RATED IN ACCORDANCE TO AHRI STANDARD 365-2009
2
Unit Data - RCA 051Pe
rfor
man
ce
Dat
a
Net Cooling
Total Capacity (Btu/h) 46,500
Electric Power (W) 3,550
Energy Efficiency Ratio (EER) 13.1
Integrated Energy Efficiency Ratio (IEER) 14.4
Elec
tric
al D
ata
Compressor(s)
Qty-Nominal Tons-Type 1 - 3.5 - Scroll
Capacity Reduction 0/50/100 (HGBP) or 0/10-100 (Digital)
Electric Supply (V/Phase/Hz) 230/1/60 208-230/3/60 460/3/60 575/3/60
Run Load Amps (RLA) 21.8 13.7 6.2 4.8
Locked Rotor Amps (LRA) 117 83 41 33
Condenser Fan Motor(s)
Qty - Horsepower (HP) 1 - 1/2
FLA (ea) 6.2 5.4 2.7 1.3
Type PSC
UnitUnit Minimum Circuit Ampacity 33.5 22.5 10.5 7.3
Max. Time Delay Fuse or HACR Breaker 50 35 15 15
Mec
hani
cal D
ata
Condenser Fan(s)Airflow (CFM) 4,000
Diameter (in)-Pitch (deg) 24 - 36
Condenser Coil(s)
Quantity 2
Tube Material - Fin Material Copper - Aluminum
Face Area (sq. ft) 15.4
Rows - Fins per Inch 4 - 12
Refrigerant Connection(s)
Suction Line (in OD) 3/4 (Qty 1)
Liquid Line (in OD) 1/2 (Qty 1)
Optional Hot Gas Bypass (in OD) 3/8 (Qty 1)
Optional Hot Gas Reheat (in OD) 3/8 (Qty 1)
Cabinet
Sheet Metal G90 Galvanized
Finish Polyester Coating
Top Pan Thickness (ga) 16
Sides and Panels Thickness (ga) 18
Bottom Pan Thickness (ga) 16
Refrigerant - R410A Charge based on 25' line set (lbs per circuit) 24
WeightsUnit Weight (lbs) 565
Shipping Weight (lbs) 615
NOTES: 1. Refrigerant connections are actual connection sizes at unit. For line sizing, see “Reference Information” tables on pages 18 - 19.
Cool
ing
Saturated Suction Temperature (°F)
Ambient Temperature (°F)
95.0 100.0 105.0
35.0Total Capacity (Btu/h) 39,000 37,400 36,000
Electric Power (W) 3,370 3,560 3,765
40.0Total Capacity (Btu/h) 42,500 41,000 39,500
Electric Power (W) 3,380 3,575 3,780
45.0Total Capacity (Btu/h) 46,500 44,500 43,000
Electric Power (W) 3,400 3,590 3,800
50.0Total Capacity (Btu/h) 50,500 48,500 47,000
Electric Power (W) 3,420 3,615 3,815
55.0Total Capacity (Btu/h) 54,500 52,500 50,500
Electric Power (W) 3,440 3,635 3,840
RATED IN ACCORDANCE TO AHRI STANDARD 365-2009.
3
Perf
orm
ance
D
ata
Net Cooling
Total Capacity (Btu/h) 55,600
Electric Power (W) 4,244
Energy Efficiency Ratio (EER) 13.1
Integrated Energy Efficiency Ratio (IEER) 14.2
Elec
tric
al D
ata
Compressor(s)
Qty-Nominal Tons-Type 1 - 4.5 - Scroll
Capacity Reduction 0/50/100 (HGBP) or 0/10-100 (Digital)
Electric Supply (V/Phase/Hz) 230/1/60 208-230/3/60 460/3/60 575/3/60
Run Load Amps (RLA) 26.4 16.0 7.8 7.6
Locked Rotor Amps (LRA) 134 110 52 54
Condenser Fan Motor(s)
Qty - Horsepower (HP) 1 - 1/2
FLA (ea) 6.2 5.4 2.7 1.3
Type PSC
UnitUnit Minimum Circuit Ampacity 39.2 25.3 12.3 8.4
Max. Time Delay Fuse or HACR Breaker 60 40 20 15
Mec
hani
cal D
ata
Condenser Fan(s)Airflow (CFM) 4,000
Diameter (in)-Pitch (deg) 24 - 36
Condenser Coil(s)
Quantity 2
Tube Material - Fin Material Copper - Aluminum
Face Area (sq. ft) 15.4
Rows - Fins per Inch 4 - 12
Refrigerant Connection(s)
Suction Line (in OD) 7/8 (Qty 1)
Liquid Line (in OD) 1/2 (Qty 1)
Optional Hot Gas Bypass (in OD) 3/8 (Qty 1)
Optional Hot Gas Reheat (in OD) 3/8 (Qty 1)
Cabinet
Sheet Metal G90 Galvanized
Finish Polyester Coating
Top Pan Thickness (ga) 16
Sides and Panels Thickness (ga) 18
Bottom Pan Thickness (ga) 16
Refrigerant - R410A Charge based on 25' line set (lbs per circuit) 24
WeightsUnit Weight (lbs) 590
Shipping Weight (lbs) 640
NOTES: 1. Refrigerant connections are actual connection sizes at unit. For line sizing, see “Reference Information” tables on pages 18 - 19.
Unit Data - RCA 061 Co
olin
g
Saturated Suction Temperature (°F)
Ambient Temperature (°F)
95.0 100.0 105.0
35.0Total Capacity (Btu/h) 45,000 43,000 42,000
Electric Power (W) 4,250 4,485 4,775
40.0Total Capacity (Btu/h) 53,500 47,000 46,000
Electric Power (W) 4,355 4,530 4,785
45.0Total Capacity (Btu/h) 55,000 51,000 50,000
Electric Power (W) 4,380 4,615 4,865
50.0Total Capacity (Btu/h) 57,000 56,000 54,000
Electric Power (W) 4,435 4,675 4,930
55.0Total Capacity (Btu/h) 62,000 60,000 58,000
Electric Power (W) 4,530 4,770 5,035
RATED IN ACCORDANCE TO AHRI STANDARD 365-2009.
4
Perf
orm
ance
D
ata
Net Cooling
Total Capacity (Btu/h) 74,500
Electric Power (W) 6,422
Energy Efficiency Ratio (EER) 11.6
Integrated Energy Efficiency Ratio (IEER) 12.7
Elec
tric
al D
ata
Compressor(s)
Qty-Nominal Tons-Type 1 - 6.3 - Scroll
Capacity Reduction 0/50/100 (HGBP) or 0/10-100 (Digital)
Electric Supply (V/Phase/Hz) 208-230/3/60 460/3/60 575/3/60
Run Load Amps (RLA) 23.2 11.2 7.7
Locked Rotor Amps (LRA) 164 75 54
Condenser Fan Motor(s)
Qty - Horsepower (HP) 1 - 1/2
FLA (ea) 5.4 2.7 1.3
Type PSC
UnitUnit Minimum Circuit Ampacity 34.4 16.7 11.2
Max. Time Delay Fuse or HACR Breaker 50 25 15
Mec
hani
cal D
ata
Condenser Fan(s)Airflow (CFM) 4,000
Diameter (in)-Pitch (deg) 24 - 36
Condenser Coil(s)
Quantity 2
Tube Material - Fin Material Copper - Aluminum
Face Area (sq. ft) 15.4
Rows - Fins per Inch 4 - 12
Refrigerant Connection(s)
Suction Line (in OD) 7/8 (Qty 1)
Liquid Line (in OD) 1/2 (Qty 1)
Optional Hot Gas Bypass (in OD) 3/8 (Qty 1)
Optional Hot Gas Reheat (in OD) 1/2 (Qty 1)
Cabinet
Sheet Metal G90 Galvanized
Finish Polyester Coating
Top Pan Thickness (ga) 16
Sides and Panels Thickness (ga) 18
Bottom Pan Thickness (ga) 16
Refrigerant - R410A Charge based on 25' line set (lbs per circuit) 25
WeightsUnit Weight (lbs) 610
Shipping Weight (lbs) 660
NOTES: 1. Refrigerant connections are actual connection sizes at unit. For line sizing, see “Reference Information” tables on pages 18 - 19.
Unit Data - RCA 071Co
olin
g
Saturated Suction Temperature (°F)
Ambient Temperature (°F)
95.0 100.0 105.0
35.0Total Capacity (Btu/h) 60,200 58,000 56,000
Electric Power (W) 6,285 6,585 6,905
40.0Total Capacity (Btu/h) 66,000 63,000 61,000
Electric Power (W) 6,415 6,720 7,045
45.0Total Capacity (Btu/h) 71,000 69,000 66,000
Electric Power (W) 6,600 6,860 7,245
50.0Total Capacity (Btu/h) 77,000 74,000 71,000
Electric Power (W) 6,695 7,005 7,330
55.0Total Capacity (Btu/h) 82,000 80,000 77,000
Electric Power (W) 6,840 7,150 7,480
RATED IN ACCORDANCE TO AHRI STANDARD 365-2009.
5
Perf
orm
ance
D
ata
Net Cooling
Total Capacity (Btu/h) 107,500
Electric Power (W) 9,430
Energy Efficiency Ratio (EER) 11.4
Integrated Energy Efficiency Ratio (IEER) 12.8
Elec
tric
al D
ata
Compressor(s)
Qty-Nominal Tons-Type 1 - 9.0 - Scroll
Capacity Reduction 0/50/100 (HGBP) or 0/10-100 (Digital)
Electric Supply (V/Phase/Hz) 208-230/3/60 460/3/60 575/3/60
Run Load Amps (RLA) 30.1 16.7 12.2
Locked Rotor Amps (LRA) 225 114 80
Condenser Fan Motor(s)
Qty - Horsepower (HP) 1 - 1
FLA (ea) 5.4 2.7 2.0
Type PSC
UnitUnit Minimum Circuit Ampacity 41.6 23.1 19.3
Max. Time Delay Fuse or HACR Breaker 70 35 30
Mec
hani
cal D
ata
Condenser Fan(s)Airflow (CFM) 6,200
Diameter (in)-Pitch (deg) 26 - 26
Condenser Coil(s)
Quantity 3
Tube Material - Fin Material Copper - Aluminum
Face Area (sq. ft) 23.1
Rows - Fins per Inch 4 - 12
Refrigerant Connection(s)
Suction Line (in OD) 11/8 (Qty 1)
Liquid Line (in OD) 5/8 (Qty 1)
Optional Hot Gas Bypass (in OD) 1/2 (Qty 1)
Optional Hot Gas Reheat (in OD) 5/8 (Qty 1)
Cabinet
Sheet Metal G90 Galvanized
Finish Polyester Coating
Top Pan Thickness (ga) 16
Sides and Panels Thickness (ga) 18
Bottom Pan Thickness (ga) 16
Refrigerant - R410A Charge based on 25' line set (lbs per circuit) 30
WeightsUnit Weight (lbs) 825
Shipping Weight (lbs) 900
NOTES: 1. Refrigerant connections are actual connection sizes at unit. For line sizing, see “Reference Information” tables on pages 18 - 19.
Unit Data - RCA 101Co
olin
g
Saturated Suction Temperature (°F)
Ambient Temperature (°F)
95.0 100.0 105.0
35.0TTotal Capacity (Btu/h) 89,000 86,000 83,000
Electric Power (W) 8,910 9,435 9,840
40.0Total Capacity (Btu/h) 97,000 94,000 90,000
Electric Power (W) 9,130 9,515 10,075
45.0Total Capacity (Btu/h) 105,000 101,000 98,000
Electric Power (W) 9,300 9,750 10,225
50.0Total Capacity (Btu/h) 113,000 109,000 106,000
Electric Power (W) 9,465 9,935 10,395
55.0Total Capacity (Btu/h) 122,000 118,000 113,000
Electric Power (W) 9,660 10,110 10,680
RATED IN ACCORDANCE TO AHRI STANDARD 365-2009.
6
Perf
orm
ance
D
ata
Net Cooling
Total Capacity (Btu/h) 137,100
Electric Power (W) 12,578
Energy Efficiency Ratio (EER) 10.9
Integrated Energy Efficiency Ratio (IEER) 12.2
Elec
tric
al D
ata
Compressor(s)
Qty-Nominal Tons-Type 1 - 12.0 - Scroll
Capacity Reduction 0/50/100 (HGBP) or 0/10-100 (Digital)
Electric Supply (V/Phase/Hz) 208-230/3/60 460/3/60 575/3/60
Run Load Amps (RLA) 48.1 18.6 15.1
Locked Rotor Amps (LRA) 245 125 100
Condenser Fan Motor(s)
Qty - Horsepower (HP) 1 - 1
FLA (ea) 5.4 2.7 2.0
Type PSC
UnitUnit Minimum Circuit Ampacity 64.0 25.4 22.4
Max. Time Delay Fuse or HACR Breaker 110 40 35
Mec
hani
cal D
ata
Condenser Fan(s)Airflow (CFM) 6,200
Diameter (in)-Pitch (deg) 26 - 26
Condenser Coil(s)
Quantity 3
Tube Material - Fin Material Copper - Aluminum
Face Area (sq. ft) 23.1
Rows - Fins per Inch 4 - 12
Refrigerant Connection(s)
Suction Line (in OD) 13/8 (Qty 1)
Liquid Line (in OD) 5/8 (Qty 1)
Optional Hot Gas Bypass (in OD) 1/2 (Qty 1)
Optional Hot Gas Reheat (in OD) 5/8 (Qty 1)
Cabinet
Sheet Metal G90 Galvanized
Finish Polyester Coating
Top Pan Thickness (ga) 16
Sides and Panels Thickness (ga) 18
Bottom Pan Thickness (ga) 16
Refrigerant - R410A Charge based on 25' line set (lbs per circuit) 35
WeightsUnit Weight (lbs) 900
Shipping Weight (lbs) 975
NOTES: 1. Refrigerant connections are actual connection sizes at unit. For line sizing, see “Reference Information” tables on pages 18 - 19.
Unit Data - RCA 141Co
olin
g
Saturated Suction Temperature (°F)
Ambient Temperature (°F)
95.0 100.0 105.0
35.0Total Capacity (Btu/h) 113,000 110,000 106,000
Electric Power (W) 12,000 12,470 13,085
40.0Total Capacity (Btu/h) 124,000 119,000 115,000
Electric Power (W) 12,150 12,845 13,340
45.0Total Capacity (Btu/h) 133,000 129,000 124,000
Electric Power (W) 12,535 13,005 13,615
50.0Total Capacity (Btu/h) 143,000 139,000 134,000
Electric Power (W) 12,710 13,295 13,905
55.0Total Capacity (Btu/h) 153,000 148,000 144,000
Electric Power (W) 13,070 13,710 14,210
RATED IN ACCORDANCE TO AHRI STANDARD 365-2009.
7
Unit Data - RCA 171Pe
rfor
man
ce
Dat
a
Net Cooling
Total Capacity (Btu/h) 165,900
Electric Power (W) 13,598
Energy Efficiency Ratio (EER) 12.2
Integrated Energy Efficiency Ratio (IEER) 13.6
Elec
tric
al D
ata
Compressor(s)
Qty-Nominal Tons-Type 1 - 13.5 - Scroll
Capacity Reduction 0/50/100 (HGBP) or 0/10-100 (Digital)
Electric Supply (V/Phase/Hz) 208-230/3/60 460/3/60 575/3/60
Run Load Amps (RLA) 51.3 23.1 19.9
Locked Rotor Amps (LRA) 300 150 109
Condenser Fan Motor(s)
Qty - Horsepower (HP) 2 - 1
FLA (ea) 3.4 / 5.4 1.7 / 2.7 2.0/2.0
Type PSC
UnitUnit Minimum Circuit Ampacity 74.8 33.4 28.9
Max. Time Delay Fuse or HACR Breaker 125 50 45
Mec
hani
cal D
ata
Condenser Fan(s)Airflow (CFM) 12,400
Diameter (in)-Pitch (deg) 26 - 32
Condenser Coil(s)
Quantity 4
Tube Material - Fin Material Copper - Aluminum
Face Area (sq. ft) 30.8
Rows - Fins per Inch 4 - 12
Refrigerant Connection(s)
Suction Line (in OD) 13/8 (Qty 1)
Liquid Line (in OD) 7/8 (Qty 1)
Optional Hot Gas Bypass (in OD) 5/8 (Qty 1)
Optional Hot Gas Reheat (in OD) 5/8 (Qty 1)
Cabinet
Sheet Metal G90 Galvanized
Finish Polyester Coating
Top Pan Thickness (ga) 16
Sides and Panels Thickness (ga) 18
Bottom Pan Thickness (ga) 16
Refrigerant - R410A Charge based on 25' line set (lbs per circuit) 50
WeightsUnit Weight (lbs) 1,250
Shipping Weight (lbs) 1,345
NOTES: 1. Refrigerant connections are actual connection sizes at unit. For line sizing, see “Reference Information” tables on pages 18 - 19.
Cool
ing
Saturated Suction Temperature (°F)
Ambient Temperature (°F)
95.0 100.0 105.0
35.0Total Capacity (Btu/h) 144,000 138,000 133,000
Electric Power (W) 12,265 12,865 13,540
40.0Total Capacity (Btu/h) 157,000 151,000 146,000
Electric Power (W) 12,400 13,015 13,670
45.0Total Capacity (Btu/h) 170,000 164,000 158,000
Electric Power (W) 12,560 13,170 13,820
50.0Total Capacity (Btu/h) 183,000 177,000 171,000
Electric Power (W) 12,775 13,390 14,015
55.0Total Capacity (Btu/h) 198,000 191,000 185,000
Electric Power (W) 12,980 13,560 14,180
RATED IN ACCORDANCE TO AHRI STANDARD 365-2009.
8
Unit Data - RCA 201Pe
rfor
man
ce
Dat
a
Net Cooling
Total Capacity (Btu/h) 192,000
Electric Power (W) 16,271
Energy Efficiency Ratio (EER) 11.8
Integrated Energy Efficiency Ratio (IEER) 13.2
Elec
tric
al D
ata
Compressor(s)
Qty-Nominal Tons-Type 1 - 15.0 - Scroll
Capacity Reduction 0/50/100 (HGBP) or 0/10-100 (Digital)
Electric Supply (V/Phase/Hz) 208-230/3/60 460/3/60 575/3/60
Run Load Amps (RLA) 55.8 26.9 23.7
Locked Rotor Amps (LRA) 340 173 132
Condenser Fan Motor(s)
Qty - Horsepower (HP) 2 - 1
FLA (ea) 3.4 / 5.4 1.7 / 2.7 2.0/2.0
Type PSC
UnitUnit Minimum Circuit Ampacity 78.8 40.0 57.6
Max. Time Delay Fuse or HACR Breaker 125 60 80
Mec
hani
cal D
ata
Condenser Fan(s)Airflow (CFM) 12,400
Diameter (in)-Pitch (deg) 26 - 32
Condenser Coil(s)
Quantity 4
Tube Material - Fin Material Copper - Aluminum
Face Area (sq. ft) 30.8
Rows - Fins per Inch 4 - 12
Refrigerant Connection(s)
Suction Line (in OD) 13/8 (Qty 1)
Liquid Line (in OD) 7/8 (Qty 1)
Optional Hot Gas Bypass (in OD) 5/8 (Qty 1)
Optional Hot Gas Reheat (in OD) 3/4 (Qty 1)
Cabinet
Sheet Metal G90 Galvanized
Finish Polyester Coating
Top Pan Thickness (ga) 16
Sides and Panels Thickness (ga) 18
Bottom Pan Thickness (ga) 16
Refrigerant - R410A Charge based on 25' line set (lbs per circuit) 58
WeightsUnit Weight (lbs) 1,300
Shipping Weight (lbs) 1,400
NOTES: 1. Refrigerant connections are actual connection sizes at unit. For line sizing, see “Reference Information” tables on pages 18 - 19.
Cool
ing
Saturated Suction Temperature (°F)
Ambient Temperature (°F)
95.0 100.0 105.0
35.0Total Capacity (Btu/h) 167,000 161,000 155,000
Electric Power (W) 14,500 15,230 16,020
40.0Total Capacity (Btu/h) 182,000 176,000 170,000
Electric Power (W) 14,740 15,415 16,175
45.0Total Capacity (Btu/h) 197,000 191,000 185,000
Electric Power (W) 14,955 15,665 16,355
50.0Total Capacity (Btu/h) 213,000 207,000 199,000
Electric Power (W) 15,170 15,865 16,635
55.0Total Capacity (Btu/h) 230,000 223,000 215,000
Electric Power (W) 15,390 16,100 16,850
RATED IN ACCORDANCE TO AHRI STANDARD 365-2009.
9
Unit Data - RCA 271Pe
rfor
man
ce
Dat
a
Net Cooling
Total Capacity (Btu/h) 241,300
Electric Power (W) 22,343
Energy Efficiency Ratio (EER) 10.8
Integrated Energy Efficiency Ratio (IEER) 12.4
Elec
tric
al D
ata
Compressor(s)
Qty-Nominal Tons-Type 1 - 21.0 - Tandem Scroll
Capacity Reduction 0/50/100 (HGBP) or 0/10-100 (Digital)
Electric Supply (V/Phase/Hz) 208-230/3/60 460/3/60 575/3/60
Run Load Amps (RLA) 33.3 17.9 12.8
Locked Rotor Amps (LRA) 239 125 80
Condenser Fan Motor(s)
Qty - Horsepower (HP) 2 - 1
FLA (ea) 3.4 / 5.4 1.7 / 2.7 2.0/2.0
Type PSC
UnitUnit Minimum Circuit Ampacity 85.7 45.7 32.8
Max. Time Delay Fuse or HACR Breaker 110 60 45
Mec
hani
cal D
ata
Condenser Fan(s)Airflow (CFM) 12,400
Diameter (in)-Pitch (deg) 26 - 32
Condenser Coil(s)
Quantity 4
Tube Material - Fin Material Copper - Aluminum
Face Area (sq. ft) 30.8
Rows - Fins per Inch 4 - 12
Refrigerant Connection(s)
Suction Line (in OD) 15/8 (Qty 1)
Liquid Line (in OD) 7/8 (Qty 1)
Optional Hot Gas Bypass (in OD) 5/8 (Qty 1)
Optional Hot Gas Reheat (in OD) 7/8 (Qty 1)
Cabinet
Sheet Metal G90 Galvanized
Finish Polyester Coating
Top Pan Thickness (ga) 16
Sides and Panels Thickness (ga) 18
Bottom Pan Thickness (ga) 16
Refrigerant - R410A Charge based on 25' line set (lbs per circuit) 58
WeightsUnit Weight (lbs) 1,400
Shipping Weight (lbs) 1,500
NOTES: 1. Refrigerant connections are actual connection sizes at unit. For line sizing, see “Reference Information” tables on pages 18 - 19.
Cool
ing
Saturated Suction Temperature (°F)
Ambient Temperature (°F)
95.0 100.0 105.0
35.0Total Capacity (Btu/h) 213,000 205,000 197,000
Electric Power (W) 19,315 20,310 21,360
40.0Total Capacity (Btu/h) 232,000 224,000 216,000
Electric Power (W) 19,590 20,570 21,620
45.0Total Capacity (Btu/h) 252,000 243,000 236,000
Electric Power (W) 20,020 21,000 21,895
50.0Total Capacity (Btu/h) 273,000 264,000 254,000
Electric Power (W) 20,360 21,330 22,365
55.0Total Capacity (Btu/h) 294,000 284,000 275,000
Electric Power (W) 20,720 21,700 22,730
RATED IN ACCORDANCE TO AHRI STANDARD 365-2009.
10
Unit Data - RCA 361Pe
rfor
man
ce
Dat
a
Net Cooling
Total Capacity (Btu/h) 288,600
Electric Power (W) 24,879
Energy Efficiency Ratio (EER) 11.6
Integrated Energy Efficiency Ratio (IEER) 12.8
Elec
tric
al D
ata
Compressor(s)
Qty-Nominal Tons-Type 1 - 24.0 - Tandem Scroll
Capacity Reduction 0/50/100 (HGBP) or 0/10-100 (Digital)
Electric Supply (V/Phase/Hz) 208-230/3/60 460/3/60 575/3/60
Run Load Amps (RLA) 48.1 18.6 15.1
Locked Rotor Amps (LRA) 245 125 100
Condenser Fan Motor(s)
Qty - Horsepower (HP) 4 - 1
FLA (ea) 3.4 / 3.4 / 5.4 / 5.4 1.7 / 1.7 / 2.7 / 2.7 2.0 / 2.0 / 2.0 / 2.0
Type PSC
UnitUnit Minimum Circuit Ampacity 125.6 51.6 41.1
Max. Time Delay Fuse or HACR Breaker 150 70 50.0
Mec
hani
cal D
ata
Condenser Fan(s)Airflow (CFM) 28,000
Diameter (in)-Pitch (deg) 26 - 32
Condenser Coil(s)
Quantity 4
Tube Material - Fin Material Copper - Aluminum
Face Area (sq. ft) 70.0
Rows - Fins per Inch 2 - 14
Refrigerant Connection(s)
Suction Line (in OD) 15/8 (Qty 1)
Liquid Line (in OD) 11/8 (Qty 1)
Optional Hot Gas Bypass (in OD) 7/8 (Qty 1)
Optional Hot Gas Reheat (in OD) 7/8 (Qty 1)
Cabinet
Sheet Metal G90 Galvanized
Finish Polyester Coating
Top Pan Thickness (ga) 16
Sides and Panels Thickness (ga) 18
Bottom Pan Thickness (ga) 16
Refrigerant - R410A Charge based on 25' line set (lbs per circuit) 65
WeightsUnit Weight (lbs) 1,700
Shipping Weight (lbs) 1,820
NOTES: 1. Refrigerant connections are actual connection sizes at unit. For line sizing, see “Reference Information” tables on pages 18 - 19.
Cool
ing
Saturated Suction Temperature (°F)
Ambient Temperature (°F)
95.0 100.0 105.0
35.0Total Capacity (Btu/h) 240,000 231,000 221,000
Electric Power (W) 23,635 24,700 26,050
40.0Total Capacity (Btu/h) 260,000 251,000 243,000
Electric Power (W) 24,090 25,140 26,135
45.0Total Capacity (Btu/h) 283,000 274,000 264,000
Electric Power (W) 24,410 25,485 26,620
50.0Total Capacity (Btu/h) 306,000 296,000 285,000
Electric Power (W) 24,890 26,010 27,190
55.0Total Capacity (Btu/h) 332,000 320,000 309,000
Electric Power (W) 25,085 26,360 27,570
RATED IN ACCORDANCE TO AHRI STANDARD 365-2009.
11
Unit Data - RCA 421
Perf
orm
ance
D
ata
Net Cooling
Total Capacity (Btu/h) 369,700
Electric Power (W) 33,609
Energy Efficiency Ratio (EER) 11.0
Integrated Energy Efficiency Ratio (IEER) 12.2
Elec
tric
al D
ata
Compressor(s)
Qty-Nominal Tons-Type 1 - 31.5 - Tandem Scroll
Capacity Reduction 0/50/100 (HGBP) or 0/10-100 (Digital)
Electric Supply (V/Phase/Hz) 208-230/3/60 460/3/60 575/3/60
Run Load Amps (RLA) 55.8 26.9 23.8
Locked Rotor Amps (LRA) 340 173 132
Condenser Fan Motor(s)
Qty - Horsepower (HP) 4 - 1
FLA (ea) 3.4 / 3.4 / 5.4 / 5.4 1.7 / 1.7 / 2.7 / 2.7 2.0 / 2.0 / 2.0 / 2.0
Type PSC
UnitUnit Minimum Circuit Ampacity 142.4 70.5 61.4
Max. Time Delay Fuse or HACR Breaker 175 90 85
Mec
hani
cal D
ata
Condenser Fan(s)Airflow (CFM) 28,000
Diameter (in)-Pitch (deg) 26 - 32
Condenser Coil(s)
Quantity 4
Tube Material - Fin Material Copper - Aluminum
Face Area (sq. ft) 70.0
Rows - Fins per Inch 2 - 14
Refrigerant Connection(s)
Suction Line (in OD) 21/8 (Qty 1)
Liquid Line (in OD) 11/8 (Qty 1)
Optional Hot Gas Bypass (in OD) 7/8 (Qty 1)
Optional Hot Gas Reheat (in OD) 7/8 (Qty 1)
Cabinet
Sheet Metal G90 Galvanized
Finish Polyester Coating
Top Pan Thickness (ga) 16
Sides and Panels Thickness (ga) 18
Bottom Pan Thickness (ga) 16
Refrigerant - R410A Charge based on 25' line set (lbs per circuit) 75
WeightsUnit Weight (lbs) 1,770
Shipping Weight (lbs) 1,900
NOTES: 1. Refrigerant connections are actual connection sizes at unit. For line sizing, see “Reference Information” tables on pages 18 - 19.
Cool
ing
Saturated Suction Temperature (°F)
Ambient Temperature (°F)
95.0 100.0 105.0
35.0Total Capacity (Btu/h) 306,000 294,000 285,000
Electric Power (W) 31,685 33,335 34,495
40.0Total Capacity (Btu/h) 334,000 322,000 309,000
Electric Power (W) 32,350 33,705 35,465
45.0Total Capacity (Btu/h) 359,000 350,000 338,000
Electric Power (W) 33,355 34,440 35,885
50.0Total Capacity (Btu/h) 391,000 375,000 365,000
Electric Power (W) 33,900 35,550 36,695
55.0Total Capacity (Btu/h) 421,000 407,000 391,000
Electric Power (W) 34,815 36,165 37,925
RATED IN ACCORDANCE TO AHRI STANDARD 365-2009.
12
NOTES: 1. Condensing unit disconnect is not provided with condensing unit as standard. Disconnect may be obtained from factory as optional equipment or provided by others. 2. Air handler, air handler disconnect, interconnecting control wiring, all refrigerant line piping and sleeve/flashing materials are by others. 3. Suction, hot gas bypass, and hot gas reheat lines should be insulated with 5/8” minimum thickness closed cell foam insulation. Liquid line exposed to high ambient temperatures should be insulated 5/8” minimum thickness closed cell foam insulation.
Typical Split System Installation
Typical Wiring Diagram
L1
L2
L3
Condensing UnitControl Panel
G
R
C
Condensing Unit
Disconnect
Y
24VAC, Switched
Compressor
Supply Fan
24VAC, Common, Unswitched
NOTES: 1. All electrical wiring and connections, including electrical grounding must comply with: a. United States: Refer to NFPA 70- latest revision, National Electrical Code, and local ordinances. b. Canada: Refer to CSA C22.1, Part 1- latest revision, Canadian Electrical Code and local ordinances. 2. Class 1 circuit 3. Condensing unit disconnect is not provided with condensing unit as standard. Disconnect may be obtained from factory as optional equipment or provided by others. 4. Terminal Y2 is only used on dual-circuit units.
Outside Air or Return Air
Liquid Line
Suction Line
Sleeve And Flashing
Disconnect
Interconnecting Control Wiring
Condensing Unit
Optional Hot Gas ReheatOptional Hot Gas Bypass
Air HandlerSupply Air
Disconnect
Trap And Drain Connection
13
Typical Installation with Unit on Bottom
NOTES: 1. To prevent oil migration, lines should slope downwards towards the condensing unit and should slope downward away from the air handler. 2. Vertical risers greater than 4' in height should have a “P” trap installed at the base of the air handler. 3. Vertical risers greater than 20' in height require an extra “P” trap for every 20' of riser height in addition to the “P” trap installed at the base of the air handler. The trap is inverted at the top of the vertical rise.
NOTES: 1. To prevent oil migration, lines should slope downwards towards the condensing unit and should slope downward away from the air handler. 2. Vertical risers greater than 4' in height should have a “P” trap installed at the base of the air handler. 3. Vertical risers greater than 20' in height require an extra “P” trap for every 20' of riser height in addition to the “P” trap installed at the base of the air handler. The trap is inverted at the top of the vertical rise.
Typical Installation with Condensing Unit on Top
Optional Hot Gas Reheat
Optional Hot Gas Bypass
Condensate Trap And PipeLoop To Top Of Coil
Suction
Liquid
Slope Down Towards Condensing Unit
Slope Down From Air Handler
Condensate Trap And Pipe
Suction
Liquid Optional Hot Gas
Reheat
Optional Hot Gas Bypass
14
Dimensions - RCA 051/061/071
A B C D E F G H K L M N P Q R(in) 3.00 47.38 42.25 52.25 0.75 40.38 39.13 2.00 3.50 5.00 9.00 13.00 20.00 3.25 53.38
COIL
CO
IL
CO
NTR
OLS
ELE
CTR
ICA
L
COMPRESSOR
OPTIONAL HOT GAS BYPASS
LIQUIDOPTIONAL HOT GAS REHEAT
SUCTION
G
F
H A K
L MN
P
Q
DC
B
A
Ø E
R
TOP VIEW MULTI-DIMENSIONAL VIEW
SIDE VIEW BACK VIEW
15
Dimensions - RCA 101/141
ØE
J
COMPRESSOR
ELE
CTR
ICA
L
B
FG
HA
A
CD
A
CO
IL
CO
IL
COIL
SUCTION
Q
N
P
KL
M
OPTIONAL HOT GAS REHEAT
LIQUID
OPTIONAL HOT GAS BYPASS
TOP VIEW MULTI-DIMENSIONAL VIEW
SIDE VIEW FRONT VIEW
A B C D E F G H J K L M N P Q(in) 3.00 68.00 45.50 55.50 0.88 41.38 40.13 49.50 4.00 5.56 8.56 8.38 11.38 14.13 74.00
16
Dimensions - RCA 171/201/271
A B C D E F G H J(in) 64.25 52.88 51.38 79.00 22.00 25.50 29.00 16.00 21.00
ELECTRICALCOMPRESSOR
B
C
D A
A
COIL
FG
E
HJ
SUCTIONOPTIONAL HOT GAS REHEAT
LIQUID
OPTIONAL HOT GAS BYPASS
TOP VIEW MULTI-DIMENSIONAL VIEW
SIDE VIEW BACK VIEW
17
Dimensions - RCA 361/421
A B C D E F G H J(in) 101.25 53.63 52.13 84.00 22.00 25.50 29.00 16.00 21.00
GF
A
D A
COMPRESSOR
BC
ELECTRICAL
COIL
SUCTION
OPTIONAL HOT GAS BYPASS
LIQUID
E
J
H
OPTIONAL HOT GAS REHEAT
TOP VIEW MULTI-DIMENSIONAL VIEW
SIDE VIEW BACK VIEW
18
Reference InformationAmbient Temperature Correction Factors
Ambient Temperature (°F) 85 90 95 100 105 110 115Total Capacity (Btu/h) 1.05 1.03 1.00 0.98 0.95 0.91 0.87
Sensible Capacity (Btu/h) 1.03 1.02 1.00 0.99 0.97 0.97 0.93Electric Power (W) 0.95 0.98 1.00 1.03 1.05 1.08 1.11
Recommended Refrigerant Line Sizes- Air Handler Below Condensing Unit (in OD)
Nominal Capacity (Btu/h)0-25 ft. Equivalent Length 26-50 ft. Equivalent Length
Suction Liquid Hot Gas Reheat
Hot Gas Bypass
Suction Liquid Hot Gas Reheat
Hot Gas Bypass
36,000 5/8, 5/8 3/8 1/2 3/8 3/4, 3/4 1/2 1/2 3/848,000 3/4, 3/4 3/8 5/8 3/8 3/4, 3/4 1/2 5/8 3/860,000 3/4, 3/4 1/2 5/8 1/2 7/8, 7/8 1/2 5/8 1/272,000 7/8, 7/8 1/2 5/8 1/2 7/8, 7/8 1/2 5/8 1/284,000 7/8, 7/8 1/2 3/4 1/2 1-1/8, 7/8 1/2 3/4 1/296,000 7/8, 7/8 1/2 3/4 1/2 1-1/8, 7/8 1/2 3/4 1/2
120,000 1-1/8, 7/8 1/2 3/4 5/8 1-3/8, 1-1/8 5/8 3/4 5/8150,000 1-1/8, 1-1/8 5/8 7/8 5/8 1-3/8, 1-1/8 5/8 7/8 5/8180,000 1-1/8, 1-1/8 5/8 7/8 5/8 1-3/8, 1-3/8 5/8 7/8 5/8220,000 1-3/8, 1-3/8 5/8 1-1/8 3/4 1-3/8, 1-3/8 3/4 1-1/8 3/4250,000 1-3/8, 1-3/8 5/8 1-1/8 3/4 1-3/8, 1-3/8 3/4 1-1/8 3/4300,000 1-3/8, 1-3/8 3/4 1-1/8 3/4 1-5/8, 1-3/8 3/4 1-1/8 3/4360,000 1-3/8, 1-5/8 3/4 1-1/8 7/8 1-5/8, 1-5/8 7/8 1-1/8 7/8420,000 1-5/8, 1-5/8 3/4 1-3/8 7/8 1-5/8, 1-5/8 7/8 1-3/8 7/8
Nominal Capacity (Btu/h) 51-75 ft. Equivalent Length 76-100 ft. Equivalent Length
Suction Liquid Hot Gas Reheat
Hot Gas Bypass
Suction Liquid Hot Gas Reheat
Hot Gas Bypass
36,000 7/8, 5/8 1/2 5/8 1/2 7/8, 3/4 1/2 5/8 N/A48,000 7/8, 3/4 1/2 3/4 1/2 7/8, 7/8 1/2 5/8 N/A60,000 1-1/8, 3/4 1/2 3/4 1/2 7/8, 7/8 1/2 3/4 N/A72,000 1-1/8, 7/8 1/2 3/4 5/8 1-1/8, 7/8 5/8 3/4 N/A84,000 1-1/8, 7/8 5/8 7/8 5/8 1-1/8, 7/8 5/8 3/4 N/A96,000 1-1/8, 1-1/8 5/8 7/8 5/8 1-1/8, 1-1/8 5/8 3/4 N/A
120,000 1-1/8, 1-1/8 5/8 7/8 3/4 1-1/8, 1-1/8 5/8 7/8 N/A150,000 1-3/8, 1-1/8 5/8 1-1/8 3/4 1-3/8, 1-1/8 3/4 7/8 N/A180,000 1-3/8, 1-3/8 3/4 1-1/8 3/4 1-3/8, 1-3/8 3/4 1-1/8 N/A220,000 1-3/8, 1-3/8 3/4 1-1/8 7/8 1-5/8, 1-3/8 3/4 1-3/8 N/A250,000 1-3/8, 1-3/8 3/4 1-3/8 7/8 1-5/8, 1-3/8 7/8 1-3/8 N/A300,000 1-5/8, 1-3/8 7/8 1-3/8 1-1/8 2-1/8, 1-5/8 7/8 1-3/8 N/A360,000 2-1/8, 1-5/8 7/8 1-3/8 1-1/8 2-1/8, 1-5/8 1-1/8 1-3/8 N/A420,000 2-1/8, 1-5/8 1-1/8 1-3/8 1-1/8 2-1/8, 1-5/8 1-1/8 1-5/8 N/A
NOTES: 1. Line sizes are calculated assuming single scroll compressors in Models 051-201 and tandem scroll compressors in Models 271-421. Contact the factory for any other compressor configuration. 2. All piping must comply with standard refrigeration piping techniques. Consult the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) Handbook-Refrigeration. 3. Suction, hot gas bypass and hot gas reheat lines should be insulated with a 5/8” minimum thickness closed cell foam insulation. Liquid line exposed to high ambient temperatures should be insulated with a 5/8” minimum thickness closed cell foam insulation. 4. First suction line diameter size is for horizontal runs. Second suction line diameter size is for vertical risers. 5. Maximum suction line vertical lift is 60’. Riser-sized traps are required for every 20’ of vertical riser starting at the lowest point. 6. If ordered, hot gas reheat and hot gas bypass require only one line. 7. Standard hot gas bypass is not recommended for use with greater than 75’ of equivalent line length. Internal hot gas bypass should be used as an alternative. 8. Contact factory for applications with digital scroll compressors. 9. Contact factory for layouts requiring more than 75’ of actual line length.
19
Reference InformationRecommended Refrigerant Line Sizes- Air Handler Level with or Above Condensing Unit (in OD)
Nominal Capacity (Btu/h) 0-25 ft. Equivalent Length 26-50 ft. Equivalent Length
Suction Liquid Hot Gas Reheat
Hot Gas Bypass
Suction Liquid Hot Gas Reheat
Hot Gas Bypass
36,000 5/8 3/8 1/2 3/8 3/4 3/8 1/2 3/848,000 3/4 3/8 5/8 3/8 7/8 1/2 5/8 3/860,000 3/4 1/2 5/8 1/2 7/8 1/2 5/8 1/272,000 7/8 1/2 5/8 1/2 1-1/8 1/2 5/8 1/284,000 7/8 1/2 3/4 1/2 1-1/8 5/8 3/4 1/296,000 7/8 1/2 3/4 1/2 1-1/8 5/8 3/4 1/2
120,000 1-1/8 5/8 3/4 5/8 1-1/8 5/8 3/4 5/8150,000 1-1/8 5/8 7/8 5/8 1-3/8 3/4 7/8 5/8180,000 1-1/8 3/4 7/8 5/8 1-3/8 3/4 7/8 5/8220,000 1-3/8 3/4 1-1/8 3/4 1-3/8 7/8 1-1/8 3/4250,000 1-3/8 3/4 1-1/8 3/4 1-3/8 7/8 1-1/8 3/4300,000 1-3/8 7/8 1-1/8 3/4 1-5/8 7/8 1-1/8 3/4360,000 1-3/8 7/8 1-1/8 7/8 1-5/8 7/8 1-1/8 7/8420,000 1-5/8 1-1/8 1-3/8 7/8 1-5/8 1-1/8 1-3/8 7/8
Nominal Capacity (Btu/h) 51-75 ft. Equivalent Length 76-100 ft. Equivalent Length
Suction Liquid Hot Gas Reheat
Hot Gas Bypass
Suction Liquid Hot Gas Reheat
Hot Gas Bypass
36,000 3/4 3/8 5/8 1/2 3/4 1/2 5/8 N/A48,000 7/8 1/2 3/4 1/2 7/8 1/2 5/8 N/A60,000 7/8 1/2 3/4 1/2 7/8 1/2 3/4 N/A72,000 7/8 1/2 3/4 5/8 7/8 1/2 3/4 N/A84,000 1-1/8 5/8 7/8 5/8 1-1/8 5/8 3/4 N/A96,000 1-1/8 5/8 7/8 5/8 1-1/8 5/8 3/4 N/A
120,000 1-1/8 3/4 7/8 3/4 1-3/8 5/8 7/8 N/A150,000 1-3/8 3/4 1-1/8 3/4 1-3/8 3/4 7/8 N/A180,000 1-5/8 3/4 1-1/8 3/4 1-3/8 3/4 1-1/8 N/A220,000 1-5/8 7/8 1-1/8 7/8 1-5/8 3/4 1-3/8 N/A250,000 1-5/8 7/8 1-3/8 7/8 1-5/8 7/8 1-3/8 N/A300,000 1-5/8 7/8 1-3/8 1-1/8 1-5/8 7/8 1-3/8 N/A360,000 2-1/8 1-1/8 1-3/8 1-1/8 2-1/8 1-1/8 1-3/8 N/A420,000 2-1/8 1-1/8 1-3/8 1-1/8 2-1/8 1-1/8 1-5/8 N/A
NOTES: 1. Line sizes are calculated assuming single scroll compressors in Models 051-201 and tandem scroll compressors in Models 271-421. Contact the factory for any other compressor configuration. 2. All piping must comply with standard refrigeration piping techniques. Consult the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) Handbook-Refrigeration. 3. Suction, hot gas bypass and hot gas reheat lines should be insulated with a 5/8” minimum thickness closed cell foam insulation. Liquid line exposed to high ambient temperatures should be insulated with a 5/8” minimum thickness closed cell foam insulation. 4. Maximum suction line vertical lift is 60’. Loop piping to the top of the coil. 5. Maximum liquid line vertical lift is 60’. 6. If ordered, hot gas reheat and hot gas bypass require only one line. 7. Standard hot gas bypass is not recommended for use with greater than 75’ of equivalent line length. Internal hot gas bypass should be used as an alternative. 8. Contact factory for applications with digital scroll compressors. 9. Contact factory for layouts requiring more than 75’ of actual line length.
Weather-Rite LLC616 North 5th StreetMinneapolis, MN 55401Telephone: +1.612.338.1401Fax: +1.612.338.6783Toll Free: 1.800.589.3691www.weather-rite.com
Printed in the USA WRRCADSGNA 0114 Rev A
Thank you for your business!
Installation Code and Annual Inspections: All installation and service of WEATHER-RITE™ equipment must be performed by a contractor qualified in the installation and service of equipment sold and supplied by Weather-Rite LLC and conform to all requirements set forth in the WEATHER-RITE™ manuals and all applicable governmental au-thorities pertaining to the installation, service, operation and labeling of the equipment. To help facilitate optimum performance and safety, Weather-Rite LLC recommends that a qualified contractor conduct, at a minimum, annual inspections of your WEATHER-RITE™ equipment and perform service where necessary, using only replacement parts sold and supplied by Weather-Rite LLC.Further Information: Applications, engineering and detailed guidance on systems design, installation and equipment performance is available through WEATHER-RITE™ representatives. Please contact us for any further information you may require, including the Installation, Operation and Service Manual.There are references on this document to various trademarks. All trademarks mentioned herein, whether registered or not, are the property of their respective owners. Weather-Rite LLC is not sponsored by or affiliated with any of the trademark or registered trademark owners, and make no representations about them, their owners, their products or services. Weather-Rite LLC is not sponsored by or affiliated with BACnet® or LonWorks®.These products (with the exception of the CGTH and UHA[X][S] 30 - 75) are not for residential use.This document is intended to assist licensed professionals in the exercise of their professional judgment.
© 2014 Weather-Rite LLC All rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form or by any means – graphic, electronic, or mechanical, including photocopying, recording, taping, or information storage and retrieval systems without written permission of Weather-Rite LLC.