pump head calculation (2)

Upload: mfaiz-rhamira

Post on 14-Jan-2016

36 views

Category:

Documents


2 download

DESCRIPTION

Pump Head Detail Calculation

TRANSCRIPT

Sheet1Pump Head CalculationProject:DIC R & DSystem:Condenser water systemDesign By:VasudevanCheck By:Job No:Pipe Dia (mm)Pipe length (ft)Bends/ ValvesTotal Equiv Length (ft)Friction Loss/100ft (ft/s)Total Static Head (ft)flow rateNo. of FittingsLoss in Ft.Equivalent length (ft)supply pipe3609681612818823.7625036316489821.961.55018410409021.80.7510627.5152541Return pipe6"150590816128278513.96"1503403164819823.964"701254104011044.43"408527.5155542.2Valve6" gate valve37212151.056" strainer111011011055.56" flexible27141450.76" check valve1606060533" gate valve23.26.46.440.2563" strainer142424241.683" flexible23.26.46.440.2563" bal. valve184848443.36Sub Total48.782Allowance10%4.878253.6602Chiller Pressure Loss (ft)Air Handling Pressure Loss (ft)14Cooling Tower Static Head (ft)15Production Machine Pressure Loss (ft)Plate Heat Exchanger Pressure Loss (ft)Total Head82.6602

Sheet2

Sheet3