05545Enclosure (23 mod.), H1250 x W600 05506 05536 05546Enclosure (27 mod.), H1450 x W600 05507 05537 05547Enclosure (33 mod.), H1750 x W600 05508 05538 05548
Description Part No.Canopy for W600 - for extra protection against water or objects falling vertically 05557Prisma GK handle - spare handle with barrel lock and two keys 05580For further information and a comprehensive list of the full GK range see the Prisma G Catalogue. For information on joining/extending enclosures consult us.
Ordering guide
Select the number of device mounting rails (Multifix rails) required for mounting Multi 9 devices: (24 x 18mm SP ways)
Rail Front Plate (with cutouts)
1 row occupies 4 vertical modules (200mm). 07501 07814
Select the number of Mulifix rails required for mounting terminal blocks:
Rail Front Plate1 row occupies 3 vertical modules (150mm). 07502 07813
Add the number of vertical modules required for the installed equipment using theabove guidelines and subtract this number from the number of modules provided inthe selected enclosure. This will give you the plain front plate requirements for theunused modules in the enclosure. Use the following table to order plain front plates:for B type pan assemblies see page xx
Plain Flat Front PlateHeight Mods. Part No.50mm 1 7801100mm 2 7802150mm 3 7803200mm 4 7804250mm 5 7805300mm 6 7806
Example Modules3 x 7501 Rows for Multi 9 devices, 72 x 18mm SP Ways 123 x 7814 3 Front Plates with cut outs for Multi 9 devices2 x 7502 2 Rows for Terminal Blocks 62 x 7803 2 Front Plates
05505 Basic Enclosure (19 mod.), H1050 x W600 1905535 Plain door for 19 mod enclosureTotal space remaining within the enclosure 1
Therefore the Filler Plates required would be:1 x 7801 1 x 1 mod (50mm) Plain Front Plate
05503 + 05543
Dimensions: see page 193
EnclosuresPragma C weatherproof IP55
130
ApplicationThese enclosures are designed to accommodate DINrail mounted products, primarily for control and metering.
Suitable for use in harsh environments they can beused indoors or outdoors. Colour: light grey (RAL 7035)
Supplied with transparent doorPart No. Capacity No. of Dimensions in mm
in 18mm rows Height Width DepthSP ways
10941 12 1 279 285 127.510942 24 2 404 285 127.510943 36 3 529 285 127.510944 48 4 654 285 127.5Suitable for most DIN standard devices
Additional accessoriesDescription Part No.80A terminal block, 4 holes 1357580A terminal block, 8 holes 1357680A terminal block, 16 holes 1357780A terminal block, 22 holes 1357880A terminal block, 32 holes 13579
IP2X protective cover terminal block, green-yellow, 4 & 8 hole 13582IP2X protective cover terminal block, green-yellow, 16, 22 & 32 hole 13583IP2X protective cover terminal block, red, 4 & 8 hole 13584IP2X protective cover terminal block, red, 16, 22 & 32 hole 13585IP2X protective cover terminal block, blue, 4 & 8 hole 13586IP2X protective cover terminal block, blue, 16, 22 & 32 hole 13587
Angled terminal block support 13600Key lock IP55 Pragma C 13625Set of 4 wall mounting hooks 14181
Installation Wall mounting Dimensions: for more detailed dimensions, see page 194
These enclosures are supplied complete with the following:
2 angled terminal block supports 1 earth terminal block without cover: 12 way enclosure supplied with 16 hole terminal
bar (8 x 10mm2 + 8 x 16mm2) 24 and 36 way enclosure supplied with 22 hole
terminal bar (11 x 10mm2 + 11 x 16mm2) 48 way enclosure supplied with 32 hole terminal
bar (16 x 10mm2 + 16 x 16mm2) 1 neutral terminal block with blue cover: 12 way enclosure supplied with 16 hole terminal
bar (8 x 10mm2 + 8 x 16mm2) 24 and 36 way enclosure supplied with 22 hole
terminal bar (11 x 10mm2 + 11 x 16mm2) 48 way enclosure supplied with 32 hole terminal
bar (16 x 10mm2 + 16 x 16mm2) Identification labels and pictograms 5 module dividable blanking plates: 12 way enclosure supplied with 1 24 way enclosure supplied with 2 36 and 48 way enclosure supplied with 3
10941
EnclosuresKaedra weatherproof enclosure IP65
131
Supplied with transparent doorPart No. Capacity No. of Dimensions in mm
in 18mm rows Height Width DepthSP ways
13441 4 1 200 123 11213442 6 1 200 159 11213443 8 1 200 195 11213444 12 1 200 267 112Suitable for most DIN standard devices
Additional accessoriesDescription Part No.80A terminal block, 4 holes 1357580A terminal block, 8 holes 1357680A terminal block, 16 holes 1357780A terminal block 22 holes 13578
Angled terminal block supports 4 way enclosure 13361Angled terminal block supports 6 way enclosure 13362Angled terminal block supports 8 way enclosure 13363Angled terminal block supports 12 way enclosure 13364
IP2X terminal cover green 4 hole 135818 hole 1358216/32 hole 13583
IP2X terminal cover blue 4 hole 135898 hole 1358616/32 hole 13587
Lock 13948Sealing kit 13947Bag of membrane glands (cable support sleeves) various sizes 14190
Installation Wall mounting Dimensions: for more detailed dimensions, see page 190
These enclosures are supplied complete with the following:
1 built in dividable blanking plate 1 marker strip 4 sealing plugs for wall mounting screws (essential
for class 2) 1 angled terminal block support to simplify cable
insertion and improve accessibility on clamping 1 terminal block fitted with a guide to simplify
cable introduction in the tunnels: 13441 - 13443, two terminals of 4 holes 13444 two terminals of 8 holes
ApplicationKaedra enclosures are manufactured using an insulating, self extinguishingmaterial. Suitable for commercial, industrial and domestic applications, forinstallation indoors and outdoors in harsh environments, ie marinas. Degree of protection: IP65 Colour: light grey (RAL 7035)
13441
EnclosuresPoylester UP weatherproof IP66
132
ApplicationWeatherproof, maintenance free enclosures manufactured from high impact glassreinforced polyester material self extinguishing to 9800C and having excellent resistance to corrosion. Degree of protection IP66 to IEC 529. Wall mounting, door hinged left or right with internal wall fixings supplied as standard.
There are 4 - M8 x 20 bolts at the back of the enclosure to fix mounting plates orchassis, both plain and perforated mounting plates are available. Custom chassisallow rapid fixing of symmetrical DIN rail mounted devices. It comprises of 2 verticalrails fitted to the back of the enclosure. The DIN rails are fitted at the required positions. Modular chassis (common to the UT enclosures) comprise a supportingstructure, symmetrical DIN rails with adjustable depth, plastic front plates with built inidentification and a 12 x 2 flat bar with earthing terminal block.
EnclosuresEnclosure size (mm) UP range
Internal fittingsMounting plates
Height Width Depth Variabledepthsliders
Plain Perforated
4305306507508501055
330430440540640850
200200250300300350
025040250520506025070250802510
025140251502516025170251802520
025540255402556025570255702560
092340223809239092400924409248
092140921809219092200922409228
2 x 123 x 163 x 164 x 224 x 286 x 40
025240252502526025270252802530
092630926409264092650926609268
092510925209253092540925509257
Withplaindoor
Withglazeddoor
4 Multifixrails
Verticaluprights
Rows of18mmmodules
Chassiscomplete
Custom chassis Modular chassis
Accessories Part No.
Set of wall fixing lugs (external) 02521
Handle with barrel + 2 keys 405
not for 02510 and 02520 09955
Blanking plate for multi 9 front plate 13730
Set of 4 - M8 x 50 spacers for
custom chassis and mounting plates 05224
Set 8 - M6 x 12 screws and nuts to
fix DIN rails in custom chassis 09917
20 cage nuts for perforated
mounting plate M4 05114
M5 05115
M6 05116
Weatherproof enclosure
Technical data Section seven
Breaking capacities 134
Tripping characteristics 135
Temperature derating 136
Grouping factors 135 - 136
MCB on lighting loads 137
MCB auxiliaries 138 - 139
DC operation 140
400Hz operation 141
Motor starters 142
Transformer inrush 143
P25M motor protection 144
Types of RCD 145
Degrees of protection 146
Surge arrester selection 147 - 149
Contactor rating 150 - 151
Impulse relay selection 153
MIN and PRE timings 154
Movement detector 155 - 156
Presence detector 157 - 158
Multimeter connection 159
Current transformer selection 161
133
Miniature circuit breakersBreaking capacitiesTripping characteristics
134
BS EN 60898 I EC947-2Type In min. In max. Type In min. In max. Typical applicationsB 3 5 U 5.5 8.8 Moderately inductive, e.g. commercial and general industrialC 5 10 C 5 10 Highly inductive, e.g. heavy industrialD 10 14 D 10 14 More highly inductive, e.g transformers, motors and certain
lighting systems
Note: BS EN 60898 calibration temperature 30°CBS EN 60947-2 calibration temperature 40°C
Note: For UL/CSA approved MCBs consult us.Maximum operating voltage 440V + 10%
Miniature circuit breaker BS EN 60898** BS EN 60947-2*(magnetic trip setting) Breaking capacity (A) Breaking capacity (A)
1 P 2,3,4P 1 P 2,3,4P 2,3,4P 2,3,4PType Ratings (A) Page 240V 415V 220V/240V 220V/240V 380V/415V 440VC60HB MCB 1A - 63A 12/13 10,000 10,000 15,000 30,000 15,000 10,000(type B: 3 - 5In)C60HC MCB 1A - 63A 12/13 10,000 10,000 15,000 30,000 15,000 10,000(type C: 5 - 10InC60HD MCB 1A - 63A 12/13 10,000 10,000 15,000 30,000 15,000 10,000(type D: 10 - 14In)C120 HB MCB 10A - 125A 17 15,000 15,000 15,000 30,000 15,000 10,000C120 HC MCB 10A - 125A 18 15,000 15,000 15,000 30,000 15,000 10,000C120 HD MCB 10A - 125A 19 15,000 15,000 15,000 30,000 15,000 10,000NG125 N 10A - 125A 35 - - 25,000 50,000 25,000 20,000NG125 H 10A - 80A 38 - - 36,000 70,000 36,000 30,000
* Breaking capacities quoted are Icu. Ics = 50% of Icu.** Breaking capacities quoted are Icn. Ics = 75% of Icn.
Magnetic tripping characteristics (50/60Hz)
Miniature circuit breakersTemperature derating/grouping factors
135
Temperature derating of MCBs Miniature circuit beakers listed in the service current tables may be used at temperatures ranging from -30˚C -60˚C. The tables show the maximum current to be employed as a function of certain ambient temperatures.Figures in bold type are the nominal current ratings at the calibration temperature.
Derating of MCBs grouped in enclosed installations.When a number of circuit breakers or combined RCD/MCBs that operate simultaneously are mounted side byside in a small enclosure, the temperature rise inside the enclosure may cause a reduction in the service current.The reduction can be calculated by multiplying the maximum service current by a 'grouping factor'.
0.8
C60H B and C curvesTemperature °C
Rat. (A) 20 25 30 35 40 45 50 55 601 1.05 1.02 1.00 0.98 0.95 0.93 0.90 0.88 0.852 2.08 2.04 2.00 1.96 1.92 1.88 1.84 1.80 1.744 4.24 4.12 4.00 3.88 8.76 3.64 3.52 5.40 5.306 6.24 6.12 6.00 5.88 5.76 5.64 5.52 5.40 5.3010 10.6 10.3 10.0 9.70 9.30 9.00 8.60 8.20 7.8016 16.8 16.5 16.0 15.5 15.2 14.7 14.2 13.8 13.320 21.0 20.6 20.0 19.4 19.0 18.4 17.8 17.4 16.825 26.2 25.7 25.0 24.2 23.7 23.0 22.2 21.5 20.732 33.5 32.9 32.0 31.4 30.4 29.8 28.4 28.2 27.540 42.0 41.2 40.0 38.8 38.0 36.8 35.6 34.4 33.250 52.5 51.5 50.0 48.5 47.4 45.5 44.0 42.5 40.563 66.2 64.9 63.0 61.1 58.0 56.7 54.2 51.7 49.2
C60H D curveTemperature °C
Rat. (A) 20 25 30 35 40 45 50 55 601 1.10 1.08 1.05 1.03 1.00 0.97 0.95 0.92 0.892 2.18 2.14 2.08 2.04 2.00 1.96 1.90 1.86 1.804 4.52 4.40 4.24 4.12 4.00 3.88 3.72 3.56 3.446 6.48 6.36 6.24 6.12 6.00 5.88 5.76 5.58 5.4610 11.4 11.1 10.7 10.4 10.0 9.60 9.20 8.80 8.4016 17.9 17.4 16.9 16.4 16.0 15.5 15.0 14.4 13.920 22.2 21.6 21.2 20.6 20.0 19.4 18.8 18.2 17.625 27.7 27.0 26.5 25.7 25.0 24.2 23.5 22.7 21.732 35.2 34.2 33.6 32.9 32.0 31.0 30.4 29.4 28.440 44.4 43.6 42.4 41.2 40.0 38.8 37.6 36.4 34.850 56.0 54.5 53.0 51.5 50.0 48.5 46.5 45.0 43.063 71.8 69.9 67.4 65.5 63.0 60.4 57.9 55.4 52.9
DPN, DPN NTemperature °C
Rat. (A) 20 25 30 35 40 45 50 55 601 1.04 1.02 1 0.98 0.96 0.93 0.91 0.89 0.862 2.08 2.04 2 1.96 1.91 1.87 1.82 1.77 1.726 6.26 6.13 6 5.87 5.73 5.60 5.45 5.31 5.1610 10.5 10.3 10 9.73 9.45 9.17 8.87 8.57 8.2516 16.7 16.4 16 15.6 16.2 14.8 14.4 14 13.520 20.9 20.4 20 19.5 19 18.7 18 17.5 1725 26.1 25.5 25 24.4 23.8 23.3 22.7 22.1 21.432 33.6 32.8 32 31.2 30.3 29.4 28.5 27.6 26.740 42 41 40 39 37.9 36.8 35.7 34.6 33.4
Groupingfactors
C60HBC60HCC60HD
Miniature circuit breakersTemperature derating/grouping factors
136
DPN Vigi, DPN N Vigi, (30 and 300mA)Temperature °C
Rat. (A) 20 25 30 35 40 45 50 55 606 6.26 6.13 6 5.87 5.73 5.60 5.45 5.31 5.1610 10.5 10.2 10 9.75 9.49 9.23 8.96 8.67 8.3816 16.8 16.4 16 15.6 16.2§ 14.8 14.3 14.9 13.420 21 20.5 20 19.5 19 18.5 17.9 17.4 16.825 26.1 25.5 25 24.4 23.9 23.3 22.7 22.1 21.432 33.4 32.7 32 31.2 30.5 29.7 28.9 28 27.140 41.6 41.8 40 38.2 38.3 37.4 36.5 35.6 34.6
NG125Temperature °C
Rat. (A) 20 25 30 35 40 45 50 55 6010 11 10.75 10.5 10.25 10 9.75 9.5 9.25 916 17.6 17.2 16.8 16.4 16 15.6 15.2 14.8 14.420 22 21.5 21 20.5 20 19.5 19 18.5 1825 27.5 26.87 26.25 25.62 25 24.37 23.75 23.12 22.532 35.2 34.4 33.6 32.8 32 31.2 30.4 29.6 28.840 44 43 42 41 40 39 38 37 3650 55 53.75 52.5 51.25 50 48.75 47.5 46.25 4563 69.3 67.72 66.15 64.57 63 61.42 59.85 58.27 56.780 88 86 84 82 80 78 76 74 72 100 110 107.5 105 102.5 100 97.5 95 92.5 90125 137.5 134.3 131.2 128.1 125 121.8 118.7 121.8 112.5
C120HTemperature °C
Rat. (A) 20 25 30 35 40 45 50 55 6010 10.7 10.4 10 9.4 9.2 8.8 8.4 8.1 7.816 17.1 16.6 16 15 14.7 14 13.4 13 12.620 21.3 20.7 20 18.7 18.3 17.5 16.7 16 15.525 27.1 26 25 23.8 22.7 21.2 20.2 19.6 1932 34.7 33.3 32 30.5 29 27.1 25.8 25 24.240 43 41.5 40 38 36 34 32 31 3050 53.9 51.9 50 47.8 45.7 43.3 41 39.8 38.663 68 65.5 63 60 57 54 51 49.5 4880 85 82.5 80 77 74 60.5 57 55.3 53.6 100 107 103.5 100 96 92 87.5 83 80.5 78125 135 130 125 118.5 114 108 102 99 96
Miniature circuit breakersFor use with lighting loads
137
Table 1: fluorescent lightingDepending on the power supply and the number andtypes of lighting units, the table gives the circuit breaker rating based on the following assumptions: Installation in an enclosure with an ambient
temperature of 25˚C (derating coefficient = 0.8) Power of ballast: 25% of tube power Power factor: 0.6 for non-compensated fluorescent
lighting. 0.86 for compensated fluorescent lighting
Circuit breakers mounted in an enclosure with anambient exterior temperature of 25˚C: derating coefficient = 0.8.
Table 2: high pressure discharge lampsTable valid for 230V and 400V, with compensated ornon-compensated ballast.
Mercury vapour + fluorescent substance Rat. (A)P(1) ≤ 700W 6P(1) ≤ 1000W 10P(1) ≤ 2000W 16Mercury vapour + metal halidesP(1) 375W 6P(1) 1000W 10P(1) 2000W 16High pressure sodium vapour lampsP(1) 400W 6P(1) 1000W 10
Single phase system: 230VThree phase + N system: 400V between phasesTypes of Power of Number of lighting units per phaselighting unit tubes (W)Single phase 18 4 9 29 49 78 98 122 157 196 245 309 392 490non-compensated 36 2 4 14 24 39 49 61 78 98 122 154 196 245
58 1 3 9 15 24 30 38 48 60 76 95 121 152Single phase 18 7 14 42 70 112 140 175 225 281 351 443 562 703compensated 36 3 7 21 35 56 70 87 112 140 175 221 281 351
58 2 4 13 21 34 43 54 69 87 109 137 174 218Two phase 2x18 = 36 3 7 21 35 56 70 87 112 140 175 221 281 351compensated 2x36 = 72 1 3 10 17 28 35 43 56 70 87 110 140 175
2x58 = 118 1 2 6 10 17 21 27 34 43 54 68 87 109MCB rating 1 2 6 10 16 20 25 32 40 50 63 80 100
Calculation: non-compensated fluorescent lighting example (star connection)(rating x 0.8) (U x 0.6)
(P x 1.25)Number =
Electrical auxiliariesFor C60/C120 MCBs
138
D1
Ph
N
U<
D2
14
mcb closed
Ph
N
C2 C112
mcb open
U>
94 92
91
fault normal
Ph
N
14 12
11
mcb closed mcb open
Ph
N
Auxiliary ON/OFF switch (OF)Alarm switch (SD)Shunt trip unit (MX)Under voltage release (MN)
Auxiliary ON/OFF switch (OF) to indicatethe ‘open’ or ‘closed’ position of a circuit breaker
AssemblyClip on the left side of the circuit breaker.
ApplicationsAudible or visual indication of the open or closed stateof the circuit. The indication can be given on the frontof a cubicle or enclosure or grouped on a control desk.Can be used in conjunction with an alarm switch.
Alarm switch (SD) to indicate circuitbreaker opening on a fault (tripped)
AssemblyClip on the left side of the circuit breaker.
ApplicationsAudible or visual indication of a fault on an electricalcircuit in air conditioned rooms, passenger and goodslifts, ventilation etc. May be used in conjunction withan auxiliary ON/OFF switch.
Shunt trip unit (MX) for remote tripping
AssemblyClip on the left side of the circuit breaker.
Applicationsremote opening of electrical circuits.
Under voltage release unit (MN)to ensure automatic tripping in case ofunder voltage and for remote trippingby EMERGENCY STOP push button
AssemblyClip on the left side of the circuit breaker.
ApplicationsAutomatic tripping of a circuit breaker whenever thevoltage drops sufficiently below its nominal rated voltage. Remote tripping of a circuit breaker by ‘emergency stop’ or other N.C. push button.
Electrical auxiliariesMX + OF and MXV releases for
NG125 circuit breakers
139
NG12514 12 C2
N LMX + OF
U >
C1
NG125
NG125
Vigi NG125
SDV
N L
MXV
1211 M2M1
=max.1 mA
ACTp
OFF
LN
Remote operation with MX + OF
Remote opening, by circuit breaker tripping,of electrical lighting circuits, etc.
OF or SD indication
OF auxiliary contact: Indication by dry contact of circuit breaker
"open or closed" condition Indication is either on the front face of the
cubicle or enclosure or centralised on a display console
SD fault indicating switch Indication of a fault on a circuit breaker:
climatic chamber, elevator, ventilation, etc
Remote operation with MXV
Remote tripping by MXV with information feedback by SDV The control switch (luminous or not) trips the
circuit breaker by means of the Vigi equipped with an MXV
An indicator, via the SDV switch in the NO condition, lights up when the Vigi module has tripped on an outgoer or by MXV
Upstream voltage taps
The voltage taps supply auxiliary circuits in order toperform the following functions: Indication, measurement Emergency stopping Remote transfer
NG12524 22 21
N LO+F
NG12596 98 95
N LSD
DC operationMiniature circuit breakers
140
Selecting the circuit breaker The selection of the type of circuit breaker most suitable for protection of a d.c. installation dependsmainly on the following criteria: The rated current, which determines the rating of
the equipment The type of system (1,2 or 3), (see below) The rated voltage, which determines the number of
poles to be involved in breaking
Breaking capacity of miniature circuit breakers on d.c. (in brackets, the number of poles involved in breaking) Type of D.C. breaking capacity(kA)-L/R < 0.015s circuit breaker (IEC 947-2 ,lcu)
Voltage 24/48V 125V 250V 500VC60HB/HC 20 (1) 25 (2) 50 (4) -C60HD 20 (1) 25 (2) 50 (4) -C120 - 15,000 25,000 -NG125N - 36,000 36,000 -NG125H - 36,000 36,000 -
The maximum short circuit current at the point ofinstallation, which determines the breaking capacity. Magnetic trip threshold increases by 1.4
Calculation the short circuit current(Isc) across the terminals of a batteryWhen a short circuit occurs across its terminals, abattery discharges a current given by Ohm's law:
Where Vb = the maximum discharge voltage (battery100 % charged).and Ri = the internal resistance equivalent to the sumof the cell resistances (figure generally given by the manufacturer according to the capacity of the battery).
ExampleWhat is the short circuit current at theterminals of a standing battery with thefollowing characteristics: Capacity: 500Ah Max. discharge voltage: 240V
(110 cells of 2.2V) Discharge current: 300A Autonomy: 1/2 hour Internal resistance: 0.5mΩ
per cellRi = 110 x 0.5 10 - 3 = 55 x10 - 3
Type of system Earthed systems Insulated systemsOne polarity of the DC supply is A centre point of the DC supply isearthed earthed
Diagramsand variouscases of faults
Fault effect Fault A Max. Isc Isc close to max. Isc No effectthe positive polarity the positive polarity is the onlyis the only one involved one involved, voltage U/2
Fault B Max. Isc Max. Isc Max. Iscboth polarities are involved both polarities are involved both polarities are involved
Fault C No effect Same as fault A but this is the No effectnegative polarity which is involved
Most unfavourable case Fault A Faults A and C Fault BDistribution of the The poles required to perform On each polarity there must be the the poles required to performbreaking poles the break are in series number of poles required to perform the break are shared between
on the positive polarity (1),(2) the break of max. Isc at U/2 the 2 polarities
U
ia
b
R
AB
C
U
ia
b
R
AB
C
U/2+U/2
ia
b
R
AB
C
Isc = VbRi
Isc = = 4.4kA 24055 10 -3
As the above calculationshows, the shor circuitcurrent is relativelyweak.
Note: If the internal resistance isnot known, the following approximate formula can beused: Isc = kC, where C is thecapacity of the battery expressedin Ampere hours, and k is acoefficient close to 10 but in anycase always lower than 20.
240 Vdc300A500AhRi = 0.5mΩ/cell
+
-250V =
Load
C120H3P80A
+
-250V =
Load
C120H4P100A
+
-250V =
Load
NS400H2P400A
(1) Or negative if the positive polarity is earthed. (2) An extra pole will be needed on the earthed polarity to provide isolation
Utilisation at 400HzPractical advice
141
The greater part of multi 9 circuit breakers can beused on 400Hz networks. Short-circuit currents at400Hz generator terminals do not, in general, exceedthe nominal current by more than 4 times. Therefore,breaking capacity problems are very rare.
Multi 9 circuit breakers
No thermal derating Increase of magnetic thresholds: Coefficient 1.5 for DPN Coefficient 1.48 for C60 Residual current circuit-breakers from the multi 9 range can be used on 400Hz
networks. It should be noted that the mA threshold varies depending on the network's frequency (see curves below)
Note:In 400Hz, the test circuit for residual current devices may present the risk of notfunctioning when actioning the test button because of threshold variation. Accordingto international studies (IEC 60479-2), the human body is less sensitive to a 400Hzcurrent that passes through the body; so well that, even though the residual currentdevice has had its frequency desensitised, these devices still ensure the protectionof persons. The method for choosing residual current devices in 400Hz is thus thesame as that for 50Hz.
RCCB Operating residual current variation curves
Curve No.Class Rating Sensitivity (mA)
(A) 10 30 100 300 500AC 25 2 1 - 1 1
25-40 - 1 1 1 163-80-100 - 2 1 1 1
A 16-25-40-63 - 3 - 2 2si type 4 - 4 -Selective s ( AC, A ) - - - 2 2
Vigi C60 Operating residual current variation curves
Curve No.Class Rating Sensitivity Sens.
(mA) (A)(A) 10 30 100 300 1A 3A
Vigi C60 110/220 V - 50HzAC 25 2 1 1 - -
63 - 2 1 - -
Vigi C60 2, 3 and 4P 220/415 V - 50HzAC 25 2 1 1 - -
40-63 - 2 1 - -A 25-63 3 3 2 2 -
All typesSelective s - 4 2 2 -
C60 si4
10 50 60 90 150 250 350 400 Hz0.5
1
1.5
2
2.5
I n
10 50 60 90 150 250 350 400 Hz0.5
1
1.5
2
2.5
I n
1234
12
Miniature circuit breakersFor use in conjunction with motor starters and transformers
142
Table 1 - 3 phase 415Vac D.O.L. starting
Recommended MCB
kW hHp Running I C60HB C60HC C60HD
0.12 0.166 0.65 2 2 1
0.18 0.25 0.7 2 2 1
0.25 0.33 0.87 4 2 1
0.37 0.5 1.35 4 4 2
0.55 0.75 1.55 4 4 2
0.75 1.0 1.93 6 4 4
1.1 1.5 2.5 6 6 4
1.5 2 3.5 10 10 6
2.2 3 4.8 16 10 10
3 4 6.4 20 20 10
3.75 5 7.8 25 25 16
4 5.5 8.1 25 25 16
5.5 7.5 11 32 32 16
7.5 10 14.4 50 50 20
9.33 12.5 17.3 63 50 20
11 15 21 63 63 25
13 17.5 25 - - 32
15 20 28 - - 40
18.5 25 35 - - 50
22 30 40 - - 50
30 40 54 - - 63
37 50 65.5 - - -
Table 2 - 1 phase 240Vac D.O.L. starting
kW Hp Running I C60HB C60HC C60HD
0.12 0.166 0.95 4 2 1
0.18 0.25 1.5 4 4 2
0.25 0.33 1.7 6 4 2
0.37 0.5 3 10 6 4
0.55 0.75 4.5 16 10 6
0.75 1 5.5 16 16 10
1.1 1.5 8.5 25 25 16
1.5 2 10.5 32 32 20
2.2 3 15.5 40 40 25
3 4 20 63 63 32
3.75 5 24 - 63 40
5.5 7.5 34 - - 50
6.3 8.5 36.5 - - 63
7.5 10 45 - - 63
11 15 66.5 - - -
Motor startersIn general miniature circuit breakers can give onlyshort circuit protection to motor loads due to the highstarting currents which may be encountered; typically3 - 12 times full load current (FLC).
AssumptionsThe tables give recommended MCB ratings for motors up to 37kW based on the followingassumptions:
Direct-on-line startingstarting current = 7 x FLC run up time = 6seconds, motors <3kW 10 seconds, motors < 22kW running currents = average values only (individualmanufacturer's figures will vary). four pole motors,i.e. speed approx. 1500rpm
For higher inertia loads, i.e. hoists or fans, run uptimes may be considerably longer than thoseassumed above. The rating of the MCB must takeaccount of the greater run up time and startingcurrent. The required MCB rating can be determinedby reference to time/current curves (consult us).
Star/delta startingSince, during the changeover from star to delta, ahigh current surge in the order of DOL values maybe met, the MCB rating selected should be thesame as that recommended for DOL starting
Miniature circuit breakersFor use in conjunction with
motor starters and transformers
143
Table 3 - 3 phase transformers 415Vac supplyVA Primary In (A) C60HB C60HC C60HD500 0.7 4 2 1750 1.04 6 4 21000 1.39 10 6 42000 2.78 16 10 65000 6.95 40 25 1610000 13.89 - 50 2515000 20.84 - 63 3220000 27.78 - - 5025000 34.73 - - 6330000 41.67 - - 63
Table 4 - 1 phase transformers 240Vac supplyVA Primary In (A) C60HB C60HC C60HD50 0.21 2 - -100 0.42 4 2 1250 1.04 6 4 2500 2.08 16 10 41000 4.17 25 16 102500 10.42 63 32 165000 20.84 - 63 3210000 41.66 - - 6312500 52.08 - - -
TransformersHigh inrush currents are also produced when transformers are switched on, typically 10 - 15 times fullload current.
AssumptionsThe tables give recommended MCB ratings for singlephase transformers up to 12500VA and three phasetransformers up to 30000VA based on the following formula.
Inrush currentsWhen LV/LV transformers are switched on, very highinrush currents are produced which must be takeninto account when choosing overcurrent protectiondevices. The peak value of the first current wave oftenreaches 10 - 15 times the rated rms current of thetransformer and may reach values of 20 - 25 timesthe rated current even for transformers rated less than50kVA. This transient inrush current decays veryquickly (in a few milliseconds).
In
θ
I
t
1st peak10 to 25 In
P25M circuit breakersFor motor protection
144
Auxiliaries: Alarm switch. ON/OFF switch. Shunt trip release or
undervoltage release(emergency stop).
Single phase connection
Emergency switch wiring
Time/current characteristics
Choice of motor supply cable size When selecting the cable size the starting current of the motor and the permissiblevoltage drop must be taken into account. The cable must be capable of carrying apermanent service current at least equal to the sum of In + Is/3 where, In = rated current, Is = starting current (4 - 8 In) depending on the motor.
Voltage dropThe permissible voltage drop from the start of the installation to the motor in question is 6% for public distribution systems. If the torque of the machine to bedriven is low during starting it is only necessary to check the voltage drop for therated current of the motor. If the starting torque is high (grinding mills, goods lifts,etc.) the voltage drop should be checked for the starting current.
Protection of the line supplying the motorEvery circuit and every motor must be protectedagainst overloads and short circuits.
Phase failure protectionThe P25M protects each phase separately and interrupts all three phases in the event of a loss ofphase. Single phasing sensitivity is achieved bymeans of a differential trip which accelerates trippingshould phase failure occur.
Two poles ofthe apparatusmust be connected inseries for thesingle phasesupply
The early closing of the auxiliary contact is necessary toenable the closing of the circuit breakerequipped with anundervoltagerelease
20
10
5
2
140
20
10
5
2
1
200
50
20
5
21.5
x rated current
2 3 4 6 8 10 15 20 30
Min
utes
Sec
onds
Mill
isec
onds
U
N Ph
1
L1 L2 L3
3 5
2 4 6
P25M motor circuit breakerThis protects motors against overloads and short circuits. P25M type circuit breaker has on each pole athermal release for protection against overloads and amagnetic release for protection against short circuits.For high short circuit currents use the limiter block, Ref. 21115.For ratings from 0.16A - 10A. 415V or from 0.16 - 18A,240V; in this case the breaking capacity of the P25Mcircuit breaker is unlimited.
ApplicationsThe P25M circuit breaker is particularly suitable for protecting small machine tools and similar machines,with local control.
Thermal release settingsThe thermal releases are supplied set to the bottomvalue of the setting range. Simultaneous setting of thethermal releases can be carried out by opening thecover and adjusting the dial on the front face of theP25M. It is recommended that the thermal releases beset to the current that the motor absorbs in normal service and not to its rated current so as to provideeffective close protection.
Ambient temperature compensationClose protection against thermal overload is enhancedby thermal releases which are ambient temperaturecompensated over the range - 20°C - +60°C. Duringoverload conditions, tripping is delayed at lower ambient temperatures, from - 20°C - +20°C, and isaccelerated at higher ambient temperatures, from 20°C- +60°C.
Rating Settings Part No. Standard power ratings kW:In (A) of 3-phase motors 50 - 60Hz AC-3 category
230 400 415 440 500 6900.16 0.1 - 0.16 21100 - - - - - -0.25 0.16 - 0.25 21101 - - - - - -0.40 0.25 - 0.40 21102 - - - - - -0.63 0.40 - 0.63 21103 - - - - - 0.371.0 0.63 - 1 21104 - - - 0.37 0.37 0.551.6 1 - 1.6 21105 - 0.37 - 0.55 0.75 1.12.5 1.6 - 2.5 21106 0.37 0.75 1.1 1.1 1.1 1.54.0 2.5 - 4 21107 0.75 1.5 1.5 1.5 2.2 36.3 4 - 6.3 21108 1.1 2.2 2.2 3 3.7 410 6 - 10 21109 2.2 4 4 4 5.5 7.514 9 - 14 21110 3 5.5 5.5 7.5 9 1118 13 - 18 21111 4 7.5 9 9 10 1523 17 - 23 21112 5.5 9 11 11 11 18.525 20 - 25 21113 5.5 11 11 11 15 22
Types of RCD
145
ime(s)
000s
100s
10s
1s
00ms
100mA 300mA 600mA 1.5A 3A 500A
current (A)
Two families of RCD are offered in this catalogue (1) Those without overcurrent protection (RCDs)
e.g. RMGs (2) Those with overcurrent protection (RCBOs)
e.g. C60H rcbo’s and DPNMiniature circuit breakers combined with a residual current device, this RCD/MCB combination can berealised in the form of the C60H RCBO combinedRCD/MCB or by combining a vigi module with an MCB.
All of these units can be used to protect individual circuits or as devices mounted within individual enclosures. Individual out going circuits within type Aor type B MCB distribution boards can be protected byinstalling RCD/MCB combinations on that particular outgoing way. Groups of circuits can be protected within distribution boards by selection of either splitload or dual incomer units with selected circuits protected by RCD incoming devices. Complete distribution systems can be given RCD protection byinstalling an RMG RCD in a separate enclosure ahead of the distribution board or by using a distribution boardhaving an incoming rcd.
Unwanted trippingThe principal reasons for unwanted tripping of RCDsare lack of discrimination between rcd's (see followingparagraph) and transient earth leakage currents, whichhave various causes such as lightning strikes, switching surges (caused by switching inductive loads)or switching capacitive loads (RF filter networks, mineral insulated cables etc) All Merlin Gerin RCDsand RCD/MCBs incorporate a filtering device which minimises their response to transients, virtually eliminating unwanted tripping.
Discrimination of RCDsFigure 3: characteristic of 231 16, 300mA time delayedRCD with 10, 30 and 100mA instantaneous devicessuperimposed to show discrimination.
Wherever two or more rcd's are installed in series withone another, measures must be taken to ensure thatthey discriminate properly - in the event of an earthfault, only the device next upstream should operate.
RCDs do not discriminate on rated residual operatingcurrent sensitivity alone. In other words, a 100mAdevice upstream of a 30mA device will not offer inherent discrimination.
To provide the necessary discrimination, RCDs can beprovided with an inbuilt time delay mechanism, usually50ms. This inbuilt time delay is sufficient to allow thedownstream device to open the circuit before theupstream device starts to operate. Such an RCD mustbe used as the incomer to a split load boardincorporating two RCDs.
Zone Physiological Effects
Usually no reaction effects
Usually no harmful physiological effects
Usually no organic damage to be expected. Likelihood of muscular contraction and difficulty of breathing reversibledisturbances of formation and conduction of impulses in the heart and transient cardiac arrest without ventricular fibrillation increases with current magnitude and time
In addition to the effects of zone 3 probability of ventricular fibrillation increased up to 5% (Curve C2) up to 50%(Curve C3) and above 50% beyond Curve C3 Increasing with magnitude and time. pathyphysiological effects suchas cardiac arrest, breathing arrest and heavy burns may occur.
4
3
2
1
IEC publication 479 "effects of currents passing through the human body"
TIME/CURRENT ZONES OF EFFECTS OF A.C. CURRENT (15 - 100HZ) ON PERSONS WITH STANDARD RCD CHARACTERISTICS SUPERIMPOSED
10
20
50
100
200
500
1000
2000
5000
10000
0.1 0.2 0.3 0.5 1 2 3 5 10 20 30 50 100 200 300 500 1000 2000 3000 5000 10000
time
in m
illis
econ
ds
current in milliamperes (R.M.S.)typical currentlimits due to body resistanceat 240V
a b c1 c2 c3 IEC 479
10mA 30mA 100mA
1 2 3 4
(fig. 3)
Merlin Gerin 300mA time delayed rcd
Typical 100mAinstantaneous rcd
Typical 30mAinstantaneous rcd
Degrees of protectionProvided by enclosures
146
ExampleIP 55
Protection indexEuropean standard EN60529 gives a protection code(IP) which characterises the ability of equipment towithstand the following external influences: Presence of solid bodies Presence of waterThis code comprises two digits, depending on theseexternal influences. The protection index is assignedto the equipment following a series of tests laid downin the respective standards.
External influencesIn many national and international standards, a largenumber of external influences to which an electrical installation can be subjected are indexed and coded:presence of water, presence of solid objects, risk ofimpact, vibrations, presence of corrosive substances,etc. These influences may be present with variableintensity depending on the conditions of installation:The presence of water may be in the form of a fewdrops or total immersion.
Test according to EN60529
1st digit
Protection against solid bodies
2nd digit
Protection against liquids
no protection
Protection against solid bodies greater than 50 mm
Protection against solid bodies greater than12.5mm
Protection against solid bodies greater than 2.5 mm
Protection against solid bodies greater than 1 mm
Protection against dust(no harmfuldeposits)
Total protection against dust
No protection
Protection againstvertical drops ofwater (condensation)
Protection againstdrops of water fallingup to 15° fromvertical
Protection againstrainwater up to 60°from vertical
Protection againstwater projected fromall directions
protection againsthosing with waterfrom all directions
Protection againstswamping with water
Protection againstimmersion
0
1
2
3
4
5
6
0
1
2
3
4
5
6
7
Protection against hosingwith water from all directions
Protection against dust(no harmful deposits)
ø 50mm
ø 12.5mm
ø 2.5mm
ø 1mm
Choosing a surge arrester for LV networksPRD/PF
147
Load considerations The surge arrester’s level of protection (Up) depends on the installed equipment and the rated voltage of the
installation Up must lie between The full voltage of the permanent operating conditions (Uc) The impulse withstand voltage (Uchoc) of the equipment to be protected: Uc<Up<Uchoc
8/20 impulse withstand table for equipment to be protected General standard: IEC 60364-4
Placing several surge arresters in a cascading configuration
Rated voltage Equipment sensitivity withstand (Uchoc)of the installationThree phase Reduced Normal High Very highnetworks electronic circuit electrical household industrial industrial
devices: appliances: devices: devices:televisions, alarms, HiFi, dishwashers, ovens motors, distribution video recorders, refrigerators, cabinets, electric meters,computers portable tools current sockets, telemeterstelecommunication transfos.
400/690/1000 2.5 kV 4 kV 6 kV 8 kV230/440 V 1.5 kV 2.5 kV 4 kV 6 kV
shock wave shock wave shock wave shock wavecategory I category II category III category IV
Earthing systems TT TN-S TN-C ITUc value for common mode ≥ 1.5 Uo ≥ 1.5 Uo ≥ 1.5 Uo ≥ 1.732 Uo(protection between live conductors and earth)Uc value for differential mode ≥ 1.1 Uo ≥ 1.1 Uo ≥ 1.1 Uo(protection between phase and neutral)Uo: Simple network voltage between phase and neutral.Uc: Full voltage under permanent operating conditions.Uc: Value as in the French standard: NF C 15100 section 534.
The incoming surge arrester (P1) is dimensioned torun off lightning currents at the source of the installation, 2 cases are possible: If there is a level of protection (Up) too high for
the impulse withstand voltage (Uchoc) of the installation's equipment:
A secondary protection surge arrester (P2) placednear loads is sufficient, to lower the voltage and make it compatible with the impulse withstand voltage of the equipment to be protected
If sensitive equipment is too far from the incomingsurge arrester (d ≥ 30 m figure 2):
A secondary protection surge arrester (P2) placednear loads suffices, to lower the voltage and make it compatible with the impulse withstand voltage of the equipment to be protected
P1
P1 P2
E
E
Up:
2 kV
Uchoc:
1.5 kV
Up:
2 kV
Uchoc:
1.5 kVUp:
1.2 kV
Example figure 1 P1
P1 P2
d ≥30 m
E
E
Example figure 2
E: Equipment to be protected with impulse withstandof 1.5 kV
P1: incoming surge arrester dimensioned with In andImax that are sufficient enough to face lightningcurrents that may appear and with a level of protection of 2.5 kV
P2: Surge arrester near equipment to be protectedwith an adapted level of protection and which isco-ordonated with P1
E: Equipment to be protected with impulse withstandof 1.5 kV
P1: Incoming surge arrester dimensioned with Inand Imax that are sufficient enough to facelightning currents that may appear and with alevel of protection of 1.5 kV. This level of 1.5 kV isacceptable in principle (even though there is nomargin), but the distance d is too great
P2: Surge arrester near equipment to be protectedwith an adapted level of protection and which isco-ordonated with P1
Choosing a surge arrester for LV networksPRD/PF
148
Site characteristics
Selection depending on the earthing system
If a lightning rod is planned or has already been installed on the building (or ina 50 m radius):
Choose an incoming protection device with an Imax of 65 kA. lightning flashdensity (Ng)
Mount a surge arrester Imax: 8 kA in a cascading configuration if: The distance between the incoming surge arrester and loads is ≥30 m The surge arrester's voltage Up is too high in regards to the sensitivity of the
load to be protected (Uchoc)
Up surge arrester < Uchoc switchgear
Installation without a lighting conductor
Residential
Geographical location Urban Rural
Lightning flash density (Ng) ≤ 0.5 0.5<Ng<1.6 ≥ 1.6 ≤ 0.5 0.5<Ng<1.6 ≥ 1.6
Imax (kA) incoming protection 15* 15 15 15 30 - 40 65
Imax (kA) secondary protection if: 8 8
Up too high and/or d ≥ 30 m
(*) recommended
Tertiary/industrial (1)
Continuity of supply of the Not necessary Partial Essential
operation
Consequence (financial) Low High Very high
of a lightning stroke on
equipment to be protected
Lightning flash density (Ng)
Imax (kA) incoming protection
Imax (kA) secondary protection if:
Up too high and/or d ≥ 30 m
(1) since in the tertiary/industrial sector the cost of equipment to be protected is higher, damage due to lightning is more significant
≤0.5
15
0.5<Ng<1.6
15
≥1.6
30 - 40
8
≤0.5
15
0.5<Ng<1.6
30 - 40
8
≥1.6
65
8
≤0.5
30 - 40
8
0.5<Ng<1.6
65
8
≥1.6
65
8
Earthing systems TT TN-S TN-C IT IT non-distributed distributedneutral neutral
Draw out surge arrestersPRD MC 1P
Uc = 275 VMC 3PUc = 440 V 3PMC/MD 1P+N 1P+N 1P+NUc = 440/275 V 3P+N 3P+N 3P+N
Fixed surge arrestersPF 30 - 65 kA MC 1P+N 1P+N 1P+N
Uc = 440 V 3P+N 3P+N 3P+NPF 8 - 15 kA MC/MD 1P+N 1P+N 1P+N
Uc = 440/275 V 3P+N 3P+N 3P+NPE MC 1P
(Uc = 440 V) 3x1P 3x1P
Choosing a surge arrester for LV networksPRD/PF
149
After having chosen the surge arrester(s) needed toprotect the installation, the appropriate disconnectioncircuit breaker is to be chosen from the oppositetable: Its breaking capacity must be compatible with the
installation's breaking capacity Each live conductor must be protected example:
a 1P+N surge arrester must be combined with a 2P disconnection circuit breaker (2 protected poles)
Choosing a disconnection circuit breaker
Maximum lightning disconnection discharge current circuit breaker
Rating Curve Range8-15-30-40 kA 20 A C -65 kA 50 A C -
Co-ordinating 2 surge arresters (the 10 m rule)In the case of an exposed site and the presence ofsensitive loads, it is recommended to co-ordinateupstream and downstream protection in a cascadingconfiguration.
Installation constraints
The 50 cm rule in the switchboardConnections must be as short as possible.Do not exceed a distance of 50 cm, to efficiently protect electrical loads.
O-OFF
O-OFF
T
OFF
O-OFF
O-OFF
O-OFF
O-OFF
NL
MERLINGER
IN
C40r-275
Imax:40kA(8/20)
In:15kA(8/20)
Up:1,2kV
Uc:275V
multi 9
PRDMER
LIN GERIN
C Neutral r
multi 9
PRD
d1
d2
d3
PRD
type
or delayed
d1+d2+d3 ≤ 50 cm
O-OFF
O-OFF
NL
MERLIN
GERINmulti 9
PRDMERLIN
GERIN
C Neutral r
multi 9
PRD
O-OFF
O-OFF
NL
MERLIN
GERINmulti 9
PRDMERLIN
GERIN
C Neutral r
multi 9
PRD
PRD1
PRD2
O-OFF
O-OFF
incomer end protection
secondary protection
ContactorsCT
150
Table 1: Heating Maximum power (kW)for a given rating
Type of heating Contactor rating (A)(AC1 - AC7a 25 40 63 100categories)400/415V heatingNo. of ops per day 25 5.4 8.6 14 21.6
50 5.4 8.6 14 21.675 4.6 7.4 12 18100 4 6 9.5 14250 2.5 3.8 6 9500 1.7 2.7 4.5 6.8
230/240V heatingNo. of ops per day 25 16 26 41 63
50 16 26 41 6375 14 22 35 52100 11 17 26 40250 5 8 13 19500 3.5 6 9 14
CT 2000 contactor applications
Inrush and holding power
Type Rating Consumption Maximum(A) inrush holding power
(VA) (VA)1P, 2P 16/25 15 3.8 1.33P, 4P 16/25 34 4.6 1.62P 40/63 34 4.6 1.63P, 4P 40/63 53 6.5 2.12P 100 53 6.5 2.14P 100 106 13 4.2
Choice of contactor Heating circuits: (AC7a table 1)
Table 1: maximum power (kW) controlled by acontactor as a function of contactor rating andservice voltage. Example of use: electric heating units, water heaters
Lighting circuits: (AC5, table 2 and 3)choice of contactor and maximum number of loaddevices controlled as a function of the unit power(W) of the load devices and the service voltage:incandescent lamps, fluorescent lamps withstarter, (individual mounting), sodium vapourlamps
Utility motors (AC7b, table 4) maximum power(kW) controlled by a contactor as a function ofcontactor rating and operating voltage. Typicalapplications: small pumps, compressors andmachine tools
Grouping of contactorsWhen contactors are mounted side by side on thesame DIN rail, a spacer must be fitted between everypair of contactors. Contactor bank spacer cat. ref.27062 enables contactors to be spaced 9mm apart toimprove ventilation and prevent overheating.
Note:For normal usage there is generally no requirement toderate due to the high calibration temperatureemployed.
Installation recommendations for contactors - when sited in close proximity to electronic equipment i.e. remote control switches, programmable timers etc.1. Install two contactor spacers between the
contactor and the electronic equipment.2. Ensure contactor coil circuit and electronic
equipment supply circuit are separated.3. Where more than one DIN rail is available the
contactor must be mounted on the upper rail and the electronic equipment on the lower rail.
4. Where only one DIN rail is available, the contactormust be mounted to the RHS of electronic equipment on horizontal rails and above electronicequipment on vertical rails.
ContactorsCT
151
Table 4: Utility Maximum power (kW)motors for a given rating
Type of motor Contactor rating (A)(AC7b category) 16 25 40 63 100230/240V - 1.4 2.5 4 4400/415V - 4 7.5 15 15
Table 3: Sodium Maximum number oflighting lamps for a given rating
230/240V Power Contactor rating (A)(W) 16 25 40 63 100
Low pressure sodium (with compensation)18 14 21 40 60 6035 3 5 10 15 1555 3 5 10 15 1590 2 5 6 11 11135 1 2 4 6 6180 1 2 4 6 6
High pressure sodium (without compensation)70 8 12 20 32 32150 4 7 13 18 18250 2 4 8 11 11400 1 3 5 8 81000 - 1 2 3 3
High pressure sodium (with compensation)70 6 9 18 25 25150 6 9 18 25 25250 2 4 8 12 12400 2 3 6 9 91000 1 2 4 6 6
Table 2: Lighting Maximum number oflamps for a given rating
230/240V Power Contactor rating (A)(W) 16 25 40 63 100
Incandescent lamp with/without halogen gas40 38 57 115 172 25060 30 45 85 125 18775 25 38 70 100 150100 19 28 50 73 110150 12 18 35 50 75200 10 14 26 37 55300 7 10 18 25 37500 4 6 10 15 221000 2 3 6 8 12
12V halogen lamp (with ELV transformer)20 15 23 42 63 9450 10 15 27 42 6375 8 12 23 35 52100 6 9 18 27 40150 4 6 13 19 28
26mm fluorescent (single tube with parallel capacitor)15 15 20 40 60 9018 15 20 40 60 9020 15 20 40 60 9036 15 20 40 60 9040 15 20 40 60 9058 10 15 30 43 6465 10 15 30 43 64115 5 7 14 20 30140 5 7 14 20 30
26mm fluorescent tube (single tube without capacitor)15 22 30 70 100 15018 22 30 70 100 15020 22 30 70 100 15036 20 28 60 90 13540 20 28 60 90 13558 13 17 35 56 8465 13 17 35 56 84115 7 10 20 32 48140 7 10 20 32 48
26mm fluorescent (twin tube with parallel capacitor)2x18 30 46 80 123 1802x20 30 46 80 123 1802x36 17 25 43 67 1002x40 17 25 43 67 1002x58 10 16 27 42 632x65 10 16 27 42 632x118 6 10 16 25 372x140 6 10 16 25 37
26mm fluorescent (four tube with parallel capacitor)4x18 15 23 46 69 100
Electronic ballast (1 x 26mm tube)18 74 111 222 333 50036 38 58 117 176 26058 25 37 74 111 160
Electronic ballast (2 x 26mm tube)2x18 36 55 111 166 2502x36 20 30 60 90 1352x58 12 19 38 57 85
Electronic compact7 133 200 400 600 90011 80 120 240 360 54015 58 88 176 264 39620 44 66 132 200 30023 38 57 114 171 256
To obtain the maximum number of lamps on threephase four wire circuits, multiply the maximum number of lights for single phase by three.
For three phase, three wire, the following formulamust be applied
Single phase quantity X 31,732
Time delay contactor auxiliaryACTt
152
ACTt 4 types of delay: Type A time delay puts back loads energisation Type B time delay energises a load for a given time, once the control contact
has closed (push button) Type C time delay extends load energisation Type H time delay energises a load for a given time, as log as the control
contact remains closed Time delay range: 1s - 10h Accuracy:+/- 0.5%
Type AThe single time delay cycle begins on energisationand the load is energised at the end of time delay T
T
S
0
CT
t
CTACTt
A1
A2
1
2
S
L
N
Load
Type BThe single time delay cycle begins when the controlcontact is closed
T
CT
BP
U(A1 A2)
0
t
CTACTt
A1
B1
Y1
1
2
A2
BP
B2
L
N
Load
Type CThe single time delay cycle begins when the controlcontact is (pushbutton) is released, at the end of timedelay T, the load is de-energised again
T
CT
BP
U(A1 A2)
0
t
CTACTt
A1
B1
Y1
1
2
A2
BP
L
N
Load
Type DThe single time delay cycle begins on energisation.the load is de-energised again at the end of timedelay T or when the control contact is released
T
CT
S
0
t
CTACTt
A1 1
2
A2B2
S
L
N
Load
153
TL impulse relaysPractical advice
The table below indicates the maximum power ratingof a number of lamps that can be installed on impulserelay controlled 240V single phase circuit. For other voltages please consult us.
impulse relay max power (W)
Impulse relay rating 16A 32ALightingIncandescent Tungsten filament (240 V)lighting 40 60 75 100 200 W
40 25 20 16 8 1600106 66 53 42 21 4260
With halogen (240 V)300 500 1000 1500 W5 3 1 1 150013 8 4 2 4000
VLV halogen lighting (12 or 24 V with transformer)20 50 75 100 W70 28 19 14 1400180 74 50 37 3700
Fluorescent Single with starter (non compensated)lighting 18 36 58 W
70 35 21 1300186 93 55 3400
Single with starter (compensated)18 36 58W50 25 16 930133 66 42 2400
Double with series compensated starter2x18 2x36 2x58W56 28 17 2000148 74 45 5300
Single HF ballast16 32 50W80 40 26 1300212 106 69 3400
Double HF ballast2x16 2x32 2x50W40 20 13 1300106 53 34 3400
Discharge Low pressure sodium vapourlamps 55 90 135 180 W
24 15 10 7 130063 40 26 18 3400
High pressure sodium vapour or metal halide250 400 1000 W5 3 1 130013 8 3 3400
154
Lighting management MIN and PREOperation diagrams
MIN timer Time delay of 1 - 7 min Pressing one of the push buttons again restarts
the timer Continuous mode by pressing switch (S) on front
face
MINe timer Time delay of 3 or 20 min Pressing one of the push buttons again restarts
the timer
MINs timer Time delay of 30s - 8 min Pressing one of the push buttons again restarts
the timer Continuous mode by pressing switch (S) on front
face
PRE switch off warning Switch off warning (P) of 20 - 40 s 50% reduction
in luminous flux
UZ
S
< 2 s< 2 s
BP
UZ
tt
< 2 s< 2 s
BP
UZ
20 min3 min
UZ
S
< 2 s< 2 s
BP
UZ
20 mint
P
UZ
50%
KeyS: Switch on front faceT: Time delayP: Switch off warning
155
Movement detectorCE30
0 30
3
0
1
2
3
1
2
m
m
m 0
2.5 m
4 12 20 30m8 18 24 2820 24 29161231
110˚
1 beam5 beams
20˚
Function
The CE30 controls switching on and off of lighting by detection of movements ofpeople and according to ambient brightness.
The CE30 controls switching on of lighting if a movement is detected and if theambient brightness is less than the pre-set threshold.
After the last movement detected, it controls switching off of lighting on completionof a time delay that can be set beforehand.
Data Power supply: 230V +/- 10%, 50 - 60Hz
Detection angle: 20°
Configuration of detection angle by cover cut out
Range: 30m
Setting of the brightness threshold for lighting control: 5 - 300lux
Setting of the time delay between the last movement detected and switching offof lighting: 40 seconds - 8 minutes
Output contact:
10A cos Ø = 1
5A cos Ø = 0.5
Incandescent lights: relays compulsory
Degree of protection: IP43
Connection: 1.05mm2 spring tunnel type terminals
Consumption : < 1W
Operating temperature: -25 to +55°C
Approvals: VDE-SEMKO-KEMA-KEUR
L
N
L N
156
Movement detectorCDM
0 1 2 3 4 5 6 7 8 9 10 11 12
5
0
1
2
3
4
5
1
23
4
m
m
m 0 1 2 3 4 5 6 7 8 9 10 11 12m
2.5 m180˚
Function
The CDM controls switching on and off of lighting by detection of movements ofpeople and according to ambient brightness.
The CDM controls switching on of lighting if a movement is detected and if theambient brightness is less than the pre-set threshold.
After the last movement detected, it controls switching off of lighting on completionof a time delay that can be set beforehand.
Data Power supply: 230 V -10% +6%, 50 - 60Hz
Detection angle: 0° - 180º
Configuration of detection angle by cover cut-out
Range; 0 - 12 m according to slope adjustment
Setting of the brightness threshold for lighting control: 3 - 80 lux
Setting of the time delay between the last movement detected and switching offof lighting: 4 seconds - 15 minutes
Lighting power
Incandescent lights: 1000 W max
Halogen lamps: 500 W max
Fluorescent and fluocompact lights: relays compulsory.
Degree of protection: IP54
Connection: screw terminals up to 205 mm2
Consumption: 1.1 VA
Operating temperature: -25 to +50 º C
Approvals: VDE-SEMKO-KEMA-KEUR
L
N
L N
157
LN
N L L
CDP
Presence detectorCDP
Function
The CDP controls switching on and off lighting according to the presence of aperson and ambient brightness.
It allows detection:
Of presence (zone A), the system detects the slightest motions,
Of movements (zone B), the system detects movements.
The CDP controls switching on if presence is detected and if ambient brightness isless than the set threshold.
It controls switching off of lighting if the outside light becomes greater the thethreshold, even in the event of movement.
Data Power supply: 230 V +/- 10%, 50 Hz
Detection angle: Horizontal 360º, vertical 180º
Recommended floor/ceiling clearance: 2.2 - 3 m
Maximum range for recommended clearance:
4m diameter presence detection zone (small motions)
24m diameter movement detection zone (movements)
Setting the brightness threshold for lighting control: 20 - 1300 lux
Setting the time delay between the last movement detected and switch off oflighting: 4 - 15 min
Lighting power
incandescent lights: 2000W max
LV halogen lights (230V) and ELV (12V): 1000W max
Fluorescent lights with conventional ballast: 1000W max (cos Ø = 0.5)
Fluorescent lights with parallel corrected ballast: 500W max ( cos Ø = 0.5)
Degree of protection: IP20
Operating temperature: -25ºC to +55ºC
Storage temperature: -25ºC to +70ºC
Weight: 144g
Dimensions:
Diameter; 120mm
Height: 70mm
Fixing centre distance: 81mm
3601m1 m 2 m2 m12 m 12 m0
AB B
158
Presence detectorCDPt
Function
The CDpt reserved for installations with 1 - 10V control ballast, regulates lightingintensity according to the presence of a person and ambient lighting.
It maintains ambient brightness at a level set by lighting variation.
The TDP remote control allows manual monitoring of lighting independently ofdetector settings.
It allows detection
Of presence (zone A) the system detects the slightest motions
Of movements (zone B), the system detects movements
Data Power supply: 230V +/- 10%, 50Hz
Detection angle:horizontal 360º, vertical 180º
Recommended floor/ceiling clearance: 2.5 - 3m
Maximum range for recommended clearance:
4m diameter motion detection zone (small motions)
24m diameter movement detection zone (movements)
Setting the brightness threshold for lighting control: 100 - 1300 lux
Setting the time delay between the last movement detected and switch off oflighting: 4 - 15 min
Lighting power(max. number of 1 - 10V ballasts)
16 x (1 x 36W)
12 x (1 x 58W)
12 x (2 x 36W)
8 x (2 x 58W)
Degree of protection: IP20
Operating temperature: -15ºC to +55ºC
Storage temperature: -25ºC to +70 ºC
Weight: 144g
Dimensions:
Diameter: 120mm
Height: 70mm
Fixing centre distance: 81mm
Remote control (TDP)
Range: 4m
Power supply: 2 xLR03-1.5V batteries (not supplied)
LN
LN L
CDPt
1-10 V
3601m1 m 2 m2 m12 m 12 m0
AB B
159
PM9 multimeterConnection
Three phase network + neutral: 3 x 230/400V
L1 L2 L3
P1
P2 S2
S1
P1
P2 S2
S1
P1
P2 S2
S1
1
N
2 3 4 5 6 7 8 9
10 11 12 13 14 15 16 17 18
Three phase network: 3 x 400V
L1 L2 L3
P1
P2 S2
S1
P1
P2 S2
S1
P1
P2 S2
S1
1 2 3 4 5 6 7 8 9
10 11 12 13 14 15 16 17 18
230V
Three phase network: 3 x 230V
L1 L2 L3
P1
P2 S2
S1
P1
P2 S2
S1
P1
P2 S2
S1
1 2 3 4 5 6 7 8 9
10 11 12 13 14 15 16 17 18
!
Three phase network with or without neutral greater than 400V
Caution Do not earth the CT secondary (S2)
Networks greater than 5A: Measurements require use of current transformers
with a 5A secondary
The measurements require use of voltagetransformers (VT) with a 230V secondary
It is essential to comply with routing direction ofpower cables in the current transformer primary.The cables enter in P1 and leave in P2 in thedirection of the loads
1 2 3 4 5 6 7 8 9
10 11 12 13 14 15 16 17 18
L1
L2
L3
N
L1
L2
L3TT (VT)x 230V
P1
P2 S2
S1
PowerLogic:Power meter series PM700
160
4 wire connection with 3 CT’s and no VT
PM700
3 wire connection with 2 CT’s and 2 VT’s
PM700
PM700
PM700
161
TI current tranformersChoosing a current transformer
Choosing a current transformer2 criteria exist for choosing a TI:
The Ip/5A ratio The type of installationThe Ip/5A ratio:It is recommended that a ratio immediately superior to the measured current (In) bechosen. Ex: In = 1103 A; ratio chosen: 1250/5Type of installation:Which TI model to choose depends on the type of installation: Insulated cables Prisma vertical busbars Insulated flexible busbars Linergy vertical busbars Rigid busbars
Important warning: Never open the secondary circuit of a current transformer while the primary circuitis energised. Before any kind of maintenance service on the secondary circuit, the secondary terminals on the transformer must be short circuited.
Determining the accuracy class of a TI:The accuracy class is a function of the transformer’s power and the consumption of the the weighing system. The latter takes device and cable consumption intoaccount. For a given accuracy class, consumption of the weighing system must not exceed the power on the TI transformer.
Primary copper Power in VAcable cross section doubled meter atin mm2 200C1 11.5 0.6852.5 0.414 0.2546 0.16910 0.0975For each temperation variation of 100C, the powerabsorbed by the cables rises by 4%
Merlin Gerin Consumptiondevice (VA)Ammeter 72 x 72 0.75Analogue ammeter 1.25Ammeter Digipact IM100 0.5Digital ammeter 0.3PM measurement centre 0.25CDS 0.25RCI 0.5CE tri 1CEr tri 1Varlogic regulator 0.7
Example
The accuracy class of the TI is deduced: Class 3 for a TI with a ratio of 50/5 Class 0.5 for a TI with a ratio of 100/5 Class 0.5 for a TI with a ratio of 125/5
Consumption of a weighing system at 200CCDS 0.25VADigital ammeter + 0.30VA2 meters of doubled wire 2.5mm2 + 0.82VAWeighing system consumption = 1.37VA
162
Dimensions Section eight
Type A distribution board 164
Type B distribution board 165
Heavy duty distribution board 166
Single phase type P&PS pan assembly 167
Three phase type P pan assembly 168
B series enclosure 169
Three phase type PS pan assembly 170
Three phase type E pan assembly 171
MCB and accessories 172 - 177
Local control devices 179
Remote control devices 180 - 181
Time management 182
Lighting management 183
Metering and measurement 184 - 187
Heating management 188
Mini Opale enclosures 189
G9 enclosures 189
Modular enclosures 189
Pragma C IP40 191
UT enclosures 192
Pragma C IP55 enclosures 194
Prisma GK enclosures 193
Kaedra enclosures 190
UP enclosures 195163
Dimensions (mm)A type distribution boards
164
Part No. A BMGAN6 260 264MGAN9, MGAN42SL 315 264
MGAN12, MGAN46DS, MGAN416/96MS 370 264
MGAN15, MGAN66/76DS, MGAN48/66DS,
MGAN520/716/912/1010/126MS, 450 264
MGAN23, MGAN1228MS (two row unit) 370 494
A series enclosurePart No. A BMGAN16DE 260 264MGAN22DE 315 264MGAN28DE 370 264MGAN34DE 450 264MGAN56DE* 370 494* 2 row enclosureAll other dimensions as A type distribution board
NEUTRAL COVER
ISOLATE SUPPLYBEFORE REMOVAL
NEUTRAL COVER
ISOLATE SUPPLYBEFORE REMOVAL
NEUTRAL COVER
ISOLATE SUPPLYBEFORE REMOVAL
NEUTRAL COVER
ISOLATE SUPPLYBEFORE REMOVAL
NEUTRAL COVER
ISOLATE SUPPLYBEFORE REMOVAL
ISOLATE SUPPLYBEFORE REMOVAL
NEUTRAL CONNECTIONCOVER
LN
A
A
31
9625
3
3
Ø32 Ø25 Ø20
3
18
B
6060
12
Datum
ø6.25
ø13
Key hole slot dimensions
Dimensions (mm)B type distribution boards
165
Part No. A BMGBN4,MGBN6 484 386MGBN8 538 440
MGBN12 700 602
MGAN16, MGAN18 808 710
MGAN24 970 872
Dimensions (mm)Heavy duty distribution board (100A)IP55 weatherproof
166
Part No. No. of Dimensions (mm)outgoing ways Height Width Depth
MGBN6HDGK 6 650 600 290*MGBN8HDGK 8 650 600 290*MGBN12HDGK 12 850 600 290*MGBN16HDGK 16 850 600 290** Denotes the maximum depth dimensions with key fitted.
525
625
575/775
max.
700/900max.
M8
ø12 ø7
10
10
B board extension box enclosures
Part No. AMGBNEXN 124MGBNEX034N 140MGBNKWH 124MGBNEXA15N 140MGBN100CCI 140MGBNDSI 124
270
470 A
6060
65
65
Dimensions (mm)Single phase type P & PS
167
Fixing details
Reference A B C D E F GMGAN6P/PS 196 182 145 70.12 70.12 - 18.5MGAN9P/PS 250 236 199 70.12 36.01 70.12 27.5MGAN12P/PS 304 290 253 70.12 108.01 70.12 18.5MGAN15P/PS 358 344 307 97.12 108.01 97.12 18.5
ISOLATE SUPPLYBEFORE REMOVAL
NEUTRAL COVER NEUTRAL COVER
ISOLATE SUPPLYBEFORE REMOVAL
NEUTRAL COVER
ISOLATE SUPPLYBEFORE REMOVAL
NEUTRAL COVER
ISOLATE SUPPLYBEFORE REMOVAL
NEUTRAL COVER
ISOLATE SUPPLYBEFORE REMOVAL
COVER CUTOUT
ISOLATE SUPPLYBEFORE REMOVAL
NEUTRAL CONNECTIONCOVER
LN
62
88
Front cover
23.5
121.7
46
18.5
B
DG
E F
C
75
BA
X
28X
X
5.3
4.2
Dimensions (mm)Three phase type E
168
Part No. A BMGBN4E 325 346MGBN6E 400 421MGBN8E 450 471MGBN12E 550 571MGBN16E 650 671MGBN18E 725 746MGBN24E 875 896
87.00 21.60
Inside of cover35
0.00
Dimension A
250.
00
Incoming device cut-out centre
87.00
125A 152.00250A
Dimension B
106.
86
Dimensions (mm)B series enclosures IP31
169
Part No. AMGBN4SXS/SXP 484
MGBN8SXS/SXP 538
MGBN12SXS/SXP 700
MGBN16SXS/SXP 808
MGBN24SXS/SXP 970
140380 45
3
45
450
45
A
45
12
Datum
ø6.5
ø13
Key hole slot dimensions
Dimensions (mm)Three phase type PS
170
Reference LengthMGBN4PS 108.0 1 x 4 way
MGBN6PS 162.0 1 x 6 way
MGBN8PS 216.0 2 x 4 way
MGBN12PS 324.0 2 x 6 way
MGBN16PS 432.0 2 x 6 way + 1 x 4 way
MGBN18PS 486.0 3 x 6 way
MGBN24PS 648.0 4 x 6 way
204.2 78.8 6.5
4 Way Assembly
A
A
6 Way Assembly
Leng
thLe
ngth
13.00
89.76
170.70
13.0
0
Fixing holes for M4 screws
183.70
GE
C
F
D
BA
Reference A B C D E F GMGBN4PS 99.58
MGBN6PS 153.52
MGBN8PS 99.52 108.0 99.52
MGBN12PS 153.52 162.0 153.52
MGBN16PS 153.52 162.0 153.52 324.0 99.52
MGBN18PS 153.52 162.0 153.52 324.0 153.52
MGBN24PS 153.52 162.0 153.52 324.0 153.52 486.0 153.52
Dimensions (mm)Three phase type EV
171
Part No. A BMGBN4EV 325 346
MGBN6EV 400 421
MGBN8EV 450 471
MGBN12EV 550 571
MGBN16EV 650 671
MGBN18EV 725 746
MGBN24EV 875 896
87.00 21.60
Inside of cover35
0.00
Dimension A
250.
00
Incoming device cut-out centre
87.00
125A 152.00250A
Dimension B
106.
86
Dimensions (mm)
172
C60 RCBO
TM C60 auxiliaries
OF, SD, OF+SD/OF, MX, MN auxiliaries for C60H, C60H RCBOs
C60/RMG/MGV/DPN/DPN+Vigi
B
G
F
E
D
A
45
C60+any code Miniature circuit breakers 1,2,3,4 70 18 36 54 72 60 44 76 81RMG+any code Residual current devices 2,4 69 36 72 60 44 76 81MGV+any code Vigi rcd for C60H MCBs 70 36 72 60 44 75 81DPN 1Ph+N MCB 1 70 18 60 44 75 81DPN+Vigi 1Ph+N RCBO 2 36 60 44 75 81
Part No. Description Width A B B B B D E F Gin 18mm 1P 2P 3P 4PSP ways
Dimensions (mm)C120 and Vigi circuit breakers
173
Miniature circuit breakers
Vigi
OF, SD, OF+SD/OF, MX, MN auxiliaries
Terminal shield Screw shield Inter-pole barriers Plug in base
Tm C120 auxiliaries
Dimensions (mm)TMC60 auxiliaries and C60H RCBO
174
TM C60 auxiliaries
C60H RCBO
Dimensions (mm)P25M circuit breakers
Vigi circuit breakers
175
P25M circuit breaker OF, MX, MN auxiliaries Limiter block
Insulated enclosure
DPN and DPN N circuit breakers DPN vigi and DPN n vigi circuit breakers
Vigi circuit breakers
Dimensions (mm)NG125 circuit breakers
176
NG125 circuit breakers Screw shield
80mm Min.300m Max. 75
75
Rotary handle Terminal shield
Distribloc MN, MX, OF and SD
Dimensions (mm)NG125 Vigi
177
NG125 Vigi circuit breakers
Screw shield
Dimensions (mm)Local control
178
Bell and safety transformers
V indicator lights BP pushbuttons10
CM selector switches
15213, 15216 15212, 15218, 15219, 15220, 15222
SO bell and RO buzzer
20 and 32A 40 - 125A
NO, NF auxiliaries
I switch disconnectors
15320, 15321, 15322, 15323
179
Dimensions (mm)Local control
PF8, PF30 and PF30r
PRD
PF65r
XB device holder
180
Dimensions (mm)Remote control
16/25A contactors
40/63A contactors
100A contactors
4P3P
16/25A contactors
40/63A contactors
CT contactors with manual operating mechanism
181
Dimensions (mm)Remote control
ACTo+f, ACTt and ACTp
Add-on auxiliaries
RLI changeover relay RBN low level relay
ERL extension
Relays and extensions
TL and ETL extensions
Impulse relays
ATLc+s add-on auxiliaries
Impulse relays
RT, etc. time delay relays
182
Dimensions (mm)Time management
IH time switch 24 hours IH time switch 60 min, 24h, 24h+7d, 7d
Time switches
15720, 15721, 15722, 15723
IHP programmable time switches
ITM multifunction time switch
183
Dimensions (mm)Lighting management
MIN timers 15231, 15232, 15363 and PRE timer 15233
Timer and switch off warning
IC200 IC2000 IC2000P
IC200, IC2000 and IC2000P
Front face and wall mounted cells
IC light sensitive switches
CE
CDM and CE30 movement detection control switches
CDP, CDPt and TDP
CDP, CDPt TDP
CDM
184
Dimensions (mm)Metering and measurement
53
90
CE and CEr kilowatt hour meters CI/CH counters
ME3, ME4 watt hour meters ME1 watt hour meters
Digital VLT and AMP Analogue VLT and AMP
CMA and CMV CME
PM9 multimeter
PowerLogic:Power meter series PM700
185
Front panel mounting
PowerLogic:Power meter series PM700
186
Series PM700 dimensions
187
Dimensions (mm)Metering and measurement
16500 - 16506 and 16541 - 16456 16509 - 16515 and 16459 - 16465
16518 - 16521 and 16468 - 16471 16523 - 16524 and 16473 - 16474
16526 - 16535 and 16476 - 16483 16537 - 16538
16540 - 16544 16545 - 16547
16548 - 16549
188
Dimensions (mm)Heating management
Ambient temp probe (15846) Outdoor temp probe (15847)
44 292553
61
59
17
TH3 thermostat TH6 thermostat
TH thermostats
189
Dimensions (mm)Enclosures, Mini Opale, G9
Mini Opale enclosures Part No. H W D A B E13392 130 44 57 36 65 1113394 130 80 57 72 65 1113396 160 119 65 108 80 1913398 160 155 65 151 80 19
E
44
B
BA
W
H
D
G9 enclosures
Part No. A14599 7214603 9920
20
50.5 50.5
25 50 25
32.5 36 32.5
27.5
27.5
514599/14603 99560
A122.5
46 210
63
77
77
46
101
200
63
190
Dimensions (mm)Weatherproof Kaedra IP65
70
111.5
200
L
Front view
Wall mounting4 modules
Side view
43.5
35.5
3.5 ø22.8
18.5
Position of DIN rail
41.5
47.5
39.3
140
=A
= ==
30
8 and 12 modules
140
==
30
Number of A Lmodules4 - 1238 88 19512 160 267
191
Dimensions (mm)Pragma C IP40 enclosures
Number of ranges A H1 10901/10911 105 2502 10902/10912 230 3753 10903/10913 455 5004 10904/10914 610 752
275
234105
270
135
150
7070
125
118
25
230
24
47.5
72
53.5
59.5
65.5
78
84
90
250
35
32
25
20
16
65
42
A
216
H46
136
125
115
252
125
752
125
136
275
65
65
43
35353535
192
Dimensions (mm)UT enclosures IP54
F
G
36
P
42
ø10
ø9
M3
12
1345
249 24
P1
P2
P3
N1
Q1
15
25
B
A
L
2525
2545I
QM
45
4545
K
N
H
J
D
25C
100
100
N2
Q2
N3
Q3
Encl.ref.
Weight(kg)
Ext. dimensions (mm)
H W D
Internal area
A B
Useable area ondoor
C D
Cable space* 2 Gland plates
F G
Wall fixings
I J K M
Chassisfixings
N Q
04583
04584
04585
04586
04587
04588
04590
3
6.5
9.5
10
15
20
35
300
400
500
600
700
800
1000
250
300
400
400
500
600
800
150
200
200
200
200
250
250
205
255
355
355
455
555
755
255
355
455
555
655
755
955
150
200
300
300
400
500
700
240
340
440
540
640
740
940
180
216
315
315
315
315
315*
62
62
120
120
120
120
120*
200
250
350
350
450
550
750
250
350
450
550
650
750
950
308
358
458
458
558
658
858
358
458
558
658
758
858
1058
175
225
325
325
425
525
725
235
325
425
525
625
725
925
Encl.ref.
Available depth
P1 P2 P3 N1 Q1 N2 Q2 N3 Q3
Chassis and mounting plates
04583
04584
04585
04586
04587
04588
04590
104
164
164
164
164
224
224
95
155
155
155
155
215
215
89
149
149
149
149
179
179
235
335
335
435
535
735
340
440
540
640
740
940
194
254
344
344
434
534
734
229
334
442
547
647
747
937
200
250
350
350
450
550
750
250
350
450
550
650
750
950
193
Dimensions (mm)Prisma GK IP55
EnclosureNumber of modules H1 A B7 425 375 47511 625 575 67515 825 775 87519 1025 975 107523 1225 1175 127527 1425 1375 147533 1725 1675 1775
25
DoorsNumber of modules C D E H7 420 - 284 45011 620 200 484 65015 820 400 684 85019 1020 600 884 105023 1220 800 1084 125027 1420 - 1284 145033 1720 - 1584 1750
450
25
575
25
H1
M6
525
650
A
M8 ø12
25
25
B
600
68
68
55
60
570
30
230260
E C H
=
=CE H
68
68 320/570
600
420
420
320/570
600
60
95
D
210
7 modules
11 - 23 modules
194
Dimensions (mm)Pragma C IP55 enclosures
Adjustable DIN rail height within the enclosure
285
148.5
125
2.1
46
H
216127.5
47
26
ø30
230
A
62.5
16759.5
X2
X1
20
35 3 x 29
8 x ø23
4 x ø29
125
148.5
70
285
39
47.5
39
72
Number of ranges A H1 10941 150 2792 10942 275 4043 10943 400 5294 10944 525 654
X1 = 47.5X2 = 71.5
195
Dimensions (mm)UP IP66 enclosures
Part No.
02504/02514
02505/02515
02506/02516
02507/02517
02508/02518
H
400
500
600
700
800
L
300
400
400
500
600
P
200
200
250
300
300
J
375
475
575
675
775
K
150
250
250
350
450
A
325
425
525
625
725
I
225
325
325
425
525
F
380
480
580
680
780
G
260
360
360
460
560
C
137
112
170
145
195
K
PLG
I
ø8
M
H J
M8
FA
196
Schneider Electric Overview Section nine
197
Schneider ElectricAn overview
198
Schneider Electric operates the largest, dedicated sales force in the UKelectrical industry.
Sales engineers have specialist expertise and an understanding of the customer needswithin each of the following market sectors:
Building systems and solutions
Industrial systems and solutions
Energy and infrastructure systems andsolutions
Schneider Electrics expertise is founded on itsthree international brands – Merlin Gerin, Square Dand Telemecanique.
With over 100 years experience in the electrical industry,Schneider Electric has established itself as a world and UK leaderin the supply and manufacture of products for the distribution,monitoring and control of electrical power.
Schneider Electric regards its customers as commercial partners,who, like us, demand the highest standards of excellence in termsof products, projects and services.
Schneider Electric is proud to provide the solutions to meet theirneeds.
Schneider ElectricAn overview
Building systems and solutions
199
The real reason for putting technology intobuildings is to simplify tasks, enhance safety andimprove the quality of life.
Schneider Electric knows this and has created attractive,functional products for the residential building sector. Well beingcomfort and entertainment are key concepts in this area.
Related industries
Retail
Education
Health
Entertainment centres
Offices
Warehouses
Agriculture
Factory
Private residential
Public residential
Principal customers in the construction market
Contracting authorities
Main contractors
Building engineers
Schneider Electric means greater comfort, lower operating costs and enhanced safety.
The same objectives apply to commercial buildings such asoffices, hotels, shopping centres, hospitals, schools and carefacilities for the elderly.
Schneider Electric offer a wide range of solutions in the area ofbuilding management services and uses its expertise in all ofthese buildings to protect people and equipment.
Schneider ElectricAn overviewIndustrial systems and solutions
200
Across a wide range of applications including:
Conveyors
Packaging
Materials handling
Hoisting
Schneider Electric focus on performance in all areas of industry.
Our products and services adapt to each specific business and environment, fromdiscrete manufacturing and production lines to continuous processes in a wide variety ofindustries such as:
Automotive
Food and beverage
Pharmaceuticals
Construction materials
Waste management
Schneider ElectricAn overview
Energy infrastructure systems and solutions
201
Key markets
Electricity distribution
Water
Rail
Airports
Seaports
Defence
Gas
Telecommunications
Road
Schneider Electric is involved in the entire electrical distribution chainfrom power plants to end users. Customer demand for completeavailability, uncompromising quality and absolute safety has made thesearch for excellence our key mission.
Today, electrical substation and network protection, monitoring and control are highlyeffective in reducing outage time.
Proven technologies offer a wide range of simple, efficient and flexible solutions foroptimised, step by step investments.
Infrastructure
Schneider Electric is involved in developing infrastructure andtransportation systems around the world. In areas where nofailures can be tolerated, such as road and rail equipment,harbour installations and airports, Schneider Electric providessolutions in electrical distribution, control and monitoring,automation and supervision.
Principal customers in the electric power market
Power suppliers involved in generation and distribution
Utility companies
Major contractors
Large end user sites
Government departments
Schneider ElectricAn overviewProjects & Services - delivering tailored solutions for your business
202
We provide solutions enabling you to reduce the totalcost and lifetime ownership risk of your electricaldistribution and automation systems, whilst fulfiling yourongoing quality, safety and environmental obligations.
co
nsultation
trai
ning
mode r n i s a t i o n
o p e r a t i o n
implemen
tati
on
design
Choice of servicesOur services aim to add value to each project phase, butthe choice of services you use is entirely yours. You maywant a full set of services that together provide a packageof support covering the entire lifecycle of your project, oryou can select a combination of services to complementyour resources or knowledge.If you are not sure of what you need, our consultationservices will help you to define the parameters of yoursolution.
ConsultationThese services provide you with an assured way to roadmap your project. We take your ideas and requirementsand apply our wide range of application experience andtechnical competence to produce conceptual designs andindicative costings.
DesignUsing the analysis from the consultation phase, orinformation that you may provide, the design phase selectsthe most suitable equipment and provides detaileddrawings and technical specifications.
ImplementationThis is often the most time-pressured stage of a projectwhen schedules demand fast implementation andcommissioning. These services provide high qualityinstallation and commissioning, preceded by thoroughpreparation.
OperationEfficient operation is vital to derive the best value from yourinvestment. These services ensure that installations achievethe highest operational efficiency and are cost effectivelymaintained with minimum downtime.
ModernisationFaulty or ageing equipment can be refurbished andrepaired if this is the most cost effective action.
TrainingA wide range of training services are available includingproduct standards and legislation. Each is regularlyupdated to stay current with the latest technology. Trainingcan be delivered at a Schneider Electric training facility, orat a customer’s own site.
Pro
jects & Services
Comprehensive quick reference index Section ten
203
NoteFor items without a page number please see MGD5336*This contains information on MCCB connection systems 15 - 2000A. Please visit www.schneider.co.uk to downloadthe relevant information.
*This reference will change after October 2005 to MGLV5751
BP
C60HB101
C60HB102
C60HB104
C60HB106
C60HB110
C60HB116
C60HB120
C60HB125
C60HB132
C60HB140
C60HB150
C60HB163
C60HB201
C60HB202
C60HB204
C60HB206
C60HB210
C60HB216
C60HB220
C60HB225
C60HB232
C60HB240
C60HB250
C60HB263
C60HB301
C60HB302
C60HB304
C60HB306
C60HB310
C60HB316
C60HB320
C60HB325
C60HB332
C60HB340
C60HB350
C60HB363
C60HB401
C60HB402
C60HB404
C60HB406
C60HB410
C60HB416
C60HB420
C60HB425
C60HB432
C60HB440
C60HB450
C60HB463
C60HC101
C60HC102
C60HC104
C60HC106
C60HC10R100
C60HC10R30
C60HC10RA30
C60HC110
C60HC116
C60HC120
C60HC125
C60HC132
C60HC140
C60HC150
C60HC163
C60HC16R100
C60HC16R30
C60HC16RA30
C60HC201
C60HC202
C60HC204
C60HC206
C60HC20R100
C60HC20R30
C60HC20RA30
C60HC210
C60HC216
C60HC220
C60HC225
C60HC232
C60HC240
C60HC250
C60HC263
C60HC301
IndexBy part number
204
5 blanking plates
1P 1A mcb type B
1P 2A mcb type B
1P 4A mcb type B
1P 6A mcb type B
1P 10A mcb type B
1P 16A mcb type B
1P 20A mcb type B
1P 25A mcb type B
1P 32A mcb type B
1P 40A mcb type B
1P 50A mcb type B
1P 63A mcb type B
2P 1A mcb type B
2P 2A mcb type B
2P 4A mcb type B
2P 6A mcb type B
2P 10A mcb type B
2P 16A mcb type B
2P 20A mcb type B
2P 25A mcb type B
2P 32A mcb type B
2P 40A mcb type B
2P 50A mcb type B
2P 63A mcb type B
3P 1A mcb type B
3P 2A mcb type B
3P 4A mcb type B
3P 6A mcb type B
3P 10A mcb type B
3P 16A mcb type B
3P 20A mcb type B
3P 25A mcb type B
3P 32A mcb type B
3P 40A mcb type B
3P 50A mcb type B
3P 63A mcb type B
4P 1A mcb type B
4P 2A mcb type B
4P 4A mcb type B
4P 6A mcb type B
4P 10A mcb type B
4P 16A mcb type B
4P 20A mcb type B
4P 25A mcb type B
4P 32A mcb type B
4P 40A mcb type B
4P 50A mcb type B
4P 63A mcb type B
1P 1A mcb type C
1P 2A mcb type C
1P 4A mcb type C
1P 6A mcb type C
RCBO 10A 100MA Type C
RCBO 10A 30MA Type C
RCBO 10A 30mA Class A Type C
1P 10A mcb type C
1P 16A mcb type C
1P 20A mcb type C
1P 25A mcb type C
1P 32A mcb type C
1P 40A mcb type C
1P 50A mcb type C
1P 63A mcb type C
RCBO 16A 100MA TypeC
RCBO 16A 30MA Type C
RCBO 16A 30mA Class A Type C
2P 1A mcb type C
2P 2A mcb type C
2P 4A mcb type C
2P 6A mcb type C
RCBO 20A 100MA Type C
RCBO 20A 30MA Type C
RCBO 20A 30mA Class A Type C
2P 10A mcb type C
2P 16A mcb type C
2P 20A mcb type C
2P 25A mcb type C
2P 32A mcb type C
2P 40A mcb type C
2P 50A mcb type C
2P 63A mcb type C
3P 1A mcb type C
Part
11,18
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
24
24
24
22
22
22
22
22
22
22
22
24
24
24
22
22
22
22
24
24
24
22
22
22
22
22
22
22
22
22
Page No.Description
C60HC302
C60HC304
C60HC306
C60HC310
C60HC316
C60HC320
C60HC325
C60HC32R100
C60HC32R30
C60HC32RA30
C60HC332
C60HC340
C60HC350
C60HC363
C60HC45R100
C60HC45R30
C60HC45RA30
C60HC6R100
C60HC6R30
C60HD101
C60HD102
C60HD104
C60HD106
C60HD110
C60HD116
C60HD120
C60HD125
C60HD132
C60HD140
C60HD150
C60HD163
C60HD201
C60HD202
C60HD204
C60HD206
C60HD210
C60HD216
C60HD220
C60HD225
C60HD232
C60HD240
C60HD250
C60HD263
C60HD301
C60HD302
C60HD304
C60HD306
C60HD310
C60HD316
C60HD320
C60HD325
C60HD332
C60HD340
C60HD350
C60HD363
MBBN24C
MG125SPEV
MG12EE
MG16C14
MG16C14T
MG16CEM4
MG16CEX4
MG18EE
MG24EE
MG250SPEV
MG25C2
MG25C2M
MG25C4
MG25C4M
MG25EXC
MG25FCC2
MG25FCC4
MG2C13
MG2C250FS
MG2C5
MG2C7
MG2C9
MG36EE
MG48EE
MG54EE
MG64M
MG66M
MG6C12
3P 2A mcb type C
3P 4A mcb type C
3P 6A mcb type C
3P 10A mcb type C
3P 16A mcb type C
3P 20A mcb type C
3P 25A mcb type C
RCBO 32A 100mA Type C
RCBO 32A 30mA Type C
RCBO 32A 30mA Class A Type C
3P 32A mcb type C
3P 40A mcb type C
3P 50A mcb type C
3P 63A mcb type C
RCBO 45A 100mA Type C
RCBO 45A 30mA Type C
RCBO 45A 30mA Class A Type C
RCBO 6A 100mA Type C
RCBO 6A 30mA Type C
1P 1A mcb type D
1P 2A mcb type C
1P 4A mcb type C
1P 6A mcb type C
1P 10A mcb type C
1P 16A mcb type C
1P 20A mcb type C
1P 25A mcb type C
1P 32A mcb type C
1P 40A mcb type C
1P 50A mcb type C
1P 63A mcb type C
2P 1A mcb type C
2P 2A MCB
2P 4A MCB
2P 6A MCB
2P 10A MCB
2P 16A MCB
2P 20A MCB
2P 25A MCB
2P 32A MCB
2P 40A MCB
2P 50A MCB
2P 63A MCB
3P 1A MCB
3P 2A MCB
3P 4A MCB
3P 6A MCB
3P 10A MCB
3P 16A MCB
3P 20A MCB
3P 25A MCB
3P 32A MCB
3P 40A MCB
3P 50A MCB
3P 63A MCB
Door and cover for MGB24N
125A single phasing kit
12 way extra earth bar
Powerpact 4 1600A 14 way Panelboard
Powerpact 4 1600A 14 way Panelboard- top entry
Powerpact 4 side extension panel 400W
Powerpact 4 side extension panel 400W with metering facility
18 way extra earth bar
24 way extra earth bar
250A single phasing kit
Powerboard 250A 9 SP ways
Powerboard 250A 9 SP ways with metering facility
Powerboard 250A 13 SP ways
Powerboard 250A 13 SP ways with metering facility
Panelboard extension box for MG25P2
Powerpact 4 door & cover 9 way
Powerpact 4 door & cover 13 way
Panelboard 250A 13 way
Powerpact 4 fuse incomer for 250A
Panelboard 250A 5 way
Panelboard 250A 7 way
Panelboard 250A 9 way
36 way extra earth bar
48 way extra earth bar
54 way extra earth bar
Powerpact 4 400A metering kit
Powerpact 4 630A metering kit
Panelboard 630A 36 SP ways
22
22
22
22
22
22
22
24
24
24
22
22
22
22
24
24
24
24
24
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
20
19
16
16
16
19
16
16
16
Part Page No.Description
MG6C18
MG6C6
MG6CEX
MG6FCC12
MG6FCC18
MG6FCC6
MG6PAC12
MG6PAC18
MG6PAC24
MG6PAC30
MG6PAC6
MG6PACN
MG6PAFC12
MG6PAFC18
MG6PAFC6
MG6PANKIT
MG72EE
MG88M
MG8C12
MG8C12T
MG8C18
MG8C18T
MG8C6
MG8C6T
MG8FCC12
MG8FCC18
MG8FCC6
MG8PAC12
MG8PAC18
MG8PAC24
MG8PAC30
MG8PAC6
MG8PACN3
MG8PACN4
MG8PANKIT
MGACE
MGALK
MGAN1010MS
MGAN12
MGAN1228MS
MGAN126MS
MGAN12C
MGAN12FK
MGAN12P
MGAN12PS
MGAN15
MGAN15C
MGAN15FK
MGAN15P
MGAN15PS
MGAN23
MGAN23C
MGAN24FK
MGAN416MS
MGAN46DS
MGAN46SL
MGAN48SL
MGAN520MS
MGAN6
MGAN66DS
MGAN66SL
MGAN6C
MGAN6FK
MGAN6P
MGAN6PS
MGAN716MS
MGAN76DS
MGAN9
MGAN912MS
MGAN96MS
MGAN9C
MGAN9FK
MGAN9P
MGAN9PS
MGANWL
MGBGPEXN
MGBL
MGBN100CCI
MGBN12
MGBN12C
MGBN12E
MGBN12HDGK
MGBN12P
Panelboard 630A 54 SP ways
Panelboard 630A 18 SP ways
Panelboard top/bott 200mm extension
Cover 630A 36 way panelboard
Cover 630A 54 way panelboard
Cover 630A 18 way panelboard
Outgoing pan assembly 630A 36 SP ways
Outgoing pan assembly 630A 54 SP ways
Outgoing pan assembly 630A 72 SP ways
Outgoing pan assembly 630A 90 SP ways
Outgoing pan assembly 630A 18 SP ways
Incoming pan assembly 630A
Cover 630/800A 36 way pan assembly
Cover 630/800A 54 way pan assembly
Cover 630/800A 18 way pan assembly
18 way neutral bar kit 630A
72 way extra earth bar
Powerpact 4 800A metering kit
Panelboard 800A 12 way
Panelboard 800A 12 way top entry
Panelboard 800A 18 way
Panelboard 800A 18 way top entry
Panelboard 800A 6 way
Panelboard 800A 6 way top entry
Cover for 800A 36 way panelboard
Cover for 800A 54 way panelboard
Cover for 800A 18 way panelboard
Outgoing pan assembly 800A 36 SP ways
Outgoing pan assembly 800A 54 SP ways
Outgoing pan assembly 800A 72 SP ways
Outgoing pan assembly 800A 90 SP ways
Outgoing pan assembly 800A 18 SP ways
Incoming pan assembly NS800 3P
Incoming pan assembly NS800 4P
18 way neutral bar kit 800A
Clean earth kit A
M4 & M6 Allen key kit
10 way + 5 SP way DIN rail dist. board
12 way SP Distribution Board
12 way+14 SP way DIN rail dist. board
12 way + 3 SP way DIN rail dist. board
Door and cover for MGA12N
Flush mounting kit for A type
A board replacement pan ass 12 way
pan ass 12 way SP&N black sliders
15 way SP Distribution Board
Door and cover for MGA15N
Flush mounting kit for A type
A board replacement pan ass 15 way
pan ass 15 way SP&N black sliders
23 way SP Distribution Board
Door and cover for MGA23N
Flush mounting kit for A type
4 way + 8 SP way DIN rail dist. board
4 way cir/t A, 6 way cir/t B dist. board
4+6 way SP&N split load dist. board
4+8 way SP&N split load dist. board
5 way + 10 SP way DIN rail dist. board
6 way SP Distribution Board
6 way cir/t A, 6 way cir/t B dist. board
6+6 way SP&N split load dist. board
Door and cover for MGA6N
Flush mounting kit for A type
A board replacement pan ass 6 way
pan ass 6 way SP&N black sliders
7 way + 8 SP way DIN rail dist. board
7 way cir/t A, 6 way cir/t B dist. board
9 way SP Distribution Board
9 way + 6 SP way DIN rail dist. board
9 way + 3 SP way DIN rail dist. board
Door and cover for MGA9N
Flush mounting kit for A type
A board replacement pan ass 9 way
pan ass 9 way SP&N black sliders
A board spare labels
Gland plate for Isobar 4 extension box
Key lock for new Isobar door catch
Isobar 4 contactor incomer kit
12 way TP Distribution Board
Doo and cover for MGB12N
pan ass 12 way TP+ earth and neutral on mtg. plate
12 way IP55 type B heavy duty dist board
B board replacement pan ass 12 way
Part Description
MGBN12PE
MGBN12PS
MGBN12SXP
MGBN12SXS
MGBN16
MGBN16C
MGBN16E
MGBN16HDGK
MGBN16P
MGBN16PE
MGBN16PS
MGBN16SXP
MGBN16SXS
MGBN18
MGBN18C
MGBN18E
MGBN18P
MGBN18PS
MGBN24
MGBN24E
MGBN24P
MGBN24PE
MGBN24PS
MGBN24SXP
MGBN24SXS
MGBN4
MGBN4C
MGBN4E
MGBN4P
MGBN4PS
MGBN4SXP
MGBN4SXS
MGBN6
MGBN6C
MGBN6E
MGBN6HDGK
MGBN6P
MGBN6PE
MGBN6PS
MGBN8
MGBN8C
MGBN8E
MGBN8HDGK
MGBN8P
MGBN8PE
MGBN8PS
MGBN8SXP
MGBN8SXS
MGBNBCE25
MGBNBCE7
MGBNEX034N
MGBNEXA15N
MGBNEXN
MGBNGPN
MGBNKWH
MGBNSJK
MGBNTJKN
MGBNWL
MGE0632C
MGE0633C
MGE0634C
MGE0634EC
MGE1002C
MGE1003C
MGE1003SC
MGE1004C
MGE1004EC
MGE1004SC
MGE1004SEC
MGE1252C
MGE1253C
MGE1254C
MGE1254EC
MGE1602C
MGE1603C
MGE1603SC
MGE1604C
MGE1604EC
MGE1604SC
MGE1604SEC
MGE2003C
MGE2004C
MGE2004EC
pan ass 12 way TP+ E and N on mtg. plate
pan ass 12 way TP&N black sliders
51 SP way steel encl plain front cover
51 SP way steel enclslotted front cover
16 way TP Distribution Board
Door and cover for MGB16N
pan ass 16 way TP+ earth and neutral on mtg. plate
16 way IP55 type B heavy duty dist board
B board replacement pan ass 16 way
pan ass 16 way TP+ E and N on mtg. plate
pan ass 16 way TP&N black sliders
68 SP way steel encl plain front cover
68 way steel enclslotted front cover
18 way TP&N metal distribution board
Door and cover for MGB18N
pan ass 18 way TP+ earth and neutral on mtg. plate
B board replacement pan ass 18 way
pan ass 18 way TP&N black sliders
24 way TP Distribution Board
pan ass 24 way TP+ earth and neutral on mtg. plate
B board replacement pan ass 24 way
pan ass 24 way TP+ E and N on mtg. plate
pan ass 24 way TP&N black sliders
85 SP way steel encl plain front cover
85 SP way steel enclslotted front cover
4 way TP Distribution Board
Door and cover for MGB4N
pan ass 4 way TP+ earth and neutral on mtg. plate
B board replacement pan ass 4 way
pan ass 4 way TP&N black sliders
34 SP way steel encl plain front cover
34 SP way steel enclslotted front cover
6 way TP Distribution Board
Doo and cover for MGB6N
pan ass 6 way TP+ earth and neutral on mtg. plate
6 way IP55 type B heavy duty dist board
B board replacement pan ass 6 way
pan ass 6 way TP+ E and N on mtg. plate
pan ass 6 way TP&N black sliders
8 way TP Distribution Board
Door and cover for MGB8N
pan ass 8 way TP+ earth and neutral on mtg. plate
8 way IP55 type B heavy duty dist board
B board replacement pan ass 8 way
pan ass 8 way TP+ E and N on mtg. plate
pan ass 8 way TP&N black sliders
34 SP way steel encl plain front cover
34 SP way steel enclslotted front cover
Spare earth/clean earth B boards
Spare earth/clean earth B boards
34 way mod extension box
15 way SP&N extension box
Type B board extension box + plain cover
Isobar 4 B board top/bottom gland plate
Kilowatt Hour Metering kit for MG B
Side joining kit
Joining kit B board top/bottom
B board self labels
Enclosed MCCB 63A 2P
Enclosed MCCB 63A 3P
Enclosed MCCB 63A 4P
Enclosed MCCB 63A 4P + earth fault
Enclosed MCCB 100A 2P
Enclosed MCCB 100A 3P
Enclosed switch disconnector 100A 3P
Enclosed MCCB 100A 4P
Enc MCCB 100A 4P + earth fault
Enc switch disconnector 100A 4P
Enclosed switch 100A 4P + earth fault
Enclosed MCCB 125A 2P
Enclosed MCCB 125A 3P
Enclosed MCCB 125A 4P
Enclosed switch 125A 4P + earth fault
Enclosed MCCB 160A 2P
Enclosed MCCB 160A 3P
Enclosed switch 160A 3P
Enclosed MCCB 160A 4P
Enc MCCB 160A 4P + earth fault
Enclosed switch 160A 4P
Enclosed switch 160A 4P + earth fault
Enclosed MCCB 200A 3P
Enclosed MCCB 200A 4P
Enclosed MCCB 200A 4P + earth fault
Part Description
IndexBy part number
205
12,19
11
11
9
8
9
9
20
11
20
114
8
20
11
20
114
8
20
11
9
9
8
8
9
8
9
8
20
11
20
114
9
9
8
9
9
20
11
20
114
11
18
11,15,18,124
17
12
20
115
13
20
115
114
16,125
16,125
12
20
115
13
20
115
114
16,125
16,125
12
20
115
20
114
12
115
20
115
114
16,125
16,125
12
20
115
20
114
16,125
16,125
12
20
115
13
20
115
114
12
20
115
13
20
115
114
16,125
16,125
19
19
17
17
17
18
17
12,19
12,19
18
Page No. Page No.
MGE2503C
MGE2503SC
MGE2504C
MGE2504EC
MGE2504SC
MGE2504SEC
MGE4003C
MGE4003SC
MGE4004C
MGE4004EC
MGE4004SC
MGE4004SEC
MGE6303C
MGE6303SC
MGE6304C
MGE6304EC
MGE6304SC
MGE6304SEC
MGES063
MGES063R
MGES100
MGES100R
MGES160
MGES160R
MGES250
MGES250R
MGES320
MGES320R
MGES400
MGES400R
MGES500
MGES500R
MGES630
MGES630R
MGEX160C
MGEX250C
MGEX630C
MGFA0201C
MGFA0203C
MGFA0321C
MGFA0323C
MGFA0631C
MGFA0633C
MGFA1001C
MGFA1003C
MGFB20007C
MGFB20012C
MGFB20018C
MGFB40007C
MGFB40012C
MGFB40018C
MGFB63007C
MGFB63012C
MGFB63018C
MGFC200
MGFC400
MGFC630
MGFD1003C
MGFD1603C
MGFD2503C
MGFD4003C
MGFD5003C
MGFD6303C
MGFK200
MGFK400
MGFK630
MGFL0201C
MGFL0203C
MGFL0321C
MGFL0323C
MGFL0631C
MGFL0633C
MGFL1001C
MGFL1003C
MGFQ100
MGFQ160
MGFQ250
MGFQ400
MGFQ630
MGFS1003C
MGFS1603C
MGFS2003C
MGFS2503C
IndexBy part number
206
Enclosed MCCB 250A 3P
Enclosed switch 250A 3P
Enclosed MCCB 250A 4P
Enclosed MCCB 250A 4P + earth fault
Enclosed switch 250A 4P
Enclosed switch 250A 4P + earth fault
Enclosed MCCB 400A 3P
Enclosed switch 400A 3P
Enclosed MCCB 400A 4P
Enclosed MCCB 400A 4P + earth fault
Enclosed switch 400A 4P
Enclosed switch 400A 4P + earth fault
Enclosed MCCB 630A 3P
Enclosed switch 630A 3P
Enclosed MCCB 630A 4P
Enclosed MCCB 630A 4P + earth fault
Enclosed switch 630A 4P
Enclosed switch 630A 4P + earth fault
Enclosed Interpact 63A
Enclosed Interpact 63A red/yellow handle
Enclosed Interpact 100A
Enclosed Interpact 100A red/yellow handle
Enclosed Interpact 160A
Enclosed Interpact 160A red/yellow handle
Enclosed Interpact 250A
Enclosed Interpact 250A red/yellow handle
Enclosed Interpact 320A
Enclosed Interpact 320A red/yellow handle
Enclosed Interpact 400A
Enclosed Interpact 400A red/yellow handle
Enclosed Interpact 500A
Enclosed Interpact 500A red/yellow handle
Enclosed Interpact 630A
Enclosed Interpact 630A red/yellow handle
Safepact extension 100mm 63 - 250A
Safepact extension 200mm 63 - 250A
Safepact extension 200mm 630A
Switch disconnector fuse 20A SP&SwN
Switch disconnector fuse 20A TP&N
Switch disconnector fuse 32A SP&SwN
Switch disconnector fuse 32A TP&N
Switch disconnector fuse 63A SP&SwN
Switch disconnector fuse 63A TP&N
Switch disconnector fuse 100A SP&SwN
Switch disconnector fuse 100A TP&N
Busbar chamber 200A 750mm
Busbar chamber 200A 1200mm
Busbar chamber 200A 1800mm
Busbar chamber 400A 750mm
Busbar chamber 400A 1200mm
Busbar chamber 400A 1800mm
Busbar chamber 630A 750mm
Busbar chamber 630A 1200mm
Busbar chamber 630A 1800mm
Busbar cable connection kit 200A
Busbar cable connection kit 400A
Busbar cable connection kit 630A
Switch disconnector 100A TP&N
Switch disconnector 160A TP&N
Switch disconnector 250A TP&N
Switch disconnector 400A TP&N
Switch disconnector 500A TP&N
Switch disconnector# 630A TP&N
Busbar interconnection kit 200A
Busbar interconnection kit 400A
Busbar interconnection kit 630A
Switch disconnector 20A SP&SwN
Switch disconnector 20A TP&N
Switch disconnector 32A SP&SwN
Switch disconnector 32A TP&N
Switch disconnector 63A SP&SwN
Switch disconnector 63A TP&N
Switch disconnector 100A SP&SwN
Switch disconnector 100A TP&N
Set of 3 copper links 100A
Set of 3 copper links 160A
Set of 3 copper links 250A
Set of 3 copper links 400A
Set of 3 copper links 630A
Fuse switch disconnector 100A TP&N
Fuse switch disconnector 160A TP&N
Fuse switch disconnector 200A TP&N
Fuse switch disconnector 250A TP&N
Part Page No.Description
MGFS3153C
MGFS4003C
MGFS5003C
MGFS6303C
MGFX100C
MGFX160C
MGFX250C
MGFX500C
MGFX630C
MGFZ160
MGFZ250
MGFZ630
MGFZ630T
MGI1252
MGI1253N
MGI1254
MGK33
MGLA
MGLAP
MGN16DE
MGN22DE
MGN28DE
MGN34DE
MGN56DE
MGNA12
MGNA15
MGNA24
MGNA4
MGNA6
MGNA7
MGNA9
MGNB12
MGNB16
MGNB18
MGNB24
MGNB4
MGNB6
MGNB8
MGNCB1004
MGNCB1604
MGNCB2004
MGNCB2504
MGNDSI
MGNI1603
MGNI1604
MGNI160RCCB
MGNI2003
MGNI2004
MGNI2254
MGNI2503
MGNI2504
MGNPBN250TB
MGP0161
MGP0162
MGP0163
MGP0164
MGP0251
MGP0252
MGP0253
MGP0254
MGP0301
MGP0302
MGP0323
MGP0324
MGP0401
MGP0402
MGP0403
MGP0404
MGP0631
MGP0632
MGP0633
MGP0634
MGP0801
MGP0802
MGP0803
MGP0804
MGP1001
MGP1002
MGP1003
MGP1003NA
MGP1004
MGP1004NA
MGP1013
Fuse switch disconnector 315A TP&N
Fuse switch disconnector 400A TP&N
Fuse switch disconnector 500A TP&N
Fuse switch disconnector 630A TP&N
Cable box 100A
Cable box 160A
Cable box 250A
Cable box 315/400/500A
Cable box 630A
Fuse switch connection kit 100, 160A
Fuse switch connection kit 250A
Fuse switch connection 315 - 630A bottom
Fuse switch connection 315 - 630A top
125A 2P switch disconnector
125A 3P switch disconnector
125A 4P switch disconnector
2 keys for distribution board & panelboard
Locking attachment
Padlock for MGLA
16 MOD steel enclosure
22 MOD steel enclosure
28 MOD steel enclosure
34 MOD steel enclosure
56 MOD steel enclosure
Distributed neutral kit
Distributed neutral kit
Distributed neutral kit
Distributed neutral kit
Distributed neutral kit
Distributed neutral kit
Distributed neutral kit
Distributed neutral kit
Distributed neutral kit
Distributed neutral kit
Distributed neutral kit
Distributed neutral kit
Distributed neutral kit
Distributed neutral kit
100A 4P TP&N dist board MCCB incomer
160A 4P TP&N dist board MCCB incomer
200A 4P TP&N dist board MCCB incomer
250A 4P TP&N dist board MCCB incomer
Dual incoming unit for B board
160A 3P+N switch disconnector incomer
160A 4P switch disconnector
160A switch disconnector + earth fault
200A 3P switch disconnector
200A 4P switch disconnector
225A 4P switch disconnector
250A 3P switch disconnector
250A 4P switch disconnector
250A terminal block w/o extension box
Powerpact 4 MCCB 16A 1P
Powerpact 4 MCCB 16A 2P
Powerpact 4 MCCB 16A 3P
Powerpact 4 MCCB 16A 4P
Powerpact 4 MCCB 25A 1P
Powerpact 4 MCCB 25A 2P
Powerpact 4 MCCB 25A 3P
Powerpact 4 MCCB 25A 4P
Powerpact 4 MCCB 30A 1P
Powerpact 4 MCCB 30A 2P
Powerpact 4 MCCB 32A 3P
Powerpact 4 MCCB 32A 4P
Powerpact 4 MCCB 40A 1P
Powerpact 4 MCCB 40A 2P
Powerpact 4 MCCB 40A 3P
Powerpact 4 MCCB 40A 4P
Powerpact 4 MCCB 63A 1P
Powerpact 4 MCCB 63A 2P
Powerpact 4 MCCB 63A 3P
Powerpact 4 MCCB 63A 4P
Powerpact 4 MCCB 80A 1P
Powerpact 4 MCCB 80A 2P
Powerpact 4 MCCB 80A 3P
Powerpact 4 MCCB 80A 4P
Powerpact 4 MCCB 100A 1P
Powerpact 4 MCCB 100A 2P
Powerpact 4 MCCB 100A 3P
Powerpact 4 100A 3P switch disconnector
Powerpact 4 MCCB 100A 4P
Powerpact 4 100A 4P switch disconnector
Powerpact 4 MCCB 100A 3P
10
14
14
18
28
28
11, 124
11, 124
11, 124
11, 124
11, 124
11
11
11
11
11
11
11
19
19
19
19
19
19
19
15
15
15
15
15
14
14
14
14
14
14
14
14
X
Part Page No.Description
MGP1014
MGP1251
MGP1252
MGP1253
MGP1254
MGP1601
MGP1602
MGP1603
MGP1603NA
MGP1604
MGP1604NA
MGP2003
MGP2004
MGP2503
MGP2503LL
MGP2503NA
MGP2503NAT
MGP2503T
MGP2504
MGP2504LL
MGP2504NA
MGP2504NAT
MGP2504T
MGP250NL
MGP4003
MGP4003NA
MGP4003NAT
MGP4003T
MGP4004
MGP4004NA
MGP4004NAT
MGP4004T
MGP6303
MGP6303NA
MGP6303NAT
MGP6303T
MGP6304
MGP6304NA
MGP6304NAT
MGP6304T
MGP630NL
MGP8003B5
MGP8003NA
MGP8004B5
MGP8004NA
MGPBB25
MGPBBP
MGPC2025
MGPC2050
MGPC4025
MGPC4050
MGPCH12
MGPCH18
MGPCH6
MGPCM12L
MGPCM12R
MGPCM18L
MGPCM18R
MGPCM6L
MGPCM6R
MGPE0163
MGPE0253
MGPE0403
MGPE0633
MGPE0803
MGPE1003
MGPE1253
MGPGPC8
MGPINC
MGPL
MGPLSK
MGPP4S007
MGPXC206
MGPXC212
MGPXC218
MGPXC506
MGPXC512
MGPXC518
MGPXCA6
MGPXCB12
MGTB1001
MGTB1252
MGTB1254
Powerpact 4 MCCB 100A 4P
Powerpact 4 MCCB 125A 1P
Powerpact 4 MCCB 125A 2P
Powerpact 4 MCCB 125A 3P
Powerpact 4 MCCB 125A 4P
Powerpact 4 MCCB 160A 1P
Powerpact 4 MCCB 160A 2P
Powerpact 4 MCCB 160A 3P
Powerpact 4 160A 3P switch disconnector
Powerpact 4 MCCB 160A 4P
Powerpact 4 160A 4P switch disconnector
Powerpact 4 MCCB 200A 3P
Powerpact 4 MCCB 200A 4P
Powerpact 4 MCCB 250A 3P
Powerpact 4 lug unit 3P
Powerpact 4 250A 3P switch disconnector
Powerpact 4 250A 3P switch disconnector
Powerpact 4 MCCB 250A 3P
Powerpact 4 MCCB 250A 4P
Powerpact 4 lug unit 4P
Powerpact 4 250A 4P switch disconnector
Powerpact 4 250A 4P switch disconnector
Powerpact 4 MCCB 250A 4P
Powerpact 4 neutral link 250A
Powerpact 4 MCCB 400A 3P
Powerpact 4 400A 3P switch disconnector
Powerpact 4 400A 3P switch disconnector
Powerpact 4 MCCB 400A 3P
Powerpact 4 MCCB 400A 4P
Powerpact 4 400A 4P switch disconnector
Powerpact 4 400A 4P switch disconnector
Powerpact 4 MCCB 400A 4P
Powerpact 4 MCCB 630A 3P
Powerpact 4 630A 3P switch disconnector
Powerpact 4 630A 3P switch disconnector
Powerpact 4 MCCB 630A 3P
Powerpact 4 MCCB 630A 4P
Powerpact 4 630A 4P switch disconnector
Powerpact 4 630A 4P switch disconnector
Powerpact 4 MCCB 630A 4P
Powerpact 4 neutral link 630A
Powerpact 4 800A 3P incoming
Powerpact 4 800A 3P switch disconnector
Powerpact 4 800A 4P incoming
Powerpact 4 800A 4P switch disconnector
Powerpact 4 25mm blank plate
Powerpact 4 SP blank plate
PP4 Panelboard corner unit 200H x 250W
PP4 Panelboard corner unit 200H x 500W
PP4 Panelboard corner unit 400H x 250W
PP4 Panelboard corner unit 400H x 500W
Powerpact 4 shrouding kit 12 way
Powerpact 4 shrouding kit 18 way
Powerpact 4 shrouding kit 6 way
12 way left hand metering box
12 way right hand metering box
18 way left hand metering box
18 way right hand metering box
6 way left hand metering box
6 way right hand metering box
Powerpact 4 MCCB 16A 16kA 3P
Powerpact 4 MCCB 25A 16kA 3P
Powerpact 4 MCCB 40A 16kA 3P
Powerpact 4 MCCB 63A 16kA 3P
Powerpact 4 MCCB 80A 16kA 3P
Powerpact 4 MCCB 100A 16kA 3P
Powerpact 4 MCCB 125A 16kA 3P
Gland pl for Powerpact 4 630/800A
Powerpact 4 direct incomer 630A
Padlock with 2 keys
Spare key
Powerpact 4 door lock up to 800A
Powerpact 4 MG6P6 250mm extension
Powerpact 4 MG6P12 250mm extension
Powerpact 4 MG6P18 250mm extension
Powerpact 4 MG6P6 500mm extension
Powerpact 4 MG6P21 500mm extension
Powerpact 4 MG6P18 500mm extension
Powerpact 4 ICDSN unit for 6 way
Panelboard ICDSN unit for 12 way
100A 1P terminal block
125A 2P terminal block
125A 4P terminal block
Part Description
MGTB2504
MGV250102
MGV630302
MGV630304
MGV631002
MGV633002
MGV633004
MSIS95AN
NKIT
PM700
PM700P
PM710
PRGPM
RMG1000302
RMG1001002
RMG1001002S
RMG1003002
RMG160102
RMG250102
RMG250302
RMG250304
RMG253004
RMG400302
RMG400304
RMG403002
RMG403004
RMG630302
RMG630304
RMG631002
RMG631004
RMG633002
RMG633004
RMG800302
RMG801002
RMG803002
2499
2504
2505
2506
2507
2508
2510
2514
2515
2516
2517
2518
2520
2521
2524
2525
2526
2527
2528
2530
2554
2556
2557
2560
4012
4013
4014
4583
4584
4585
4586
4587
4588
4590
4629
5056
5114
5115
5116
5196
5224
5502
5503
5504
5505
5506
5507
5508
250A 4P terminal block
25A 10MA 2P Vigi
63A 30MA 2P Vigi
63A 30MA 4P Vigi
63A 100MA 2P Vigi
63A 300MA 2P Vigi
63A 300MA 4P Vigi
250A Incoming components for MG pan assembley
Pack of 4 neutral links
PowerLogic Meter
PowerLogic Meter
PowerLogic Meter
Gland plate metal
100A 30MA 2P RCD
100A 100MA 2P RCD
2P 100A 100MA
100A 300MA 2P RCD
16A 10MA 2P RCD
25A 10MA 2P
25A 30MA 2P RCD
25A 30MA 4P RCD
25A 300MA 4P RCD
40A 30MA 2P RCB
40A 30MA 4P RCD
40A 300MA 2P RCB
40A 300MA 4P RCD
63A 30MA 2P RCB
63A 30MA 4P RCD
63A 100MA 2P RCB
63A 100MA 4P RCD
63A 300MA 2P RCD
63A 300MA 4P RCD
80A 30MA 2P RCD
80A 100MA 2P RCD
80A 300MA 2P RCD
Aerosol paint - RAL7032
430x330x200mm enclosure and door
530x430x200mm enclosure and door
650x440x250mm enclosure and door
750x540x300mm enclosure and door
850x640x300mm eenclosure and door
1055x850x350mm enclosure and door
430x330x200mm enclosure and door
530x430x200mm enclosure and door
650x440x250mm enclosure and door
750x540x300mm enclosure and door
850x640x300mm enclosure and door
1055x850x350mm enclosure and door
External wall fixing lugs
Chassis for 430mm high enclosure
Chassis for 530mm high enclosure
Chassis for 650mm high enclosure
Chassis for 750mm high enclosure
Chassis for 850mm high enclosure
Chassis for 1055mm high enclosure
Variable sliders for 200mm enclosure
Variable sliders for 250mm enclosure
Variable sliders for 300mm enclosure
Variable sliders for 350mm enclosure
2P 1P+N Multiclip distribution block
3P Multiclip distribution block
4P 3P+1N Multiclip distribution block
Enclosure 300x250x150mm + door
Enclosure 400x300x200mm + door
Enclosure 500x400x200mm + door
Enclosure 600x400x200mm + door
Enclosure 700x500x200mm + door
Enclosure 800x600x250mm + door
Enclosure 1000x800x250mm + door
Enclosure external + lugs
Enc stackable spacers, H=55mm
Enclosure clip-on nuts, M4 (x20)
Enclosure clip-on nuts, M5 (x20)
Enclosure clip-on nuts, M6 (x20)
UT enclosure key lock handle + 2 keys
Enclosure stack spacers,M8,H=50mm
Prisma GK W-M enclosure 7 mod.
Prisma GK W-M enclosure 11 mod.
Prisma GK W-M enclosure 15 mod
Prisma GK W-M enclosure 19 mod
Prisma GK W-M enclosure 23 mod
Prisma GK W-M enclosure 27 mod
Prisma GK W-M enclosure 33 mod
Part Description
IndexBy part number
207
76
76
18
10
15
15
23
23
23
23
23
23
115
11,19,21
43
43
43
127
10,74
74
10,74
74
74
74
74
74
74
74
74
74
74
10,74
10,74
10,74
10,74
10,74
10,74
10,74
10,74
10,74
128
132
132
132
132
132
132
132
132
132
132
132
132
132
132
132
132
132
132
132
132
132
132
132
116
116
116
128
128
128
128
128
128
128
128
138
132
132
132
128
132
129
129
129
129
129
129
129
Page No. Page No.
5532
5533
5534
5535
5536
5537
5538
5542
5543
5544
5545
5546
5547
5548
5557
5580
6619
7046
7802
7803
7804
7805
7806
7813
7814
9211
9214
9218
9219
9220
9224
9228
9231
9234
9238
9239
9240
9244
9248
9251
9252
9253
9254
9255
9257
9263
9264
9265
9266
9268
9917
10901
10902
10903
10904
10911
10912
10913
10914
13392
13394
13396
13398
13429
13430
13441
13442
13443
13444
13512
13514
13575
13576
13577
13578
13579
13581
13582
13583
13584
13585
13586
13587
IndexBy part number
208
Prisma GK plain door 7 mod.
Prisma GK plain door 11 mod.
Prisma GK plain door 15 mod.
Prisma GK plain door 19 mod.
Prisma GK plain door 23 mod.
Prisma GK plain door 27 mod.
Prisma GK plain door 33 mod.
Prisma GK trans. Door 7 mod.
Prisma GK trans. Door 11 mod.
Prisma GK trans. Door 15 mod.
Prisma GK trans. Door 19 mod.
Prisma GK trans. Door 23 mod.
Prisma GK trans. Door 27 mod.
Prisma GK trans. Door 33 mod.
Canopy W600 + hardware
Prisma GK handle + 2 key
5 Pratic adaptors
12x2 mm flat bar, L=461mm
plain front plate 2 mod
Plain front plate, 3 mod
Plain front plate, 4 mod
Plain front plate, 5 mod
Plain front plate, 6 mod
Prisma front plate 3 mods
Prisma front plate 4 mod
Perforated mounting plate 300
Perforated mounting plate 400
Perforated mounting plate 500
Perforated mounting plate 600
Perforated mounting plate 700
Perforated mounting plate 800
Perforated mounting plate 1000
Plain mounting plate 300x200
Plain mounting plate 400x300
Plain mounting plate 500x400
Plain mounting plate 600x400
Plain mounting plate 700x500
Plain mounting plate 800x600
Plain mounting plate 1000x800
Vertical uprights 400 nominal
Vertical uprights 500 nominal
Vertical uprights 600 nominal
Vertical uprights 700 nominal
Vertical uprights 800 nominal
Vertical uprights 1000 nomina
4 Multi fix rails 300 nominal
4 Multi fix rails 400 nominal
4 Multi fix rails 500 nominal
4 Multi fix rails 600 nominal
4 Multi fix rails 800 nominal
Set of screw
1 row Pragma C IP40 + door
2 row Pragma C IP40 + door
3 row Pragma C IP40 + door
4 row Pragma C IP40 + door
1 row Pragma C IP40 + Door
2 row Pragma C IP40 + Door
3 row Pragma C IP40 + Door
4 row Pragma C IP40 + Door
2 SP way Mini Opale enclosure
4 SP way Mini Opale enclosure
6 SP way Mini Opale enclosure
8 SP way Mini Opale enclosure
Blanking/label 10x5 way
Blanking strip 24 way
Kaedra 4 mod ins enclosure IP65
Kaedra 6 mod ins enclosure IP65
Kaedra 8 mod ins enclosure IP65
Kaedra 12 mod ins enclosure IP65
125A 4P multi-stage distribution block
125A 4P multi-stage distribution block
80A, 4 hole strip terminal block
80A terminal bock 8 hole
80A terminal bock 16 hole
80A, 22 hole strip terminal block
80A terminal bock 32 hole
80A terminal bock 32 hole
4/8 hole terminal block yell/gr cover
IP2 cover for terminal block grn
4/8 hole terminal block red cover
IP2 cover for terminal block red
8 hole terminal block blue cover
IP2 cover for block blue 16
Part
129
129
129
129
129
129
129
129
129
129
129
129
129
129
129
129
119
116
129
129
129
129
129
129
129
128,129
128,129
128,129
128,129
128,129
128,129
128,129
128,129
128,129
128,129
128,129
128,129
128,129
128,129
128,129
128,129
128,129
128,129
128,129
128,129
128,129
128,129
128,129
128,129
128,129
128,129
126
126
126
126
126
126
126
126
77,124
77,124
77,124
77,124
127
127
77,131
77,131
77,131
77,131
117
117
126,130,131
126,130,131
126,130,131
126,130,131
126,130,131
126,130,131
131
131
131
131
131
131
Page No.Description
13589
13600
13625
13665
13730
13811
13812
13813
13814
13815
13816
13841
13842
13843
13844
13845
13846
13851
13852
13853
13854
13855
13856
13861
13863
13864
13866
13871
13875
13876
13877
13879
13880
13947
13948
14181
14190
14210
14211
14599
14603
14801
14802
14803
14804
14811
14812
14813
14814
14818
14880
14881
14882
14883
14884
14885
14886
14887
14888
14890
14891
14892
14893
14894
14915
14936
14937
14938
14939
14949
14962
14963
14964
14965
14975
14976
14977
14979
14989
15005
15006
15007
15008
IP2 cover for block blue 16
Sloping terminal block support
Key lock for IP55 pragma c/d
Pragma C enclosure lock + key
Blanking strip grey 10x5 Mod
1 row Pragma metal enclosure
2 row Pragma metal enclosure
3 row Pragma metal enclosure
4 row Pragma enclosure
5 row Pragma enclosure
6 row Pragma enclosure
1 row Pragma enclosure + door
2 row Pragma enclosure + door
3 row Pragma enclosure + door
4 row Pragma enclosure + door
5 row Pragma enclosure + door
6 row Pragma enclosure + door
1 row Pragma enclosure + door
2 row Pragma enclosure + door
3 row Pragma enclosure + door
4 row Pragma enclosure + door
5 row Pragma enclosure + door
6 row Pragma enclosure + door
Interpact mounting/front plate
NS mounting plate & front plate
Pragma slotted mounting plate
Connections to Polybloc
1 row plain front plate
160A connection blocks
Earth/neutral terminal block
Enclosure door lock key No. 405
Label strip 24 pole
Enclosure touch up paint
Kaedra sealing kit
Lock & key for IP65 Mini Pragma
4 wall mounting brackets
Glands for Kaedra
Prisma P window 10 mod
Prisma P DIN rail support 10 mod
4 SP way G9 IP30 steel enclosure
5 SP way G9 IP30 steel enclosure
1P comb busbar, 108x9mm
2P comb busbar, 108x9mm
3P comb busbar, 108x9mm
3P+N comb busbar, 108x9mm
1P comb busbar, 27mm pitch
2P comb busbar, 27mm pitch
3P comb busbar, 27mm pitch
4P comb busbar, 27mm pitch
Comb busbar end and tooth caps
1P+N comb busbar, 26x9mm
1P comb busbar, 24x9mm
2P comb busbar, 24x9mm
3P comb busbar, 24x9mm
4P comb busbar, 24x9mm
4 25mm2 insulated connectors
End caps 1P/2P/1P+N comb x40
End caps 3P/4P/3P+N comb x40
Tooth caps for comb teeth x40
Comb busbar, 1 P + N, 48x9mm
1P comb busbar (x2) 48x9mm
2P comb busbar 2x48mm
3P comb busbar (x2) 48x9mm
4P comb busbar (x2) 48x9mm
Symm/asym rail stops(x10)
1P terminal block
2P terminal block
1P terminal block
2P terminal block
140A 12 hole stepped terminals
80A 4 hole connection strip
80A 7 hole connection strip
80A 11 hole connection strip
125A,14 hole connection strip
80A 4 hole distribution block
125A 6 hole distribution block
125A 10 hole distribution block
125A 14 hole distribution block
Blue & yellow/green ident cards
20A 1P (I) switch disconnector
20A 2P (I) switch disconnector
20A 3P (I) switch disconnector
20A 4P (I) switch disconnector
131
131
130
126
128,132
127
127
127
127
127
127
127
127
127
127
127
127
127
127
127
127
127
127
127
127
127
127
127
127
127
127
127
127
77,131
77,131
77,131
77,131
119
119
77,189
77,189
117
117
117
117
109,117
109,117
109,117
109,117
109,117
81,117
117
117
117
117
81,117
117
117
117
81,117
117
117
117
117
118
118
118
118
118
117
118
118
118
118
118
118
118
118
118
32
33
33
33
Part Page No.Description
15009
15010
15011
15012
15013
15014
15015
15016
15019
15020
15023
15024
15057
15059
15060
15063
15064
15090
15091
15092
15093
15094
15096
15100
15101
15125
15126
15151
15152
15196
15201
15202
15208
15209
15212
15213
15214
15215
15216
15218
15219
15220
15222
15233
15266
15268
15270
15280
15281
15284
15319
15320
15321
15322
15323
15335
15336
15337
15338
15359
15363
15365
15366
15367
15368
15393
15409
15410
15411
15416
15440
15443
15464
15465
15466
15467
15500
15502
15503
15505
15510
15511
15512
32A 1P (I) switch disconnector
32A 2P (I) switch disconnector
32A 3P (I) switch disconnector
32A 4P (I) switch disconnector
63A 1P (I) switch disconnector
63A 2P (I) switch disconnector
63A 3P (I) switch disconnector
63A 4P (I) switch disconnector
40A 4P I switch disconector
40A 2P I switch disconector
40A 3P I switch disconector
40A SP I switch disconector
125A 1P (I) switch disconnector
125A 3P (I) switch disconnector
125A 4P (I) switch disconnector
20A SP I sw'h discon'r + Indic'r
20A 2P I sw'h discon'r + Indic'r
100A 1P (I) switch disconnector
100A 2P (I) switch disconnector
100A 3P (I) switch disconnector
100A 4P (I) switch disconnector
Terminal shield (1P PR) for 100A
I switch disconnr auxiliary switch
32A SP I sw'h discon'r + Indic'r
32A 2P I sw'h discon'r + Indic'r
CMV voltmeter selector switch
CMA ammeter selector switch
Device holder - 22mm
Device holder - Universal
PM9 Multimeter
0 - 600Vac digital voltmeter
0 - 10A digital ammeter
20 - 100Hz digital frequency meter
Digital Ammeter range 0 - 5000A
240 - 8 - 12Vac 16VA bell transformer
240 - 8 - 12Vac 4VA bell transformer
Bell transformer 4VA 230 / 8 v
Bell transformer 25VA 230 / 12 - 24 v
240 - 8 - 12Vac 8VA bell transformer
240 - 12/24Vac 16VA transformer
240 - 12/24Vac 25VA transformer
240 - 12/24Vac 40VA transformer
240 - 12/24Vac 63VA transformer
MINp Delay off timer
IC2000P light level time switch
Photo cell for IC2000
Multi function time switch
Memory for MF timeswitch 15270
Photo cell for IC2000
IC200 light sensing switch
63A contactor 2NO+1NC 240V coil
SO bell 220/240 Volt
SO bell 12 Volt
RO buzzer 220/240 Volt
RO buzzer 12 Volt
24HR analogue time switch
24HR analogue time switch
IH 1c 24hr 150hr reserve 2 chan'l
IH 60 minute analogue time switch
MIN timer terminal shield
MIN time switch 1 - 7mins
IH 24 hour analogue time switch
IH 24 hour + 7 day analogue
IH 7 day analogue time switch
IC2000 light sensitive switch
2A 240Vac RBN changeover relay
ATLC+S impulse relay auxiiary
ATLC+C impulse relay aux
ATLT impulse relay aux
RTBT interface relay
Hours counter 240V
CI Impulse counting module
Single phase kilowatt hour meter
Three phase kilowatt hour meter
Single phase kWH meter
Three phase kWH meter
16A 1P 230 - 240Vac coil TL relay
1P 48Vac 24Vdc TLI relay
16A 1P 24Vac coil TL relay
32A 1P 230 - 240Vac ETL for TL32
16A 1P 230 - 240Vac coil TL relay
16A 1P 130Vac 48Vdc TL relay
16A 1P 48Vac 24Vdc TL relay
Part Description
15513
15514
15515
15516
15517
15518
15520
15521
15522
15523
15524
15525
15526
15527
15528
15530
15531
15532
15533
15534
15535
15536
15537
15538
15539
15540
15541
15542
15636
15646
15651
15656
15658
15668
15687
15688
15689
15690
15692
15693
15695
15696
15720
15721
15722
15723
15775
15776
15777
15779
15840
15841
15845
15846
15847
15848
15854
15914
15917
15919
15920
15921
15922
15923
15957
15958
15959
15960
15961
15962
15963
15964
15966
15967
15968
15969
15971
15972
15973
15974
15975
15977
15978
16A 1P 24vac coil TL relay
16A 1P 12Vac coil TL relay
32A 1P 230 - 240Vac coil TL relay
TLM impulse relay
TLS impulse relay
TLC impulse relay
16A 2P 230 - 240vac coil TL relay
16A 2P 130Vac 48Vdc relay
16A 2P 48Vac 24Vdc relay
16A 2P 24Vac coil TL relay
16A 2P 12vac coil TL relay
TLc impulse relay 24Vac
TLc impulse relay 48Vac
TLs impulse relay 24Vac 12Vdc
TLs impulse relay 48Vac 24Vdc
ETL 230 - 240Vac coil aux for Tl/TLI
16A 1P 130Vac 48Vdc ETL relay
16A 1P 48Vac 24Vdc ETL relay
ETL 24Vac coil aux for TL/TLI
16A 1P 12Vac 6Vdc ETL relay
10A (AC1) 240Vac RLI relay
10A (AC1) 48Vac RLI relay
10A (AC1) 24Vac RLI relay
10A (AC1) 12Vac RLI relay
10A (AC1) 240Vac ERL extension
10A (AC1) 48Vac ERL extension
10A (AC1) 24Vac ERL extension
10A (AC1)12Vac ERL extension
1 pole STI fuse carier
1 pole and neutral STI fuse carier
2 pole STI fuse carrier
3 pole STI fuse carier
3 pole and neutral STI fuse carier
Blown fuse indicator
PF30 10kA 1P+N surge arrester
PF30 10kA 3P+N surge arrester
PF30r 10kA 1P+N surge arrester
PF30r 10kA 3P+N surge arrester
PF15 5kA 1P+N surge arrester
PF15 5kA 3P+N surge arrester
PF8 2kA 1P+N surge arrester
PF8 2kA 3P+N surge arrester
1 channel IHP time switch
1 channel IHP time switch
2 channel IHP time switch
2 channel IHP time switch
2A gG fuse links 10.3x38mm
4A gG fuse links 10.3x38
6A gG fuse links 10.3x38mm
10A gG fuse links 10.3x38mm
TH6 thermostat
TH3 thermostat
TH6 thermostat ground probe
TH6 thermostat ambient probe
TH6 thermostat outdoor probe
TH6 thermostat collar probe
IHP 18mm I channel
ACTo+F add on aux contact
ACTt add on time delay unit
ACTp filter 24V devices
ACTp filter 240V devices
25A 3/4P contactor screw shield
40/63A 2P contactor screw shield
63A 3/4P contactor screw shield
Contactor 16A 2NC 240V ac
25A 1P contactor 240V ac
25A 2P contactor 240Vac coil
25A 2P contactor 240Vac coil
25A 3P contactor 240V coil
25A 4P contactor 240Vac coil
25A 4P contactor 240Vac coil
25A 4P contactor 2NO+2NC
40A 2P contactor 240V coil
40A 3P contactor 240V coil
40A 4P contactor 240V coil
40A 4P contactor 240V coil
63A 2P contactor 240V coil
63A 3P contactor 3NO 240Vac coil
63A 4P contactor 240Vac coil
63A 4P contactor 240Vac coil
63A 4P contactor 2NO+2NC
100A 2P contactor 240V coil
100A 4P contactor 240V coil
Part Description
IndexBy part number
209
32
33
33
33
32
33
33
33
33
33
33
32
32
33
33
32
33
32
33
33
33
33
33
32
33
64
64
42
42
63
62
62
62
62
34
34
34
34
34
34
34
34
34
58
59
59
57
57
59
59
46
35
35
35
35
55
55
55
55
58
58
55
55
55
59
48
54
54
54
48
68
68
67
67
67
67
53
53
53
53
53
53
53
53
53
53
53
53
53
53
53
53
53
53
53
53
53
53
53
53
53
53
53
48
48
48
48
48
48
48
48
36
36
36
36
36
36
38
38
38
38
38
38
38
38
56
56
56
56
36
36
36
36
71
71
71
71
71
71
56
47
47
47
47
46
46
46
46
46
46
46
46
46
46
46
46
46
46
46
46
46
46
46
46
46
46
Page No. Page No.
15981
15982
15983
15984
15986
15987
15988
16020
16022
16023
16024
16025
16026
16029
16030
16031
16032
16033
16034
16035
16036
16037
16038
16039
16040
16041
16042
16043
16044
16045
16060
16061
16065
16066
16067
16068
16069
16070
16111
16113
16115
16116
16118
16120
16122
16124
16126
16127
16129
16130
16261
16364
16451
16452
16453
16454
16456
16459
16460
16461
16462
16463
16464
16465
16468
16469
16470
16471
16473
16474
16476
16477
16478
16479
16480
16481
16482
16483
16500
16501
16502
16503
16504
IndexBy part number
210
25A 2P contactor with manual ctrl
Contactor W/MANL 3NO 25A
25A 4P contactor with manual ctrl
40A 2P contactor with manual ctrl
40A 4p contactor 4NO 240Vac coil
63A 2P contactor with manual ctrl
63A 4P contactor with manual ctrl
25A 2P contactor 24Vac coil
25A 4P contactor 24Vac coil
25A 4P contactor 24Vac coil
63A 2P contactor 24V coil
63A 4P contactor 24Vac coil
63A 4P contactor 24Vac coil
Ammeter 0 - 30A direct connection
AMP ammeter without scale 5A
AMP ammeter scale 0 - 5A
AMP ammeter scale 0 - 50A
AMP ammeter scale 0 - 75A
AMP ammeter scale 0 - 100A
AMP ammeter scale 0 - 150A
AMP ammeter scale 0 - 200A
AMP ammeter scale 0 - 250A
AMP ammeter scale 0 - 300A
AMP ammeter scale 0 - 400A
AMP ammeter scale 0 - 500A
AMP ammeter scale 0 - 600A
AMP ammeter scale 0 - 800A
AMP ammeter scale 0 - 1000A
AMP ammeter scale 0 - 1500A
AMP ammeter scale 0 - 2000A
0 - 300V Modular Voltmeter
VLT voltmeter 0 - 500V
RTA time delay before ON relay
RTB time delay before OFF relay
RTC time delay before OFF relay
RTH time delay before OFF relay
RTL pulsed On and OFF timer
RTMF time delay relay
16A contactor 1NC 24Vac coil
16A contactor 1NO 240Vac coil
16A contactor 2NC 24Vac coil
16A contactor 2NC 240Vac+Man
16A contactor 3NC 24Vac coil
16A contactor 3NC 240Vac coil
16A contactor 4NC 24Vac coil
16A contactor 4NC 240Vac coil
16A contactor 1NO+1NC 24Vac
16A contactor 1NO+1NC 240Vac
16A contactor 2NO+2NC 24Vac
16A contactor 2NO+2NC 240Vac
80A 30mA 4P RCCB RMG
IH 1c 24hr no reserve
CT 50/5 trop 21mm ID 1.25VA
CT 75/5 trop 21mm ID 1.5VA
CT 100/5 trop 21mm ID 2.5VA
CT 125/5 trop 21mm ID 4VA
CT 200/5 trop 21mm ID 6VA
CT 150/5 trop 22 ID/30x10 5.5VA
CT 200/5 trop 22 ID/30x10 7VA
CT 250/5 trop 22 ID/30x10 9VA
CT 300/5 trop 22 ID/30x10 11VA
CT 400/5 trop 22 ID/30x10 15VA
CT 500/5 trop 22 ID/30x10 18VA
CT 600/5 trop 22ID/30x10 21.5VA
CT 250/5 trop 35 ID/40x10 5VA
CT 300/5 trop 35 ID/40x10 8VA
CT 400/5 trop 35 ID/40x10 12VA
CT 500/5 trop 35 ID/40x10 12VA
CT 500/5 trop 51X31/64X11
CT. 600/5 TROP 51X31/64X12
CT 200/5 trop 65x32 slot 2VA
CT 250/5 trop 65x32 slot 4VA
CT 300/5 trop 65x32 slot 6VA
CT 400/5 trop 65x32 slot 7.5VA
CT 500/5 trop 65x32 slot 10VA
CT 600/5 trop 65x32 slot 10VA
CT 800/5 trop 65x32 slot 15VA
CT 1000/5 trop 65x32 slot 20VA
CT 40/5 trop 21mm ID 1VA
CT 50/5 STD 21mm ID 1.25VA
CT 75/5 STD 21mm ID 1.5VA
CT 100/5 STD 21mm ID 2.5VA
CT 125/5 STD 21mm ID 4VA
Part
46
46
46
46
46
46
46
46
46
46
46
46
46
61
61
61
61
61
61
61
61
61
61
61
61
61
61
61
61
61
61
61
51
51
51
51
51
51
46
46
46
46
46
46
46
46
46
46
46
46
14,74
55
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
Page No.Description
16505
16506
16509
16510
16511
16512
16513
16514
16515
16518
16519
16520
16521
16523
16524
16528
16529
16530
16531
16532
16533
16534
16535
16537
16538
16540
16541
16542
16543
16544
16545
16547
16548
16549
16550
16551
16552
16553
16557
16558
16559
16562
16563
16564
16567
16568
16569
16572
16573
16574
16577
16578
16579
16581
16583
16585
16587
16589
16590
16591
16627
16956
16990
16992
16994
16995
17065
17066
17067
17070
17071
17072
17075
17076
18030
18031
18032
18033
18034
18035
18036
18037
18038
CT 150/5 STD 21mm ID 4VA
CT 200/5 STD 21mm ID 6VA
CT 150/5 STD 22 ID/30x10 5.5VA
CT 200/5 STD 22 ID/30x10 7VA
CT 250/5 STD 22 ID/30x10 9VA
CT 300/5 STD 22 ID/30x10 11VA
CT 400/5 STD 22 ID/30x10 15VA
CT 500/5 STD 22 ID/30x10 18VA
CT 600/5 STD 22 ID/30x10 21.5VA
CT 250/5 STD 35 ID/40x10 5VA
CT 300/5 STD 35 ID/40x10 8VA
CT 400/5 STD 35 ID/40x10 12VA
CT 500/5 STD 35 ID/40x10 12VA
CT 500/5 STD 51X31/64X11
CT 600/5 STD 51X31/64X11
CT 300/5 STD 65x32 slot 6VA
CT 400/5 STD 65x32 slot 7.5VA
CT 500/5 STD 65x32 slot 10VA
CT 600/5 STD 65x32 slot 10VA
CT 800/5 STD 65x32 slot 15VA
CT 1000/5 STD 65x32 slot 20VA
CT 1250/5 trop 65x32 slot 25VA
CT 1500/5 trop 65x32 slot 30VA
CT 1250/5
CT 1500/5 trop 84x34 slot 20VA
CT 1250/5 trop 127x38 slot 12VA
CT 1500/5 trop 127x38 slot 15VA
CT 2000/5 trop 127x38 slot 20VA
CT 2500/5 trop 127x38 slot 25VA
CT 3000/5 trop 127x38 slot 30VA
CT 2500/5 trop 127x52 slot 50VA
CT 4000/5 trop 127x52 slot 80VA
CT 5000/5 trop 165x55 slot 60VA
CT 6000/5 trop 165x55 slot 70VA
copper sleeve for 21mm ID CT
copper sleeve for 22mm ID CT
CT terminal cover
CT terminal cover
PRD65r 1P+N surge arrester
PRD65r 3P surge arrester
PRD65r 3P+N surge arrester
PRD40r 1P+N surge arrester
PRD40r 3P surge arrester
PRD40r 3P+N surge arrester
PRD40 1P+N surge arrester
PRD40 3P surge arrester
PRD40 3P+N surge arrester
PRD15 1P+N surge arrester
PRD15 3P surge arrester
PRD15 3P+N surge arrester
PRD8 1P+N surge arrester
PRD8 3P surge arrester
PRD8 3P+N surge arrester
C65r - 275 surge arrester cartridge
C40r - 275 surge arrester cartridge
C40 - 275 surge arrester cartridge
C15 - 275 surge arrester cartridge
C8 - 275 surge arrester cartridge
C neutral r surge arrester cartridge
C neutral surge arrester cartridge
Curr transf 250/5
16A 2P contactor 1NO+1NC
CDM PIR detector
Presence detector
CDPt Pressence detector
CDPt additional remote
ME1 kilowatt hour meter 63A
ME1z kilowatt hour meter 63A
ME1zr kilowatt hour meter 63A
ME4 kilowatt hour meter 63A
6E4zr kilowatt hour meter 63A
ME4zrt kilowatt hour meter 63A
ME3 kilowatt hour meter 63A
ME3zr kilowatt hour meter 63A
BP Grey pushbutton 1NC
BP Red pushbutton 1NC
BP Grey pushbutton 1NO
BP Grey pushbutton 1NO + 1NC
BP Double pushbutton 1NC + 1NO
BP Double pushbutton 1NO + 1NO
Grey p/button 1NO+ light
Grey p/button 1NC+red light
Grey p/button 1NO+green light
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
51
46
60
60
60
60
67
67
67
67
67
67
67
67
39
39
39
39
39
39
39
39
39
Part Page No.Description
18039
18070
18071
18072
18073
18074
18308
18309
18310
18311
18312
18320
18321
18322
18323
18324
18326
18327
18330
18331
18332
18333
18334
18335
18394
18395
18396
18397
18398
18399
18400
18401
18402
18403
18404
18405
18406
18407
18408
18409
18410
18411
18412
18413
18414
18415
18416
18417
18418
18419
18420
18421
18422
18423
18424
18425
18426
18427
18428
18429
18430
18431
18432
18433
18434
18435
18436
18437
18438
18439
18440
18441
18442
18443
18444
18445
18446
18447
18448
18449
18450
18451
18452
Grey p/button 1NC+red light
CM 2 pos 20A selector switch
CM 2 pos 20A selector switch
CM 2 pos 20A selector switch
CM 3 pos 20A selector switch
CM 3 pos 20A selector switch
Contactor auxiliary ACTC
Contactor auxiliary ACTC
1P/2P TMC60 remote control
3P/4P TMC60 remote control
1 - 2P Tm remote control
V 110/230Vac red indicator light
V 110/230Vac green indicator light
V 110/230Vac white indicator light
V 110/230Vac blue indicator light
V 110/230Vac yellow indicator light
V 230Vac red flash indicator light
3 phase indicator lights 230/400V
V 12/48Vac/dc red indicator light
V 12/48Vac/dc green indicator light
V 12/48Vac/dc white indicator light
V 12/48Vac/dc blue indicator light
V 12/48Vac/dc yellow indicator light
110/230Vac double indicator light
10A 1P 15kA C120H MCB Type B
16A 1P 15kA C120H MCB Type B
20A 1P 15kA C120H MCB Type B
25A 1P 15kA C120H MCB Type B
32A 1P 15kA C120H MCB Type B
40A 1P 15kA C120H MCB Type B
50A 1P 15kA C120H MCB Type B
63A 1P 15kA C120H MCB Type B
80A 1P 15kA C120H MCB Type B
100A 1P 15kA C120H MCB Type B
125A 1P 15kA C120H MCB Type B
10A 2P 15kA C120H MCB Type B
16A 2P 15kA C120H MCB Type B
20A 2P 15kA C120H MCB Type B
25A 2P 15kA C120H MCB Type B
32A 2P 15kA C120H MCB Type B
40A 2P 15kA C120H MCB Type B
50A 2P 15kA C120H MCB Type B
63A 2P 15kA C120H MCB Type B
80A 2P 15kA C120H MCB Type B
100A 2P 15kA C120H MCB Type B
125A 2P 15kA C120H MCB Type B
10A 3P 15kA C120H MCB Type B
16A 3P 15kA C120H MCB Type B
20A 3P 15kA C120H MCB Type B
25A 3P 15kA C120H MCB Type B
32A 3P 15kA C120H MCB Type B
40A 3P 15kA C120H MCB Type B
50A 3P 15kA C120H MCB Type B
63A 3P 15kA C120H MCB Type B
80A 3P 15kA C120H MCB Type B
100A 3P 15kA C120H MCB Type B
125A 3P 15kA C120H MCB Type B
10A 4P 15kA C120H MCB Type B
16A 4P 15kA C120H MCB Type B
20A 4P 15kA C120H MCB Type B
25A 4P 15kA C120H MCB Type B
32A 4P 15kA C120H MCB Type B
40A 4P 15kA C120H MCB Type B
50A 4P 15kA C120H MCB Type B
63A 4P 15kA C120H MCB Type B
80A 4P 15kA C120H MCB Type B
100A 4P 15kA C120H MCB Type B
125A 4P 15kA C120H MCB Type B
10A 1P 15kA C120H MCB Type C
16A 1P 15kA C120H MCB Type C
20A 1P 15kA C120H MCB Type C
25A 1P 15kA C120H MCB Type C
32A 1P 15kA C120H MCB Type C
40A 1P 15kA C120H MCB Type C
50A 1P 15kA C120H MCB Type C
63A 1P 15kA C120H MCB Type C
80A 1P 15kA C120H MCB Type C
100A 1P 15kA C120H MCB Type C
125A 1P 15kA C120H MCB Type C
10A 2P 15kA C120H MCB Type C
16A 2P 15kA C120H MCB Type C
20A 2P 15kA C120H MCB Type C
25A 2P 15kA C120H MCB Type C
Part Description
18453
18454
18455
18456
18457
18458
18459
18460
18461
18462
18463
18464
18465
18466
18467
18468
18469
18470
18471
18472
18473
18474
18475
18476
18477
18478
18479
18480
18481
18482
18483
18484
18485
18486
18487
18488
18489
18490
18491
18492
18493
18494
18495
18496
18497
18498
18499
18500
18501
18502
18503
18504
18505
18506
18507
18508
18509
18510
18511
18512
18513
18514
18515
18516
18517
18518
18519
18520
18521
18522
18523
18524
18525
18526
18527
18528
18544
18545
18546
18547
18548
18549
18556
32A 2P 15kA C120H MCB Type C
40A 2P 15kA C120H MCB Type C
50A 2P 15kA C120H MCB Type C
63A 2P 15kA C120H MCB Type C
80A 2P 15kA C120H MCB Type C
100A 2P 15kA C120H MCB Type C
125A 2P 15kA C120H MCB Type C
10A 3P 15kA C120H MCB Type C
16A 3P 15kA C120H MCB Type C
20A 3P 15kA C120H MCB Type C
25A 3P 15kA C120H MCB Type C
32A 3P 15kA C120H MCB Type C
40A 3P 15kA C120H MCB Type C
50A 3P 15kA C120H MCB Type C
63A 3P 15kA C120H MCB Type C
80A 3P 15kA C120H MCB Type C
100A 3P 15kA C120H MCB Type C
125A 3P 15kA C120H MCB Type C
10A 4P 15kA C120H MCB Type C
16A 4P 15kA C120H MCB Type C
20A 4P 15kA C120H MCB Type C
25A 4P 15kA C120H MCB Type C
32A 4P 15kA C120H MCB Type C
40A 4P 15kA C120H MCB Type C
50A 4P 15kA C120H MCB Type C
63A 4P 15kA C120H MCB Type C
80A 4P 15kA C120H MCB Type C
100A 4P 15kA C120H MCB Type C
125A 4P 15kA C120H MCB Type C
10A 1P 15kA C120H MCB Type D
16A 1P 15kA C120H MCB Type D
20A 1P 15kA C120H MCB Type D
25A 1P 15kA C120H MCB Type D
32A 1P 15kA C120H MCB Type D
40A 1P 15kA C120H MCB Type D
50A 1P 15kA C120H MCB Type D
63A 1P 15kA C120H MCB Type D
80A 1P 15kA C120H MCB Type D
100A 1P 15kA C120H MCB Type D
125A 1P 15kA C120H MCB Type D
10A 2P 15kA C120H MCB Type D
16A 2P 15kA C120H MCB Type D
20A 2P 15kA C120H MCB Type D
25A 2P 15kA C120H MCB Type D
32A 2P 15kA C120H MCB Type D
40A 2P 15kA C120H MCB Type D
50A 2P 15kA C120H MCB Type D
63A 2P 15kA C120H MCB Type D
80A 2P 15kA C120H MCB Type D
100A 2P 15kA C120H MCB Type D
125A 2P 15kA C120H MCB Type D
10A 3P 15kA C120H MCB Type D
16A 3P 15kA C120H MCB Type D
20A 3P 15kA C120H MCB Type D
25A 3P 15kA C120H MCB Type D
32A 3P 15kA C120H MCB Type D
40A 3P 15kA C120H MCB Type D
50A 3P 15kA C120H MCB Type D
63A 3P 15kA C120H MCB Type D
80A 3P 15kA C120H MCB Type D
100A 3P 15kA C120H MCB Type D
125A 3P 15kA C120H MCB Type D
10A 4P 15kA C120H MCB Type D
16A 4P 15kA C120H MCB Type D
20A 4P 15kA C120H MCB Type D
25A 4P 15kA C120H MCB Type D
32A 4P 15kA C120H MCB Type D
40A 4P 15kA C120H MCB Type D
50A 4P 15kA C120H MCB Type D
63A 4P 15kA C120H MCB Type D
80A 4P 15kA C120H MCB Type D
100A 4P 15kA C120H MCB Type D
125A 4P 15kA C120H MCB Type D
C120 MCB terminal shield
C120 MCB terminal screw shield
Rear connection terminal + shield
300mA 2P C120H s Class AC Vigi
1000mA 2P C120H s Class AC Vigi
300mA 3P C120H s Class AC Vigi
1000mA 3P C120H s Class AC Vigi
300mA 4P C120H s Class AC Vigi
1000mA 4P C120H s Class AC Vigi
300mA 2P C120H si Type Vigi
Part Description
IndexBy part number
211
39
39
39
39
39
39
47
47
87
87
87
39
39
39
39
39
39
39
39
39
39
39
39
39
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
83
90
90
91
85
85
85
85
85
85
85
Page No. Page No.
18557
18558
18559
18560
18561
18563
18564
18565
18566
18567
18568
18569
18570
18571
18572
18573
18574
18575
18576
18577
18578
18579
18580
18581
18582
18583
18584
18585
18586
18587
18588
18589
18591
18592
18593
18594
18595
18596
18597
18598
18599
18610
18611
18612
18613
18614
18615
18616
18617
18618
18621
18622
18623
18624
18625
18626
18627
18628
18629
18632
18633
18634
18635
18636
18637
18638
18639
18640
18642
18644
18649
18650
18651
18652
18653
18654
18655
18656
18658
18660
18662
18663
18664
IndexBy part number
212
1000mA 2P C120H si Vigi
300mA 3P C120H si Type Vigi
1000mA 3P C120H si Type Vigi
300mA 4P C120H si Type Vigi
1000mA 4P C120H si Type Vigi
30mA 2P C120H Class AC Vigi
300mA 2P C120H Class AC Vigi
500mA 2P C120H Class AC Vigi
30mA 3P C120H Class AC Vigi
300mA 3P C120H Class AC Vigi
500mA 3P C120H Class AC Vigi
30mA 4P C120H Class AC Vigi
300mA 4P C120H Class AC Vigi
500mA 4P C120H Class AC Vigi
30mA 2P C120H Class A Vigi
300mA 2P C120H Class A Vigi
500mA 2P C120H Class A Vigi
30mA 3P C120H Class A Vigi
300mA 3P C120H Class A Vigi
500mA 3P C120H Class A Vigi
30mA 4P C120H Class A Vigi
300mA 4P C120H Class A Vigi
500mA 4P C120H Class A Vigi
300mA 2P C120H Class A Vigi
500mA 2P C120H Class A Vigi
1000mA 2P C120H Class A Vigi
300mA 3P C120H Class A Vigi
500mA 3P C120H Class A Vigi
1000mA 3P C120H Class A Vigi
300mA 4P C120H Class A Vigi
500mA 4P C120H Class A Vigi
1000mA 4P C120H Class A Vigi
30mA 2P C120H si Type Vigi
300mA 2P C120H si Type Vigi
500mA 2P C120H si Type Vigi
30mA 3P C120H si Type Vigi
300mA 3P C120H si Type Vigi
500mA 3P C120H si Type Vigi
30mA 4P C120H si Type Vigi
300mA 4P C120H si TypeVigi
500mA 4P C120H si Type Vigi
10A 1P 25kA NG125N curve C
16A 1P 25kA NG125N curve C
20A 1P 25kA NG125N curve C
25A 1P 25kA NG125N curve C
32A 1P 25kA NG125N curve C
40A 1P 25kA NG125N curve C
50A 1P 25kA NG125N curve C
63A 1P 25kA NG125N curve C
80A 1P 25kA NG125N curve C
10A 2P 25kA NG125N curve C
16A 2P 25kA NG125N curve C
20A 2P 25kA NG125N curve C
25A 2P 25kA NG125N curve C
32A 2P 25kA NG125N curve C
40A 2P 25kA NG125N curve C
50A 2P 25kA NG125N curve C
63A 2P 25kA NG125N curve C
80A 2P 25kA NG125N curve C
10A 3P 25kA NG125N curve C
16A 3P 25kA NG125N curve C
20A 3P 25kA NG125N curve C
25A 3P 25kA NG125N curve C
32A 3P 25kA NG125N curve C
40A 3P 25kA NG125N curve C
50A 3P 25kA NG125N curve C
63A 3P 25kA NG125N curve C
80A 3P 25kA NG125N curve C
100A 3P 25kA NG125N curve C
125A 3P 25kA NG125N curve C
10A 4P 25kA NG125N curve C
16A 4P 25kA NG125N curve C
20A 4P 25kA NG125N curve C
25A 4P 25kA NG125N curve C
32A 4P 25kA NG125N curve C
40A 4P 25kA NG125N curve C
50A 4P 25kA NG125N curve C
63A 4P 25kA NG125N curve C
80A 4P 25kA NG125N curve C
100A 4P 25kA NG125N curve C
125A 4P 25kA NG125N curve C
80A 3P 25kA NG125N curve B
100A 3P 25kA NG125N curve B
Part
85
85
85
85
85
85
85
85
85
85
85
85
85
85
85
85
85
85
85
85
85
85
85
85
85
85
85
85
85
85
85
85
85
85
85
85
85
85
85
85
85
96
96
96
96
96
96
96
96
96
96
96
96
96
96
96
96
96
96
96
96
96
96
96
96
96
96
96
96
96
96
96
96
96
96
96
96
96
96
96
96
96
96
Page No.Description
18665
18666
18667
18668
18669
18670
18671
18672
18673
18674
18705
18706
18707
18708
18709
18710
18711
18712
18713
18714
18715
18716
18717
18718
18719
18720
18721
18722
18723
18724
18725
18726
18727
18728
18729
18730
18731
18732
18733
18734
18735
18736
18737
18738
18739
18740
18868
18869
18870
18871
18872
18873
18874
18875
18876
18879
18880
18881
18882
18883
18884
18885
18886
18887
18889
18890
18891
18892
18893
18894
18895
18896
19000
19001
19002
19003
19004
19005
19008
19009
19012
19013
19014
125A 3P 25kA NG125N curve B
80A 4P 25kA NG125N curve B
100A 4P 25kA NG125N curve B
125A 4P 25kA NG125N curve B
80A 3P 25kA NG125N curve D
100A 3P 25kA NG125N curve D
125A 3P 25kA NG125N curve D
80A 4P 25kA NG125N curve D
100A 4P 25kA NG125N curve D
125A 4P 25kA NG125N curve D
10A 1P 36kA NG125H curve C
16A 1P 36kA NG125H curve C
20A 1P 36kA NG125H curve C
25A 1P 36kA NG125H curve C
32A 1P 36kA NG125H curve C
40A 1P 36kA NG125H curve C
50A 1P 36kA NG125H curve C
63A 1P 36kA NG125H curve C
80A 1P 36kA NG125H curve C
10A 2P 36kA NG125H curve C
16A 2P 36kA NG125H curve C
20A 2P 36kA NG125H curve C
25A 2P 36kA NG125H curve C
32A 2P 36kA NG125H curve C
40A 2P 36kA NG125H curve C
50A 2P 36kA NG125H curve C
63A 2P 36kA NG125H curve C
80A 2P 36kA NG125H curve C
10A 3P 36kA NG125H curve C
16A 3P 36kA NG125H curve C
20A 3P 36kA NG125H curve C
25A 3P 36kA NG125H curve C
32A 3P 36kA NG125H curve C
40A 3P 36kA NG125H curve C
50A 3P 36kA NG125H curve C
63A 3P 36kA NG125H curve C
80A 3P 36kA NG125H curve C
10A 4P 36kA NG125H curve C
16A 4P 36kA NG125H curve C
20A 4P 36kA NG125H curve C
25A 4P 36kA NG125H curve C
32A 4P 36kA NG125H curve C
40A 4P 36kA NG125H curve C
50A 4P 36kA NG125H curve C
63A 4P 36kA NG125H curve C
80A 4P 36kA NG125H curve C
4A 2P NG125LMA
6.3A 2P NG125LMA
10A 2P NG125LMA
12.5A 2P NG125LMA
16A 2P NG125LMA
25A 2P NG125LMA
40A 2P NG125LMA
63A 2P NG125LMA
80A 2P NG125LMA
4A 3P NG125LMA
6.3A 3P NG125LMA
10A 3P NG125LMA
12.5A 3P NG125LMA
16A 3P NG125LMA
25A 3P NG125LMA
40A 3P NG125LMA
63A 3P NG125LMA
80A 3P NG125LMA
63A 3P NG125 NA switch dis
80A 3P NG125 NA switch dis
100A 3P NG125 NA switch dis
125A 3P NG125 NA switch dis
63A 4P NG125 NA switch dis
80A 4P NG125 NA switch dis
100A 4P NG125 NA switch dis
125A 4P NG125 NA switch dis
63A 2P NG125 Vigi 30mA
63A 2P NG125 Vigi 300mA
63A 3P NG125 Vigi 30mA
63A 3P NG125 Vigi 300mA
63A 4P NG125 Vigi 30mA
63A 4P NG125 Vigi 300mA
63A 2P NG125 Vigi 30mA
63A 2P NG125 Vigi 300mA
63A 2P NG125 Vigi 30mA
63A 2P NG125 Vigi 300mA
63A 3P NG125 Vigi 30mA
96
96
96
96
96
96
96
96
96
96
97
97
97
97
97
97
97
97
97
97
97
97
97
97
97
97
97
97
97
97
97
97
97
97
97
97
97
97
97
97
97
97
97
97
97
97
98
98
98
98
98
98
98
98
98
98
98
98
98
98
98
98
98
98
94
94
94
94
94
94
94
94
100
102
100
102
100
102
101
103
103
101
103
Part Page No.Description
19015
19016
19030
19031
19032
19033
19034
19035
19036
19037
19039
19041
19042
19044
19046
19047
19049
19053
19054
19055
19056
19058
19059
19060
19064
19065
19066
19067
19068
19069
19070
19071
19072
19073
19074
19075
19076
19077
19078
19080
19081
19082
19083
19084
19085
19086
19087
19088
19089
19090
19091
19092
19093
19094
19095
19100
19101
19106
19107
19249
19250
19252
19254
19255
19256
19257
19258
19260
19261
19263
19264
19266
19268
19269
19270
19271
19272
19661
19663
19665
19666
19667
19668
63A 3P NG125 Vigi 300mA
63A 4P NG125 Vigi 30mA
63A 4P NG125 Vigi 300mA
63A 2P NG125 Vigi 300mA TD
63A 2P NG125 Vigi 1000mA TD
63A 3P NG125 Vigi 300mA TD
NG125 Vigi 3P 63A 1000mA TD
63A 4P NG125 Vigi 300mA TD
63A 4P NG125 Vigi 1000mA TD
63A 3P NG125 Vigi 300..3000mA
63A 4P NG125 Vigi 300..3000mA
125A 3P NG125 Vigi 30mA
125A 4P NG125 Vigi 30mA
125A 4P NG125 Vigi 300mA
125A 3P NG125 Vigi 300..1000mA
125A 4P NG125 Vigi 300..1000mA
125A 3P NG125 Vigi 300..3000mA
125A 4P NG125 Vigi 300..3000mA
63A 3P NG125 Vigi 300..3000mA
63A 4P NG125 Vigi 300..3000mA
125A 3P NG125 Vigi 300..3000mA
125A 4P NG125 Vigi 300..3000mA
NG125 Vigi SDV,NO aux contact
NG125 Vigi SDV,NC aux contact
NG125 Vigi MXV auxiliary
NG125 230..415Vac MX+OF aux
NG125 48..130Vac MX+OF aux
NG125 24Vac MX+OF auxiliary
240Vac voltage release (MN)
48Vac voltage release (MN)
48Vdc voltage release (MN)
OF+OF electrical auxiliary
OF+SD electrical auxiliary
OF+OF or OF+SD electrical aux/y
63A 2P NG125 RCD terminal shield
63A 3P NG125 RCD terminal shield
63A 4P NG125 RCD terminal shield
63A 3P NG125 RCd terminal shield
63A 4P NG125 RCD terminal shield
1P NG125 terminal shield
2P NG125 terminal shield
3P NG125 terminal shield
4P NG125 terminal shield
1P NG125 terminal screw shield (x10)
2P NG125 terminal screw shield (x10)
3P NG125 terminal screw shield (x10)
4P NG125 terminal screw shield (x10)
Rotary handle,standard black
Rotary handle,red/yellow front
NG125 padlocking accessory
INS40/80 bare cable connector (x4)
Direct Rotary Handle
NG125 connection screws&nuts
NG125 cable lugs
NG125 terminal for alu cable
125A 3P NG125 Vigi 30mA,si Type
125A 4P NG125 Vigi 30mA,si Type
125A 3P NG125 Vigi 300..3000mA
125A 4P NG125 Vigi 300..3000mA
4A 6kA DPN rated curve B
6A 6kA DPN rated curve B
10A 6kA DPN curve B
16A 6kA DPN curve B
20A 6kA DPN curve B
25A 6kA DPN curve B
32A 6kA DPN curve B
40A 6kA DPN curve B
1A 6kA DPN curve C
2A 6kA DPN curve C
4A 6kA DPN curve C
6A 6kA DPN curve C
10A 6kA DPN curve C
16A 6kA DPN curve C
20A 6kA DPN curve C
25A 6kA DPN curve C
32A 6kA DPN curve C
40A 6kA DPN curve C
6A 30mA 2P DPN Vigi curve C
10A 30mA 2P DPN Vigi curve C
16A 30mA 2P DPN Vigi curve C
20A 30mA 2P DPN Vigi curve C
25A 30mA 2P DPN Vigi curve C
32A 30mA 2P DPN Vigi curve C
Part Description
19669
20267
21100
21101
21102
21103
21104
21105
21106
21107
21108
21109
21110
21111
21112
21113
21115
21116
21117
21118
21119
21120
21121
21127
21128
21129
21130
21133
21140
21141
21142
21143
21144
21145
21146
21147
21148
21180
21181
23111
23116
23146
23213
23227
23249
23253
23258
23303
23308
24872
24873
24875
24876
24877
24878
24879
24880
24881
24882
24883
24884
25211
25212
25214
25215
25216
25217
25218
25219
25220
25221
25222
25223
26476
26477
26478
26483
26484
26485
26923
26924
26927
26929
40A 30mA 2P DPN Vigi curve C
Brackets for through door mounting
0.1 - 0.16A P25M MCB
0.16 - 0.25A P25M MCB
0.25 - 0.4A P25M MCB
0.4 - 0.63A P25M MCB
0.63 - 1A P25M MCB
1 - 1.6A P25M MCB
1.6 - 2.5A P25M MCB
1.5 - 4A P25M MCB
4 - 6.3A P25M MCB
6.3 - 10A P25M MCB
9 - 14A P25M MCB
13 - 18A P25M MCB
17 - 23A P25M MCB
20 - 25A P25M MCB
P25M limiter block
P25M MCB contact position, F+F
P25M MCB contact position, O+F
P25M position&alarm F+SD.F
P25M position&alarm O+SD.F
P25M position&alarm F+SD.O
P25M position+alarm 0+SD.O
P25M 240 MX voltage release
P25M 415 MX inst voltage release
P25M MN undervoltage release
P25M MN undervoltage release
P25M IP55 enclosure
P25M MCB green indicator
P25M MCB green neon indicator
P25M MCB red neon indicator
P25M MCB red neon indicator
P25M MCB busbar terminal block
2P P25M MCB comb busbar
4P P25M MCB comb busbar
P25M insulated cable connector
P25M comb busbar end cover
RCP phase failure relay
RCI relay 230V
80A 100mA 2P RMG
100A 300mA 2P RMG
63A 300mA 4P RMG
100A 300mA 4P RCCB (RMG)
100A 300mA 4P RMG
25A 30mA 2P Class A RCD
40A 30mA 2P Class A RCD
63A 30mA 2P Class A RCD
40A 30mA 4P Class A RCD
63A 30mA 4P Class A RCD
1A 4P 10kA C60H curve C
2A 4P 10kA C60H curve C
4A 4P 10kA C60H curve C
6A 4P 10kA C60H curve C
10A 4P 10kA C60H curve C
16A 4P 10kA C60H curve C
20A 4P 10kA C60H curve C
25A 4P 10kA C60H curve C
32A 4P 10kA C60H curve C
40A 4P 10kA C60H curve C
50A 4P 10kA C60H curve C
63A 4P 10kA C60H curve C
1A 4P 10kA C60H curve D
2A 4P 10kA C60H curve D
4A 4P 10kA C60H curve D
6A 4P 10kA C60H curve D
10A 4P 10kA C60H curve D
16A 4P 10kA C60H curve D
20A 4P 10kA C60H curve D
25A 4P 10kA C60H curve D
32A 4P 10kA C60H curve D
40A 4P 10kA C60H curve D
50A 4P 10kA C60H curve D
63A 4P 10kA C60H curve D
MCB 110-415Vac/110-130Vdc MX
MCB 48Vac/dc MX
MCB 12/24Vac/dc MX
2P replacement cover for Vigibloc
3P replacement cover for Vigibloc
4P replacement cover for Vigibloc
RMG auxiliary switch (OFS)
C60H/RMG OF auxiliary contact
C60H SD fault indicatibg switch
C60H OF+SD/OF selector switch
Part Description
IndexBy part number
213
101
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
103
106
106
105
105
105
106
106
106
106
105
105
105
109
109
109
109
109
109
109
109
109
109
109
109
109
109
109
109
20,90,109
109
109
109
109
101
101
103
103
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
81
81
81
81
81
81
81
118
110
110
110
110
110
110
110
110
110
110
110
110
110
110
110
111
111
111
111
111
111
111
111
111
111
112
112
112
112
112
112
112
112
112
112
49
49
10,74
10,74
14,74
14,74
14,74
74
74
74
74
74
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
26,75,88
26,75,88
26,75,88
30,91
30,91
30,91
26,75,89
26,75,89
26,75,89
26,75,88
Page No. Page No.
26946
26947
26948
26959
26960
26961
26962
26963
26969
26970
26971
26975
26976
26977
26978
26979
26980
26981
26982
26991
27001
27053
27060
27062
27145
27150
28952
28957
28958
29211
29242
29243
29252
29253
29254
29256
29257
29258
29259
29260
29320
29323
29324
29337
29354
29370
29371
29387
29388
29407
29408
29450
29451
29455
29456
29457
29458
29461
29462
29504
29505
29506
29507
30555
30556
30557
30558
30561
30562
31536
31563
31564
31565
31566
31567
31568
31569
31570
32456
32479
32480
32481
32482
IndexBy part number
214
MX+OF shunt trip
MCB MX+OF shunt trip
MCB 24Vac/dc MX+OF shunt trip
MCB 115Vac 400Hz MN
Undervoltage release (MN)
Undervoltage release (MN)
Undervoltage release (MN)
Undervoltage release,time delay
Emergency stop (MNx)
MCB/RCD padlock attachment
MCB emergency stop (MNx)
1P C60H MCB terminal shields
2P C60H MCB terminal shields
MCB 230Vac MNx (C60)
4P C60H MCB terminal shields
MCB voltage threshold release
MCB voltage threshold release
C60H MCB terminal screw shield
C60H Vigi terminal screw shield
MCB 400Vac MNx (C60)
C60H MCB interpole barrier
MCB screw connection
16 - 50mm2 alu cable terminal
Modular device spacer
C120 MCB padlock attachment
C120 MCB label holder
4 cable lugs 95mm2 Cu cable
Pair terminal shields Interpact 63A
Pair terminal shields Interpact 160A
Earth fault protection 160A
3 Tunnel terminal 160A 1.5 - 95mm2
4 Tunnel terminal 160A 1.5 - 95mm2
3 lugs NS250 120mm2 Cu cable
3 lugs NS250. 150mm2 Cu cable
3 lugs NS250.185mm2 Cu cable
4 lugs NS250 120mm2 Cu cable
4 lugs NS250 150mm2 Cu cable
4 lugs NS250 185mm2 Cu cable
3 Tunnel terminal 1.5 - 185mm2
4 Tunnel terminal 1.5 - 185mm2
One pole terminal shield
Three pole terminal shield, pair
Four pole terminal shield, pair
Rotary handle for 63 - 250A
Mechanical interlock for 2 MCCB
Toggle padlocking attachment
Toggle padlocking attachment
Shunt trip 240V
Shunt trip 380/415V
Undervoltage release 240V
Undervoltage release 380/415V
Auxiliary switch
SDE auxiliary contact adaptor
Direct metering 100A 3P
Direct metering 100A 4P
CT module 100A 3P
CT module 100A 4P
CT module with voltage output 100/5 3P
CT module with voltage output 100/5 4P
3 lugs NS250. 150mm2 Al cable
4 lugs NS250. 150mm2 Al cable
3 lugs NS250. 185mm2 Al cable
4 lugs NS250. 185mm2 Al cable
Direct metering 160A 3P
Direct metering 160A 4P
CT module 160A 3P
CT module 160A 4P
CT module with voltage output 150/5 3P
CT module with voltage output 150/5 4P
MCCB Vigi module 250A 4P
1 set of 3P spreader 250A
1 set of 4P spreader 250A
Ammeter module 250A 3P
Ammeter module 250A 4P
CT module 250A 3P
CT module 250A 4P
CT module with voltage output 250/5 3P
CT module with voltage output 250/5 4P
MCCB Vigi module 400A 4P
3 clamps for 35 - 300mm2
4 clamps for 35 - 300mm2
3 clamps 2x35 - 240mm2
4 clamps 2x35 - 240mm2
Part
26,75,88
26,75,88
26,75,88
26,75,88
26,75,88
26,75,88
26,75,88
26,75,88
26,88
28,76,81,90
26,88
28,90
28,76,90
26,88
28,76,91
26,89
26,90
28,76,90
28,76,91
37, 98
29,91
91
90
30,46,91
91
Page No.Description
32490
32491
32500
32501
32502
32503
32504
32505
32506
32507
32564
32565
32597
32631
32653
32654
32655
32656
32657
32658
32855
32856
32857
32858
32861
32862
33466
33469
33487
33489
33490
33492
33494
33495
33564
33566
33568
33570
44936
57655
99217
99219
99221
99223
99225
99560
7795P
7796P
7797P
7798P
7799P
99246A
99246B
1 set of 3P spreader 630A
1 set of 4P spreader 630A
3 lugs for NS630. 240mm2
4 lugs for Interpact. 240mm2
3 lugs for NS630. 300mm2
4 lugs for NS630. 300mm2
3 lugs for NS630. 240mm2
4 lugs for NS630. 240mm2
3 lugs for NS630. 300mm2
4 lugs for NS630. 300mm2
Terminal shields 3P, one pair
Terminal shields 4P, one pair
Direct rotary handle
Fixed toggle padlock device
CT module with voltage output 400/5 3P
CT module with voltage output 400/5 4P
Ammeter module 400A 3P
Ammeter module 400A 4P
CT module 400A 3P
CT module 400A 4P
Ammeter module 600A 3P
Ammeter module 600A 4P
CT module 600A 3P
CT module 600A 4P
CT module with voltage output 600/5 3P
CT module with voltage output 600/5 4P
NS800N 3P Micrologic 2.0
NS800N 4P Micrologic 2.0
NS800NA 3P MCCB
NS1250NA 3P MCCB
NS1600NA 3P MCCB
NS800NA 4P MCCB
NS1250NA 4P MCCB
NS1600NA 4P MCCB
NS1250N 3P Micrologic 5.0
NS1250N 4P Micrologic 5.0
NS1600N 3P Micrologic 5.0
NS1600N 4P Micrologic 5.0
MCCB padlocking device
CE30 passive infrared detector
Earth and neutral bar 19 hole
Earth and neutral bar 24 hole
Earth and neutral bar 37 hole
Earth and neutral bar 48 hole
Earth and neutral bar 72 hole
3 SP way G9 IP30 steel enclosure
Prisma Front cover 6 way
Prisma Front cover 8 way
Prisma Front cover 12 way
Prisma Front cover 16 way
Prisma Front cover 24 way
4 way hinged cover
4 way hinged cover
60
118
118
118
118
118
77
115
115
115
115
115
118
118
Part Page No.Description
Enclosed switch disconnectors
Merlin Gerin is a world leader in the manufacture and supply of high, medium and low voltage products for the distribution, protection, control and management of electrical systems and is focused on the needs of both thecommercial and industrial sectors. The newly launched VDINetwork Solutions offer provides flexible, configurableethernet systems for all communication needs.
Square D is a total quality organisation and its business is to put electricity to work productively and effectively, protecting people, buildings and equipment. Its low voltageelectrical distribution equipment, systems and services areused extensively in residential and commercial applications.
Telemecanique is a UK market leader and world expert inautomation and control. It provides complete solutions, withit's range of components, Modicon range of high technologyprogrammable controllers (PLCs), multiple fieldbus andethernet communication networks, HMI, motion controlsystems, variable speed drives and communicationssoftware. In addition, it offers power distribution throughprefabricated busbar trunking.
Schneider Electric’s local supportSchneider Electric is committed to supporting its customers at every stage of a project. Our 180 sales engineers, the largestdedicated sales force in the UK electrical industry, operate from 4 customer support centres.
Our sales engineers are skilled at assessing individual requirements and combined with the expert support of our product specialists, will develop the most effective and economical answer taking relevant regulations and standards fully into account.
To access the expertise of the Schneider Electric group, please call 0870 608 8 608. Each customer support centre includesfacilities for demonstrations and training, and presentation rooms fully equipped with audio visual and video, providing excellent meeting facilities.
www.schneider.co.uk
AUG 2005MGLV5750
Industrial systems and solutions showroomSchneider Electric Ltd, University of Warwick Science Park, Sir William Lyons Road, Coventry CV4 7EZ
Building systems and solutions showroomSchneider Electric Ltd, Stafford Park 5, Telford, Shropshire TF3 3BL
Energy and Infrastructure systems and solutions showroomSchneider Electric Ltd, 123 Jack Lane, Hunslet, Leeds LS10 1BS
Product showrooms
Fax 0870 608 8 6060870 608 8 608Nationwide support on one number - call the Customer Information Centre on