quicktronic ice universal voltage systems · 2019. 5. 18. · item number 50319 qtp 2 x 96t12 / ho...
TRANSCRIPT
-
160
SYLVANIA QUICKTRONIC ICE ballasts offer several advantages:
• Operate SYLVANIA ICETRON® electrodeless fluorescent lamps with maximum efficacy and full lumen output.
• Longest life available from a fluorescent system – 100,000 hour average rated life:• greatly reducing maintenance costs• extending relamping cylces.
• Extensive thermal performance: rated for operation in environments from – 40ºC (-40ºF) up to 50ºC (122ºF). SYSTEM ICE is suitable for a variety of applications traditionally addressed by HID systems.
(Note: starting temp. -25°C (-13°F) for 40W
and 70W lamps)
These ballasts are RoHS compliant and feature lead-free solder and manufacturing process.
Setting the standard for quality, the ICETRON lamp and ballast System are covered by the QUICK 60+® warranty, the first and most comprehensive system warranty in the industry.
QUICKTRONIC® ICE Universal Voltage Systems
www.sylvania.com
Electrodeless Fluorescent Systems
ICE
Lamp / Ballast GuideICETRON lamp: ICE 40W Ballast: QT1x40ICE/UNV
ICETRON lamp: ICE 70WBallast: QT1x100ICE/UNV
ICETRON lamps: ICE 100WBallast:QT1x100ICE/UNV QT1x150ICE/UNV
ICETRON lamp: ICE 150W Ballast: QT1x150ICE/UNV
Key System Features
• 100,000 Hour lamp life• Instant on / Instant restrike• Universal voltage• 1.00 - 1.38 Ballast factor• High luminous efficacy• Quiet operation• High power factor• Low harmonic distortion• UL, CSA, FCC• RoHS compliant - Ballast• Lead-free solder and manufacturing
process
SYLVANIA QUICKTRONIC ICE ballasts are ideally suited for:• Commercial• Retail• Sign lighting• Street lighting• Tunnel lighting
Application Information
Input Initial System System Type Wattage Lumens LPW
Metal Halide 70W 90 5200 58 FBO31 2-lamp 57 4900 86 ICE70W 79/77 6500 82/84
Metal Halide 100W 125 8500 68 FBO31 3-lamp 84 7360 88 ICE100 106/103 8000 75/77
Metal Halide 150W 180 12,900 72 ICE150 161/156 12,000 74/76
ICE ballast features:
• Operation from a line voltage of either 120V or 277V
• A special wire/connector system required for inductively coupled systems.
• Inductively coupled lamp design: • eliminates the use of filaments
inside the lamp, removing one of the life limiting factors of a fluorescent lamp
• reduces blackening • provides an average rated life of
100,000 hours with maximum energy efficiency
Lamp amalgam tip position will affect light output at various temperatures.
System Information
QUICKTRONIC ICE ballast is available in two case configurations, UL Type 1 or Type 2 Outdoor rated. The Type 1 models are suitable for general applications and the Type 2 models are ideal for harsh environments, such as damp or wet locations.
-
Specifications subject to change without notice.
OSRAM SYLVANIA National Customer Service and Sales Center1-800-LIGHTBULB (1-800-544-4828)www.sylvania.com
161
Starting Method: I.C.E.Circuit Type: I.C.E.Lamp Frequency: 200-300kHzStarting Temp: -40°F (-40°C) -13°F(-25°C) for 40W and 70W lampsInput Frequency: 50/60 Hz Low THD: 90%Voltage Range: ±10% of 120-277V
rated line (108-305V)
UL Listed Class P, Type 1 or Type 2, Outdoor CSA CertifiedTemp. Test Point (Tc) on ballast label: 70°C Max (150W) 65ºC Max (100W & 40W)FCC 47CFR Part 18 Non-ConsumerSound Rated ARoHS Compliant - Ballast3
ANSI C62.41 Cat. A Transient ProtectionRemote Mounting: contact OSRAM SYLVANIA
2 Data based on ICETRON lamp types.
3 Complies with European Union Restriction of Hazardous Substances Directive (Directive EC 2002/95)
Specifications2
7.1"(180mm)
1.7"(43mm)6.7"
(170mm)
6.2"(158mm)
3.9"(99mm)
1.9"(48mm)
Output Harness24" (609mm)
4.3"(109mm)
Input Harness24" (609mm)
6.30"(160mm)
3.96"(100mm)
Output Connector
Input Connector1.70"
(43mm)
1.90"(48.3mm)
6.70"(170mm)
7.15"(181mm)
Input Input Rated 1 Ballast Input SystemItem OSRAM SYLVANIA Voltage Current Lamp Lumens No. of Factor System Power EfficacyNumber Description (VAC) (AMPS) Type (lm) Lamps (BF) Lumens (W) (lm/W) BEF1
49758 QT1x40ICE/UNV-T 120-277 0.36/0.16 ICE40 2800 1 1.00 2800 44 64 2.29
49753 QT1x100 ICE/UNV-T 120-277 0.88/0.37 ICE100 8000 1 1.00 8000 106/103 75/77 0.97 49756 QT1x100 ICE/UNV-W 0.66/0.29 ICE70 6200 1 1.05 6500 79/77 82/84 1.36
49772 QT1x150 ICE/UNV-T 120-277 1.34/0.58 ICE150 12,000 1 1.00 12,000 161/156 74/76 0.64 49773 QT1x150 ICE/UNV-W 1.28/0.54 ICE100 8000 1 1.38 11,000 154/149 71/73 0.93
1 Rated lamp lumens and performance data based on SYLVANIA ICETRON lamps. Use only with SYLVANIA ICETRON lamps (for additional lamp types contact OSRAM SYLVANIA).
Item Number Lamp Description Item Number Lamp Description Item Number Lamp Description Item Number Lamp Description26310 ICE40/835/RCT/2P 26087 ICE 70/835/2P 26102 ICE100/835/2P 26152 ICE150/835/2P26311 ICE40/835/CIR/2P 26088 ICE 70/841/2P 26103 ICE100/841/2P 26153 ICE150/841/2P26312 ICE40/841/RCT/2P 26089 ICE 70/850/2P 26105 ICE100/850/2P 26155 ICE150/850/2P26313 ICE40/841/CIR/2P 26314 ICE40/850/RCT/2P 26315 ICE40/850/CIR/2P
Item Number 49753 QT 1 x 100 ICE / UNV - T
QUICKTRONIC
Number of Lamps
Case Type (Topmount or Watertight)
Line Voltage (120-277V)
System Type - ICETRON
Primary Lamp Wattage
Type 1 Dimensions:Overall: 7.15" L x 3.96" W x 1.70" HMounting: 6.70" L x 1.90" W
Packaging: Quantity: 5 Weight: 1.9 lbs ea. (approx.)
Type 2 Dimensions:Overall: 7.10" L x 4.30" W x 1.70" HMounting: 6.70" L x 1.90" W
Packaging: Quantity: 5 Weight: 2.5 lbs ea. (approx.)
ICETRONTYPE 1
BALLAST
ICETRON
LAMP
24" Lamp Wiring Harness w/ Connector
BLK
WHT
Ground Ballast Case
ICETRONTYPE 2
BALLAST
ICETRON
LAMP 24" Lamp Wiring Harness w/ Connector
BLACK
WHITE
Ground Ballast Case
Type 1 Wiring: Connector (No leads provided)Input: Use solid copper wire only
18 AWG, strip length 3/8"Output: Use only output connector with
SYLVANIA ICETRON® 2P lamps listed above
Type 2 Wiring: Input: Integral lead wires, 600V, 18 AWG solid copper,
approx. 24" length Output: Wire harness, approx. 24" length with mating
connector to lamp wiring harness
ICE
Performance Guide
* Models rated UL Type 1 (“T” suffix) are designed for general lighting applications. Models rated UL Type 2 (“W” suffix) provide protection from water intrusion and are suitable for damp or wet locations.
Electrodeless Fluorescent Systems Universal Voltage (120-277V)
ICETRON®
QUICKTRONIC products are covered by the QUICK 60+® warranty, a comprehensive lamp and ballast system warranty. For additional details, refer to the QUICK 60+ warranty bulletin.
System Life / Warranty
Catalog # Date Type
Project Prepared by
Comments
SPECIFICATION DATA
-
Item Number 50319 QTP 2 x 96T12 / HO / UNV
QUICKTRONIC
Number of Lamps
Line Voltage (120-277V)
System Type
Primary Lamp Type
162
T12H
O S
YSTE
MS
Input Input System Current Rated2 Ballast Power Efficacy Item OSRAM SYLVANIA (AMPS) Lamp1 Lumens No. of Factor System (W) (lm/W) Number Description @120/277V Type (lm) Lamps (BF) Lumens @120/277V @120/277V BEF3
50319 QTP2x96T12HO/UNV 1.65/0.71 F96T12HO 9050 2 0.85 15,385 196 78 0.43 1.38/0.60 F96T12HO/SS 8000 2 0.90 14,400 164 88 0.55 1.30/0.56 F72T12HO 6250 2 0.90 11,250 154 73 0.58 1.10/0.47 F60T12HO 5200 2 0.90 9360 132 71 0.68 0.88/0.38 F48T12HO 4050 2 0.90 7290 104 70 0.87 0.88/0.38 F96T12HO 9050 1 0.92 8325 104 80 0.88
1 Also compatible with other manufacturer’s equivalent lamp types that meet ANSI standards. 2 96T12HO rated lamp lumens and performance data based on F96T12CW/HO/SS and F96T12/D41/HO series lamps. 3 Ballast Efficiency Factor (BEF) shown = (Ballast Factor x 100) divided by Input Power (Note: calculation based on lowest wattage value). 50319 replaces discontinued item numbers 49883 QT2x96/120 HO and 49884 QT 2x96/277HO
Catalog # Date Type
Project Prepared by
Comments
SPECIFICATION DATA
Performance GuideQUICKTRONIC® T12HO Rapid Start Electronic Fluorescent Ballasts Universal Voltage (120-277V)
Starting Method: Rapid StartCircuit Type: SeriesStarting Temp:4 -20°F (-29°C) for F96T12HO; 60°F (16°C) for SUPERSAVER F96T12HO/SSLamp CCF: Less than 1.7Lamp Frequency: >20 kHzLow THD: 98%
cUL Listed Class P, Type 1 Outdoor 75°C Max Case Temperature FCC 47CFR Part 18 Non-Consumer ANSI C62.41 Cat A. Transient Protection Remote Mounting: Contact OSI forremote mounting options.Class A Sound Rating
4 Operation below 50ºF (10°C) may affect light output or lamp operation – see “Low Temp. Starting” definition.
SpecificationsData based on F96T12HO
System Life / WarrantyQUICKTRONIC products are covered by the QUICK 60+® warranty, a comprehensive warranty. For additional details, refer to the QUICK 60+ warranty bulletin.
Normal Ballast Factor
96 T12HO Professional Series
Note: For one lamp application, individually cap each yellow lead. Insulate to 600 volts.
Length
MountingLength
Height
Width
QUICKTRONIC 2x96T12HO
LAMP
LAMP
LAMP
BALLASTBlueBlueBlueRed
BlackWhite
Note: For two lamp application, cap any blue lead. Insulate to 600 volts.
QUICKTRONIC 3x32
BALLAST
LAMP
BlackWhite
Blue
Red
QUICKTRONIC 1x32
BALLAST
LAMP
LAMP
LAMP
LAMP
BlackWhite
YellowYellow
BlueBlue
RedRed
Note: For three lamp application, cap any unused blue lead. Insulate to 600 volts.
QUICKTRONIC 4x32
QUICKTRONIC 1x40DL
BALLASTBlackWhite
Blue
Red
BALLAST
Note: For one lamp application, cap any blue lead. Insulate to 600 volts.
QUICKTRONIC 2x40DL
BlackWhite
BlueBlue
Red
Note: For one lamp application, cap any unused blue lead. Insulate to 600 volts.
QUICKTRONIC 2x59*QUICKTRONIC 2x96IS
BALLASTBlackWhite
Blue
Blue
Red
LAMP
LAMP
QUICKTRONIC 2x96HO
BlackLine White
YellowYellow
BlueBlueRedRed
BALLAST
LAMP
LAMP
LAMP
LAMP
BlueBlue
RedBALLAST
BlackWhite
Note: For one lamp application, cap any blue lead. Insulate to 600 volts.
QUICKTRONIC 2x32
BALLAST
QUICKTRONIC FM (1 LAMP)Note: For QT-FM green ground wire to terminal required.
LAMP
Black
White
Blue
Red
QUICKTRONIC 3x40DL
BALLASTBlackWhite Blue
Blue
BlueRed
Note: For two lamp application, cap any blue lead. Insulate to 600 volts.
QUICKTRONIC FM (2 LAMP)Note: For QT-FM green ground wire to terminal required.
LAMP
LAMP Blue
Yellow
Red
BALLASTGreen BlackGreenWhite
LAMP
LAMP
LAMP
BALLASTBlueBlueBlueRed
BlackWhite
Note: For two lamp application, cap any blue lead. Insulate to 600 volts.
QUICKTRONIC 3x32
BALLAST
LAMP
BlackWhite
Blue
Red
QUICKTRONIC 1x32
BALLAST
LAMP
LAMP
LAMP
LAMP
BlackWhite
YellowYellow
BlueBlue
RedRed
Note: For three lamp application, cap any unused blue lead. Insulate to 600 volts.
QUICKTRONIC 4x32
QUICKTRONIC 1x40DL
BALLASTBlackWhite
Blue
Red
BALLAST
Note: For one lamp application, cap any blue lead. Insulate to 600 volts.
QUICKTRONIC 2x40DL
BlackWhite
BlueBlue
Red
Note: For one lamp application, cap any unused blue lead. Insulate to 600 volts.
QUICKTRONIC 2x59*QUICKTRONIC 2x96IS
BALLASTBlackWhite
Blue
Blue
Red
LAMP
LAMP
QUICKTRONIC 2x96HO
BlackLine White
YellowYellow
BlueBlueRedRed
BALLAST
LAMP
LAMP
QUICKTRONIC 1x96HO
BlackLine White
YellowYellow
BlueBlueRedRed
BALLAST
LAMP
LAMP
LAMP
BlueBlue
RedBALLAST
BlackWhite
Note: For one lamp application, cap any blue lead. Insulate to 600 volts.
QUICKTRONIC 2x32
BALLAST
QUICKTRONIC FM (1 LAMP)Note: For QT-FM green ground wire to terminal required.
LAMP
Black
White
Blue
Red
QUICKTRONIC 3x40DL
BALLASTBlackWhite Blue
Blue
BlueRed
Note: For two lamp application, cap any blue lead. Insulate to 600 volts.
QUICKTRONIC FM (2 LAMP)Note: For QT-FM green ground wire to terminal required.
LAMP
LAMP Blue
Yellow
Red
BALLASTGreen BlackGreenWhite
Dimensions:Overall: 11.8" L x 2.15" W x 1.61" HMounting: 11.0"
Packaging: Quantity: 6 pieces Weight: 2.77 lbs ea. (1260 grams)
Wiring:Leads
Specifications subject to change without notice.
OSRAM SYLVANIA National Customer Service and Sales Center1-800-LIGHTBULB (1-800-544-4828)www.sylvania.com
-
Specifications subject to change without notice.
163
OSRAM SYLVANIA National Customer Service and Sales Center1-800-LIGHTBULB (1-800-544-4828)www.sylvania.com
T12 SYS
TEMS
Input Input System Current Rated Ballast Power Efficacy2 Item OSRAM SYLVANIA (AMPS) Lamp1 Lumens No. of Factor System (W) (Im/W) Number Description @120/277V Type (lm) Lamps (BF) Lumens @120/277V @120/277V BEF1
50314 QTP2x40T12/UNV/RS/SC 0.62/0.27 F40T12/D30/ECO 3200 2 0.88 5630 74/74 76 1.19
0.53/0.23 F34/D830/SS 2900 2 0.85 4930 63/63 78 1.35
50308 QTP2x96/T12/UNV/IS 1.12/0.50 F96T12/D41/ECO 6420 2 0.86 11,040 134/130 82/85 0.66
0.91/0.40 F96T12/CW/SS 5300 2 0.87 9220 108/106 85/87 0.82
0.88/0.40 F72T12/CW 4500 2 0.92 8280 105/103 79/80 0.89
0.62/0.28 F48T12/CW 2820 2 0.92 5190 73/71 71/73 1.30
0.52/0.24 F48T12/SS/CW 2450 2 0.92 4510 62/61 73/74 1.51
0.69/0.31 F96T12/D41/ECO 6420 1 1.01 6485 82/81 79/80 1.25
0.56/0.27 F96T12/CW/SS 5300 1 1.10 5830 67/66 87/88 1.67
0.55/0.26 F72T12/CW 4500 1 1.07 4815 65/64 74/75 1.67
New 50308 QTP2x96T12/UNV/IS model replaces 50318 that is discontinued. Also compatible with other manufacturer’s equivalent lamp types that meet ANSI standards. 1 Ballast Efficiency Factor (BEF) shown = (Ballast Factor x 100) divided by Input Power (Note: calculation based on lowest wattage value). 2 System Efficacy calculation based on lowest input power value unless otherwise noted.
Catalog # Date Type
Project Prepared by
Comments
SPECIFICATION DATA
QUICKTRONIC® T12 Electronic Fluorescent Ballasts 40T12RS & 96T12IS Universal Voltage (120-277V)
Starting Method: RS - Rapid Start
IS - Instant StartCircuit Type: RS - Parallel
IS - ParallelStarting Temp: 0°F (-18°C) SUPERSAVER® Lamps: 60°F(16°C)Input Frequency: 60 HzTHD: QTP40T12/UNV RS: 0.96 (for F96T12); >0.91(for other lamps) Input Voltage: ±10% of Rated InputLamp Crest Factor: 20 kHz
UL Listed Class P, Type 1 OutdoorCSA or CUL Certified70°C Max. Case Temp. FCC 47CFR Part 18 Non-ConsumerClass A Sound RatingANSI C62.41 Cat A. Transient Protection
Specifications Data based on F40T12 for RS, F96T12 for IS
Item Number 50314 QTP 2 x 40T12 / UNV / RS SC
QUICKTRONIC PROFESSIONAL
Number of Lamps (2)
Case Size
Starting Type / Ballast Factor
Line Voltage (120-277V)
Primary Lamp Wattage
System Life / WarrantyQUICKTRONIC products are covered by the QUICK 60+® warranty. For additional details, refer to the QUICK 60+ warranty bulletin.
Normal Ballast Factor
T12 Professional Series
Dimensions: Model QTP2x40T12/UNV/RS/SC enclosure size Overall: 9.5" L x 1.38" W x 1.18" H Mounting: 8.9"Weight: 1.25 lbs ea. (approx.)
Dimensions: Model QTP2x96/T12/UNV/IS enclosure size Overall: 11.75" L x 2.15" W x 1.61" H Mounting: 11"Weight: 4.67 lbs ea. (approx.)
QTP2X96/T12/UNV/IS
LAMP
LAMP
BlueBlue
Red
BlackWhite
LAMP
BlueBlue
Red
BlackWhite
LineLine
BALLAST BALLAST
Cap off/Insulate unused leads for 1000V.
Ground Ballast and mount lamps within 1/2" of grounded metal reflector
QTP 2x96T12 IS
Note: For one lamp application, cap blue lead. Insulate to 1000 volts.
Performance Guide
QTP2X40T12/UNV/RS/SC
BALLAST
LAMP
WhiteBlackLine
YellowYellow
BlueBlue
RedRed
LAMP
BALLAST
WhiteBlackLine
Ground Ballast and mount lamps within 1/2" of grounded metal reflector
YellowYellow
BlueBlue
RedRed
LAMP
Cap off/Insulate unused leads for 600V.
QTP 2x40T12 RSQTP2X40T12/UNV/RS/SC
BALLAST
LAMP
WhiteBlackLine
YellowYellow
BlueBlue
RedRed
LAMP
BALLAST
WhiteBlackLine
Ground Ballast and mount lamps within 1/2" of grounded metal reflector
YellowYellow
BlueBlue
RedRed
LAMP
Cap off/Insulate unused leads for 600V.
-
164
SYLVANIA QUICKTRONIC RESIDENTIAL ballasts bring all the energy saving features from standard commercial grade ballasts to an economical design acceptable for residential fixtures. These ballasts comply with FCC Part18 Consumer requirements thereby making them a perfect complement for ENERGY STAR® rated fixtures. QTR ballasts are for residential use only.
SYLVANIA QUICKTRONIC RESIDENTIAL T8 electronic ballasts operates OCTRON T8 lamps with maximum efficacy, high lumen output, and provides up to 30-40% energy savings when compared to F40T12 magnetic systems.
Small can enclosure allows for low profile fixture design and application.
Parallel circuitry is utilized to keep the remaining lamps lit if one or more should go out.
QUICKTRONIC RESIDENTIAL T8 is available in two and four lamp models in 120V to cover a wide range of applications.
These ballasts are RoHS compliant and feature lead-free solder and manufacturing process.
Input System Type Power Initial System 2-lamp ISN-SC (W) Lumens LPW
F40T12 Std. Magnetic Ballast 96 5795 60 E.S. Magnetic Ballast 86 5795 67
F34T12 Std. Magnetic Ballast 82 4750 58 E.S. Magnetic Ballast 72 4750 66
F32T8/700 Magnetic 71 5320 75
FO32/800XP QTR2x32T8/120 ISN-SC 55 5220 95
Input System Type Power Initial System 4-lamp ISN (W) Lumens LPW
F40T12 Std. Magnetic Ballast 192 11,590 60 E.S. Magnetic Ballast 172 11,590 67
F34T12 Std. Magnetic Ballast 164 9500 58 E.S. Magnetic Ballast 144 9500 66
F32T8/700 Magnetic 142 10,640 75
FO32/800XP QTR4x32T8/120 ISN-SC 110 10,080 92
Lamp / Ballast Guide32W T8 - OCTRON® lamps2 or 1 lamp QTR2x32T8/120 ISN-SC4 or 3 lamp QTR4x32T8/120 ISN-SC
Also operates:FBO32, FBO31, FO25, FBO24, FO17, FBO16, FO30/SS, FBO30/SS (30W), FBO29/SS (29W), FO28/SS (28W) & FO25/SS (25W)
F40T8 operation:1 lamp on 2L ballast3 lamp on 4L ballast
• RESIDENTIAL USE ONLY • Normal power factor (>0.50) • High THD (
-
165
Specifications subject to change without notice.
OSRAM SYLVANIA National Customer Service and Sales Center1-800-LIGHTBULB (1-800-544-4828)www.sylvania.com
RESIDENTIAL USE ONLY – QTR electronic ballasts meet FCC consumer limits, have high THD (0.50), therefore are for residential use only and cannot
be used in commercial applications. (RESIDENTIAL ONLY: Do not use in commercial/three phase applications, neutral wire/overheating can occur due to high harmonic currents).
Installation Notes
Item Number 49313 QTR 2 x 32T8 / 120 ISN-SC
QUICKTRONIC RESIDENTIAL
Number of Lamps
Case Size
Starting/Ballast Factor
Line Voltage
Primary Lamp Wattage
QTR
T8 R
ES
Catalog # Date Type
Project Prepared by
Comments
SPECIFICATION DATA
Performance GuideResidential Series (Residential Use Only), Fluorescent Electronic T8 Systems 120V
RESIDENTIAL USE ONLYStarting Method: Instant StartBallast Factor: NormalCircuit Type: ParallelLamp Frequency: >42 kHzLamp CCF: Less than 1.7Starting Temp:2
0°F for OCTRON® T8 lamps; 60°F for SUPERSAVER® T8 lamps
Input Frequency: 60 HzTHD: 0.50Voltage Range: ±10% of Rated Input
UL Listed Class P, Type 1 OutdoorCSA Certified (4L only)70°C Max Case TemperatureFCC 47CFR Part 18 ConsumerClass A Sound RatingRoHS Compliant3
ANSI C62.41 Cat. A Transient ProtectionRemote Mounting (Max. wire length from ballast case to lampholder): up to 18 feet
2 Operation below 50°F (10°C) may affect light output or lamp operation – see “Low Temp. Starting” definition.
3 Complies with European Union Restriction of Hazardous Substances Directive (Directive EC 2002/95)
SpecificationsData based on F32T8 lamp
Residential Ballast WarrantyQUICKTRONIC T8 RESIDENTIAL electronic ballasts are under warranty for 2 years. OSRAM SYLVANIA shall correct any defects, at our option, and replace any ballast determined to be defective under the terms of this warranty. Note: Labor costs are not reimbursed by OSRAM SYLVANIA.
Data shown based upon SYLVANIA OCTRON® FO32 lamps. QUICKTRONIC® RESIDENTIAL T8 ballasts are also compatible with other lamp manufacturers equivalent lamp types that meet ANSI specifications.
All models will also operate F17, F25 and F32 (and the U-Bend equivalent) T8 lamps.
Normal Ballast Factor
T8 Instant Start 120V Residential Series
LAMP
LAMP
LAMP
BALLASTBlueBlueBlueRed
BlackWhite
Note: For two lamp application, cap any blue lead. Insulate to 600 volts.
QUICKTRONIC 3x32
BALLAST
LAMP
BlackWhite
Blue
Red
QUICKTRONIC 1x32
BALLAST
LAMP
LAMP
LAMP
LAMP
BlackWhite
YellowYellow
RedRed
BlueBlue
Note: For three lamp application, cap any unused blue lead. Insulate to 600 volts.
QUICKTRONIC RESIDENTIAL 4x32
QUICKTRONIC 1x40DL
BALLASTBlackWhite
Blue
Red
BALLAST
Note: For one lamp application, cap any blue lead. Insulate to 600 volts.
QUICKTRONIC 2x40DL
BlackWhite
BlueBlue
Red
Note: For one lamp application, cap any unused blue lead. Insulate to 600 volts.
QUICKTRONIC 2x59*QUICKTRONIC 2x96IS
BALLASTBlackWhite
Blue
Blue
Red
LAMP
LAMP
QUICKTRONIC 2x96HO
BlackWhiteYellowYellow
BlueBlueRedRed
BALLAST
LAMP
LAMP
LAMP
LAMP
BlueBlueRed
BALLASTBlackWhite
Note: For one lamp application, cap any blue lead. Insulate to 600 volts.
QUICKTRONIC RESIDENTIAL 2x32
BALLAST
QUICKTRONIC FM (1 LAMP)Note: For QT-FM green ground wire to terminal required.
LAMP
Black
White
Blue
Red
QUICKTRONIC 3x40DL
BALLASTBlackWhite Blue
Blue
BlueRed
Note: For two lamp application, cap any blue lead. Insulate to 600 volts.
QUICKTRONIC FM (2 LAMP)Note: For QT-FM green ground wire to terminal required.
LAMP
LAMP Blue
Yellow
Red
BALLASTGreen BlackGreenWhite
LAMP
LAMP
LAMP
BALLASTBlueBlueBlueRed
BlackWhite
Note: For two lamp application, cap any blue lead. Insulate to 600 volts.
QUICKTRONIC 3x32
BALLAST
LAMP
BlackWhite
Blue
Red
QUICKTRONIC 1x32
BALLAST
LAMP
LAMP
LAMP
LAMP
BlackWhite
YellowYellow
RedRed
BlueBlue
Note: For three lamp application, cap any unused blue lead. Insulate to 600 volts.
QUICKTRONIC RESIDENTIAL 4x32
QUICKTRONIC 1x40DL
BALLASTBlackWhite
Blue
Red
BALLAST
Note: For one lamp application, cap any blue lead. Insulate to 600 volts.
QUICKTRONIC 2x40DL
BlackWhite
BlueBlue
Red
Note: For one lamp application, cap any unused blue lead. Insulate to 600 volts.
QUICKTRONIC 2x59*QUICKTRONIC 2x96IS
BALLASTBlackWhite
Blue
Blue
Red
LAMP
LAMP
QUICKTRONIC 2x96HO
BlackWhiteYellowYellow
BlueBlueRedRed
BALLAST
LAMP
LAMP
LAMP
LAMP
BlueBlueRed
BALLASTBlackWhite
Note: For one lamp application, cap any blue lead. Insulate to 600 volts.
QUICKTRONIC RESIDENTIAL 2x32
BALLAST
QUICKTRONIC FM (1 LAMP)Note: For QT-FM green ground wire to terminal required.
LAMP
Black
White
Blue
Red
QUICKTRONIC 3x40DL
BALLASTBlackWhite Blue
Blue
BlueRed
Note: For two lamp application, cap any blue lead. Insulate to 600 volts.
QUICKTRONIC FM (2 LAMP)Note: For QT-FM green ground wire to terminal required.
LAMP
LAMP Blue
Yellow
Red
BALLASTGreen BlackGreenWhite
For two lamp application, cap both unused blue leads & one yellow lead individually. Insulate to 600 volts.
Dimensions:Overall: 9.5" L x 1.68" W x 1.18" H Mounting: 8.90"
Product Weight: 1.6 lbs each (approx.)
Wiring: Leads only (no connectors provided)
Length
MountingLengthHeight
Width
8.7 mmSlot
Input Rated Ballast Input SystemItem Current Lamp Lumens No. of Factor System Power EfficacyNumber Description (AMPS) Type (lm) Lamps (BF) Lumens (W) (lm/W) BEF1
QTR2x32T8/120 ISN-SC 0.89 FO32/XP 3000 2 0.87 5220 55 95 1.58 49313 10-Pack 0.56 3000 1 1.03 3090 34 91 3.03
0.74 FO25/XP 2175 2 0.90 3915 45 87 2.00 0.49 2175 1 1.05 2285 28 82 3.75
0.54 FO17/XP 1375 2 0.93 2560 30 85 3.10 0.36 1375 1 1.07 1470 19 77 5.63
0.89 FBO32/XP 2900 2 0.87 5045 55 92 1.58 0.56 2900 1 1.03 2985 34 88 3.03
0.85 FBO31/XP 2775 2 0.88 4885 54 90 1.63 0.56 2775 1 1.03 2860 33 87 3.12
0.68 FO40/XP 3750 1 1.02 3825 40 96 2.55
QTR4x32T8/120 ISN-SC 1.70 FO32/XP 3000 4 0.84 10,080 110 92 0.76 49317 10-Pack 1.46 3000 3 0.96 8640 92 94 1.04
1.38 FO25/XP 2175 4 0.88 7655 86 89 1.02 1.18 2175 3 1.00 6525 72 91 1.39
1.00 FO17/XP 1375 4 0.92 5060 60 84 1.53 0.87 1375 3 1.03 4250 51 83 2.02
1.71 FO40/XP 3750 3 0.91 10,235 112 91 0.81 1.36 3750 2 1.09 8175 86 95 1.27
1 Ballast Efficiency Factor (BEF) = (Ballast Factor x 100) divided by Input Power
Note: For one lamp application, cap blue lead. Insulate to 600 volts.
LAMP
LAMP
LAMP
BALLASTBlueBlueBlueRed
BlackWhite
Note: For two lamp application, cap any blue lead. Insulate to 600 volts.
QUICKTRONIC 3x32
BALLAST
LAMP
BlackWhite
Blue
Red
QUICKTRONIC 1x32
BALLAST
LAMP
LAMP
LAMP
LAMP
BlackWhite
YellowYellow
RedRed
BlueBlue
Note: For three lamp application, cap any unused blue lead. Insulate to 600 volts.
QUICKTRONIC RESIDENTIAL 4x32
QUICKTRONIC 1x40DL
BALLASTBlackWhite
Blue
Red
BALLAST
Note: For one lamp application, cap any blue lead. Insulate to 600 volts.
QUICKTRONIC 2x40DL
BlackWhite
BlueBlue
Red
Note: For one lamp application, cap any unused blue lead. Insulate to 600 volts.
QUICKTRONIC 2x59*QUICKTRONIC 2x96IS
BALLASTBlackWhite
Blue
Blue
Red
LAMP
LAMP
QUICKTRONIC 2x96HO
BlackWhiteYellowYellow
BlueBlueRedRed
BALLAST
LAMP
LAMP
LAMP
LAMP
BlueBlueRed
BALLASTBlackWhite
Note: For one lamp application, cap any blue lead. Insulate to 600 volts.
QUICKTRONIC RESIDENTIAL 2x32
BALLAST
QUICKTRONIC FM (1 LAMP)Note: For QT-FM green ground wire to terminal required.
LAMP
Black
White
Blue
Red
QUICKTRONIC 3x40DL
BALLASTBlackWhite Blue
Blue
BlueRed
Note: For two lamp application, cap any blue lead. Insulate to 600 volts.
QUICKTRONIC FM (2 LAMP)Note: For QT-FM green ground wire to terminal required.
LAMP
LAMP Blue
Yellow
Red
BALLASTGreen BlackGreenWhite
LAMP
LAMP
LAMP
BALLASTBlueBlueBlueRed
BlackWhite
Note: For two lamp application, cap any blue lead. Insulate to 600 volts.
QUICKTRONIC 3x32
BALLAST
LAMP
BlackWhite
Blue
Red
QUICKTRONIC 1x32
BALLAST
LAMP
LAMP
LAMP
LAMP
BlackWhite
YellowYellow
RedRed
BlueBlue
Note: For three lamp application, cap any unused blue lead. Insulate to 600 volts.
QUICKTRONIC RESIDENTIAL 4x32
QUICKTRONIC 1x40DL
BALLASTBlackWhite
Blue
Red
BALLAST
Note: For one lamp application, cap any blue lead. Insulate to 600 volts.
QUICKTRONIC 2x40DL
BlackWhite
BlueBlue
Red
Note: For one lamp application, cap any unused blue lead. Insulate to 600 volts.
QUICKTRONIC 2x59*QUICKTRONIC 2x96IS
BALLASTBlackWhite
Blue
Blue
Red
LAMP
LAMP
QUICKTRONIC 2x96HO
BlackWhiteYellowYellow
BlueBlueRedRed
BALLAST
LAMP
LAMP
LAMP
LAMP
BlueBlueRed
BALLASTBlackWhite
Note: For one lamp application, cap any blue lead. Insulate to 600 volts.
QUICKTRONIC RESIDENTIAL 2x32
BALLAST
QUICKTRONIC FM (1 LAMP)Note: For QT-FM green ground wire to terminal required.
LAMP
Black
White
Blue
Red
QUICKTRONIC 3x40DL
BALLASTBlackWhite Blue
Blue
BlueRed
Note: For two lamp application, cap any blue lead. Insulate to 600 volts.
QUICKTRONIC FM (2 LAMP)Note: For QT-FM green ground wire to terminal required.
LAMP
LAMP Blue
Yellow
Red
BALLASTGreen BlackGreenWhite
Note: For three lamp application, cap blue lead. Insulate to 600 volts.