  • PLUSPTS400.3 ,class0.02Modularthree-phasePortableTestSystem

  • -2--2-

    PTS 400.3 PLUS Three-phase, fully automatictest system with class 0.02 reference stan-dard and integrated three-phase current andvoltage source available in two versions.

    Two modules allowing combinations formany applications

    Formany years, electricity utility companies haverealized the importance of performing measure-ments and tests, on-site, at the metering installa-tion. MTE continually supplies and develops newand improved products that reduces and simpli-fies the on-site efforts. The test systemPTS400.3PLUS with enhanced functionality and high mea-surement accuracy does not only determine theaccuracy of meters, but also provides additionalinformation relating to the conditions at therespectivemains points.

    ThePTS400.3 PLUS system consists of the refe-rence standard PRS 600.3 of class 0.02 and thepower sourcemodule PPS400.3, which is availa-ble in two versions of up to 12Aor 120A.

    The reference standard PRS 600.3 may be sim-ply and quickly connected with the power sourcemodule PPS 400.3 thereby producing a portabletest system with 1 up to 3 positions. Operation ofthe system may begin immediately after connec-ting bothmodules.

    In this combination, the reference standard con-trols the source via blue-tooth.

    Due to the extended power quality analyzerfunctions of the reference standard PRS 600.3,the test system can also be used to resolvedisputes at contractual applications, for statis-tical surveys, including EN 50160 reporting, andfor online troubleshooting of different kind ofpowerqualityproblems.

    The power source module, if used without thePRS 600.3, can be controlled via the serialinterface RS 232 C. It is therefore possible toeasily apply the source module unchanged in astationarytestsystem.

    The operator can not only perform single teststeps but also can easily predefine and store auto-matic test runs using the sequence function andadvanced database functions of the system.

    The overall functionality is comparable tomodernstationarymeter test systems.

    In case the touch operation is not possible (e.g. ifgloves must be worn for safety reasons at on-sitetests), the system can also be operated with theintegrated pen on the right side of the housing.

    The two displays with identical graphical userinterface can be used to control the referencestandard and the power source each with a sepa-rate display or they can be used to show differentfunctions of the sameunit on two displays.

    The same functionality is available on both sides,left and right, freely selectable by the user.

    Operation of the system

    The PRS 600.3 is the operation interface for thetwo system modules of the Portable Test SystemPTS 400.3 PLUS and allows direct operation ofthe reference standard and / or one of the availa-ble portable power source modules PPS 400.3-12AorPPS400.3-120A.

    The operation concept is based on touch screenoperation with self-explaining functional softwarebuttons.

    Modules

    Further the system can alternatively also be com-fortably operatedwith a keyboard or amouse con-nected to the USB type A connector of thePRS600.3. This is especially useful, if the systemis operated in the laboratory.

  • Modules

    PRS 600.3 Portable peference standard

    The reference standard of the modular system isbased on the well-known digital measurementvalue retrieval, fast analogue-digital conversionand calculation of the values using fast signal pro-cessors. As opposed to the past, reference stan-dards are not only used as standards for metertesting in a stationary meter test installation, butpredominantly in the field for the measurement ofallmain parameters.

    In order to meet these requirements, the PRS600.3 offers the followingmain functions:

    Simultaneous testing of up to three meters orregisters of amulti-functionalmeter

    Internal memory for measurement results andcustomer data

    Vector diagram, harmonics spectrum, waveform and rotary field display for analysis of themains conditions

    Active, reactive and apparent energy measur-ement in three-wire or four-wire circuits withintegrated error measurement and pulse out-put for energy

    Voltagemeasurement

    Current measurement, direct and with currenttransformer clamps up to 3000Aor sensors forvoltage and currentmeasurements on high vol-tage potential

    Active, reactive and apparent powermeasure-ment per phase and sumof all phases

    Phase angle, power factor and frequencymea-surement

    Burden measurement and ratio test of PTsandCTs

    Power quality recording and analysis regar-ding standard IEC61000-4-30

    PPS 400.3 Portable power source module

    The PPS 400.3 portable power source modulemay be used as enhancement of the referencestandard PRS 600.3 as well as independently.Following the different demands of the custo-mers, this source is available in two versions, forthe supply of transformermeters with amaximumcurrent up to 12Aas well as a wider range sourceup to 120 A.The source is designed to generateany network independent of its supply voltage,e.g. 3-phase 4-wire Y or , 3-phase 3-wire, 1-phase 2-wire or others. Generation of harmonicsin both voltage and current circuits aswell as ripp-le control signals are available.

    The power source module may be connected tothe reference meter with little effort. The controlsoftware automatically recognises the module. Itmay therefore immediately be put into operation,and automatic measurement of a load curve ofthemetermay begin.

    Controlling the source is carried out in a similarway as to control the reference meter, by use ofone of the PRS 600.3 touch displays or via RS232C.

    ThePPS400.3 source is developed such as to befully operational without the referencemeter.

    -3--3-

  • -4--4-

    Combinationsforvariousapplications

    PTS400.3PLUS-12 A Three-phaseportabletestsystem

    ReferencestandardmodulePRS600.3,accuracyclass0.02

    Currentandvoltagemeasurementupto120 A and520V

    Currentandvoltagegenerationupto12 A and300V

    Vectordiagram,harmonicspectrum,waveformandrotaryfielddisplay,PQmeasurementfunctions

    BurdenmeasurementandratiotestofPTsandCTs

    Dimensions: W510xH195xD480mm

    Weight: approx.26kg

    PRS600.3Three-phasepo

  • -5--5-

    Combinationsforvariousapplications

    PTS400.3PLUS-120 A Three-phaseportabletestsystem

    ReferencestandardmodulePRS600.3accuracyclass0.02

    Currentandvoltagemeasurementupto120 A and520V

    Currentandvoltagegenerationupto120 A and300V

    Vectordiagram,harmonicspectrum,waveformandrotaryfielddisplay,PQmeasurementfunctions

    BurdenmeasurementandratiotestofPTsandCTs

    Dimensions: W510xH195xD480mm

    Weight: approx.29kg

    rtablereferencestandard

  • -6--6-

    Communicationandoperation

    The portable reference standard PRS 600.3 canbe operated on a stand-alone basis or togetherwith the portable power source PPS 400.3module, which is in this application controlled viablue-tooth.

    The innovative technology allows easy and com-fortable measurements and tests on site even indifficult accessible situations.

    The reference standard and the portable powersource can be arranged separately in differentways for optimal connections to the installation.

    ThePPS400.3module is operated and controlledfromdistance in such a configuration.

    Communicationbetweenthemodules

    Features and functions

    Automatic test procedures (if PPS 400.3-12AorPPS400.3-120Aare used)

    Database formeter types, test procedures andcustomers that can be preprogrammed in theinstrument and allocated when carrying outmeter tests

  • -7--7-

    Typesofmetertestracksandquickconnectiondevices

    Metertestrackwith quickconnection

    deviceQCD3I

    Metertestrackwith universalsocketadapterQCDFormS

    Metertestrackfor3measurementpositionswithquickconnectiondevicesEMP 1.3

    Metertestrackwithstandardsuspension

  • -8--8-

    StationarysinglepositiontestsystemPTS400.3PLUS-1

    The stationary system type PTS 400.3 PLUS-1 allows the automatic testing of a singlemeter, without theneed of an additional personal computer and has the following characteristics:

    Test systemPTS400.3 PLUS-1 consists of the three-phase reference standard PRS600.3, the three-phase voltage and current sourcePPS400.3 plus a single positionmeter suspension rack

    The suspension rack provides a fast and easymounting of themeter

    Scanning head support SCD2003with scanning head SH2003 for scanning themarks ofmechanicalrotating discmeters or the detection of light emitting diodes (LED's) of electronicmeters

    The PTS 400.3 PLUS

    which allow fast suspen-

    sion and connection of meters

    is supplied with integrated software, allowing automatic measuring runs with(programmable) predefined load points to be carried out

    Optional quick connection devices according to IEC-, BS- orANSI standard,

  • -9--9-

    StationarysinglepositiontestsystemPTS400.3PLUS-2

    Modular evaluation systemSMM400 formeter error display, inputs for the testing of output contacts orpulses plus a serial interface formeter communications and programming

    Software packageCALegration provides aPCcontrolled fully automaticmeasuring test system

    Optional quick connection devices according to IEC-, BS- orANSI standard,

    which allow fast suspen-

    sion and connection of meters

    The stationary system type PTS 400.3 PLUS-2 allows the testing of a a simple meter, a high presicionmultifunctionmeter or a smartmeter fully automatic and has the following characteristics:

    Test systemPTS400.3 PLUS-2 consists of the three-phase reference standard PRS600.3, the three-phase voltage and current sourcePPS400.3, plus a single positionmeter suspension rack

    Scanning head support SHC x.x with scanning head SH 2003 or SH 11 for scanning the marks ofmechanical rotating disc meters or the detection of light emitting diodes (LED's) of electronic meters.The scanning head is adjustable in all 3 axis (left to right, up and down, in and out) as required to alignwith all normal configurations ofmeters

  • -10--10-

    Covering all requirements of the modernmeter testing environment, CALegration pro-vides the flexibility to easily incorporatefuture meter testing requirements as well.

    Tests can be carried out for simple or highlycomplex (smart) meters in accordance withcustomer requirements and national / interna-tional test and calibration regulations (e.g.PTB, IEC, BS,ANSI).

    Reduced complexity

    User-friendly operations

    SQL based database

    Full database interchange

    Flexible access fast stor-age and interchange

    Fully-automatic test sequences

    Manual control module

    power quality testing

    statistics and schematic diagrams

    Modular system

    various hardware com-binations

    Data export

    several lan-guages color profiles

    KeyadvantagesofCALegration

    due to an all-in-onesoftware for the entireMTEproduct portfolio

    and clearlyarranged user interface making the systemeasy understandable, also to operators withlimited computer knowledge

    with stable access,organized backups, extended database sizeand server installation support

    between portabledevices and CALegration with control of por-table functions by external PC

    to database andof new testing data pack-

    ages

    for metertestingwith clearly laid out database structure

    for testing variousindividual functions such asmeter test, record-ing of load values, detection of installationerrors andmanymore

    Prepared for and anal-ysis functions according to IEC 62586 and IEC61000-4-30 for specificMTEdevices

    Transparent evaluation and presentation ofresults,of all relevant values in an individual createdprotocol

    allows the integration of cus-tomer specified applications

    Suitable for use with

    in standard format (e.g. MSExcel)

    Operator interface available inand in different

    The philosophy of CALegration is to inte-grate all basic test elements (administration,database, operation, results) into one singlesoftware and to use it with both MTEs porta-ble and stationary test devices.

    WhiletestingwithCALegration ,theresultsarestoredinacentralizedSQL baseddata-basegivingtheusertheflexibilitytoaccessthedatawherevertheyaretesting:On-site(portabletestequipment),inthelaboratoryorinthemeterproductionplant(stationaryequipment).

    Moreover, CALegration provides the userwith its database a complete history and over-view of all tested meters, giving the opportu-nity to track the meters respectively their testresults over its full life cycle.

    SoftwarepackageCALegration

    CALegration is an all-in-one software pack-age designed to operate MTEs portable andstationary test equipment product lines withthe same software and on a common data-base. It bundles the functionalities and ad-vantages in a new and comprehensive soft-ware solution.

  • -11--11-

    CALegration combines the various functionalmodules required inmodern stationary and porta-ble test devices, with a common and consistentuser interface.

    The modular system allows the control of varioushardware units with a common software platform.Functions for laboratory or on-site measurementare provided together with the ability to test highlycomplexmodernmeters (smart meters) with inte-gral tariff devices.

    For any test equipment, test sequence or metertype, CALegration is structured along the follow-ing basic test elements:

    By setting up newsuch as e.g. contact details of energy customers,also client information can be added to the meterstock. can be definedand called out for testing on-site installations.With CALegration various canbe defined. A test procedure or test sequencedescribes the order and content of different

    in a whole procedure. For eachtest step the desired Source Settings (current,voltage, phase angle, frequency etc.), TestSettings (e.g. error measurement) and ControlFunctions (e.g. automatic meter readout) can bespecified.

    Administrative Data (ADS)

    Instrument Transformers

    Test Procedures

    TestPoint Elements

    SoftwarepackageCALegration

    After defining the settings andbasic parameters, the actualtesting can be executed.

    Themodule allows

    a simple quick check of theinstallation on-site (e.g.Manual Meter Test, ManualCT / PT Burden and RatioMeasurements , ManualSource Control) without the

    necessity to integrate these test procedures intoa full test sequence.

    Forinstance,CALegration showstheuseratCT BurdenMeasurementaschematicdiagramandallrelevantsettingsandresultsreadoutfromtheportabletestdevice.

    Manual Control /Measurement

    OperationAdministration

    With thethe user interface can

    be adapted individually to thespecific customer require-ments, access levels andrights of particular user. Onthe basis of User Profiles the

    Software Configu-ration

    interface of the software can be customized (Soft-wareProfile, Color Profile) and task-oriented userrights and access levels (Tester, Supervisor, Ser-vice) can be assigned to a user.

    In the the user himselfcan adapt CALegration to the actual test system.The test system devices (e.g. reference meter,power source, error evaluation system,handheld) are configured here and can be com-bined and saved as various system configura-tions (e.g. portable reference meters up to com-plex full automatic test systems). A demo systemconfiguration is also included for training pur-poses.

    System Configuration

    The anddefinition function is used todefine and administrate anykind ofmeters. Themeter typedefinition contains the electri-cal and functional definitionsof meters under test (connec-tion values, meter constantsregisters etc.). The type defi-nitions can further be calledup and allocated to the meterstock / inventory of the cus-tomer (meter name, manufac-turer number etc.).

    Meter Meter Type

    Database

  • -12--12-

    Optional software modules

    Customer specified adaptations

    Tariff device communication / dlms

    Referencemeter testing

    Tariff device testingwith pulse transmitter

    Error compensation

    Sample testmodules

    Archiving databases

    Generation of ripple control signals

    Generation of special test signals and waveshapes according to IEC 62052-11 andIEC62053-11/-21/-22

    Generation of harmonics

    MTE provides customer specifiedmodules whichcan be integrated into the standard software forfully automatic calibration of modern (smart)meters. MTE also supports the integration ofalternative communication protocols for tariffdevices.

    SoftwarepackageCALegration

    With the CALegrationallows the user to readout measurement resultsstored in portable test devices or to preload data-base elements (Administrative Data, Meters,Instrument Transformers, Test Procedures, TestPoint Elements) into the test devices.

    By undertaking an the user allo-cates to each active measurement position ameter type and selects a test procedure. Subse-quently the user will comfortably be guidedthrough the test. It is possible to display simulta-neously the actual test values, wave forms andresults in their own windows using large, goodvisible and configurable fonts.

    Device Communication

    Automatic Test

    After executing an AutomaticTest or aManual Control /Mea-surement all saved results arecentralized on the SQL data-

    base and available for further data processing,such as creating an individual detailed test reportor export to MS Excel tables. This is particularlyuseful for new meter evaluation, long runningproblemmeter analysis and duplicating field con-ditions.

    The CALegration enables theuser to create and define their own protocolmasks (calibration certificates, pass / fail reports,statistical reports, customer reports etc). With itsflexibility to add on logos, diagrams and text fields(e.g. for signatures), the Report Designer meetsindividual and different requirements. Further-more, on the basis of theSQLdatabase, full resulthistories and protocols of meter types or particu-larmeters can be generated and stored.

    Report Designer

    Results

  • -13--13--13-

    Extendedfunctionalities

    Clamp-on current transformers to the por-table test system PTS 400.3 PLUS

    The PTS 400.3 PLUS allows to use severalclamp-onCTs in the range of 100Aup to 3000Aorsensors for voltage and current measurementson high voltage potential.

    The clamp-on CTs and high voltage sensors areclamped around conductors to perform non-contact / intrusive measurements without inter-rupting the circuit under test.

    Error compensated clamp-on CTs for measurementsin the range 0.1 A ... 100 Awith a maximum error of0.2%.

    Flexible current transfor-mers FLEX 3000 for cur-rent up to 30 / 300 / 3000A.

    Clamp-on CTs for meas-urements in the range of 1Aup to 1000A.

    Testing of CTs, PTs in operating state

    The portable test system PTS 400.3 PLUS features wide-ranging alternatives for the testing ofinstrument transformers during normal measuring equipment operations, i.e. without any shutdowns orsafety disconnections.

    AmpLiteWire andVoltLiteWire sen-sors for voltageand current mea-surements onhigh voltage pot-ential up to 40 KVand currents up to2000A.

    Secondarymeasurement

    parallel

    Primarymeasurement

    Voltage