RADON SCREENING SURVEY – FOLLOW-UP GREAT SENECA CREEK ELEMENTARY SCHOOL 13010 Dairymaid Drive, Germantown, Maryland 20874 EXECUTIVE SUMMARY Date of Test Report: 3/31/16 Follow-Up Round of Testing: Initial Follow-up Post Remediation # Rooms Tested 3 # Rooms > 4.0 pCi/L: 0 Low Value: <0.4 High Value: 2.5 Confirmed Rooms ≥ 4.0 pCi/L US EPA Action Level 0 Summary of Sampling Events ≥ 4.0 pCi/L Room Result (pCi/L) 2/15/16 Initial Result (pCi/L) 3/31/16 Follow-Up Average Result (pCi/L) 179 4.9 2.5 3.7 184 0.5 Tampered <0.4 0.5 175 3.5 1.3 2.4

Upload: others

Post on 06-Oct-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: RADON SCREENING SURVEY FOLLOW-UP GREAT SENECA CREEK ...montgomeryschoolsmd.org/uploadedFiles/departments/facilities... · 3015321 3028833 02/29/2016 1:36 pm 03/03/2016 11:34 am Unit

RADON SCREENING SURVEY – FOLLOW-UP GREAT SENECA CREEK ELEMENTARY

SCHOOL

13010 Dairymaid Drive, Germantown, Maryland 20874

EXECUTIVE SUMMARY

Date of Test Report: 3/31/16 Follow-Up

Round of Testing: Initial Follow-up Post Remediation

# Rooms Tested 3

# Rooms > 4.0 pCi/L: 0

Low Value: <0.4

High Value: 2.5

Confirmed Rooms ≥ 4.0 pCi/L US EPA Action Level

0

Summary of Sampling Events ≥ 4.0 pCi/L

Room Result (pCi/L) 2/15/16 Initial

Result (pCi/L) 3/31/16 Follow-Up

Average Result (pCi/L)

179 4.9 2.5 3.7

184 0.5 Tampered <0.4 0.5

175 3.5 1.3 2.4

Page 2: RADON SCREENING SURVEY FOLLOW-UP GREAT SENECA CREEK ...montgomeryschoolsmd.org/uploadedFiles/departments/facilities... · 3015321 3028833 02/29/2016 1:36 pm 03/03/2016 11:34 am Unit

E N G I N E E R S • P L A N N E R S • S C I E N T I S T S • C O N S T R U C T I O N M A N A G E R S

936 RIDGEBROOK ROAD • SPARKS, MD 21152 • 410-316-7800 • (FAX) 410-316-7935

MCPS RADON TESTING

Executive Summary: Great Seneca Creek Elementary School

Date of Test Report: 3/31/2016 Round of Testing: Initial

Follow-up Post Remediation

# Rooms Tested: 3 # Rooms ≥ 4.0 pCi/L: 0 Low Value: < 0.4 High Value: 2.5

Project Status: Retesting completed; use the average of the initial and re-test results in a room to determine if

remediation is necessary.

KC I TE C H N O L O G I E S , IN C . w w w . k c i . c o m Employee-Owned Since 1988

Page 3: RADON SCREENING SURVEY FOLLOW-UP GREAT SENECA CREEK ...montgomeryschoolsmd.org/uploadedFiles/departments/facilities... · 3015321 3028833 02/29/2016 1:36 pm 03/03/2016 11:34 am Unit

E N G I N E E R S • P L A N N E R S • S C I E N T I S T S • C O N S T R U C T I O N M A N A G E R S

936 RIDGEBROOK ROAD • SPARKS, MD 21152 • 410-316-7800 • (FAX) 410-316-7935

March 31, 2016 Mr. Richard Cox Indoor Air Quality Team Leader Montgomery County Public Schools 850 Hungerford Drive Rockville, MD 20850 Re: Radon Testing Services

KCI Job # 12146341.30 Location: Great Seneca Creek Elementary School

13010 Dairymaid Drive Germantown, MD 20874

Dear Mr. Cox: KCI Technologies, Inc. (KCI) is pleased to submit the following report to the Montgomery County Public Schools (MCPS) pursuant to completing a “short-term” 3 day radon test for the Great Seneca Creek Elementary School, located at 13010 Dairymaid Drive in Germantown, Maryland 20874 (subject site). Scope of Services: KCI conducted radon testing at the subject site to evaluate indoor radon levels relative to the USEPA's recommended action level of 4.0 picocuries per Liter (pCi/L) - the level at which EPA recommends that schools take action to reduce the level. KCI conducted the radon testing in accordance with American Association of Radon Scientists and Technologists (AARST) Protocol for Conducting Measurements of Radon and Radon Decay Products in Schools and Large Buildings. A National Radon Safety Board (NRSB) Radon Measurement Specialist (certification #14SS056) supervised the testing. Additional information on radon management and the health effects of radon exposure is available from www.montgomerycountymd.gov/dep/air/radon or www.epa.gov/radon. KCI visited the site on February 29, 2016 and deployed five (5) activated charcoal (AC) radon test kits. KCI deployed radon test kits in frequently-occupied ground contact rooms, and other areas, (if applicable) in accordance with AARST guidance. A floor plan map of the building with the test locations is included as Attachment A of this report. As a quality control measure, KCI included duplicate samples, field blanks, lab transit blanks, and office blanks in accordance with AARST recommendations. In addition, KCI submitted six (6) test kits to Bowser-Morner, Inc. as spike samples. The spiked tests were exposed to a known radon concentration by Bowser-Morner prior to being returned to the laboratory for analysis. KCI returned to the site on March 3, 2016 to retrieve the radon sampling test kits. KCI shipped all radon tests to Accustar Labs for analysis by gamma-ray spectroscopy. Accustar Labs is a NRSB certified analytical laboratory for radon analysis (certification # ARL0007) located at 929 Mount Zion Road,

KC I TE C H N O L O G I E S , IN C . w w w . k c i . c o m Employee-Owned Since 1988

Page 4: RADON SCREENING SURVEY FOLLOW-UP GREAT SENECA CREEK ...montgomeryschoolsmd.org/uploadedFiles/departments/facilities... · 3015321 3028833 02/29/2016 1:36 pm 03/03/2016 11:34 am Unit

Mr. Richard Cox March 31, 2016 Page 3

Lebanon, Pennsylvania.

Evaluation of Testing Conditions:

The operating condition that represents the greatest amount of significantly occupied time for this building is; heating active, with outdoor temperature averages ≤ 65° F.

KCI concludes that the test period reasonably represents normal conditions when the building is significantly occupied. Clear characterization of the radon hazard is most likely to be observed under this normal operating condition. Based on the evaluation of test conditions, this test should reasonably characterize radon hazards.

KCI also conducted observations of field conditions which could affect the results of the test and compiled weather data for the testing period. KCI recorded observations of the following conditions in each room at the time of deployment and collection of the radon test kits:

• Indoor temperature,• HVAC Operation,• Dehumidifier operation,• Humidifier operation,• Ceiling fan operation, and• Open windows or doors.

Results:

The results of the radon test analysis indicated the following:

Radon Concentration Room Result ≥4.0 piC/L none n/a <4.0 piC/L See Attachment B

Notes: D- Duplicate sample

The field blank, office blank, and lab transit blanks had test results of less than or equal to the laboratory detection limit of 0.4 pCi/L. Review of the duplicate sample analysis indicates that adequate laboratory measurement precision was achieved. The Spike sample analysis results indicate the laboratory is operating within statistical control limits.

The sampling locations, field observations, and analytical results are listed on Table 1 (Attachment B). The laboratory analytical results are also attached (Attachment C). Laboratory results and exposure data for the spike samples are also included in Attachment C.

Our professional services have been performed in accordance with customary principles and practices in the field of industrial hygiene and engineering. If you have any questions or comments regarding this report, please feel free to contact me at (410) 316-7800.

KC I TE C H N O L O G I E S , IN C . w w w . k c i . c o m Employee-Owned Since 1988

Page 5: RADON SCREENING SURVEY FOLLOW-UP GREAT SENECA CREEK ...montgomeryschoolsmd.org/uploadedFiles/departments/facilities... · 3015321 3028833 02/29/2016 1:36 pm 03/03/2016 11:34 am Unit

Mr. Richard Cox March 31, 2016 Page 4 Sincerely, James M. Moulsdale Radon Measurement Specialist KCI Technologies, Inc. Attachments: A- Floor Plan with Test Locations B- Table 1-Radon Test Summary Spreadsheet C- Laboratory Analytical Results

KC I TE C H N O L O G I E S , IN C . w w w . k c i . c o m Employee-Owned Since 1988

Page 6: RADON SCREENING SURVEY FOLLOW-UP GREAT SENECA CREEK ...montgomeryschoolsmd.org/uploadedFiles/departments/facilities... · 3015321 3028833 02/29/2016 1:36 pm 03/03/2016 11:34 am Unit

ATTACHMENT A

Floor Plan With Test Locations

Page 7: RADON SCREENING SURVEY FOLLOW-UP GREAT SENECA CREEK ...montgomeryschoolsmd.org/uploadedFiles/departments/facilities... · 3015321 3028833 02/29/2016 1:36 pm 03/03/2016 11:34 am Unit

ATTACHMENT B

Radon Test Summary Spreadsheet

Page 8: RADON SCREENING SURVEY FOLLOW-UP GREAT SENECA CREEK ...montgomeryschoolsmd.org/uploadedFiles/departments/facilities... · 3015321 3028833 02/29/2016 1:36 pm 03/03/2016 11:34 am Unit

Table Notes:

AC- Activated Charcoal

ACI- Air Chek, Inc.

D- Duplicate

FB- Field Blank

KCI- KCI Technologies, Inc.

OB- Office Blank*

PM- Project Manager

QC- Quality Control

*Office blanks were submitted at a rate of 1% for all samples deployed in Phase 10 testing. Officeblanks were not submitted under each school individually.

Page 9: RADON SCREENING SURVEY FOLLOW-UP GREAT SENECA CREEK ...montgomeryschoolsmd.org/uploadedFiles/departments/facilities... · 3015321 3028833 02/29/2016 1:36 pm 03/03/2016 11:34 am Unit

Kit Number Room / Area Result3028797 175 1.33028833 179 2.53028832 184 <0.4

Radon Testing ResultsGreat Seneca Creek Elementary School

Test Period: 02/29/16-03/03/16

Table Note: * Missing or Compromised Sample

Page 10: RADON SCREENING SURVEY FOLLOW-UP GREAT SENECA CREEK ...montgomeryschoolsmd.org/uploadedFiles/departments/facilities... · 3015321 3028833 02/29/2016 1:36 pm 03/03/2016 11:34 am Unit

Kit Number QC Type Result3028836 D (184) 0.73028834 FB (179) 0.4

Radon Testing ResultsGreat Seneca Creek Elementary School

Test Period: 02/29/16-03/03/16

Table Note: * Missing or Compromised Sample

Page 11: RADON SCREENING SURVEY FOLLOW-UP GREAT SENECA CREEK ...montgomeryschoolsmd.org/uploadedFiles/departments/facilities... · 3015321 3028833 02/29/2016 1:36 pm 03/03/2016 11:34 am Unit

ATTACHMENT C

Laboratory Analytical Results

Page 12: RADON SCREENING SURVEY FOLLOW-UP GREAT SENECA CREEK ...montgomeryschoolsmd.org/uploadedFiles/departments/facilities... · 3015321 3028833 02/29/2016 1:36 pm 03/03/2016 11:34 am Unit

Test Exposure Duration: Result (pCi/L)

KCI Technologies

Sparks MD 21152 Germantown MD 20874

Great Senica Creek E. S.

Radon in Air

12146341

936 Ridgebrook Rd 13010 Dairymaid Dr

NRSB ARL0007

NRPP 10511AL

EPA Method #402-R-92-004

NRSB Device Code 10317

NRPP Device Code 6048

Charcoal Canister

Area TestedDevice Number

Log Number

Laboratory Report for: Property Tested: Project #

3015318 3028832 Unit 184 First Floor03/03/2016 11:30 am1:32 pm02/29/2016 <0.4

3015319 3028836 Unit 184 First Floor03/03/2016 11:30 am1:32 pm02/29/2016 0.7

3015320 3028834 Unit 179 First Floor03/03/2016 11:34 am1:36 pm02/29/2016 0.4

3015321 3028833 Unit 179 First Floor03/03/2016 11:34 am1:36 pm02/29/2016 2.5

3015322 3028797 Unit 175 First Floor03/03/2016 11:37 am1:38 pm02/29/2016 1.3

This report may only be transferred to a third party in its entirety. Analytical results relate to the samples AS RECEIVED BY THE LABORATORY. Results shown on this report represent levels of radon gas measured between the dates shown in the room or area of the site identified above as "Property Tested". Incorrect information will affect results. The results may not be construed as either predictive or supportive of measurements conducted in any area of this structure at any other time. AccuStar Labs, its employees and agents are not responsible for the consequences of any action taken or not taken based upon the results reported or any verbal or written interpretation of the results.

03/07/2016 03/08/2016 03/08/2016

PO BOX 990 Jonestown PA 17038 717-274-8310

The uncertainty of this radon measurement is ~+/- 10 %. Factors contributing to uncertainty include statistical variations, daily and seasonal variations in radon concentrations, sample collection techniques and operation of the dwelling. Interference with test conditions may influence the test results.

Page 1 of 1Rev 1402

Distributed by: KCI Technologies, Inc.

A copy of this report was emailed to [email protected]:

03/07/2016

Disclaimer:

Date Received: Date Logged: Date Analyzed: Date Reported:

Report Approved By: _______________________Carolyn D. Koke, President, AccuStar Labs

Report Reviewed By: _________________

Page 13: RADON SCREENING SURVEY FOLLOW-UP GREAT SENECA CREEK ...montgomeryschoolsmd.org/uploadedFiles/departments/facilities... · 3015321 3028833 02/29/2016 1:36 pm 03/03/2016 11:34 am Unit
Page 14: RADON SCREENING SURVEY FOLLOW-UP GREAT SENECA CREEK ...montgomeryschoolsmd.org/uploadedFiles/departments/facilities... · 3015321 3028833 02/29/2016 1:36 pm 03/03/2016 11:34 am Unit
Page 15: RADON SCREENING SURVEY FOLLOW-UP GREAT SENECA CREEK ...montgomeryschoolsmd.org/uploadedFiles/departments/facilities... · 3015321 3028833 02/29/2016 1:36 pm 03/03/2016 11:34 am Unit
Page 16: RADON SCREENING SURVEY FOLLOW-UP GREAT SENECA CREEK ...montgomeryschoolsmd.org/uploadedFiles/departments/facilities... · 3015321 3028833 02/29/2016 1:36 pm 03/03/2016 11:34 am Unit
Page 17: RADON SCREENING SURVEY FOLLOW-UP GREAT SENECA CREEK ...montgomeryschoolsmd.org/uploadedFiles/departments/facilities... · 3015321 3028833 02/29/2016 1:36 pm 03/03/2016 11:34 am Unit
Page 18: RADON SCREENING SURVEY FOLLOW-UP GREAT SENECA CREEK ...montgomeryschoolsmd.org/uploadedFiles/departments/facilities... · 3015321 3028833 02/29/2016 1:36 pm 03/03/2016 11:34 am Unit
Page 19: RADON SCREENING SURVEY FOLLOW-UP GREAT SENECA CREEK ...montgomeryschoolsmd.org/uploadedFiles/departments/facilities... · 3015321 3028833 02/29/2016 1:36 pm 03/03/2016 11:34 am Unit
Page 20: RADON SCREENING SURVEY FOLLOW-UP GREAT SENECA CREEK ...montgomeryschoolsmd.org/uploadedFiles/departments/facilities... · 3015321 3028833 02/29/2016 1:36 pm 03/03/2016 11:34 am Unit
Page 21: RADON SCREENING SURVEY FOLLOW-UP GREAT SENECA CREEK ...montgomeryschoolsmd.org/uploadedFiles/departments/facilities... · 3015321 3028833 02/29/2016 1:36 pm 03/03/2016 11:34 am Unit

E N G I N E E R S • P L A N N E R S • S C I E N T I S T S • C O N S T R U C T I O N M A N A G E R S

936 RIDGEBROOK ROAD • SPARKS, MD 21152 • 410-316-7800 • (FAX) 410-316-7935

MCPS RADON TESTING

Executive Summary: Great Seneca Creek Elementary School

Date of Test Report: 2/15/2016 Round of Testing: Initial

Follow-up Post Remediation

# Rooms Tested: 53 # Rooms ≥ 4.0 pCi/L: 1

Low Value: < 0.3 High Value: 4.9

Rooms with results ≥ 4.0 pCi/L: Room 179 (4.9 pCi/L)

Project Status: Initial testing completed; re-test needed for results ≥ 4.0 pCi/L.

Initial testing completed; missing or compromised samples need re-test.

KC I TE C H N O L O G I E S , IN C . w w w . k c i . c o m Employee-Owned Since 1988

Page 22: RADON SCREENING SURVEY FOLLOW-UP GREAT SENECA CREEK ...montgomeryschoolsmd.org/uploadedFiles/departments/facilities... · 3015321 3028833 02/29/2016 1:36 pm 03/03/2016 11:34 am Unit

E N G I N E E R S • P L A N N E R S • S C I E N T I S T S • C O N S T R U C T I O N M A N A G E R S

936 RIDGEBROOK ROAD • SPARKS, MD 21152 • 410-316-7800 • (FAX) 410-316-7935

February 15, 2016

Mr. Richard Cox Indoor Air Quality Team Leader Montgomery County Public Schools 850 Hungerford Drive Rockville, MD 20850

Re: Radon Testing Services KCI Job # 12146341.25

Location: Great Seneca Creek Elementary School 13010 Dairymaid Drive Germantown, MD 20874

Dear Mr. Cox:

KCI Technologies, Inc. (KCI) is pleased to submit the following report to the Montgomery County Public Schools (MCPS) pursuant to completing a “short-term” 3 day radon test for the Great Seneca Creek Elementary School, located at 13010 Dairymaid Drive in Germantown, Maryland 20874 (subject site).

Scope of Services:

KCI conducted radon testing at the subject site to evaluate indoor radon levels relative to the USEPA's recommended action level of 4.0 picocuries per Liter (pCi/L) - the level at which EPA recommends that schools take action to reduce the level. KCI conducted the radon testing in accordance with American Association of Radon Scientists and Technologists (AARST) Protocol for Conducting Measurements of Radon and Radon Decay Products in Schools and Large Buildings. A National Radon Safety Board (NRSB) Radon Measurement Specialist (certification #14SS056) supervised the testing. Additional information on radon management and the health effects of radon exposure is available from www.montgomerycountymd.gov/dep/air/radon or www.epa.gov/radon.

KCI visited the site on January 19, 2016 and deployed sixty-four (64) activated charcoal (AC) radon test kits. KCI deployed radon test kits in frequently-occupied ground contact rooms, and other areas, (if applicable) in accordance with AARST guidance. A floor plan map of the building with the test locations is included as Attachment A of this report.

As a quality control measure, KCI included duplicate samples, field blanks, lab transit blanks, and office blanks in accordance with AARST recommendations. In addition, KCI submitted six (6) test kits to Bowser-Morner, Inc. as spike samples. The spiked tests were exposed to a known radon concentration by Bowser-Morner prior to being returned to the laboratory for analysis.

KCI returned to the site on January 22, 2016 to retrieve the radon sampling test kits. KCI shipped all radon tests via overnight delivery to Airchek, Inc. for analysis by gamma-ray spectroscopy. Airchek, Inc. is a NRSB certified analytical laboratory for radon analysis (certification # ARL1402) located at 1936

KC I TE C H N O L O G I E S , IN C . w w w . k c i . c o m Employee-Owned Since 1988

Page 23: RADON SCREENING SURVEY FOLLOW-UP GREAT SENECA CREEK ...montgomeryschoolsmd.org/uploadedFiles/departments/facilities... · 3015321 3028833 02/29/2016 1:36 pm 03/03/2016 11:34 am Unit

Mr. Richard Cox February 15, 2016 Page 3 Butler Bridge Road, Mills River, North Carolina. Evaluation of Testing Conditions: The operating condition that represents the greatest amount of significantly occupied time for this building is; heating active, with outdoor temperature averages ≤ 65° F. KCI concludes that the test period reasonably represents normal conditions when the building is significantly occupied. Clear characterization of the radon hazard is most likely to be observed under this normal operating condition. Based on the evaluation of test conditions, this test should reasonably characterize radon hazards. KCI also conducted observations of field conditions which could affect the results of the test and compiled weather data for the testing period. KCI recorded observations of the following conditions in each room at the time of deployment and collection of the radon test kits:

• Indoor temperature, • HVAC Operation, • Dehumidifier operation, • Humidifier operation, • Ceiling fan operation, and • Open windows or doors.

Results: The results of the radon test analysis indicated the following:

Radon Concentration Room Result ≥4.0 piC/L 179 4.9 <4.0 piC/L See Attachment B

Notes: D- Duplicate sample All field blanks, office blank, and lab transit blanks had test results of less than the laboratory detection limit of 0.3 pCi/L. Review of the duplicate sample analysis indicates that adequate laboratory measurement precision was achieved. The Spike sample analysis results indicate the laboratory is operating within statistical control limits. The sampling locations, field observations, and analytical results are listed on Table 1 (Attachment B). The laboratory analytical results are also attached (Attachment C). Laboratory results and exposure data for the spike samples are also included in Attachment C. Our professional services have been performed in accordance with customary principles and practices in the field of industrial hygiene and engineering. If you have any questions or comments regarding this report, please feel free to contact me at (410) 316-7800.

KC I TE C H N O L O G I E S , IN C . w w w . k c i . c o m Employee-Owned Since 1988

Page 24: RADON SCREENING SURVEY FOLLOW-UP GREAT SENECA CREEK ...montgomeryschoolsmd.org/uploadedFiles/departments/facilities... · 3015321 3028833 02/29/2016 1:36 pm 03/03/2016 11:34 am Unit

Mr. Richard Cox February 15, 2016 Page 4 Sincerely, James M. Moulsdale Radon Measurement Specialist KCI Technologies, Inc. Attachments: A- Floor Plan with Test Locations B- Table 1-Radon Test Summary Spreadsheet C- Laboratory Analytical Results

KC I TE C H N O L O G I E S , IN C . w w w . k c i . c o m Employee-Owned Since 1988

Page 25: RADON SCREENING SURVEY FOLLOW-UP GREAT SENECA CREEK ...montgomeryschoolsmd.org/uploadedFiles/departments/facilities... · 3015321 3028833 02/29/2016 1:36 pm 03/03/2016 11:34 am Unit

ATTACHMENT A

Floor Plan With Test Locations

Page 26: RADON SCREENING SURVEY FOLLOW-UP GREAT SENECA CREEK ...montgomeryschoolsmd.org/uploadedFiles/departments/facilities... · 3015321 3028833 02/29/2016 1:36 pm 03/03/2016 11:34 am Unit

ATTACHMENT B

Radon Test Summary Spreadsheet

Page 27: RADON SCREENING SURVEY FOLLOW-UP GREAT SENECA CREEK ...montgomeryschoolsmd.org/uploadedFiles/departments/facilities... · 3015321 3028833 02/29/2016 1:36 pm 03/03/2016 11:34 am Unit

Table Notes:

AC- Activated Charcoal

ACI- Air Chek, Inc.

D- Duplicate

FB- Field Blank

KCI- KCI Technologies, Inc.

OB- Office Blank

PM- Project Manager

QC- Quality Control

Page 28: RADON SCREENING SURVEY FOLLOW-UP GREAT SENECA CREEK ...montgomeryschoolsmd.org/uploadedFiles/departments/facilities... · 3015321 3028833 02/29/2016 1:36 pm 03/03/2016 11:34 am Unit

Kit Number Room / Area Result7721551 100 0.77721511 102 0.97721536 104 1.17721537 104 17721539 106 1.17721515 107 0.87721520 107 0.77721531 110 0.97721544 111 0.57721538 122 27721517 123 < 0.37721523 123 < 0.37721530 124 2.37721529 126 2.17721519 128 0.57721505 130 0.67721547 133 0.77721509 135 0.67716993 137 17716996 138 1.17721522 141 1.17721508 142 1.57721532 144 0.67721506 151 < 0.37721507 155 0.57716992 157 0.67716997 161 0.67721503 165 0.77721510 169 2.37721512 170 2.17721545 172 2.37721513 173 1.77721552 175 3.57721546 176 1.97721502 179 4.97721548 181 1.17721541 * 184 (tampered) 0.57721501 210 0.67721524 221 0.87721549 235 1.37716995 239 1.37721525 258 0.77721542 100B < 0.37721543 100C 0.57721535 100D < 0.37721534 100E < 0.3

Radon Testing ResultsGreat Seneca Creek Elementary School

Test Period: 01/19/16-01/22/16

Table Note: * Missing or Compromised Sample

Page 29: RADON SCREENING SURVEY FOLLOW-UP GREAT SENECA CREEK ...montgomeryschoolsmd.org/uploadedFiles/departments/facilities... · 3015321 3028833 02/29/2016 1:36 pm 03/03/2016 11:34 am Unit

Kit Number Room / Area Result

Radon Testing ResultsGreat Seneca Creek Elementary School

Test Period: 01/19/16-01/22/16

7721527 102D 0.87721550 107A 0.77721540 108B 0.77721516 123A 0.77721504 130A 0.87716994 135A < 0.37716998 137A 17716991 ML849 < 0.37716990 ML850 < 0.37716999 ML859 < 0.3

Table Note: * Missing or Compromised Sample

Page 30: RADON SCREENING SURVEY FOLLOW-UP GREAT SENECA CREEK ...montgomeryschoolsmd.org/uploadedFiles/departments/facilities... · 3015321 3028833 02/29/2016 1:36 pm 03/03/2016 11:34 am Unit

Kit Number QC Type Result7721533 D (100E) < 0.37721526 D (124) 2.57721518 D (130) 0.77721514 D (144) 0.87721521 D (165) 0.67721528 FB (110) < 0.37716988 FB (130A) < 0.37721571 OB (0) < 0.3

Radon Testing ResultsGreat Seneca Creek Elementary School

Test Period: 01/19/16-01/22/16

Table Note: * Missing or Compromised Sample

Page 31: RADON SCREENING SURVEY FOLLOW-UP GREAT SENECA CREEK ...montgomeryschoolsmd.org/uploadedFiles/departments/facilities... · 3015321 3028833 02/29/2016 1:36 pm 03/03/2016 11:34 am Unit

ATTACHMENT C

Laboratory Analytical Results

Page 32: RADON SCREENING SURVEY FOLLOW-UP GREAT SENECA CREEK ...montgomeryschoolsmd.org/uploadedFiles/departments/facilities... · 3015321 3028833 02/29/2016 1:36 pm 03/03/2016 11:34 am Unit

February11,2016

** LABORATORY ANALYSISREPORT **

Radon test result report for:GREAT SENECA CREEK ELEMENTARY SCHOOMAIN

Kit # Room Id Started Ended pCi/L Analyzed7721571 0 2016-01-19 @ 7:00 pm 2016-01-22 @ 2:00 pm < 0.3 2016-01-267721551 100 2016-01-19 @ 2:00 pm 2016-01-22 @ 9:00 am 0.7 ± 0.3 2016-01-277721542 100B 2016-01-19 @ 2:00 pm 2016-01-22 @ 9:00 am < 0.3 2016-01-267721543 100C 2016-01-19 @ 2:00 pm 2016-01-22 @ 9:00 am 0.5 ± 0.2 2016-01-267721535 100D 2016-01-19 @ 2:00 pm 2016-01-22 @ 9:00 am < 0.3 2016-01-267721534 100E 2016-01-19 @ 2:00 pm 2016-01-22 @ 9:00 am < 0.3 2016-01-267721533 100E 2016-01-19 @ 2:00 pm 2016-01-22 @ 9:00 am < 0.3 2016-01-277721511 102 2016-01-19 @ 4:00 pm 2016-01-22 @ 9:00 am 0.9 ± 0.3 2016-01-277721527 102D 2016-01-19 @ 4:00 pm 2016-01-22 @ 9:00 am 0.8 ± 0.3 2016-01-277721536 104 2016-01-19 @ 2:00 pm 2016-01-22 @ 10:00 am 1.1 ± 0.3 2016-01-277721537 104 2016-01-19 @ 2:00 pm 2016-01-22 @ 10:00 am 1.0 ± 0.3 2016-01-277721539 106 2016-01-19 @ 2:00 pm 2016-01-22 @ 9:00 am 1.1 ± 0.3 2016-01-277721515 107 2016-01-19 @ 3:00 pm 2016-01-22 @ 10:00 am 0.8 ± 0.3 2016-01-277721520 107 2016-01-19 @ 3:00 pm 2016-01-22 @ 10:00 am 0.7 ± 0.3 2016-01-277721550 107A 2016-01-19 @ 3:00 pm 2016-01-22 @ 10:00 am 0.7 ± 0.3 2016-01-277721540 108B 2016-01-19 @ 2:00 pm 2016-01-22 @ 10:00 am 0.7 ± 0.3 2016-01-277721528 110 2016-01-19 @ 2:00 pm 2016-01-22 @ 10:00 am < 0.3 2016-01-277721531 110 2016-01-19 @ 2:00 pm 2016-01-22 @ 10:00 am 0.9 ± 0.3 2016-01-277721544 111 2016-01-19 @ 3:00 pm 2016-01-22 @ 10:00 am 0.5 ± 0.2 2016-01-267721538 122 2016-01-19 @ 3:00 pm 2016-01-22 @ 10:00 am 2.0 ± 0.4 2016-01-277721517 123 2016-01-19 @ 3:00 pm 2016-01-22 @ 10:00 am < 0.3 2016-01-267721523 123 2016-01-19 @ 3:00 pm 2016-01-22 @ 10:00 am < 0.3 2016-01-277721516 123A 2016-01-19 @ 3:00 pm 2016-01-22 @ 10:00 am 0.7 ± 0.3 2016-01-277721526 124 2016-01-19 @ 3:00 pm 2016-01-22 @ 10:00 am 2.5 ± 0.4 2016-01-277721530 124 2016-01-19 @ 3:00 pm 2016-01-22 @ 10:00 am 2.3 ± 0.4 2016-01-277721529 126 2016-01-19 @ 3:00 pm 2016-01-22 @ 10:00 am 2.1 ± 0.3 2016-01-277721519 128 2016-01-19 @ 3:00 pm 2016-01-22 @ 10:00 am 0.5 ± 0.2 2016-01-267721505 130 2016-01-19 @ 4:00 pm 2016-01-22 @ 10:00 am 0.6 ± 0.3 2016-01-277721518 130 2016-01-19 @ 4:00 pm 2016-01-22 @ 10:00 am 0.7 ± 0.3 2016-01-277716988 130A 2016-01-19 @ 4:00 pm 2016-01-22 @ 10:00 am < 0.3 2016-01-277721504 130A 2016-01-19 @ 4:00 pm 2016-01-22 @ 10:00 am 0.8 ± 0.3 2016-01-277721547 133 2016-01-19 @ 4:00 pm 2016-01-22 @ 10:00 am 0.7 ± 0.3 2016-01-277721509 135 2016-01-19 @ 4:00 pm 2016-01-22 @ 10:00 am 0.6 ± 0.3 2016-01-277716994 135A 2016-01-19 @ 4:00 pm 2016-01-22 @ 10:00 am < 0.3 2016-01-277716993 137 2016-01-19 @ 3:00 pm 2016-01-22 @ 10:00 am 1.0 ± 0.3 2016-01-277716998 137A 2016-01-19 @ 3:00 pm 2016-01-22 @ 10:00 am 1.0 ± 0.3 2016-01-277716996 138 2016-01-19 @ 3:00 pm 2016-01-22 @ 10:00 am 1.1 ± 0.3 2016-01-27

Air Chek, Inc. 1936 Butler Bridge Rd, Mills River, NC 28759-3892 Phone: (828) 684-0893 Fax: (828) 684-8498

Page 33: RADON SCREENING SURVEY FOLLOW-UP GREAT SENECA CREEK ...montgomeryschoolsmd.org/uploadedFiles/departments/facilities... · 3015321 3028833 02/29/2016 1:36 pm 03/03/2016 11:34 am Unit

February11,2016

** LABORATORY ANALYSISREPORT **

Radon test result report for:GREAT SENECA CREEK ELEMENTARY SCHOOMAIN

Kit # Room Id Started Ended pCi/L Analyzed7721522 141 2016-01-19 @ 3:00 pm 2016-01-22 @ 10:00 am 1.1 ± 0.3 2016-01-277721508 142 2016-01-19 @ 3:00 pm 2016-01-22 @ 10:00 am 1.5 ± 0.3 2016-01-277721532 144 2016-01-19 @ 3:00 pm 2016-01-22 @ 10:00 am 0.6 ± 0.3 2016-01-277721514 144 2016-01-19 @ 3:00 pm 2016-01-22 @ 10:00 am 0.8 ± 0.3 2016-01-277721506 151 2016-01-19 @ 3:00 pm 2016-01-22 @ 10:00 am < 0.3 2016-01-277721507 155 2016-01-19 @ 3:00 pm 2016-01-22 @ 10:00 am 0.5 ± 0.3 2016-01-277716992 157 2016-01-19 @ 3:00 pm 2016-01-22 @ 10:00 am 0.6 ± 0.3 2016-01-277716997 161 2016-01-19 @ 3:00 pm 2016-01-22 @ 10:00 am 0.6 ± 0.3 2016-01-277721503 165 2016-01-19 @ 3:00 pm 2016-01-22 @ 10:00 am 0.7 ± 0.3 2016-01-277721521 165 2016-01-19 @ 3:00 pm 2016-01-22 @ 10:00 am 0.6 ± 0.3 2016-01-277721510 169 2016-01-19 @ 3:00 pm 2016-01-22 @ 10:00 am 2.3 ± 0.4 2016-01-277721512 170 2016-01-19 @ 3:00 pm 2016-01-22 @ 10:00 am 2.1 ± 0.4 2016-01-277721545 172 2016-01-19 @ 3:00 pm 2016-01-22 @ 10:00 am 2.3 ± 0.4 2016-01-277721513 173 2016-01-19 @ 3:00 pm 2016-01-22 @ 10:00 am 1.7 ± 0.4 2016-01-277721552 175 2016-01-19 @ 3:00 pm 2016-01-22 @ 10:00 am 3.5 ± 0.4 2016-01-277721546 176 2016-01-19 @ 3:00 pm 2016-01-22 @ 10:00 am 1.9 ± 0.3 2016-01-267721502 179 2016-01-19 @ 3:00 pm 2016-01-22 @ 10:00 am 4.9 ± 0.4 2016-01-267721548 181 2016-01-19 @ 3:00 pm 2016-01-22 @ 10:00 am 1.1 ± 0.3 2016-01-277721541 184 2016-01-19 @ 3:00 pm 2016-01-22 @ 10:00 am 0.5 ± 0.3 2016-01-277721501 210 2016-01-19 @ 4:00 pm 2016-01-22 @ 10:00 am 0.6 ± 0.3 2016-01-277721524 221 2016-01-19 @ 4:00 pm 2016-01-22 @ 10:00 am 0.8 ± 0.3 2016-01-277721549 235 2016-01-19 @ 4:00 pm 2016-01-22 @ 10:00 am 1.3 ± 0.3 2016-01-277716995 239 2016-01-19 @ 4:00 pm 2016-01-22 @ 10:00 am 1.3 ± 0.3 2016-01-277721525 258 2016-01-19 @ 4:00 pm 2016-01-22 @ 10:00 am 0.7 ± 0.3 2016-01-27

Air Chek, Inc. 1936 Butler Bridge Rd, Mills River, NC 28759-3892 Phone: (828) 684-0893 Fax: (828) 684-8498

Page 34: RADON SCREENING SURVEY FOLLOW-UP GREAT SENECA CREEK ...montgomeryschoolsmd.org/uploadedFiles/departments/facilities... · 3015321 3028833 02/29/2016 1:36 pm 03/03/2016 11:34 am Unit

February11,2016

** LABORATORY ANALYSISREPORT **

Radon test result report for:GREAT SENECA CREEK ELEMENTARY SCHOOPORTABLES

Kit # Room Id Started Ended pCi/L Analyzed7716991 ML849 2016-01-19 @ 4:00 pm 2016-01-22 @ 10:00 am < 0.3 2016-01-277716990 ML850 2016-01-19 @ 4:00 pm 2016-01-22 @ 10:00 am < 0.3 2016-01-277716999 ML859 2016-01-19 @ 4:00 pm 2016-01-22 @ 10:00 am < 0.3 2016-01-27

Air Chek, Inc. 1936 Butler Bridge Rd, Mills River, NC 28759-3892 Phone: (828) 684-0893 Fax: (828) 684-8498

Page 35: RADON SCREENING SURVEY FOLLOW-UP GREAT SENECA CREEK ...montgomeryschoolsmd.org/uploadedFiles/departments/facilities... · 3015321 3028833 02/29/2016 1:36 pm 03/03/2016 11:34 am Unit

February2,2016

** LABORATORY ANALYSISREPORT **

Radon test result report for: MCPS PHASE 5 & 6TRANSIT BLANKS

Kit # Room Id Started Ended pCi/L Analyzed7722194 1 2016-01-19 @ 12:00 pm 2016-01-22 @ 12:00 pm < 0.3 2016-01-277718494 10 2016-01-19 @ 12:00 pm 2016-01-22 @ 12:00 pm < 0.3 2016-01-277718475 11 2016-01-19 @ 12:00 pm 2016-01-22 @ 12:00 pm < 0.3 2016-01-277718495 12 2016-01-19 @ 12:00 pm 2016-01-22 @ 12:00 pm < 0.3 2016-01-277718496 13 2016-01-19 @ 12:00 pm 2016-01-22 @ 12:00 pm < 0.3 2016-01-277718497 14 2016-01-19 @ 12:00 pm 2016-01-22 @ 12:00 pm < 0.3 2016-01-277718498 15 2016-01-19 @ 12:00 pm 2016-01-22 @ 12:00 pm < 0.3 2016-01-277718499 16 2016-01-19 @ 12:00 pm 2016-01-22 @ 12:00 pm < 0.3 2016-01-277718500 17 2016-01-19 @ 12:00 pm 2016-01-22 @ 12:00 pm < 0.3 2016-01-277718296 18 2016-01-19 @ 12:00 pm 2016-01-22 @ 12:00 pm < 0.3 2016-01-277718295 19 2016-01-19 @ 12:00 pm 2016-01-22 @ 12:00 pm < 0.3 2016-01-277722195 2 2016-01-19 @ 12:00 pm 2016-01-22 @ 12:00 pm < 0.3 2016-01-277716789 20 2016-01-19 @ 12:00 pm 2016-01-22 @ 12:00 pm < 0.3 2016-01-277716785 21 2016-01-19 @ 12:00 pm 2016-01-22 @ 12:00 pm < 0.3 2016-01-267716791 22 2016-01-19 @ 12:00 pm 2016-01-22 @ 12:00 pm < 0.3 2016-01-277716786 23 2016-01-19 @ 12:00 pm 2016-01-22 @ 12:00 pm < 0.3 2016-01-277716793 24 2016-01-19 @ 12:00 pm 2016-01-22 @ 12:00 pm < 0.3 2016-01-277718274 25 2016-01-19 @ 12:00 pm 2016-01-22 @ 12:00 pm < 0.3 2016-01-277716792 26 2016-01-19 @ 12:00 pm 2016-01-22 @ 12:00 pm < 0.3 2016-01-277718294 27 2016-01-19 @ 12:00 pm 2016-01-22 @ 12:00 pm < 0.3 2016-01-277718293 28 2016-01-19 @ 12:00 pm 2016-01-22 @ 12:00 pm < 0.3 2016-01-277718292 29 2016-01-19 @ 12:00 pm 2016-01-22 @ 12:00 pm < 0.3 2016-01-277722197 3 2016-01-19 @ 12:00 pm 2016-01-22 @ 12:00 pm < 0.3 2016-01-277718290 30 2016-01-19 @ 12:00 pm 2016-01-22 @ 12:00 pm < 0.3 2016-01-277722198 4 2016-01-19 @ 12:00 pm 2016-01-22 @ 12:00 pm < 0.3 2016-01-277722199 5 2016-01-19 @ 12:00 pm 2016-01-22 @ 12:00 pm < 0.3 2016-01-277722211 6 2016-01-19 @ 12:00 pm 2016-01-22 @ 12:00 pm < 0.3 2016-01-277718491 7 2016-01-19 @ 12:00 pm 2016-01-22 @ 12:00 pm < 0.3 2016-01-277718476 8 2016-01-19 @ 12:00 pm 2016-01-22 @ 12:00 pm < 0.3 2016-01-267718479 9 2016-01-19 @ 12:00 pm 2016-01-22 @ 12:00 pm < 0.3 2016-01-27

Air Chek, Inc. 1936 Butler Bridge Rd, Mills River, NC 28759-3892 Phone: (828) 684-0893 Fax: (828) 684-8498

Page 36: RADON SCREENING SURVEY FOLLOW-UP GREAT SENECA CREEK ...montgomeryschoolsmd.org/uploadedFiles/departments/facilities... · 3015321 3028833 02/29/2016 1:36 pm 03/03/2016 11:34 am Unit

February15,2016

** LABORATORY ANALYSISREPORT **

Radon test result report for: MCPS

Kit # Room Id Started Ended pCi/L Analyzed7718273 101A 2016-01-30 @ 9:00 am 2016-02-01 @ 9:00 am 6.5 ± 0.6 2016-02-047718281 102B 2016-01-30 @ 9:00 am 2016-02-01 @ 9:00 am 6.4 ± 0.6 2016-02-047718282 103C 2016-01-30 @ 9:00 am 2016-02-01 @ 9:00 am 6.3 ± 0.6 2016-02-047718288 104D 2016-01-30 @ 9:00 am 2016-02-01 @ 9:00 am 6.7 ± 0.6 2016-02-047718289 105E 2016-01-30 @ 9:00 am 2016-02-01 @ 9:00 am 6.6 ± 0.6 2016-02-047718291 106F 2016-01-30 @ 9:00 am 2016-02-01 @ 9:00 am 6.5 ± 0.6 2016-02-04

Air Chek, Inc. 1936 Butler Bridge Rd, Mills River, NC 28759-3892 Phone: (828) 684-0893 Fax: (828) 684-8498

Note: Spike samples are test canisters that are deliberately exposed to a controlled high level of radon in a laboratory. They provide a quality control measure in the testing process and do NOT reflect radon levels in the building being tested.

Spike Sample Laboratory Results

Page 37: RADON SCREENING SURVEY FOLLOW-UP GREAT SENECA CREEK ...montgomeryschoolsmd.org/uploadedFiles/departments/facilities... · 3015321 3028833 02/29/2016 1:36 pm 03/03/2016 11:34 am Unit
Page 38: RADON SCREENING SURVEY FOLLOW-UP GREAT SENECA CREEK ...montgomeryschoolsmd.org/uploadedFiles/departments/facilities... · 3015321 3028833 02/29/2016 1:36 pm 03/03/2016 11:34 am Unit