range - shrimanshrimanelectrical.com/lnt/motor_starters/motor starters type... · lst switchgea...

8
LST SWITCHGEA Motor Starters Type MN . Direct-On-Line Starters . Star-Delta Starters LARSEN & TOUBRO LIMITED Its all about Imagineering TM

Upload: lamnhan

Post on 13-Apr-2018

221 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: Range - Shrimanshrimanelectrical.com/lnt/motor_starters/Motor Starters Type... · LST SWITCHGEA Motor Starters Type MN. Direct-On-Line Starters. Star-Delta Starters LARSEN & TOUBRO

LST SWITCHGEA

Motor StartersType MN

. Direct-On-Line Starters

. Star-Delta Starters

LARSEN & TOUBRO LIMITED

Its all about ImagineeringTM

Page 2: Range - Shrimanshrimanelectrical.com/lnt/motor_starters/Motor Starters Type... · LST SWITCHGEA Motor Starters Type MN. Direct-On-Line Starters. Star-Delta Starters LARSEN & TOUBRO

Larsen & Toubro Limited, India's largestmanufacturer of low voltage switchgearproducts introduces the new MN range ofstarters. These starters are available inDirect-On-Line (DOL) and Star-Delta versions.This range represents the culmination ofintensive R&D and extensive field trials. MNstarters, comprising MN contactors and MNrelays, provide Overload and Single phasingprotection to your motors.

MN starter family conforms to IS13947-4, IEC 60947-4

StarterRange

Page 3: Range - Shrimanshrimanelectrical.com/lnt/motor_starters/Motor Starters Type... · LST SWITCHGEA Motor Starters Type MN. Direct-On-Line Starters. Star-Delta Starters LARSEN & TOUBRO

Sal ;en* Features. Conform to IS 13947 (Part 4) & IEC 60947-4. Built-in single phasing protection. In Star Delta Starters, Star contactor has

same rating as Hold-on & Delta. Suitable for Industrial & Rural applications. Terminal block for ease of termination. Starter enclosure with IP 54° of protection

Ap"licationsMN starters are available in following versions:

• Direct-On-Line starter

• Semi automatic Star-Delta, starter (SASD). Fully automatic Star-Delta, starter (FASD)

All MN DOL & Star-Delta starters are suitablefor 3-Phase Squirrel Cage motors. MN DOLstarters are available in following ratings:

▪ MN 16 DOL-upto 10 HP (7.5kW). MN 25 DOL-upto 15 HP (11 kW). MN 32 DOL-upto 20 HP (15kW). MN 45 DOL-upto 30 HP (22.5kW). MN 65 DOL-upto 45 HP (33.5kW)

MN Star-Delta starters are available infollowing ratings:

. MN 16 Star-Delta-upto 15 HP (11 kW)

. MN 25 Star-Delta-upto 25 HP (18.5kW)

. MN 32 Star-Delta-upto 35 HP (26kW)

. MN 45 Star-Delta-upto 50 HP (37.5kW)

. MN 65 Star-Delta-upto 75 HP (55kW)

. MN 80 Star-Delta-upto 90 HP (67.5kW)

. MN 110 Star-Delta-upto 125 HP (90kW)

. MN 140 Star-Delta-upto 175 HP (130kW)

MN 45, MN 65, MN 80, MN 110 & MN 140Star-Delta starters are available only in FASDversion.

ConstructionMN starters consist of MNX contactors & MNrelays. The relay is directly mounted on thecontactor. The colour of the sheet steel enclosureis two-toned. The box is powder coated and grayin colour. The cover is powder coated with ivorycolour. The push button is flush mounted in anenclosure cover, which has been given analtogether `new look'.

Operational DetailsRelay Setting

A screwdriver is used to set the relayindicator (which is on the dial) to thefull load current setting. This ensuresoptimum protection under Overload andSingle Phasing of the motor. In case ofStar-Delta Starters, the relay must be setat the values In /j (0.58 In) as given inthe selection table, since the connectedrelay carries only the phase current inMotors having Delta connected winding.

MN DOL starters

. MN 16, 25, 32, 45, 65 DOL startersincorporate type MNX contactors.

• MN 16, 25, 32 DOL startersincorporate MN 2 relays.

• MN 45, 65 DOL starters incorporateMN 5 relays.

MN Star-Delta Starters

MN Star-Delta starters are available insemi automatic and fully automaticversions.

MN 16, 25, 32, 45, 65, 80, 110, 140Star-Delta starters incorporate typeMNX contactors.

• MN 16, 25, 32, Star-Delta startersincorporate MN 2 relays.

• MN 45, 65, 80, 110, Star-Delta startersincorporate MN 5 relays.

• MN 140 Star-Delta startersincorporate MN 12L relays.

In case of SASD Starters, the motorgets connected in Star connection whenthe green button is pressed, afterreleasing the green button motor getsconnected in Delta connection. Thebutton must be released only when themotor reaches its normal speed.

In case of FASD Starter, motor getsconnected in Star connection, whenthe green button is pressed. An electronictimer automatically performs the change-over function from Star to Delta.

1

Page 4: Range - Shrimanshrimanelectrical.com/lnt/motor_starters/Motor Starters Type... · LST SWITCHGEA Motor Starters Type MN. Direct-On-Line Starters. Star-Delta Starters LARSEN & TOUBRO

Different sized holes with grommetsat top & bottom for various cable sizes IP54 Protection class of enclosure

makes it suitable forindustrial and rural applications.

Earthing screw withproper marking

Two-tone colourcombinations with box insteel gray & cover in ivory

Better corrosion resistancethrough powder coated

enclosure

Flush-mountedpush buttons.

Single Phasing Protection

MN relays having phase failuresensitive tripping mechanismprovides reliable protection againstSingle Phasing & Overloadconditions. MN relays arecompensated for variation in ambienttemperature from -5°C to 55°C.

IP 54 degree of protectionCorrosion resistant powder coatedenclosure with IP/54 protection classmakes MN starters most suitable forchemical factories, polluted industrialand dusty agricultural environment.

Terminal BlockMN Star-Delta starters are providedwith terminal block with properterminal marking for ease of wiring.Terminal block can accommodateboth aluminium & copper cables.

Features & BenefitsBase Plate Mounting

MN Star-Delta starters are mountedon base plate that can absorbvibrations and it makes MN startersmaintenance friendly.

Electronic TimerMN Fully Automatic Star-Deltastarters are provided with ElectronicTimer for high repeat accuracy.

Trip Test FacilityThis facility enables the user tomanually check the operation of thetrip mechanism. Move the trip slide inthe direction shown on the relay. Therelay trips with an audible 'Click'sound, indicating that the tripmechanism is in good working order.

Off / Reset Push-ButtonThe relay will trip in case of overloadsor single phasing conditions.

Simultaneously 'Alarm Contact' (97-98) will close. The motor cannot berestarted until the relay has beenreset. To reset the relay, allow thebimetals to cool down sufficiently &push this button to reset the tripcontact (95-96).

If the relay is in reset condition,pressing this push-button will open'Trip Contact'. But now the alarmcontact will not close. This indicateshealthy operation of the relaymechanism. The trip contact willagain close when this button isreleased.

Auto-Manual Reset SwitchThere are two modes of resetavailable : Manual and Auto. Bydefault the relay is in the Manual resetmode and can be converted to Autoreset mode by moving the switch toAuto position marked on the label.

2

Page 5: Range - Shrimanshrimanelectrical.com/lnt/motor_starters/Motor Starters Type... · LST SWITCHGEA Motor Starters Type MN. Direct-On-Line Starters. Star-Delta Starters LARSEN & TOUBRO

Chart for MN DOL starers

Type

Maximum Motor Rating Approx. FullLoad

Current In

RelayRange

( A)Relay Contactor

RecommendedBack-up HRC Fuse

SwitchDisconnector

Fuse Unit

at 415V, 3

50Hz

Type Rating (A)HP KW (A)

2 1.5 3.5 3-5 HF 16 FN32

2.5 1.8 4.8 3-5 HF 16 FN32

3 2.2 5 4.5-7.5 HF 16 FN32

MN 16 4 3 6.2 4.5 - 7.5 HF 20 FN 32DOL 5 3.7 7.5 6-10

MN 2 MNX 18HF 20 FN32

6 4.5 9 6-10 HF 25 FN32

7.5 5.5 11 9 - 15 HF 32 FN 32

10 7.5 14 9 - 15 HF 32 FN 32

7.5 5.5 11 9 - 15 HF 32 FN 32

MN 25 10 7.5 14 9-15 HF 32 FN32

DOL 12.5 9.3 18 14 - 23MN 2 MNX 25

HF 50 FN 63

15 11 21 14 - 23 HF 63 FN 63

15 11 21 20 - 33 HF 63 FN 63MN 32 17 .5 13 24 20 - 33 MN 2 MNX 32 HF 63 FN 63DOL

20 15 28 20 - 33 HN/100 63 FN 100

MN 45 25 18.5 35 30 - 50 HN/100 80 FN 100

DOL 30 22.5 40 30 - 50MN 5 MNX 45

HN/100 80 FN 100

30 22.5 40 30 - 50 HN/100 80 FN 100

MN 65 35 26 47 30 - 50 HN/100 100 FN 100

DOL 40 30 55 45 - 75MN 5 MNX 70

HN/100 100 FN 100

45 33.5 60 45 - 75 HN/100 100 FN 100

Selection Chart for MN DOL Starters

Chart for Star-Delta startersMaximum Motor Rating Approx. Full

Loadphase Relay Recommended

Back-up HRC FuseSwitch

at 415V, 3 O 50HzType Current In Current Range Relay Contactor Disconnectori /,un (A) Fuse Unit

Type Rating (A)HP KW ( A)

10 7.5 14 8.08 6- 10 HF 20 FN 32MN 16SASD/ 12.5 9.3 18 10.4 9 - 15 MN 2 MNX 18 HF 32 FN 32FASD

15 11 21 12.1 9-15 HF 32 FN32

MN 25 20 15 28 16.2 14 - 23 HF 40 FN 63SASD/ 25 18.5 35 20.2 14 - 23

MN 2 MNX 25HF 50 FN 63

MN 32 30 22.5 40 23 20 - 33 HF 63 FN 63SASD/FASD 35 26 47 27 20 - 33

MN 2 MNX 32HN/00 63 FN 100

40 30 55 31.8 30 - 50 HN/00 63 FN 100MN 45FASD 45 33.5 60 34.6 30 - 50 MN 5 MNX 45 HN/00 80 FN 100

50 37.5 66 38.2 30 - 50 HN/00 80 FN 100

60 45 80 46.2 45 - 75 HN/00 100 FN 100

MN 65 65 48.5 87 50 45 - 75 HN/00 100 FN 100FASD 70 52 94 54.5 45 - 75

MN 5 MNX 70HN/00 125 FN 125

75 55 100 57.5 45 - 75 HN/00 125 FN 125MN 80FASD 90 67.5 120 69.2 45 - 75 MN 5 MNX 80 HN/0 160 Fn 200

MN 110 100 75 135 77.9 66 - 110 HN/0 160 FN 200MN 5 MNX 110FASD 125 90 165 95 66 - 110 HN/0 200 FN 200

MN 140 150 110 200 115 90 - 150 HN/1 250 FN 250MN 12L MNX 140FASD 175 130 230 132.8 90 - 150 HN/1 250 FN 250

Selection Chart for MN Star-Delta Starters

3

Page 6: Range - Shrimanshrimanelectrical.com/lnt/motor_starters/Motor Starters Type... · LST SWITCHGEA Motor Starters Type MN. Direct-On-Line Starters. Star-Delta Starters LARSEN & TOUBRO

Ordering Information - MN DOL Starter*Example: MN 16 DOL - 240V with relay range 9-15 A

Ordering Information - SS94015BOBO

Srarter Type Version MN 16 MN 25 MN 32 MN 45 MN 65

Cat. No. SS94351 SS94352 SS94353 SS94017 SS94018Rated control

voltage (Us) V„c Relay Range

3.0 - 5.0 - - - - -

4.5 - 7.5 - - - - -

6.0-10 - - - - -

9.0 - 15 - BOBO - - -240

14 - 23 - BODO - - -

20 - 33 - - BOEO - -

30 - 50 - - - - -

45 - 75 - - - - -

3.0 - 5.0 COSO - - - -

4.5-7.5 COUO - - - -

6.0 - 10 COVO - - - -

9.0 - 15 COBO COBO - - -360

14 - 23 - CODO - - -

20 - 33 - - COED - -

30 - 50 - - - - -

45 - 75 - - - - -

3.0 - 5.0 DOSO - - - -

4.5-7.5 DOUG - - - -

6.0 - 10 DOVO - - - -

9.0 - 15 DOBO DOBO - - -415

14 - 23 - DODO - - -

20 - 33 - - DOEO - -

30 - 50 - - - DOGO -

45 - 75 - - - - DOJO

Ordering Information - MN Star- Delta Starter*Example: MN 16 SASD - 360V with relay range 9-15 A

Ordering Information - SS94019COBO

Srarter Type Version MN 16 MN 25 MN 32 MN 45 MN 65 MN 80 MN 110 MN 140

SASD SS94361 SS94363 SS94365 - - - - -Cat. No. FASD SS94362 SS94364 SS94366 SS94021 SS94022 SS94705 SS94706 SS94707Rated control

voltage (Us) VA,

RelayRange

6.0 - 10 COVO - - - - - - -

9.0 - 15 COBO - - - - - - -

14 - 23 - CODO - - - - - -

20 - 33 - - COED - - - - -360

30-50 - - - - - - - -

45-75 - - - - - - - -

66-110 - - - - - - - -

90 - 150 - - - - - - - -

6.0-10 DOVO - - - - - - -

9.0 - 15 DOBO - - - - - - -

14 - 23 - DODO - - - - - -

20 - 33 - - DOEO - - - - -415

30 - 50 - - - DOGO - - - -

45-75 - - - - DOJO DOJO - -

66 - 110 - - - - - - DOKO -

90 - 150 - - - - - - - DOMO

* Note: These are the stnadard combinations of relay and contactor. Any other combinations can be supplied on request.

4

Page 7: Range - Shrimanshrimanelectrical.com/lnt/motor_starters/Motor Starters Type... · LST SWITCHGEA Motor Starters Type MN. Direct-On-Line Starters. Star-Delta Starters LARSEN & TOUBRO

Overall Dimensions4 MOUNTING HOLES 0 6

128

DOL StartersMN 16, MN 25, MN 32

I

105

139 ►

► 2.34-

l-O

-----------------------------------------

O11

S

200

J•

IOlmI

e•

136

to $l

e•

235

m

352I 153

FASD StartersMN 45, MN 65

026

297 4 MOUNTING HOLES08.5

Alk

FASD StartersMN 80F, MN 110F, MN 140F

212.6

4 MOUNTING HOLES 011

5

Page 8: Range - Shrimanshrimanelectrical.com/lnt/motor_starters/Motor Starters Type... · LST SWITCHGEA Motor Starters Type MN. Direct-On-Line Starters. Star-Delta Starters LARSEN & TOUBRO

For selection and product demonstration, please contact any of our branch offices listed below:

REGISTERED OFFICE AND L&T House A28,lndira NagarHEAD OFFICE Group MIG - 5 Faizabad RoadL&T House, Ballard Estate Padmanabhpur Lucknow 226 016P. O. Box 278 Durg 491 001 Uttar PradeshMumbai 400 001 Tel: 0788-2200105, 2322809 Tel: 0522-4040905 / 902 / 903Tel: 022-67525656 Fax: 0788-2210161 Fax: 0522-2311671Fax: 022-67525858 e-mail: [email protected]: www.Larsentoubro.com Al

Astronauts AvenueBidhan Nagar Plot No. 518

ELECTRICAL STANDARD PRODUCTS (ESP) Durgapur 713 212 4th Main Road501, Sakar Complex Tel: 0343-2536891 / 952 K.K. NagarOpp. Gandhigram Rly. Station Fax: 0343-2536493 Madurai 625 020Ashram Road e-mail: [email protected] Tel: 0452-2537404/303Ahmedabad 380 009 Fax: 0452-2537552Tel: 079-55304007-11, 55304000/1 (Faridabad Switchgear Works) e-mail: [email protected]: 079-26580491 12/4, Delhi-Mathura Roade-mail: [email protected] Faridabad 121 003 North Wing, Level II,

Tel: 0129-2277543, 2275314 Gate 7, Powai38, Cubbon Road, Post Box 5098 Fax: 0129-2275405 Mumbai 400 072Bangalore 560 001 e-mail: [email protected] Tel: 022-67052287 / 2661 / 2737Tel: 080-25020100 / 325 Fax: 022-67051112Fax: 080-25580525 Milanpur Road, Bamuni Maidan e-mail: [email protected]: [email protected] Guwahati 781 021

Tel: 0361-2550565 8B, Farmland, Ramdaspeth131/1, Zone II Fax: 0361-2551308 Behind Hotel RadhikaMaharana Pratap Nagar e-mail: [email protected] Nagpur 440 010Bhopal 462 011 Tel: 0712-2420641 / 24Tel: 0755-4233907 / 8 / 9 5-10-173, Fatah Maidan Road Fax: 0712-2420619Fax: 0755-2769264 R. O. Box 12 e-mail: [email protected]: [email protected] Hyderabad 500 004

Tel: 040-23296468 32, Shivaji Marg, P.O. Box 6223Plot No. 559, Annapurna Complex Fax: 040-23242356 New Delhi 110 015Lewis Road e-mail: [email protected] Tel: 011-41419500 / 1, 41419515Bhubaneswar 751 014 Fax: 011-41419600Tel: 0674-2537301, 2436696 D-24, Prithvi Raj Road e-mail: [email protected]: 0674-2537309 C-Schemee-mail: [email protected] Jaipur 302 001 L&T House, P.O. Box 119

Tel: 0141-2341385/386 191/1, Dhole Patil RoadSCO 32, Sector 26-D Fax: 0141-2373280 Puna 411 001Madhya Marg, P. O. Box 14 e-mail: [email protected] Tel: 020-26135048, 26135611Chandigarh 160 026 Fax: 020-26129586, 26124910Tel: 0172-2790750 / 151 Akashdeep Plaza, 2nd Floor e-mail: [email protected]: 0172-2792764 P. O. Golmurie-mail: [email protected] Jamshedpur 831 003 3rd Floor, Vishwakarma Chambers

Jharkhand Majura Gate, Ring Road10, Club House Road Tel: 0657-2433673 Surat 395 002Chennai 600 002 Fax: 0657-2341250 Tel: 0261-2473726Tel: 044-28462072 / 4 e-mail: [email protected] Fax: 0261-2477078Fax: 044-28462102 e-mail: [email protected]: [email protected] Skybright Bldg.

M.G. Road Radhadaya Complex67, Appuswamy Road Ravipuram Junction Old Padra RoadPost Bag 7156 Emakulam Near Charotar SocietyOpp. Nirmala College Kochi 682 016 Vadodara 390 015Coimbatore 641 045 Tel: 0484-2358513, 2358761 Tel: 0265-6613610/11/12Tel: 0422-2588120, 2588123 Fax: 0484-2358982 Fax: 0265-2336184Fax: 0422-2588148 e-mail: [email protected] e-mail: [email protected]: [email protected]

3-B, Shakespeare Sarani 48-8-16, DwarakanagarKolkata 700 071 Visakhapatnam 530 016Tel: 033-44002301/2/3/4/5, 44002572 Tel: 0891-2755493, 2704928Fax: 033-22822589 Fax: 0891-2746075e-mail: [email protected] e-mail: [email protected]

Product improvement is a continuous process. For the latest information and special applications, please contact any of our offices listed here.

L&T SWITCH

kllir

Electrical Standard Products

Larsen & Toubro LimitedPowai Campus, Mumbai 400 072Tel: 022-6705 0505Fax: 022-67051324 / 1746E-mail: [email protected]: www.LNTEBG.com

LARSEN & TOUBRO LIMITED

Its all about Imagineering'

SP 01936 R

10407