radios de curvatura minimo para conductores thhw-ls.pdf
DESCRIPTION
CALCULO DE DIAMETROS MINIMOS DE CURVATURA DE CADA CONDUCTOR ELECTRICO DE ACUERDO A NORMAS Y ESPECIFICACIONES ESTABLECIDAS POR PEMEX, PARA EL HABILITADO Y CONSTRUCCION DE LINEAS EN BAJA TENSION.TRANSCRIPT
CALIBRE NUM DE HILOS DIAMETROEXTERIOR MM
RADIO DE CURVATURAMINIMO (MM)
14 19 3.3 13.212 19 3.8 15.210 19 4.3 17.28 19 5.8 23.26 19 7.6 30.44 19 8.9 35.63 19 9.4 37.62 19 10.2 40.81 19 12.2 48.8
1/0 19 13.2 52.82/0 19 14.5 583/0 19 15.7 62.84/0 19 17 68250 37 19.1 76.4300 37 20.3 81.2350 37 21.6 86.4400 37 22.9 91.6500 37 25.1 100.4600 61 27.7 138.5750 61 30.2 151
1000 61 34 170 115 KV5, 15, 25 Y 35 KV CON PANTALLA 12 D
4 D (25.4 mm Ø EXTERIOR Y MENOR)
5 D (25.4 mm a 50.8 mm Ø EXTERIOR)6 D (50.81 mm Ø EXTERIOR Y MAYOR)
THHW-LS, 600 V, 90 °C/75 °C CON AISLAMIENTO DE PVC
RADIO DE CURVATURA MINIMO DE CONDUCTORES
DE ACUERDO A FABRICANTE
600 V (MONOCONDUCTOR, CONTROL YMULTICONDUCTOR
D= DIAMETRO EXTERIOR DEL CONDUCTOR(NRF-048-PEMEX-2007 "DISEÑO DE INSTALACIONES ELECTRICAS")