Installation Instructions Please Read Before Installing Lutron Electronics Co., Inc. 7200 Suter Road, Coopersburg, PA 18036-1299 P/N 032-367 Rev. B 10 / 2011 English Lutron, Quantum, and are registered trademarks of Lutron Electronics Co., Inc. NEC and National Electrical Code are registered trademarks of the National Fire Protection Association, Quincy, Massachusetts. ©2011 Lutron Electronics Co., Inc. Technical Assistance: www.lutron.com/quantum U.S.A. / Canada: 1.800.523.9466 Mexico: +1.888.235.2910 Other Countries: +1.610.282.3800 24 hours / 7 days Light Management Hub (QP3) QP3-1PL-100-240 120-240 V ~ 50 / 60 Hz 1 A Use these instructions to install the model number listed above. 1. Mount Enclosure For indoor use only. NEMA, Type 1 enclosure, IP20. Install in accordance with all national and local electrical codes. Maintain at least 5 inches (127 mm) of spacing between installed panel and other equipment. 2. Control Power Wiring WARNING! Danger of Shock. May result in serious injury or death. DO NOT WIRE WHEN LIVE! Switch off power to all power feeds via circuit breaker or isolator before wiring or servicing the Light Management Hub. Turn power off. Remove metal outer panel cover. Remove internal metal line voltage shield. Use 14 AWG to 12 AWG (2.5 mm( to 4.0 mm() conductors (depending on breaker rating) to feed the control power wiring. The device draws less than 1 A. 3. Configurable Link Wiring Turn power off. Link communication uses IEC PELV / NECR Class 2 wiring. Follow all local and national electrical codes when installing IEC PELV / NECR Class 2 wiring with line voltage wiring. 22 AWG to 12 AWG (0.5 mm( to 4.0 mm() Up to two 18 AWG (1.0 mm() wires Data (terminals 3 and 4 of each Configurable Link) twisted and shielded pair of 22 AWG (0.5 mm() wires. Strip length: 3/8 in (8.5 mm) Torque: 5 in•lb (0.5 N•m) Link length not to exceed 2000 ft (609 m) if using 12 AWG (4.0 mm() wire or 500 ft (152 m) if using 18 AWG (1.0 mm() wire. For more information on wiring the configurable links, please visit www.lutron.com and refer to the QuantumR Light Management Hub (QP3) Specification Submittal (369423). For use with LutronR power panels, install LT-1 link terminator on terminals 3 & 4 4. Inter-Processor Link Wiring Connect Hubs together using Ethernet cable and one of the RJ45 jacks and an external Ethernet switch. DO NOT daisy chain panels together. A “wire segment” is a length of cable connecting two devices communicating over Ethernet. Ethernet wire segment length not to exceed 300 ft (91 m). Hubs cannot be more than 6 “wire segments” from the server. For more information on Inter-processor wiring, please visit www.lutron.com and refer to the QuantumR Light Management Hub (QP3) Specification Submittal (369423). For more information about connecting a QuantumR System to a corporate or building wide network, please visit www.lutron.com and refer to the Ethernet Network by Others Specification Submittal. Replace metal outer panel cover. 6. Troubleshooting Configurable Links Enclosure Dimensions Measurements in inches (millimeters) Terminal Assembly 500-10561 Rev. B H H N N N G G N N N 11.2 (287.0) 0.2 (5.1) dia. 0.9 (22.8) 0.8 (20.3) 9.2 (233.7) 7.5 (190.5) 13.3 (337.8) LED Normal Operation Problem Indicator Probable Cause and Solution Processor Flashing Orange Off or Solid Orange Link error: Run software diagnostics Flashing Green (solid green if no links are present) Solid Red Link power is shorted or overloaded: After fault is cleared, will flash once per second for 5 seconds to indicate link power has been restored Flashing Orange (solid orange if no links are present) Flashing Red Link error: Run software diagnostics Flashing Green Off Check power supply Off Solid Red for 3 Seconds Link error: Run software diagnostics Solid Green Off Check power supply Power Supply Power LED - On Off No power from power supply: Check power feed Ground/Earth Neutral Hot/Live 120-240 V~ H H N N N G G N N N (5) Drain (Shield) (4) (3) MUX (2) 24 V- (1) COM Processor Configuration Class 1 Line voltage wiring entry 5. Activate the System You have completed your QuantumR system installation. For onsite factory startup, call LutronR Technical Support and select Startup to schedule a field service visit. Allow for 10 working days between day of call and scheduled visit. In the U.S., Canada, and the Caribbean: 1.800.523.9466 In Mexico: 888.235.2910 In Europe: +44.207.702.0657 Frequently Asked Questions 1. Can I fit more than one hub on a breaker? Yes. The hub draws 1 A; do not exceed the capacity of the breaker. 2. Can I mount one hub near another? Yes. A Light Management Hub (QP3) many be mounted above, below, or beside another Light Management Hub (QP3). Maintain at least 5 inches (127 mm) of spacing between installed panel and other equipment, and follow NECR guidelines for minimum conduit bend radii. 3. What else can I mount in the hub? No other devices or components may be mounted in the hub. 4. How much heat does the hub generate? The Light Management Hub (QP3) generates 240 BTUs/Hour. 5. What does the knob do on the power supply? The trim knob can be used to adjust the power supply’s output voltage. The hub ships with the output preset to 24 V-, but can be adjusted between 22.5-25 V-. The output voltage can be verified by using a digital multi-meter to measure the voltage between the + and - terminals on the power supply. 6. How do I tell if the links are shorted? The corresponding L1/L2 LED will be lit solid red. Once the short is removed, the link heartbeat LED will return to its normal status (flashing green). 7. How do I tell if the processor is running? Normal operation is indicated by the LEDs on the processor. Refer to Section 6 (Troubleshooting) of this install guide for normal LED operation. QuantumR S e l e c t

Upload: others

Post on 01-Jun-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Quantum Light Management Hub (QP3) Enclosure …500-10561 Re v. B L1 5 4 3 2 1 CO M MU V+ X D 5 4 3 2 1 CO M V+ H H N N N G G MU X L2 10/100 1 2 COM of call and scheduled visit. P

Installation InstructionsPlease Read Before Installing

Lutron Elec tron ics Co., Inc. 7200 Suter Road, Coopersburg, PA 18036-1299P/N 032-367 Rev. B 10 / 2011

English

Lutron, Quantum, and are registered trademarks of Lutron Electronics Co., Inc. NEC and National Electrical Code are registered trademarks of the National Fire Protection Association, Quincy, Massachusetts. ©2011 Lutron Electronics Co., Inc.

Technical Assistance: www.lutron.com/quantum U.S.A. / Canada: 1.800.523.9466 Mexico: +1.888.235.2910 Other Countries: +1.610.282.3800 24 hours / 7 days

Light Management Hub (QP3)QP3-1PL-100-240120-240 V~ 50 / 60 Hz 1 A

Use these instructions to install the model number listed above.

1. Mount Enclosure

• Forindooruseonly.• NEMA,Type1enclosure,IP20.• Installinaccordancewithallnationalandlocalelectricalcodes.• Maintainatleast5inches(127mm)ofspacingbetweeninstalled

panel and other equipment.

2. Control Power Wiring

WARNING! Danger of Shock. May result in serious injury ordeath.DONOTWIREWHENLIVE!Switchoffpowertoall power feeds via circuit breaker or isolator before wiring or servicing the Light Management Hub.

• Turnpoweroff.• Removemetalouterpanelcover.• Removeinternalmetallinevoltageshield.• Use14AWGto12AWG(2.5mm( to 4.0 mm()conductors

(dependingonbreakerrating)tofeedthecontrolpowerwiring.Thedevicedrawslessthan1A.

3. Configurable Link Wiring

• Turnpoweroff.• LinkcommunicationusesIECPELV/NECR Class 2 wiring. Follow

all local and national electrical codes when installing IEC PELV / NECR Class 2 wiring with line voltage wiring.

• 22AWGto12AWG(0.5mm( to 4.0 mm()• Uptotwo18AWG(1.0mm()wires• Data(terminals3and4ofeachConfigurableLink)twistedand

shieldedpairof22AWG(0.5mm()wires.• Striplength:3/8in(8.5mm)• Torque:5in•lb(0.5N•m)• Linklengthnottoexceed2000ft(609m)ifusing12AWG

(4.0mm()wireor500ft(152m)ifusing18AWG(1.0mm()wire.• For more information on wiring the configurable links, please visit

www.lutron.com and refer to the QuantumR Light Management Hub (QP3)SpecificationSubmittal(369423).

• ForusewithLutronRpowerpanels,installLT-1linkterminatoronterminals 3 & 4

4. Inter-Processor Link Wiring

• ConnectHubstogetherusingEthernetcableandoneoftheRJ45jacksandanexternalEthernetswitch.DONOTdaisychainpanelstogether.

• A“wiresegment”isalengthofcableconnectingtwodevicescommunicating over Ethernet.

• Ethernetwiresegmentlengthnottoexceed300ft(91m).• Hubscannotbemorethan6“wiresegments”fromtheserver.• FormoreinformationonInter-processorwiring,pleasevisit

www.lutron.com and refer to the QuantumR Light Management Hub (QP3)SpecificationSubmittal(369423).

• FormoreinformationaboutconnectingaQuantumR System to a corporate or building wide network, please visit www.lutron.com and refer to the Ethernet Network by Others Specification Submittal.

• Replacemetalouterpanelcover.

6. TroubleshootingConfigurable LinksEnclosure Di men sionsMeasurements in inches (millimeters)

Terminal Assembly 500-

1056

1 Re

v. B

L1

5 4 3 2 1

COM

V+MUX

MUX

D

5 4 3 2 1

COM

V+MUX

H H N N N G G

MUX

D

L2

10/100 1 2

COM

P

3 4 5

L1

10/100

PWR24 V 500 mA

L2

24 V 2 A

N N N

11.2 (287.0)

0.2 (5.1) dia.

0.9 (22.8)

0.8 (20.3)

9.2 (233.7)

7.5 (190.5)

13.3 (337.8)

LED Normal Operation

Problem Indicator

Probable Cause and Solution

Processor

Flashing Orange Off or Solid Orange

Link error: Run software diagnostics

Flashing Green (solid green if no links are present)

Solid Red Link power is shorted or overloaded: After fault is cleared, will flash once per second for 5 seconds to indicate link power has been restored

Flashing Orange (solid orange if no links are present)

Flashing Red

Link error: Run software diagnostics

Flashing Green Off Check power supply

Off Solid Red for 3 Seconds

Link error: Run software diagnostics

Solid Green Off Check power supply

Power Supply

Power LED-

On Off No power from power supply: Check power feed

Ground/EarthNeutral

Hot/Live120-240 V~

500-

1056

1 Re

v. B

L1

5 4 3 2 1

COM

V+MUX

MUX

D

5 4 3 2 1

COM

V+MUX

H H N N N G G

MUX

D

L2

10/100 1 2

COM

P

3 4 5

L1

10/100

PWR24 V 500 mA

L2

24 V 2 A

N N N

500-

1056

1 Re

v. B

L1

5 4 3 2 1

COM

V+MUX

MUX

D

5 4 3 2 1

COM

V+MUX

H H N N N G G

MUX

D

L2

10/100 1 2

COM

P

3 4 5

L1

10/100

PWR24 V 500 mA

L2

24 V 2 A

N N N

(5) Drain (Shield)

(4)

(3) MUX

(2) 24 V-

(1) COM

Processor Configuration

Class 1Line voltage wiring entry

5. Activate the System You have completed your QuantumR system installation. For onsite

factory startup, call LutronRTechnicalSupportandselectStartuptoschedule a field service visit. Allow for 10 working days between day of call and scheduled visit.

In the U.S., Canada, and the Caribbean: 1.800.523.9466 In Mexico: 888.235.2910 In Europe: +44.207.702.0657

Frequently Asked Questions

1. Can I fit more than one hub on a breaker? Yes. The hub draws 1 A; do not exceed the capacity of the

breaker.2. Can I mount one hub near another? Yes. A Light Management Hub (QP3) many be mounted above,

below, or beside another Light Management Hub (QP3). Maintain at least 5 inches (127 mm) of spacing between installed panel and other equipment, and follow NECR guidelines for minimum conduit bend radii.

3. WhatelsecanImountinthehub? No other devices or components may be mounted in the hub.4. How much heat does the hub generate? The Light Management Hub (QP3) generates 240 BTUs/Hour.5. Whatdoestheknobdoonthepowersupply? The trim knob can be used to adjust the power supply’s output

voltage. The hub ships with the output preset to 24 V-, but can be adjusted between 22.5-25 V-. The output voltage can be verified by using a digital multi-meter to measure the voltage between the + and - terminals on the power supply.

6. How do I tell if the links are shorted? The corresponding L1/L2 LED will be lit solid red. Once

the short is removed, the link heartbeat LED will return to its normal status (flashing green).

7. How do I tell if the processor is running? Normal operation is indicated by the LEDs on the processor. Refer

to Section 6 (Troubleshooting) of this install guide for normal LED operation.