The PV Skid is available in configurations up to 2.2 MW and
incorporates the latest offering from Schneider Electric,
the Conext Core XC-NA inverters, along with a medium-
voltage transformer, NEC 2011 compliant DC recombiners,
and auxiliary switchboard for local loads and field tracker
motors (optional) — all prewired and factory tested on a
single skid. The integrated solution also offers an optional
remote control operation using the Schneider Electric
SCADA system, Conext ControlTM.
PV SkidOptimized solar power conversion system tailored to enhance any North American PV power plant.
Product at a glance
True bankability
• Warranty from a trusted partner with 180 years of experience
• World leader in industrial power drives, UPS, and electrical distribution
• Strong service infrastructure worldwide to support your global needs
Higher return on investment
• Factory integration reducing on-site labour
• Reduced costs of transportation, offloading, and site preparation
• Reliable design reducing frequency and cost of site interventions
Designed for reliability
• Designed to sustain harsh environmental conditions (low temperatures, desert, salty environment)
• Industrialized solution to cater to customer’s needs
• 20+ years lifetime
Flexible
• Configurations ranging from 1 MW to 2.2 MW AC for PV power plants
• Extended temperature range from -35 to +55 °C
• Salt corrosion resistance and high seismicity withstand options
• Optional load center for tracker systems
• NEC 2011 compliant DC recombiner disconnects
Easy to service
• Provision of maintenance corridor on the skid for easy access to inverters during periodic servicing
• Optional sun and rain canopy
• Optional integration of Conext Control for remote plant monitoring and control to minimize downtime*
Easy to install
• Solution delivered pre-assembled, configured and tested to reduce on-site labour and expedite project completion
• Mono-block basement design for faster installation; ability to pad or pier mount
Product applications
PV power plants centralized
*Also compatible with other SCADA systems in the market.
solar.schneider-electric.com | 2PV Skid // Optimized solar power conversion system tailored to enhance any North American PV power plant.
DS20160822 © 2016 Schneider Electric. All Rights Reserved. Schneider Electric | Life Is On is a trademark and the property of Schneider Electric SE, its subsidiaries, and affiliated companies. • 998-19794716_CA-US
Schneider Electric Industries SASHead Office35 rue Joseph Monier92500 Rueil Malmaison Cedex- FranceTel.: +33 (0)1 41 29 70 00www.schneider-electric.com
Device short name PV Skid 540 kVA PV Skid 630 kVA PV Skid 680 kVA PV Skid 1080 kVA PV Skid 1260 kVA PV Skid 1360 kVA
Electrical specifications
Nominal PV box power at PF=1 1×540 kW 1×630 kW 1×680 kW 2×540 kW 2×630 kW 2×680 kW
Max. DC voltage, open circuit 1000 V
Max. DC current 1×1280 A 2×1280 A
Max short circuit DC current in STC conditions
1x1600 A 2x1600 A
Max. short circuit DC current 1×2000 A 2×2000 A
Number of protected DC inputs up to 10 inputs per inverter up to 10 inputs per inverter
Output ratings (AC)
Nominal AC power 540 kVA 630 kVA 680 kVA 1080 kVA 1260 kVA 1360 kVA
Nominal MV voltage Up to 34.5 kV
Grid frequency 60 Hz
Power factor range (cosφ) 0 to 1 (leading or lagging)
Nominal output voltage 300 V 350 V 380 V 300 V 350 V 380 V
Auxiliary power connection
Voltage 208 Y/120 V or (208 Y/120 V + 480 Y/277 V) for tracker application
Frequency 60 Hz
Auxiliary power transformer (optional) 15 kVA or 10 kVA + 45 kVA tracker
Dimensions and weight
Nominal dimensions (transportation) (L/W/H) 126"/270"/120" 126"/324"/120"
Weight < 44000 lbs < 65000 lbs
Device short name PV Skid 1466 kVA PV Skid 1620 kVA PV Skid 1890 kVA PV Skid 2040 kVA PV Skid 2200 kVA
Input ratings (DC)
Nominal PV box power at PF=1 2×733 kW 3×540 kW 3×630 kW 3×680 kW 3×733 kW
Max. DC voltage, open circuit 1000 V
Max. DC current 2×1280 A 3×1280 A
Max short circuit DC current in STC conditions
2x1600 A 3x1600 A
Max. short circuit DC current 2×2000 A 3×2000 A
Number of protected DC inputs 2x up to 10 inputs per inverter 3x up to 10 inputs per inverter
Output ratings (AC)
Nominal AC power 1466 kVA 1620 kVA 1890 kVA 2040 kVA 2200 kVA
Nominal MV voltage Up to 34.5 kV
Grid frequency 60 Hz
Power factor range (cosφ) 0 to 1 (leading or lagging)
Nominal output voltage 407 V 300 V 350 V 380 V 407 V
Auxiliary power connection
Voltage 208 Y/120 V or (208 Y/120 V + 480 Y/277 V) for tracker application
Frequency 60 Hz
Auxiliary power transformer (optional) 15 kVA or 10 kVA + 45 kVA tracker
Dimensions and weight
Nominal dimensions (transportation) (L/W/H) 2 inverters 126"/324"/120" 3 inverters 126"/428"/120"
Weight < 65000 lbs < 70000 lbs