EIA Cabinet Server Mounting
Ronald GD Davis Data Center Eng. Services
4/1/2016
Mounting Standards
EIA Rack Mounted Servers sometimes don’t fit within a cabinet. This may be due to the cabinet not conforming to the EIA standards. This usually happens when cabinets are shipped and a belly band is used to secure the cabinets against the shipping container walls. The way to mitigate this issue is to place 1U-3U blanks in midsection of the cabinet to relieve the cabinet from the bending stresses imposed by the belly straps used to secure the cabinets during shipping.
1RU0.0”
44.45mm
17.717” / 450mm 18.307” / 465mm 19.016” / 483mm
Server Space 1.75”
3.5”
5.25”
1.75”
0.625”
0.625”
0.500”
#10-32 UNC Threaded Hole
0.354” / 9mm
0.295” / 7.5mm