reactive power management and voltage control

26
Reactive Power Management and Voltage Control First experts group session C8-WG04/Gah RPM Brussels, 25/02/2016 Koen Vandermot

Upload: lamthien

Post on 14-Feb-2017

236 views

Category:

Documents


4 download

TRANSCRIPT

Page 1: Reactive Power Management and Voltage Control

Reactive Power Management and Voltage Control

First experts group session

C8-WG04/Gah RPMBrussels, 25/02/2016

Koen Vandermot

Page 2: Reactive Power Management and Voltage Control

1. Context and Related network codes

2. Requirements for Generators

3. Demand Connection Code

4. Agenda next Experts Group meeting

Experts Group - Network codes on Reactive Power Management and Voltage Control - Brussels - 25/02/2016

Agenda

* Reactive Power Management and Voltage Control (RPM & VC)

Page 3: Reactive Power Management and Voltage Control

Context and Related network codes

Page 4: Reactive Power Management and Voltage Control

Switch centralized production → decentralized production

moments with VERY LOW loading of TSO lines/cables AND almost NO centralized production (summer/interseason)

Reactive absorption needs ↑, while absorption capabilities ↓

Higher interconnectivity with other TSO grids

Moments with VERY HIGH loading of lines/cables AND almost NO centralized production (winter/interseason)

Reactive injection needs ↑, while injection capabilities ↓

Reactive power management becomes 2 times more complex

Facing new challenges in RPM & VC

Experts Group - Network codes on Reactive Power Management and Voltage Control - Brussels - 25/02/2016

Page 5: Reactive Power Management and Voltage Control

Facing new challenges in RPM & VC

Experts Group - Network codes on Reactive Power Management and Voltage Control - Brussels - 25/02/2016

P

QPmax,2009

Pmin,2009

Pmax,2013

Pmin,2013

Shift in reactive needs of the Belgian System

Page 6: Reactive Power Management and Voltage Control

Facing new challenges in RPM & VC

Experts Group - Network codes on Reactive Power Management and Voltage Control - Brussels - 25/02/2016

• Decrease of the number of centralized units in the TSO grid

• Decrease of the number of running hours of the production units that participate in reactive power management

Decrease of reactive power capabilities @ almost all moments

0

2500

5000

7500

10000

2009 2010 2011 2012 2013 2014

P ins

talle

d(M

W)

Installed capacity

NuclearFossil fuelsRES

source: ENTSOe

Percentage of time when Mvar contracted Pus run

Page 7: Reactive Power Management and Voltage Control

Future use of reactive capabilities for reactive needs

Future use of reactive capabilities for reactive needs

Future available reactive

capabilities

Future available reactive

capabilities

Future reactive

needs and reactive

capabilities

Future reactive

needs and reactive

capabilities

Network Codes related to RPM & VC

Experts Group - Network codes on Reactive Power Management and Voltage Control - Brussels - 25/02/2016

Network codes

Network codes

RfGRfG

DCCDCC

HVDCHVDC

OSOS

E&RE&R

Page 8: Reactive Power Management and Voltage Control

RPM & VC is a shared responsibility

Experts Group - Network codes on Reactive Power Management and Voltage Control - Brussels - 25/02/2016

1. Comparison between FTR-C10/11 and NC RfG + first interpretation + detection of possible quick wins(today’s discussion)

2. See what additional possibilities this gives @ TSO-DSO level on short term and on long term(Synergrid study/Expert View)

3. Discussion of first results and on extra requirements for1. PGM owners (with FB on quick-wins)2. Demand facilities3. Distribution Grid Operators (DSOs + CDSOs)4. Transmission Grid Operators(Next Experts Groups)

4. How to use the available reactive capabilities to ensure secure operation(Next Experts Groups)

RfGRfG

DCCDCC

OSOS E&RE&R

Page 9: Reactive Power Management and Voltage Control

Requirements for Generators

1. Hypotheses2. “As Is” (FTR/RTF and C10/11)3. “To Be” (NC RfG)4. Interpretation & Implementation Goal

Page 10: Reactive Power Management and Voltage Control

• Hypothesis: A/B/C/D classification start point as discussed in previous Experts Groups

• FTR/RTF vs NC RfG

• Interpretation/Goal

• Action points

Approach

Experts Group - Network codes on Reactive Power Management and Voltage Control - Brussels - 25/02/2016

Draft thresholds for BE-implementation of Network Codes

Clear game changers

Latitudes & limitations in

Network Codes

Alignment with existing

Belgian texts

Topics for BE-implementation of Network Codes (Frequency,

Voltage, Information Exchanges, …)

Iterative process

(expected end 2016)

Type A17%

Type B  DSO connected

28%

Type B TSO connected

6%

Type C14%

Type D ‐SPGM21%

Type D ‐ PPM14%

2025 – expected/constrained progress

Page 11: Reactive Power Management and Voltage Control

Action points:

Type A

Experts Group - Network codes on Reactive Power Management and Voltage Control - Brussels - 25/02/2016

HypothesisPinstalled

FTR/RTF C10/11NC RfG Interpretation/Goal

SPGM PPM SPGM PPM

800W - 250kW

Voltage stabilityDefined by ∆V-frequency profile (-7.5% to +7.5% @ generator terminal)

Must be capable to permanently

operate at U+/- 10% (at connection

point)

Nothing specifiedgeneral Synergrid

requirements(reference: standards)

Reactive power capabilities

Nothing specified to be discussed with

SOCosphi>0,95 Nothing specified

general Synergridrequirements, based on

realistic capabilities (reference: standards)

Voltage/reactive power control

At least 2 set points (agreement between

owner and SO) Specific requirements

on Qref control (fast-slow)

Nothing specified

Nothing specifiedgeneral Synergrid

requirements(reference: standards)

Shall be included in next Synergrid C10/11

Goal: enlarge RPM & VC possibilities in DS

Page 12: Reactive Power Management and Voltage Control

∆V-frequency profile

Experts Group - Network codes on Reactive Power Management and Voltage Control - Brussels - 25/02/2016

Page 13: Reactive Power Management and Voltage Control

HypothesisPinstalled

FTR/RTF C10/11NC RfG Interpretation/Goal

SPGM PPM SPGM PPM

250kW – 25MW

Voltage stability

As in type A

Must be capable to permanently operate at U+/-

10% (at connection point)

Nothing specified

TSO grid user: specified by TSO DSO grid user: general Synergrid

requirements(reference: standards)

Reactive power

capabilities

to be discussed with

SO

> 1MVA: Q-capability

range-0,1 Pnom … 0,33 Pnom

To be specified by the relevant SO

TSO grid user: specified by TSO DSO grid user: general Synergrid

requirements(reference: standards)

Voltage/reactive power control

At least 2 set points (agreement between owner and SO)

Specific requirements on Qref control (fast-slow)

> 1MVA: multiple setpoints (Q or

cosphi) possible

> 2,5 MVA:Real time tele-

operation possible, for

more dynamic voltage control

Constant V (alternator

terminal) @ a selectable set point over the

entire operation range

Nothing specified

TSO grid user: Constant V (alternator terminal) @ a selectable set point over the entire operation

range

DSO grid user: Dynamic Q- or cosphi setpoint (remote control

above given kVA threshold)

Type B

Experts Group - Network codes on Reactive Power Management and Voltage Control - Brussels - 25/02/2016

Action points: Shall be included in next Synergrid C10/11

Goal: enlarge RPM & VC possibilities in DS

Page 14: Reactive Power Management and Voltage Control

HypothesisPinstalled

FTR/RTF NC RfG Interpretation/GoalSPGM PPM SPGM PPM

25MW – 75MW

Voltage stability

As in type B Auto disconnection for V-levels (SO specified) Terms and settings (SO/TSO specified)

Auto disconnection for V-levels (SO specified) Terms and settings (SO/TSO specified)

Reactive power

capabilities

-10% and +45% of Pnom (for each

voltage between 0.9 and 1.05 Vexpl.)

SO specifies compensation for HV lines or cables

@ max. capacity: SO/TSO specifies

U-Q/Pmax-profile (SO/TSO specified)

Within specific boundaries (Q/Pmax=0.95)

@ connection point Capable of moving

to any point in U-Q/Pmax

Below max. capacity: capable of operating @ every point in PQ-diagram of the alternator

SO specifies compensation for HV lines or cables

@ max. capacity: SO/TSO specifies

U-Q/Pmax-profile (SO/TSO specified)

Within specific boundaries (Q/Pmax=0.75)

@ connection point Capable of moving

to any point in U-Q/Pmax

Below max. capacity: SO/TSO specifies P-

Q/Pmax profile Within specific

boundaries Capable of moving

to any point in P-Q/Pmax

Compensation of the no-load-losses

Make the U-Q/Pmax-profile more symmetric: To solve future

problems for RPM & VC

To align more with the available technology (e.g. rotated frame)

Compensation of the no-load-losses

Make the U-Q/Pmax-profile more symmetric: To solve future

problems for RPM & VC

To align more with the available technology

Type C

Experts Group - Network codes on Reactive Power Management and Voltage Control - Brussels - 25/02/2016

Goal: symmetrize reactive power capabilities by win-win

Page 15: Reactive Power Management and Voltage Control

VoltageRange

Max. 0.95 or 0.75

RfG – U-Q/Pmax profile boundaries

Experts Group - Network codes on Reactive Power Management and Voltage Control - Brussels - 25/02/2016

Q/Pmax

U (pu)

Art. 18.2Art. 18.2

Fixed Outer Envelope

0.65-0.5

0.875

1.100

To be determined ?

1.050

0.900

-0.1 0.45

Actual FTR

Q/Pmax Range

Inner Envelope

Max. 0.225pu

Page 16: Reactive Power Management and Voltage Control

VESTAS V112 – 3.3MW capability @ LV terminals

Experts Group - Network codes on Reactive Power Management and Voltage Control - Brussels - 25/02/2016

Page 17: Reactive Power Management and Voltage Control

HypothesisPinstalled

FTR/RTF NC RfG Interpretation/GoalSPGM PPM SPGM PPM

25MW – 75MW

Voltage/reactive power control

Capability to adapt Q on demand of SO(AVR - voltage @ connection point with selectable constant droop)

Equipped with OEL, UEL and PSS

Auto Qnet adaptation so that relative sensitivity coefficient is within 18 and 25

As in type B

Specific requirements on reactive power control modes: V-control Q-control cos phi control

automatic voltage regulation within U-

Q/Pmax profile (i.e AVR + OEL, UEL, PSS)

voltage @ connection point with selectable

constant droop

No position yet

Priority between active or reactive power

Nothing specified Nothing specifiedSpecified by the relevant

TSONothing specified

Specified by the relevant TSO

Type C

Experts Group - Network codes on Reactive Power Management and Voltage Control - Brussels - 25/02/2016

Action points?To be discussed

Keep control possibilities

Page 18: Reactive Power Management and Voltage Control

HypothesisPinstalled

FTR/TFR NC RfG Interpretation/GoalSPGM PPM SPGM PPM

25MW – 75MW

Voltage/reactive power control

Capability to adapt Q on demand of SO(AVR - voltage @ connection point with selectable constant droop)

Equipped with OEL, UEL and PSS

Auto Qnet adaptation so that relative sensitivity coefficient is within 18 and 25

As in type B

Specific requirements on reactive power control modes: V-control Q-control cos phi control

automatic voltage regulation within U-

Q/Pmax profile (i.e AVR + OEL, UEL, PSS)

voltage @ connection point with selectable

constant droop

automatic voltage regulation within U-

Q/Pmax profile (i.e AVR + OEL, UEL, PSS)

voltage @ connection point with selectable

constant droop

Priority between active or reactive power

Nothing specified Nothing specifiedSpecified by the relevant

TSONothing specified

Specified by the relevant TSO

Type D

Experts Group - Network codes on Reactive Power Management and Voltage Control - Brussels - 25/02/2016

HypothesisPinstalled

FTR/RTF NC RfG Interpretation/GoalSPGM PPM SPGM PPM

≥ 75MW

Voltage stability As in type C As in type C As in type C As in type C As in type CReactive power

capabilitiesAs in type C As in type C As in type C As in type C As in type C

Voltage/reactive power control

As in type C

As in type C Parameters

and settings of V-control system (AVR) agreed between SO and owner in coordination by TSO, containing BW limitation, UEL, OEL, PSS and stator current limiter

As in type C

automatic voltage regulation within U-Q/Pmax profile (i.e AVR + OEL, UEL,

PSS) voltage @

connection point with selectable constant droop

No position yet

Priority between active or reactive

power- As in type C As in type C As in type C As in type C

To be discussed

Page 19: Reactive Power Management and Voltage Control

• NC RfG: art. 13, 14, 15, 16, 17, 18, 19, 20, 21, 22, 23, 24 & 25

• NC RfG specifies only the requirements, doesn’t indicate how this requirements should be used operationally and doesn’t specify how ancillary services should be rewarded

• FTR/RTF & C10/11 requirements are a minimum on top of the minimal requirements set by the NC RfG.

• Goal:

• Symmetrize the reactive power capabilities if technical possibilities allow to and without expensive additional cost

• Enlarge reactive power control possibilities if technical possibilities allow to especially on distribution system connected PGMs

Belgian completion

Experts Group - Network codes on Reactive Power Management and Voltage Control - Brussels - 25/02/2016

Page 20: Reactive Power Management and Voltage Control

Demand Connection Code

1. Hypotheses2. “As Is” (FTR/RTF)3. “To Be” (NC DCC)4. Interpretation & Implementation Goal

Page 21: Reactive Power Management and Voltage Control

NC DCC

Experts Group - Network codes on Reactive Power Management and Voltage Control - Brussels - 25/02/2016

Hypothesis FTR/RTF NC DCC Interpretation/Goal

Transmissiongrid

connected demand facilities

• No specific requirements• The demand facility owner has

the right to have a reactive load (cap. or ind.) of 32.90% Ploadfor each time interval (min. 3.29% Ponderschreven) cos φ 0.95

• Reactive power range specified by TSO is not larger than 48% of the larger import/export capacity cos φ 0.9exception: techno-economical optimization to be proven by demand facility owner

• @ connection point

No position yet

Transmission grid

connected distribution

systems

Possibilities on generators as determined by

RfG

• No specific requirements• The demand facility owner has

the right to have a reactive load (cap. or ind.) of 32.90% Ploadfor each time interval (min. 3.29% Ponderschreven) cos φ 0.95

• Reactive power range specified by TSO is not larger than 48% of the larger import/export capacity cos φ 0.9exception: techno-economical optimization to be proven by joint analysis

• @ connection point• TSO may require the capability to not export

Q when P ≤ 25% should been justified by ajoint analysis

• TSO may require to actively control Q. Control method shall been agreed between TSO and DSO.

Joint analysis to be started with relevantDistribution System Operators (DSOs,

CDSOs)

Page 22: Reactive Power Management and Voltage Control

Art 15.2 ? to be explained by EU

Art 15.2

cos φ = 0.95

3.29% Pond.

NC DCC – art 15.1 & 15.2

Experts Group - Network codes on Reactive Power Management and Voltage Control - Brussels - 25/02/2016

Q

max. import/export capacity

100%25%

cos φ = 0.9

(*) Exceptions are possible but should be proven by demand facility owner or by a joint-analysis for transmission system connected distribution systems

(**) request should be justified by a joint-analysis

P

Actual FTR Specified by TSO

Page 23: Reactive Power Management and Voltage Control

• NC DCC: art. 15

• NC DCC specifies only the requirements, doesn’t indicate how this requirements should be used operationally and doesn’t specify how tariffs should be set.

• FRT/TFR requirements as a start point

• Joint analysis in Synergrid to determine requirements with DSOs

• Joint analysis with relevant CDS owners to determine requirements for CDS

• Goal: reduce reactive power requirements by demand facilities and to enlarge reactive power control capabilities of distribution systems and demand facilities

Belgian completion

Experts Group - Network codes on Reactive Power Management and Voltage Control - Brussels - 25/02/2016

Page 24: Reactive Power Management and Voltage Control

Agenda Experts Group April 2016

Experts Group - Network codes on Reactive Power Management and Voltage Control - Brussels - 25/02/2016

Page 25: Reactive Power Management and Voltage Control

• NC RfG

• Follow-up action points

• First proposal of NC RfG Belgian completion

• NC DCC

• Follow-up action points

• First results on high-level joint-analyses

• NC OS

• Overview of NC OS articles related to RPM & VC

Agenda Experts Group April 2016

Experts Group - Network codes on Reactive Power Management and Voltage Control - Brussels - 25/02/2016

Page 26: Reactive Power Management and Voltage Control

Thank you for your attention!

ELIA SYSTEM OPERATORBoulevard de l'Empereur 201000 Brussels

+32 2 546 70 11info@ elia.be

www.elia.beAn Elia Group company