  • 8/6/2019 Radial, Loop Double and Grid Form Systems

    1/29

    Primary distributionsystem is that partof the electricdistribution system

    between distributionsubstation anddistributiontransformers.

    It is madeup of circuits calledprimary feeders ordistribution feeders.

    1

  • 8/6/2019 Radial, Loop Double and Grid Form Systems

    2/29

    2

  • 8/6/2019 Radial, Loop Double and Grid Form Systems

    3/29

    In this system all the sections/branches of afeeder are fed from a single source in afixed direction

    3

    Load

    Load

    Load

    Generator

  • 8/6/2019 Radial, Loop Double and Grid Form Systems

    4/29

    In this it is shownthat there are twoprimary feeders

    from which furthersubfeeders supply tothere respectiveloads. If any one ofthe feeder becomes

    faulty then supplythrough that feederhas to cut so noreliability

    4

  • 8/6/2019 Radial, Loop Double and Grid Form Systems

    5/29

    Merits Reasons

    Simple in design, construction,operation and maintenance

    Suitable size of conductor.Very simple protection schemes.Maintenance easy.Easy fault current calculations.

    cheapest system No extra length of line andswitching arrangements required.Less capital cost as different sizesof conductors can be used.As no alternative arrangementsare necessary so shortest route

    can be adopted hence cost savingAs used in rural areas so largespans can be used which furtherreduces cost

    5

  • 8/6/2019 Radial, Loop Double and Grid Form Systems

    6/29

    Demerits ReasonsVery poor service reliability In case of fault on a feeder the

    supply to consumers from thosefeeders is cutoff and restored onfault removal.

    Excessive voltage drop and linelosses

    Due to passage of total currentthrough the common main sectionof the feeder, voltage drop(IR)and line losses will be more ascompared to the system whichfacilitates distribution of loadcurrents into two or more paths

    6

  • 8/6/2019 Radial, Loop Double and Grid Form Systems

    7/29

    It is considered more suitable for the areaswith low density of load involving longdistances and requiring low degree ofavailability.

    7

  • 8/6/2019 Radial, Loop Double and Grid Form Systems

    8/298

    5

    132KV

    4

    Grid Station

    11KV

    3

    2

    Distribution

    Transformer

    1

    5

    3

    11KV

    2

    Distribution

    Substation

    0.4KV

    1

  • 8/6/2019 Radial, Loop Double and Grid Form Systems

    9/29

  • 8/6/2019 Radial, Loop Double and Grid Form Systems

    10/29

  • 8/6/2019 Radial, Loop Double and Grid Form Systems

    11/29

    What is closed loop system? If a HT line emanating from a Grid station and

    covering the load area in shape of a loop,

    finishes at the same Grid station returning to

    same breaker or another independent breaker it

    is called closed loop and the system is calledclosed loop system.

    In this system each transformer has two

    sectinalizers, one on either side of the

    transformers tap-off point.

  • 8/6/2019 Radial, Loop Double and Grid Form Systems

    12/29

    Typical WAPDA closed loop system

    Bus bar

    Station circuit breaker

    Sectionalizing

    switch closed

    transformer

    LoadSectionalizing switch

    closed

  • 8/6/2019 Radial, Loop Double and Grid Form Systems

    13/29

    Merits of closed loop system1. This system is more reliable than radial system.

    In case of fault, breaker at grid station opens.

    After tracing the fault the faulty section is isolated, and supply to

    remaining section is restored.

    The consumers dont have to wait very long till the rectification of

    the fault as in the case of Radial system. In case of two simultaneously faults, the consumers have to wait

    much till the rectification of the fault of at least one section. But

    possibility of two simultaneously faults is less.

    It is usually preferred that there must be two breakers instead of

    one.

    2. Less voltage drop, less line losses As compared to radial system the voltage drop and line losses is less.

  • 8/6/2019 Radial, Loop Double and Grid Form Systems

    14/29

  • 8/6/2019 Radial, Loop Double and Grid Form Systems

    15/29

    Application

    It is usually recommended for HIGH density areas wheredistances are small. preferably for urban areas.

    This system can be equally useful for rural areas whereeconomy so permits. But to ensure effectiveness, the loop

    should be of small size.

  • 8/6/2019 Radial, Loop Double and Grid Form Systems

    16/29

  • 8/6/2019 Radial, Loop Double and Grid Form Systems

    17/29

    OPEN LOOP SYSTEM

    In a closed-loop system with two breakers

    (one at each end), if one of the two

    sectionalizers is kept normally open, thesystem is named as open-loop system.

  • 8/6/2019 Radial, Loop Double and Grid Form Systems

    18/29

  • 8/6/2019 Radial, Loop Double and Grid Form Systems

    19/29

    ADVANTAGES

    Economical

    Availability of service is improved Locating fault is easy

  • 8/6/2019 Radial, Loop Double and Grid Form Systems

    20/29

  • 8/6/2019 Radial, Loop Double and Grid Form Systems

    21/29

  • 8/6/2019 Radial, Loop Double and Grid Form Systems

    22/29

    Double Supply System

    Additional radial feeder is provided side by

    side to feed the same consumer.

    Using automatic change over switches.

    Duplicate supply system or parallel

    feeders.

  • 8/6/2019 Radial, Loop Double and Grid Form Systems

    23/29

    Substation Bus

    CircuitBreakerSectionalizing

    switch

    FUSE

    TRANSFORMERS

    LOAD

    LOAD

  • 8/6/2019 Radial, Loop Double and Grid Form Systems

    24/29

    Merits and DemeritsAdvantages Disadvantages

    Higher service reliability. Very Expensive Extra feeders are installed which

    doubles the cost. Cost of sectionalizers. Additional length of line needed

    to connect the feeder to thetransformer.

    Less line losses. Reduced Safety

  • 8/6/2019 Radial, Loop Double and Grid Form Systems

    25/29

  • 8/6/2019 Radial, Loop Double and Grid Form Systems

    26/29

    GRID FORM OF H.V SYSTEM

    In this system all the distribution transformers of a load area, areinterconnected providing normally two or more alternatives. while

    the whole system is fed from two or more bulk supply sources.

    But availability can not be improved through

    manual operation of sectionalizer to isolate faulty section during

    emergency as it will take quite a considerable time to identify thefaulty section and to determine the better alternative.

    As manual operation may result in wrong

    operation due to complexity of the system so to have a real benefit

    of this system, automatic switching arrangements with sophisticated

    protection schemes should be provided including establishment of aremote control center.

  • 8/6/2019 Radial, Loop Double and Grid Form Systems

    27/29

    C.BC.BC.B C.B

    C.BC.BC.BC.BC.BC.B C.BC.B

    C.B C.B C.B C.B

    C.B C.B C.B C.B C.B C.B C.B C.B C.B C.B C.B

    C.B C.B C.B C.BC.B C.BC.B C.B C.B C.B C.B

    C.BC.B

    STEP DOWN

    TRANSFORMER

    C.B C.B

    11KV BUS BAR

    132KV BUS BAR

    DISTRIBUTION

    TRANSFORMER

    C.B C.B C.B C.B

    400 VOLT

    400 VOLT

    SINGLE LINE DIAGRAM OG GRID FORM OF H.V-DISTRIBUTION

    SYSTEM

  • 8/6/2019 Radial, Loop Double and Grid Form Systems

    28/29

    Merits Most reliable because normally no possibility of failure of

    supply and availability is almost 100%.

    In case of two simultaneous faults, service to the

    consumers will not be affected at all, or effect will be

    limited.

    Demerits It is most costly system.

  • 8/6/2019 Radial, Loop Double and Grid Form Systems

    29/29

    Applications The system being the most reliable, and at the same time

    the most costly, is recommended for the areas of highest

    priority of supply with very high load density.

    If the economy for a county is not a problem, this system

    is considered the most suitable one for urban areas,

    specially the big cities